Report RECE1V ED //I/74 71v' J pK• OCT 7 2021 Page : 1, t Y TIGAHLi SENJU SPRINKLER CO.,LTD. I_ 3UILDI G DIVISION Residential Lead Free Flat Concealed Sprinkler, Pendent, Model: RC-RES, K-Factor: 4.9, SIN: SS8464 _ GENERAL DESCRIPTION The Model RC-RES Residential Flat Concealed Sprinklers are automatic sprinklers of the compressed fusible solder type.These are decorative and fast response.The Cover Plate Assembly hides the Deflector,Heat Responsive Element etc.,which is in turn concealed above the ceiling. The cover plate has a flat profile, and its diameter is extremely small (2-5/8 inch, 68mm). The push-on and/or thread-on, thread-off design of the concealed cover plate assembly allows easy installation of the cover plate. Therefore, the Model RC-RES should be your first choice when aesthetics is the major consideration for ultimate appeal and unbeatable performance is desired. The Model RC-RES is designed for the residential occupancies and it is perfect for use in homes,hotels and other living quarters. The Model RC-RES is to be used in wet pipe residential sprinkler systems for One- and Two- Family Dwellings and Manufactured Homes per NFPA 13D; wet pipe residential sprinkler systems for Residential Occupancies up to and Including Four Stories in Height per NFPA 13R;or,wet pipe sprinkler systems for the residential portions of any occupancies per NFPA 13. The Model RC-RES has a 4.9 (70.6 LPM/bar1/2) K-factor that meets the required residential flow rates with minimal residual pressure,which allows for smaller pipe sizes and water supply requirements. For extended installation flexibility, the Model RC-RES provides 1/2 inch (12.8mm) vertical adjustment. This adjustment in installation decreases the need for precise cutting of the pipe that drops to the sprinkler and allows for a perfect fit with a range of pipe lengths. The heat sensitivity and water distribution design of Model RC-RES allows for an increased chance of residents'escape or evacuation in case of fire.However, residential fire sprinkler systems are not a substitute for fire safety awareness or fire safety construction required by building codes. "Lead Free"is defined in the Reduction of Lead in Drinking Water Act(S.3874)endorsed by AWWA's Water Utility Council, and Califomia Assembly Bill#1953 as having less than or equal to a weighted average of 0.25% lead in wetted surface of pipes, plumbing fittings and fixtures. WARNINGS The Model RC-RES must be installed and maintained in accordance with the rules stated herein as well as in compliance with the applicable standards of the National Fire Protection Association regulations and the standards of any other authorities having jurisdiction. In the event of this condition,consult the authorities having jurisdiction for guidance and approval. Failure to do so may impair the integrity of these devices. It is the responsibility of the installing contractor to provide a copy of this document to the owner or his representative, and in turn,it is the obligation of the owner to provide a copy of this document to a succeeding owner. The owner is responsible for maintaining their fire protection system and devices in proper operating condition. The installing contractor or sprinkler manufacturer should be contacted with any related questions. Document No.U085162 Date :Feb/09/2017 Page :2 of 8 TECHNICAL DATA Approvals:cULps Listed, NSF-61-G Sprinkler Identification Number(SIN): SS8464 Maximum Working Pressure:175psi(12.1bar) Discharge Coefficient(Nominal K-Factor): K=4.9 GPM/psi112(70.6 LPM/bar112) 2-1/16"(452mm) fT1L ~ Temperature Rating: ( -- Marking 162T (72°C)Sprinkler with 140T (60°C)Cover Plate a. I 1 -Lot No 175T (79°C)Sprinkler with 140T (60°C)Cover Plate ' / Year or Manufacture SIN SS8464 175 F (79°C)Sprinkler with 162T (72°C)Cover Plate . K-factor K4.9 Color Code(Sprinkler) ' '4). Temperature Rating:162'F/72'C ( p ) w r 'N. -- — -A UL Mark a 175�F/7SC 162T (72°C): Uncolored 7 (. ____T Control No:6P37 175 F (79°C):White NSF Mark:NSF-81-G ----- --RES SPKR Color Code(Cover Plate) � -- i.t Body(Copper Alloy) 140T (60°C): No Mark (;;, Deflector(Phosphorus Bronze) "(rb 68mm) '4, Gasket(PTFE) 2-5l8 162T (72°C):White-Colored Mark .4; Fusible Metal(Solder) or 3-1/4"((683mm) (5: Heat Collector(Copper, Vertical Adjustment: 1/2 inch(12.8 mm) r -/8" r (5. Cover Plate Assembly Cover Plate Finishes: Standard Finishes- White,Ivory, Beige,Brown,Black, Nickel, Wood Grain Marking(Deflector) /-SIN:S58464 Custom Finishes- J— Cola Code K-factor:K4.9 I -Temperature Rating: Custom color and custom pattern cover plates are r , 162`F72'C or 1T5`F'79`C available on special order. Contact a SenjupfoUL Mark Sprinkler representative with any custom orders. Please see chart on Page 8 for more detail. a ,' _i i Physical Characteristics: Ref.Figure 1 + COVER PLATE SPRINKLER OPERATION — (Top new) (Bottom view) — In case of fire, the solder component that holds together the Cover Plate and the Retainer melts. Then, the Cover Plate is released at once.As a result,the Deflector drops down to the intended position. Two Heat Collectors are exposed to fire, and when sufficient heat from the fire is recorded,internal components of the sprinkler to fall apart.This leads to allow the water flow to be distributed on the affected by fire area.(Ref. Figure 2) .., , .:., , . : .. ' ;j �1 4 _ . ... _{ ,,_„,;_. ,,,,n. , . : ,__,,f. ji IIf, _ „- -i I` Normal Condition Cover Plate Operation Sprinkler Operation 'Nate,Eh,harge FIGURE 2. OPERATION PROCESS (The figure is for illustrative purpose only) Document No.U085162 Date :Feb/09/2017 Via Page :3 of 8 DESIGN CRITERIA The herein stated rules for use and installation of Model RC-RES are provided by the manufacturer and must be strictly implemented for safe and full results. NOTES Residential Fire Sprinkler Systems should only be designed and installed by individuals who are completely familiar with automatic sprinkler system design,installation procedures,and techniques. Several criteria may apply to the installation and usage of each sprinkler. Consequently, it is recommended that the sprinkler system designer review and develop a working understanding of the complete list of criteria prior to initiating the design of the sprinkler system. Questions concerning sprinkler installation and usage criteria, which are not coverage by the following instructions, should be submitted to Contact Company.Include sketches and technical details as appropriate. In some instances,the requirements of this document may concern specifications which are more stringent and which take precedence over those specified in NFPA 13, 13D, 13R,or by the authority having jurisdiction. The Model RC-RES must not be used in applications where the air pressure above the ceiling is greater than that below. Inspect all sprinklers after installation to ensure that both the gap between the cover plate,ceiling and the 6 slots in the cup are open and free from any air flow impediment. The spray from the sprinkler is distributed radically outward and downward from the sprinkler deflector.Consequently, the sprinklers must be located such that there will be no blind spaces shielded from spray by partitions,room dividers, overhangs or other parts of the dwelling structure. The number of sprinklers within each compartment(as defined by NFPA 13, 13D, or 13R) must be kept as small as possible.Do NOT use more sprinklers than necessary to cover a particular space. Use only the Cover Plate provided with the Model RC-RES. The sprinkler must be secured in place by firmly fastening the sprinkler system piping to the structure. If the sprinkler is not properly secured in position, reaction forces resulting from sprinkler operation could alter its orientation and its water distribution pattern. Obstruction to Water Distribution Locations of sprinklers must follow the obstruction rules of NFPA 13 for Residential Sprinklers. General Service Conditions The Model RC-RES must only be utilized in WET PIPE sprinkler systems. Heat Source Criteria Refer to NFPA 13D or 13R for the requirements relating to the prevention of possible activation of the Heat Responsive Element of Model RC-RES,due to exposure to a heat sources other than an actual fire. Available Sprinkler Temperature Ratings Sprinkler Temperature Sprinkler Nominal Maximum Ambient Ceiling Temperature Rating of the Classification Temperature Rating Temperature Cover Plate Assembly Ordinary 162F (72°C) 100'F (38°C) 140F (60°C) Intermediate 175T (79°C) 150E (66°C) 140T (60°C)1> Intermediate 175T (79°C) 150'F (66°C) 162F (72°C) 1)Maximum ambient temperature for the Cover Plate Assembly is 100T (38°C). Precautionary Warnings for Corrosive Environments The Model RC-RES should not be installed where they may be subjected to a corrosive environment including the following: (1)Chlorine ion and Chloride environment. Stress corrosion cracking may be caused by exposure to environments with Chlorine ion and Chloride. Exposure to this environment may result in sprinklers operating under Non-Fire conditions or Not Operating when exposed to an actual fire. (2)Sprinkler system piping with Copper. Sprinkler systems should be constructed in compliance with the applicable standards and the requirements for the copper piping when copper piping is used in the sprinkler system. (Reference standards NFPA 13, ASTM B813, B828, and CDA (Copper Development Association)—Solder Joint) All residual flux must be removed from the interior and exterior of copper piping by thoroughly flushing before installation of the Sprinkler Heads.Otherwise,residues of flux may cause corrosion and leakage in the sprinkler system. Document No.U085162 Date :Feb/09/2017 Page :4 of 8 Hydraulic Design Criteria The minimum required sprinkler flow rates for system designed to NFPA 13D or 13R are given in Table A as a function of temperature rating and the maximum allowable coverage areas. The sprinkler flow rate is the minimum required discharge from the most hydraulically demanding sprinkler from each of the total number of"design sprinklers"as specified in NFPA 13D or 13R. For systems designed to NFPA 13, the number of designed sprinklers is to be the four most hydraulically demanding sprinklers.The minimum required discharge from each of the four sprinklers is to be the greater of the followings; • The flow rates given in Table A for NFPA 13D and 13R as a function of temperature rating and maximum allowable coverage area. • A minimum discharge 0.1GPM/sq.ft. [4.07LPM/sq.m] over the "design area" comprised of the four most hydraulically demanding sprinklers for the actual coverage areas being protected by the four sprinklers. TABLE A.NFPA 13D& 13R WET PIPE HYDRAULIC DESIGN CRITERIA for Model SS8464 Maximum Ordinary Intermediate Coverage Maximum Temperature Rating Temperature Rating Minimum Deflector Area(a) Spacing 162 F (72°C) 175T (79°C) Installation Spacing Ft. Flowro} Pressure(b) Flow(b) Pressure(6) to Type Ft. Ft.x Ft. GPM PSI GPM PSI Ceiling (m) (m) (m xm) (LPM) (bar) (LPM) (bar) Smooth 12x12 12 13 7.0 13 7.0 Ceilings (3.7x3.7) (3.7) (49.2) (0.48) (49.2) (0.48) 3/8 to 7/8 Inches. 14x14 14 13 7.0 13 7.0 (4.3x4.3) (4.3) (49.2) (0.48) (49.2) (0.48) Beamed Ceilings per NFPA 16x16 16 13 7.0 14 8.2 13D,13R 8 (4.9x4.9) (4.9) (49.2) (0.48) (53.0) (0.57) or 13 Concealed (2.4) Installed in beam 18 x 18 18 17 12.0 18 13.5 3/8 to (5.5x5.5) (5.5) (64.3) (0.83) (68.1) (0.93) 7/8 inches 20x20 20 21 18.4 below (6.1x6.1) (6.1) (79.5) (1.27) — — bottom of beam. (a) For coverage area dimensions less than the above mentioned,it needs to use the minimum required flow for the Next Higher Coverage Area listed. (b) Requirement is based on minimum flow in GPM/LPM from each sprinkler.The associated residual pressures are calculated using the nominal K-Factor.Refer to Hydraulic Design Criteria Section for details. (c) For systems with ceiling types smooth flat horizontal,or beamed,or sloped, in accordance with the 2013 Edition of NFPA 13D, 13R or 13 as applicable. Sprinkler Spacing Criteria The minimum spacing between sprinklers is 8 feet(2.4m).The maximum spacing between sprinklers cannot go beyond the coverage area calculated by using the specific hydraulic factors.(Ref.Table A) Document No.U085162 Date :Feb/09/2017 Page :5 of 8 INSTALLATION The Model RC-RES must be installed in accordance with the following instructions. NOTES Do not use any sprinklers which have been subjected to potential mechanical damage.Do not use any sprinklers which show deformation or cracking in either the Sprinkler or the Protective Cap. Prior to installation,sprinklers should be maintained in the original cartons and packaging until used to minimize the potential for damage to sprinklers that would cause improper operation or non-operation. The Protective Cap must remain on the sprinkler during installation and until the ceiling installation is completed. The Protective Cap must be removed to place the sprinkler in service. Use a torque of 7 to 14 ft.lbs(9.5 to 19.0Nm) to achieve a 1/2 inch NPT sprinkler joint.If you exceed the recommended maximum torque,this could result in damage to the sprinkler inlet,which may lead to leakage from the sprinkler. In case of insufficient adjustment in Cover Plate installation,do not try to overly tighten,screw the sprinkler too loosely or make any modification to the cover plate assembly.Readjust the sprinkler fitting for a better fit. Do not force to rotate the Cap Remover RC to the left when placing the two hook arms into place. The installed sprinkler may become loosened,which may cause water leakage. Installing Procedure Step 1 The installation requirements for the sprinkler are as follows: to be installed only in the pendent position with the waterway perpendicular to the ceiling. Install the sprinkler fitting so that the distance from the face of the fitting to the mounting surface will be nominally 2 inch(50.8mm)as shown in Figure 3. Step 2 With pipe thread sealant applied to the threads, hand tighten the sprinkler into the sprinkler fitting. Then tighten it with the Sprinkler Socket or Wrench & Socket Combination (Ref. Figure 4). The grooves of the Socket must fit perfectly with the grooves on the Sprinkler for proper installation(Ref.Figure 4). Step 3 If desired the Protective Cap may also be used to locate the center of the clearance hole by gently pushing the ceiling material against the center point of the Protective Cap.Before the installation of the ceiling,the sprinkler installation can be started with the 2-3/8 inch (60mm) diameter clearance hole (Ref. Figure 3). Use the "Tolerance Limit of Ceiling Level' indicator on the Protective Cap to check for proper installation height(Ref.Figure 3). Make a Space Here Ave.1/4"(8.4mm) Over-T Min 1/8"(3.2mm)• I •-.. Groove on the Spnnkle• Tolerance Limn of Co,i = Protective Cap of Ceiling Level r i 4. � Groove on the Socket r_.._ 144.-. 1 Socket Mowing Surface/ Wrench Mounting 2-318"(cb60mm) Surface Ceiling Hole Diameter f I CORRECT INCORRECT �-'z:r`--- FIGURE 3. INSTALLATION FIGURE 4 Step 4 Use the Cap Remover RC to remove the Protective Cap(Ref.Figure 5),and then push or screw a Cover Plate Assembly on the Cup of the Sprinkler by hand until its flange just comes in contact with the ceiling (Ref. Figure 6 and Figure 7). Stop tightening the Cover Plate Assembly once the flange has come in contact with the ceiling. If the ceiling has been lifted from its normal position in the process of tightening of the Cover Plate Assembly.readjust the cover plate assembly as necessary. If Document No.U085162 Date :Feb/09/2017 Page :6 of 8 the flange of the Cover Plate Assembly cannot come in contact with the ceiling sufficiently, readjust the sprinkler fitting as necessary.When properly installed,there is a nominal 1/16 inch(1.6mm)air gap between the lip of the Cover Plate and the ceiling,as shown in Figure 6 Sprinkler IIOd9. -•� Nook UP ,ri :::ff-7.--1---11� Protective C60, ..[Al _____ Lao Remover RC 7 I i 1......_. ', I PullIown Ste.I < p Step 3 FIGURE 5.PROTECTIVE CAP REMOVAL is •e Cup WE I�I. Y __ i °ri ulfl�lrr �dU�r`a\c N. • ..!'3, _ -. �J7°� 9}� .. „._�_, 1 Screw 4 E 8 Deletion/ E vi Cover Platembly .Plat_Assembly tr. ao I /'" L 8 . 2-5/"(r 88mm) I a 3-lie(083mm) or 2-5,'8"square(088mm) FIGURE 6 4 7 ££ • ii EE <0 4 IINCORRtCI [CORRECT] INCORRECT_ FIGURE 7.INSTALLATION(CORRECT OR INCORRECT) Document No.U085162 Date :Feb/09/2017 Page : 7 of 8 CARE AND MAINTENANCE The following instructions must be implemented for the maintenance and service of the Model RC-RES. NOTES Wet pipe sprinkler systems must be maintained at a minimum temperature of 40 F/4 t' to prevent freezing and bursting of the pipe and/or sprinklers. Automatic sprinklers are not to be tested with a heat source.Operation of the heat responsive element can result. Absence of a Cover Plate Assembly may delay the response time of the sprinkler in case of fire. Install the cover plate assembly properly,as shown in Figure 6.Improper installation of the cover plate assembly may cause improper operation or non-operation. If the ceiling is to be repainted after the installation of the Sprinkler,care must be exercised to ensure that the new paint does not seal off any of the air gap. Factory painted Cover Plates must not be repainted. They should be replaced, if necessary,by factory painted cover plates.Non-factory applied paint may adversely delay or prevent sprinkler operation in case of a fire. Do not pull the Cover Plate.Separation may result. In preparation for maintenance of the fire protection system, permission to close the main control valve must be obtained from the proper authorities and all affected by this action parties must be informed before the maintenance session can commence. Do NOT enclose any sprinklers within drapes,curtains,or valances. Do NOT hang anything from the sprinklers. Do NOT clean the sprinklers with soap and water, detergents, ammonia, cleaning fluids, or other chemicals. Remove dust,lint, cobwebs,cocoons, insects,and larvae by gently brushing with a feather duster or gently vacuuming with a soft bristle(i.e.,dusting)brush attachment. Exercise suitable safety precautions in the use and storage of highly flammable materials. The rapid rate of fire development and spread of these materials can reduce the ability of the sprinkler systems to aid in the control of a fire involving such hazards. Leaking or corroded sprinklers must be replaced. Automatic Sprinklers must never be shipped or stored where the temperature exceeds 100'F/38°C. Automatic sprinkler must never be physically altered, such as painted, plated, or coated, once shipped from the factory. If the sprinklers have been in any way modified,they must be replaced. Great caution must be applied to prevent damage to the sprinklers at all stages-before,during,and after installation.Damaged units,as a result of dropping,hitting,over-tightening,or wrench slippage, must be replaced. The Model RC-RES must only be replaced with pendent sprinklers which are listed for residential fire protection service and which have the same nominal K-Factor,the same coverage area,and the same or lower flow ratings(as indicated under Table A "Hydraulic Design Criteria"). When remodeling,such as by adding false beams or light fixtures or changing the location of compartment walls,first verity that the new construction will not violate the installation requirements of the applicable standards of NFPA.Alter the new construction and/or the sprinkler system to suit the requirements of this document and the applicable NFPA regulations. The owner is responsible for the maintenance of the sprinkler system, including inspection and testing, its compliance with this documents,as well as the standards of the National Fire Protection Association(e.g., NFPA 25),and the regulations of any other authorities having jurisdiction.The owner should direct any questions regarding the above rules and regulations to the installing contractors or the sprinkler manufacturer. It is recommended that automatic sprinkler systems be inspected, tested, and maintained by a qualified Inspection Service in accordance with NFPA 25. Document No.U085162 Date :Feb/09/2017 • • Page :8of8 ORDER PROCEDURE When placing an order,please contact a local distributor with the following information(Model Name,Specify,Temp.and Finish). Sprinkler: Model:RC-RES (SIN:SS8464,Residential Flat Concealed Sprinkler,Pendent, K4.9,Temperature: 162`F (72°C)or 175'F (79°C)) Cover Plate Assembly: 2-5/8 inch(068mm)or 3-1/4 inch(083mm)or 2-5/8 inch square(068mm),Order Separately from Sprinkler Please refer to the chart below for available sizes,temperature,and finishes. Standard Finishes Custom Finishes White Ivory Beige Brown Black Nickel Wood grain Custom Color Custom Pattern 2-5/8"Round, 140°F 0 0 - - - 0 - 0 0 3-1/4"Round, 140°F 0 0 0 0 0 0 0 0 0 2-5/8"Square, 140°F 0 - - - - - - 0 0 2-5/8"Round, 162°F 0 - - - - - - 0 0 3-1/4"Round, 162°F 0 - - - - - - 0 0 Tools for Installation of Model:RC-RES • Socket for Model RC-RES •Wrench&Socket for Model RC-RES • Cap Remover RC Document No.U085162 Date :Feb/09/2017 RECEIVED OCT 7 2021 FIRE SPRINKLER CALC. SHEET FROM RYAN'S PLUMBING INC. CITY OF TIGARD TO:_Local Fire Marshall 3UILDING DIVISION TYPE OF PIPE: CPVC A.Water pressure at meter/pump I 801psi. 80 psi. B.Meter size 3/4 C.Demand 1 size A psi. 7 psi. D.Deduct loss for elevation Remote area#1 Remote area#2 16 x 0.434 = 11111M12 psi. I 161 x 0.434 = 6.944 psi E.Deduct loss for pipe 2"pipe x 200 ft= 200 Area niT x 16 Area 16 x 161 0 45 s 0 ft= 0 Single Head 13 gpm Single Head 13 gpm 1 90s x 9 ft= 9 Demand 7 psi Demand 7 psi 0 check valve 27 ft= 0 Double Head 26 gpm Double Head 26 gpm Demand 7 psi Demand 7 psi Total ft 209 x single head 0.0045 = 0.9405 psi single head 0.0045 = 0.9405 psi double head 0.0164 = 3.4276 psi double head 0.0164 = 3.4276 psi F.Deduct loss from control valve to farthest sprinkler Size Qty Type Total ft. Size Qty Type Total ft. 1 86 pipe 86 1 44 pipe 44 1 0 90'sx iiE 0 1 0 90'sx 7 0 1 3 is x © 15 1 2 is x 5 10 1 4 45'sx © 8 1 4 45'sx 2 8 1 0 valvesx © 0 1 0 valvesx 3 0 double double check check 1 valve 60 60 0 1 valve 60 60 Total ft MEW Total ft 1221 Single head at 0.0306 = 5.1714 Single head at 0.0306 = 3.7332 Double head at 0.1105 = 18.6745 Double head at 0.1105 = 13.4810 G.Add total pressure loss Lines C,D,E,and F Single Head 20.0559 Single Head 18.6177 Double Head 36.0461 Double Head 30.8526 H.System requirements Total pressure loss Single Head 20.06 psi Single Head 18.62 psi Double Head 36.05 psi Double Head 30.85 psi Total demand required Total demand required Single Head 20.06 psi. Single Head 18.62 psi Double Head 36.05 psi. Double Head 30.85 psi Remaining Pressure Single Head 59.94 psi. Single Head 61.38 psi. Double Head 43.95 psi. Double Head 49.15 psi. demand required for this design Area 16 x 16 Area 16 x 16 Single Head 13 gpm Single Head 13 gpm Demand 7 psi Demand 7 psi Double Head 26 gpm Double Head 26 gpm Demand 7 psi Demand 7 psi This exceeds demand and design is acceptable. • N/ASHINGTON STATE i Comments: The system is supplied by a city water ' GER TIFICAT E OR COMPETENCY FIRC PRO rCCTIOt,SPRINKLER SYSTEMS -,! .1 Rya! ar Lippe Level2 - • • ' . i Ryanu Irir:g,Inc. • '. 'VAN=P19.9.;E i /,-'-2 EF ! `i/ - >� ,2r31.21 : Signal- Date L..-•f".s r� RECEIVED OCT 7 2021 t;ITY OF TIGAHL Attic Piping Section 3h1ILD1NGDIVISI0N not to scale Maximum head spacing is 20' between heads or 10' from walls. All piping shall be 1" PEX CPVC . Piping shall be installed and hung per NFPA & Manufacture's recommsndations. Fitter to install cover over piping to prevent insulation from getting between piping and the ceiling. Owner is resposible for the installation of the insulation over the piping to prevent freezing. Unheated Blown-in attic insulation space \�i —� hi 1 1 1 Tenting material 'Tent'space keeping insulation above piping NHeated space