Model F1 Recessed -
Standard Response
Sprinklers
The Designer®Model Fl Sprinkler
Standard Upright RECEIVE®
Standard Pendent ii...
-
Extended Coverage Pendent � `
Conventional SU ' .3 'ILL' it
Vertical Sidewall CITY OF TIGARD
Horizontal Sidewall Upright Pendent
-HSW 1 Deflector BUILDING DIVISION
Horizontal Sidewall Extended Coverage
-EC-6 Deflector 1
The Designer l Model Fl Recessed Sprinkler
Recessed Pendent
Recessed Extended Coverage Pendent I } 11,11
Recessed Extended Coverage Horizontal Sidewal Vertical Sidewall Conventional
Approval Organizations
1. Underwriters Laboratories Inc. ;_ _ ._ r;
2. Underwriters' Laboratories of Canada -
3. Factory Mutual Research Corp.
4. Loss Prevention Council
5. NYC BS&A No. 587-75-SA Horizontal Sidewall Recessed Pendent
6. Pleniere Assemblee
7. Verband der Schadenversicherer
8. NYC MEA 258-93-E
UL Listing Category °. ' v
Sprinklers, Automatic&Open (VNIV) "� t
Patents: US Patent No. 6,374,920 Applies to
Model F1 Vertical Sidewall Sprinklers Extended Coverage Recessed Extended
Horizontal Sidewall Coverage Horizontal
Product Description Sidewall
The F1 Glass Bulb Sprinkler combines the durability of a
standard sprinkler with the attractive low profile of a decora- -,,,,.,
tive sprinkler. Whether installed on exposed piping or in an a`
office ceiling, it is functional and attractive. The Horizontal _ • '
and Vertical Sidewall Sprinklers provide an equally attractive `
appearance when ceiling piping cannot be used. w_ _.
Beautifully versatile is the description for the Reliable Model Extended Coverage Recessed Extended
F1 Recessed Designer glass bulb sprinkler. Recessing The Pendent Coverage Pendent
Designer enhances its already low profile decorative appear-
ance, and facilitates a rapid and perfect installation. At normal temperatures,the glass bulb contains the fluid
Model F1 Recessed Designer's escutcheon is highly ad- in both the liquid phase and in the vapor phase.The vapor
justable.The two piece construction makes field installation a phase can be seen as a small bubble.As heat is applied,the
very easy and rapid task.This also allows ceiling panels to later liquid expands forcing the bubble smaller and smaller as the
be removed without shutting down the fire protection system, liquid pressure increases. Continued heating forces the liq-
thus facilitating maintenance of above ceiling services. uid to push out against the bulb,causing the glass to shatter,
The Designer® Automatic Sprinkler utilizes a frangible opening the waterway and allowing the deflector to distribute
glass bulb. The glass bulb consists of an accurately con- the discharging water.
trolled amount of special fluid hermetically sealed inside of a The F1 Sprinkler temperature rating is identified by the
precisely manufactured glass capsule. This glass bulb is color of the glass bulb capsule as well as frame color where
specially constructed to provide fast thermal response. applicable.
The Reliable Automatic Sprinkler Co.,Inc., 525 North MacQuesten Parkway,Mount Vernon, New York 10552
Model Fl Upright, Pendent & Conventional Sprinklers
Installation Wrench: Model D Sprinkler Wrench
ii
1 — f $ .
Upright Pendent Conventional
Installation Data:
Nominal Sprinkler
Nominal Thread Sprinkler Approval Identification
Orifice Size K Factor Height Organization Numbers (SIN)
US Metric Upright Pendent
Standard-Upright(SSU)and Pendent(SSP)Deflectors Marked to Indicate Position
1/2"(15mm) 1/2"NPT(R1/2) 5.6 80 2.2"(56mm) 1,2,3,4,5,6,7 R1725 R1715
1%2"(20mm) 3A"NPT(R3A)(') 8.0 115 2.3"(58mm) 1,2,3,4,7,8 R1722 R1712
' "(15mm)(3) 1"NPT(R1) 5.6 80 2.2"(56mm) 7
1/32"(20mm)(3) 3/a"NPT(R34) 8.0 115 2.3"(58mm) 7
'/,6"(11mm) ' "NPT(R1/2) 4.2 60 2.2"(56mm) 1,2,8 R1723 R1713
3/e"(10mm) ' "NPT(RY2)(2) 2.8 40 2.54"(65mm) 1,2,8 R1721 R1711
10mm XLH R% 4.2 60 56.1mm 4,6,7 R1724 R1714
Conventional-Install in Upright or Pendent Position
10mm XLH R% 4.2 60 56.1mm R1774
15mm Y"NPT(R1/2) 5.6 80 . 56.1mm 4,6,7 R1775
20mm 3/4"NPT(MA) 8.0 115 58.1mm 4,7 R1772
(')LPC Approval up 286°F(141°C)
(2)FM Approval for SSU up to and including 200°F(93°C)only.
(3)VdS Approval for Intermediate Response 155°F(68°C)only.
I I
I
2.
Model Fl Recessed Pendent Sprinkler
Installation Wrench: Model RC1 Sprinkler Wrench
4.-2 1/4'11 E DK
(57.2rm,J
1 15/16'OK
(19.2mm7
��y_s
rz-- Y i1
.•,,- '. RIRN cOIUR IT (2x Mr•n 9 12.E
Af44INST SPRINKLER
\. `. WENCH ' I —I I 1
1 IL __i 1
Fl Recessed 9 + T,1211
'Ldui A
114/ '/e_t }
2--) 1•(25.4mm]
1 f7FCOuA 2 27/2I2'Oft
(n.2m•]
(1)When installed directly into a tee,the escutcheon dimension's
adjustment will be reduced.
Installation Data:
Nominal Sprinkler
Nominal Thread K Factor Sprinkler Approval Identification
Orifice Size US Metric Height Organizations Numbers (SIN)
/"(15mm) },"NPT(R/,) 5.6 80 2.2"(56mm) 1,2,3(2),4,5,7 R1715
17/2"(20mm) %"NPT(R3/4) 8.0 115 2.3"(58mm) 1,2,3(2),4,8 R1712
y,"(15mm)141 y"NPT(R/) 5.6 80 2.2"(56mm) 7
17A,"(20mm)141 %"NPT(RX) 8.0 115 2.3"(58mm) 7
/fi'(11mm) y"NPT(R1/2) 4.2 60 2.2"(56mm) 1,2,8 R1713
%"(10mm) X"NPT(RY) 2.8 40 2.2"(56mm) 1,2,8 R1711
10mm R% 4.2 60 56.1mm 4(3),7 R1714
(2)FM Approval
• Light Hazard-No Limitations.
• Ordinary Hazard-Groups 1 &2,Wet Systems only.
(3)LPC Approval is for 57°C through 93°C ratings.
(4)VdS Approval for Intermediate Response 155°F(68°C)only.
3.
Model Fl Vertical Sidewall Sprinkler
Installation Wrench: Model D Sprinkler Wrench
Installation Position: Upright or Pendent
Approval Type: Light Hazard Occupancy
Vertical Sidewall
U.S. Patent No. 6,374,920
Installation Data:
Nominal Sprinkler
Nominal Thread Sprinkler Approval
Orifice Size K Factor Height Organizations Identification
US Metric Numbers(SIN)
, "(15mm) }2"NPT(R}2) 5.6 80 2.2"(56.1mm) 1,2,3,4(1),6,8 R1785
(1)LPC Approval is pendent only,57°C through 141°C ratings.
Sprinkler Deflector to
Type Ceiling Distance
(Min. -Max.)
Upright 4"(102mm)-12"(305mm)
Pendent 4"(102mm)-12"(305mm)
Model Fl Horizontal Sidewall Sprinkler
Deflector: HSW 1
Installation Wrench: Model D Sprinkler Wrench
f/////4
1
:
[5mm-24mm]
ref to • I 1/4"MIN.
[3 L6mml
2 1/4"HOLE DIA. " 4"-6"
[57.2mmi [101.6mm-152.4mm)
[31.2/mm8 ) CEILING TO
1"X 1/2"REDUCER DEFLECTOR
_r1
Horizontal Sidewall / r—
I ,
( t
15/16"DIA.
---
[49.2mmj I - - 2 27/32"DIA.
L III [72.2mm]
TURN COLLAR UNTIL gTIGHT AGAINST SPRINKLER WRENCH BOSS.
tl7FGO34 3/4"[19mm1
ADJUSTMENT
Installation Data:
Nominal Approval Organizations
Nominal Thread K Factor Sprinkler PP g Sprinkler
Identification
Orifice Size Length Light Ordinary Numbers (SIN)
US Metric Hazard Hazard
'/2"(15mm) 1/2"NPT(R'/2) 5.6 80 2.63"(67mm) 1,2,3,5 1,2,5 R1735
Note:UL and ULC Listing permits use with F1 escutcheons,light hazard only.
4.
Model Fl Extended Coverage Pendent Sprinkler
Deflector: EC Pendent
Installation Wrench: Model D Sprinkler Wrench• r..,f
Approval Type: Extended Coverage- Light Hazard Occupancy I _ -
y.
Installation Data:
I Nominal Temperature =y
Nominal Thread Sprinkler Approval perat Sprinkler
Orifice Size K Factor Height Organizations oF Rating o Identification
US Metric C Numbers(SIN)
1%„'(20mm) y"NPT(R3/4) 8.0 115 2.2"(56mm) 1,22 Extended Coverage
,8 135; 155 57;68 R1742
},"(15mm) y"NPT(R1) 5.6 80 2.2"(56mm) 1,2,8 135; 155 57;68 R1745 Pendent
COVERAGE AREA
Pressure
Flow Rate Nominal Max.Area
Width x Length
K=8.0 (115) K=5.6 (80)
gpm L/min psi bar _ psi bar ft.x ft. m x m
26 98.4 10.6 0,7 21.6 1,5 16 x 16 4.9 x 4.9
33 125.0 17.0 1,2 34.7 2,4 18 x 18 5.5 x 5.5
40 151.4 25.0 1,7 51.0 3,5 20 x 20 6.0 x 6.0
Model Fl Recessed Extended Coverage Pendent Sprinkler
Deflector: EC Pendent
Installation Wrench: Model RC1 Sprinkler Wrench 2 I/4-HOLE OM. ..
Approval Type: Extended Coverage - Light Hazard Occupancy (57.2mm]
1 152rmn]/
f49. 16"OM
_ =
rS��+==i, I-X3/4•REDUCER
4 7I (25m.4 rRX ,9.1mm]
TURN COLLAR I I ;'X 1/2'REDUCER
UNTIL TIGHT 1 125.4mm X ;2-7mmf
AGAINST SPRINKLER /-
WRENCH BOSS :-) , 11
, ` 1 riTr7 _ J
"I�4-Y _..0 Y/--1JJ j Was. 75/I6'
0044 J/4'AWSIINN7 (1` I�i (23Bmm]
(,9.,. , _ kid �" i I•
`N' I/8 1 3I4
(3.2mm] 3I9.Imm]
Extended Coverage __ A ._. 1
Recessed
r rMO24 2 27/32"DM.
(72.2m]
"I When instated directly into a tee,the escutcheon
dimension's adjustment will be reduced.
Installation Data:
Nominal Temperature Sprinkler
Nominal Thread Sprinkler Approval
Orifice Size K Factor Height Organizations Rating o Identification
US Metric °F C Numbers(SIN)
1%,"(20mm) X"NPT(R3A) 8.0 115 2.2"(56mm) 1,2,8 135; 155 57;68 R1742
y,"(15mm) y"NPT(R'/z) 5.6 80 2.2"(56mm) 1,2,8 135; 155 57;68 R1745
COVERAGE AREA
Pressure
Nominal Max. Area
! Flow Rate
K=8.0 (115) K=5.6(80) Width x Length
gpm L/min psi bar psi bar ft.x ft. m x m
26 98.4 10.6 0,7 21.6 1,5 16x16 4.9x4.9
33 125.0 17.0 1,2 34.7 2,4 18 x 18 5.5 x 5.5
40 151.4 25.0 1,7 51.0 3,5 20 x 20 6.0 x 6.0
5.
Model Fl Extended Coverage Horizontal Sidewall Sprinkler
Deflector: EC-6
Glass Bulb: 3mm 155°F (68°C) Standard, Unless 5mm 135°F (57°C) is Specified
Installation Wrench: Model D Sprinkler Wrench
Approval Type: Extended Coverage—Light Hazard Occupancy
i _....�a.�.
.�,_ t
Extended Coverage Horizontal Sidewall
Installation Data:
Temperature Sprinkler
Nominal Thread K Factor Sprinkler Approval Rating Identification
Orifice Size US Metric Height Organizations of oC Numbers (SIN)
%%2'(20mm) %"NPT(R3A) 8.0 115.3 2.75"(70mm) 1,2,8 135(5mm bulb) 57 R1762
155(3mm bulb) 68
COVERAGE AREA
Max. Area Deflector to
Flow Rate Pressure Width x Length Ceiling Dimensions
(Min. - Max.)
gpm L/min psi bar ft.x ft. m x m
36 136.3 20.3 1,4 16 x 22 4.9 x 6.7 4"(102mm)-6"(152mm)
39 147.6 23.8 1,6 16x24 4.9x7.3 4"(102mm)-6"(152mm)
'.i
6.
Model Fl Recessed Extended Coverage Horizontal Sidewall Sprinkler
Deflector: EC-6
Glass Bulb: 3mm 155°F (68°C) Only
Installation Wrench: Model GFR1 Sprinkler Wrench
Approval Type: Extended Coverage — Light Hazard Occupancy
7
(13.6mmJ r 4"M 6"
Ot.6mm TO/51Amm)
1 I
TORN UNTIL WIT (IAINST
r" SPRINKLER WRENCH
I -4-1 Boss.
! 15/16•Del., _ _ 1 27/31•DM.
(49.1mm1 1 (72.1mm)
r
Recessed Extended Coverage
Horizontal Sidewall RECOMMENDED k I.:�
WALL HOLE ley Vim-1
3/,6•�
1 1/4"Du n
I.— ---- 3/4'ADJUSTMENT
(r9.1mm)
")When instated directly into a tee,the escutcheon dimension's
adjustment will be reduced.
Installation Data:
Temperature Sprinkler
Nominal Thread K Factor Sprinkler Approval Rating Identification
Orifice Size US Metric Height Organizations of oC Numbers (SIN)
1/32"(20mm) 3/4"NPT(R3/a) 8.0 115.3 2.75"(70mm) 1,2,8 155 68 R1762
COVERAGE AREA
Max. Area Deflector to Ceiling
Flow Rate Pressure Width x Length Dimensions
(Min. - Max.)
gpm L/min psi bar ft.x ft. m x m
36 136.3 20.3 1,4 16 x 22 4.9 x 6,7 4"(102mm)-6"(152mm)
39 147.6 23.8 1,6 16 x 24 4.9 x 7.3 4"(102mm)-6"(152mm)
7.
w,
Model F1 & F1 Recessed Sprinklers Maintenance
Application The Models F1 and Fl Recessed Sprinklers should
Model F1 and F1 Recessed sprinklers are used in fixed be inspected quarterly and the sprinkler system main
fire protection systems: Wet, Dry, Deluge or Preaction. tained in accordance with NFPA 25. Do not clean sprin
Care must exercised that the orifice size, temperature rat- klers with soap and water, ammonia or any other
ing, deflector style and sprinkler type are in accordance cleaning fluid. Remove any sprinkler which has been
with the latest published standards of the National Fire Pro- painted(other than factory applied)or damaged in any
tection Association or the approving Authority Having way. A stock of spare sprinklers should be maintained
Jurisdiction. to allow quick replacement of damaged or operated
sprinklers. Prior to installation, sprinklers should be
Installation maintained in the original cartons and packaging until
Model F1 sprinklers are standard response sprinklers in- used to minimize the potential for damage to sprinklers
tended for installation as specified in NFPA 13. They must that would cause improper operation or non-operation.
also be installed with the Model D Sprinkler Wrench specifi-
cally designed by Reliable for use with these sprinklers.
The Model Fl Recessed Sprinklers are to be installed Temperature Ratings
with a maximum recess of 3/4 inch (19mm). The Model Fl Sprinkler Maximum Ambient
Escutcheon illustrated is the only recessed escutcheon to Classification Temperature Temperature Bulb
be used with the Model Fl Pendent and EC Sprinklers.The °F °c °F °c Color
use of any other recessed escutcheon will void all approv- Ordinary 135 57 100 38 Orange
als and negate all warranties.When installing Model Fl Re- Ordinary 155 68 100 38 Red
cessed Pendent,EC Pendent,and EC HSW Sprinklers,use Intermediate 175 79 150 66 Yellow
the Model GFR1 Sprinkler Wrench. Any other type of Intermediate 2
wrench maydamage these sprinklers. High (1) 360006 18193 150 66 Green
300 149 Blue
g p Extra High 360 182 300 149 Mauve
Glass bulb sprinklers have orange covers to protect the
bulb during the installation process. REMOVE THIS PRO- "'Not Available For F1 Recessed
TECTION ONLY AFTER THE SYSTEM HAS BEEN HYDRO- Patents: U.S. Patent No. 6,374,920
STATICALLY TESTED AND, WHEN APPLICABLE, THE Applies to Model Fl Vertical Sidewall Sprinklers.
ESCUTCHEONS HAVE BEEN INSTALLED. RASCO
wrenches are designed to install sprinklers when covers are Finishes (1)
in place.
Standard Finishes
Sprinkler Escutcheon
Bronze Brass
Chrome Chrome
Ordering Information White Polyester Coated') White Painted
Specify: Special Application Finishes
1. Sprinkler Model Sprinkler Escutcheon
2. Sprinkler Type Bright Brass'2"6' Bright Brass
Black Plated(5) Black Plated
3. Orifice Size Black Paint(3)(5) Black Paint
4. Deflector Type Off White(3"6' Off White
Satin Chrome Satin Chrome
5.Temperature Rating: Lead Plated(3'")
Wax Coated(3)('''')
Specify Bulb Size when ordering Wax Over Lead(3"5"5)
Model F1 EC HSW Sprinkler.
"
6. Sprinkler Finish (')Other colors and finishes are available on special order.
Consult factory for details.
7. Escutcheon Finish (where applicable) (2)200°F(93°C)maximum.
(3)UL and ULC Listed,and NYC Approved Only.
(4)155°F to 200°F(68°C to 93°C)ratings only.
(5)286°F(141°C)Sprinklers may be coated for ambient conditions
not exceeding 150°F(66°C).
`a'LPC approved for 10mm and 15mm sprinklers only.
The equipment presented in this bulletin is to be installed in accordance with the latest pertinent Standards of the National Fire Protection Association,Fac-
tory Mutual Research Corporation,or other similar organizations and also with the provisions of governmental codes or ordinances whenever applicable.
Products manufactured and distributed by Reliable have been protecting life and property for over 80 years,and are installed and serviced by the most highly
qualified and reputable sprinkler contractors located throughout the United States,Canada and foreign countries
Manufactured by
IIIIIIIIIIMINIIIMMININIMMINIMI The Reliable Automatic Sprinkler Co.,Inc. cled
ReIiabIi (800) 431-1588Sales Offices ® Recycled
Paper
(800) 848-6051 Sales Fax Revision lines indicate updated or new data.
(914) 668-3470 Corporate Offices
www,reliablesprinkler.com Internet Address EG printed in USA. 5/05 P/N 9999970011
Bulletin 117Rev.R
,�Reliabido Model Fl co
(15_
Model F1 Recessed
Standard Response
Sprinklers DJ
The Designer®Model Fl Sprinkler
Standard Upright RECEIVED
Standard Pendent .
Extended Coverage Pendent , .� :� t
Conventional SEP i K T` I
Vertical Sidewall CITY OF TIGARD `-
Horizontal Sidewall Upright Pendent
-HSW 1 Deflector 3UILDING DIVISION
Horizontal Sidewall Extended Coverage
-EC-6 Deflectortt fill
The Des' ner®II Model Fl Recessed Sprinkler
�9p
Recessed Pendent
Recessed Extended Coverage Pendent
Recessed Extended Coverage Horizontal Sidewal Vertical Sidewall Conventional
Approval Organizations , <3
R 1. Underwriters Laboratories Inc. filo,
2. Underwriters' Laboratories of Canada
3. FactoryMutual Research Corp. '� ' .
P
4. Loss Prevention Council - ',
5. NYC BS&A No. 587-75-SA Horizontal Sidewall Recessed Pendent
6. Pleniere Assemblee
7. Verband der Schadenversicherer
8. NYC MEA 258-93-E .. . '
UL Listing Category "' "
Sprinklers, Automatic& Open (VNIV) 11. 4TdV
Patents: US Patent No. 6,374,920 Applies to
Model F1 Vertical Sidewall Sprinklers Extended Coverage Recessed Extended
Horizontal Sidewall Coverage Horizontal
Product Description Sidewall
The Fl Glass Bulb Sprinkler combines the durability of a
standard sprinkler with the attractive low profile of a decora- ;... ..
tive sprinkler.Whether installed on exposed piping or in an te , ,
office ceiling, it is functional and attractive. The Horizontal 4..
and Vertical Sidewall Sprinklers provide an equally attractive
appearance when ceiling piping cannot be used. ., • '-_
Beautifully versatile is the description for the Reliable Model Extended Coverage Recessed Extended
F1 Recessed Designer glass bulb sprinkler. Recessing The Pendent Coverage Pendent
Designer enhances its already low profile decorative appear-
ance, and facilitates a rapid and perfect installation. At normal temperatures,the glass bulb contains the fluid
Model Fl Recessed Designer's escutcheon is highly ad- in both the liquid phase and in the vapor phase.The vapor
justable.The two piece construction makes field installation a phase can be seen as a small bubble.As heat is applied,the
very easy and rapid task.This also allows ceiling panels to later liquid expands forcing the bubble smaller and smaller as the
be removed without shutting down the fire protection system, liquid pressure increases. Continued heating forces the liq-
thus facilitating maintenance of above ceiling services. uid to push out against the bulb,causing the glass to shatter,
The Designer® Automatic Sprinkler utilizes a frangible opening the waterway and allowing the deflector to distribute
glass bulb. The glass bulb consists of an accurately con- the discharging water.
trolled amount of special fluid hermetically sealed inside of a The F1 Sprinkler temperature rating is identified by the
precisely manufactured glass capsule. This glass bulb is color of the glass bulb capsule as well as frame color where
specially constructed to provide fast thermal response. applicable.
The Reliable Automatic Sprinkler Co.,Inc., 525 North MacQuesten Parkway,Mount Vernon, New York 10552
Model Fl Upright, Pendent & Conventional Sprinklers
Installation Wrench: Model D Sprinkler Wrench
Upright Pendent Conventional
Installation Data:
Nominal Sprinkler
Nominal Thread Sprinkler Approval Identification
` Orifice Size K Factor Height Organization Numbers(SIN)
US Metric Upright Pendent
Standard-Upright(SSU)and Pendent(SSP)Deflectors Marked to Indicate Position
' "(15mm) Y"NPT(R1/2) 5.6 80 2.2"(56mm) 1,2,3,4,5,6,7 R1725 R1715
'%2'(20mm) 3/4"NPT(R3/4)I') 8.0 115 2.3"(58mm) 1,2,3,4,7,8 R1722 R1712
/2"(15mm)(3) 1/2"NPT(R'h) 5.6 80 2.2"(56mm) 7
17/32"(20mm)(3) 3/4"NPT(R3/4) 8.0 115 2.3"(58mm) 7
'/s'(11mm) 1"NPT(RY) 4.2 60 2.2"(56mm) 1,2,8 R1723 R1713
Y8"(10mm) Y"NPT(R'/)(2) 2.8 40 2.54"(65mm) 1,2,8 R1721 R1711
10mm XLH R% 4.2 60 56.1mm 4,6,7 R1724 R1714
Conventional-Install in Upright or Pendent Position
10mmXLH R% 4.2 60 56.1mm R1774
15mm 1/2"NPT(RY) 5.6 80 56.1mm 4,6,7 R1775
20mm 3/4"NPT(R3A4) 8.0 115 58.1mm 4,7 R1772
(')LPC Approval up 286°F(141°C)
(2)FM Approval for SSU up to and including 200°F(93°C)only.
(3)VdS Approval for Intermediate Response 155°F(68°C)only.
3t
2.
Model Fl Recessed Pendent Sprinkler
Installation Wrench: Model RC1 Sprinkler Wrench
_ 2 lie HOLE p0.
r57.2mmJ
- / 15/16•p4--
(47.2mmq
(--
rr = ei1
s-x"^'A"*^+*• TURN MIA' IT
L ,•X I/2'DEDUCED
r16.Imm X 12.7rong
I'/
UNIX m+r I
1 sac n 1- � illr77Xv7 L _ -- _I
A; "wi617n_W
11hll '
Fl Recessed ' // , t
f 2 J 1:[25.4mm]
t!
1I77D0IA 1 27/32'DM.
(7a1mmJ
(1)When instated directly into a tee,the escutcheon dimension's
adjustment will be reduced.
1
Installation Data:
Nominal Sprinkler
Nominal Thread Sprinkler Approval
Orifice Size K Factor_ Height Organizations Identification
US Metric Numbers(SIN)
X"(15mm) y,"NPT(R/,) 5.6 —__ 80 2.2"(56mm) 1,2,3(2),4,5,7 R1715
1X,"(20mm) y4"NPT(R3/,) 8.0 115 2.3"(58mm) 1,2,3( ,4,8 R1712
y,"(15mm)(4) y,"NPT(RX) 5.6 80 2.2"(56mm) 7
17X2"(20mm)(4) y,"NPT(R3y,) 8.0 115 2.3"(58mm) 7
%fi'(11mm) y,"NPT(R1/) 4.2 60 2.2"(56mm) 1,2,8 R1713
("(10mm) y"NPT(R1h) 2.8 40 2.2"(56mm) 1,2,8 R1711
10mm R% 4.2 60 56.1mm 4(3),7 R1714
(2)FM Approval
• Light Hazard—No Limitations.
• Ordinary Hazard—Groups 1 &2,Wet Systems only.
(3)LPC Approval is for 57°C through 93°C ratings.
(4)VdS Approval for Intermediate Response 155°F(68°C)only.
3.
Model Fl Vertical Sidewall Sprinkler
Installation Wrench: Model D Sprinkler Wrench
Installation Position: Upright or Pendent
Approval Type: Light Hazard Occupancy
1
Vertical Sidewall
U.S. Patent No. 6,374,920
Installation Data:
Nominal Sprinkler
Nominal Thread Sprinkler Approval
Orifice Size K Factor Height Organizations Identification
US Metric Numbers(SIN)
y"(15mm) J2"NPT(Ry) 5.6 80 2.2"(56.1mm) 1,2,3,4(1),6,8 R1785
(1)LPC Approval is pendent only,57°C through 141°C ratings.
Sprinkler Deflector to
Type Ceiling Distance
(Min. -Max.)
Upright 4"(102mm)-12'(305mm)
Pendent 4"(102mm)-12"(305mm)
Model Fl Horizontal Sidewall Sprinkler
Deflector: HSW 1
Installation Wrench: Model D Sprinkler Wrench
01 Per, A
, ,<:
... [Smm-24mm]
t 1 1/4"MIN.
11 [31.8mm]
•f 2 1/4"HOLE DIA. 4"-6"
[57.2mmJ [372mm] [101.6mm-152. mm]
CEING TO
1"X 1/2"REDUCER DEFLECTOR
Horizontal Sidewall r�r4 I 1
1 15/16"D/A.
[49.2mm] -- 2 27/32"DG9.
I ■- -
I rim [72.2mm]
TURN COLLAR UNTIL
TIGHT AGAINST SPRINKLER
WRENCH BOSS.
---."1 Lo-i17fGG34 3/4"[19mm]
ADJUSTMENT
Installation Data:
Nominal Approval Organizations Sprinkler
Nominal Thread K Factor Sprinkler
Identification
Orifice Size Length Light Ordinary NumbumberssI
US Metric Hazard Hazard (SIN)
1/2"(15mm) 1"NPT(R1/2) 5.6 80 2.63"(67mm) 1,2,3,5 1,2,5 R1735
Note:UL and ULC Listing permits use with F1 escutcheons,light hazard only.
4.
Model Fl Extended Coverage Pendent Sprinkler
Deflector: EC Pendent
Installation Wrench: Model D Sprinkler Wrench r> ].•
Approval Type: Extended Coverage- Light Hazard Occupancy '
1 Installation Data:
Nominal Thread Nominal Sprinkler A royal Temperature Sprinkler
Orifice Size K Factor Height Organ zations Rating Identification
US Metric °F °C Numbers(SIN)
e C Coverage
1%;'(20mm) %"NPT(WA) 8.0 115 2.2"(56mm) 1,2,8 135; 155 57;68 R1742 Extendedg
};"(15mm) y"NPT(R1/2) 5.6 80 2.2"(56mm) 1,2,8 135; 155 57;68 R1745 Pendent
I
COVERAGE AREA
Pressure
Flow Rate Nominal Max. Area
K=8.0(115) K=5.6(80) Width x Length
gpm , L/min psi . bar psi bar ft.x ft. m x m
26 98.4 10.6 0,7 21.6 1,5 16x16 4.9x4.9
33 125.0 17.0 1,2 34.7 2,4 18 x 18 5.5 x 5.5
40 151.4 25.0 1,7 51.0 3,5 20 x 20 6.0 x 6.0
Model Fl Recessed Extended Coverage Pendent Sprinkler
Deflector: EC Pendent
Installation Wrench: Model RC1 Sprinkler Wrench 21/+-ROLE DM.
Approval Type: Extended Coverage - Light Hazard Occupancy [57.
2"'4
[1ts.2mm)15/16•DM----
L- =a
S-��+mci
r 1 f'X J/I•REDUCER
4 [25.4mmoRX 19.1mm]
TURN COLLAR I I••X 1/2 REDUCER
UN1 71CM7 /�125.4mm X 127mm)
WENCH 1� lI- I 1
U7P 7 L_ J
a � 1'/�i J�71�raW L -2 15I
3/4•ADJUSTMENT !11 cull [23.emm]
[f9,Im] _jIii�I.III
VW '/13, 1 Jt
Extended Coverage _- - [i2mm) [`"mm)
Recessed 2 27/32•DM.
117FD02A
[72.2mm]
"'When installed directly into a tee,the escutcheon
dimension's adjustment will be reduced.
Installation Data:
Nominal Temperature Sprinkler
Nominal Thread Sprinkler Approval
K Factor Rating Identification
Orifice Size US Metric Height Organizations °F °C Numbers(SIN)
17/;'(20mm) X"NPT(R3/4) 8.0 115 2.2"(56mm) 1,2,8 135; 155 , 57;68 R1742
};"(15mm) y"NPT(R1) 5.6 80 2.2"(56mm) 1,2,8 135; 155 57;68 R1745
COVERAGE AREA
Pressure
Flow Rate Nominal Max. Area
Width x Length
K=8.0(115) K=5.6(80)
qpm L/min psi bar psi bar ft.x ft. m x m
26 98.4 10.6 0,7 21.6 1,5 16x 16 4.9 x 4.9
33 125.0 17.0 1,2 34.7 2,4 18 x 18 5.5 x 5.5
40 151.4 25.0 1,7 51.0 3,5 20 x 20 6.0 x 6.0
5.
Model Fl Extended Coverage Horizontal Sidewall Sprinkler
Deflector: EC-6
Glass Bulb: 3mm 155°F (68°C) Standard, Unless 5mm 135°F (57°C) is Specified
Installation Wrench: Model D Sprinkler Wrench
Approval Type: Extended Coverage—Light Hazard Occupancy
Extended Coverage Horizontal Sidewall
Installation Data:
Temperature Sprinkler
Nominal Thread K Factor Sprinkler Approval Rating Identification
Orifice Size US Metric Height Organizations of oC Numbers(SIN)
1%2"(20mm) ,;"NPT(R3/4) 8.0 115.3 2.75"(70mm) 1,2,8 135(5mm bulb) 57 R1762
155(3mm bulb) 68
COVERAGE AREA
Max. Area Deflector to
Flow Rate Pressure Width x Length Ceiling Dimensions
(Min. -Max.)
gpm L/min psi bar ft.x ft. m x m
36 136.3 20.3 1,4 16x22 4.9x6.7 4"(102mm)-6"(152mm)
39 147.6 23.8 1,6 16 x 24 4.9 x 7.3 4"(102mm)-6"(152mm)
6.
•
Model Fl Recessed Extended Coverage Horizontal Sidewall Sprinkler
Deflector: EC-6
Glass Bulb: 3mm 155°F (68°C) Only
Installation Wrench: Model GFR1 Sprinkler Wrench
Approval Type: Extended Coverage— Light Hazard Occupancy
I17FGo3 \X\\\\ ' .
\
15/16" I/6"(3.2nunj
(23.6mmJ 9"TV 6'
,&,..:: (POI.6mm 7o 7521mmJ
_ TURN SPRING COLLAR
°
UNTIL TIGHT AGAINST
-
Ti�� �'`" $gUP NLER WRENCH
! 2 7/32"DIA
�
1 (72.2mm1
/4$ [49.1mm] I
Recessed Extended Coverage �;�
Horizontal Sidewall RECOMMENDED
C��EED \I _,LH
L_
57 2mmLJ ( /6-r
(1)
3/4•ADJUSTMENT
09.ImmJ
`11 When installed directly into a tee,the escutcheon dimension's
adjustment will be reduced.
Installation Data:
Temperature Sprinkler
Nominal Thread K Factor Sprinkler Approval Rating Identification
Orifice Size US Metric Height Organizations of oC Numbers(SIN)
1%2I(20mm) 3/4"NPT(R3/4) 8.0 115.3 2.75"(70mm) 1,2,8 155 68 R1762
COVERAGE AREA
Max.Area Deflector to Ceiling
Flow Rate Pressure Width x Length Dimensions
(Min. -Max.)
gpm L/min psi bar ft.x ft. m x m
36 136.3 20.3 1,4 16 x 22 4.9 x 6.7 4"(102mm)-6"(152mm)
39 147.6 23.8 1,6 16 x 24 4.9 x 7.3 4"(102mm)-6"(152mm)
7.
v W
IINIIIIIIIIMIIIIIIIIIIIIIIISIWI
Model Fl & Fl Recessed Sprinklers Maintenance
Application The Models F1 and F1 Recessed Sprinklers should
Model F1 and F1 Recessed sprinklers are used in fixed be inspected quarterly and the sprinkler system main
fire protection systems: Wet, Dry, Deluge or Preaction. tained in accordance with NFPA 25. Do not clean sprin-
klersCare must exercised that the orifice size, temperature rat-
ing, deflector style and sprinkler type are in accordance cleaning fluid. Remove any sprinkler which has been
with the latest published standards of the National Fire Pro- painted(other than factory applied)or damaged in any
tection Association or the approving Authority Having way. A stock of spare sprinklers should be maintained
Jurisdiction. to allow quick replacement of damaged or operated
sprinklers. Prior to installation, sprinklers should be
Installation maintained in the original cartons and packaging until
Model F1 sprinklers are standard response sprinklers in- used to minimize the potential for damage to sprinklers
tended for installation as specified in NFPA 13. They must that would cause improper operation or non-operation.
also be installed with the Model D Sprinkler Wrench specifi-
cally designed by Reliable for use with these sprinklers.
The Model F1 Recessed Sprinklers are to be installed Temperature Ratings
with a maximum recess of 3/4 inch (19mm). The Model F1 Sprinkler Maximum Ambient
Escutcheon illustrated is the only recessed escutcheon to Classification Temperature Temperature Bulb
be used with the Model F1 Pendent and EC Sprinklers.The °F °c °F °C Color
use of any other recessed escutcheon will void all approv- Ordinary 135 57 100 38 Orange
als and negate all warranties.When installing Model F1 Re- Ordinary 155 68 100 38 Red
cessed Pendent,EC Pendent,and EC HSW Sprinklers,use Intermediate 175 79 150 66 Yellow
the Model GFR1 Sprinkler Wrench. Any other type of Interm�diate 200 931 150 66 Green
wrench maydamage these sprinklers. High ( ) 360 182 300 149 Blue
g p Extra High 360 182 300 149 Mauve
Glass bulb sprinklers have orange covers to protect the
bulb during the installation process. REMOVE THIS PRO- "'Not Available For F1 Recessed
TECTION ONLY AFTER THE SYSTEM HAS BEEN HYDRO- Patents: U.S. Patent No. 6,374,920
STATICALLY TESTED AND, WHEN APPLICABLE, THE Applies to Model Fl Vertical Sidewall Sprinklers.
ESCUTCHEONS HAVE BEEN INSTALLED. RASCO
wrenches are designed to install sprinklers when covers are Finishes ")
in place. Standard Finishes
Sprinkler Escutcheon
Bronze Brass
Chrome Chrome
Ordering Information White Polyester Coatedd') White Painted
Specify: Special Application Finishes
1. Sprinkler Model Sprinkler Escutcheon
2. Sprinkler Type Bright Brass`2"6) Bright Brass
Black Plated`6) Black Plated
3. Orifice Size Black Paint"m6) Black Paint
4. Deflector Type Off White""' ' Off White
Satin Chrome Satin Chrome
5.Temperature Rating: Lead Plated`3""'
Wax Coated"")(')
Specify Bulb Size when ordering Wax Over Lead""""s'
Model F1 EC HSW Sprinkler.
6. Sprinkler Finish "'Other colors and finishes are available on special order.
p Consult factory for details.
7. Escutcheon Finish (where applicable) `2'200°F(93°C)maximum.
"'UL and ULC Listed,and NYC Approved Only.
`")155°F to 200°F(68°C to 93°C)ratings only.
l')286°F(141°C)Sprinklers may be coated for ambient conditions
not exceeding 150°F(66°C).
"'LPC approved for 10mm and 15mm sprinklers only.
The equipment presented in this bulletin is to be installed in accordance with the latest pertinent Standards of the National Fire Protection Association,Fac-
tory Mutual Research Corporation,or other similar organizations and also with the provisions of governmental codes or ordinances whenever applicable.
Products manufactured and distributed by Reliable have been protecting life and property for over 80 years,and are installed and serviced by the most highly
qualified and reputable sprinkler contractors located throughout the United States,Canada and foreign countries
Manufactured by
11.111.111111111191.110111111.11111.1.11.11 The Reliable Automatic Sprinkler Co.,Inc. Recycled
�'���'� (800) 66 —1588 Sales Offices ® Paper
(800) 848-6051 Sales Fax Revision lines indicate updated or new data.
(914) 668�470 Corporate Offices
www.reliablesprinkier.com Internet Address EG printed in USA. 5/05 P/N 9999970011