Report (2) u . W
/-iF 2/- oo6E6
ib/zo Kmsrrf sqi2 go 1FFICE COPY
RM1Carr1er
SUBMITTAL
Project
Sim Golf
Date
Monday,October 11,2021
. .
���K� �� �~�������
"~°~""~~ ~=" ~~~~""�=""��
Project:Sim Golf 10M1/2021
Prepared By: 09:49AM
rtu~I--'__—'—_—
UnitRe _4
Certified Drawing
Performance Summary-_.
Unit Feature Sheet- �1
Spec Sh ____ __ _ 12
Packaged Rooftop Builder 1.6O Page 2of12
rtu-1
Project:Sim Golf 10/11/2021
Prepared By: 09:49AM
rtu-1
Tag Cover Sheet
Unit Report
Certified Drawing
Performance Report
Unit Feature Sheet
Spec Sheet
Packaged Rooftop Builder 1.60 Page 3 of 12
Unit Report For rtu-1
Project:Sim Golf 10/11/2021
Prepared By: 09:49AM
Unit Parameters Dimensions (ft. in.) & Weight(lb.) ***
Unit Model: 48TCDD08A2A5-0A0G0 Unit Length: __7'4.125"
Unit Size: _..-._ __,•,_._ 08 (7.5 Tons) Unit Width: --.-..-- _- '
11.5"
Volts-Phase-Hertz: 230-3-60 Unit Height: __-_-- 3' 5.25"
Heating Type: _ Gas ••* Total Operating Weight:---__,_-. �__---_870 b
Duct Cfg: Vertical Supply / Vertical Return
Low Heat *** Weights and Dimensions are approximate. Weight
Round Tube Plate Fin Coils does not include unit packaging. Approximate
dimensions are provided primarily for shipping
purposes. For exact dimensions and weights, refer
to appropriate product data catalog.
Lines and Filters
Gas Line Size: 1/2
---------- ---------------------
Condensate Drain Line Size: _ .__3/4
Return Air Filter Type: Throwaway
Return Air Filter Quantity:. 4
Return Air Filter Size: 16 x 20 x 2
Unit Configuration
Medium Static Option(Belt Drive)
Al/Cu-Al/Cu
Base Electromechanical Controls
Standard Packaging
2-Speed indoor fan motor controlled by VFD
Warranty Information
1-Year parts(std.)
5-Year compressor parts(std.)
10-Year heat exchanger-Aluminized(std.)
15-Year heat exchanger-Stainless Steel(std.)
No optional warranties were selected.
Ordering Information
Part Number Description Quantity
48TCDD08A2A5-0A0G0 Rooftop Unit 1
Packaged Rooftop Builder 1.60 Page 4 of 12
Certified Drawing for rtu-1
Project:Sim Golf 10/11/2021
Prepared By: 09:49AM
NOTES: UNITED P.O.IOU IRON TNIE DMIMENT IE iNC PROREST!R CARRISM CORPOAAIIpI
UNIT OUTDOOR 3 N N TECHNOLOGIES STNACDSE,n ASS IS DELIVERED UPON TDE ESPAESS C01(DITIOS TRAT TNF SUINISSIDN OP TRUE DAARRDS OR DOEUNENTS
1. DIMENSIONS ARE IN INCHES DIMENSIONS COIL TYPE CARR[ER vuI CONTENTS pll MOT RE SISCl03ED OS USED NTTXOD1 CMRI CA ODES NOTA�KEIT,IIIRDE RA[Mii.W1F[T �E OR
IN I 1 ARE IN MILLIMETERS. 41 1/4 33 3/4 15 7IB CwroAATION4:ITm coxnNr.
2. CENTER OF GRAVITY 481C-A0B RTPF 11048] [8571 [403]
487C-A09 RTPF I12531 (925/] 2[71581 CONNECTION SIZES
3.0*DIRECTION OF AIR FLOW 49 3/8 36 3/8 15 7/8 A 1 3/8• [351 DIA FIELD POWER SUPPLY HOLE
3/8
48TC-Al2 RTPF (1253] [9251 [403] [0[10UR]
8 2 1/2' L641 DIA POWER SUPPLY KNOCKOUT
"1 67
/1 1/4 33 3/4 15 118
48TC-DOB RTPF C 1 3/1' [51]DIA GAUGE ACCESS PLUG
(1D487 L8511 [/031
48TC-DON RIPE 19 3/8 36 3/8 15 718 - - I D 7/8' [221 DIA FIELD CONTROL WIRING HOLE
[1253] [9257 [/037 20-3// E 3/4•-14 NPT CONDENSATE DRAIN
19 318 36 3/8 15 7/8 ECONOMIZER HOOD F 1!2'-1/NPT GAS CONNECTION
48TC-D12 RTPF t1253) 1925] [/031 - (OPTIONAL] • I527] 3/4'-14 NPT GAS CONNECTION
IbTG DOB NCNX 41 1/4 33 3/4 23
110481 [8571 1584.21 G 2 [511 DIA POWER SUPPLY KNOCK-OUT
48TC-D12 NCH% 19 3/8 3630
11 A- _ - 't
I12s3] [92s7 [2i9.41 THRU-THE-BASE CHART (FIELD INST)
RTPF-ROUND TUBE, PLATE FIN(COPPER/ALUM( '_-ACHE-500611OX(ALUM/ALUNI • �-- I THESE HOLES REQUIRED FOR USE WITH ACCY NITS:
//1 \\ 36-3/8 12-5/8 CRBTNPWR002A01:GAS THRU CURB
t�;l 4!�. 19251 [321] GRUMPWR0040.01: GAS THRU BASEPAN
• '(I �� I RETURN AIR - ; 1 AIRURN THREADED WIRE REO'D HOLE
/� CONDUIT SIZE USE SIZES(MAX.)
..
2 Y P -
'' I + N 1/2' ACC. 7/8' (22.21
FILTER ACCESS PANEL - � I X 1/2' 24V 7/8' 122.21
• (TOOL-LES51 -• E SAT. - -
CONDENSATE Y 1 1/4' 1002,0041 POWER 1 3/4' [44.41
'DRAIN OPENING 28-3/4
i
CONDENSER /.� 7. IN BASEPAN [7311 37-5/8 40-316NO, Z• (0041 3/4'FPT GAS 1 314' 144.4]
N L
SUPPLY (955] (10271
INDOOR COIL 1�;` ��) ;19 7 X SEE THRU AIR SUPPLY D (002]PROVIDES 3/4'FPT THRU CURB
/' �.. THE BASE FLANGE 6 FITTING, HOLE SIZE: 2' t50.81
ACCESS PANEL - �V� %A' CHART 3
AIR
18
BACK [469][1121 pass] 17 \"� THRU-THE-BASE CHART (FIOP)
__ (2791 V — FOR'THRU-THE-BASEPAN'FACTORY OPTION,
P'�LTCS t _F, -r -]N UC7� FITTINGS FOR ONLY X. Y, b Z ARE PROVIDED. NN
• FOR BELOW LISTED MODELS.A FIELD
6-1/4 SUPPLIED 1/2'ADAPTER IS REQUIRED
-4 [1591 WR BETWEEN BASE PAN FITTING AND GAS VALVE:
t— 29-5/8 --.- [100] NLUp y 11 ~� IB374 48TCD,S•08,09
[751113561
TOP _—25-1/2
1647]
H 1-1/4
1-5/8 [32] 12-5/8
[1(81 [321]
�I A f
LECTRICAL CONTROL BOX DISCONNECTE STD.
A, LOCATION ACCESS PANEL CONDENSATE 'I FILTER
CONDENSER B, N�II F-1 DRAIN
COIL G ' ' r 28-3t8
Ij 51- ® INDOOR BLOWER 17201
OPTIONAL
OPTIONAL 3 FACTORY ACCESS SUPPLY AIR
FACTORY I INSTALLEDINSTALLED27 7/B 1 1 OUTSIDE
CONVENIENCE I� C7081 DISCONNECT ANDLE 13718 26AIR
C- -OUTLE7 7 II- �_� /�--H [353] i[ j
'HANDLE ! i � 16591
i g -7— H n681 I ';100 '(3- L ,E=1' : : 00 j, 401 _ -
3-3/1 2-5/8-•• 6-1/4 7 5-3/4 4-3/8
1951 59-1/2 8.3/8 (1601 (1771
(fill
[15101 (67 37 [2141 37-7/8 (146] 4, 11131
TIP19401 19621
41-7/8
LEFT WIDTTH 88-1/8 [10651 BAROMETRIC
[22387 SAIUPPLYR RETURN RELIEF
FRONT RIGHT AIR FLOW
INSET DATE SUPERMEN 48TC 08-12 SINGLE ZONE ELECTRICAL WEE
1oF2 10-01-10 11-24-08 COOLING WITH GAS HEAT 48TM500985 F
Packaged Rooftop Builder 1.60 Page 5 of 12
Certified Drawing for rtu-1
Project:Sim Golf 10/11/2021
Prepared By: 09:49AM
ot UNITED P.O.ION ISO THIS HOCMIERT IS THE PROPERTY 0 CARRIER CORPONATIN SUIMISSIOR Of THESE MENU OR OOCONNTS
STD. UNIT CORNER CORNER CORNER CORNER TECHNOLOGIES SYRACUSE,RT ANO IS UELIVEREO OPON THE ESMESS C01RIT70N THAT THE 00%S NOT MINIM PART PERFORMANCE OR
C0ITCNTS OILI MDT 8[DISCLOSCO OA HSED RITNWT CAARICA
UNIT OUTDOOR WEIGHT RNa WEIGHT(A1 WEIGHT 181 WEIGHT(CI WEIGHT (D> C.G. CARRIER 10zzt CORPORATION'S RATTLER CONSENT. ACCEPTANCE 0 CONTRACT.
COIL TYPE LBS. KG. LBS. K6. LBS. KG. LBS. KG. LBS. K6. % T 2
48TC-408 RTPF 780 354 178 81 158 72 209 95 236 107 41 1/2[10541 33 7/8[860] 20 1/2 [521] NRN STANDARD UNIT WEIGHT IS WITH LOW GAS HEAT AND WITHOUT PACKAGING.
48TC-409 RTPF 920 418 212 96 183 83 243 110 282 126 40 7/8 110381 34 [8641 21 1/8 15871 FOR OTHER OPTIONS AND ACCESSORIES, REFER TO THE PRODUCT DATA CATALOG.
487C-412 RTPF 930 422 216 98 196 89 241 112 272 123.5 42 110671 33 1/8 18411 24 1/4 1616]
481C-008 RTPF 835 379 164 74.5 170 77.2 25S 115.8 246 111.7 44 7/8 11140] 35 5/8[905] 19 3/8 14921
48TC-009 RTPF 930 422 228 103.5 187 85 232 105.3 283 128.5 39 3/4 [10101 32 7/8[835] 18 5/8 14731
481C-012 RTPF 940 421 231 104.9 189 85,8 234 106.2 286 129.8 39 3/4 [[010] 33[8381 18 1/2 1470]
48TC-008 NCH% 805 365.5 160 72.6 153 69,5 240 109 260 118 43[1092] 38 3/8 19241 20 3/8[511.71
48TC-012 NCH% 895 406.3 185 81 176 79.9 260 118 274 124.4 42 7/8 110891 35 1/2 1902] 22 7/8[5811
RIPE-ROUND T PLATE UBE, (COPPER/ALUM) CORNER A
NCH%-909400ON (ALUM/ALUM CORNER 8
I
, ''/, ,-------,"-j--- , .',
T fit , -J/�/;
•
CORNER D U CORNER C
TOP
%
I.- 1
•
• c=i
1 .
FRONT
SHEET DATE SOPERCED1S 48TC 08-12 SINGLE ZONE ELECTRICAL REV
48TM500985
20F 2 10-01-10 11-24-08 COOLING WITH GAS HEAT F
Packaged Rooftop Builder 1.60 Page 6 of 12
Certified Drawing for rtu-1 .
Project:Sim Golf 10/11/2021
Prepared By:
09:49AM
Service Clearance
�10000.
� i r
4i
C11247
LOCATION DIMENSION CONDITION
48-in(1219 mm) •Unit disconnect is mounted on panel
36-in(914 mm) •If dimension-0 is 12-in(305 mm)
A 18-in(457 mm) •No disconnect,convenience outlet option
•Recommended service clearance(use electric screwdriver)
12-in(305 mm) •Minimum clearance(use manual ratchet screwdriver)
36-in(914 mm) •Unit has economizer
B 12-in(305 mm) •If dimension-A is 36-in(914 mm)
Special •Check for sources of flue products within 10-ft of unit fresh air intake hood
C 36-in(914 mm) •Side condensate drain is used
18-in(457 mm) •Minimum clearance
48-in(1219 mm) •No flue discharge accessory installed,surface is combustible material
42-in(1067 mm) •Surface behind servicer is grounded(e,g.,metal,masonry wall,another unit)
D 36-in(914 mm) •Surface behind servicer is electrically non-conductive(e.g.,wood,fiberglass)
Special •Check for adjacent units or building fresh air intakes within 10-ft of this unit's
flue outlet
NOTE:Unit not designed to have overhead obstruction.Contact Application Engineering for guidance on any
application planning overhead obstruction or vertical clearances.
Packaged Rooftop Builder 1.60 Page 7 of 12
Performance Summary For rtu~1
Project:Sim Golf 1011/2021
Prepared By: 09:48AM
Part Number:48TCCI
AREER _ 11.00
IEE1:Z-------------- __ 12'8
Base Unit Dimensions
Unit�eng��� _ 88.1 in
UnitVViUth:______. __. _ 59.5 in
Unit Height:.-.--,-,,. 41.3 in
Operating Weight
Base Unit VV�igh�� ��� lb
Medium Static Option(Belt Dhvo): — -1� �
2 Speed Fan Contm||ar (VFD)' ____ _ _____ _____ 20 Ib
Total Operating Weight— _ ____ _ _ __ _ 870 b
Unit
UnitVo|uoga-Phese-He¢r:-____ _ 230'3-60
Air Discharge: --'__ _-�Vertical
Fan Drive Type: _ ga|t
Actual Airflow:.. ��n� CFM
Site Altitude: _ 39 ft
. Cooling Performance
Condenser Entering Air DB: ______----------gV.0 F
Evaporator Entering Air D8: _____ 78.0 F
Evaporator Entering Air YVB: _ 64.4 F
Entering Air Entho|py: _��.4g 8TLNh
Evaporator Leaving Air DB:__ 56.3 F
Evaporator Leaving Air VVB: _ _ ___54.6 F
Evaporator Leaving Air Entho|py:-______ 23.93 BTUAb
Gross Cooling Capacity:_--------- 88.40 N0H
Gross Sensible Capaci|y:______ ------- 70.45 M]M
Compressor Power|nput:___ _ ---_' 5.97 MN
Coil Bypass Factor: _ _ 0104
;
Mixed Air
Outdoor Air Airflow: __420 {FN
` Outdoor Air DB: 90.0 F
Outdoor Air VVB: _ ____ ___ 6T.O F
Outdoor Air nto Temp.:______ ----------22.V p
Return Air DD:| 7�.O F'---------' ---'-- -----
` Ro�um/urVv8� _- ___---_-_ 64.0 F
Return Air ntg.Tomp.:- —_- --_. -_--__----'70.0 p
| Heating Performance
Heating Airflow:-------___ _ 3000 CpM
Entering Air Tomp� __ 63.3 F
Leaving Air Tomp,..--- _________ __________. _____ ______'95.1 F
Gas Heating Input Capaoig/: __12s.0 K��|-----
. Gas Heating Output Capacity: 103.0 MBH
Temperature Rion� -�31.8 F
Thermal Efficiency —_-__-82.0
Supply Fan
External Static Pressure: __ ______jD.80 inwg
Fan RPM: _-- __'-_- 818
' Fan Power 1.g5 BHP
| _
NOTE:_ ____'-Sw|mctwd|FAH RPM Range: 733'q49
Electrical Data
| Packaged Rooftop Builder 1.0V Page 0of12
ueuaaxwu.uunawuaauwu4uuarwuuuunuusyu{ff.N.###yM#MfUIMW!!Nf##sNIINN!}#NFffld4Nu.. .
Performance Summary For rtu-1
Project:Sim Golf 10/11/2021
Prepared By: 09:49AM
Voltage Range: _
Compressor#1 RLA: 13.6
Compressor#1 LRA: 83
Compressor#2 RLA:-_--___ _ - 13.6
Compressor#2 LRA: 83
__-__.._____...._
Indoor Fan Motor Type:-_-_--__-__- _ MED
Indoor Fan Motor FLA: -__ -_- 8.3
Combustion Fan Motor FLA(ea):-__- 0.48
Power Supply MCA: _ _-_ 42
Power Supply MOCP(Fuse or HACR):_ _ _ - 50
Disconnect Size FLA: 44
Disconnect Size LRA: 227
Electrical Convenience Outlet:._ _._..._.-__. -_ None
Outdoor Fan[Qty/FLA(ea)]:_....
Control Panel SCCR: 5kA RMS at Rated Symmetrical Voltage
Acoustics
Sound Power Levels,db re 10E-12 Watts
Discharge Inlet Outdoor
63 Hz 98.6 95.7 85.8
125 Hz 91.8 86.9 84.3
250 Hz 78.9 74.6 80.5
500 Hz 71.4 67.2 78.7
1000 Hz 68.3 64.4 76.4
2000 Hz 67.0 59.5 72.7
4000 Hz 68.3 59.0 68.3
8000 Hz 71.2 58.5 65.1
A-Weighted 80.2 75.2 82.0
Advanced Acoustics
Advanced Accoustics Parameters
1.Unit height above ground: - 30.0 ft
2. Horizontal distance from unit to receiver: 50.0 ft
3.Receiver height above ground: _--_5.7 ft
4. Height of obstruction: _0.0 ft
5.Horizontal distance from obstruction to receiver: .-0.0 ft
6.Horizontal distance from unit to obstruction: 0.0 ft
Detailed Acoustics Information
Octave Band Center Freq. Hz 63 125 250 500 1k 2k 4k 8k Overall
Packaged Rooftop Builder 1.60 Page 9 of 12
Performance Summary For rtu-1
Project:Sim Golf 10/11/2021
Prepared By: 09:49AM
A 85.8 84.3 80.5 78.7 76.4 72.7 68.3 65.1 89.6 Lw
B 59.6 68.2 71.9 75.5 76.4 73.9 69.3 64.0 81.4 LwA
C 53.4 51.9 48.1 46.3 44.0 40.3 35.9 32.7 57.2 Lp
D 27.2 35.8 39.5 43.1 44.0 41.5 36.9 31.6 49.0 LpA
Legend
A Sound Power Levels at Unit's Acoustic Center, Lw
B A-Weighted Sound Power Levels at Unit's Acoustic Center, LwA
C Sound Pressure Levels at Specific Distance from Unit,Lp
D A-Weighted Sound Pressure Levels at Specific Distance from Unit,LpA
Calculation methods used in this program are patterned after the ASHRAE Guide;other ASHRAE Publications and the AHRI Acoustical
Standards. While a very significant effort has been made to insure the technical accuracy of this program,it is assumed that the user is
knowledgeable in the art of system sound estimation and is aware of the tolerances involved in real world acoustical estimation. This
program makes certain assumptions as to the dominant sound sources and sound paths which may not always be appropriate to the real
system being estimated. Because of this, no assurances can be offered that this software will always generate an accurate sound
prediction from user supplied input data. If in doubt about the estimation of expected sound levels in a space,an Acoustical Engineer or a
person with sound prediction expertise should be consulted.
Fan Curve
, ,_____ lam``
1 1100RPM *FM
18
,.��
16
---
- �\
_--__,,,_
14 1
- 700RPM
12
o 03 \ \
co _
U) 900I�NI
40CFPM
\ 3.008HP
200BHP
1.5°B1P '
02 ! 1.OI18FP
0.50EFP
U7581-P
CO 04 CB 12 16 X 24 28 32 M to 44
Airibw(CFM-thousands)
RPM=818 BHP=1.95 MaximumRPM=1400 MaximumBHP--4.70
Note:Pleasecontactapplicationengineeringforselectionsoutsidetheshaded.region.
SC-SystemCurve RP-RatedPoint
Packaged Rooftop Builder 1.60 Page 10 of 12
Unit Feature Sheet for rtu-1
Project:Sim Golf 10/11/2021
Prepared By: 09:49AM
Eciarrter)
(;)
WeatherMaker — 48TC
PACKAGED ROOFTOP GAS HEATING/ELECTRIC COOLING UNITS
6,7.5,8.5,10,12.5,15 TONS
STANDARD FEATURES INCLUDE:
• Puron(R-410A)HFC refrigerant
• Single-stage/single-circuit cooling capacity control on 07 models
• Two-stagethvo-circuit cooling capacity control on 08-16 models
• Two-stage/single circuit cooling capacity control on 08,09,12 models
• EER's up to 11 1
)i • IEER's up to 12.8
• Energy Saving Staged Air Volume(SAW')2-speed indoor fan motor
on two circuit(08-16)and 07 models Required in U S installations
Not available or required to meet DOE on 48TC'M models 08 09 12
• Scroll compressors with internal line break and overload protection
• Acutro 'and or TXV refrigerant metering system
i xr • Exclusive non-corrosive composite condensate pan in accordance with
r- ASHRAE Standard 62.sloping design,side or center drain
• Standard cooling operation up to 115°F(46:C)and down to 40'F(4°C)
- down to 25°F(-4'C)with Winter start kit
• Pre-painted exterior panels and primer-coated interior panels tested to
500 hours salt spray protection
Optional Louvered Hail Guard Shown • Exclusive IGC solid-state control for on-board diagnostics with LED
error code designation burner control logic and energy saving indoor
fan motor delay
• Induced draft gas heat combustion design
• Redundant gas valves with up to two stages of heating
IISnRNE • LOW pressure and high pressure switch protected
Pur
on MAINTENANCE FEATURES:
• Access panels with easy grip handles
COMPLIANT • Innovative easy starting,no-stnp screws on unit access panels
•Two-inch disposable return air filters and Tool-less filter access door
• Central terminal board facilitating simple safety circuit troubleshooting
WEATHERMAKER SERIES and simplified control box arrangement
WeatherMaker(48TC)units are one-piece gas heating,electric INSTALLATION FEATURES:
cooling units that are pre-wired and charged with Puron • Thru-Ihe-bottom power entry capability
(R-410) refrigerant. They are factor/ tested in both heating • Single point gas and electric connections
and cooling modes, and rated in accordance with AHRI • Full perimeter base rail with built-in rigging adapters and fork slots
Standard 340/360 (07-16 sizes). WeatherMaker units are • Field convertible from vertical to horizontal airflow for slab mounting
designed in accordance with UL Standard 1995. and listed by (16 size models require field installed supply duct cover).
the Underwriters'Laboratories.
STANDARD WARRANTY:
• 10-year heal exchanger-15-year stainless steel option
Approved and certified by: • 5-year compressor
• 1-year parts
• 3-year parts on Novation Condenser coils-where available
Alen CERTIfiEo. • Many optional upgrades also available
OPTIONS INCLUDE BUT ARE NOT LIMITED TO:
Htx1„� "° '' • PremierLink"and RTU Open Multi-Protocol CDC Controls
C(a)US s•noeae e. • Supply and Return Air Smoke Detectors,high static motors
Fer ra•�aos • Louvered condenser coil guards
s•W • Economizer,disconnect and convenience outlet options
• Stainless Steel heat exchanger option
• Humidi-MiZer°adaptive dehumidification system available on all
models with RTPF condenser coils-Motor Master I controller included
• Hinged access panels
• Condensate overflow switch
• VFD had field accessory display kit
ro,a aargM'a iiv nt cn+r-nx and accermones efea b s e Product Data CataWug it mr_
Packaged Rooftop Builder 1.60 Page 11 of 12
NFHl4itILL#iiYW}4iipAiif{.ffiHtNMMY}WU)#k1iW W WitiLitNiilii
Spec Sheet for rtu-1
Project:Sim Golf 10/11/2021
Prepared By: 09:49AM
Packaged Rooftop Builder 1.60 Page 12 of 12