Loading...
Report (3) WEz2bz/- OD.S6 COMeheck Software Version COMcheckWeb Mechanical Compliance Certificate Wel raglill Project Information Energy Code: 90.1 (2019) Standard Project Title: Sim Golf Location: Tigard, Oregon Climate Zone: 4c Project Type: Addition Construction Site: Owner/Agent: Designer/Contractor: 10114 SW Washington Square Rd Clint Latimer #A07 Latimer HVAC LLC Tigard,Oregon 97223 clint@latimerhvac.com Mechanical Systems List QuantitySystem Type & Description 1 HVAC System(Single Zone): Heating: 1 each-Central Furnace,Gas,Capacity=125 kBtufh Proposed Efficiency= 80.00%Et,Required Efficiency: 80.00%Et(or 80%AFUE) Cooling: 1 each-Single Package DX Unit, Capacity= 88 kBtu/h,Air-Cooled Condenser,Air Economizer Proposed Efficiency= 11.00 EER,Required Efficiency: 11.00 EER + 12.7 PEER Fan System: FAN SYSTEM 1--Compliance(Motor nameplate HP and fan efficiency method) : Passes Fans: FAN 1 Supply,Constant Volume,3000 CFM, 1.9 motor nameplate hp,0.00 fan energy index,fan exception: Fan array<= 5 total HP or<=4.1 kW Mechanical Compliance Statement Compliance Statement: The proposed mechanical design represented in this document is consistent with the building plans, specifications,and other calculations submitted with this permit application.The proposed mechanical systems have been designed to meet the 90.1 (2019)Standard requirements in COMcheck Version COMcheckWeb and to comply with any applicable mandatory requirements listed in the Inspection Checklist CI I Of- 1,,e 10lIl/?.a2- Name-Title Si ture Date Project Title: Sim Golf Report date: 10/12/21 Data filename: Page 1 of 9 COMeheck Software Version COMcheckWeb Inspection Checklist Energy Code: 90.1 (2019) Standard Requirements: 0.0% were addressed directly in the COMcheck software Text in the "Comments/Assumptions" column is provided by the user in the COMcheck Requirements screen. For each requirement, the user certifies that a code requirement will be met and how that is documented, or that an exception is being claimed. Where compliance is itemized in a separate table, a reference to that table is provided, Section Plan Review Complies? Comments/Assumptions & Req.JD � 4.2.2, Plans,specifications,and/or LJComplies 6.4.4.2.1, calculations provide all information ,ODoes Not 6.7.2 with which compliance can be [PR2]1 determined for the mechanical Not Observable systems and equipment and ONot Applicable document where exceptions to the standard are claimed.Load calculations per acceptable ;engineering standards and handbooks. 4.2.5.2 Commissioning shall be performed as aComplies [PR5]1 stated in Sections 5.9.2,6.9.2, 7.9.2, ❑Does Not 8.9.2, 9.9.2, 10.9.2, 11.2(d),and G1.2.1(c).Commissioning must utilize Not Observable ASHRAE/IES Standard 202 or other ONot Applicable generally accepted engineering standards acceptable to the building official. FPT and verification requirements for commissioning are as stated in Section 4.2.5.1. Commissioning shall document compliance of the building systems, ;controls,and building envelope with ',required provisions of this standard. ;Commissioning requirements shall be :incorporated into the construction ;documents. Additional Comments/Assumptions: r1 High Impact(Tier 1) 2 Medium Impact(Tier 2) 3 Low Impact(Tier 3) Project Title: Sim Golf Report date: 10/12/21 Data filename: Page 2 of 9 .au.:.-.a..H.....x:.u:uu.:aastau,ruau+sautuutawu.i`wu+uttauewaxru... •• Section Footing/Foundation Inspection Complies? Comments/Assumptions & Req.ID 6.4.3.7 Freeze protection and snow/ice OComplies (FO913 melting system sensors for future ❑Does Not connection to controls. ONpt Observable ,IMfiot Applicable Additional Comments/Assumptions: 1 High Impact(Tier 1) 2 Medium Impact(Tier 2) 3 Low Impact(Tier 3) i Project Title: Sim Golf Report date: 10/12/21 Page 3 of 9 Data filename: Section Mechanical Rough-In Plans Verified Field Verified # Inspection Value Value Complies? Comments/Assumptions & Req.ID �,f 6,4.1.4, HVAC equipment efficiency Efficiency: . Efficiency: ;L`1Complies See the Mechanical Systems list 6.4.1.5 verified. Non-NAECA HVAC Does Not for values. [MEl]2 equipment labeled as meeting • 90.1. :Not Observable _ __ _ ONot Applicable 6.4.3.4.1 Stair and elevator shaft vents OComplies [ME3]3 have motorized dampers that ❑Does Not automatically close. ❑ t Observable BNot Applicable 6.4.3.4.2, Outdoor air and exhaust systems r� DComplies 6.4.3.4.3 have motorized dampers that DDoes Not [ME4]3 automatically shut when not in use and meet maximum leakage ❑ t Observable rates.Check gravity dampers Q:Not Applicable __ where allowed. 6.4.3.4.5 Enclosed parking garage -- _ DComplies [ME39]3 ventilation has automatic DDoes Not contaminant detection and capacity to stage or modulate ❑.�t Observable fans to 50%or less of design Cu1Not Applicable capacity. 6.4.3.4.4 Ventilation fans>0.75 hp have [J`Complies [ME5P automatic controls to shut off fan DDoes Not when not required. ONot Observable ❑N�t Applicable 6.4.3.8 Demand control ventilation EJ omplies [ME6]1 provided for spaces>500 ft2 and DDoes Not >25 people/1000 ft2 occupant density and served by systems ONot Observable with air side economizer,auto ONot Applicable modulating outside air damper control,or design airflow >3,000 cfm. 6.5.3.2.1 DX cooling systems >= 75 kBtu/h DComplies See the Mechanical Systems list `[ME40]2 (>= 65 kBtu/h effective 1/2016) ❑Does Not for values. and chilled-water and evaporative cooling fan motor hp ONot Observable >= 1/4 designed to vary supply ONot Applicable fan airflow as a function of load and comply with operational _ _ requir_e_ments. _ ,�r_ 6.4.4.1.1 Insulation exposed to weather DComplies [ME7]3 protected from damage. DDoes Not Insulation outside of the conditioned space and associated ONot Observable with cooling systems is vapor 'DNot Applicable retardant. 6.4.4.1.2 HVAC ducts and plenums R-4— R- DComplies 4[ME8]2 insulated per Table 6.8.2.Where ❑Does Not ducts or plenums are installed in or under a slab,verification may :Not Observable need to occur during Foundation .❑Not Applicable Inspection. z 6.4.4.1.3 HVAC piping insulation thickness. In. _in. ;IComplies [ME9I2 Where piping is installed in or DDoes Not under a slab,verification may need to occur during Foundation ONot Observable _ Inspection. ,ONot Applicable 6.4.4,1.4— Thermally ineffective panel DComplies • ,: [ME41]3 surfaces of sensible heating DDoes Not panels have insulation>= R 3.5. GIN&Observable Not Applicable ' 1 High Impact(Tier 1) 1 2 `Medium Impact(Tier 2) 3 Low Impact(Tier 3) Project Title: Sim Golf Report date: 10/12/21 Data filename: Page 4 of 9 li Section I Mechanical Rough-In Inspection Plans Verified Field Verified Value Value# Complies? Comments/Assumptions L& Req.ID i 6.4.4.2.1 Ducts and plenums having Complies i[ME10]2 pressure class ratings are Seal ❑Does Not ' Class A construction. ONot Observable I ONot Applicable 6.8.1-15,—Electrically operated DX-DOAS V__�..._____._______..____ �.___ ❑Complies 16.8.1-16 units meet requirements per ❑Does Not '[ME110]2 Tables 6.8.1-15 or 6.8.1-16. ❑pt Observable SNot Applicable 6.4.4.2.2 Ductwork operating >3 in.water ❑Complies [ME11]3 column requires air leakage ODoes Not testing. DNA Observable E Plot Applicable ' 6.5.2.3 Dehumidification controls ❑Complies [ME19]3 provided to prevent reheating, DDoes Not recooling, mixing of hot and cold airstreams or concurrent heating ONot Observable and cooling of the same 17114ot Applicable airstream. 6.5.2.4.1 Humidifiers with airstream ❑Complies [ME68]3 mounted preheating jackets have DDoes Not preheat auto-shutoff value set to activate when humidification is ❑N9t Observable not required. of Applicable 6.5.2.4.2 Humidification system dispersion ❑Complies [ME69]3 tube hot surfaces in the ODoes Not airstreams of ducts or air- handling units insulated >= R- ❑N, Observable 0.5, LL�Hoot Applicable 6.5.2.5 Preheat coils controlled to stop —�W — LNComplies (ME70]3 heat output whenever ODoes Not 'mechanical cooling, including economizer operation, is active. ONot Observable ❑Not Applicable 6.5.2.6 Units that provide ventilation air ❑Complies [ME106]3 to multiple zones and operate in ODoes Not conjunction with zone heating and cooling systems are ❑ t Observable prevented from using heating or L'iNot Applicable heat recovery to warm supply air ,above 60°F when representative building loads or outdoor air temperature indicate that most zones demand cooling. 6.5.3.6 Motors for fans>= 1/12 hp and C'Complies [ME72]2 < 1 hp are electronically- ODoes Not commutated motors or have a minimum motor efficiency of ONot Observable 70%.These motors are also ONot Applicable speed adjustable for either balancing or remote control. 1'High Impact(Tier 1) 12 Medium Impact(Tier 2) 3 Low Impact(Tier 3) Project Title: Sim Golf Report date: 10/12/21 Data filename: Page 5 of 9 Section Mechanical Rough-In Plans Verified Field Verified & Re ID Inspection Value Value Complies? Comments/Assumptions 16.5.3.4 Parallel-flow fan-powered VAV air ❑Complies [ME10812 terminals have automatic ODoes Not controls to a)turn off the terminal fan except when space ['Not Observable heating is required or if required LUNot Applicable for ventilation; b)turn on the terminal fan as the first stage of heating before the heating coil is activated; and c)during heating for warmup or setback temperature control,either operate the terminal fan and heating coil without primary air s or reverse the terminal damper logic and provide heating from the central air handler through primary air. ;��� 16.5.3.7 Required minimum outdoor air l Complies (ME109)2 rate is the larger of minimum ODoes Not outdoor air rate or minimum exhaust air rate required by ❑Not Observable Standard 62.1, Standard 170,or ❑Not Applicable applicable codes or accreditation standards.Outdoor air ventilation systems shall comply with one of ,{ the following: a)design minimum system outdoor air provided < 135%of the required minimum outdoor air rate, b)dampers, ductwork,and controls allow the system to supply<=the required minimum outdoor air rate with a single set-point adjustment.,or c)system includes exhaust air energy recovery complying with Section 6.5.6.1. 6.5.3.3 Multiple zone VAV systems with ❑Complies See the Mechanical Systems list [ME42]3 DDC of individual zone boxes ODoes Not for values. have static pressure setpoint ❑Ndt Observable reset controls. of Applicable 6.5.4.2 HVAC pumping systems with >_ ❑Complies [ME25]3 3 control values designed for ODoes Not variable fluid flow(see section ❑ Observable details). IVot Applicable 6.5.6.1.1 Exhaust Air Energy Recovery for ❑Complies [ME56]1 Nontransient Dwelling Units ODoes Not DN,ot Observable gigot Applicable 6.5.6.1.2 Exhaust air energy recovery for ❑Complies [ME111]1 spaces other than Nontransient ODoes Not dwelling units meeting Tables 6.5.6.1.2-1,and 6.5.6.1.2-2. ❑Npt'Observable flEfiot Applicable Kitchen hoods>5,000 am have � ❑compiles [ME3212 make up air>=50%of exhaust ODoes Not air volume. ❑N Observable I^� of Applicable 1 High Impact(Tier 1) 2 Medium Impact(Tier 2) 3 Low Impact(Tier 3) J Project Title: Sim Golf Report date: 10/12/21 Data filename: Page 6 of 9 aaeaa Ha .a waa s4U4W., „aaauswa _ Section iMechanical Rough-In Plans Verified Field Verified I Complies? Comments/Assumptions & Re !D j Inspection Value Value 6.5.7.1 Conditioned supply air to space 26omplies [ME100]2 with mechanical exhaust<=the ❑Does Not greater of criteria of supply flow, required ventilation rate,exhaust :Not Observable flow minu the available transffer ONot Applicable air(see section details). 6.5.3.8 'Occupied standy controls for ���� omplies [ME112]1 zones serving rooms that are ❑Does Not required to have automatic partial OFF or automatic full OFF fI k GNot Observable lighting controls per Section ? ❑Not Applicable '9.4.1.1 shall meet the following within five minutes of all rooms in ",y that zone entering occupied- ' 'standby mode: a)Active heating set point shall be setback at least 1°F, b)Active cooling set point shall be setup at least 1°F and i c)All airflow supplied to the zone shall be shut off whenever the space temperature is between the active heating and cooling set points. _� 6.5.7.2.4 Approved field test used to CJComplies [ME49]3 evaluate design airflow rates ❑Does Not and demonstrate proper capture ❑Not Observable and containment of kitchen exhaust systems. ❑Not Applicable 6.5.8.1 Unenclosed spaces that are ❑Complies [ME3412 heated use only radiant heat. ❑Does Not ❑l t Observable L Not Applicable 6.5.9 Hot gas bypass limited to: <=240 a ElO omplies [ME35]1 kBtu/h-15%>240 kBtu/h-10% ❑Does Not :Not Observable ❑Not Applicable 6.4.3.9 Heating for vestibules and air DComplies [ME63]2 curtains with integral heating ❑Does Not include automatic controls that ❑N t Observable shut off the heating system when outdoor air temperatures>45F. L'dNot Applicable Vestibule heating and cooling systems controlled by a thermostat in the vestibule with heating setpoint<=60F and t.�)" cooling setpoint>= 80F. 6.5.10 Doors separating conditioned [ME73]3 space from the outdoors have DDoes Not controls that disable/reset heating and cooling system when ❑Not Observable open. ❑Not Applicable Additional Comments/Assumptions: 1 High Impact(Tier 1) 2 Medium Impact(Tier 2) 3 Low Impact(Tier 3) Project Title: Sim Golf Report date: 10/12/21 Data filename: Page 7 of 9 ____ _______ ___ _.. _. __ .+«...n..wwwawwwwwwawawwxxutauauaulutuNUNIuuNNWdHNNANNtNtti{Idi ! Section Rough-In Electrical Inspection Complies? Comments/Assumptions & Req.ID v�/ 10.4.1 Electric motors meet requirements L�Complies [EL9]2 where applicable. ❑Does Not ❑Not Observable' ❑Not Applicable Additional Comments/Assumptions: 1 High Impact(Tier 1) 12 {Medium Impact(Tier 2) 3 Low Impact(Tier 3) Project Title: Sim Golf Report date: 10/12/21 Data filename: Page 8 of 9 m,wwueauaswt»uiuwetee...6uNtHHtNtisil#......YMHiNNNiilliltiMlawateastuActaueWiNeia AN... •: Section Final Inspection Complies? Comments/Assumptions & Req,ID 6.4.3.1.2 Thermostatic controls have a 5°F omplies [F13]3 deadband. ODoes Not ONot Observable O Not Applicable 6.4,3.2 Temperature controls have setpoint ,2Complies [F120]3 overlap restrictions. :❑Does Not I❑Not Observable' ❑Net Applicable 6.4.3.3.1 HVAC systems equipped with at least INIComplies [FI21]3 one automatic shutdown control. ODoes Not ONot Observable _ ,D,�NN�ot Applicable 6.4.3.3.2 Setback controls allow automatic It�Complies [F122]3 restart and temporary operation as ODoes Not required for maintenance. ONot Observable C, �i t Applicable 6.4,3.12 Air economizer has a fault detection ClComplies (FI200]3 and diagnostics(FDD)system(see ODoes Not details for configuration and operational requirements). ONot Observable ONot Applicable 6.4.3.6 When humidification and ❑Complies [F16]3 dehumidification are provided to a ODoes Not zone,simultaneous operation is prohibited. Humidity control prohibits ,❑N t Observable the use of fossil fuel or electricity to �-=-Not Applicable produce RH > 30%in the warmest zone humidified and RH <60%in the coldest zone dehumidified. _ �� 6.7.2.1 Furnished HVAC as-built drawings t mplies [FI7]3 submitted within 90 days of system ODoes Not acceptance. ONot Observable ❑N t Applicable 6.7.2.2 Furnished O&M manuals for HVAC Beomplies [FIS]3 systems within 90 days of system ODoes Not acceptance. :Not Observable ONot Applicable 6.7.2.3 An air and/or hydronic system DComplies (FI9]1 balancing report is provided for HVAC ODoes Not systems serving zones>5,000 ft2 of ONot Observable conditioned area. I'P'N;of"Applicable 10.4,3 Elevators are designed with the OComplies [FI24]2 proper lighting,ventilation power,and ODoes Not standby mode. ❑ Observable of Applicable Additional Comments/Assumptions: L1 IHiQh Impact(Tier 1) 12 jMedium Impact(Tier 2) 13 ILow Impact(Tier 3) Project Title: Sim Golf Report date: 10/12/21 Data filename: Page 9 of 9