Report (3) WEz2bz/- OD.S6
COMeheck Software Version COMcheckWeb
Mechanical Compliance Certificate
Wel raglill
Project Information
Energy Code: 90.1 (2019) Standard
Project Title: Sim Golf
Location: Tigard, Oregon
Climate Zone: 4c
Project Type: Addition
Construction Site: Owner/Agent: Designer/Contractor:
10114 SW Washington Square Rd Clint Latimer
#A07 Latimer HVAC LLC
Tigard,Oregon 97223 clint@latimerhvac.com
Mechanical Systems List
QuantitySystem Type & Description
1 HVAC System(Single Zone):
Heating: 1 each-Central Furnace,Gas,Capacity=125 kBtufh
Proposed Efficiency= 80.00%Et,Required Efficiency: 80.00%Et(or 80%AFUE)
Cooling: 1 each-Single Package DX Unit, Capacity= 88 kBtu/h,Air-Cooled Condenser,Air Economizer
Proposed Efficiency= 11.00 EER,Required Efficiency: 11.00 EER + 12.7 PEER
Fan System: FAN SYSTEM 1--Compliance(Motor nameplate HP and fan efficiency method) : Passes
Fans:
FAN 1 Supply,Constant Volume,3000 CFM, 1.9 motor nameplate hp,0.00 fan energy index,fan exception: Fan
array<= 5 total HP or<=4.1 kW
Mechanical Compliance Statement
Compliance Statement: The proposed mechanical design represented in this document is consistent with the building plans,
specifications,and other calculations submitted with this permit application.The proposed mechanical systems have been
designed to meet the 90.1 (2019)Standard requirements in COMcheck Version COMcheckWeb and to comply with any applicable
mandatory requirements listed in the Inspection Checklist
CI I Of-
1,,e 10lIl/?.a2-
Name-Title Si ture Date
Project Title: Sim Golf Report date: 10/12/21
Data filename: Page 1 of 9
COMeheck Software Version COMcheckWeb
Inspection Checklist
Energy Code: 90.1 (2019) Standard
Requirements: 0.0% were addressed directly in the COMcheck software
Text in the "Comments/Assumptions" column is provided by the user in the COMcheck Requirements screen. For each
requirement, the user certifies that a code requirement will be met and how that is documented, or that an exception
is being claimed. Where compliance is itemized in a separate table, a reference to that table is provided,
Section
Plan Review Complies? Comments/Assumptions
& Req.JD �
4.2.2, Plans,specifications,and/or LJComplies
6.4.4.2.1, calculations provide all information ,ODoes Not
6.7.2 with which compliance can be
[PR2]1 determined for the mechanical Not Observable
systems and equipment and ONot Applicable
document where exceptions to the
standard are claimed.Load
calculations per acceptable
;engineering standards and
handbooks.
4.2.5.2 Commissioning shall be performed as aComplies
[PR5]1 stated in Sections 5.9.2,6.9.2, 7.9.2, ❑Does Not
8.9.2, 9.9.2, 10.9.2, 11.2(d),and
G1.2.1(c).Commissioning must utilize Not Observable
ASHRAE/IES Standard 202 or other ONot Applicable
generally accepted engineering
standards acceptable to the building
official. FPT and verification
requirements for commissioning are
as stated in Section 4.2.5.1.
Commissioning shall document
compliance of the building systems,
;controls,and building envelope with
',required provisions of this standard.
;Commissioning requirements shall be
:incorporated into the construction
;documents.
Additional Comments/Assumptions:
r1 High Impact(Tier 1) 2 Medium Impact(Tier 2) 3 Low Impact(Tier 3)
Project Title: Sim Golf Report date: 10/12/21
Data filename: Page 2 of 9
.au.:.-.a..H.....x:.u:uu.:aastau,ruau+sautuutawu.i`wu+uttauewaxru... ••
Section
Footing/Foundation Inspection Complies? Comments/Assumptions
& Req.ID
6.4.3.7 Freeze protection and snow/ice OComplies
(FO913 melting system sensors for future ❑Does Not
connection to controls.
ONpt Observable
,IMfiot Applicable
Additional Comments/Assumptions:
1 High Impact(Tier 1) 2 Medium Impact(Tier 2) 3 Low Impact(Tier 3) i
Project Title: Sim Golf Report date: 10/12/21
Page 3 of 9 Data filename:
Section Mechanical Rough-In Plans Verified Field Verified
# Inspection Value Value Complies? Comments/Assumptions
& Req.ID �,f
6,4.1.4, HVAC equipment efficiency Efficiency: . Efficiency: ;L`1Complies See the Mechanical Systems list
6.4.1.5 verified. Non-NAECA HVAC Does Not for values.
[MEl]2 equipment labeled as meeting •
90.1. :Not Observable
_ __ _ ONot Applicable
6.4.3.4.1 Stair and elevator shaft vents OComplies
[ME3]3 have motorized dampers that ❑Does Not
automatically close.
❑ t Observable
BNot Applicable
6.4.3.4.2, Outdoor air and exhaust systems r� DComplies
6.4.3.4.3 have motorized dampers that DDoes Not
[ME4]3 automatically shut when not in
use and meet maximum leakage ❑ t Observable
rates.Check gravity dampers Q:Not Applicable
__ where allowed.
6.4.3.4.5 Enclosed parking garage -- _ DComplies
[ME39]3 ventilation has automatic DDoes Not
contaminant detection and
capacity to stage or modulate ❑.�t Observable
fans to 50%or less of design Cu1Not Applicable
capacity.
6.4.3.4.4 Ventilation fans>0.75 hp have [J`Complies
[ME5P automatic controls to shut off fan DDoes Not
when not required.
ONot Observable
❑N�t Applicable
6.4.3.8 Demand control ventilation EJ omplies
[ME6]1 provided for spaces>500 ft2 and DDoes Not
>25 people/1000 ft2 occupant
density and served by systems ONot Observable
with air side economizer,auto ONot Applicable
modulating outside air damper
control,or design airflow >3,000
cfm.
6.5.3.2.1 DX cooling systems >= 75 kBtu/h DComplies See the Mechanical Systems list
`[ME40]2 (>= 65 kBtu/h effective 1/2016) ❑Does Not for values.
and chilled-water and
evaporative cooling fan motor hp ONot Observable
>= 1/4 designed to vary supply ONot Applicable
fan airflow as a function of load
and comply with operational
_ _ requir_e_ments. _ ,�r_
6.4.4.1.1 Insulation exposed to weather DComplies
[ME7]3 protected from damage. DDoes Not
Insulation outside of the
conditioned space and associated ONot Observable
with cooling systems is vapor 'DNot Applicable
retardant.
6.4.4.1.2 HVAC ducts and plenums R-4— R- DComplies
4[ME8]2 insulated per Table 6.8.2.Where ❑Does Not
ducts or plenums are installed in
or under a slab,verification may :Not Observable
need to occur during Foundation .❑Not Applicable
Inspection. z
6.4.4.1.3 HVAC piping insulation thickness. In. _in. ;IComplies
[ME9I2 Where piping is installed in or DDoes Not
under a slab,verification may
need to occur during Foundation ONot Observable
_ Inspection. ,ONot Applicable
6.4.4,1.4— Thermally ineffective panel DComplies •
,: [ME41]3 surfaces of sensible heating DDoes Not
panels have insulation>= R 3.5. GIN&Observable
Not Applicable '
1 High Impact(Tier 1) 1 2 `Medium Impact(Tier 2) 3 Low Impact(Tier 3)
Project Title: Sim Golf Report date: 10/12/21
Data filename: Page 4 of 9
li
Section I Mechanical Rough-In
Inspection Plans Verified Field Verified
Value Value# Complies? Comments/Assumptions
L& Req.ID i
6.4.4.2.1 Ducts and plenums having Complies
i[ME10]2 pressure class ratings are Seal ❑Does Not
' Class A construction.
ONot Observable
I ONot Applicable
6.8.1-15,—Electrically operated DX-DOAS V__�..._____._______..____ �.___ ❑Complies
16.8.1-16 units meet requirements per ❑Does Not
'[ME110]2 Tables 6.8.1-15 or 6.8.1-16.
❑pt Observable
SNot Applicable
6.4.4.2.2 Ductwork operating >3 in.water ❑Complies
[ME11]3 column requires air leakage ODoes Not
testing.
DNA Observable
E Plot Applicable '
6.5.2.3 Dehumidification controls ❑Complies
[ME19]3 provided to prevent reheating, DDoes Not
recooling, mixing of hot and cold
airstreams or concurrent heating ONot Observable
and cooling of the same 17114ot Applicable
airstream.
6.5.2.4.1 Humidifiers with airstream ❑Complies
[ME68]3 mounted preheating jackets have DDoes Not
preheat auto-shutoff value set to
activate when humidification is ❑N9t Observable
not required. of Applicable
6.5.2.4.2 Humidification system dispersion ❑Complies
[ME69]3 tube hot surfaces in the ODoes Not
airstreams of ducts or air-
handling units insulated >= R- ❑N, Observable
0.5, LL�Hoot Applicable
6.5.2.5 Preheat coils controlled to stop —�W — LNComplies
(ME70]3 heat output whenever ODoes Not
'mechanical cooling, including
economizer operation, is active. ONot Observable
❑Not Applicable
6.5.2.6 Units that provide ventilation air ❑Complies
[ME106]3 to multiple zones and operate in ODoes Not
conjunction with zone heating
and cooling systems are ❑ t Observable
prevented from using heating or L'iNot Applicable
heat recovery to warm supply air
,above 60°F when representative
building loads or outdoor air
temperature indicate that most
zones demand cooling.
6.5.3.6 Motors for fans>= 1/12 hp and C'Complies
[ME72]2 < 1 hp are electronically- ODoes Not
commutated motors or have a
minimum motor efficiency of ONot Observable
70%.These motors are also ONot Applicable
speed adjustable for either
balancing or remote control.
1'High Impact(Tier 1) 12 Medium Impact(Tier 2) 3 Low Impact(Tier 3)
Project Title: Sim Golf Report date: 10/12/21
Data filename: Page 5 of 9
Section Mechanical Rough-In Plans Verified Field Verified
& Re ID Inspection Value Value Complies? Comments/Assumptions
16.5.3.4 Parallel-flow fan-powered VAV air ❑Complies
[ME10812 terminals have automatic ODoes Not
controls to a)turn off the
terminal fan except when space ['Not Observable
heating is required or if required LUNot Applicable
for ventilation; b)turn on the
terminal fan as the first stage of
heating before the heating coil is
activated; and c)during heating
for warmup or setback
temperature control,either
operate the terminal fan and
heating coil without primary air s
or reverse the terminal damper
logic and provide heating from
the central air handler through
primary air. ;���
16.5.3.7 Required minimum outdoor air l Complies
(ME109)2 rate is the larger of minimum ODoes Not
outdoor air rate or minimum
exhaust air rate required by ❑Not Observable
Standard 62.1, Standard 170,or ❑Not Applicable
applicable codes or accreditation
standards.Outdoor air ventilation
systems shall comply with one of ,{
the following: a)design minimum
system outdoor air provided <
135%of the required minimum
outdoor air rate, b)dampers,
ductwork,and controls allow the
system to supply<=the
required minimum outdoor air
rate with a single set-point
adjustment.,or c)system
includes exhaust air energy
recovery complying with Section
6.5.6.1.
6.5.3.3 Multiple zone VAV systems with ❑Complies See the Mechanical Systems list
[ME42]3 DDC of individual zone boxes ODoes Not for values.
have static pressure setpoint ❑Ndt Observable
reset controls.
of Applicable
6.5.4.2 HVAC pumping systems with >_ ❑Complies
[ME25]3 3 control values designed for ODoes Not
variable fluid flow(see section ❑ Observable
details).
IVot Applicable
6.5.6.1.1 Exhaust Air Energy Recovery for ❑Complies
[ME56]1 Nontransient Dwelling Units ODoes Not
DN,ot Observable
gigot Applicable
6.5.6.1.2 Exhaust air energy recovery for ❑Complies
[ME111]1 spaces other than Nontransient ODoes Not
dwelling units meeting Tables
6.5.6.1.2-1,and 6.5.6.1.2-2. ❑Npt'Observable
flEfiot Applicable
Kitchen hoods>5,000 am have � ❑compiles
[ME3212 make up air>=50%of exhaust ODoes Not
air volume.
❑N Observable
I^� of Applicable
1 High Impact(Tier 1) 2 Medium Impact(Tier 2) 3 Low Impact(Tier 3) J
Project Title: Sim Golf Report date: 10/12/21
Data filename: Page 6 of 9
aaeaa Ha .a waa s4U4W., „aaauswa _
Section iMechanical Rough-In Plans Verified Field Verified
I
Complies? Comments/Assumptions
& Re !D j Inspection Value Value
6.5.7.1 Conditioned supply air to space 26omplies
[ME100]2 with mechanical exhaust<=the ❑Does Not
greater of criteria of supply flow,
required ventilation rate,exhaust :Not Observable
flow minu the available transffer ONot Applicable
air(see section details).
6.5.3.8 'Occupied standy controls for ���� omplies
[ME112]1 zones serving rooms that are ❑Does Not
required to have automatic
partial OFF or automatic full OFF fI k GNot Observable
lighting controls per Section ? ❑Not Applicable
'9.4.1.1 shall meet the following
within five minutes of all rooms in ",y
that zone entering occupied- '
'standby mode: a)Active heating
set point shall be setback at least
1°F, b)Active cooling set point
shall be setup at least 1°F and i
c)All airflow supplied to the zone
shall be shut off whenever the
space temperature is between
the active heating and cooling
set points. _�
6.5.7.2.4 Approved field test used to CJComplies
[ME49]3 evaluate design airflow rates ❑Does Not
and demonstrate proper capture ❑Not Observable
and containment of kitchen
exhaust systems. ❑Not Applicable
6.5.8.1 Unenclosed spaces that are ❑Complies
[ME3412 heated use only radiant heat. ❑Does Not
❑l t Observable
L Not Applicable
6.5.9 Hot gas bypass limited to: <=240 a ElO omplies
[ME35]1 kBtu/h-15%>240 kBtu/h-10% ❑Does Not
:Not Observable
❑Not Applicable
6.4.3.9 Heating for vestibules and air DComplies
[ME63]2 curtains with integral heating ❑Does Not
include automatic controls that ❑N t Observable
shut off the heating system when
outdoor air temperatures>45F. L'dNot Applicable
Vestibule heating and cooling
systems controlled by a
thermostat in the vestibule with
heating setpoint<=60F and t.�)"
cooling setpoint>= 80F.
6.5.10 Doors separating conditioned
[ME73]3 space from the outdoors have DDoes Not
controls that disable/reset
heating and cooling system when ❑Not Observable
open. ❑Not Applicable
Additional Comments/Assumptions:
1 High Impact(Tier 1) 2 Medium Impact(Tier 2) 3 Low Impact(Tier 3)
Project Title: Sim Golf Report date: 10/12/21
Data filename: Page 7 of 9
____ _______ ___ _.. _. __ .+«...n..wwwawwwwwwawawwxxutauauaulutuNUNIuuNNWdHNNANNtNtti{Idi !
Section
Rough-In Electrical Inspection Complies? Comments/Assumptions
& Req.ID v�/
10.4.1 Electric motors meet requirements L�Complies
[EL9]2 where applicable. ❑Does Not
❑Not Observable'
❑Not Applicable
Additional Comments/Assumptions:
1 High Impact(Tier 1) 12 {Medium Impact(Tier 2) 3 Low Impact(Tier 3)
Project Title: Sim Golf Report date: 10/12/21
Data filename: Page 8 of 9
m,wwueauaswt»uiuwetee...6uNtHHtNtisil#......YMHiNNNiilliltiMlawateastuActaueWiNeia AN... •:
Section
Final Inspection Complies? Comments/Assumptions
& Req,ID
6.4.3.1.2 Thermostatic controls have a 5°F omplies
[F13]3 deadband. ODoes Not
ONot Observable
O
Not Applicable
6.4,3.2 Temperature controls have setpoint ,2Complies
[F120]3 overlap restrictions. :❑Does Not
I❑Not Observable'
❑Net Applicable
6.4.3.3.1 HVAC systems equipped with at least INIComplies
[FI21]3 one automatic shutdown control. ODoes Not
ONot Observable
_ ,D,�NN�ot Applicable
6.4.3.3.2 Setback controls allow automatic It�Complies
[F122]3 restart and temporary operation as ODoes Not
required for maintenance.
ONot Observable
C, �i t Applicable
6.4,3.12 Air economizer has a fault detection ClComplies
(FI200]3 and diagnostics(FDD)system(see ODoes Not
details for configuration and
operational requirements). ONot Observable
ONot Applicable
6.4.3.6 When humidification and ❑Complies
[F16]3 dehumidification are provided to a ODoes Not
zone,simultaneous operation is
prohibited. Humidity control prohibits ,❑N t Observable
the use of fossil fuel or electricity to �-=-Not Applicable
produce RH > 30%in the warmest
zone humidified and RH <60%in the
coldest zone dehumidified. _ ��
6.7.2.1 Furnished HVAC as-built drawings t mplies
[FI7]3 submitted within 90 days of system ODoes Not
acceptance.
ONot Observable
❑N t Applicable
6.7.2.2 Furnished O&M manuals for HVAC Beomplies
[FIS]3 systems within 90 days of system ODoes Not
acceptance. :Not Observable
ONot Applicable
6.7.2.3 An air and/or hydronic system DComplies
(FI9]1 balancing report is provided for HVAC ODoes Not
systems serving zones>5,000 ft2 of ONot Observable
conditioned area. I'P'N;of"Applicable 10.4,3 Elevators are designed with the OComplies
[FI24]2 proper lighting,ventilation power,and ODoes Not
standby mode. ❑ Observable
of Applicable
Additional Comments/Assumptions:
L1 IHiQh Impact(Tier 1) 12 jMedium Impact(Tier 2) 13 ILow Impact(Tier 3)
Project Title: Sim Golf Report date: 10/12/21
Data filename: Page 9 of 9