Report .. . _ , .. . _
, OFFICE COPYi',20, 001(3
-75- e bad-ewe/xi 4
RECEIVED
tqco ;r' ; Worldwide www.tyco-fire.com
SEA - �? Contacts
CITY OF TIGARD
BUILDING DIVISION
Series TY-FRB - 2.8, 4.2, 5.6, and 8.0 K-Factor
Upright, Pendent, and Recessed Pendent Sprinklers
Quick Response, Standard Coverage
General to corrosive atmospheres. Although
corrosion-resistant coated sprinklers w `..
IM
Description have passed the standard corrosion
p tests of the applicable approval agen- g '•
The TYCO Series TY-FRB 2.8,4.2,5.6,
cies, the testing is not representative
and 8.0 K-factor Upright, Pendent, of all possible corrosive atmospheres. i,l
Consequently, it is recommended that } i
and Recessed Pendent Sprinklers t.. t
the end user be consulted with respect
described in herein are quick response, to the suitability of these coatings for
standard coverage, decorative 3 mm
glass bulb-type spray sprinklers.They any given corrosive environment. The �:;
effects of ambient temperature, con-
are designed for use in light or ordinary centration of chemicals, and gas/
hazard,commercial occupancies such chemical velocity, should be consid-
as banks, hotels,and shopping malls. ered,as a minimum,along with the cor
The TY-FRB Recessed Pendent Sprin- rosive nature of the chemical to which
kler, where applicable, is intended for the sprinklers will be exposed.
use in areas with a finished ceiling.This
recessed pendent sprinkler uses one of An intermediate level version of the ,
If
the following Recessed Escutcheons: sSedetai detailed inries Technical Pendent Sprinklers
Sheet 4 r �t�l, ;
• A two-piece Style 10 (1/2 in. NPT) TFP356.Sprinkler Guards are detailed +
or Style 40 (3/4 in. NPT) Recessed in Technical Data Sheet TFP780.
Escutcheon with 1/2 in. (12,7 mm)of ,...44/1
recessed adjustment or up to 3/4 in. NOTICE
(19,1 mm) of total adjustment from
the flush pendent position. The Series TY-FRB 2.8, 4.2, 5.6,
and 8.0 K-factor Upright, Pendent, Sprinkler
• A two-piece Style 20 (1/2 in. NPT) and Recessed Pendent Sprinklers
or Style 30 (3/4 in. NPT) Recessed described herein must be installed Identification
Escutcheon with 1/4 in. (6,4 mm)of and maintained in compliance with
recessed adjustment or up to 1/2 in. this document and with the applicable Number (SIN)
(12,7 mm) of total adjustment from standards of the National Fire Protec-
the flush pendent position. tion Association(NFPA), in addition to TY1131 . . .Upright 2.8K,1/2 in. NPT
The adjustment provided by the the standards of any authorities having TY1231 . . Pendent 2.8K, 1/2 in.NPT
Recessed Escutcheon reduces the jurisdiction. Failure to do so may impair TY2131 . . .Upright 4.2K, 1/2 in.NPT
accuracy to which the fixed pipe drops the performance of these devices. TY2231 . . Pendent 4.2K, 1/2 in.NPT
to the sprinklers must be cut. The owner is responsible for maintain- TY3131 . . . Upright 5.6K,1/2 in.NPT
Corrosion-resistant coatings, where ing their fire protection system and TY3231 .. Pendent 5.6K,1/2 in.NPT
applicable, are utilized to extend the devices in proper operating condition. TY4131 .. .Upright 8.0K,3/4 in.NPT
life of copper alloy sprinklers beyond The installing contractor or sprinkler TY4231 . . Pendent 8.0K,3/4 in. NPT
what would be obtained when exposed manufacturer should be contacted with
any questions. TY4831 . . .Upright 8.0K,1/2 in.NPT
IMPORTANT
NFPA 13 prohibits installation of 1/2 in. TY4931 . . Pendent 8.0K, 1/2 in.NPT
Refer to Technical Data Sheet NPT sprinklers with K-factors greater Technical
TFP2300 for warnings pertaining to than 5.6 in new construction. They are
regulatory and health information. intended for retrofit in existing sprinkler Data
systems only.
Always refer to Technical Data
Sheet TFP700 for the "INSTALLER Approvals UL andovals
C-UL Listed
WARNING"that provides cautions FM,LPCB,and NYC Approved
with respect to handling and instal-
lation of sprinkler systems and com See Tables A, B, C and D for complete
onents. Improper and approval information including corrosion-
phandling resistant status.
installation can permanently damage
a sprinkler system or its compo- Maximum Working Pressure
nents and cause the sprinkler to fail See Table E
to operate in a fire situation or cause
it to operate prematurely.
Page 1 of 12 DECEMBER 2020 TFP171
TFP171
Page 2 of 12
*Temperature rating ** Pipe thread connections per 1 - Frame 3 - Sealing 5 - Compression
is indicated on ISO 7-1 can be provided on ESCUTCHEON 2 - Button Assembly Screw
Deflector. special request. PLATE SEATING 4 - Bulb 6 - Deflector*
SURFACE 7 - Bushing
rrl-r�T'PT�-T-.'T-'Ifin — P 7
/
7/16" ,, jliT 1
1
mil
0111
NOMINAL 2-1/4" ���L I A I
MAKE-IN ��� I 2
t�r 2 3/16" (57,2 mm)
1 (55,6 mm) 1 /10 1-9/16"
! . (39,7 mm) . 5
\ Ire
1/2" NPT** f WRENCH STYLE 10 or 20 2-7/8"(73,0 mm)DIA.
FLATS RECESSED
UPRIGHT PENDENT ESCUTCHEON RECESSED PENDENT CROSS SECTION
FIGURE 1
QUICK RESPONSE SERIES TY-FRB UPRIGHT(TY1131)AND PENDENT(TY1231)SPRINKLERS
2.8 K-FACTOR, 1/2 IN. NPT
*Temperature rating ** Pipe thread connections per 1 - Frame 3 - Sealing 5 - Compression
is indicated on ISO 7-1 can be provided on ESCUTCHEON 2 - Button Assembly Screw
Deflector. special request. PLATE SEATING 4 - Bulb 6 - Deflector*
SURFACE
1
7/16" �,,= 3
(11,1 mm) '� t■'`��.
NOMINAL 2-3/16" ��`� 2
01
MAKE-IN (556 mm)
2-3/16" 0 1-1/2" 4
(556 mm) 1 ,(38,1 mm)
�-----5
....._ 11#1
6*
1/2"NPT** t WRENCH STYLE 10 or 20 2-7/8 (73,0 mm)DIA.
FLATS RECESSED
UPRIGHT PENDENT ESCUTCHEON RECESSED PENDENT CROSS SECTION
FIGURE 2
QUICK RESPONSE SERIES TY-FRB UPRIGHT(TY2131)AND PENDENT(TY2231)SPRINKLERS
4.2 K-FACTOR, 1/2 IN. NPT
Discharge Coefficient Poly-Stainless Design
K=2.8 GPM/psis(40,3 LPM/bares) Physical Characteristics
K=4.2 GPM/psis(60,5 LPM/bars) Frame Bronze
K=5.6 GPM/psis(80,6 LPM/bares) Button L316 Stainless Steel* Criteria
K=8.0 GPM/psii(115,2 LPM/bars) Bulb Glass
Compression Screw L316 Stainless Steel* The TYCO Series TY-FRB 2.8,4.2,5.6,
Temperature Rating Deflector Copper/Bronze and 8.0 K-factor Upright, Pendent,
See Tables A and B Sealing Assembly.Gold Plated Beryllium Nickel and Recessed Pendent Sprinklers are
w/TEFLON
Finishes *Type L316 stainless steel(UNS 31603)per ASTM intended for fire protection systems
Sprinkler:See Table D A479/479M or BS EN 1008 WN1.4404. designed in accordance with the stan-
dard installation rules recognized by
Recessed Escutcheon:Signal or Pure White, Operation the applicable Listing or Approval
Grey Aluminum,Jet Black,Chrome Plated,
or Natural Brass The glass bulb contains a fluid that agency, such as UL Listing based on
the
Physical Characteristics expands when exposed to heat.When requirements of NFPA 13 and FM
Approval based on the requirements
Frame Bronze the rated temperature is reached, the of the FM Global Loss Prevention Data
Button Sealing Assembly..Beryllium NickelBrss/Copw/TEFLON per fluid expands sufficiently to shatter the Sheets.Use only the style 10,20,30,or
Bulb Glass glass bulb, allowing the sprinkler to 40 Recessed Escutcheon, as applica-
Compression Screw Bronze activate and water to flow. ble,for recessed pendent installations.
Deflector Copper/Bronze
Bushing(K=2.8) Bronze
TFP171
Page 3 of 12
*Temperature rating ** Pipe thread connections per 1 - Frame 3 - Sealing 5 - Compression
is indicated on ISO 7-1 can be provided on 2 - Button Assembly Screw
Deflector. special request. ESCUTCHEON 4 - Bulb 6 - Deflector*
PLATE SEATING
SURFACE
7/16" ,�— 3
(11,1 min) '�'',�.
NOMINAL i1 I2-3/16" M��� 2r MAKE-IN (55,6 min)
'IF
�� 2-3/16" 1 1/2" 4
1 (55,6 mm) (38,1 mm)
,------5
6*
1/2" NPT** t WRENCH STYLE 10 or 20 2-7/8"(73,0 mm)DIA. -
FLATS RECESSED
UPRIGHT PENDENT ESCUTCHEON RECESSED PENDENT CROSS SECTION
ALL FINISHES EXCEPT POLY-STAINLESS
WRENCH 1/2" ESCUTCHEON 1 - Frame 3 - Sealing 5 - Compression *Temperature
FLATS NPT PLATE SEATING 2 - Button Assembly Screw rating indicated
ISURFACE 4 - Bulb— 6 - Deflector* on Deflector.
iL/.// 1111
+'T �\D 1
7/16" �r�—_ 3
(11,1 mm) '■'i,� \\
NOMINAL2 3/16" �: _", �� 2
MAKE IN (55,6 mm) 6—
4
` 2-3/16" 1-1/2" I
(55,6 mm) (38,1 mm) c11111,
,=, 5
--_ jif %- '_v—�i('4 . 6*
f STYLE 10 2-7/8' (73,0 mm)DIA. -
RECESSED
UPRIGHT PENDENT ESCUTCHEON RECESSED PENDENT CROSS SECTION
POLY-STAINLESS FINISH ONLY
FIGURE 3
QUICK RESPONSE SERIES TY-FRB UPRIGHT(TY3131)AND PENDENT(TY3231)SPRINKLERS
5.6 K-FACTOR, 1/2 IN. NPT
Installation of the sprinkler.Do not attempt to corn- Series TY FRB Recessed Pendent
pensate for insufficient adjustment in Sprinklers
The TYCO Series TY-FRB 2.8,4.2,5.6, the escutcheon plate by under-or over- The Series TY-FRB Recessed Pendent
and 8.0 K-factor Upright,Pendent,and tightening the sprinkler. Re-adjust the Sprinklers must be installed in accor-
Recessed Pendent Sprinklers must position of the sprinkler fitting to suit. dance with the following instructions:
be installed in accordance with this Series TY-FRB Upright and Pendent Step 1.After installing the Style 10,20,
section. Sprinklers 30, or 40 Mounting Plate, as applica-
General Instructions The Series TY-FRB Upright and ble,over the sprinkler threads and with
Do not install any bulb type sprinkler Pendent Sprinklers must be installed pipe-thread sealant applied to the pipe
if the bulb is cracked or there is a loss in accordance with the following threads,hand-tighten the sprinkler into
of liquid from the bulb.With the sprin- instructions: the sprinkler fitting.
kler held horizontally,a small air bubble Step 1.Install pendent sprinklers in the Step 2. Tighten the sprinkler into the
should be present.The diameter of the pendent position. Install upright sprin- sprinkler fitting using only the W-Type 7
air bubble is approximately 1/16 in. klers in the upright position. Recessed Sprinkler Wrench,see Figure
(1,6 mm) for the 135°F (57°C) and Step2. Withpipethread sealant 15. With reference to Figure 1 to 4,
3/32 in.(2,4 mm)for the 286°F(141°C) apply the W-Type 7 Recessed Sprinkler
temperature ratings.A leak-tight 1/2 in. applied to the pipe threads, hand Wrench to the sprinkler wrench flats.
NPT sprinkler joint should be obtained tighten the sprinkler into the sprinkler
by applying a minimum-to-maximum fitting. Step 3.After the ceiling is installed or
torque of 7 to 14 lb-ft(9,5 to 19,0 N•m). Step 3. Tighten the sprinkler into the the fin10,sh co is applied,40d, slide on the
A leak tight 3/4 in. NPT sprinkler joint sprinkler fitting using only the W-Type 6 Stylee Series 20, 30,RB or Recessed Closure dent
should be obtained with a torque of Sprinkler Wrench(Ref.Figure 14).With the erndT push Clour Pendent
10 to 20 lb-ft(13,4 to 26,8 N•m).Higher reference to Figure 1 to Figure 5,apply Sprinkler and push the Closure over the
levels of torque can distort the sprinkler the W-Type contact 6 Sprinkler Wrench to the o Plate until its flange comes in
inlet and cause leakage or impairment sprinkler wrench flats. conttaacctt with the ceiling.
TFP171
Page 4 of 12
*Temperature rating ** Pipe thread connections per 1 - Frame 3 - Sealing 5 - Compression
is indicated on ISO 7-1 can be provided on ESCUTCHEON 2 - Button Assembly Screw
Deflector. special request. PLATE SEATING 4 - Bulb 6 - Deflector*
SURFACE
1
---------- i / mit-___
1/2" --- 3
(12,7 mm) '
NOMINAL I-I } 2-5/16" = lr • 2
MAKE-IN (58,7 mm) 11110
2 1/4" 4
1 9/16"
(57,2 mm) I (39,7 mm)
-\ ..___X__.. ' III -----5
6*
3/4"NPT** t WRENCH STYLE 30 or 40 FLATS RECESSED 2-7/8"(73,0 mm)DIA.
UPRIGHT PENDENT ESCUTCHEON RECESSED PENDENT CROSS SECTION
ALL FINISHES EXCEPT POLY-STAINLESS
WRENCH 3/4" ESCUTCHEON 1 - Frame 3 - Sealing 5 - Compression *Temperature
FLATS NPT PLATE SEATING 2 - Button Assembly Screw rating indicated
SURFACE 4 - Bulb 6 - Deflector* on Deflector.
-- /
1/2" _ 3
(12,7 mm)NOMINA 1� 1�l j^
MAKE-IN
L = 2 5/16" �: �% I Irig \ 2
r�� (58,7 mm) 4
= 2-1/4" 1-9/16" 1
1 (57,2 mm) 1111111
(39,7 mm) ' . 5
STYLE 40 2-7/8'(73,0 mm)DIA.
RECESSED
UPRIGHT PENDENT ESCUTCHEON RECESSED PENDENT CROSS SECTION
POLY-STAINLESS FINISH ONLY
FIGURE 4
QUICK RESPONSE SERIES TY-FRB UPRIGHT(TY4131)AND PENDENT(TY4231)SPRINKLERS
8.0 K-FACTOR,3/4 IN.NPT
CEILING PLATE 1 - Frame 5 - Compression
SEATING SURFACE 2 - Button Screw
1 3 - Sealing 6 - Deflector
a•�-� � Assembly
Y 3 4 - Bulb
7/16" 2-1/4"
(11,1 mm) I 1 (57,2 mm)
1114 NOMINAL 2
MAKE IN * Temperature rating is
I I 2-3/16" 1-9/16" 4 indicated on Deflector.
(55,6 mm) 1 i (39,7 mm)
_ 5 ** Pipe thread connections
\ -- -- per ISO 7-1 can be
6 * provided on special
1/2"NPT** t WRENCH request.
FLATS
UPRIGHT PENDENT CROSS SECTION
FIGURE 5
QUICK RESPONSE SERIES TY-FRB UPRIGHT(TY4831)AND PENDENT(TY4931)SPRINKLERS
8.0 K-FACTOR, 1/2 IN.NPT
•
TFP171
Page 5 of 12
2-7/8"DIA. _ 2-7/8"DIA.
5/8t1/4" (73,0 mm) 3/4"(19,1 mm) (73,0 mm) 1/2"(12,7
1/2t1/8" mm)
(15,9±6,4 mm) (6,4 1/4
1/4"(6,4 mm) (12,7t3,2 mm) "
2-1/4"DIA. 2-1/4"DIA. mm)
/ FACE OF (57,2 mm) MOUNTING / FACE OF (57,2 mm) MOUNTING
SPRINKLER PLATE SPRINKLER PLATE
FITTING FITTING
401_ zi
1/8" 1/8"
11- 'i (3,2 mm) 1 T __Ii pTr (3,2 mm)
MN
i
\ ,,� # MOUNTING ,I'
MOUNTING SURFACE
SURFACE
CLOSURE SERIES 1-5/16"(33,3 mm) CLOSURE SERIES 1-5/16"(33,3 mm)
TY-FRB 13/16"(20,6 mm) TY-FRB 1-1/16"(27,0 mm)
FIGURE 6 FIGURE 7
SERIES TY-FRB RECESSED PENDENT SERIES TY-FRB RECESSED PENDENT
WITH TWO-PIECE 3/4 INCH TOTAL ADJUSTMENT WITH TWO-PIECE 1/2 INCH TOTAL ADJUSTMENT
STYLE 10 RECESSED ESCUTCHEON STYLE 20 RECESSED ESCUTCHEON
2.8 K-FACTOR, 1/2 IN.NPT 2.8 K-FACTOR, 1/2 IN.NPT
2-7/8"DIA. _ 2-7/8"DIA.
(73,0 mm) 3/4"(19,1 mm) (73,0 mm) 1/2"(12,7
5/8±1/4" 1/2t1/8" mm)
(15,9±6,4 mm) (6,4 1/4"(6,4 mm) (12,7±3,2 mm) 1/4"
2-1/4"DIA. 2-1/4"DIA. _ mm)
/ FACE OF (57,2 mm) MOUNTING / FACE OF (57,2 mm) MOUNTING
SPRINKLER PLATE SPRINKLERr--- PLATE
FITTING FITTING
/ 1/8" 1/8"
_ (3,2 mm) (3,2 mm)
Z i_
\ ,,, MOUNTING IP f
MOUNTING . SURFACE
SURFACE .._ .. -- --
SERIES 1-1/4"(31,8 mm) SERIES 1-1/4"(31,8 mm)
CLOSURE CLOSURE
TY-FRB 3/4"(19,1 mm) TY-FRB 1"(25,4 mm)
FIGURE 8 FIGURE 9
SERIES TY-FRB RECESSED PENDENT SERIES TY-FRB RECESSED PENDENT
WITH TWO-PIECE 3/4 INCH TOTAL ADJUSTMENT WITH TWO-PIECE 1/2 INCH TOTAL ADJUSTMENT
STYLE 10 RECESSED ESCUTCHEON STYLE 20 RECESSED ESCUTCHEON
4.2 K-FACTOR, 1/2 IN.NPT 4.2 K-FACTOR, 1/2 IN. NPT
TFP171
Page 6 of 12
2-7/8"DIA. 2-7/8"DIA.
5/8f1/4" (73,0 mm) 3/4"(19,1 mm) (73,0 mm) 1/2"(12,7
1/2±1/8" mm)
(15,9±6,4 mm) 1/4"(6,4 mm) (12,7±3,2 mm) 1/4"(6,4
2-1/4"DIA. _ 2-1/4"DIA. mm)
/ FACE OF r (57,2 mm) MOUNTING / FACE OF (57,2 mm) MOUNTING
SPRINKLER PLATE SPRINKLER PLATE
FITTING FITTING
/ 1/8" / 1/8"
(3,2 mm) (3,2 mm)1 I ��/ Gil rt Prr,.
/ 711
-J t \
\ , t MOUNTING ,�rMOUNTING _ _ SURFACE
SURFACE ,�A _.A.-;-, •
SERIES 1-1/4"(31,8 mm) SERIES 1-1/4"(31,8 mm)
CLOSURE TY-FRB 3/4"(19,1 mm) CLOSURE TY-FRB 1"(25,4 mm)
FIGURE 10 FIGURE 11
SERIES TY-FRB RECESSED PENDENT SERIES TY-FRB RECESSED PENDENT
WITH TWO-PIECE 3/4 INCH TOTAL ADJUSTMENT WITH TWO-PIECE 1/2 INCH TOTAL ADJUSTMENT
STYLE 10 RECESSED ESCUTCHEON STYLE 20 RECESSED ESCUTCHEON
5.6 K-FACTOR, 1/2 IN. NPT 5.6 K-FACTOR, 1/2 IN.NPT
2-7/8"DIA. 2-7/8"DIA.
5/8t1/4" (73,0 mm) - 3/4"(19,1 mm) 1/2±1/8" (73,0 mm) 1/2"(12,7 mm)
15,9±6,4 mm 1/4"(6,4 mm) (12,7±3,2 mm) 1/4"(6,4 mm)
( ) 2 1/4"DIA. 2 1/4"DIA.
/ FACE OF (57,2 mm) MOUNTING / FACE OF (57,2 mm) MOUNTING
SPRINKLER PLATE SPRINKLER PLATE
FITTING FITTING
1/8" 1/8"
/ (3,2 mm) / (3,2 mm)
lat. -2/a-/7/ /
f \
\ MOUNTING
MOUNTING SURFACE
SURFACE ,
CLOSURE SERIES 1-5/16"(33,3 mm) CLOSURE SERIES 1-5/16"(33,3 mm)
TY-FRB 13/16"(20,6 mm) TY-FRB 1-1/16"(27,0 mm)
FIGURE 12 FIGURE 13
SERIES TY-FRB RECESSED PENDENT SERIES TY-FRB RECESSED PENDENT
WITH TWO-PIECE 3/4 INCH TOTAL ADJUSTMENT WITH TWO-PIECE 1/2 INCH TOTAL ADJUSTMENT
STYLE 40 RECESSED ESCUTCHEON STYLE 30 RECESSED ESCUTCHEON
8.0 K-FACTOR,3/4 IN.NPT 8.0 K-FACTOR,3/4 IN.NPT
WRENCH
G RECESS
WRENCH RECESS Sr
(END"A"USED FOR
^ 1/2"NPT MODELS) I
.41rill
*war
WRENCH RECESS
PUSH WRENCH
(END"B" USED FOR
IN TO ENSURE
3/4"NPT MODELS) ENGAGEMENT
WITH SPRINKLER
WRENCHING AREA
FIGURE 14 FIGURE 15
W-TYPE 6 SPRINKLER W-TYPE 7 RECESSED
WRENCH SPRINKLER WRENCH
TFP171
Page 7 of 12
Sprinkler Finish5
Bulb Liquid
K-Factor Type Temperature
Color Natural Chrome Plated Polyester
Brass
135°F(57°C) Orange
155°F(68°C) Red
Pendent 175°F(79°C) Yellow
(TY1231)
200°F(93°C) Green
286°F(141°C) Blue
1,2,3,4
135°F(57°C) Orange
155°F(68°C) Red
Upright(TY1131) 175°F(79°C) Yellow
2.8 200°F(93°C) Green
1/2 in.NPT 286°F(141°C) Blue
135°F(57°C) Orange
Recessed Pendent (68
°C)( °C) Red
(TY1231)a 175°F(79°C) Yellow
Figure 6
200°F(93°C) Green
1,2,4
135°F(57°C) Orange
Recessed )Pendent (155°F 68°C Red
(TY1231)b 175°F(79°C) Yellow
Figure 7
200°F(93°C) Green
NOTES
a. Installed with Style 10(1/2 in.NPT)or Style 40(3/4 in.NPT)3/4 in.Total Adjustment Recessed Escutcheon,as applicable.
b. Installed with Style 20(1/2 in.NPT)or Style 30(3/4 in.NPT)1/2 in.Total Adjustment Recessed Escutcheon,as applicable.
c. Frame and Deflector only.
1. Listed by Underwriters Laboratories,Inc.,(UL)as Quick Response Sprinklers.
2. Listed by Underwriters Laboratories,Inc.,for use in Canada(C-UL)as Quick Response Sprinklers.
3. Approved by Factory Mutual Research Corporation(FM)as Quick Response Sprinklers.
4. Approved by the City of New York under MEA 354-01-E.
5. Where Polyester Coated Sprinklers are noted to be UL and C-UL Listed,the sprinklers are UL and C-UL Listed,the sprinklers are UL and C-UL Listed as corrosion-resistant
sprinklers.
TABLE A
LABORATORY LISTINGS AND APPROVALS FOR
2.8 K-FACTOR SPRINKLERS
TFP171
Page 8 of 12
Sprinkler Finish3
K-Factor Type Temperature Bulb Liquid
Color Natural Chrome Plated Polyesters
Brass
135°F(57°C) Orange
155°F(68°C) Red
Pendent 175°F(79°C) Yellow
(TY2231)
200°F(93°C) Green
286°F(141°C) Blue
135°F(57°C) Orange
155°F(68°C) Red
Upright(TY2131) 175°F(79°C) Yellow
4.2 200°F(93°C) Green
1,2
1/2 in.NPT
286°F(141°C) Blue
135°F(57°C) Orange
Recessed )Pendent (155°F 68°C Red
(TY2231)a 175°F(79°C) Yellow
Figure 8
200°F(93°C) Green
135°F(57°C) Orange
Recessed Pendent 155°F(68°C) Red
(TY2231)b 175°F(79°C) Yellow
Figure 9
200°F(93°C) Green
NOTES
a. Installed with Style 10(1/2 in.NPT)or Style 40(3/4 in.NPT)3/4 in.Total Adjustment Recessed Escutcheon,as applicable.
b. Installed with Style 20(1/2 in.NPT)or Style 30(3/4 in.NPT)1/2 in.Total Adjustment Recessed Escutcheon,as applicable.
c. Frame and Deflector only.
1. Listed by Underwriters Laboratories,Inc.,(UL)as Quick Response Sprinklers.
2. Listed by Underwriters Laboratories,Inc.,for use in Canada(C-UL)as Quick Response Sprinklers.
3. Where Polyester Coated Sprinklers are noted to be UL and C-UL Listed,the sprinklers are UL and C-UL Listed,the sprinklers are UL and C-UL Listed as corrosion-resistant
sprinklers.
TABLE B
LABORATORY LISTINGS AND APPROVALS FOR
4.2 K-FACTOR SPRINKLERS
•
TFP171
Page 9 of 12
Sprinkler Finish8
K-Factor Type Temperature Bulb Liquid
Color Natural Chrome Polyesters Poly-Stainlessc Lead
Brass Plated Coated
135°F(57°C) Orange
155°F(68°C) Red
Pendent 175°F(79°C) Yellow 1,2,3,4,5,6,7 1,2 1,2,3,5
(TY3231)
200°F(93°C) Green
286°F(141°C) Blue
135°F(57°C) Orange
155°F(68°C) Red
Upright 175°F(79°C) Yellow 1,2,3,5,6 1,2 1,2,3,5
(TY3131)
200°F(93°C) Green
5.6 286°F(141°C) Blue
1/2 in.
NPT 135°F(57°C) Orange
Recessed 155°F(68°C) Red
Pendent 175°F(79°C) Yellow 1,2,4,5 1,2 N/Ad
(TY3231)a
Figure 10 200°F(93°C) Green
286°F(141°C) Blue
135°F(57°C) Orange
Recessed 155°F(68°C) Red
Pendent 175°F 79°C Yellow 1,2,3,4,5 N/A N/A
(TY3231)b ( )
Figure 11 200°F(93°C) Green
286°F(141°C) Blue
NOTES
a. Installed with Style 10(1/2 in.NPT)or Style 40(3/4 in.NPT)3/4 in.Total Adjustment Recessed Escutcheon,as applicable.
b. Installed with Style 20(1/2 in.NPT)or Style 30(3/4 in.NPT)1/2 in.Total Adjustment Recessed Escutcheon,as applicable.
c. Frame and Deflector only.
d. Not available(N/A).
1. Listed by Underwriters Laboratories,Inc.,(UL)as Quick Response Sprinklers.
2. Listed by Underwriters Laboratories,Inc.,for use in Canada(C-UL)as Quick Response Sprinklers.
3. Approved by Factory Mutual Research Corporation(FM)as Quick Response Sprinklers.
4. Approved by the Loss Prevention Certification Board(LPCB Ref.No.007k/04)as Quick Response Sprinklers.However,LPCB does not rate the thermal sensitivity of recessed
sprinklers.
5. Approved by the City of New York under MEA 354-01-E.
6. VdS Approved(For details,contact Johnson Controls,Enschede,Netherlands,Tel.31-53-428-4444/Fax 31-53-428-3377.)
7. Approved by the Loss Prevention Certification Board(LPCB Ref.No.094a/06)as Quick Response Sprinklers.
8. Where Polyester Coated and Lead-Coated Sprinklers are noted to be UL and C-UL Listed,the sprinklers are UL and C-UL Listed as Corrosion-Resistant Sprinklers.Where
Lead-Coated Sprinklers are noted to be FM Approved,the sprinklers are FM Approved as a Corrosion-Resistant Sprinklers.
TABLE C
LABORATORY LISTINGS AND APPROVALS FOR
5.6 K-FACTOR SPRINKLERS
•
•
•
TFP171
Page 10 of 12
Sprinkler Finish°
K-Factor Type Temperature Bulb Liquid
Color Natural Chrome polyesters Poly-Stainlessc Lead
Brass Plated Coated
135°F(57°C) Orange
155°F(68°C) Red
Pendent 175°F(79°C) Yellow
(TY4231)
200°F(93°C) Green
286°F(141°C) Blue
135°F(57°C) Orange 1,2,3,4,5,6,7 1,2 1,2,5
155°F(68°C) Red
Upright 175°F(79°C) Yellow
(TY4131)
200°F(93°C) Green
8.0 286°F(141°C) Blue
NPT3/ in.
135°F(57°C) Orange
g
Recessed 155°F(68°C) Red
Pendent
(TY4231)a 175°F(79°C) Yellow 1,2,5 1,2 N/Ad
Figure 12 200°F(93°C) Green
286°F(141°C) Blue
135°F(57°C) Orange
Recessed 155°F(68°C) Red
Pendent
175°F(79°C) Yellow 1,2,3,5 N/A N/A
(TY4231)
Figure 13 200°F(93°C) Green
286°F(141°C) Blue
135°F(57°C) Orange
155°F(68°C) Red
Pendent 175°F(79°C) Yellow
(TY4931)
200°F(93°C) Green
8.0 286°F(141°C) Blue
1/2 in. 1,2,4,5,6 N/A 1,2,5
NPT 135°F(57°C) Orange
155°F(68°C) Red
Upright 175°F(79°C) Yellow
(TY4831)
200°F(93°C) Green
286°F(141°C) Blue
NOTES
a. Installed with Style 10(1/2 in.NPT)or Style 40(3/4 in.NPT)3/4 in.Total Adjustment Recessed Escutcheon,as applicable.
b. Installed with Style 20(1/2 in.NPT)or Style 30(3/4 in.NPT)1/2 in.Total Adjustment Recessed Escutcheon,as applicable.
c. Frame and Deflector only.
d. Not available(N/A).
1. Listed by Underwriters Laboratories,Inc.,(UL)as Quick Response Sprinklers.
2. Listed by Underwriters Laboratories,Inc.,for use in Canada(C-UL)as Quick Response Sprinklers.
3. Approved by Factory Mutual Research Corporation(FM)as Quick Response Sprinklers.
4. Approved by the Loss Prevention Certification Board(LPCB Ref.No.007k/04)as Quick Response Sprinklers.However,LPCB does not rate the thermal sensitivity of recessed
sprinklers.
5. Approved by the City of New York under MEA 354-01-E.
6. VdS Approved(For details,contact Johnson Controls,Enschede,Netherlands,Tel.31-53-428-4444/Fax 31-53-428-3377.)
7. Approved by the Loss Prevention Certification Board(LPCB Ref.No.094a/06)as Quick Response Sprinklers.
8. Where Polyester Coated and Lead-Coated Sprinklers are noted to be UL and C-UL Listed,the sprinklers are UL and C-UL Listed as Corrosion-Resistant Sprinklers.Where
Lead-Coated Sprinklers are noted to be FM Approved,the sprinklers are FM Approved as a Corrosion-Resistant Sprinklers.
TABLE D
LABORATORY LISTINGS AND APPROVALS FOR
5.6 AND 8.0 K-FACTOR SPRINKLERS
• TFP171
Page 11 of 12
Sprinkler Finish
K-Factor Type Natural Chrome
Brass Plated Polyester Lead Coated
Pendent(TY1231)
and
2.8 Upright(TY1131)
1/2 in. 175 psi(12,1 bar) N/A2
NPT Recessed
Pendent(TY1231)
Pendent(TY2231)
and
4.2 Upright(TY2131)
1/2 in. 175 psi(12,1 bar) N/A
NPT Recessed
Pendent(TY2231)
Pendent(TY3231)
and
5.6 Upright(TY3131) 250 psi(17,2 bar)
1NPT or 175 psi(12,1 bar)1
Recessed
Pendent(TY3231)
Pendent(TY4231) 175psi
and8.0 Upright(TY4131) (12,1 bar)
3/4 in. 175 psi(12,1 bar)
NPT Recessed
N/A
Pendent(TY4231)
8.0 Pendent(TY4931) 175 psi
1/2 in. and 175 psi(12,1 bar) (12,1 bar)
NPT Upright(TY4831)
NOTES
1. The maximum working pressure of 250 psi(17,2 bar)only applies to the Listing by Underwriters Laboratories Inc.(UL);the Listing by Underwriters Laboratories,Inc.for use in
Canada(C-UL);and,the Approval by the City of New York.
2. Not available(N/A).
TABLE E
MAXIMUM WORKING PRESSURE
Care and corrosive products of combustion, but tion Service in accordance with local
have not operated,should be replaced requirements and/or national codes.
Maintenance if they cannot be completely cleaned Care must be exercised to avoid
by wiping the sprinkler with a cloth or damage to the sprinklers before,
The TYCO Series TY-FRB 2.8,4.2,5.6, by brushing it with a soft bristle brush. during, and after installation. Sprin-
and 8.0 K-factor Upright,Pendent,and Care must be taken to avoid damage klers damaged by dropping, striking,
Recessed Pendent Sprinklers must be to the sprinklers before, during, and wrench twist/slippage,or the like,must
maintained and serviced in accordance after installation. Sprinklers damaged be replaced.Also,replace any sprinkler
with this section. Before closing a fire by dropping, striking, wrench twist/ that has a cracked bulb or that has lost
protection system main control valve slippage,or the like,must be replaced. liquid from its bulb.For more informa-
for maintenance work on the fire pro- Also, replace any sprinkler that has tion,see Installation section.
tection system that it controls, obtain a cracked bulb or that has lost liquid Initial and frequent visual inspections of
permission to shut down the affected from its bulb.For more information,see random samples are recommended for
fire protection systems from the proper Installation section. corrosion-resistant sprinklers to verify
authorities and notify all personnel who The owner is responsible for the the integrity of the corrosion-resis-
may be affected by this action. inspection,testing,and maintenance of tant material of construction. There-
Absence of the outer piece of an their fire protection system and devices after, annual inspections per NFPA 25
escutcheon, which is used to cover in compliance with this document, as should suffice. Inspections of corro-
a clearance hole, can delay sprinkler well as with the applicable standards sion-resistant sprinklers are recom-
operation in a fire situation. of the National Fire Protection Associ- mended at close range,instead of from
Sprinklers which are found to be ation such as NFPA 25, in addition to the floor level per NFPA. Inspection at
leaking or exhibiting visible signs of the standards of any other authorities close range can better determine the
must be replaced. having jurisdiction.Contact the install- exact sprinkler condition and the long-
corrosionng contractor or sprinkler manufac- term integrity of the corrosion-resistant
Automatic sprinklers must never be turer regarding any questions. material,which can be affected by the
painted, plated, coated, or other- Automatic sprinkler systems are rec corrosive conditions present.
wise altered after leaving the factory. ommended to be inspected, tested,
Modified sprinklers must be replaced. and maintained by a qualified Inspec-
Sprinklers that have been exposed to
TFP171
Page 12 of 12
P/N 57 - XXX - X - XXX
SIN TEMPERATURE
SPRINKLER RATINGS
FINISH
330 2.8K UPRIGHT(1/2 in. NPT) TY1131 135 135°F(57°C)
1 NATURAL BRASS
331 2.8K PENDENT(1/2 in.NPT) TY1231 POLY STAINLESS GREY 155 155°F(68°C)
2 ALUMINUM(RAL9007)1
340 4.2K UPRIGHT(1/2 in.NPT) TY2131 POLYESTER 175 175°F(79°C)
PURE WHITE
341 4.2K PENDENT(1/2 in. NPT) TY2231 3 POLYESTER(RAL9010)2 200 200°F(93°C)
SIGNAL WHITE
370 5.6K UPRIGHT(1/2 in. NPT) TY3131 4 POLYESTER(RAL9003) 286 286°F(141°C)
JET BLACK
371 5.6K PENDENT(1/2 in. NPT) TY3231 5 POLYESTER(RAL9005)3
390 8.0K UPRIGHT(3/4 in.NPT) TY4131 7 LEAD COATED
391 8.0K PENDENT(3/4 in. NPT) TY4231
9 CHROME PLATED
360 8.0K UPRIGHT(1/2 in.NPT) TY4831 NOTES
1. Available only on TY3131,TY3231,TY4131,and TY4231
2. Eastern Hemisphere sales only.
361 8.0K PENDENT(1/2 in. NPT) TY4931 3. Available in only 2.8K,4.2K,and 8.0K,155°F(68°C)and 200°F(93°C);requires longer
lead time to manufacture.
TABLE F
SERIES TY-FRB PENDENT AND UPRIGHT SPRINKLERS
PART NUMBER SELECTION
Limited Ordering
Warranty Procedure
For warranty terms and conditions,visit Contact your local distributor for
www.tyco-fire.com. availability. When placing an order,
indicate the full product name and Part
Number(P/N).
Sprinkler Assemblies with NPT
Thread Connections
Specify: Series TY-FRB(Specify SIN),
(specify K-factor), (specify Pendent or
Upright)Sprinkler(specify)temperature
rating, (specify) finish or coating, P/N
(specify from Table F)
Recessed Escutcheon
Specify: Style (10, 20, 30, or 40)
Recessed Escutcheon with (specify`)
finish, P/N (specify')
'Refer to Technical Data Sheet TFP770
Sprinkler Wrench
Specify: W-Type 6 Sprinkler Wrench,
P/N 56-000-6-387
Specify: W-Type 7 Sprinkler Wrench,
P/N 56-850-4-001
1400 Pennbrook Parkway,Lansdale,PA 19446 I Telephone+1-215-362-0700 AV
IAJohnson Controls.All rights reserved.All specifications and other information shown were current as of document revision date and are subject to change without notice. Johnson l 1 IsoA
NATIONAL FIRE PROTECTION ASSOCIATION and NFPA are registered trademarks of National Fire Protection Association;re Controls S
TEFLON is a registered trademark of DuPont