Loading...
Report OFFICE COPY fPSZoz.f- rx"/.5" FireLock® V27, K5.6 RECEIVED ✓ctaulic. Models V2703, V2707, V2704, V2708 CEP 2 0 iOL 40.10 • CITY OF TIGARD • 3UILDING DIVISION • V2703/V2704 V2707/V2708 V2707/V2708 V2707/V2708 V2703/V2704 Upright Pendent Recessed Pendent Pendent w/V9 Upright w/V9 1.0 PRODUCT DESCRIPTION ��/I� Models: V2703, V2704, V2707, V2708 l/3 0 0 lvf7`4 P k k 7 Style: Pendent, Upright or Recessed Pendent Nominal Orifice Size: 1/2713 mm K Factor: 5.6 Imp./8.1 S.I.1 Nominal Connection Size: 1/2" NPT/20 mm BSPT/IGS Grooved Max. Working Pressure: • 175 psi/1200 kPa (FM) • 250 psi/1725 kPa (UL) Factory Hydrostatic Test: 100% @ 500 psi/3450 kPa Min. Operating Pressure: • 7 psi/48 kPa • 0.35 bar/5 psi (VdS for upright only) Temperature Rating: See chart For K-Factor when pressure is measured in Bar,multiply S.I.units by 10.0. 2.0 CERTIFICATION/LISTINGS C vas C E LISTED ®TED LP CB. CD 0786 Threaded and IGS connections have different approvals/listings. See tables on pages 2 and 3. ALWAYS REFER TO ANY NOTIFICATIONS AT THE END OF THIS DOCUMENT REGARDING PRODUCT INSTALLATION,MAINTENANCE OR SUPPORT. • System No. Location Spec Section Paragraph Submitted By Date Approved Date L • victaulic.com • 40.10 2544 Rev L Updated 04/2020 ©2020 Victaulic Company.All rights reserved. 1 ictaUlic'' victaulic.com , 2.0 CERTIFICATION/LISTINGS (CONTINUED) Threaded Sprinkler Approvals/Listings: APPROVALS/LISTINGS Model V2703 V2707 V2707 V2704 V2708__ V27083 Orifice Size(inches) th° 1/2° 1/2. 1/2" 1/2" 1h° Orifice Size(mm) 13 13 13 13 13 13 Nominal K Factor Imperial 5.6 5.6 5.6 5.6 5.6 5.6 Nominal K Factor S.I.2 8.1 8.1 8.1 8.1 8.1 8.1 Response Standard Standard Standard Quick Quick Quick Deflector Type Upright Pendent Recessed Upright Pendent Recessed Pendent Pendent Approved Temperature Ratings P/C° 135°F/57°C 135°F/57°C 155°F/68°C 155"F/68°C 135°F/57°C 135°F/57°C 135°F/57°C 135°F/57°C 175"F179°C 175°F/79°C 155°F/68°C 155°F/68°C 155°F/68°C 155°F/68°C cULus 200°F/93°C 200°F/93°C 175°F/79°C 175°F/79°C 175°F/79°C 175°F/79°C 286°F/141°C 286°F/141°C 200°F/93°C 200°F/93°C 200°F/93°C 200"F/93°C 360°F/182°C 360°F/182°C 286°F/141°C 286°F/141°C 286°F/141°C ,. , 500°F/260°C 500°F/260°C 135°F/57°C 135"F/57°C 135"F/57°C 135°F/57°C 155°F/68°C 155°F/68°C 135°F/57°C 155°F/68°C 155"F/68°C 135°F/57°C FM 175°F/79°C 175°F/79°C 155°F/68°C 175°F/79°C 175°F/79°C 155°F/68°C 200°F/93°C 200°F/93°C 175°F/79°C 200"F/93°C 200°F/93°C 175°F/79°C 286°F/141°C 286°F/141°C 200"F/93°C 286°F/141°C 286°F/141°C 200°F/93°C 360°F/182°C 360"F/182°C 135°F/57°C 135"F/57°C 135°F/57°C 135"F/57°C 135°F/57°C 155°F/68°C 155"F/68°C 135°F/57°C 155°F/68°C 155"F/68°C 155°F/68°C 175°F/79°C 175°F/79°C 155°F/68°C NYC/MEA 62-99-E 200"F/93°C 200°F/93°C 175°F/79°C 175°F/79°C 175°F/79°C 175°F/79°C 286°F/141°C 286°F/141°C 200°F/93°C 200"F/93°C 200°F/93°C 200°F/93°C 360°F/182°C 360"F/182°C 286°F/141°C 286°F/141°C 286°F/141°C 135°F/57°C 135°F/57°C 135°F/57°C 135°F/57°C 135°F/57°C 155°F/68°C 155"F/68°C 155°F/68°C 155°F/68°C 155°F/68°C 135°F/57°C CSFM 7690-0531:112 175°F/79°C 175°Fl79°C 175"F/79°C 175°F/79°C 175"F/79°C 155°F/68°C 200"F/93°C 200°F/93°C 200°F/93°C 200°F/93°C 200°F/93°C 175°F/79°C 286°F/141°C 286°F/141°C 286°F/141°C 286°F/141°C j 286°F/141°C 200°F/93°C 360°F/182°C 360°F/182°C 135°F/57°C 155°F/68°C 135°F/57°C LPCB 175°F/79°C None None 155°F/68°C None None 200°F/93°C 175"F/79°C 286"F/141°C 200°F/93°C 360°F/182°C ZSTZ ZSTX K-ZSTZ K-ZSTZ CCC 155°F/68°C 155°F/68°C None 155°F/68°C 155°F/68°C None 200°F/93°C 200°F/93°C 200°F/93°C 200°F/93°C 135°F/57°C 155°F/68°C 135°F/57°C 175°F/79°C 155°F/68°C Vds 200°F/93°C None None 175°F/79°C None None 200°F/93°C 286°F/141°C 360"F/182°C 286°F/141°C 0 F 135°F/57°C 135°F/57°C 155°F/68°C 155°F/68°C CE 175°F/79°C None None 175°F/79°C None None 200"F/93°C 200°F/93°C 286°F/141°C 286°F/141°C • 360°F/182°C r 2 For K Factor when pressure is measured in Bar,multiply S.I.units by 10.0 3 FM Approved with 1/"adjustment escutcheon only-quick response NOTE • Listings and Approvals as of printing.All are approved open. • •40.10 2544 Rev L Updated 04/2020 ©2020 Victaulic Company.All rights reserved. victaulic.com 2 , ✓ctsiulia if victaulic.com • • 2.0 CERTIFICATION/LISTINGS (CONTINUED) IGS Sprinkler Approvals/Listings APPROVALS/LISTINGS I Model ! I V2703 V2707 V2704 V2708 ( Orifice Size(inches) 'h" '/I" 'h" 'h" _Orifice Size(mm) 13 13 13 13 Nominal K-Factor Imperial 5.6 5.6 5.6 5.6 Nominal K-Factor 5.1.2 8.1 8.1 8.1 8.1 Response Standard Standard Quick Quick Deflector Type Upright Pendent Upright Pendent Adjustment Approved Temperature Ratings F"/C• 135°F/57°C 135°F/57°C 155°F/68°C 155°F/68°C 135°F/57°C 135°F/57°C 175°F/79°C 175°F/79°C 155°F/68°C 155°F/68°C cULus 200°F/93°C 200°F/93°C 175°F/79°C 175°F/79°C 286°F/141°C 286°F/141°C 200°F/93°C 200°F/93°C 360°F/182°C 360°F/182°C 286°F/141°C 286°F/141°C 500°F/260°C 500°F/260°C 135°F/57°C 135°F/57°C 135°F/57°C 135°F/57°C 155°F/68°C 155°F/68°C 155°F/68°C 155°F/68°C 175°F/79°C 175°F/79°C FM 175°F/79°C 175°F/79°C 200°F/93°C 200°F/93°C 200°F/93°C 200°F/93°C 286°F/141°C 286°F/141°C 286°F/141°C 286°F/141°C 360°F/182°C 360°F/182°C 2 For K-Factor when pressure is measured in bar,multiply S.I.units by 10.0 NOTE • Listings and Approvals as of printing.All are approved open. • • 40.10 2544 Rev L Updated 04/2020 ©2020 Victaulic Company.All rights reserved. victaulic.com 3 ✓ctaulic victaulic.com . . 3.0 SPECIFICATIONS — MATERIAL Upright Deflector: Bronze Pendent Deflector: Bronze Bulb: Glass with glycerin solution Bulb Nominal Diameter: Li Standard: 5.0 mm ❑ Quick Response: 3.0 mm Load Screw: Bronze Pip Cap: Bronze Spring: Beryllium nickel Seal: PTFE tape Frame: Die cast brass Lodgement Spring: Stainless steel Installation Wrench: ❑ Open End: V27 Li Recessed: V27-2 ❑ 3/16 Hex Bit: V9 coupling Sprinkler Finishes: ❑ Plain Brass4 ❑ Chrome plated ❑ White polyester coated5 ❑ Black painted5 ❑ Custom painted5 ❑ VC-2506 4 Plain Brass is only available for the V9 coupling. 5 UL Listed for corrosion resistance. 6 UL Listed and FM Approved for corrosion resistance. U alt . 1,k, UP Exaggerated for clarity . . 40.10 2544 Rev L Updated 04/2020 ©2020 Victaulic Company.All rights reserved. victaulic.com 4 ctaulac° , victaulic.com . _ _ __ . _ 4.0 DIMENSIONS I I f l'/1d'/ I I 37 mm immt Two ur23/a"/ _0 60 mm 1s/s"/ 15/87 41 mm _ 23/s"/ 41 mmpi 60mm Mil = 1"/ I I 25mm I i Standard Pendent with/without standard V9 coupling—V2707,V2708 Standard Upright with/without standard V9 coupling—V2703,V2704 NOTE: • V27,K5.6 sprinklers with Style V9 coupling dimensions are the same as threaded sprinkler dimensions. 23/a"/60 mm Max.Hole —' 2"/51 mm f Min.Hole 17 mm ��I� I�� Typical C�fling Tile IZ�I.010 ` tl1�30 m } I f 111/16'/ 13/16/ 43 mm 01"1 Finished Surface a 30 m •— MAXIMUM RECESS 215/,67 75mm MAXIMUM EXTENSION '/z"Adjustment Recessed—V2707,V2708(drawing not to scale) 23/4"/60 mm Max.Hole 2"/51 mm Min.Hole Il�ilill 1 "/ 6�6"' •�j �1•�24 mm 18 mm M�m• �I�� Typical Ceiling Tile �� ® �� 3m f f f �`�'� Qy/� 15�6�/roll 1IJ Finished Surface 24 mm .' MAXIMUM RECESS 2171 / _ 75mm MAXIMUM EXTENSION 3/4"Adjustment Recessed—V2707,V2708(drawing not to scale) 011111M111 iff.44 —irjara- Oi l iJ liNli i , t !IMMO Standard Pendent with V9 Sprinkler Coupling—V2707,V2708 Standard Upright with V9 Sprinkler Coupling—V2703,V2704 NOTE: • IGS options are not available for recessed applications. • • 40.10 2544 Rev L Updated 04/2020 ©2020 Victaulic Company.All rights reserved. victaulic.com 5 ✓ataulic' victaulic.com 5.0 PERFORMANCE Sprinkler is to be installed and designed as per NFPA, FM Datasheets, or any local standards. 6.0 NOTIFICATIONS A WARNING • Always read and understand installation,care, and maintenance instructions, supplied with each box of sprinklers, before proceeding with installation of any sprinklers. WIT" • Always wear safety glasses and foot protection. • Depressurize and drain the piping system before attempting to install, remove, or adjust any Victaulic piping products. • Installation rules, especially those governing obstruction, must be strictly followed. • Painting, plating,or any re-coating of sprinklers (other than that supplied by Victaulic) is not allowed. Failure to follow these instructions could result in serious personal injury and/or property damage. The owner is responsible for maintaining the fire protection system and devices in proper operating condition. For minimum maintenance and inspection requirements, refer to the current National Fire Protection Association pamphlet that describes care and maintenance of sprinkler systems. In addition,the authority having jurisdiction may have additional maintenance,testing,and inspection requirements that must be followed. If you need additional copies of this publication, or if you have any questions about the safe installation of this product, contact Victaulic World Headquarters: P.O. Box 31, Easton, Pennsylvania 18044-0031 USA, Telephone: 001-610-559-3300. • • 40.10 2544 Rev L Updated 04/2020 ©2020 Victaulic Company.All rights reserved. victaulic.com 6 ✓ataulac victaulic.com • • 7.0 REFERENCE MATERIALS Ratings All glass bulbs are rated for temperatures from -65°F/-54°C to those shown in table below. Temperature— F/C Maximum Sprinkler Victaulic Nominal Ambient Glass Temperature Part Temperature Temperature Bulb Classification Identification Rating Allowed Color I Ordinary A 135 F/57 C 100 F/38 C Orange Ordinary C 155 F/68 C 100 F/38 C Red Intermediate i E 175 F/79 C 150 F/65 C i Yellow . Intermediate F 200 F/93 C 150 F/65 C Green I High J 286 F/141 C 225 F8/107 C Blue Extra High' K 360 F/182 C 300 F/149 C Purple — M Open — No bulb Ultra High' N 500 F/260 C 475 F/246 C Black • ' Standard response only. Available Wrenches: V27-2 V27 Sprinkler Type Recessed Open End Hex-Bit , V2707,V2708 Pendent I / 1 / V2707,V2708 Recessed Pendent / I — — V2703,V2704Upright ✓ ' V2703,V2704 Upright wN9 — I — / I V2707,V2708 Pendent wN9 I — — / NOTE • 3/1e-inch hex bit provided with V9 coupling shipment. 29.01:Victaulic Terms and Conditions of Sale 1-40:Victaulic FireLockTM Automatic Sprinklers I-V9:Style V9 Victaulic FireLockTM IGSTM Installation-ReadyTM Sprinkler Coupling Installation Instructions • • User Responsibility for Product Selection and Suitability Note Each user bears final responsibility for making a determination as to the suitability of This product shall be manufactured by Victaulic or to Victaulic specifications.All products Victaulic products for a particular end-use application,in accordance with industry to be installed in accordance with current Victaulic installation/assembly instructions. standards and project specifications,and the applicable building codes and related Victaulic reserves the right to change product specifications,designs and standard regulations as well as Victaulic performance,maintenance,safety,and warning equipment without notice and without incurring obligations. instructions.Nothing in this or any other document,nor any verbal recommendation, Installation advice,or opinion from any Victaulic employee,shall be deemed to alter,vary,supersede, provision of Victaulic Company's standard conditions of sale,installation Reference should always be made to the Victaulic installation handbook or installation or waive anyinstructions of the product you are installing.Handbooks are included with each shipment guide,or this disclaimer. of Victaulic products,providing complete installation and assembly data,and are available Intellectual Property Rights in PDF format on our website at www.victaulic.com. No statement contained herein concerning a possible or suggested use of any material, Warranty product,service,or design is intended,or should be constructed,to grant any license Refer to the Warranty section of the current Price List or contact Victaulic for details. under any patent or other intellectual property right of Victaulic or any of its subsidiaries or affiliates covering such use or design,or as a recommendation for the use of such Trademarks material,product,service,or design in the infringement of any patent or other intellectual Victaulic and all other Victaulic marks are the trademarks or registered trademarks of property right.The terms"Patented"or"Patent Pending"refer to design or utility patents Victaulic Company,and/or its affiliated entities,in the U.S.and/or other countries. or patent applications for articles and/or methods of use in the United States and/or other countries. • • 40.10 2544 Rev L Updated 04/2020 ©2020 Victaulic Company.All rights reserved. victaulic.com 7 %Ctaulicr sf+ff”44{ trtai...s4ik1ifdfifd13Nf3tittstdtt{SG}ti44/4 Nf i h.itiiftdhtt..,,Htt.44.0444 i#M{#{H4i44 4.1.0N.4.4.ki#Mifeiti14 f }...,01 frtima.4.}.1,..iYiieAit3.011.061 ttk6.KN+tdf44 of4404.4.444#!`#41,14#tfpfPiY.4MIWrF3tA#N'tiA10.011.wii#4*+tft#torktf/#YHib,O,±; Victaulic° VicFlexTM Sprinkler Fittings ✓ctaulic° Series AH2 and AH2-CC Braided Flexible Hoses 10.85 Vic Flex- Series AH2 Series AH2-CC 1.0 PRODUCT DESCRIPTION Available Sizes by Component • Series AH2 1"/DN25 Nominal ID Braided Hose: 31, 36, 48, 60, 727790, 915, 1220, 1525, 1830mm. Note: length includes adapter nipple and 5.757140 mm straight reducer. • Series AH2-CC 1"/DN25 Nominal ID Braided Hose: 31, 36, 48, 60, 72"/790, 915, 1220, 1525, 1830mm. Note: length includes captured coupling and 5.757140 mm straight reducer. • Sprinkler Reducers: • Sprinkler Connections: 'hand 3/4715 and 20 mm • Straight Lengths: 5.75, 9, 137140, 230, 330 mm • 90"Elbows: • Short (typically used with concealed sprinklers) • Long (typically used with recessed pendent sprinklers) • Low Profile Short (for use with Style AB5, AB11, AB12, ABBA and ABMM Bracket) • Low Profile Long (for use with Style AB5, AB11, AB12, ABBA and ABMM Bracket) • Inlet Connections: • 1"/25mm Grooved IGS • 1"/25mm NPT or BSPT adapter nipples for attaching to pipe and fittings outlined in NFPA standards. • 3/4720 mm NPT or BSPT adapter nipples available for VdS. • 11/4"/32 mm BSPT adapter nipples available for LPCB. ALWAYS REFER TO ANY NOTIFICATIONS AT THE END OF THIS DOCUMENT REGARDING PRODUCT INSTALLATION,MAINTENANCE OR SUPPORT. • • System No. Location Spec Section Paragraph Submitted By Date Approved Date victaulic.com • 10.85 5839 Rev AG Updated 07/2019 ©2019 Victaulic Company.All rights reserved. 1 victaul.c° , victaulic.com 1.0 PRODUCT DESCRIPTION (Continued) • Brackets: • Style AB1 for suspended and hard-lid ceilings and sidewalls, allows installation before most ceiling tiles in place • Style AB2 for suspended and hard-lid ceilings and sidewalls, allows for vertical sprinkler adjustment, and installation before most ceiling tiles in place • Style AB3 for surface mount applications, wood, metal and block walls, or ceilings • Style AB4 for hard-lid ceilings with hat furring channel grid systems, allows for vertical sprinkler adjustment • Style AB5 for hard-lid ceilings and sidewalls, allows for vertical sprinkler adjustment • Style AB7 for suspended and hard-lid ceilings • Style AB7 Adjustable for suspended and hard-lid ceilings • Style AB8 for hard-lid ceilings with CD 60/27 profile metal studs (regionally available) • Style AB9 for hard-lid ceilings with hat furring channel grid systems • Style AB10 for Armstrong® TechZoneTM ceilings • Style AB11 for lay-in panel suspended t-grid ceilings or drywall suspended t-grid ceilings, allows for low profile installations (use only with 90° low profile elbows) • Style AB12 for suspended and hard-lid ceilings, allows for vertical sprinkler adjustment, and allows for low profile installation down to 4"/100mm. • Style ABBA bracket for suspended, exposed, and hard-lid ceilings • Style ABMM bracket for surface mount and stand off-mount applications, wood, metal and block walls, or ceilings and hard-lid ceilings Maximum Working Temperature • 225°F/107°C Maximum Working Pressure • 200 psi/1375 kPa (FM Approval) • 175 psi/1206 kPa (cULus Listed) • 1600 kPa/232 psi (VdS/LPCB Approved) • 1.4 MPa (CCCf Approved) Connections • To adapter nipple (inlet) via • 1725.4 mm Grooved IGS • 1725.4mm NPT or BSPT male thread • 3/n"/20 mm BSPT male thread (VdS only) • 11/732 mm BSPT male thread (LPCB only) • To sprinkler head (outlet) via 1/" or 3/715 mm or 20 mm Minimum Bend Radius • 7"/178mm (FM/CCCf Approval) • 2"/51 mm (cULus Listed) • 3"/76.2 mm (VdS/LPCB Approved) Maximum Allowable Sprinkler K-Factors • FM (1/2715 mm reducer) K5.6/8,1 (S.I.), (3/720 mm reducer) K14.0/20,2 (S.I.) • cULus (1/2715 mm reducer) K8.0/11,5 (S.I.), (34/20 mm reducer) K14.0/20,2 (S.I.) • VdS/LPCB (1/"/15mm reducer) K5.6/8,1 (S.I.), (3/4"/20mm reducer) K8.0/11,5 (S.I.) • 10.85 5839 Rev AG Updated 07/2019 ©2019 Victaulic Company.All rights reserved. victaulic.com 2 ictaulic° victaulic.com 2.0 CERTIFICATION/LISTINGS • 41> Os vas LPCB lig LISTED ,.d...... NOTE • The VicFlex Series AH2 Hose has been tested and evaluated by Spears®for acceptable use with Spears®CPVC Products and is therefore covered under the Spears®FlameGaurd®Installer Protection Plan. 3.0 SPECIFICATIONS — MATERIAL Series AH2 • Flexible Hose: 300-series Stainless Steel • Collar/Weld Fitting: 300-series Stainless Steel • Gasket Seal: Victaulic EPDM • Isolation Ring: Nylon • Nut and Nipple: Carbon Steel, Zinc Plated • Reducer (1/2/15 mm or 3I4"I20 mm): Carbon Steel, Zinc-Plated • Low Profile Elbows: Ductile Iron, Zinc-Plated Brackets: Carbon Steel, Zinc-Plated Series AH2-CC • Flexible Hose: 300-series Stainless Steel • Collar/Weld Fitting: 300-series Stainless Steel • Gasket Seal: Victaulic EPDM • Isolation Ring: Nylon • Coupling Retainer Ring: Polyethelene • Nut and Nipple: Carbon Steel, Zinc Plated • Reducer (1 "/15 mm or 34720 mm): Carbon Steel, Zinc-Plated • Housing: Ductile iron conforming to ASTM A 536, Grade 65-45-12. Ductile iron conforming to ASTM A 395, Grade 65-45-15, is available upon special request. Coupling Housing Coating: • Orange enamel (North America, Asia Pacific). • Red enamel (Europe). • Hot dipped galvanized. Gasket:' • Grade "E" EPDM (Type A) FireLock EZ products have been Listed by Underwriters Laboratories Inc., Underwriters Laboratories of Canada Limited, and Approved by Factory Mutual Research for wet and dry (oil free air) sprinkler services within the rated working pressure. 1 Services listed are General Service Guidelines only.It should be noted that there are services for which these gaskets are not compatible.Reference should always be made to the latest Victaulic Gasket Selection Guide for specific gasket service guidelines and for a listing of services which are not compatible. • Bolts/Nut: Zinc electroplated carbon steel, trackhead meeting the physical and chemical requirements of ASTM A 449 and physical requirements of ASTM A 183. • Linkage: CrMo Alloy Steel zinc electroplated per ASTM B633 Zn/Fe 5, Type III Finish 10.85 5839 Rev AG Updated 07/2019 ©2019 Victaulic Company.All rights reserved. victaulic.com 3 jctaulic° victaulic.com 4.0 DIMENSIONS Product Details - Series AH2 Braided Hose Item Description 1 1 Flexible Hose 0 2 .r Isolation Ring 0 o 0 i o 0 o 3 _} Gasket 4 Nut 1111:1 1i,1 ��,m�' j 5 _- Adapter Nipple Alb 6 Braid < -- A ) 7 Collar/Weld Fitting < B , 8 l Sleeve Hose Length Dimensions Hose Length A B inches inches inches mm mm mm 31/790 25.3/641 31/790 36/915 31.3/794 36/915 48/1219 42.3/1073 1 48/1220 60/1525 54.3/1378 60/1525 72/1830 66.3/1683 I 72/1830 Series AH2-CC Braided Hose Item Description 5, iQ 0 © 0 ° © O 1 Flexible Hose._ 1 2 Isolation Ring ®' EmmuIIi I11'�{R !rf{ILii1RfWI�1 3 Gasket 1uu umunrn ui 4 Nut Aart — 5 _. - Captured Coupling B 6 1 Braid 7 Collar/Weld Fitting ' 8 Sleeve I Hose Length A B inches inches inches mm mm mm 31/790 24.5/622 29.8/757 36/915 29.5/749 34.8/884 48/1219 i 41.5/1054 ' 46.8/1189 60/1525 53.5/1359 58.8/1494 72/1830 1 65.5/1664 70.8/1798 • •10.85 5839 Rev AG Updated 07/2019 C 2019 Victaulic Company.All rights reserved. victaulic.com 4 ✓ctaulic' victaulic.com , 4.0 DIMENSIONS (Continued) Standard Reducer runitimiiiimiitimilim iniunnuiu nuiuiun11111 5.75"/140 mm straight reducer Optional Reducers 9.07229 mm straight reducer lllllll lullllllllllll I Im°41IIInumluuul lllllll 1 lllllll mini 1 13.0"/330 mm straight reducer 2.62"/ --0. 66.5 mm h- 2.62"/ I' 66.5 mm Ti. ___ ___ 4.83"/ 6.57"/ _ - 166.9 mm 122.7 mm = _ n MI MEI ■■ I Short 90°elbow reducer Long 90°elbow reducer NOTE • The Short 90°elbow reducer is typically used with concealed sprinklers while the longer 90 elbow is typically used in the installation of recessed pendent sprinklers. • FM/VdS Approved only. Low Profile _A_ Ii 1 hi A . . l = - 4.597 = = 116mm _I72mm 2.84"/ _ _ _ 1.47 1.47 36mm 36mm Short 90°elbow reducer Long 90°elbow reducer NOTE • Style AB11:When low profiles elbows are used with the Style AB11 bracket,the Low Profile Short Elbow is typically used with concealed sprinklers while the Low Profile Long Elbow is typically used in the installation of recessed pendent sprinklers. • • 10.85 5839 Rev AG Updated 07/2019 ©2019 Victaulic Company.All rights reserved. victaulic.com 5 ✓ctaullc° , victaulic.com • • 4.1 DIMENSIONS VicFlex Brackets Style AB1 to • Suspended Ceilings l � • Hard-Lid Ceilings (FM Only) o Item Description 1 24/610 mm or 48"/1219 mm Square Bar 2 Patented Center Bracket , 3 ( End Bracket `' 0 NOTE • Both sizes FM/VdS/LPCB Approved,cULus listed 104, Style AB2 • Suspended Ceilings • Hard-Lid Ceilings 423 ily0.4%4%4N . Item j Description q14; :tb,, 1 24"/610 mm or 48"/1219 mm Square Bar 2 ++ Patented Vertically Adjustable Center Bracket 3 i End Bracket NOTE O • Both sizes FM/VdS/LPCB Approved,cULus listed 0 ./9 Style AB3 • Surface Mount Applications / , �' _ . , • FM/LPCB Approved i$ �i// _i • • 10.85 5839 Rev AG Updated 07/2019 ©2019 Victaulic Company.All rights reserved. victaulic.com 6 ✓ataulic° victaulic.com • 4.2 DIMENSIONS • VicFlex Brackets Style AB4 • Hard-Lid Ceilings with Hat furring 2 channel grid system 3 Item Description 1 24"/610 mm or 48"/1219 mm Square Bar 3 2 Patented Vertically Adjustable Center Bracket 3 End Bracket for Hat Furring Channel NOTE • Both sizes FM/VdS/LPCB Approved,cULus listed. Style AB5 • Hard-Lid Ceilings se%, Item Description 24'/610mm or 48/1219 mm Square Bar 2 Patented Vertically Adjustable Center Bracket 3 End Bracke %t . NOTE 44/� • Both sizes FM/VdS/LPCB Approved,cULus listed. Style AB7 • Suspended Ceilings • Hard-Lid Ceilings Item Description s 1 I 24"1610mmor48/1219mm Square Bar 2 Patented 1 Bee2°Center Bracket O 3 End Bracket NOTE • Both sizes FM/VdS/LPCB Approved. 0- 1% Style AB7 Adjustable %lam • Suspended Ceilings • Hard-Lid Ceilings Item Description 1 700 mm or 1400 mm Square Bar 2 Patented 1 Bee2°Center Bracket 1 3 j _ End Bracket(adjustable) y 0 NOTE • Both sizes FM/VdS/LPCB Approved. I.' 0 • • 10.85 5839 Rev AG Updated 07/2019 ©2019 Victaulic Company.All rights reserved. victaulic.com 7 ictaulicr . victaulic.com •4.3 DIMENSIONS VicFlex Brackets Style AB8 ." • Hard-Lid Ceilings � 0 Item Description 1 .700mm or'140O n Squ Bar _ 2 Patented Vertically Adjustable Center Bracket ;i' NOTE • Both sizes FM/VdS/LPCB Approved. \ Style AB10 • Suspended ceilings • Armstrong®TechZone- 4 © 0 1 Item Description .i. r1 1 6"/152mm Square Bar 1 2 Patented 1 Beet®Center Bracket 3 End Bracket NOTE • FM/VdS/LPCB Approved,cULus listed. Style AB11 • Suspended ceilings • Hard Lid ceilings `- 1 Item I Description 1 I� i- 1 r 24/610 mm or 48/1219 mm Square Bar 2 I Patented 1-Beer Center Bracket L 3 End Bracket nt "._ _. __ _ \'� O NOTE • FM/VdS Approved,cULus listed. O 1 0� 1 Style AB12 • Suspended ceilings • Hard-Lid ceilings r„ Item Description I i`, \ 1 I Style A612 Bracket Body j -yam - ,. 9/I 2 ; #2 Square Drive Set Screw I `,. ,. NOTE 111// O • FM/VdS Approved. • • 10.85 5839 Rev AG Updated 07/2019 ©2019 Victaulic Company.All rights reserved. victaulic.com 8 ✓ctaulrc victaulic.com • • 4.3 DIMENSIONS (CONTINUED) VicFlex Brackets Style ABBA o • Floor-above mount eA411 • Cantilever mount • Temporary mount in exposed ceilings 6 Item Description Style ABBA Mounting Plate 2 Style ABBA Square Bar 3 Cap Screw, T25 Torxted Drive Recessed 1 x 20, ® I 4 1 Style ABMM Bracket Body �h Cap Screw,Serated Flange,M6 x 1 x 15.24, E d„'. L � 5 T25 Torx Drive Recessed J Style ABMM • Surface mount o,c� d { • Stand-off mount \ ...� !�m�41 " '04�• IoI ° 4 P I Item I Description 4%`a j1 —,' 1 , Style ABMM Bracket Body liio. Cap Flange, \I��j Screw,Serated M6 x 1 x 15.24, r 2 i T25 Torx Drive Recessed • • 10.85 5839 Rev AG Updated 07/2019 ©2019 Victaulic Company.All rights reserved. victaulic.com 9 ✓ctaulic° victaulic.com • 4.4 DIMENSIONS Clearances Series AH2 Braided Hose and Style AB1 Bracket e ..., A MA Lg.:. Bracket See Chart eDi Assembly 23/a'/60 mm 2136'/68 mm W Style AB1 it." max hole max hole liil�t ��'I � 2"/51 mm 23/8'/60mm s/e^/ 4.4"/ min.hole m in.hole ��' _= 15.9 mm H' 113 mm — Typical Ill_a ME 1.7743 mm p `�ceiling tile E" I*I ;1M Typical ceiling 11,-31 lr ll` %I�i l i�I grid -- ,'; Finished P'..1 See note ceiling face '",p 24"/610 mm or V27 V38 48"/1219mm on Pendent Center Hose Clearance Chart Straight Reducer Long Elbow Short Elbow V 707 V3802 I Max R Recess Max Recess MaxMaxRe Recess Max Recess 3/a"Max Recess V2"Max8Recess 3/a"Max Recess i'2"MaxV3802 inches inches inches inches inches 1 inches inches inches mm mm mm mm mm mm mm mm "R"Minimum 2.0 j 3.0 7.0 ! _ Bend Radius 50 80 175 ---- -------- _T "A"Minimum - . Required 8.6 i 10.1 9.6 11.1 13.6 15.1 5.8 5.8 Installation 218 269 244 281 345 383 147 147 Space NOTE • Variations of ceiling grids,sprinkler heads,brackets,and hoses are permitted but may result in clearance differences from the figures above. • • 10.85 5839 Rev AG Updated 07/2019 ©2019 Victaulic Company.All rights reserved. victaulic.com 10 ✓ctaulic 1 victaulic.com . 4.5 DIMENSIONS Clearances Series AH2 Braided Hose and Style AB2 Bracket ME A CZ' See Chart ra Bracket 1.8/ ri 2'ta"/68 mm 23/a"/60 mm 23/e"/60 mm 2 x 4" Scree Assembly 45 mm w Style A82 �,,,,► max.hole max hole max.hole Stud il' rii mum 111 1 23/e"/60 mm 2"/51 mm 2"/51 mm ►I, i min,hole min.hole min.hole 1 i � 18mm 1tir•9 ' E1 u ' IMii:'�I 1r�1 /1� G1 /iIiiki% , Finished i 16"/405mm ceiling roil, 'fir Stud C/C Hose Clearance Chart Straight Reducer V2707 V3802 1 V2709 V2707 V3802 V2709 V2707 V3802 V2709 3/a"I 20mm 1/2"I 13mm 3/4"I 20mm 3/4"I 20mm 'h"113mm 3/a"I 20mm 3/4"I 20mm '/"113mm 3/4'I 20mm Max Recess"' Max Recess Sidewall Max Recess Max Recess Sidewall Max Recess Max Recess Sidewall inches inches inches inches inches inches inches inches inches mm mm mm mm mm mm mm mm mm "R"Minimum 2.0 3.0 7.0 Bend Radius 50 80 175 "A"Minimum - , Required 6.2 7.6 6.1 7.2 8.6 7.1 11.2 12.6 11.1 Installation 158 193 155 183 218 180 285 320 282 Space Hose Clearance Chart Long Elbow Short Elbow V2707 V2709 V3802 3/4"120 mm 3/4'120 mm 1/2"113 mm Max Recess Sidewall Max Recess inches inches inches mm mm mm "R"Minimum _ Bend Radius "A"Minimum Required 3.3 3.6 3.3 Installation 84 91 84 Space _. NOTE • Variations of ceiling grids,sprinkler heads,brackets,and hoses are permitted but may result in clearance differences from the figures above. • • 10.85 5839 Rev AG Updated 07/2019 ©2019 Victaulic Company.All rights reserved. victaulic.com 11 ✓ctaulic . victaulic.com 4.6 DIMENSIONS Clearances Series AH2 Braided Hose and Style AB4 Bracket fi _ tm:we A2;/e"/60 mm 2 1As"/68 mm max.hole max hole '-I� I '-. See Chart 2"/51 mm 2%760 mm IiiiI' 111l min.hole min.hole n ii 411 J. - il•ImiII1# • +Itosoliwl , il111iirhil i i. i 1W•A'Lif -11 � 4 11 ' 1::! 5/e'715.9 mm Typical I..-1 Typical finished Ilip, ceiling tile ceiling face - See note 7/s"/23 mm Typical 167406 mm- Typical V27 V38 24'/610 mm on Center ceiling grid Pendent Hose Clearance Chart Straight Reducer Long Elbow Short Elbow V2707 V3802 V2707 V3802 3/0" lh" 3/4" t/i' V2707 V3802 V2707 V3802 Max Recess Max Recess Max Recess Max Recess 3/4"Max Recess lh"Max Recess 3/4"Max Recess 1/2"Max Recess inches inches inches inches inches inches inches inches mm mm mm mm mm mm mm mm "R"Minimum j 2.0 2.0 3.0 3.0 7.0 7.0 i _ Bend Radius ; 50 50 80 80 175 175 "A"Minimum Required 8.8 10.2 9.8 11.2 13.8 15.2 8.0 5.9 Installation 224 259 249 285 351 386 203 150 Space NOTE Variations of ceiling grids,sprinkler heads,brackets,and hoses are permitted but may result in clearance differences from the figures above. i • •10.85 5839 Rev AG Updated 07/2019 ©2019 Victaulic Company.All rights reserved. victaulic.com 12 ✓ataulic r victaulic.com . • 4.7 DIMENSIONS . Clearances Series AH2 Braided Hose and Style AB5 Bracket 0_ A 1 See Chart Amp' Bracket t Assembly 2W/60 mm 2'Ni"/68 mm 2W/60 mm I_ 2.3'/ ��.�_ Style AB5�� max.hole max.hole max.hole i�� 'I 1. 1 ,�57 mm 2"/51 mm 2'55/60 mm 2"/51 mm ii _ ii -_ ,,11 _ ii _i iii� min.hole min.hole min.hole ti a -7_ ii 1 n ff ff ..r ff f 3.6"/ ILL 2x4" 1 ii ii i i 92mmim MetalStud I 1 i Em I i 1 i Mr 1r ►'i ir 40 '/"/ Finished r'j r4.1 15.9 mm ceiling face ISi.t Drywall 16"/406 mm Stud C/C V27 V38 V27 Pendent Sidewall Hose Clearance Chart L Straight Reducer "V2707 V3802 1 V2709 I V2707 V3802 V2709 V2707 V3802 V2709 3/4"120mm 1/2"113mm 13/4"120mm ' 3/e'120mm Y2 I13mm 3/4"120mm 3/4"120mm ' t "I13mm 3/4"120mm Max Recess" Max Recess " Sidewall Max Recess Max Recess Sidewall Max Recess Max Recess Sidewall inches inches inches inches inches inches inches inches inches mm mm mm mm mm mm mm mm mm "R"Minimum 2.0 3.0 7.0 Bend Radius 50 80 175 "A"Minimum Required 6.0 ' 7.7 6.1 7.0 8.7 7.1 11.0 12.7 11.1 Installation 158 I 196 155 178 221 180 279 323 282 Space I Hose Clearance Chart Low-Profile Long Elbow Long Elbow Short Elbow V2707 V3802 V2709 V3802 V3802 3/4"I20mm 1/2"I13mm " 3/4"I20mm 1/2"I13mm 1h"I13mm Max Recess Max Recess Sidewall Max Recess Max Recess inches inches inches inches inches mm mm mm mm mm "R"Minimum _ Bend Radius "A"Minimum Required 3.5 4.9 3.6 2.9 3.3 Installation 89 124 91 74 84 Space NOTE • Variations of ceiling grids,sprinkler heads,brackets,and hoses are permitted but may result in clearance differences from the figures above. • •10.85 5839 Rev AG Updated 07/2019 ®2019 Victaulic Company.All rights reserved. victaulic.com 13 ✓ctaulic° • victaulic.com 4.8 DIMENSIONS Clearances Series AH2 Braided Hose and Style AB11 Bracket (LOW PROFILE SOLUTION) 23/8"/60 mm 2nw768 mm Bracket 7ij max.hole max.hole Assembly ,I.'411 2"/51 mm 23/8760 mm A Style A611 min.hole min.hole See Chart 0a �0 3.0"/ 76 mm i_ I II ire_ � 1-,.1 - 1.7"/43 mm � Finished �I� Typical * 5/8"/15.9 mm ceiling face ceiling grid Typical ceiling tile See Note 24"/610 mm or V27 V38 48"/1219 mm on center Pendent Hose Clearance Chart Low-Profile Low-Profile Long Elbow Short Elbow V2707 V3802 3/4"I20mm 1/2'l13mm Max Recess" Max Recess inches inches mm mm "A"Minimum Required 4.0 3.9 Installation 102 99 Space NOTE • Variations of ceiling grids,sprinkler heads,brackets,and hoses are permitted but may result in clearance differences from the figures above. • • 10.85 5839 Rev AG Updated 07/2019 ©2019 Victaulic Company.All rights reserved. victaulic.com 14 ✓ctaulid victaulic.com 4.9 DIMENSIONS Clearances Style AB12 and ABBA Bracket Suspended Ceiling Grid with Recessed Sprinkler with Suspended Ceiling Grid with Recessed Sprinkler and Low Profile Short Elbow Straight 5.75"/140 mm Reducer I i i . [ Unfinished Ceiling Face I 144 inch/ i 29mm /' i • j /All i Square bar �_ i Nominal length I l • 14'/355.6 min i }�. /I • See Table r7 I Unfinished inch/ jii jijijCeiling face.I = 29mm i�. Kinch/ 1' fff 3 -.i;j- lE iii1X4 l" i3minIglillt ,J.1i .IpI>urAi ' nI _ �_ Square bar (',, i j I - - • ��ICI ,��p I e� 1 GG�7�� A inch/ 5r_0 iYi/ 47 • 3mm p 1 See?able "B"See Table -lijlint-Rill;; 1=7= "B"See Table i == i QJ ■■ 1 4- • Finished Face of 0 Finished Face of Typical Ceiling 00 Typical Ceiling V2707 Ye/12.7 mm MAX.RECESS V2707 94"/19 mm MAX.RECESS r I Low Profile Low Profile Standard 1 Standard Standard Dimension Short Elbow Long Elbow Short Elbow Long Elbow Straight Reducer a �3 rr 3/d'/19 mm 3/4719 mm 719 min /4"/19 mm R719 min, Recessed* Concealed Recessed Concealed Recessed I Concealed Recessed Concealed Recessed Concealed', inches inches inches inches inches inches inches inches inches inches mm mm mm mm mm mm mm mm mm mm A Minimum Required 4.0 5"5 5.6 7.2 5.9 7.5 7.7 9.3 15.0 16.6 Installation Space 101.6 139.7 142.2 ' 182.9 149.9 190.5 195.6 236.2 381.0 421.6 Distance from Top of 0.5 2.0 1.5 1.5 1.5 1.5 3.0 3.0 3.0 3.0 B ITypical Ceiling Tile to 12.7 50.8 38.1 38.1 38.1 38.1 76.2 76.2 76.2 76.2 L_ Bottom of Gate ) _L *Adjustability will be limited Style ABMM Bracket Stand-off Dimensions ' z.zz"/ 56 min i- I I ° Hi 141 3.93"/ 2.94"/ 75 min 0.28"/ 100 min I O C7 3.94"/ CIE)j�EA:13 100 mm 7 mm ■ o • •10.85 5839 Rev AG Updated 07/2019 ©2019 Victaulic Company.All rights reserved. victaulic.com 15 ✓ctaulia vi;' ,;1.:Ei;.t..t;?'pf •4.10 DIMENSIONS Clearances Style AB3 and ABMM Bracket Surface Mount Application with Recessed Sprinkler 7 7--- C i h-.: 33/4"/ £ _� �_ 95.3 mm A •.r, 1..• 1 A ._J 111 roo %„r ______ 23/8"/60 mm max.hole 2"/51 mm min.hole Hose Clearances inches inches ' inches inches inches inches inches inches inches inches Dimension mm mm mm , mm mm 1 mm mm mm mm mm Wall Thickness 2 4 6 8 10 2 4 6 8 10 "A" 50 100 150 200 250 50 100 150 200 250 Outlet Length 5.75 9 13 5.75 9 13 9 13 13 13 5.75 9 13 5.75 9 13 9 13 13 13 146.1 228.6 330.2 146.1 228.6 330.2 228.6 330.2 330.2 330.2 146.1 228.6 330.2 146.1 228.6 330.2 228.6 330.2 330.2 330.2 Hose Clearance 11.6 14.8 18.8 9.6 12.8 16.8 10.8 14.8 12.8 10.8 12.6 15.8 19.8 10.6 13.8 17.8 11.8 15.8 13.8 11.8 "C" 294 376 478 243 325 427 275 376 325 275 319 402 503 268 351 452 300 402 351 300 Bend Radius 7 8 175 1 200 ' NOTE • Variations of ceiling grids,sprinkler heads,brackets,and hoses are permitted but may result in clearance differences from the figures above. • • 10.85 5839 Rev AG Updated 07/2019 ©2019 Victaulic Company.All rights reserved. victaulic.com 16 jictaulic° victaulic.com • • 5.0 PERFORMANCE - FRICTION LOSS DATA Series AH2 and AH2-CC Braided Hoses with Straight 5.75"/140 mm Reducers COUS LISTED Style AB1, AB2, AB4, AB5 and AB10 Brackets Maximum Equivalent Length Number of of 1733.7 mm 90° Bends at 2751 mm Sch.40 Pipe(C=120) Bend Radius inches/mm inches/mm/type feet/meters 31/790 1/2"/15/Straight 16/4.9 4 3/4"/20/Straight 17/5.2 4 36/915 1/2"/15/Straight 21/6.4 5 3/4"/20/Straight r 23/7.0 5 48/1220 '/z"/15/Straight 32/9.8 8 ____ 3/4"/20/Straight 37/11.3 8 60/1525 I /z"/15/Strai ht 46/14.0 10 34C/20/Straight 46/14.0 10 1/2"/15/Straight 55/16.8 I 12 " 72/1830 -- _____ _ 34C/20/Straight 53/16.2 12 Series AH2 and AH2-CC Braided Hose with 90° Low Profile Elbows COUS LISTED Style AB11 VicFlex Bracket Maximum Equivalent Length Number of of 1733.7 mm 90°Bends at 2751 mm Sch.40 Pipe Bend Radius inches/mm inches/mm feet/meters 31/790 '/z"/15 24/7.3 4 3/4"/20 24/7.3 j 4 36/915 '/2"/15 26/7.9 5 3/4"/20 28/8.5 5 48/1220 3/4'/20 l 42/12.8 j 8 r 1/2"/15 49/14.9 10 60/1525 3/4"/20 50/15.2 10 1/2"/15 65/19.8 12 72/1830 --___ _.__—w___— _ _ y 3/4'720 63/19 2 12 • • 10.85 5839 Rev AG Updated 07/2019 ©2019 Victaulic Company.All rights reserved. victaulic.com 17 ✓ctaulic' victaulic.com • .. .. ............. 5.0 PERFORMANCE — FRICTION LOSS DATA (CONTINUED) Series AH2 and AH2-CC Braided Hoses Equivalent Length Design Guide Equivalent length values at various numbers of 90 degree bends at 2"/51 mm center line bend radius Length of Stainless Steel Flexible Outlet 1 2 3 4 5 6 7 8 9 10 11 12 Hose Size Bend Bends Bends Bends Bends Bends Bends Bends Bends Bends Bends Bends inches/ inches/ feet/ feet/ feet/ feet/ feet/ feet/ feet/ feet/ feet/ feet/ feet/ feet/ mm mm meters meters meters meters meters meters meters meters meters meters meters meters 31/790 '/z/15 8.5/2.6 11.0/3.4 13.0/4.0 16.0/4.9 N.A N.A N.A N.A N.A N.A N.A N.A 3/4720 10.0/3.0 12.5/3.8 14.0/4.3 17.0/5.2 N.A N.A N.A N.A N.A N.A N.A N.A 36/915 1/2/15 13.5/4.1 16.0/4.9 18.0/5.5 19.0/5.8 21.0/6.4 N.A N.A N.A N.A N.A N.A N.A 3/4"/20 14.0/4.3 17.0/5.2 19.5/5.9 20.0/6.1 23.0/7.0 N.A N.A N.A N.A N.A N.A N.A 48/1220 1h"/15 15.5/4.7 17.0/5.2 19.5/5.9 20.0/6.1 21.0/6.4 22.0/6.7 28.0/8.5 32.0/9.8 N.A N.A N.A N.A 3/4'720 17.0/5.2 19.0/5.8 21.5/6.6 24.5/7.5 26.0/7.9 27.0/8.2 30.0/9.1 37.0/11.3 N.A N.A N.A N.A 60/1525 1/2715 21.5/6.6 24.0/7.3 27.0/8.2 28.5/8.7 30.0/9.1 31.0/9.4 37.0/11.3 42.0/12.8 44.0/13.4 46.0/14.0 N.A N.A 3/4720 23.0/7.0 24.0/7.3 28.0/8.5 29.5/9.0 30.5/9.3 31.0/9.4 38.0/11.6 42.0/12.8 44.0/13.4 46.0/14.0 N.A N.A 72/1830 1/2/15 30.0/9.1 32.0/9.8 36.5/11.1 37.5/11.4 40.5/12.5 41.0/12.8 42.0/12.8 46.0/14.0 49.0/14.9 52.0/15.8 54.0/16.5 55.0/16.8 3/4"/20 32.0/9.8 32.5/9.9 35.0/10.7 35.5/10.8 40.0/12.3 40.5/12.3 41.0/12.5 46.0/14.0 50.0/15.2 51.0/15.5 52.0/15.8 53.0/16.2 NOTES: • Values for use with 5.757140mm straight reducers. How to use this Design Guide: • For some systems,it may be advantageous for the designer to calculate the system hydraulics using shorter equivalent lengths associated with fewer than the maximum allowable number of bends.In this case,the designer may select a design number of bends for the job and use the associated equivalent length from the design guide to determine the system hydraulics. • It is possible that the actual installed condition of some of the flexible drops may have more bends than the designer selected.When this happens,the design guide may be used to find equivalent lengths based on the actual installed number of bends for particular sprinkler installations.The system hydraulics can be recalculated using actual equivalent lengths to verify the performance of the system. • • 10.85 5839 Rev AG Updated 07/2019 ©2019 Victaulic Company.All rights reserved. victaulic.com 18 jctaulic' vicctaulic.corn •5.1 PERFORMANCE - FRICTION LOSS DATA ® Series AH2 and AH2-CC Braided Hoses Style AB1, AB2, AB3, AB4, AB5, AB7, AB7 Adj., AB8, AB10, AB12, ABBA and ABMM VicFlex Brackets Maximum Equivalent Number Length of Length of of 90°Bends Stainless Steel Outlet 1'733.7mm at 7'7178 mm Flexible Hose K-Factor Size Sch.40 Pipe Bend Radius inches/mm Imperial/S.I. inches/mm/type feet/meters 31/790 5.6/8.1 1/2"/15/Straight 13.8/4.2 2 j 1/2715/90°Elbow 23.5/7.1 Y2"/15/Straight 16.6/5.1 ' 36/915 5.6/8.1 2 1/2715/90°Elbow 25.6/7.8 1/2715/Straight - 23.4/7.1 48/1220 5.6/8.1 .,_ 3 1 1/2"/15/90°Elbow 30.7/9.3 , z/15/Straight 30.2/9.2 1 60/1525 5.6/8.1 4 1/2/15/90°Elbow 35.9/10.9 1/2'715/Straight 37.0/11.3 i 72/1830 5.6/8.1 4 1_ 715/90°Elbow 41.1/12.5 a /4/20/Straight 16.8/5.1 31/790 8.0/11.5 } 2 4/20/90'Elbow 16.8/5.1 3/4'/20/Straight 20/6.0 36/915 8.0/11.5 --i 2 3/4'/20/90°Elbow 19.7/6.0 3/4"/20/Straight 27.8/8.4 I 48/1220 8.0/11.5 3/4"/20/90'Elbow 26.6/8.1 3 3/4"/20/Straight 35.7/10.9 60/1525 8.0/11.5 4 3/4720/90'Elbow 33.6/10.2 1 3/4"/20/Straight 43.5/13.2 72/1830 8.0/11.5 I 4 3/4720/90'Elbow 40.6/12.2 34"/20/Straight 16.5/5.0 31/790 11.2/16.1 3/ 2 /4/20/90'Elbow 17.8/5.4 3 '/20/Straight 19.5/5.9 ' 36/915 112/161 2 3/4/20/90*Elbow 20.7/6.3 I /4 g720/Strai ht 26.7/8.1 1 3 48/1220 1 11.2/16.1 �_ 3 3/4720/90°Elbow ( 27.9/8.5 l 3/4720/Straight 1 33.9/10.3 1 1 60/1525 11.2/16.1 4 3/a"/20/90°Elbow 35/10.7 1 3/4720/Straight 41.3/12.5 I 72/1830 11.2/161 4 i 3/720/90'Elbow 42.2/12.8 31/790 14.0/20.2 /4720/Straight 14.9/4.5 ( 1, 3/4/20/90°Elbow ! 15.5/4.72 2 3/4/20/Straight 19.4/5.9 36/915 14.0/20.2 2 3/4720/90'Elbow 19.6/5.9 3 °/20/Straight _30.3/9.2 48/1220 14.0/20.2 4 3 1 3/4"/20/90°Elbow 29.5/8.9 3 "/20/Strai ht 33.9/10.3 60/1525 14.0/20.2 3 g 4 '/20/90°Elbow 34.1/10.4 3/4"/20/Straight 37 5/11 4 i 72/1830 14.0/20.2 4 1 3/4720/90'Elbow 386/11 7 FM NOTES: • The Series AH2 hose has been tested and Approved by FM Global for use in wet,dry and preaction systems per NFPA 13,13R,and 13D and FM data sheets 2-0,2-5,and 2-8.FM 1637 standard for safety include,but are not limited to,pressure cycling,corrosion resistance,flow characterisitics,vibration resistance, leakage,mechanical and hydrostatic strength. • EXAMPLE:A 48-inch hose installed with two 30°bends and two 90°bends is permitted and considered equivalent to the data in the table shown above.In this example,the total number of degrees is 240°,which is less than the allowable 270°. • • 10.85 5839 Rev AG Updated 07/2019 ©2019 Victaulic Company.All rights reserved. victaulic.com 19 jctaulic° victaulic.com • • 5.2 PERFORMANCE — FRICTION LOSS DATA ® Series AH2 Braided Hose with 90° Low Profile Elbows Style AB5, AB11, AB12, ABBA and ABMM VicFIex Bracket Maximum Equivalent Number Length of Length of of 90° Bends Stainless Steel Outlet 1733.7mm at 7"/178mm Flexible Hose K-Factor Size Sch.40 Pipe Bend Radius inches/mm Imperial/S.I. inches/mm feet/meters 31/790 5.6/8.1 1/2"/15 13.7/4.2 2 36/915 5.6/8.1 1/2"/15 1 17.0/5.2 2 48/1220 i 5.6/8.1 1/2"/15 25.0/7.6 3 �_..- 60/1525 5.6/8.1 1/2715 33.0/10.1 4 72/1830 5.6/8.1 1/2"/15 41.1/12.5 4 31/790 8.0/11.5 3/4"/20 13.6/4.14 2 36/915 8.0/11.5 3/4"/20 16.9/5.2 2 48/1220 8.0/11.5 3/4720 27.8/8.5 3 1 _ .. 60/1525 8.0/11.5 3/4"/20 32.6/9.9 4 72/1830 8.0/11.5 3/4"/20 40.6/12.4 4 31/790 11.2/16.1 1 3/4"/20 13.7/4.2 2 36/915 11.2/16.1 3/4"/20 1 17.0/5.2 2 48/1220 11.2/16.1 3/4"/20 24.9/7.6 3 60/1525 11.2/16.1 3/4"/20 32.9/10.0 4 .aTtt I 1 72/1830 11.2/16.1 i /4"/20 40.9/12.5 4 3 31/790 14.0/20.2 3/4"/20 13.5/4.1 2 36/915 14.0/20.2 3/4"/20 16.8/5.1 2 48/1220 14.0/20.2 3/4"/20 24.7/7.5 3 4-, 60/1525 14.0/20.2 W/20 32.7/9.9 4 72/1830 14.0/20.2 3/4"/20 — 40.7/12.4 4 i_ _J FM NOTES: • The Series AH2 hose has been tested and Approved by FM Global for use in wet,dry and preaction systems per NFPA 13,13R,and 13D and FM data sheets 2-0,2-5,and 2-8.FM 1637 standard for safety include,but are not limited to,pressure cycling,corrosion resistance,flow characterisitics,vibration resistance, leakage,mechanical and hydrostatic strength. • EXAMPLE:A 48-inch hose installed with two 30°bends and two 90°bends is permitted and considered equivalent to the data in the table shown above.In this example,the total number of degrees is 240°,which is less than the allowable 270°. • •10.85 5839 Rev AG Updated 07/2019 ®2019 Victaulic Company.All rights reserved. victaulic.com 20 ✓ctaulid' • 5.3 PERFORMANCE — FRICTION LOSS DATA 1 Series AH2 and AH2-CC Braided Hose (VdS Style AB1, AB2, AB4, AB5, AB7, AB7 Adj., AB8, AB10, AB11 and AB12 Brackets 1 Equivalent Length of Maximum Number Length of steel pipe according to of 90"Bends at Stainless Steel Outlet EN 10255 DN 25 3"/76.2 mm Bend Flexible Hose Size (33,7 x 3,25) Radius mm/inches mm/inches meters/feet meters/feet 31/790 ).__ _ �._ 15mm//z" { 5.5/18.0 3 a 20 mm/3/4" 36/915 15 mm/'/z" 6.4/21.0 3 20mm/3/4 15 mm/'/2" 48/1220 8.5/27.9 ! 3 20 mm/3/4" 15mm/Y' 60/1525 20 mm/3/4" 10.7/35.1 4 72/1830 15 mm/1/2" 12.8/42.0 4 20 mm/3/4" VDS CEILING MANUFACTURERS LIST AB1,AB2,AB7,AB10,AB11 AB4 AB5,AB8 1.AMF No specific approval 1.Hilti 2.Armstrong 2.Knauf 3.Chicago Metallic 3.Lafarge 4.Dipling 4.Lindner 5.Durlum 5.Rigips 6.Geipel 7.Gema-Armstrong 8.Hilti 9.Knauf 10.Lafarge 11.Linder 12.Odenwald 13.Richter 14.Rigips 15.Rockfon Pagos 16.Suckow&Fischer 17.USG Donn Series AH2 and AH2-CC Braided Hose Series AH2 Braided Hose [LPCBI Style AB1, AB2, AB3, AB4, AB5, AB7, AB8, (sC Style AB1, AB2, AB3, AB4, AB5, AB7, AB8, and AB10 Brackets AB10 and AB12 Brackets Length of Equivalent Length Maximum Stainless of steel pipe Number of Steel according to 90"Bends at Length of Flexible Outlet EN 10255 DN 25 3"/76.2 mm Flexible Equivalent Length of Hose Size (33,7 x 3,25) Bend Radius Hose 1'/33.7mm Sch.40 Pipe mm ' mm/inches mm/inches/type meters/feet inches Straight Configuration Bend Configuration 15 mm/'h"/Straight 790 0.87 2.70 790/31 1.8/6.0 2 20 mm/3/4 i 915/36 15 mm/'h"/Straight 3.6/11.9 3 915 1.00 2.80 20 mm/3/4"/Straight 36 3.3 9.2 15 mm/1/2"/Straight 1 1 1220 2.23 4.66 1220/48 20mm/3/4"/Straight 4.3/14.0 3 48 7.3 15.3 15 mm/1/2"/Straight l 1525 2.90 6.5 1525/60 4.1/13.6 3 [..-_ 60 9.5 21. l 20 mm/3/4"/Straight 3 15 mm/1/2"/Straight j ! 1830 3.31 7.16 1830/72 20mm/3/4"/Straight 5.5/18.1 3 72 10.9 23.5 I CCCF NOTE • Friction loss data is in accordance with GB5135.16 tested at a flow rate of 114 liters per minute(30 gallons per minute). • 10.85 5839 Rev AG Updated 07/2019 ©2019 Victaulic Company.All rights reserved. victaulic.com 21 ✓ctaulic • •6.0 NOTIFICATIONS A WARNING Irki) umtomos o • Read and understand all instructions before attempting to install, remove, adjust, or maintain any Victaulic piping products. • Always verify that the piping system has been completely depressurized and drained immediately prior to installa- tion, removal, adjustment, or maintenance of any Victaulic products. • Wear safety glasses, hardhat, and foot protection. Failure to follow these instructions could result in death or serious personal injury and property damage. A WARNING • It is the responsibility of the system designer to verify suitability of 300-series stainless steel flexible hose for use with the intended fluid media within the piping system and external environments. • The effect of chemical composition, pH level, operating temperature, chloride level, oxygen level, and flow rate on 300-series stainless steel flexible hose must be evaluated by the material specifier to confirm system life will be acceptable for the intended service. Failure to follow these instructions could cause product failure, resulting in serious personal injury and/or property damage. 10.85 5839 Rev AG Updated 07/2019 ©2019 Victaulic Company.All rights reserved. • victaulic.com 22 jotaulicP victaulic.com . 7.0 REFERENCE MATERIALS - CHARACTERISTICS VicFlex Maximum Load Values Series AH2 Hose with 24" Bracket Actual Length Total Load Max. Uniform Load ft Model Size m lb N lb/linear ft N/linear m 31/790 0.8 5.2 23 . 2.6 38 36/915 0.9 5.5 25 2.8 40 48/1220 1 2 6.3 ' 28 , 31 46 60/1525 1.5 7.0 31 3.5 51 72/1830 6 1.8 7.7 34 3.9 I 57 I Series AH2 Hose with 48" Bracket Actual Length Total Load Max.Uniform Load ft Model Size m lb N lb/linear ft N/linear m 2.6 31/790 0.8 6.1 27 1.5 22 36/915 ' 3 6.4 29 1.6 23 0.9 48/1220 12 7.2 32 18 26 60/1525 15 7.9 35 2.0 29 72/1830 1.8 8.7 39 2.2 32 Total Load is defined as the sum of the weights of the following: • water-filled flexible sprinkler hose with threaded end fittings, including a typical fire sprinkler • bracket assembly (any applicable Victaulic bracket model of the relevant associated size) ASTM C 635: Suspension System Load-Carrying Capabilities (excerpted) Actual Length Min.Allowable Uniform Load Suspension System ft/m lb/linear ft N/linear m l Light 5.0 I 75.7 e Direct Hung Intermediate 12.0 1 181.0 Heavy 16.0 i 241.7 SUMMARY: All direct-hung suspension system duty classifications per ASTM C 635 are able to withstand the maximum water-filled weight of the VicFlex sprinkler hose and bracket. 10.85 5839 Rev AG Updated 07/2019 ©2019 Victaulic Company.All rights reserved. victaulic.com 23 ✓ctauliC' victaulic.com • 7.0 REFERENCE MATERIALS -CHARACTERISTICS (CONTINUED) Flexible Hose In-Plane Bend Characteristics One Bend Two Bends Three Bends • 2X MinimumXMinimum i Minimum I ' bend radius bend radius bend radius OR OR • Minimum lnimum Minimum bend radius bend radius Minimum bend radius • --- Minimum bend radius NOTE For out-of-plane (three-dimensional) bends, care must be taken to avoid imparting torque on the hose. I-VicFlex-AB1-AB2-AB10 I-VicFlex-AB3 I-VicFlex-AB4 I-VicFlex-AB7 I-VicFlex-AB8 I-VicFlex-AB12 J-VicFlex-ABBA I-VicFlex-ABMM • • User Responsibility for Product Selection and Suitability Note Each user bears final responsibility for making a determination as to the suitability of This product shall be manufactured by Victaulic or to Victaulic specifications.All products Victaulic products for a particular end-use application,in accordance with industry to be installed in accordance with current Victaulic installation/assembly instructions. standards and project specifications,and the applicable building codes and related Victaulic reserves the right to change product specifications,designs and standard regulations as well as Victaulic performance,maintenance,safety,and warning equipment without notice and without incurring obligations. instructions.Nothing in this or any other document,nor any verbal recommendation, Installation advice,or opinion from any Victaulic employee,shall be deemed to alter,vary,supersede, Reference should always be made to I-VICFLEX-AB1-AB2-AB10,I-VICFLEX-AB4, or waive any provision of Victaulic Company's standard conditions of sale,installation I-VICFLEX-AB7,or I-VICFLEX-AB8 for the product you are installing.Handbooks are guide,or this disclaimer. included with each shipment of Victaulic products for complete installation and assembly Intellectual Property Rights data,and are available in PDF format on our website at www.victaulic.com. No statement contained herein concerning a possible or suggested use of any material, Warranty product,service,or design is intended,or should be constructed,to grant any license Refer to the Warranty section of the current Price List or contact Victaulic for details. under any patent or other intellectual property right of Victaulic or any of its subsidaries or affiliates covering such use or design,or as a recommendation for the use of such Trademarks material,product,service,or design in the infringement of any patent or other intellectual Victaulic and all other Victaulic marks are the trademarks or registered trademarks of property right.The terms"Patented"or"Patent Pending"refer to design or utility patents Victaulic Company,and/or its affiliated entities,in the U.S.and/or other countries. or patent applications for articles and/or methods of use in the United States and/or other countries. • •10.85 5839 Rev AG Updated 07/2019 ©2019 Victaulic Company.All rights reserved. victaulic.com 24 4taU-I.d Ductile Ir on Threaded Fittings ,....... , ,,,„.,-, ,,,,,,70,,,,,.,," p k co.' $k' U" r ry a b dt; ^;-'mow. d>� +� ez R� ztd y�� ! * 3* 1 dt; !`r.: F� ! 'fit" ha t N� A e x Uw: Ductile Iron Threaded Fittings Specifications • <' > branded fittings are UL Listed and FM Approved at 500 psi • Rated to 300 psi WSP 41)) • Ductile iron castings conform to ASTM A536 C US j LISTED • Fitting dimensions conform to ASME B 16.3 • Bushings and plugs conform to ASME B16.14 4; • All fittings are 100% air tested APPROVED • NPT threads on all fittings conform to ASME B1.20.1 • Independent lab verification that fittings meet applicable chemical & mechanical properties • Manufacturing facilities are ISO 9001:2008 and ISO 14001 • ProPakTM Packaging Temperature Working Pressure, Non-Shock psig Degrees F Class 300 Threaded Fittings .. -20 to 100 500 150 500 200 480 250 460 � ��t 300 440 350 420 {t. F t t ,, 400 400 ; vF ;itoi. 450 380 ,..,i. 500 360 ft„ 44 -" , i i G 550 340 r ; ,, , : .+. 600 320 , -„ 650 300 t: i z i: t. SCI ProPakrm System i 1 i, '; .i t .gir r ,>: 3 e;t t{;?; f.e.;F i his) t7u i t tFiri v tt ys,I 1; t i}y�s i, ,iE t } ttl t P, ,,y; �i a -t a.t,iii .Yii ¢9., I t + i i 3 r • :ifit .ai 3 f ;#t=} o F t pi 7. ,F...St if j t ;:/g d i { . - ( :1 Ductile Iron Threaded Fittings - Class 300 UL/FM ,7.f; r,1i , c ® us 441," APPROVED Fig. 35E 3- 90°Elbow LISTED A Size A Packing Weight ni..•o4, in Fart Number in Inner Master lb __ .,_ e 1/2 35E 3004 1.13 100 200 0.2 S 3/4 35E 3006 1.31 70 140 0.3 %%0. A 1 35E 3010 1.50 40 80 0.5 p,� 1-1/4 35E 3012 1.75 25 50 0.8 1-1/2 35E 3014 1.94 18 36 1.1 D 2 35E 3020 2.25 10 20 1.8 U 2-1/2 35E 3024 2.70 4 8 3.2 T Fig. 35RE3- 90°Reducing Elbow 11 L' B Size Part Number A B Packing Weight �..` in in in Inner Master lb 3/4 x 1/2 35RE3006004 1.20 1.22 80 160 0.3 1 1 x 1/2 35RE3010004 1.26 1.36 70 140 0.4 ��� A 1 x 3/4 35RE3010006 1.38 1.45 50 100 0.4 ,'111111 1-1/4 x 1/2 35 R E3012004 1.34 1.53 35 70 0.5 1-1/4 x 3/4 35RE3012006 1.45 1.63 35 70 0.6 1-1/4 x 1 35RE3012010 1.58 1.67 30 60 0.7 1-1/2 x 1/2 35RE3014004 1.52 1.75 30 60 0.6 1-1/2 x 3/4 35RE3014006 1.52 1.75 25 50 0.7 1-1/2 x 1 35RE3014010 1.65 1.80 20 40 0.8 1-1/2 x 1-1/4 35RE3014012 1.82 1.88 18 36 1.0 2 x 1/2 35RE3020004 1.60 1.97 18 36 1.0 2 x 314 35RE3020006 1.60 1.97 18 36 1.0 2 x 1 35RE3020010 1.73 2.02 16 32 1.2 2 x 1-1/4 35RE3020012 1.90 2.10 12 24 1.3 2 x 1-1/2 35RE3020014 2.02 2.16 10 20 1.5 2-1/2 x 1-1/2 35RE3024014 2.16 2.51 6 12 2.2 2-1/2 x 2 35RE3024020 2.39 2.60 6 12 2.5 Fig. 35F 3-45°Elbow Size Part Number A Packing Weight \A in in Inner Master lb \, 1/2 35F 3004 0.88 150 300 0.2 A,40i 3/4 35F 3006 0.98 80 160 0.3 '� 1 35F 3010 1.13 40 80 0.5 y,4 A 1-1/4 35F 3012 1.29 25 50 0.7 �I�i IA 1-1/2 35F 3014 1.44 20 40 1.0 �� i 2 35F 3020 1.69 10 20 1.6 2-1/2 35F 3024 1.95 4 8 2.7 Fig. 35T3- Tee Size A Packing Weight __ Part Number in in Inner Master lb 'v� �A 1/2 351 3004 1.13 80 160 0.3 3/4 35T 3006 1.31 30 60 0.5 1 35T 3010 1.50 25 50 0.7 30_`.•� I 1-1/4 35T 3012 1.75 10 20 1.1 A A 1-1/2 351 3014 1.94 10 20 1.5 2 35T 3020 2.25 6 12 2.4 2-1/2 35T 3024 2.70 4 8 4.3 201 SMITH-COOPER INTERNATIONAL® • TOLL FREE 1-800-766-0076 • FAX(323)890-4456 • www.smithcooper.com I Ductile Iron Threaded Fittings - Class 300 UL/FM c ® us ® Fig. 35RT3-Reducing Tee LISTED APPROVED Size Part Number A B C Packing Weight �■�t, in in in in Inner Master lb C 3/4 x 1/2 35RT3006004 1.20 1.20 1.22 60 120 0.4 atili,. -firm.-....,,,,,...... -- ... 1 x 1/2 35RT3010004 1.26 1.26 1.36 30 60 0.6 0 i - 1 x 1/2 x 1 35RT3010004010 1.50 1.36 1.50 30 60 0.6 1 x 3/4 35RT3010006 1.38 1.38 1.45 25 50 0.6 >ii 1 x 3/4 x 3/4 35RT3010006006 1.38 1.31 1.45 35 70 0.6 B A 1 x 3/4 x 1 35RT3010006010 1.50 1.45 1.50 25 50 0.7 1-1/4 x 1/2 35RT3012004 1.34 1.34 1.53 20 40 0.8 1-1/4 x 1/2 x 1-1/4 35RT3012004012 1.75 1.53 1.75 25 50 0.9 1-1/4 x 3/4 35RT3012006 1.45 1.45 1.62 15 30 0.9 1-1/4 x 3/4 x 1-1/4 35RT3012006012 1.75 1.62 1.75 20 40 1.0 1-1/4 x 1 35RT3012010 1.58 1.58 1.67 15 30 1.0 1-1/4 x 1 x 1/2 35RT3012010004 1.34 1.26 1.53 25 50 0.7 1-1/4 x 1 x 3/4 35RT3012010006 1.45 1.38 1.63 20 40 0.8 1-1/4 x 1 x 1 35RT3012010010 1.58 1.50 1.69 20 40 0.9 1-1/4 x 1 x 1-1/4 35RT3012010012 1.75 1.69 1.75 15 30 1.0 1-1/2 x 1/2 35RT3014004 1.41 1.41 1.66 16 32 1.0 1-1/2 x 1/2 x 1-1/4 35RT3014004012 1.81 1.56 1.88 24 48 1.1 1-1/2 x 1/2 x 1-1/2 35RT3014004014 1.94 1.66 1.94 12 24 1.2 1-1/2 x 3/4 35RT3014006 1.52 1.52 1.75 16 32 1.1 F 1-1/2 x 3/4 x 1-1/4 35RT3014006012 1.94 1.66 1.88 20 40 1.1 1-1/2 x 3/4 x 1-1/2 35RT3014006014 1.94 1.75 1.94 18 36 1.2 1-1/2 x 1 35RT3014010 1.65 1.65 1.80 12 24 1.2 1-1/2 x 1 x 1/2 35RT3014010004 1.44 1.25 1.69 20 40 0.8 1-1/2 x 1 x 3/4 35RT3014010006 1.50 1.44 1.75 16 32 0.9 1-1/2 x 1 x 1 35RT3014010010 1.65 1.50 1.80 16 32 1.0 1-1/2 x 1 x 1-1/4 35RT3014010012 1.82 1.67 1.88 12 24 1.2 1-1/2 x 1 x 1-1/2 35RT3014010014 1.94 1.80 1.94 12 24 1.3 1-1/2 x 1-1/4 35RT3014012 1.82 1.82 1.88 12 24 1.4 1-1/2 x 1-1/4 x 1/2 35RT3014012004 1.41 1.34 1.66 16 32 0.9 1-1/2 x 1-1/4 x 3/4 35RT3014012006 1.52 1.45 1.75 16 32 1.0 1-1/2 x 1-1/4 x 1 35RT3014012010 1.65 1.58 1.80 16 32 1.1 1-1/2 x 1-1/4 x 1-1/4 35RT3014012012 1.82 1.75 1.88 14 28 1.3 1-1/2 x 1-1/4 x 1-1/2 35RT3014012014 1.94 1.88 1.94 14 28 1.4 2 x 1/2 35RT3020004 1.49 1.49 1.88 10 20 1.5 2x 4 3/ 35RT3020006 1.60 1.60 1.97 10 20 1.6 2 x 1 35RT3020010 1.73 1.73 2.02 8 16 1.7 2 x 1 x 2 35RT3020010020 2.25 2.02 2.25 8 16 1.9 2 x 1-1/4 35RT3020012 1.90 1.90 2.10 8 16 1.9 2 x 1-1/4 x 2 35RT3020012020 2.25 2.10 2.25 8 16 2.0 2 x 1-1/2 35RT3020014 2.02 2.02 2.16 8 16 2.1 2 x 1-1/2 x 1/2 35RT3020014004 1.49 1.41 1.88 10 20 1.3 2 x 1-1/2 x 3/4 35RT3020014006 1.60 1.52 1.97 10 20 1.4 2 x 1-1/2 x 1 35RT3020014010 1.73 1.65 2.02 8 16 1.5 2 x 1-1/2 x 1-1/4 35RT3020014012 1.90 1.82 2.10 8 16 1.7 2 x 1-1/2 x 1-1/2 35RT3020014014 2.02 1.94 2.16 8 16 1.8 Fig. 35BT3-Bull Head Tee Size part Number A B C Packing Weight "Mil; �C in in in in Inner Master lb • 3/4 x 1 35BT3006010 1.45 1.45 1.37 30 60 0.6 1 x 1-1/4 35BT3010012 1.67 1.67 1.58 20 40 0.9 ----�-- ) 1 x 1-1/2 35BT3010014 1.80 1.80 1.65 15 30 1.0 -)4------4 1-1/4 x 1 x 1-1/2 35BT3012010014 1.88 1.80 1.82 15 30 1.2 A B 1-1/4 x 1-1/2 35BT3012014 1.88 1.88 1.82 15 30 1.3 1-1/4 x 2 35BT3012020 2.10 2.10 1.90 10 20 1.6 1-1/2 x 1-1/4 x 2 35BT3014012.020 2.16 2.10 2.02 10 20 1.8 1-1/2 x 2 35BT3014020 2.16 2.16 2.02 8 16 1.8 202 SMITH-COOPER INTERNATIONAL® • TOLL FREE 1-800-766-0076 • FAX(323)890-4456 • www.smithcooper.com Ductile Iron Threaded Fittings - Class 300 UL/FM c ® us 411:0111" APPROVED A Fig. 35CP3 -Straight Coupling with Ribs LISTED ea1 Size Part Number A Packing Weight in in Inner Master lb 1/2 350P3004 1.38 200 400 0.1 3/4 35CP3006 1.63 100 200 0.2 "' '-''� 1 35CP3010 1.75 60 120 0.4 1-1/4 35CP3012 2.00 35 70 0.5 1-1/2 350P3014 2.19 25 50 0.7 2 35CP3020 2.62 15 30 1.2 2-1/2 35CP3024 3.00 9 18 2.2 Fig. 35RC3 -Hex Reducing Coupling 1111 Size A Packing Weight in Part Number in Inner Master lb �i , A 1 x 1/2 35RC3010004 1.69 80 160 0.3 1 x 3/4 35RC3010006 1.69 60 120 0.4 1-1/4 x 3/4 35RC3012006 2.06 40 80 0.6 2 x 1 (not hex) 35RC3020010 2.81 20 40 1.0 Fig. 35HB3 -Hex Bushing Size Part Number A B Packing Weight in in in Inner Master lb B 1 x 1/2 35HB3010004 1.06 1.40 180 360 0.2 1I ^A 1 x 3/4 35HB3010006 1.06 1.40 180 360 0.1 I c 1-1/4 x 1 35HB3012010 1.19 1.80 90 180 0.2 1-1/2 x 1 35HB3014010 1.25 1.95 75 150 0.4 1-1/2 x 1-1/4 35HB3014012 1.25 1.95 75 150 0.3 2 x 1 35HB3020010 1.38 2.55 40 80 0.6 2 x 1-1/4 35HB3020012 1.38 2.55 40 80 0.6 2 x 1-1/2 35HB3020014 1.38 2.55 40 80 0.6 Fig. 35SP3 -Square Head Plug Size Part Number A Packing Weight in in Inner Master lb ^ `` 2 350 700 0.1 � 1/2 35SP3004 0.94 600 1200 0.07 ` /Pi 1 35SP30101 A 3435SP3006 25 200 400 0.1 I\ dl .. 1-1/4 35SP3012 1.37 100 200 0.3 1-1/2 35SP3014 1.44 80 160 0.4 2 35SP3020 1.50 45 90 0.6 Fig. 35U 3-Union with Brass Seat A Size j A Packing Weight in Part Number in Inner Master lb 1 35U 3010 2.19 20 40 1.0 II �I 1-1/4 35U 3012 2.50 15 30 1.2 _ 1-1/2 35U 3014 2.62 10 20 1.7 ��� i 2 35U 3020 3.12 6 12 2.4 203 SMITH-COOPER INTERNATIONAL® • TOLL FREE 1-800-766-0076 • FAX(323)890-4456 • www.smithcooper.com i. • Ductile Iron Threaded Fittings - Class 300 UL/FM c ® us Af> APPROVED Fig. 35X 3- Cross LISTED A " A Size A Packing Weight Part NumberA InnerMaster, 1 35X 3010 1.50 20 40 0.9 :---I 1-1/4 35X3012 1.75 12 24 1.4 i A 1 1/2 35X 3014 1.94 8 16 1.8 k 2 35X 3020 2.25 6 12 2.8 p !N!I Li C T Fig. 35RX3-Reducing Cross E ` B _`` B ' Size A B Packing Weight UNI/a Part Number _ A in in Inner Master lb 1-1/4 x 1 35RX3012010 1.67 1.58 15 30 1.2 i__ r_l _ __ JJ in 1-1/2 x 1 35RX3014010 1.80 1.65 12 24 1.4 IA 2 x 1 35RX3020010 2.02 1.73 8 16 2.0 IFelluir" Fig. 35C 3- Cap Size Part Number A Packing Weight in in Inner Master lb A 1/2 35C 3004 0.87 300 600 0.1 3/4 35C 3006 0.97 200 400 0.1 1 35C 3010 1.16 110 220 0.2 1-1/4 35C 3012 1.28 70 140 0.4 1-1/2 35C 3014 1.33 50 100 0.5 2 35C 3020 1.45 25 50 0.8 2-1/2 35C 3024 1.70 18 36 1.6 Fig. 35BC3-Beam Clamp _ - Size A Packing Weight 1 � � in Part Number in 0 Inner Master lb 0' 3/8 A 35B03003 .75 100 200 .3 il/.r r% ll 111 1/2 35BC3004 0.75 80 160 0.5 as 49 204 SMITH-COOPER INTERNATIONAL® • TOLL FREE 1-800-766-0076 • FAX(323)890-4456 • www.smithcoopeccom TOIL Free: 6OO 626.1266 •www,pioneerplpe*com Scope Bending Test tCold3 Covers black and hot-dipped galvanized furnace butt-welded For NPS 2"and under (continuous welded)Grade A pipe. Pipe is intended Degree of Bend Diameter of Mandrel (. for mechanical and pressure applications and is acceptable Standard 90' 12 x outside pipe for ordinary uses In steam,water,gas and air lines. Pipe diameter Close Coiling 90' 8 x outside pipe Is suitable for welding,threading,grooving and bending. diameter Flattening Test Hot"Dipped Galvanized As a test for quality of the weld far pipe 2%s"NPS and larger, The average weight of zinc coating shall be not less than position the weld at 90'from the direction of force and flatten until the 1,8 oz.per sq.ft.of surface(inside and outside). OD Is%of the original outside diameter, No cracks shall occur along When galvanized pipe is bent or otherwise fabricated the inside or outside surface of the weld. to a degree which causes zinc coating to stretch or compress beyond the limit of elasticity,some flaking of the coating Frequency of Tests may occur. Tensile tests are required on each lot of 25 tons or fraction thereof of pipe NPS 1%" and smaller and from each lot of 50 tons or fraction Hydrostatic Testing thereof of pipe NPS 2 and larger. Hydrostatic lest pressures for plain-end pipe are For NPS 2W and larger,a flattening test is also required on each tot of Indicated below. 50 tons. NPS Std.Weight Extra Strong %'through 1" 700 psi 850 psi Dimensions and Weights 1'/" through 3" 1000 psi 1300 psi The dimensions and weights furnished under this specification are in • agreement with the standardized dimensions and weights specified in End Finish ASME B 36.10. Plain End: Black Plain End NPS 114"and smaller.unless otherwise specified on order, Permissible end finish shall be at the option of the manufacturer. Variations Soh.40 Soh.80 in Wall Nominal OD Weight Weight NPS 2"and larger,STD and XS weights:ends beveled Thickness Size Inches Wall Lh./Ft. Wall LbsJFt. to angle of 30',+5°,-0'with a root face of Yu"±!,f2" 'I, .405 .068 .24 .095 .31 Minimum wall thick- t,° .540 .088 .43 .119 .54 °/a .675 .091 .57 .128 .74 • Threaded:To ANSI Standard B 1.20.1 ness at any point shall 'I? .840 .109 .85 .147 1.09 not be more than V.' 1.050 .113 1.13 .154 1.48 • Couplings:To ASTM Standard A 865 1' 1.315 .133 1.68 .179 2.17 12.5%under nominal 1'A° 1.880 .140 2.27 .191 3.00 114 1.900 .145 2.72 .200 3.63 Chemical Requirements wall thickness 2" 2.376 .154 3.86 .218 5.03 2/2" 2.875 .203 6,80 .276 7.67 Composition,max.% specified. 3" 3.600 .218 7.58 .300 10.26 Carbon Manganese Phosphorus Sulfur 30 1.20 .05 .045 Permissible Variations In Outside Diameter NPS 1'/2"and under: ±.016" *Copper *Nickel Igirgmlom "Molybdenum "Vanadium 40 .40 .40 .15 Og NPS 2"and over: ±1% *The combination of these five elements shall not exceed 1.00%. Permissible Variations Weight Per Foot Pipe shall not vary more than t 10%from the standard specified. Tensile Requirements Product Marking Tensile Strength,min. 48,000 psi Each length of pipe'/' NPS and larger is continuously stenciled to ' Yield Strength,min. 30,000 psi show the manufacturer,the grade of pipe(ASTM A53),the kind of pipe Elongation In 2" Refer to A53 Table X4.1 (F for continuous weld,A for Grade A),the size,XS for extra strong, and length. Legal Notice:This brochure is Intended for general information only. Pioneer makes no warranty or representation,expressed or implied,of any kind with respect to the information contained herein and shall in no event assume liability or responsibility for any loss,damage or Injury whatsoever resulting from the use of this information. In all cases,the customer is therefore requested to use this Information at its own risk and responsibility, CR D Y , ; 115 Standard Duty 1i1, '+d�`(t ltfl(�ra3�1 t1£1, 3 �1. Loo Han er wrl `!t fit`li r11 fiM t o x rrrb 't?i,?i �'t `i�rt tl€�� ;t�i. ldstrl,�alid�'gf1�#r�t�'�x tr�liit,' n�tiu r+�',�i r6�f1$?� wiii Features "i The 115 Standard Duty Loop Nit • Flared edges help Hanger, part of the CADDY® line RS '%'` prevent any sharp of fasteners and supports from ;` Ill F i surfaces from coming ERICO, is ideal for suspending itqf into contact with the stationary, non-insulated pipe c pipe (1/2" to 4" sizes) lines, including CPVC pipes, in B A fire sprinkler systems. A knurled /., • Retained insert nut insert nut helps simplify vertical OD helps ensure the loop adjustments and flared edges on „ hanger and insert the base(1/2" to 4" sizes) help x nut stay together protect pipes from coming into ,,, ..:F t.,r,: F • Recommended for contact with any sharp edges of the suspension of the hanger. stationary non- insulated pipe lines Material: Steel • Manufactured to Finish: Pre-galvanized APP> c®us NW use the minimum Outer Rod Static rod size permitted Part Pipe Diameter Size A B C Load by NFPA® for fire Number Size OD RS F sprinkler piping 1150050EG 1/2" 0.840" 3/8" 2 13/16" 1 1/8" 1" 300 lb 1150075EG 3/4" 1.050" 3/8" 3" 1 3/16" 15/16" 300 lb • Conforms with 1150100EG 1" 1.315" 3/8" 3 1/4" 1 3/8" 15/16" 300 lb Federal Specification 1150125EG 1 1/4" 1.660" 3/8" 3 9/16" 1 1/2" 15/16" 300 lb rs ,f;aala,i,ln;j, WW-H-171 (Type 1150150EG 1 1/2" 1.900" 3/8" 3 13/16" 1 5/8" 15/16" 300 lb a=; lid i#i('- 10), Manufacturers 1150200EG 2" 2 3/8" 3/8" 4 1/4" 1 7/8" 15/16" 300 lb Standardization 1150250EG 2 1/2" 2 7/8" 3/8" 5 9/16" 2 13/16" 1 9/16" 525 lb Society (MSS) SP-58 1150300EG 3" 3 1/2" 3/8" 6 9/16" 3 1/2" 1 15/16" 525 lb r ` rl ` ' ,; and SP-69 (Type 10) 1150350EG 3 1/2" 4" 3/8" 7 1/16" 3 3/4" 1 15/16" 585 lb 1)a �,s$flifls# w R,.,;`w 1150400EG 4" 41/2" 3/8" 79/16" 4" 1 15/16" 6501b ft 1,,.tt `,+r, €ititi Th,,!,1114rhlst. ms 1150500EG 5" 5 9/16" 1/2" 9 13/16" 4 3/4" 2 1/4" 1,000 lb 1 'fr rj d1a°i;'" 1150600EG 6" 6 5/8" 1/2" 11 5/16" 6 5/16" 3 5/16" 1,000 lb t:i 4'„, }0fi; 1150800EG 8" 8 5/8" 1/2" 12 7/8" 6 7/8" 2 7/8" 1,000 lb 1?1t'rttilltdfT 1 I. j"t1t Jjt!/I . am arigi, 1,4 IIl Surge Restraint Features • Surge restraint for 115 standard duty loop hangers ;>y°f # Specifications Material:Steel s, Finish: CADDY®ARMOUR Part Number Pipe Size - SR6 1/2" —2" t. 1 cULus and UL are registered certification marks of UL LLC. FM is a registered certification mark of M FM Approvals LLC,LTD. NFPA is a registered trademark of National Fire Protection Association,Inc. WARNING WI ERICO products shall be installed and used only as indicated in ERICO's product instruction sheets and training materials.Instruction sheets are available at www.erico.com and from your ERICO customer service representative.Improper installation,misuse,misapplication or other failure to completely follow ERICO's instructions and warnings may cause product malfunction,property C7IDDydamage,serious bodily injury and death. Copyright 0 2014 ERICO International Corporation.All rights reserved. Q CADDY,CADWELD,ademar s of EC,ERICO, Corporation. and LENTON are ERICD® 10' ' Ilk(� • registered trademarks of ERICO International Corporation. www.erico.com M1186S-NAEN M115LT14NAEN 05M0414 R 300 Universal Beam Clamp iot 4.4), 4". , i' t Features • Conforms with Federal Specification WW-H-171 (Type 23), Manufacturers Standardization Society ANSI®/MSS-SP-58 (Type 19 and 23), install in accordance with ANSI/MSS-SP-69 ' Y 30 sc 4-- F• Rs ri in Specifications Material: Steely c®us Rod Size Flange Screw Torque Static Static Standard Listings Part Number RS Thickness A Diameter TQ Load 1 Load 2 Packaging Approvals FT Sc F1 F2 Quantity Finish:Electro-galvanized 3000037EG 3/8" 13/16" Max 1 1/8" 3/8" 5 ft lb 500 lb 250 lb 100 pc cUL, UL, FM 3000050EG 1/2" 13/16" Max 1 1/8" 7/16" 8 ft lb 950 lb 760 lb 50 pc cUL, UL, FM 3000062EG 5/8" 13/16" Max 1 1/8" 3/8" 5 ft lb 950 lb 760 lb 50 pc cUL, UL 3000075EG 3/4" 13/16" Max 1 1/8" 3/8" 5 ft lb 950 lb 760 lb 50 pc cUL, UL 3000087EG 7/8" 13/16" Max 1 1/8" 3/8" 5 ft lb 950 lb 760 lb 50 pc cUL,UL Finish:Plain 3000037PL 3/8" 13/16" Max 1 1/8" 3/8" 5 ft lb 500 lb 250 lb 100 pc cUL,UL, FM 3000050PL 1/2" 13/16" Max 1 1/8" 7/16" 8 ft lb 950 lb 760 lb 50 pc cUL,UL,FM 3000062PL 5/8" 13/16" Max 1 1/8" 3/8" 5 ft lb 950 lb 760 lb 50 pc cUL, UL 3000075PL 3/4" 13/16" Max 1 1/8" 3/8" 5 ft lb 950 lb 760 lb 50 pc cUL,UL xi m 3000087PL 7/8" 13/16" Max 1 1/8" 3/8" 5 ft lb 950 lb 760 lb 50 pc cUL, UL zi Setscrew must be tightened and torqued onto the sloped side of the I-beam. D Recognizing that torque wrenches are generally not used or available on many job sites,the setscrew should be tightened so it contacts the I-beam and then an additional 1/4 to 1/2 turn added. D D 1 zT A n C71DDY. 44 www.erico.com