EQUIPMENT SUBMITTAL
CO® Worldwide www.tyco-fire.com
Contacts
Series RFII — 5.6 K-factor
"Royal Flush II" Concealed Pendent Sprinklers
Quick & Standard Response, Standard Coverage
General The Series RFII Sprinklers are shipped
with a Disposable Protective Cap.The
Description Protective Cap is temporarily removed
during installation and replaced to help
The TYCO Series RFII 5.6 K-factor, protect the sprinkler during ceiling
"Royal Flush II" Concealed Pendent installation or finish.The tip of the Pro
Sprinklers Quick Response (3 mm tective Cap can be used to mark the ( �t
bulb) and Standard Response (5-mm center of the ceiling hole into plaster -
bulb), are decorative sprinklers fea board or ceiling tiles by gently pushing _ 4,
turing a flat cover plate designed to the ceiling product against the Pro- —.,,�,
conceal the sprinkler.These sprinklers tective Cap. When ceiling installa
are optimal for architecturally sensi tion is complete, the Protective Cap is
tive areas such as hotel lobbies, office removed and the Cover Plate/Retainer
buildings, churches,and restaurants. Assembly is installed.
Each sprinkler includes a Cover Plate/ As an option,the Series RFII Standard
Retainer Assembly and a Sprinkler/ Response(5-mm bulb)"Royal Flush II"
Support Cup Assembly. The separa-
Concealed Pendent Sprinklers can be
ble, two-piece assembly design pro fitted with a silicone Air and Dust Seal. Technical
vides the following benefits: (Refer to Figure 5.) The Air and Dust
Seal is intended for sensitive areas Data
• Allows installation of the sprinklers where it is desirable to prevent air and
and pressure testing of the fire pro- dust from the area above the ceiling to Sprinkler Approvals
tection system prior to installation of pass through the cover plate. Approvals apply only to the service
a suspended ceiling or application of conditions indicated in the Design Criteria
the finish coating to a fixed ceiling. NOTICE section.
• Permits the removal of suspended The Series RFII Concealed Pendent • TY3531 (3 mm Bulb)is UL Listed,C-UL
ceiling panels for access to building Sprinklers described herein must be Listed and NYC Approved(MEA 353-
service equipment without having installed and maintained in compliance 01-E)as Quick Response.
to first shut down the fire protection with this document and with the appli- • TY3531 (3 mm Bulb)is VdS Approved
system and remove sprinklers. cable standards of the NATIONAL FIRE (Certificate No.G4090007).
mm)ofPROTECTION ASSOCIATION (NFPA),
• Provides for 1/2 in.
(12,7 ver- • TY3531 (3 mm Bulb)is FM and
tical adjustment to allow a measure in addition to the standards of any LPCB Approved(Ref.No.094a/10)as
of flexibility in determining the length authorities having jurisdiction. Failure Standard Response.
of fixed piping to cut for the sprinkler to do so may impair the performance
drops. of these devices. Note:FM and LPCB do not approve
concealed sprinklers for quick
The owner is responsible for maintain- response.
ing their fire protection system and
devices in proper operating condition. • TY3551 (5 mm Bulb)is UL Listed,C-UL
The installing contractor or sprinkler Listed,FM Approved,LPCB Approved
manufacturer should be contacted with (Ref.No.094a/9),and NYC Approved
any questions. (MEA 353-01-E)as Standard Response.
IMPORTANT Approvals for Air and Dust Seal
Refer to Technical Data Sheet Sprinkler UL and C-UL Listed for use with the RFII
•
TFP2300 for warnings pertaining to Standard Response Concealed Sprinkler
regulatory and health information. Identification (TY3551)
Always refer to Technical Data Maximum Working Pressure
Sheet TFP700 for the "INSTALLER Number (SIN) Maximum 250 psi(17,3 bar)by UL,
WARNING" that provides cautions C-UL,and NYC
with respect to handling and instal- TY3531 — 3 mm bulb Maximum 175 psi(12,1 bar)by FM,VdS,
lation of sprinkler systems and com- TY3551 — 5 mm bulb and LPCB
ponents. Improper handling and Temperature Rating
installation can permanently damage 155°F(68°C)Sprinkler with
a sprinkler system or its compo- 139°F(59°C)Cover Plate
nents and cause the sprinkler to fail
to operate in a fire situation or cause 200°F(93°C)Sprinkler with
it to operate prematurely. 165°F(74°C)Cover Plate
Page 1 of 4 SEPTEMBER 2018 TFP181
.0
TFP181
Page 2 of 4
Discharge Coefficient 1/2"NPT SEALING
K=5.6 GPM/psi112(80,6 LPM/barti2) ASSEMBLY
Adjustment
1/2 inch(12,7 mm)
Finishes FRAME ��
See the Ordering Procedure section. ."\ A I CAP
Physical Characteristics
Frame Bronze
Support Cup Plated Steel SUPPORT
Guide Pins Stainless Steel CUP WITH I BULB
Deflector Bronze ROLL FORMED
Compression Screw Brass THREADS
Bulb Glass
Cap Bronze or Copper ra R
Sealing Assembly..Beryllium Nickel w/TEFLON I I COMPRESSION
Cover Plate Brass — SCREW
Retainer Brass GUIDE
Ejection Spring Stainless Steel PINS(2) _
Design DEFLECTOR
(DROPPED
Criteria DEFLECTOR c_ J _D POSITION)
The TYCO Series RFII 5.6 K-factor, 1 r
"Royal Flush II" Concealed Pendent SPRINKLER/SUPPORT CUP
1 Sprinklers are intended for fire protec- ASSEMBLY
tion systems designed in accordance
with the standard installation rules THREAD INTO P I RETAINER
recognized by the applicable Listing SUPPORT ) I WITH THREAD
1 or Approval agency; for example, UL CUP UNTIL \ 0 0 DIMPLES
j Listing is based on NFPA 13 and VdS MOUNTING
Approval is based on the CEA 4001. SURFACE IS EJECTION
FLUSH WITH SPRING
For more information on LPCB and VdS CEILING
Approvals,contact Johnson Controlss
at the following office:
Enschede, Netherlands r�/1111111111111IIMIIIIIIIIIIIK —of
Telephone:31-53-428-4444
Fax:31-53-428-3377 SOLDER J COVER
The Series RFII Concealed Pendent TABS(3) COVER PLATE/RETAINER PLATE
Sprinklers are only listed and approved ASSEMBLY
with the Series RFII Concealed Cover FIGURE 1
Plates having a factory applied finish. MODEL RFII CONCEALED SPRINKLER
ASSEMBLY
NOTICE
Do not use the Series RFII in applica- Installation Do not attempt to compensate for
tions where the air pressure above the insufficient adjustment in the Sprinkler
ceiling is greater than that below.Down The TYCO Series RFII 5.6 K-factor, by under-or over-tightening the Sprin-
drafts through the Sprinkler/Support "Royal Flush II" Concealed Pendent kler/Support Cup Assembly. Re-adjust
Cup Assembly can delay sprinkler Sprinklers must be installed in accor- the position of the sprinkler fitting to
operation in a fire situation. dance with this section. suit.
Step 1. Install the sprinkler only in the
Operation General Instructions•
not install any bulb type sprinkler pendent position with the center-line
if the bulb is cracked or there is a loss of the sprinkler perpendicular to the
When exposed to heat from a fire, the mounting surface.
Cover Plate, normally soldered to the of liquid from the bulb. With the sprin-
Retainer at three points, falls away to kler held horizontally,a small air bubble Step 2.Remove the Protective Cap.
expose the Sprinkler/Support Cup should be present.The diameter of the Step 3. With pipe thread sealant
Assembly. air bubble is approximately 1/16 inch applied to the pipe threads, hand-
(1,6 mm)for the 155°F(68°C)and 3/32 tighten the sprinkler into the sprinkler
The Deflector — supported by the inch(2,4 mm)for the 200°F(93°C)tem- fitting.
Guide Pins — then drops down to its perature ratings. Step 4. Wrench-tighten the sprinkler
operational position. using only the RFII Sprinkler Wrench.
I A leak-tight 1/2 inch NPT sprinkler Refer to Figure A I the RFII
The glass bulb contains a fluid that joint should be obtained by applying a ( g 3.) pp y
Sprinkler Wrench to the Sprinkler as
expands when exposed to heat.When minimum to maximum torque of 7 to 14
the rated temperature is reached, the ft.-lbs. (9,5 to 19,0 Nm). Higher levels shown in Figure 3.
fluid expands sufficiently to shatter the of torque can distort the sprinkler Inlet
glass bulb,activating the sprinkler and with consequent leakage or impairment
allowing water to flow. of the sprinkler.
TFP181
Page 3 of 4
FACE OF CLEARANCE HOLE _..._ CLEARANCE
SPRINKLER DIAMETER HOLE
` FITTING DIMENSION C J
cs 1 SPRINKLER ��1
SUPPORT CUP
ASSEMBLY 1 IrI
1THREADED)DADJUSTMENTi „■'• i i
FACEOF CEILING,
RETAINING RING ""'�� A
MOUNTING j
SURFACE / FIGURE 4
` I / DISPOSABLE PROTECTIVE CAP
______ L-7-1
Step 5. Replace the Protective Cap
by pushing it upwards until it bottoms
out against the Support Cup. (Refer
T to Figure 4.)The Protective Cap helps
3/16"to 11/16" MANUFACTURER DEFLECTOR COVER PLATE prevent damage to the Deflector and
(4,8 to 17,5 mm) PRESET GAP IN DROPPED RETAINER Arms during ceiling installation and/or
REFERENCE 3/32" (2,4 mm) POSITION ASSEMBLY finish.You can also use the Protective
Cap to locate the center of the clear-
COVER PLATE COVER PLATE ance hole by gently pushing the ceiling
ttt PROFILE DEPTH DIAMETER material up against the center point of
DIMENSION B DIMENSION A the Protective Cap.
A:3-1/4 inches(82,6 mm) C:2-3/8 to 2-5/8 inches(60,3 to 66,7 mm) NOTICE
B:3/16 inches(4,8 mm) D:1-3/4 to 2-1/4 inches(44,5 to 57,2 mm) As long as the Protective Cap remains
in place, the system is considered "Out
FIGURE 2 of Service". .
SERIES CONCEALED SPRINKLER INSTALLATION DIMENSIONS Step 6. After the ceiling has been
completed with the 2-1/2 in.(63,5 mm)
diameter clearance hole and in prep-
-- aration for installing the Cover Plate/
Retainer Assembly,remove and discard
l=t FRAME j=l the Protective Cap. Verify that the
,� ARM % �_ 11 Deflector moves up and down freely.
/ \ �, If the Sprinkler is damaged and the
III
SUPPORT / ' Deflector does not move up and down
freely, replace the entire Sprinkler.
,) CUP j ' Do not attempt to modify or repair a
�' ' ) iiavit1
damaged sprinkler.
=-- _ Step 7. When installing an Air and
I■I Dust Seal,refer to Figure 5; otherwise,
proceed to Step 8. To attach the Air
7/8"(23 mm) and Dust Seal, verify the angle of the
SQUARE outside edge of the seal is oriented -
according to Figure 5.Start the edge of
_ the Retainer in the grooved slot of the
ALIGN �� Air and Dust Seal and continue around
ARROWS WITH /// 1 1 the retainer until the entire Air and Dust
FRAME ARMS // al Seal is engaged.
r
ACCEPTS \
0 1/2"SOCKET \ —r
DRIVE \
FIGURE 3
RFII SPRINKLER WRENCH
I
b
TFP181
Page 4 of 4
Step 8. Screw on the Cover Plate/ SUPPORT SPRINKLER FACE OF ORIENT
Retainer Assembly until the Retainer CUP CEILING SEAL
(shown in Figure 2)or the Air and Dust BEVEL AS
Seal (shown in Figure 5) contacts the 11�1,__ SHOWN
ceiling.Do not continue to screw on the 1 COVER -j�
Cover Plate/Retainer Assembly so that � d ; PLATE
it lifts a ceiling panel out of its normal RETAINER
position. If you cannot engage the ); ASSEMBLY • •
Cover Plate/Retainer Assembly with :� /
the Support Cup or you cannot engage
1 - the Cover Plate/Retainer Assembly suf-ficiently to contact the ceiling,you must �yreposition the Sprinkler Fitting. AP4
'• ,fir. ��/ ANDDUST
�'_� �__ SEAL
�- _maimir LIP OF COVER
Care and RETAINER PLATE
FIGURE 5
Maintenance OPTIONAL AIR AND DUST SEAL FOR SERIES RFII(TY3551)
The TYCO Series RFII 5.6 K-factor, Care must be exercised to avoid
"Royal Flush II" Concealed Pendent damage to the sprinklers - before, Ordering
Sprinklers must be maintained and during, and after installation. Sprin-
serviced in accordance with this klers damaged by dropping, striking,l' Procedure
section. wrench twist/slippage,or the like,must
Before closing a fire protection system be replaced. Also, replace any sprin- Contact your local distributor for
main control valve for maintenance kler that has a cracked bulb or that has availability. When placing an order,
work on the fire protection system lost liquid from its bulb. (Ref. Installs indicate the full product name.
I that it controls, obtain permission to tion Section.) Sprinkler/Support Cup Assembly
shut down the affected fire protection Specify: Series RFII (specify SIN),
l Exercise care to avoid damage to sprin-
system from the proper authoritiesK=5.6, "Royal Flush II" Pendent Sprin-
klers before, during, and after instal- klers(specify)temperature rating,P/N*
and notify all personnel who may be by dr. Replace sprinklers damaged ( p y) p
affected by this action. by dropping, striking, wrench twist- (specify):
Absence of the Cover Plate/Retainer ing, wrench slipping, or the like. Also, 155°F(68°C) 200°F(93°C)
Assembly can delay sprinkler opera replace any sprinkler that has a cracked TY3531 51-792-1-155 51-792-1-200
TY3551 51-790-1-155 51-790-1-200
tion in a fire situation. bulb or that has lost liquid from its bulb.
(Refer to the Installation section.)
When properly installed, there is a - Use Suffix"I"for ISO 7-1 connection;for example,
nominal 3/32 in. (2,4 mm) air gap If you must remove a sprinkler, do not 51-792-1-155-I
between the lip of the Cover Plate and reinstall it or a replacement without Separately Ordered Cover Plate/
the ceiling, as shown in Figure 2. reinstalling the Cover Plate/Retainer Retainer Assembly:
Assembly. If a Cover Plate/Retainer rating from
This air gap is necessary for proper Assembly becomes dislodged during below)Specify:S (temperaturees RFII Concealed Coverrm
operation of the sprinkler. If the ceiling service,replace it immediately.
1 requires repainting after sprinkler Plate with (finish), P/N (specify).
installation, ensure that the new paint The owner is responsible for the 139°F(59°C)(a) 165°F(74°C)(b)
inspection,testing,and maintenance of
does not seal off any of the air gap. Grey White
their fire protection system and devices (RAL9002) 56-792-0-135 56-792-0-165
Do not pull the Cover Plate relative to in compliance with this document, as Brass 56-792-1-135 56-792-1-165
the Enclosure.Separation may result. well as with the applicable standards pure White(c)
Sprinklers of the NATIONAL FIRE PROTECTION (RAL9010) 56-792-3-135 56-792-3-165
whichare found to be
{ king exhibiting visible signs ASSOCIATION,for example, NFPA 25, Signal White
corrosionor must be replaced. in addition to the standards of any other (RAL9003) 56-792-4-135 56-792-4-165
authorities having jurisdiction.Contact Jet Black
Isi Automatic sprinklers must never be the installing contractor or sprinkler (RAL9005) 56-792-6-135 59-792-6-165
painted, plated, coated, or other- manufacturer regarding any questions. Bsh
Chromerued 56-792-8-135 56-792-8-165
• wise altered after leaving the factory. Automatic sprinkler systems should be Chrome 56-792-9-135 56-792-9-165
Modified sprinklers must be replaced. inspected,tested,and maintained by a Custom 56-792-X-135 56-792-X-165
I Sprinklers that have been exposed to qualified Inspection Service in accor
corrosive products of combustion, but dance with local requirements and/or (a) For use with 155°F(68°C)sprinklers.
have not operated,should be replaced national code. (b) For use with 200°F(93°C)sprinklers.
if they cannot be completely cleaned (c) Eastern Hemisphere sales only.
by wiping the sprinkler with a cloth or Limited S rmkler Wrench
by brushing it with a soft bristle brush. p
Specify: RFII Sprinkler Wrench,
Warranty P/N 56-000-1-075
For warranty terms and conditions,visit Air and Dust Seal
www.tyco-fire.com. Specify:Air and Dust Seal,
P/N 56-908-1-001
111
i 1400 Pennbrook Parkway,Lansdale,PA 194461 Telephone 41-215-362-0700 /,�j
0 2018 Johnson Controls.All rights reserved.All specifications and other information shown were current as of document revision date and are subject to change without notice. Johnson r�Isoi^1 ) °
NATIONAL FIRE PROTECTION ASSOCIATION and NFPA are registered trademarks of National Fire Protection Association Controls
TEFLON is a registered trademark of DuPont Controls
1{.1
Eddyth read 40
A Lightweight Schedule 40 Replacement Pipe
That Has a Corrosion Resistance Ratio of 1.0
Bull Moose Tube Company has been making pipe for a long time and is recognized as a producer of quality pipe
products. Eddythread 40 is designed with the same thoroughness as our other fine pipe products and now our
customers have an option to buy a carefully designed replacement for Schedule 40 that:
• Has a Corrosion Resistance Ratio of 1.0
• Has a Pressure Rating of 300 psi
• Is Lighter Weight Than Schedule 40
• Is Approved by Factory Mutual and Listed by Underwriters Laboratories
• Is Produced in Accordance to ASTM A-135 and A-795
• Can be Used With Standard Schedule 40 Threaded Fittings,
Couplings and Valves
• Is Produced From Steel With Excellent Properties of
Strength and Threadability
• Can be Used in Wet, Dry, Preaction, and Deluge Type Sprinkler Systems*
• Offers Lower Freight Costs
EDDYTHREAD 40 SPECIFICATIONS
NOMINAL PIPE SIZE (in)
1 1.461 1.083 70
1 1/4 2.070 1.418 51
1 1/2 2.547 1.654 44
2 3.308 2.123 30
CORROSION RESISTANCE RATIOS
1 1.00 1.00
1 1/4 1.00 1.00
1 1/2 1.00 1.00
2 1.00 1.00
*Eddythread 40 can be hot dipped galvanized to meet FM's requirement for dry systems
Q11 ClarksonRoad For additional information, C �I. us
/� Chesterfield,MO 63017 contact your salesperson today at
1 f BULL MOOSE TUBE COMPANY (800)325-4467 (800)325-4467 or(636)537-2600 LISTED
FAX:(636)537-2645 in the USA,or from Canada
www.bullmoosetube.com call(800)882-4666
A C A O company e-mail:sales@bullmoosetube.com
APPROVED
All information contained herein is accurate as known at the time of publication. Bull Moose Tube reserves the right to change product specifications without notice and without incurring obligation.
8/08
Ductile Ir on Threaded •Fittings
.... ."„....,,,,,,....,,,,...:...,. .:........
, . ,...- -- . ..,:44,,, \-,... ..,-
-..„ ,..„
as#x TF_ . .
:.
..
tfrig
i yY ,- c p<,.-" fir" r i -at z ,
i
i.s+ :-t nia Ae4I16"4 7]i � " 1 32
3r .
r t ;' t -. -''r i #Ate :L 't"rt..€e: b, �,f ��i ',s
�r,, - - > r r n s
y
iii,i-i 1,'.,'iri:&'r,,.-i,i t9i'a.r
YY Y
> t: t «tea t . e-
}gam .1, }Y f-f }y. i•!v)
1
g e I.
gam. `.
INTERNATIONALSMITH ,, COOPER
Ductile Iron Threaded Fittings
Specifications
• CT branded ductile iron threaded fittings are UL Listed and FM Approved at 500 psi
• Rated to 300 WSP
(111.)
Ductile iron castings conform to ASTM A536 G US
• LISTED
• Fitting dimensions conform to ASME B16.3
• Bushings and plugs conform to ASME B16.14
• Fittings are 100% air tested APPROVED
• NPT threads on all fittings conform to ASME B 1.20.1
• Independent lab verification that fittings meet applicable chemical&physical properties
•
• Manufacturing facilities are ISO 9001:2008 and ISO 14001
Temperature Working Pressure, Nonshock psiG
Degrees F 300# Class Threaded Fittings
-20 to 100 500
150 500
200 480
250 460
300 440
350 420
400 400
450 380 •
500 360
550 340
600 320
650 300
,r , r ��` Ouch a ron fittings- ass I I I
c (11/1,) us 44*
APPROVED
Fig. 35E 3- 90°Elbow LISTED
A Size A Packing Weight
Part Number
�. in in Inner Master lb
y 1/2 35L 3004 13 100 200 0.2
1 3/4 35E 3006 1.31 70 140 0.3
A 1 35E 3010 1.50 40 80 0.5
1___ _ 1-1/4 35E 3012 1.75 25 50 0.8
1-1/2 35E 3014 1 94 18 36 1.1
2 35E 3020 2.25 10 20 1.8
2-1/2 35E 3024 2.70 4 8 3.2
Fig. 35RE3- 90°Reducing Elbow
liltB Size A B Packing Weight
likr-� in Part Number in in Inner Master lb
3/4 x 1/2 358E3006004 1.20 22 80 160 0.3
1 x 1/2 35RE3010004 1.26 1.36 70 140 0.4
1 i
111,
1 x 3/4 35RE3010006 1.38 1.45 50 100 0.4
JIA
1-1/4 x 1/2 35RE3012004 1.34 1.53 35 70 0.5
1-1;4 x 3/4 35RL3012006 1.45 1.63 35 70 0.6
1-1/4 x 1 35RE3012010 1.58 1.67 30 60 0.7
1-1/2x 1/2 35RL3014004 1.52 1.75 30 60 0.6
1-1/2 x 3/4 35RE3014006 1.52 1.75 25 50 0.7
1-1/2 x 1 35RL3014010 1 65 1.80 20 40 0.8
1-1/2 x 1-1/4 35RE3014012 1.82 1.88 18 36 1.0
- 2 x 1/2 35RL3020004 1.60 1 97 18 36 1.0
2 x 3/4 35RE3020006 1.60 1.97 18 36 1.0
2 x 1 35RL3020010 1.73 2-02 16 32 1-2
2 x 1-1/4 35RE3020012 1.90 2.10 12 24 1.3
D 2 x 1-1/2 3511E3020014 2.02 2.16 10 20 1.5
U 2-1/2 x 1-1/2 35RE3024014 2.16 2.51 6 12 2.2
C 2-1/2 x 2 35RE3024020 2.39 2.60 6 12 2.5
T
Fig. 35F 3-45°Elbow
L. Size A Packing WeightPart Number
lA in in Inner _ Master lb
�, 1/2 35F 3004 0.88 150 300 0.2
3/4 35F 3006 0.98 80 160 0.3
1 35f 3010 1.13 40 80 0.5
1-1/4 35F 3012 1.29 25 50 0.7
IA 1-1/2 351- 3014 1.44 20 40 1.0
2 35F 3020 1.69 10 20 1.6
2-1/2 35F 3024 1.95 4 8 2.7
Fig. 35T 3- Tee
Size A Packing Weight
Part Number
in in Inner Master lb
J111111 1/2 351 300•1 1.13 80 160 0.3
3/4 35T 3006 1.31 30 60 0.5
1 351 3010 1 50 75 50 0.7
c.,®..,lilt v(L1-1/4 35T 3012 1.75 10 20 1.1
A Ne ) I-1/2 351 3014 1.94 10 20 1.5
2 af'35T 3020 2.25 6 12 2.4
2-1/2 351 3024 2.70 4 8 4.3
Ill SMITH-COOPER INTERNATIONAL® • TOLL FREE 1-800-766-0076 • FAX(323)890-4456 • www.smithcooper.com
i
`�l'''' Ductile Iron Fittings- Class 300 UL/FM
1 _QUALM PLUS_
c ® us 411100...
APPROVED
Fig. 35RT3-Reducing Tee LISTED
a -
Size Part Number A B C Packing Weight
in in in in Inner Master lb
C 3/4 x 1,') 35RT3006004 1.20 20 1 22 60 120 0.4
1 x 1(2 35RT3010004 1.26 1.26 1.36 30 60 0.6
x 1/2_x 1 35RT3010004010 50 1.36 50 30 60 0.6
1 x 3/4 35RT3010006 1.38 1.38 1.45 25 50 0.6
1 x 3/4 x 3/4 358 13010006006 1,38 1.31 1.45 35 70 0.6
B A 1 x 3/4 x 1 35RT3010006010 1.50 1.45 1.50 25 50 0.7
1-1/4 x 1/2 350 13012004 1.34 1.34 1.53 20 40 0.8 •
1-1/4 x 1/2 x 1-1/4 35RT3012004012 1.75 1.53 1.75 25 50 0.9
1 1/4 x 3/4 3513313012006 1-45 1.45 1.62 15 30 0.9
1-1/4 x 3/4 x 1-1/4 35RT3012006012 1.75 1.62 1.75 20 40 1.0
1 1/4 x 1 35813012010 1.58 1,58 1.67 15 30 1.0
1-1/4 x 1 x 1/2 35RT3012010004 1.34 1.26 1.53 25 50 0.7
1 1/4 x 1 x 3/4 35R13012010006 1.45 1.38 1.63 20 40 0.8
1-1/4 x 1 x 1 35RT3012010010 1.58 1.50 1.69 20 40 0.9
1 114 x 1 x 1-1/4 35813012010012 1.75 1.69 1.75 15 30 1.0
1-1/2 x 1/2 35RT3014004 1.41 1.41 1.66 16 32 1.0
1-1/2x 1/2x 1-1/4 35RT3014004012 1.81 1.56 1,88 74 48 1.1
1-1/2 x 1/2 x 1-1/2 35RT3014004014 1.94 1.66 1.94 12 24 1.2
1-1/2 x 3/4 35013014006 1.52 1.52 1.75 16 32 1.1
1.1/2 x 3/4 x 1-1/4 35RT3014006012 1.94 1.66 1.88 20 40 1.1
1-1/2x3/4x 1-1/2 35RT3014006014 1.94 1.75 1.94 18 36 1.2
1-1/2 x 1 35RT3014010 1.65 1.65 1.80 12 24 1.2
1-1/2 x 1 x 1/2 35813014010004 1.44 1.25 1.69 20 40 0.8
1-1/2 x 1 x 3/4 35RT3014010006 1.50 1.44 1.75 16 32 0.9
1-1/2 x 1 x 1 35R13014010010 1.65 1.50 1.80 16 32 1.0
1-1/2 x 1 x 1-1/4 35RT3014010012 1.82 1.67 1.88 12 24 1.2
1-1/2 x 1 x 1-1/2 35813014010014 1 94 1.80 1.94 12 24 1.3 .
1-1/2 x 1-1/4 35RT3014012 1.82 1.82 1.88 12 24 1.4
1-1/2 x 1 1/4 x 1/2 35813014012004 1.41 1.34 1.66 16 32 0.9
1-1/2 x 1-1/4 x 3/4 35RT3014012006 1.52 1.45 1.75 16 32 1.0
1-1/2 x 1 1/4 x 1 351313014012010 1,65 1.58 1.80 16 32 1.1
1-1/2 x 1-1/4 x 1-1/4 35RT3014012012 1.82 1.75 1.88 14 28 1.3
1-1/2 x 1-1/4 x 1-1/2 3581[3014012014 1 94 1.88 1.94 14 28 1.4
2 x 1/2 35RT3020004 1.49 1.49 1.88 10 20 1.5
2 x 3/4 351113020006 1.60 1 60 1.97 10 20 1.6
2 x 1 35RT3020010 1.73 1.73 2.02 8 16 1.7
2 x 1 x 2 35R13020010020 2.25 2 02 2.25 8 16 1.9
2 x 1-1/4 35RT3020012 1.90 1.90 2.10 8 16 1.9
2 x 1 1/4 x 2 35RT3020012020 2.25 2.10 2.25 8 16 2.0
2 x 1-1/2 35RT3020014 2.02 2.02 2.16 8 16 2.1
2 x 1-1/2 x 1/2 35813020014004 1.49 1.41 1.88 10 20 1.3
2 x 1-1/2 x 3/4 35RT3020014006 1.60 1.52 1.97 10 20 1.4
2 x 1 1/2 x 35R13020014010 1.73 1.65 2.02 8 16 1.5 '
2 x 1-1/2 x 1-1/4 35RT3020014012 1.90 1.82 2.10 8 16 1.7
2 x 1-1/2 x 1-1/2 35843020014014 2.02 1.94 2.16 8 16 1.8
Fig. 35BT3-Bull Head Tee
, Size Part Number A B C Packing Weight
J �� in in in in Inner Master lb
� �C 3/4 x 1 35BT3006010 1 45 1 45 1.37 30 60 0-6
• -11 1JJ 1 x 1-1/4 35BT3010012 1.67 1.67 1.58 20 40 0.9
1 x 1-1/2 351313010011 1.80 1,80 1.65 15 30 1 0
A It B > 1-1/4 x 1 x 1-1/2 35B13012010014 1.88 1.80 1.82 15 30 1.2
1-1/4 x 1-1/2 35131301 2014 1 88 1-88 1 82 15 30 1 3
1-1/4 x 2 35BT3012020 2.10 2.10 1.90 10 20 1.6
1 1/2 x 1 1/4 x 2 358T3014012020 2.16 2.10 2.02 10 21) 1-8
1-1/2 x 2 35B13014020 2.16 2.16 2.02 8 16 1.8 .
SMITII-COOPER INTERNAT1ONAI,"' • "I'OI.I. FREE 1-800-766-01176 • FAX(323)890-4456 • www.sminccooper.corn 112
„. .. . ., ., ..r i r0„u.rwera.uaw.zx.nms+..wu.u.wxxauwwuxuaux.444444..M.ArxU.M.twwrwwn.runoa“.....41.i... area...i1...0.......iMitsttttt:utt00msa.etf,.iri+tt>utsttttttettiwtiNtuta tmauualawnttar
` ` Ductile Iron Fittings-Class 300 UL/FM
-77,7777,77
cCillus
APPROVED
A
• Fig. 35CP3 -Straight Coupling with Ribs LISTED
Size Part Number A Packing Weight
, rill in in Inner Master lb
1/2 35C03004 1,38 200 400 0.1
,,..
3/4 35CP3006 1.63 100 200 0.2
1 35CP3010 1 76 60 120 0.4
- 1-1/4 35CP3012 2.00 35 70 0.5
1-1;2 35C03014 2 19 2.5 50 0.7
2 35CP3020 2.62 15 30 1.2
• 2-1/2 35CP3024 3.00 9 18 2 2
• Fig. 35RC3 -Hex Reducing Coupling
III Size Part Number A Packing Weight
N' in in lb
® A 1
x 1/2
1 x 3/4 359C3010004 1.69 80 160 0.3
35RC3010006 1.69 60 120 0.4
_'_ 1-1/4 x 3/4 35RC3012006 2,06 40 Inner Master 80 0.6
2 x 1 (not hex) 35RC3020010 2.81 20 40 1.0
Fig. 35HB3 -Hex Bushing
Size Part Number A Packing Weight
B in in Inner Master lb
1 x 1/2 35H83010004 1-06 180 360 0.2
1 x 3/4 35HB3010006 1.06 180 360 0.1
-,, , 1-1/4 x 1 35HB3012010 1.19 90 180 0.2
1-1/2 x 1 35HB3014010 1.25 75 150 0.4
o 1-1/2 x 1-1/4 35HB3014012 1.25 75 150 03
D 2 x 1 35HB3020010 1.38 40 80 0.6
2 x 1-1/4 35HB3020012 1 38 40 80 0.6
2 x 1-1/2 35HB3020014 1.38 40 80 0.6
I
Fig. 35SP3 -Square Head Plug
Size Part Number A Packing Weight
inin Inner Master lb
1/2 35SP3004 0.94 600 1200 0.07
1 I IA
3/4 35SP3006 1.12 350 700 0.1
� � � 1 35sP3010 125 200 400 01
1-1/4 35SP3012 1.37 100 200 0.3
1-1/2 35SP3014 144 80 160 0.4
2 35SP3020 1.50 45 90 0.6
•
Fig. 35U 3- Union with Brass Seat
A Size A Packing Weight
Part Number
t in _ in Inner Master lb
35U 3010 2 19 20 40 1.0
1
1.2
I �Iill1-1/4 35U 3012 2.50 15 30
!2_ 3SU 3014 7-62 0 20 1.7
'1�I.+� 2 35U 3020 3.12 6 12 2.4
ilo
113 SMITH-COOPER INTERNATIONAL® • TOLL FREE 1-800-766-0076 • FAX(323)890-4456 • www.smithcooper.com
ucti e ron fittings- ass I I I
[QUALITY PUS__;
C ® US
APPROVED
Fig. 35X 3— Cross LISTED
A )1( A ) Size A Packing Weight
) Part Number
i ; l_.— IA in inInner Master Ib
I1 35X 3010 1 50 ,30 40 0.9
I I� 1-1/4 35X 3012 1.75 12 24 1.4
I 35X 3014 L94 8 16 8
I A 2 35X 3020 2.25 6 12 2.8
f Ic-----
, ,
Fig. 35RX3—Reducing Cross
B B ' Size A B Packing Weight
iii__ -iiii '_ I in Part Number in in Inner Master lb
1-1/4 x 1 358X3012010 1.67 1 58 15 30 1 2
- 1-1/2 x 1 35RX3014010 1.80 1.65 12 24 1.4
m I II 2 x 1 35RX3020010 2.02 1 73 8 16 2.0
,401 !rt �A
Fig. 35C3— Cap
Size Part Number A Packing Weight
in in Inner Master lb
if !! A 3/4 350 3006 0.97 200 400 0.1 •
�= 1 35C 3010 1 16 1 10 220 0.2
1-1/4 350 3012 1.28 70 140 0.4
1-1/2_ 35C 3014 1.33 50 100 0 5
2 35C 3020 1.45 25 50 0.8
2-1/2 35C 3024 1.70 18 36 1.6
Fig. 35BC3—Beam Clamp
01 _awl Nil Size A Packing Weight
Part Number
A in in Inner Master lb
3%8 35E3C3003 0.75 100 200 0 3
®® III
■� 1/2 35BC3004 0.75 80 160 0.5
SMITH-COOPER INTERNATIONAL® • TOLL FREE 1-800-766-0076 • FAX(323)890-4456 • www.smithcooper.com 114
IPS,CARBONSTEEL PIPE - HOLE CUT PRODUCTS
MpgirPI c C 0 ® I(vdsll LPCB
„� P �,# ®� cu EDus ` J 491a/27
SEE VICTAULIC PUBLICATION 10.01 FOR DETAILS
STYLE 922
The Style 922 Outlet-T provides a convenient method of incorporating'/2,3/4,and 1'/15, 20
and 25mm outlets for directly connecting sprinklers,drop nipples,sprigs,gauges,drains and
other outlet products.Available for 11/4 through 76.1 mm/32 to 76.1mm piping systems,Style
922 outlets are UL/ULC Listed, LPCB and FM Approved for branch connections and VdS
Approved for direct sprinkler connection only on wet and dry systems.
I -
The locating collar engages into the hole prepared in the pipe.When tightened,the assembly
compresses the gasket onto the OD of the pipe.The Style 922 Outlet-T is UL/FM rated up
to 300 psi/2068 kPa and VdS rated up to 16 bar at the ambient temperatures typical for fire
protection systems.
Style 922 is suitable for use on standard, lightwall,Schedule 5 and other specialty pipes.*
Contact Victaulic for other optional coatings.
*Consult Section 10.01 for specific listings/approvals.
MATERIAL SPECIFICATIONS Housing: Ductile iron conforming to ASTM A-536,grade 65-45-12. Ductile iron conforming to
ASTM A-395,grade 65-45-15,is available upon special request.
Gasket:
• Grade"E"EPDM-Type A
(Violet color code). FireLock products have been Listed by Underwriters Laboratories Inc.and
Approved by Factory Mutual Research for wet and dry(oil free air)sprinkler services up to the
c •
rated working pressure using the Grade"E"Type A Gasket System.
Bolts/Nuts: Heat-treated plated carbon steel,trackhead meeting the physical and chemical
requirements of ASTM A-449 and physical requirements of ASTM A-183.
Housing Coating:
• Orange enamel(North America, Latin America,Asia Pacific)
• Red enamel(Europe)
13
JOB/OWNER CONTRACTOR ENGINEER
System No. _ Submitted By Spec Sect Para
Location Date Approved
Date
www.victaulic.com
\ iE taulid
IPS CARBON STEEL PIPE - HOLE CUT PRODUCTS 10.52
FireLock® Outlet-I
STYLE 922
DIMENSIONS Nominal Size Hale Approx.
inches/mm Diameter Dimensions-inches/millimeters Weight Each
Run X Branch +0.06/+1.5
Y .-Z-1 IPTt -0,00/-0.0 T" V W 8 Z Ws/kg .
11/4 '/2 13/16 1.30 1.83 1.10 3.87 2.56 1.0
V i 32 X 15 30.2 33.0 46.5 27.9 98.3 65.0 0.45
T 3/4 13/16 1.28 1.83 1.10 3.87 2.56 1.1
20 30.2 32.5 46.5 279 98.3 65.0 0.50 •
W 1�' 1 13/16 1.52 2.18 1.10 3.87 2.56 1.2
I V I 25 {' 30.2 38.6 55.4 27.9 98.3 65.0 0.54
--
1 Y2 h 1 3/16 1.42 1.95 1.22 4.08 2.56 1.2
40 X 15 I 30.2 36.1 49.5 31.0 103.6 65.0 0.54
-----1
44 13/16 1.40 1.95 1.22 4.08 2.56 1.2
20 30.2 35.6 49.5 31.0 103.6 65.0 0.54
1 13/16 1.64 2.30 1.22 4.08 2.56 1.3
25 30.2 41.7 58.4 31.0 103.6 65.0 0.59
2 1/2 j 13/16 1.66 2.19 1.46 4.60 2.56 1.3
50 X 15 30.2 42.2 55.6 37.1 116.8 65.0 0.59
3/4 13/16 1.64 2.19 1.46 4.60 2.56 1.4
20 1 30.2 41.7 55.6 37.1 116.8 65.0 0.64
1 13/16 1.88 2.54 1.46 4.60 2.56 1.5
25 30.2 47.8 64.5 37.1 116.8 65.0 0.68
21/2 k 13/16 1.91 2.44 1.71 5.40 2.56 1.6
65 X 15 30.2 48.5 62.0 43.4 137.2 65.0 0.73
3/4 1 3/16 1.89 2.44 1.71 5.40 2.56 1.6
20 30.2 48.0 62.0 43 4 137.2 65.0 0.73
1 13/16 2.13 2.79 1.71 5.40 2.56 1.6
25 30.2 54.1 70.9 43.4 137.2 65.0 0.73
76.1 mm X h 1 3/16 1.91 2.44 1.71 5.50 2.56 1.6
15 30.2 48.5 62.0 43.4 139.7 65.0 0.73
4/4 1 3/16 1.89 2.44 1.71 5.50 2.56 1.6
20 30.2 48.0 62.0 43.4 139.7 65.0 0.73
1 13/16 2.13 2.79 1.71 5.50 2.56 1.7
25 i 30.2 54.1 70.9 43.4 139.7 65.0 0.80
t Victaulic female threaded products are designed to accommodate standard NPT or BSPT(optional)
male pipe threads only.Use of male threaded products with special features,such as probes,dry pen-
dent sprinklers,etc.,should be verified as suitable for use with this Victaulic product.Failure to verify
suitability in advance may result in assembly problems or leakage.
"Center of run to engaged pipe end for NPT threads(dimensions are approximate).
www.victaulic.com
IPS CARBON STEEL PIPE-HOLE CUT PRODUCTS 10.52
FireLock® Outlet-T
STYLE 922
PERFORMANCE
Equivalent Length of I inch
Schedule 40 Steel Pipe(per UL
n Sipe z Oullrl Slm 213 tinn 16'iC-120'',FT
Inches/mm Feet/meters
l r/a X 1 8.5
32 25 2.6
11/2 ..�_X 1 8.5
40 25 2.6
2 X 1 j 8.5
50 25 ? 2.6
65 25 ' 2.6
76.1 mm X 25 2.6
Hazen-Williams coefficient of friction is 120
•
www.victaulic.com
.ctaLJt.r
FireLock® Ou kk
STYLE 922
INSTALLATION Reference should always be made to the 1-100 Victaulic Field Installation Handbook for the product
you are installing. Handbooks are included with each shipment of Victaulic products for complete
installation and assembly data,and are available in PDF format on our website at www.victaulic.com.
•
WARRANTY Refer to the Warranty section of the current Price List or contact Victaulic for details.
NOTE This product shall be manufactured by Victaulic or to Victaulic specifications.All products to be
installed in accordance with current Victaulic installation/assembly instructions.Victaulic reserves the
right to change product specifications,designs and standard equipment without notice and without
incurring obligations.
{
}
For complete contact information,visit www.victaulic.com
10.52 3355 REV G UPDATED 12/2009 \ ictaulic
Pipe Hangers
Fig. 200 - "Trimline" Adjustable Band Hanger (B-Line Fig.B317ONF) ®TOLCD
Fig. 200F - "Trimline" Adjustable Band Hanger with Felt Lining (B-Line Fig.B317ONFF) c ul us
Fig. 200C- "Trimline" Adjustable Band Hanger with Plastic Coated (B-Line Fig. B317ONFC) LISTED
Fig. 200S - "Trimline" Adjustable Band Hanger with Non-Captured Nut
Size Range:
Fig. 200 - 1/2" (15mm)thru 8" (200mm)pipe
Material: Steel, Pre-Galvanized to G90 specifications s
Function: For fire sprinkler and other general piping purposes. Knurled
u
swivel nut design permits hanger adjustment after installation.
Features: /
• (1/2" (15mm)thru 2" (50mm)) Flared edges ease installation for all pipe `''
types and protect CPVC plastic pipe from abrasion. Captured design r 1
keeps adjusting nut from separating with hanger. Hanger is easily B
installed around pipe. A
For hanger with non captured nut order Fig. 200S.
• (21/2" (65mm)thru 8" (200mm)) Spring tension on nut holds it securely in '' ' -��
hanger before installation.Adjusting nut is easily removed. �I
Approvals: Underwriters Laboratories listed (1/2" (15mm)thru 8" (200mm)) f ..,____,/--------Fig.200-1/2.200-3/4
in the USA(UL) and Canada (cUL)for steel and CPVC plastic pipe and
lFactory Mutual Engineering Approved(FM) (3/4" (20mm)thru 8" (200mm)). Fig.2001to2002 Fig.200-21/zto200-8
Conforms to Federal Specifications VWV-H-171 E &A-A-1192A,Type 10
and Manufacturers Standardization Society ANSI/MSS SP-69&SP-58,
Type 10.
Maximum Temperature: 650°F(343°C)
Finish: Pre-Galvanized. Stainless Steel ,`
materials will be supplied with (2) hex nuts
in place of a knurl nut.
Order By: Figure number and pipe size
E
Designed to meet or exceed requirements of m 1 FMDS2-0. ' ' a
a
it
Fig.200
Fig.200C Fig.200F
Pipe Size Rod Size A B Approx.Wt./100
Part No. in. (mm) in. (mm) in. (mm) lbs. (kg) "+*'
200-1/2 1/2" (15) 3/8"-16 31/8" (79.4) 25/8" 166.7) 11 15.0)
200-3/4 3/4" (20) 3/8"-16 31/8" (79.4) 21/2" (63.5) 11 (5.0)
200-1 1" (25) 3/8"-16 33/8" (85.7) 25/8' (66.71 12 (5.5)
200-11/4 11/4" (32) 3/8"-16 33/4" (94.0) 22/t' (73.0) 13 (5.9)
200-11/2 11/2" 140) 3/8"-16 37/8' (98.4) 27/8" (73.0) 14 (6.4)
200-2 2' (50) 3/8"-16 41/2" (114.3) 3" (76.3) 15 (6.9)
200-21/2 21/2" (65) 3/8"-16 55/8" (142.9) 41/8" 1104.7) 27 (12.3)
200-3 3' (751 3/8"-16 57/8" (149.1) 4" (101.6) 29 (13.3) Fig.200S
200-31/2 31/2" (90) 3/e"-16 73/8" (187.3) 51/4" (133.3) 34 (15.6)
200-4 4" (100) 3/8"-16 73/8" (187.3) 5' (127.01 35 (16.0)
200-5 5" (125) 1/2"-13 91/8" (231.8) 61/4" (158.7) 66 (30.2)
200-6 6" (150) 1/2"-13 101/8" (257.21 63/4" (171.4) 73 (33.4)
200-8 8" (200) 1/2"-13 131/8" (333.4) 83/4" (222.2) 136 (62.3)
All dimensions in charts and on drawings are in inches.Dimensions shown in parentheses are in millimeters unless otherwise specified. p
Fire Protection Solutions by Line
21 by E:T•N
Threaded Accessories
B3205 - Threaded Rod (right-hand threads - both ends) (TOLCO Fig.103) >
B3205L - Threaded Rod (right& left hand threads) /IL
Size Range: 3/8"-16 thru 3"-4 rod SpecifyLength
/
Material: Steel ��
Function: Recommended for use as a hanger support in hanger assemblies. TL \1l
1101011.
Rod is threaded on both ends with right hand threads of the length shown.Also 111�\��111 A
available with left and right hand threads-specify Fig.B3205L when ordering. Thread Size
Maximum Temperature: 750°F(399°C)
Finish: Plain.Contact B-Line for alternative finishes and materials.
Order By: Part number, rod size, length and finish
Standard Design Load
Thread Size Thread Length TL 650°F(343°C) 750°F(399°C)
Part No. A in. (mm) Lbs. (kN) Lbs. (kN)
B3205-3/8 X'L' 3/8"-16 21/2" (63.5) 730 (3.25) 572 (2.54)
B3205-1/2 x'L' 1/2"-13 21/2" (63.5) 1350 (6.00) 1057 (4.70)
B3205-5/8 x'L' 5/8"-11 21/2" (63.5) 2160 (9.61) 1692 (7.52)
B3205-3/4 x'L' 3/4"-10 3" (76.2) 3230 (14.37) 2530 (11.25)
B3205-7/8 x'L' 7/8"-9 31/2" (88.9) 4480 (19.93) 3508 (15.60)
B3205-1 x'L' 1"-8 4" (101.6) 5900 (26.24) 4620 (20.55)
B3205-11/8 x'L' 11/8%7 41/2" (114.3) 7450 (33.14) 5830 (25.93)
B3205-11/4 x'L' 11/4"-7 5" (127.0) 9500 (42.25) 7440 (33.09)
B3205-11/2 x'L' 11/2" 6 6" (152.4) 13800 (61.38) 10807 (48.07)
B3205-13/4 x'L' 13/4"-5 7" (177.8) 18600 (82.73) 14566 (64.79)
83205-2 x'L' 2"-41/2 8" (203.2) 24600 (109.42) 19625 (87.29)
B3205-21/4 x'L' 21/4"-41/2 9" (228.6) 32300 (143.67) 25295 (112.51)
B3205-21/2 x'L' 21/2"-4 10" (254.0) 39800 (177.03) 31169 (138.64)
B3205-23/4 x'L' 23/4"-4 11" (279.4) 49400 (219.73) 38687 (172.08)
83205-3 x'L' 3"-4 12" (304.8) 60100 (267.32) 47066 (209.35)
ATR - All Threaded Rod 120" (3.05m) Lengths (TOLCO Fig. 100)
Fig. 99 - All Threaded Rod Cut To Length ����` ,,,,,,,,,��
,� ,,,,aa?>�'"���1111111,
Size Range: 3/8"-16 thru 11/2"-6 rod in 120"(3.05m)lengths or cut to length ��°������10'
° �111111 Si
Material: Steel H
Maximum Temperature: 750°F(399°C) y
Finish: Plain.Contact B-Line for alternative finishes and materials. ...-``' . 0
Order By: Part number, rod diameter and finish Q
Part No.-Size x Length Threads Recommended Load Approx.Wt./100 Ft.
ATR Fig.99 Per Inch Lbs. (kN) Lbs. (kg)
ATRIA"x 120 99-1/4"x length 20 240 (1.07) 12 (5.44)
ATR 3/8"x 120 99-3/a"x length 16 730 (3.24) 29 (13.15)
ATR 1/2"x 120 99-1/2"x length 13 1350 (6.00) 53 (24.04)
ATR 5/8"x 120 99-5/8"x length 11 2160 (9.60) 89 (40.37)
ATR 3/4"x 120 99-3/4"x length 10 3230 (14.37) 123 (55.79)
ATR 7/a"x 120 99-7/8"x length 9 4480 (19.93) 170 (77.11) '
ATR 1"x 120 99-1"x length 8 5900 (26.24) 225 (102.06)
All dimensions in charts and on drawings are in inches.Dimensions shown in parentheses are in millimeters unless otherwise specified. '
B-
Pipe Hangers&Supports 236 Revised 4/28/2014 dine
by !E`:L•W
VERTICAL MOUNT SAMMYS
SAMMYS° for Wood , -r „ ,T r.'" ' ' '' -. - -1 -
Not less than
2"nominal width Wood Flooring Product Features
(1-1/7)
--♦ •No pre-drilling required.
Ne3"t nominal less man ' •Quick to install using the Sammy
thickness Nut Driver with an 18V cordless
(depm or side Wood Joist drill/driver.
of vertical member) [[
_._ '22A-~---- •Saves time from traditional
Double Sheetrock ;fl methods.
Ceiling
For vertical use-
install in center of lower face.
•Reduces installation cost.
Minimum 2'embedment into base
material for NFPA 13 compliance. ' Composite)Truss •Made in the U.S.A.
Consult truss manufacturer for
l' {I recommended installation point.
i 'Pre-drilling maybe required for GST
25-380.Tool available on page 10r.
Approvals Rod Part Model Screw Ultimate UL Test FM Test Box Case
Size Number Descriptions Pullout(Ibs) Load(lbs) Load(lbs) Qty Qty
1/4" 8002957 GST 100 1/4 x 1" 210(7/16"OSB) 25 125
670(3/4"Ply)
1/4" 8003957 GST 200 1/4 x 2" 1760 (Fir) 25 125
1/4" 8004957 GST 300 1/4 x 3" 2060(Fir) 25 125
3/8" 8006957 GST 75 1/4 x 3/4" 564 (3/4"Ply) 25 125
3/8" 8007957 GST 10 1/4 x 1" 210(7/16"OSB) 300 25 125
670(3/4"Ply) _
3/8" 8008957 GST 20 1/4 x 2" 1760 (Fir) 850 1475 25 125
Q. 3/8" 8068925 GST 20-SS 1/4 x 2" 1760(Fir) 850 25 125
°Q`. 3/8" 8009925 GST 25-380 3/8 x 2-1/2" 2113 (Fir) 1500 25 125
v•`� 3/8" 8010957 GST 30 1/4 x 3" 2060(Fir) 1500 1475 25 125 #14 Black
Nut Driver
3/8" 8069925 GST 30-SS 1/4 x 3" 2060 (Fir) 25 125 Part#8113910
3/8" 8011925 GST 40 1/4 x 4" 2180 (Fir) 25 125
3/8" 8012925 GST 60 1/4 x 6" 2230 (Fir) 25 125
1/2" 8013925 GST 2 1/4 x 2° 1760(Fir) 25 125
1/2" 8014925 GST 2.5-380 3/8 x 2-1/2" 2113 (Fir) 25 125
1/2" 8015925 GST 3 1/4 x 3° 2275(Fir) 25 125 —
1/2" 8016925 GST 4 1/4 x 4" 2180 (Fir) 25 125
1/2" 8017925 GST 6 1/4 x 6" 2230 (Fir) 25 125 #14 SW Red
Nut Driver
* Part#8114910
SAMMY Swivel Head° for Wood
4
Product Features
•Eliminates distortion of threaded rod. •Saves time from traditional methods.
•Accommodates up to 3'/"x 12 pitch roof. •Reduces installation cost.
11116
Allows 17°deflection from vertical. •Made in the U.S.A.
Approvals Rod Part Model Screw Ultimate UL Test FM Test Min Box Case
Size Number Descriptions Pullout fibs) Load(lbs) Load(Ibs) Thickness Qty Qty
Qt 4,;,.. 3/8 8139957 SH-GST 20 1/4 x 2" 1257(Fir) 1050 '415 26 125 125
Q"•> 3/8" 8141957 SH-GST 30 1l4 x 3" 1720(Fir) 1500 1475 25 125
#14 Black
Nut Driver
SPECIAL NUT DRIVER SYSTEM The nut drivers were designed with a unique spin-off feature which provides a fast and safe installation each time.When the face of the driver comes into Part#8113910
contact with the material you are installing into,continue drilling until nut driver spins free.Installation is then complete.Warranty requires the use of the appropriate nut driver for installations.
For the most up to date information,visit www.sammysuperscrew.com 4 r'Y