Loading...
The URL can be used to link to this page
Your browser does not support the video tag.
Plans (14)
E LC2020 - 002 10 ABBREVIATIONS POWER COMMUNICATIONS Am& A AMPERE 0 i p AFC ABOVE FINISHED CEILING 1. ALL ENDS OF CONDUIT SYSTEM SHALL HAVE A BUSHING OR A COUPLING INSTALLED FOR THE AFF ABOVE FINISHED FLOOR HOMERUN TO PANEL INDICATED (CONCEALED). MINIMUM 3/4" CONDUIT. UNLESS OTHERWISEa DATA OUTLET - WALL MOUNTED - UON CENTER MOUNTED 18" AFF PURPOSE OF PROVIDING PROTECTION OF CONDUCTORS. AFG ABOVE FINISHED GRADE NOTED PROVIDE #12 CONDUCTORS AS REQUIRED BY THE NUMBER OF CIRCUITS SHOWN. 2. ALL LOW VOLTAGE WIRING IN INACCESSIBLE AREAS SHALL BE INSTALLED IN METALLIC CONDUIT. AHU AIR HANDLING UNITINCLUDE #12 GROUND AND #12 NEUTRAL CONDUCTORS. FOR HOMERUNS EXCEEDING 75' IN , TELEPHONE OUTLET - WALL MOUNTED - UON CENTER MOUNTED 18" AFF -LF G„,;,6_,AL ALUMINUM oJ IIOT� LENGTH PROVIDE #10 CONDUCTORS. FOR HOMERUNS EXCEEDING 100' IN LENGTH PROVIDE 3. CONDUIT SYSTEMS INSTALLED ON THE ROOF SHALL BE SUPPORTED EVERY FIVE FEET. ATS AUTOMATIC TRANSFER SWITCH #8 CONDUCTORS. THERE SHALL BE A MAXIMUM OF 2 BRANCH CIRCUITS FOR SINGLE PHASE . 1 DATA/TELEPHONE OUTLET - WALL MOUNTED - UON CENTER MOUNTED 18" AFF 4. E.C. TO PROVIDE ALL WIRING INCLUDING LOW VOLTAGE TO DRIVE-UP LANE DESIGNATOR SIGNAGE. 4 W AWG AMERICAN WIRE GAUGE AND 3 BRANCH CIRCUITS FOR THREE PHASE PER HOMERUN (AS INDICATED ON THE PLANS). REFER TO MANUFACTURERS WIRING DIAGRAMS. TEXT SHOWN BY HOMERUN INDICATES PANELBOARD DESIGNATION AND CIRCUIT NUMBER(S). I-C) TV OUTLET - WALL MOUNTED - UON CENTER MOUNTED 18" AFF BFC BELOW FINISHED CEILING 5. THE CONDUITS THAT CONTAIN THE SERVICE CONDUCTORS FROM THE METER TO THE ELECTRICAL BFP BACKFLOW PREVENTER a, v FLUSH FLOOR BOX WITH THE FOLLOWING: ROOM SHALL BE ENCASED IN A MINIMUM OF FOUR INCHES (4") OF CONCRETE. ) In (2) DATA OUTLETS 6. THE CIRCUIT BREAKERS FOR EMERGENCY LIGHTING AND EXIT SIGNS SHALL BE LOCATED IN THE C CONDUIT CONDUIT CONCEALED IN WALL OR ABOVE CEILING SPACE. UNLESS OTHERWISE NOTED v (2) TELEPHONE OUTLETS BOTTOM RIGHT OF THE ELECTRICAL PANEL IF APPLICABLE CAT CATEGORY PROVIDE #12 CONDUCTORS AS REQUIRED BY THE NUMBER OF CIRCUITS SHOWN. (1) QUAD RECEPTACLE OUTLET (ONE STANDARD AND ONE ISOLATED GROUND DUPLEX) 7. ALL WIRING FOR THE PURPOSE OF EMERGENCY SYSTEMS SHALL BE INSTALLED IN A SEPARATE CB CIRCUIT BREAKER INCLUDE #12 GROUND AND #12 NEUTRAL. MINIMUM 1/2" CONDUIT. WIREMOLD RFB4 SERIES CAST IRON FLOOR BOX WITH POWER AND COMMUNICATION CONDUIT SYSTEM AND COMPLETELY INDEPENDENT. CH CHILLER ACCESSORIES AS REQUIRED PLUS APPROPRIATE COVER PLATE IN BRASS FINISH. CKT CIRCUIT 8. THERE SHALL BE A SEPARATED IDENTIFIED NEUTRAL INSTALLED FOR EACH EMERGENCY LIGHTING CL CENTER LINE r-_ UNDERGROUND OR BELOW SLAB CONDUIT. UNLESS OTHERWISE NOTED PROVIDE #12 CONTRACTOR TO FURNISH AND INSTALL FLOOR BOX AND ALL OUTLETS, CONNECTORS, ETC. CIRCUIT AND/OR EXIT LIGHTING CIRCUIT. �'- CONDUCTORS AS REQUIRED BY THE NUMBER OF CIRCUITS SHOWN. INCLUDE 12 REFER TO ARCHITECTURAL DRAWINGS FOR LOCATION, CTG CUILRING # 9. THE FUSE HOLDER FOR THE PARKING LOT LIGHTING SHALL BE BUSSMANN IN-LINE, TYPE"HEB-AA"OR 5----------111:C6::---- mr CT CURRENT TRANSFORMER GROUND AND #12 NEUTRAL. MINIMUM 3/4" CONDUIT. �- CU COPPER EQUAL, WITH A RUBBER COVER "BOOT' TO BE INSERTED OVER THE CRIPED AREA OF THE FUSE HOLDER. DW DISHWASHER F IRE A _ A R M 10. AT LEAST TWO CORNERS OF EACH LIGHTING FIXTURE (CEILING GRID SYSTEMS) SHALL BE SUPPORTED DWG DRAWING . GROUND ROD AS INDICATED INDEPENDENTLY FROM ANY OTHER SUPPORTING SYSTEM. a0 11. ALL FLUORESCENT LIGHTING SHALL BE PROTECTED BY A MAXIMUM OF A TWENTY (20) AMP CIRCUITPri(j) U EB EQUIPMENT BOARD O CEILING OR WALL MOUNTED JUNCTION BOX - UON SIZE AS REQUIRED BY NEC O DUCT MOUNTED SMOKE DETECTOR - 120 VOLT - FURNISHED AND WIRED BY DIVISION 16 - BREAKER. EC ELECTRICAL CONTRACTOR EF EXHAUST FAN INSTALLED BY DIVISION 15 12. ALL GREENFIELD SHALL CONTAIN A PROPERLY SIZED GREEN GROUND CONDUCTOR AND SHALL NOT EM EMERGENCY MOTOR AS INDICATED EXCEED SIX FEET (6') IN LENGTH. EMT ELECTRICAL METALLIC TUBING ® REMOTE ALARM INDICATOR WITH KEY OPERATED TEST SWITCH, LED, AND RESET - WALL w SPD SURGE PROTECTIVE DEVICE AS INDICATED MOUNT 60" AFF TO CENTER 13. A 3/4" EMT CONDUIT AND A 2-1/2" EMT CONDUIT SHALL BE RUN INTO THE ATTIC SPACE FOR FUTURE a- ENCL ENCLOSURE - EXPANSION. A 3/4" EMT OR LARGER SHALL BE PROVIDED OFF OF THE SLAB AS WELL. THE ENDS OF EWC ELECTRIC WATER COOLER • SINGLE PUSHBUTTON - UON CENTER MOUNTED 48" AFF MAXIMUM n RELAY - FOR UNIT SHUT-DOWN SUCH CONDUITS SHALL BE PROTECTED BY AT LEAST ONE (1) BOX WITH A COMPLETELY ENCLOSED EWH ELECTRIC WATER HEATER COVER. EX EXISTING MIK PANELBOARD - BRANCH CIRCUIT TYPE - 120/208V 14. ALL BRANCH CIRCUIT CONDUCTORS SHALL BE CONNECTED BY MEANS OF A SCREW TERMINAL. RECEIVED FA FIRE ALARM 15. THE CONTINUITY OF ANY BRANCH CIRCUIT CONDUCTOR INCLUDING ANY IDENTIFIED GROUNDED APR 232020 FATC FIRE ALARM TERMINAL CABINET T O UTILITY TRANSFORMER AS INDICATED (PAD OR POLE MOUNTED) CONDUCTOR SHALL NOT DEPEND UPON DEVICE CONNECTIONS, SUCH AS LAMPHOLDERS, FCP FIRE ALARM CONTROL PANEL RECEPTACLES, ETC., WHERE THE REMOVAL OF SUCH DEVICES WOULD INTERRUPT THE CONTINUITY. r 'tITY OF TIGARD FO FIBER OPTIC I ` ' METER SOCKET 16. DE-RATING OF NEUTRALS IS PROHIBITED. CO W3UILDING DIVISION CFI GROUND FAULT CIRCUIT INTERRUPTER 17. THE USE OF AUXILIARY GUTTERS, WIREWAYS, RACEWAYS AS ENCLOSURES FOR SERVICE ENTRANCE c umGND,G GROUND o-1 NON-FUSIBLE DISCONNECT SWITCH - HEAVY DUTY - SEE OR TAPPING OF SERVICE ENTRANCE CONDUCTORS IS STRICTLY PROHIBITED.SPECIFICATIONS - LION MOUNT TOP OF ENCLOSURE 66" AFF E L ITY0 18. METAL IDENTIFICATION TAGS SHALL BE INSTALLED WHERE THE GROUNDING CONDUCTOR IS �/ HACR HEATING/AIR CONDITIONING-RATED FUSIBLE DISCONNECT SWITCH - HEAVY DUTY - FUSED AS INDICATED ON PLANS CONNECTED TO THE GROUNDING ELECTRODE. HD HAND DRYER Cil - SEE SPECIFICATIONS - UON MOUNT TOP OF ENCLOSURE 66" AFF CR CARD READER - UON BOTTOM MOUNTED 48" AFF HID HIGH INTENSITY DISCHARGE ❑ 19. ALL SWITCH AND RECEPTACLE COVERPLATES TO BE WHITE. CL Ce W HOA HAND-OFF-AUTO ElENCLOSED CIRCUIT BREAKER - HEAVY DUTY - SEE SPECIFICATIONS PB PUSH BUTTON ACTUATOR - UDN BOTTOM MOUNTED 48" AFF 20. ALL JUNCTION BOXES FOR SIGNAGE SHALL BE PLACED AS CLOSE AS POSSIBLE TO CENTER SIGNAGE. ❑ 0 4 HORSEPOWER - UON MOUNT TOP OF ENCLOSURE 66" AFF ce Csi HPF HIGH POWER FACTOR W pii HPS HIGH PRESSURE SODIUM 0 SINGLE RECEPTACLE - 20A, 124v - UON 15" AFF FROM BOTTOM OF BOX. ® KEY PAD - UON BOTTOM MOUNTED 48" AFF 0 („) Li.FACILITIES COMMENTS i;: ISOLATED GROUND 0 DUPLEX RECEPTACLE - 20A, 120V - UON 15" AFF FROM BOTTOM OF BOX. ® ELECTRIC STRIKE - MOUNTED ON DOOR � a n 0 COUNTERTOP DUPLEX RECEPTACLE - 20A, 120V - UON 48"AFF FROM TOP OF BOX. - r/ .1 Ce JUNCTION BOX � ® DOOR CONTACTMOUNTED ON DOOR FRAME qui DOUBLE DUPLEX RECEPTACLE - 20A, BOX. ® AUTOMATIC DOOR OPERATOR BUTTON ELECTRICAL CONTRACTOR TO STICK-ON LABEL TO ALL RECEPTACLES. Z o O KCMIL THOUSAND CIRCULAR MILS 120V - UON 15"AFF FROM BOTTOM OF Q KVA KILOVOLT AMPERE COUNTERTOP DOUBLE DUPLEX RECEPTACLE - 20A, 120V - UON ; W 0 Q KW KILOWATT BOTTOM MOUNTED 42" AFF @ AUTOMATIC TELLER MACHINE ELECTRICAL CONTRACTOR TO STICK-ON LABEL TO ALL BREAKERS. BLANK BREAKERS LABELrt SPARE. ON EACH PANEL. i/) W MCB MAIN CIRCUIT BREAKER 0 CONTROLLED RECEPTACLE QD AHD - AFTER HOURS DEPOSITORY 4 Q MCC MOTOR CONTROL CENTER ` 18" PREFERREDL EMERGENCY EXITS WITH AUDIBLE ALARMS: VON-DUPRIN MODEL# 99NL-OP ALK-ARI 3 PS9. MDP MAIN DISTRIBUTION PANEL ® EQUIPMENT OR SIGNAGE CONNECTION © ALARM TCD - TELLER CASH DISPENSER MH METAL HALIDE J15" MIN Z CI Q ALARM LIGHT/LAMP 0 80" A.F.F., U.O.N. O 0 MLO MAIN LUGS ONLY MMST MANUAL MOTOR STARTER CHASE BANK GENERAL NOTE Z0 MMSW MANUAL MOTOR SWITCH L I H T I N 0 VAULT W 4ii•• MOD MODULAR O HUB - HOLDUP BUTTON WHUB - WIRELESS HOLDUP BUTTON N MTD MOUNTED CnZ i U_1° CEILING MOUNTED 2'x4' LIGHT FIXTURE CONTRACTOR SHALL COORDINATE FINAL LOCATION OF 4 - I NC NORMALLY CLOSED DSS ALARM SHUNT SWITCH NEC NATIONAL ELECTRICAL CODE THERMOSTATS, SWITCHES, FLOOR AND WALL = NEMA NONIOFUSEDLECTRlCAL MANUFACTURERS ASSOCIATION A ° a CEILING MOUNTED 2'x2' LIGHT FIXTURE OPT DYE PACK TRANSMITTER RECEPTACLES, CARD READER, DOOR ACTUATOR, J-BOXES, �/ NEPA NATIONAL FIRE PROTECTION ASSOCIATION MSP MAIN SECURITY PANEL 0ETC. WITH ARCHITECTURAL AND/OR STRUCTURALNIC NOT IN CONTRACT AI o IQ CEILING MOUNTED LIGHT FIXTURE NIGHT LIGHT JB/Y JUNCTION BOX/MAIN DRAWINGS PRIOR TO INSTALLATION. CONTRACTOR SHALL NO NORMALLY OPEN NON NON-MODULAR AI 1 I a WALL MOUNTED LIGHT FIXTURE VSS VIDEO SWITCHER CONTACT THE ARCHITECT IN CASE OF ANY OR ORANGE AO a CEILING MOUNTED ROUND LIGHT FIXTURE Vt VIDEO TIMER DISCREPANCIES AND AWAIT FOR A WRITTEN RESPONSE ARCHITECT/ENGINEER OF RECORD PNL PANEL WR DIGITAL VIDEO RECORDER PRIOR TO PROCEEDING WITH THE WORK. Pm ALLOWABLE PHASE A❑ a CEILING MOUNTED SQUARE LIGHT FIXTURE PUSHBUTTON W VIDEO MONITOR PIV POST INDICATOR VALVE 1 PP PATCH PANEL A Q lviATERIALS a WALL MOUNTED LIGHT FIXTURE 0 RADIO 0 12" ABOVE CEILING PVC POLYVINYL CHLORIDE CONDUIT CITY OF TIGARD DESIGN REF REFRIGERATOR A H-O I a FLUORESCENT STRIP 0 INTERNAL ATM CAMERA NOTE: REVIEWED FOR�4llE COMPLIANCE � �y•_ r/ Architectural RGC RIGID GALVANIZED STEEL CONDUIT Approved: [ ] t7t,c, A❑ > POLE MOUNTED AREA LIGHT - 1 HEAD SECURITY/COMMUNICATION SYSTEM G.C. TO PROVIDE ROUGH-IN L� CONCEALED SPACES; OTC: [ I Solutions Group A. Conduit: SE SERVICE ENTRANCE ROUGH-IN TO CONSIST OF 3/4" CONDUIT, 4x4 BOXES AND SINGLE GANG RINGS (VERTICAL) 1 . Galvanized rigid conduit (CRC): Hot dipped SM SURFACE MOUNT 1 - Permit #: 6 ZZ� ' OO 19120 SE 34TH STREET, SUITE 115 g SPD SURGE PROTECTIVE DEVICE A< ❑ > POLE MOUNTED AREA LIGHT 2 HEADS Address: /7.io 5,,•• 4,, (.-s f trM �` galvanized rigid steel with threaded ends. Meet SW SWITCH Suite #; 4,4,n VANCOUVER, WA 98683 ASTM standard A-153 galvanized after SWBD SWITCHBOARD 1 - rD� s����A ® EXIT SIGN SINGLE FACE �)' ICC// fa b r i e a t i o n, of!P Morgan Chase end shot!not be coped or reproduced without w„en TB TERMINAL BLOCK QS autho zat on. The contract documents we a prepared to use an,his spec fic site in con unction with ifs¢sue dale and are not suitable for use on a different 2. Intermediate Metal Conduit (IMC): RI Id TS TIME SWITCH 1 EXIT SIGN - DOUBLE FACE site or at a late time. Use OF these drawings for reference or expmple on g TTB TELEPHONE TERMINAL BOARD A another pra;ec, requires ,he se cont of properly icenser architects and engineers. Reproducfion of the canlracl tlocumenfs for reuse on another project is not authorized. mild steel tube with welded seams, hot dipped TVSS TRANSIENT VOLTAGE SURGE SUPPRESSOR galvanized with threaded ends. TYP TYPICAL 3. Thin Wall: Electra-galvanized electrical UGUNDERGROUND SEAL UH UNIT HEATER CCN DUI T N OTE , ,,° PR°F�'1/45> mtallic tubing (EMT). UON UNLESS OTHERWISE NOTED , G I N6-e0 4. Flexible: Allowed with-in 12" flexible UPS UNINTERRUPTIBLE POWER SUPPLY W I H I N 15,423 ? UREF UNDERCOUNTER REFRIGERATOR r connection only. Hot dipped galvanized material "RIGID CONDUIT IS PERMITTED IN DEMISING WALLS OR of mild steel of uniform width and thickness. VAV VARIABLE AIR VOLUME FOR PRIMARY ELECTRICAL RUNS. IF INSTALLED IN VE VOICE EVACUATION $a SINGLE POLE SWITCH - 20A, 120V - UON 48" AFF FROM TOP OF BOX. �e o`lo 5. Flexible Liquid Tight: Allowed with-in 12" VFD VARIABLE FREQUENCY DRIVEPARTITION WALLS OR ABOVE CEILING FLEXIBLE CONDUIT �4 31, o� flexible connection only. Hot dipped galvanized C DOUBLE POLE SWITCH - 20A, 120V - UON 48" AFF FROM TOP OF BOX. Rk D. RO'B 04/14/20 material of mild shell of uniform width and WG WIREGUARD $3 THREE WAY SWITCH - 20A, 120V -- UON 48" AFF FROM TOP OF BOX. SHALL BE USED FOR SHORT CONNECTING RUNS ONLY WM WEthickness with extruded moisture and oil proof WP WEAT ERL D PROOF $4 FOUR WAY SWITCH - 20A, 120V - LION 48" AFF FROM TOP of BOX. WHICH SHALL NOT EXCEED 12" IN LENGTH ROBISON PVC jacket. XFMR TRANSFORMER $K KEYED SWITCH - 20A, 120V - UON 48" AFF FROM TOP OF BOX. ENGINEERING, INC B. Conduit Fittings: $p DIMMER SWITCH - UON 42" AFF FROM TOP OF BOX. 19401 40TH AVE W SUITE 302.LvNNwOoo,WA 98036 TEL:206-364-3343 FAX:425-835-0098 CONTACT:SHANE MCCLURE 1 . GRC Conduit: Threaded type. $hi MOTOR RATED SWITCH WITH TOL - SEE EQUIPMENT SCHEDULE FOR SPECIFICATIONS ISSUE DATE DESCRIPTION 2. IMC Conduit: Threaded type. TS TIME SWITCH AS INDICATED - UON MOUNT TOP OF ENCLOSURE 66" AFF 3. Thin wall or EMT: Rain-tight and concrete-tight, gland compression type, I-n PHOTO CELL - COORDINATE MOUNTING LOCATION WITH ARCHITECT E R A \AI I N insulated nylon throat with die-cast body and LJ LIGHTING CONTACTOR - ELECTRICALLY HELD - NUMBER OF POLES AS NEEDED INDEX steel nut, Appleton type 86T series or equal. ({OSI OCCUPANCY SENSOR -- WALL MOUNTED - SEE SPECIFICATIONS For conduit sizes 3" and larger (where not - UON CENTER MOUNTED 42" AFF DRAWING NO DESCRIPTION required to be rain or concrete tight) set-screw E0.0 LEGEND, ABBREVIATIONS, NOTES, INDEX. type IS acceptable. EDI SITE PLAN (NORTH) Eo.2 SITE PLAN (SOUTH) 4-13-20 PERMIT SUBMISSION 4. Flexible Conduit: Single Or two piece GENERAL INFORMATION E0.3 SITE LIGHTING PHOTOMETRIC PLAN (NORTH) CITY COM MENTSSITE squeeze type. E0.5 DRIVE LITHRU POWER/SYSTEM/CONDUIT/LIGHT O PLAN 4-3-20 PLANNING 5. Flexible Liquid Type: Compression type. a• ALL WORK TO COMPLY WITH 2016 CEC. (2011 NEC) 1. TEXT SHOWN ON PLANS ADJACENT TO LIGHTING FIXTURES SHALL DENOTE THE 3 20 20 FOLLOWING: E1.0 LIGHTING PLAN PROJECT INFORMATION BLOCK C. Prohibited materials: b. LIGHT FIXTURE IN CONTACT WITH INSULATION TO BE U.L. LISTED FOR THERMAL BARRIER OR PROVIDE 3" A - E1.1 LUMINAIRE SCHEDULE & COVER PLATE FINISHES UPPERCASE LETTER INDICATES FIXTURE TYPE JOB# JPM19010.0 a - LOWERCASE LETTER INDICATES LIGHT SWITCH CONTROL E1.2 LIGHTING CONTROL DETAILS DATE: 1/20/2020 1 . Armored and metal-sheathed cables, MINIMUM CLEARANCE. 1 - NUMBER INDICATES BRANCH CIRCUIT NUMBER E1.3 LIGHTING CONTROL DETAILS DRAWN BY: GH types AC and MC, shall not be permitted. c. LIGHTS AND PANELS SHALL NOT BE RECESSED IN FIRE RATED ASSEMBLIES UNLESS BOXED, 1MTH 2. LIGHTING FIXTURES SHALL BE INTERPRETED AS FOLLOWS: E2.0 POWER PLAN CHECKED BY: PR 2. Non-metallic sheathed cables, typesNM, EQUIVALENT CONSTRUCTION. E2.2 ROOF POWER PLAN NMC and NMS, shall not be permitted. d. MOUNT THE FOLLOWING ABOVE FINISHED FLOOR: ® NORMAL BRANCH CIRCUIT MODEL OUTLETS- 15" TO 48" a EMERGENCY LIGHT FIXTURE WITH BATTERY BACKUP E3.0 ONE-LINE DIAGRAM AND SCHEDULES DRAWING STANDARDS v20. 1 SWITCHES- 36" TO 42" E3.1 VOLTAGE DROP CALCULATIONS THERMOSTATS- 36" TO 44" 3. NUMBERS SHOWN ON PLANS ADJACENT TO WIRING DEVICES INDICATE BRANCH CIRCUIT E4.0 TELLER POWER DETAILS SHEET TITLE PHONE- +40" NUMBER. MEASURED FROM BOTTOM & TOP OF BOXES RESPECTIVELY. E4.1 ENLARGE DATA ROOM & ELEVATIONS LEGEND, 4. STANDARD SYMBOLS SHOWN ON LEGEND MAY NOT APPEAR ON ALL PLANS. WHERE E5.0 SECURITY PLAN e. PANEL CIRCUIT DIRECTORY TO COMPLY WITH SECTION 408.4, CEC. SYMBOL APPEARS ON PLANS FURNISH AND INSTALL AS SPECIFIED. E5.1 SECURITY DETAILS ABBREVIATIONS E5.2 SECURITY DETAILS NOTES AND INDEX f. W.P. COVER OF OUTLETS TO COMPLY WITH SECT. 406.8 (B) (I), CEC. 9. ALL ELECTRICAL WORK SHALL BE DESIGNED PER 2016 CALIFORNIA ELECTRICAL CODE, 2014 NATIONAL E6.0 ENERGY COMPLIANCE FORMS ELECTRICAL CODE, AND 2016 BUILDING ENERGY EFFICIENCY STANDARDS. E7.0 SPECIFICATIONS SHEET NUMBER E7.1 SPECIFICATIONS ALL ELECTRICAL EQUIPMENT SHALL BE LABELED, LISTED OR CERTIFIED BY A NATIONALLY RECOGNIZED h. TESTING LABORATORY ACCREDITED BY THE UNITED STATES OCCUPATIONAL SAFETY HEALTH ADMINISTRATION. E n • O SITE LUMINAIRE SCHEDULE GENRAL NOTES: FLAG NOTES: I 1. EXTERIOR FIXTURES ARE EXEMPT FROM SECTION 140.7 OF TITLE 24 PER EXCEPTION 140.7(a) I p , CALLOUT SYMBOL ' DESCRIPTION MODEL MOUNTING BALLAST LAMP VOLTS TOTAL VA NOTE 1 SECTION 6:LIGHTING SPECIFICALLY FOR AUTOMATED TELLER MACHINES AS REQUIRED BY E-SL o--0 EXISTING AREA LIGHT EXISTING POLE ELECTRONIC (1) 250W MH 120V 1P 2W 250 FINANCIAL CODE SECTION 13040, OR REQUIRED BY LAW THROUGH A LOCAL ORDINANCE. 111111110- NEW POLE LIGHTS. PROVIDE CONDUITS AND CONDUCTORS 2. NEW LIGHT FIXTURE, CONTRACTOR SHALL PROVIDE: BACK TO CHASE PANEL. FIXTURES SHALL BE CONTROLLED BY DAlNTREE SYSTEM, L6A EXTERIOR SEMI-RECESSED LED CANOPY GE: ERCAOA5F5401BWHTE CEILING ELECTRONIC 35W LED 120V 1P 2W 35 PROVIDED WITH CANOPY BY • • LIGHT FIXTURE HEAD ❑ GE: ERCA005F5401BWHTE CANOPY MANUFACTURER • POLE` POLE BASE © PROVIDE TRENCHING, CONDUITS, CONDUCTORS, AND III L21B WALL MTD EXTERIOR LIGHT, FULL CUT OFF W/ LUMARK - XTOR6B W BZ SURFACE ELECTRONIC (1) 58W LED 120V 1P 2W 58 VERIFY EXACT FIXTURE LENGTH • CONDUITS BACK-FILL FOR NEW SIGNAGE. ROUTE POWER BACK TO • CONDUCTORS CHASE ELECTRICAL PANEL. \ _ - 1-111PHOTOCELL AND 50% DIMMMING MOTION SENSOR AND PC1/2 MS DIM L20 CBP WITH OWNER/ARCHITECT PRIOR • TRENCHING/ROUTING FROM FIXTURE TO ELECTRICAL PANEL. 90-MINUTE BACKUP BATTERY TO ORDERING • SF2 0 ❑ LED AREA LIGHT GE: EACL 01 0 H4 AF 7 30 X POLE ELECTRONIC (1) 153W LED 12OV 1P 2W 153 Q Cl DKBZ F .... — Uill . ------- . i ..-_. I o 2_ n r� 54 L- co = 1 Ui z rri Li.J REFER TO LIGHT FIXTURE SCHEDULE FOR I = POLE HEIGHT -- U 1.- < Q RE: LIGHT FIXTURE SCHEDULE FOR NUMBER / ANDTYPEOFHEADSANDCONFIGURATION / r LIGHT POLE. RE: LIGHT FIXTURE I i SCHEDULE FOR TYPE. OPTIONS AND ACCESSORIES AS SPECIFIED. ❑ M H � IIMI HANDHOLE WITH REMOVABLE COVER f-/ AS SPECIFIED c6 \\\\\ a1311W INSULATED GROUNDING BUSHINGS ON a -1 N ENDS OF GRS CONDUITS. BOND LLI EQUIPMENT GROUNDING Q lIL lc: CONDUCTOR TO BUSHING AND TO I J POLE GROUNDING LUG WITH #6 CU � CO QCIE J � GROUND. � ZCIo0 ,,. POLE BASE PLATE - i' GROUT - � r 4tW - - II II ANCHOR BOLTS, PER MANUFACTURER Ce II , WQ � a 3/4" PVC li I,Ill li LINE OF GRADE OR PAVING t n Z CI GRS (TYP) / O i• Q PVC (TYP) /� Z W IJ N—ELECTRICAL CIRCUIT TO LIGHT POLE. / 4 N 5/8"X 8' DRIVEN GROUND \ REFER TO SITE PLAN AND PANELBOARD / Cl) Z ROD WITH #6 CU. GROUND SCHEDULES FOR SIZES OF CONDUITS / BONDED TO POLE \ AND CONDUCTORS / Q MN GROUNDING LUG AND TO \ PROPERTY GROUND ROD - N /� \ / LINE N� MGRS-PVC COUPLING `I N "—REINFORCED CONCRETE ___.__\_____} 0 FOUNDATION. SIZE AND TYPE AS +• REQUIRED TO MEET SITE CONDITIONS 1 r ��� illill Mil / ARCHITECT/ENGINEER OF RECORD igligg /Mli / SCALE r ATM 50' BOUNDARY-\), z POLE BASE FOR REFERENCE „m- NTS 2 mPm MidMI" MOUNTED - DES G N SF2 AT +30'M. J • Architectural - �''`� .. --11-41111111NW Solutions Group Mil0 / SF2 (413 19120 SE 34TH STREET, SUITE 1 i 5 / / B-8 VANCOUVER, WA 98683 VIA CONTROLS These drawings and specifications are the confidential and proprietary properly .-r .,'' '''' '''''''1.,,,/_ / of Morgan Chase and shah not be copied a reproduced without wnflen / _ MONUMENT SIGN authorization. The contract documents were prepared for use on this specific -- - site in conjunction with its issue date and are not suitable for use on a different ' ' ` , _ 1.2KVA,12D Y1P2W_ site or another t o later requires e. Use e f these drawings for reference or example on project 11 I eq property licensed architects and ,� _ engineers. Reproducton of the contract documents far reuse on anothe / / 1 ATM 5' BOUNDARY �rajecti5nata�lh«�ed. (--- ---. (/: -- 17\ T� / 0 SEAL H I H L6A L6A _ L6AI I 1 .. c , Ea PROFF r, , I \\ I I I i ■ • 6A SI - IT VIAB-ICONTROLS \ 0 �,N G 1 /V 6e V/o I I II i � — ` �' 15,423 r 1 - 141: .. I ) ‘1111° -44)'11'4-1:-' R 31, 2�Spm -1 - I k Q O 04/14/20 _ m 4 — Iliert RoBlsoN z ENGINEERING, INC 71 19401 40TH AVE W SUITE 302.LYNNWOOD,WA 98036 V BOUNDARY ISSUE TEL:206-364-3343 FAX:425-835-0098 sorot F-- AROUND CORNER CONTACT:SHANE MCC LU RE DATE DESCRIPTION soAajo B-12I VIA CONTROLS L21B gTh7) � „, .._ r ' '1 4-13-20 PERMIT SUBMISSION .. „ 'IA 4-3-20 90% SET / \ 3-20-20 PLANNING I j PROJECT INFORMATION BLOCK / \ I / \ I JOB## JPM19010.0 N. DATE. 1/20/2020 DRAWN BY: GH MONUMENT SIGN CHECKED BY: PR 1.2KVA,12OV1 P2W \r>s MODEL DRAWING STANDARDS v20.1 1 __ — SHEET TITLE SITE ELECTRICAL PLAN - - - - - (north) Svv 121s1- A \v/ NORTH I�� SHEET NUMBER SITE PLAN ___D Z SCALE: 1” = 10' EO . 1 NI IT LUTHNAIR ' P 'CH UL.E P • GENERAL NOTES: N � p Ln FLAG NOTES: ED UCAL �/ SYMBOL o DESCRIPTION MODEL MOUNTING BALLAST LAMP VOLTS TOTAL VA NOTE 1 1. EXTERIOR FIXTURES ARE EXEMPT FROM SECTION 140.7 OF TMA 24 PER EXCEPTION 140.7(a) P SECTION 6:LIGHTING SPECIFICALLY FOR AUTOMATED TELLER MACHINES AS REQUIRED BY _ FINANCIAL CODE SECTION 13040, OR REQUIRED BY LAW THROUGH A LOCAL ORDINANCE. +� _ • — —� EXISTING ARA LIGHT — — — --WING — — POLE — — ELECTRONIC (1�250W MH — — 120V 1P 2W 250 NEW POLE LIGHTS. PROVIDE CONDUITS AND CONDUCTORS — IIIII 2. NEW LJGHT FIXTURE. CONTRACTOR SHALL PROVIDE: BACK TO CHASE PANEL FIXTURES SHALL BE CONTROLLED IGHT FIXTURE HEAD BY DAINTREE SYSTEM. POWER SHALL BE PULLED FROM L6A EXTERIOR SEMI-RECESSED LED CANOPY : ERCA005F5401BWHTE CEILING ELECTRONIC 110W LED 120V 1P 2W 110 PROVIDED WITH CANOPY BY EXISTING NEARBY PEDESTAL El CANOPY MANUFACTURER • POLE ` POLE BASE PROVIDE TRENCHING, CONDUITS, CONDUCTORS, AND SF2 LED AREA LIGHT GE: CL 01 0 H4 AF 7 30 X POLE ELECTRONIC (1) 153W LED 120V 1P 2W, 153 • CONDUITS BACK-FILL FOR NEW SIGNAGE. ROUTE POWER BACK TO °-0 D Cl D' :Z F i CONDUCTORS CHASE ELECTRICAL PANEL • TRENCHING/ROUTING FROM FIXTURE TO ELECTRICAL PANEL. UllN N w \ — _ 2.Z �- T o il--- - 1 H i.c• rTi aL fn LU CL 4 U w Z d N P7'1 W rn 41, w Z �'1 I t SD v C.3 L REFER TO LIGHT FIXTURE SCHEDULE FOR ~ fll I POLE HEIGHT M It RE: LIGHT FIXTURE SCHEDULE FOR NUMBER r — 1 (...wilgag° AND TYPE OF HEADS AND CONFIGURATION00 W to — i_, \ LIGHT POLE. RE: LIGHT FIXTURE SCHEDULE FOR TYPE. OPTIONS AND in i Q ir ACCESSORIES AS SPECIFIED. M 4 m 1 ov ---X X 0 \ L- W Ce Z HANDHOLE WITH REMOVABLE COVER O 4 -1 ce AS SPECIFIED W , \ o �. f:' INSULATED GROUNDING BUSHINGS ON o 4 ,1 ., ti, ..,..,„["/ ENDS OF GRS CONDUITS. BOND y EQUIPMENT GROUNDING CI . 1 CONDUCTOR TO BUSHING AND TOIII Nill CO .1 Le / \ POLE GROUNDING LUG WITH #6 CU Z O 0 GROUND. Q *k W = o • X �� O �� POLE BASE PLATE T m z i �/ Zs LF-1 ` GROUT Cl. Q I 11 I,u a // I ll ANCHOR BOLTS, PER MANUFACTURER > z CI 44 I= f 1 3/4" PVC 1 i� LINE OF GRADE OR PAVING 0 0 L it NMI Z O • \ lir- GRS (TYP) � N 4. PVC (TYP) Z 4 r — r 1- IM 5/8"X$' DRIVEN GROUND —ELECTRICAL CIRCUIT TO LIGHT POLE.0004 il11o.00.0 Cr ROD WITH #6 CU. GROUND _ REFER TO SITE PLAN AND PANELBOARD BONDED TO POLE SCHEDULES FOR SIZES OF CONDUITSI 05 GROUNDING LUG AND TOH _ _1 N. AND CONCTORS `/ GROUND ROD N. GRS-PVC COUPLING (IIII) �REINFORCED CONCRETE l� Q ,� FOUNDATION.DUSIZE AND TYPE // / EXISTING ` REQUIRED TO MEET SITE CONDITASIONS ARCHITECT/ENGINEER OF RECORD \ i/!'1/' ` O Pm „SL ..r // // / -V SCALE // /' POLE BASE FOR REFERENCE l / NTS 2 DESIGN // :� �~11 \ ma 0 I Architectural // /J / �� // // Solutions Group �� / // // ATM 50' BOUNDARY I // t.,/.._<, // �/ 19120 SE 34TH STREET, SUITE 115 / — „ VANCOUVER, WA 98683 - / • These drawings and specifications are the confidential and proprietary property // I�/ /�/ / ' \ of Jr Morgan Chase and shall not be copied or reproduced without written / ' — authorization. The contract documents were prepared for use on this specific VIi. ' /// \ site in conjunction with ifs issue date and are not suitable for use on a different si/ r1 \ . t I I te at ar laeter tieme. Use of these drawings p o forreferenceused or example on nd NJ , i i , I I I i I ,'''r.,,,>'''- I I I another project requires the services of property Fcensed architects and / �\irillit I engineers. Reproduction of the contract documents for reuse on another / ` / project is not authorized, r SEAL 1 111611 \ PR11 4 1 0 / ED OFFS 1� �;` \ \ 1 16 .,/''''':..„::.,'''''''--''''''''' ''. �\ 15,423 ,,,,-----,0000. \\4 I�IN:\ It , N \ A.. _ 0 f f ,1� �, tvi\\\A11 — A x �qR� Q 1,o\S ? \� / ` \I 11 \\ MOUNTED 1 R 04/14/20 `, A �/ (TYP) \\\ AT +30 \ ' Z ROBISON 1,1 �� // \\ ATM 5 BOUNDARYI ,\ \y� , SF2 \\ A m _Z ENGINEERING, INC J 19401 40TH AVE W SUITE 302,LYNNwOOD,WA 98036 v \ U TEL:206-364-3343 FAX:425-8350098 I ,1, �\ ❑ ❑SF2 \` ICONTACT;SHANE MCGLURE \ SF2 \ 11 �\\\ „\ -.4., i. , _ ❑CF ¢ ISSUE DATE DESCRIPTION 1 \\ Ni.414 . i 11 \\ A I ' ! , } \ \\ 1 2 W ` \ _� / F-7\%*‘?k\ ' . j / \-- \ Q DW W 1 ` TO VAULT /I \\ °' o NJ 4-13-20 PERMIT SUBMISSION y 4 — — / 4-3-20 90% SET — — — - 3-20-20 PLANNING 1 _2 = =7—Z— •— ® \ / PROJECT INFORMATION BLOCK ATM 50' BOUNDARY M19010. DATE: 1/20/2020 \ / DRAWN BY: GH O / CHECKED BY: PR N. / I MODEL \ ' ‘ ® \ , DRAWING STANDARDS v20.1 C ` , ' ® ! SHEET TITLE r, -._.._ - El SITE ELECTRICAL PLAN _, JIII (south) SOUTH SHEET NUMBER SITE PLAN \....) SCALE: 1" = 10' EJ . 2 •______. __•••_____ .. 11 III 1 1 1 1 1 1 IP 1 --------) r .,... ________________________„, I 1u_ Iu_ O a ___, UJ Q 0_ UJ CC a 111 ..L. r CO W cel t Fel in IM ❑ M CIE LLW oc i \\\\\\\\\\\ ' . o a ..1 ceN � a o � N c N0 J o• 0o _. ,. , co) z o 0 L * WwUo v, w ) 0- Li! Q a > ZO N0 r r o 0 1- - zo ri. W -1 atiN chz PROPERTY 4 - / 0.9 1.2 1._ 1.8 2.3 : ..7 3.0 3.3 ; .3 3.4 3.2 2.7 2.4 \1.8 1. • ONE C4000 ,....- i -/ 1.1 1.4 1.9 2 - 2.9 . .2 3.4 3.3 . .7 4.1 4.4 4.2 3.0 .8 1.3 0 // G-I 1.3 1.7 2.2 2.9 3.6 3.8 3.6 3.8 4.2 ___4.8 5. 4.7 3.2 2 .4 // - - ARCHITECT/ENGINEER OF RECORD 011111/ 1.5 1.9 2.4 3.0 3.6 4f - 4.3 4.6 4.8 6.2 5.5 4.2 3.5 2.5 1.8 M ATM 50' BOUNDARY / pmM 1.7 2.1 2.4 2.8 3.2 4.3 5.5 5.8 6.8 5.9 4.5 3.8 3.3 3.0 2.2 1 . aiii MOUNTED 1.8 2.1 2.4 /2.7 3.3 4.2 6.1 7.8 6.9 5.4 4.0 SF2 .4 AT :Zr 2.9 •.6 1.9 DESIGN • -- Architectural Wigr 3 , • Solutions Group Aiiiir1. !To -9 3.5 4.5 3.5 7.7 7.3 5 . 4.4 SF2 3.7 3.4 3.1 . . 1.8 (1) / / B--s 19120 SE 34TH STREET, SUITE 115 VIA CON1ROLs VANCOUVER, WA 98683 1. 3 2 / 2.8 �5 4.3 5.5 3.5 6.9 7.6 7 5.7 5.0 4.1 3.5 2. 1.6 111P.►- 0....,. MONUMENT SIGN 2 These drawings and specifications are the confidential and proprietary property 1.2KVA 12aV1P2w� of 1P Morgan Chase and shall not be copied or reproduced without written r authorization- The contract documents were prepared for use on this specific site in canjunclion wdh its rive date and are not suitable for use on a different 1 2. 3.1 `O 7.4 8.3 3.7 8.8 9.0 9.6 8.1 6.2 3.5 2.1 1 1.4 1 _ site ar a} a titer li„e. Use of these d swings for reference or example on n another project requres the services of property licensed architects and ` / I - / ATM 5 BOUNDARY engineers. Reproduction of the contract documents far reuse on another project is not authorized. 010 F 1.4 _k.0 3.5 7.5 114.7 15.7 16.5 15.6 15.4 17.5 15.7 17.01.3 4.3 2.1 1.4 1.1 I I 1 I I L6A L6A Lsr / 8_10-111 SEAL \• II 11 la---. • 6A i `® I �A CON S �' , Ep PRo . 00 I I 1.2 1.8 3.3 8.0 1117.4 18.2 19.9 18.4 17.9 20.7 1 .5 / • 3 . I'.F 2.2 1.1 AN G I N e�,�3> I I -_. I I - I ) - : - 15,423 � r i�.0 ;.7 4.6 2.5 1.: 1.2 I 4•: .. I �O3c. 311.° 1 .2 :.6 4.9 2.9 1.8 1.2 0 � ,fr Q Rog\ 04/14/20 •A11 • 11.7 5.5 3.2 2.0 1.2 0.7 JROBISON ___<.i IMsgoort ENGINEERING, INC 11.6 1 *Q-ATM BOUNb�Ai�Y 2 O 2 1 9401 40TH AVE W SUITE 302,LYNNWOOD,WA 98036 TEL:206-364-3343 FAX:425-835-0098 I AROUND CORNER CONTACT:SHANE MCCLURE ISSUE DATE DESCRIPTION B-12+1111-7.3 f 13.4 6.1 3.3 1.7 1.0 VIA CONTROLS TjiL21B 16.1 112.5 5.7 3.0 .6 _5.1_ . 6.2 3.8 _- - - -� 5310in 1:7 1.8 1. 4-13-20 PERMIT SUBMISSION I 4-3-20 90% SET / \ / \ I 3-20-20 PLANNING •// � PROJECT INFORMATION BLOCK j6 \1 I JOB# JPM19010.0 DATE: 1/20/2020 DRAWN BY: GH CHECKED BY: PR MODEL DRAWING STANDARDS v20.1 SHEET TITLE SITE LIGHTING �- PHOTOMETRIC PLAN (north) sw 121st Av/ . , __ _„,„,„,./ NORTH SITE PHOTOMETRIC PLAN 7.D SHEET NUMBER SCALE: 1' = 10' E0 . 3 HT 2020,RONSON ENGINEERING, NG SiICCLURE FA_PECRO+MIXRACIQ]ILCHILSE BAII(S\424-1384 CHASE TIGARD it(RUNWAY- WARD, G 2 SITE LIGHTING PHOS 03-20-2020 01147 I 1 1 1 tin 1 < . I . iZ u ,0 U- a w crQ 0_ w er 0_ • iv Ni V SD L ; n � ao m N V mmxi � ; rw las'.6.sw- � zK n T■ oft% NJ II Na 2 n m \ CO LLI p 0 .00 I, Ql . b N ca m• im. N VD 1W I- 0 r, I in o - DC \ el a. 0- W >- oa -Icece N o a � N v NI 4)CO 0 a. CIZ00 CI = • o \ *k LLI ge V ❑ WQ � Q � N0 Z 0 - o _ __ 0 ' o W J aN � z o I- 41\411 4 - Cf ti) V) 4.0 )11* 1-- ) cD, EXISTING pi.O /// // E-SL ENGINEER OF RECORD // // Li 0 �` /1 // ` ry // /// // / E- O SL pm / // lif,f // // // ;4#p n // m / �� DESIGN / \ O // 11 0.8 1.1 1.4 1. / 2.2 2.7 3.3// /4.2 5.6 6.7 6.4 7.2 9.0 9.8 8.6 8.2 6.6 : 1 5.2 3.7 4.7 Architectural / / // // ATM 50' BOUNDARY n N. Solutions Group // // m 1.0 1.3 1.7 /2.3 2.8 3.4 . �/ 5.3 6.6 �. 8.3 9.5 -1- ,9 10.3 8.6 7.6 � 5 4.8 4.0 2.9 „ 1 19120 SE 34TH STREET, SUITE 1 15 / // i� �' N VANCOUVER, WA 98683 / / / t►' wn 1.0 1.4 Id 2.6 3.3 3.6/ 7� 6.0 7.7 8.6 9.1 9.9 10.9 10.4 8.2 6.7 5.6 4.3 3. 2.5 - W These drawings and specifications are the confidential and proprietary properly / ' / of JP Morgan Chase and shall not be copied or reproduced without written 1N authorization. The contract documents were prepared for use an this specific f) ` \ site in conjunction with ifs issue date and are not suitable for use on a different (r site or at a later lime. Use of these drawings fix reference or example on }� another project requires the services of properly icensed architects and engineers- Reproduction of the contract documents far reuse on another 1.1 1.5 // 2.1 2.9 3.7 4.? 4.9 ..1 8.0 8.6 8.8 9.4 10.0 9.2 7.1 5.7 .9 3.2 2.4 1.7 p ajeof a rpt aull or zea. i / `► \ ® 1.1 1.611 2.3 3.2 i6‘ 4.6A 5. 6.5 8 • 8.8 8.8 9.1 9.6 8.8 6.7 5.5 4.9 \ .3 -. Gj2.30 1.6 SEAL II \ ' , ED PROFFS II ' \� ANG I NEF�S) 1.2 1.7 \I 2. 3.7 4.94 5.4 \;\\6.2 8.1 11.2 11.• 10.4 10.8 11.6 10.5 7.6 6.1 5.6 4.8\ 3. - 2.4 .6 15,423 ? ,:-- \I \1 \1 1.2 1.8 \\2.811 /4.2 5.8 6.8 71'$ 10.` 15.0 14.6 14.3 14.5 14.8 13.6 9.8 7.4 G.0 5.4 .5\/ .5 1.7 aI .• o \\ ' 11\ / % 1 if c. 31, ��\cam' \\ \) / MOUNTED 1.2 1.8 2/ 4.2 5. 6.8 7.5 10.1 4 12.7 �, .+ TYl . 13.AT +31)2.5 9.2 7.1 6.7 5.3 3.7 2. 1.7 4 X00 \\\ ( i ' 04/14/20 \\\ ,\ �� // 1 �� ATM 5' BOUNDARY \� // SI-2 \ JRoBIsoN 1.2 1.8 2.7 \\\ 4.2 5.5 6.4 7.1 Sk2 13.8 1197 .eirr-• .4 '1 .1 11.7 8.3 6.7 6.3 5.2 3.6 1 2.4 1.6ENGINEERING, INC \\ S.2. ■cry N` 1 19401E4 206-364-3343VE E 302,FAX: NWOOD,9 A 98036 \\ \�� 1.2 1.8 217 *.2 5.6 7.3 9.6 . 11.: 'AI 10.9 12.3 11.9 8.6 6.8 6.4 5.2 3.6 12.4 1.6 CONTACT:SHANE MCCLURE \,\ oED ISSUE DATE DESCRIPTION 1.2 1.8 2\8 4.2 \\ 5.8 6.8 6 10.4 14.4 13 13-`4 2:5 13.4 1 9.3 7.1 6.7 5. 3.6 \\ ,2_� 1- - f \\ O LIA 1.2 1.8 2. 3.9 .3 5.9 6.8 9.1 12.7 1 11. ' 11. 1 .3 5.8 4.8 3.4 / 2.3 1.5 r \ O 1.1 1.6 2.3 \ 3.4 4.3\ 4.7 5.3 6.6 9.1 8.a 8.1 8.3 9.(I ilia4.0 4.6 4.0 3.fi 2.1 1.4 TO VAULT / N 1.1 1.5 2.1 0 3.7 4.0 -4..5 5.4 6.9 6.8 6.5 6.6 6. 6.4 5.0 4.3 3.9 3.5 /2.6 1.9 1.3 4-13-20 PERMIT SUBMISSION ® - - - 4-3-20 90%SET \ - - - 1` 3-20-20 PLANNING 1.0 1.5 2.0 2.7 \3.3 3.7 4.2 5.0 6.4 6.5 6.1 6.2 6.5 5.9 4.7 3.9 3.5 3�1 2.4 1.3 PROJECT INFORMATION BLOCK ATM 50' BOUNDARY / JOB# JPM19010.0 \ / DATE: 1/20/2020 1.0 1.3 1.8 2.3 2.8 \ 3.2 3.7 4.3 5.0 5.1 5.0 5.0 50 /1 4.8 4.0 3.5 3 2.6 2.1 1.6 1.2 1 DRAWN BY: GH \\ c 1 CHECKED BY: PR 1.21.51.92.5N 2.7 3.0 3.4 3.5 3.4 3.4 3.5 3.3 2.9 2.87 2.4 2.1 1.7 1.3 1.0 1 0.9 2 2 MODEL Ea W � � C_ ® DRAWING STANDARDS v20.1 "-1 `-- 0.7 1.0 1.2 1.5 1.7 1.8 1.9 2.1- - 2.3 2.4 2.3 2.3 2.3 2.2 2.0 1.9 1.7 1.6 1.3 1.1 0.8 m SHEET TITLE a O SITE LIGHTING PHOTOMETRIC PLAN (south) SOUTH SHEET NUMBER SITE PHOTOMETRIC PLAN SCALE: 1" = 10' N EO . 4 COPYRIGHT 2020, ROBISON ENGINEERING, NC SIACCLURE F:\_PEDRO+NOCRAcI(EN\_CHASE BANKS\424-1360 CHASE 11GARD &GREINWAY- TIGARD, OR\DWG\E0-2 SITE LIGHING PHOTOAE1RIC.DWG 03-20-2020 00:47 ELECTRICAL NOTES FOR ATM AND VAT: 11'1 1. POWER PULL BOX- 12"X12"X6" PVC PULL BOX WITH SIDEWALK RATED GASKET TOP SET FLUSH W/ TOP FO CONC. ISLAND SECURED WITH SCREWS. 1 2. ATM PULL BOX-8"X8"X6" PVC PULL BOX MOUNTED FLUSH IN CONCRETE. 1111 1 3. ATM TOPPER PULL BOX - 2"X4"X2" PVC PULL BOX MOUNTED FLUSH IN CONCRETE. 4. (2) 3/4"CONDUIT FROM POWER PULL BOX TO ATM PULL BOX FOR POWER TO ATM . PROVIDE 1 1/4" NON-METALLIC LIQUID-TIGHT CONDUIT FOR POWER INTO ATM. tin 5. 1/2" CONDUIT FROM POWER PULL BOX THROUGH ATM PULL BOX TO ATM TOPPER PULL BOX FOR POWER TO S YN 30L LEGEND ATM TOPPER. PROVIDE 1/2" NON-METALLIC LIQUID-TIGHT CONDUIT FOR POWER INTO ATM TOPPER. SECURITY CAMERA NOTE: CONTRACTOR SHALL COORDINATE WITH CHASE SECURITY VENDOR FOR ALL FINAL 6. PROVIDE (1) 3/4" CONDUIT WITH FEEDERS FROM THE EXISTING REMOTE ELECTRICAL VAULT TO REMOTE ATM LOCATIONS PRIOR TO ROUGH-IN. ii) SECURITY RUGGED DOME CAMERA CEILING MOUNTED 7. PROVIDE (2) 1" CONDUITS EMPTY WITH PULL STRING FROM DATA ROOM TO REMOTE ATM. IS STANDARD. ("w" DENOTES WALL-MOUNTED). KP SECURITY KEYPAD, LCD 8. 3/4" PVC CONDUIT FOR LOW VOLTAGE CABLES FROM LOW VOLTAGE PULL BOX TRANSITIONING INTO 3/4" LIQUID TIGHT FLEXIBLE NON-METALLIC CONDUIT UNDER AND INTO ATM. ALL CABLES ARE TO BE CONTINUOUS ATM ATM PROTECTION- DEVICES PROVIDED BY FROM BANKBRANCH TO FINAL TERMITATION. MANUFACTURER; DOOR CONTACT, SEISMIC AND 9. 1/2" LIQUID TIGHT NON-METALLIC CONDUIT FOR POWER FROM ATM TOPPER. HEAT DETECTOR ARE TYPICAL 0 u_ 0 w cca CL w 4fite N c s O OPEN - __ \ \\ /// 1 \y \ HzraV•/"i OFF LANE 1r ,.., \ / I //' 1 CLOSED I- --I / \ IV .� ATM /,// /// \ / CO / / / CO p I-ILI` 0 0 _� •_ ______ _ _ /, / / • O OPEN / , / r • OFF LANE 2 11) Ci s • CLOSED / \ a. 1- W 4 ///' O q -I w N W LANE STATUS SIGN WIRING DIAGRAM p ��,,, c•, I. i/ c,) 4 P. / NTS / Ci Cl.N J o• C / / , / M Z o 0 . m , 1 , O z . /• , iii / // / /'/ NAME PLATES (TYPICAL SINGLE POLE, SINGLE THROW ---FOR OVERRIDE CONTROL 4t W re V 0 / / THREE (3} POSITION MAINTAINED CONTACT OF 4) TOGGLE SWITCH, HUBBELL OF DRIVE THROUGH / Le / '/ / /// SWITCH WITH CENTER OFF, HUBBELL #HBL1221W CANOPY LIGHTS y #HBL1385W, FOR CONTROL OF TYPE"L5" NOTES: W Q / / / I III /'/ FIXTURES (TYPICAL OF 2) LANE LANE OVERRIDE NAME PLATES TO BE WHITEit - �/ I If /// l 2 LANES 1&2 "LAMICOD"WITH INNER BLACK ZH 0 / / / ( � CD CD LAYER TO SHOW BLACK0 F""' / — LETTERS WHEN ENGRAVED. 0 o / / I I WHITE FLUSH TRIM OPEN OPEN ON Z 1-1 4 a DRIVE- THRU SYSTEMS P L A N / PLATE OFF ■ OFF ■ ■ SUBMIT DRAWING FOR W SCALE: 1/4" = 1'-0" / // CLOSED CLOSED FABRICATION. � � OFF � APPROVAL BEFORE � z (y / /I 1 111 COORDINATE DESIGN OF 4 — ININ I I 1 1\ LANE STATUS CONTROL PANEL I WITH ARCHITECT PRIOR TO I I �� FABRICATION. (11111) 1 t \ Il LI) ,' LANE STATUS CONTROL STATION ( 1 \\\ NTS 1 \ 1 1 1 \\\\ ARCHITECT/ENGINEER OF RECORD 11 1 I, , \ \\ 1 1 \\\ \\1PM 1 1 4/\ \\ 1;f\\ \\\ DESIGN \ \ \\\ ., \ \ \\\ Architectural I. \ Solutions Group \ \ 1 1 \\ \\\\ 19120 SE 34TH STREET, SUITE 115 \\ \\\\ VANCOUVER, WA 98683 \ i __ __ \ \ \ These drawings and specifications are the confidential and proprietary properly \ \\ /7 \\ of JR Mogan Chose and shall not be copied or reproduced without written authorization. The contract documents were prepared far use on this specific \\\ / / \\ site in conjunction with its issue dote and ore not suitable tor use on a dfferent site or of a later time. Use of these drawings for reference or example on another project requires the services of properly licensed architects and \ \ \ / / \\ engineers. Reproduction of the contract documents for reuse on another \ \ / / \\ project is not authorized. \ \ \\ / / \\ \ \ \\ / / \\ \ \\\\ / / \\\ SEAL \ \�1 / / \ \ , ED PROFF / / \ S \ \\\ \. \ / / \\ cNGIN Seo \ II- \ \\\\ N / / \\\ 15,423 2 \ \ \\ N /' / \\\ \ \\\ N / \\ TERMINI).TE C NbUITS WITH -- \ ��; ._ \ FLEXIBLE P TO OPENING \\\ • Ot, 261' \ \ \ IN BASE OF ti4TM \ 31 p \ N DRIVE-THRU ATM \ \ xRk Ra- \ \ \ DRIVE-THRU ATM \ \ 04/14/20 \ \\\ LIGHTING _ \\ \ g, _,__.r c,___ .. 8 ------.\\, , . -,... iRoBIsoN \ ,\ ` ��� ENGINEERING, INC N _1—� co\ \ \ �1+� 19401 40TH AVE W SUITE 302,LYNNW000,WA 98036 \ --\ TEL:206-364-3343 FAX:425-835098 \ \,____ .0 A-6 ` àIA \ CONTACT:SHANE MCCLURE \ , _ _ / f / 2 O \ \ ////` ISSUE DATE DESCRIPTION \ f \ DRIVE-THRU ATM 1011110- \ }, \ TOPPER \ \ TO DATA ROOM 1\ 1 411=2 CI= \ 4-13-20 PERMIT SUBMISSION \ / = LIMMI 4-3-20 90% SET \ / IMIIIMEIM3-20-20 PLANNING \ / / PROJECT INFORMATION BLOCK \ I JOB# JPM19010.0 \ 1=2 DATE: 1/20/2020 DRAWN BY: GH \ CHECKED BY: PR \ \ MODEL \\ DRAWING STANDARDS v20. 1 N. N. N SHEET TITLE N N DRIVE THRU _ POWER/SYSTEM/ DRIVE- THRU POWER PLAN _ _ _ _ _ _ _ _ _ _ _ _ _ CONDUIT/LIGHT PLAN SCALE: 1/4" = 1'-O" _.z, _-- :_------_---__� -w — — — - — SHEET NUMBER E0 . 5 G E N E A L LIGHTING NOTES LIGHTING PLAN KEYED NOTES DAINTREE CONTROL NOTES: I. EMERGENCY/NIGHT LIGHT LUMINAIRES WILL BE WIRED TO RESPECTIVE DAINTREE CONTROLS KEY G E N E A L AREA LIGHTING SWITCHBANK ZONE 0-10V CONTROL ONLY. EMERGENCY/NIGHT LIGHTS ARE WOS2-RM-E WIRELESS OCCUPANCY SENSOR CEILING il UNSWITCHED. �')) REFER TO SHEETS E12 & E1_3 FOR DETAILED LIGHTING CONTROL DIAGRAMS AND SPECIFICATIONS A. CONNECT EXIT SIGNS/BATTERY BACKUP AHEAD OF LOCAL SWITCHING. 1. GENERAL AREA LIGHTING SWTCHBANK WITH LIGHTING OVERRIDE CAPABILITY. FIELD DETERMINE EXACT LOCATION. SWITCHBANK SHALLRECESSED MOUNT; PIR, 1000 SF COVERAGE BE CAPABLE OF DIMMING THE GENERAL AREA, ENTRY LIGHTING, AND DISPLAY LIGHTING. REFER TO SHEET [0.3 FOR DETAILS. 2. SIGNAGE, EXTERIOR LIGHTING, HOT WATER HEATERS AND OTHER NON LIGHTING CONTROLS WILL BE PROVIDED BY WIRELESS ADAPTERS ATOCCUPANCY SENSOR, CEILING MOUNT, PASSIVE B. PROVIDE SEPARATED IDENTIFIED NEUTRALS FOR EMERGENCY LIGHTS AND EXIT SIGNS. OS 2. CONNECT INTERNAL BATTERY UNIT IN FIXTURE TO CONSTANT HOT ON CIRCUIT CONDUCTOR (SAME CIRCUIT SERVING FIXTURE) AHEAD PANEL LOCATED IN ELECTRICAL ROOM. INFRARED, WITH 3-WAY MANUAL OVER-RIDE SWITCH. 2-HOUR MAX MAIN D. ALL EQUIPMENT SHALL HAVE AN APPROVED TESTING LABORATORY LABEL ATTACHED (UL, CSA, ETC.) (CEC 110-2). OF ANY LOCAL WALL SWITCH OR IIMECLOCK AND/OR PHOTOCELL CONTROL (TYPICAL). 3. ALL SWITCH PACKS ARE UNNECESSARY. ALL LOW VOLTAGE SENSOR WATTSTOPPER #CI355 Z1 Z2 Z3 Z4 Z5 Z6 SWITCHOVERRIDE WRING IS ALSO REMOVED AND IS OBSOLETE WITH A WIRELESS 11101:19) ❑)))❑0 d))❑t)) ❑1 t)) S E. SECURELY FASTEN EACH RECESSED LIGHT FIXTURE TO THE CEILING SYSTEM WITH APPROPRIATE SUPPORT BRACKETS AND 3. PROVIDE SURFACE MOUNTED, LINEAR LED LUMINAIRE FROM COLOR KINETICS AND INTEGRAL DRIVER. REFER TO LUMINAIRE SCHEDULE. SYSTEM. 0,)) WPS1 WIRELESS PHOTOCELLIII CUPS PER INDUSTRY STANDARDS. FIELD VERIFY EXACT LOCATION ON GROUND WITH PROJECT MANAGER. 1' LINEAR LED MODULES. SPACE EVENLY WITH 1" GAPS 4• ALL LUMINAIRES -CONTAINED IN WIREA DEFINEDOZONE MUST BE ZONEDAISY BETWEEN FIXTURES (TYPICAL). CHAINED WITH 0-10V DIMMING TO THE RESPECTIVE WAPM t) WA100-PM WIRELESS ADAPTER WITH POWER ( ) WA100-PM. } MONITORING F. ELECTRICAL CONTRACTOR TO VERIFY TYPE OF MOUNTING FOR HARD LID AND SUSPENDED CEILING GRID BEFORE ORDERING. 5. ALL LUMINAIRES MUST BE 0-10V DIMMING FOR DAINTREE TO PROVIDE 4. L410 FIXTURE SHALL BE UNSWITCHED FOR SECURITY LIGHTING AND SHALL PROVIDE LESS THAN 0.1 WATTS PER SQUARE FOOT OF DIMMING CONTROL. 1Q y)) WWD1 WIRELESS WALL DIMMER tin G. ALL LIGHTING SHALL BE PROTECTED BY A MAXIMUM OF A 20 AMP CIRCUIT BREAKER. ILLUMINATION. 6. ALL WA100-PM WIRELESS ADAPTERS MUST BE PROVIDED WITH UNINTERRUPTED POWER AND SWITCH THE S SINGLE POLE DOUBLE THROW LINE VOLTAGE TOGGLE H. INSTALL JUNCTION BOXES FOR SIGNAGE AS CLOSE TO CENTER OF SIGNAGE AS POSSIBLE. 5. 100W POWER SUPPLY FOR BLUE TOWER LED. 60FT MAX PER SLOANLED 100W 24VDC POWER SUPPY. COORDINATE FINAL LOCATION RESPECTIVE LUMINAIRES IN SPECIFIED ZONE. ZONES ARE LABELED SWITCH AND QUANTITIES WITH PM/ARCHITECT PRIOR TO INSTALLATION. BY LETTER. I. COORDINATE LOCATION OF ALL LUMINAIRES WITH ARCHITECTURAL DRAWINGS. NOTIFY ARCHITECT OF ANY DISCREPANCIES. 7. ELECTRICAL CONTRACTOR MUST PERFORM WIRELESS ADAPTER TEST WALL-MOUNT SINGLE RELAY OCCUPANCY SENSOR J. ELECTRICAL CONTRACTOR TO PROVIDE ALL LOW VOLTAGE WRING FOR LIGHTING CONTROL SYSTEM. VERIFY QUANTITY AND 6. J-BOX FOR VERTICAL FIXTURE "L308". CONTRACTOR SHALL VERIFY EXACT QUANTITY AND LOCATION WITH PROJECT DURING/POST INSTALL SEE WAIOO-PM INSTALLATION GUIDE FOR SOS WITH COMBINED SWITCH: LEVITION ODS1O-IDW REQUIREMENTS WITH MANUFACTURER PRIOR TO WORK. MANAGER/ARCHITECT. INSTRUCTIONS. Os DIMMER SWITCH WITH OCCUPANCY SENSOR K. CONTRACTOR TO PROVIDE A FULLY OPERATIONAL LIGHTING CONTROL SYSTEM. 7. ILLUMINATED OCTAGONAL SIGNAGE. CONTRACTOR SHALL PROVIDE MAXBRITE DIMMER *RE-DIM12V. COORDINATE EXACT LOCATION WITH PROJECT MANAGER. REMOTELY MOUNTED 12V DC MAXBRITE DIMMER MUST BE WIRED TO SECONDARY (12V) SIDE OF THE POWER S 0C2 WALL-MOUNT SINGLE-RELAY OCCUPANCY SENSOR I SUPPLY. POWER SUPPLY SHALL BE REMOTELY MOUNTED BEHIND THE WALL. WITH COMBINED SWITCH: WATTSTOPPER DSW-302 8. CONTRACTOR SHALL PROVIDE LED POWER SUPPLY: MAXBRITE ECONO LP-1260P-12. COORDINATE EXACT LOCATION WITH PM. Vi PUSH BUTTON LINE VOLTAGE 5/10/15/30 MINUTE 0 TIMER: WATTSTOPPER TS-400-24 u_ 9. EXTERIOR TOWER BLUE LED STRIP. CONTRACTOR SHALL COORDINATE EXACT LENGTHS, LOCATION, AND REQUIREMENTS WITH o PM/ARCHITECT PRIOR TO INSTALLATION. ALPS ))) EXTERIOR PHOTOCELL CC a 10. ALL EXTERIOR WALL PACK/WALL SCONCE ARE EXISTING TO REMAIN. EXTERIOR LIGHTS SHALL BE CIRCUITED TO CHASE PANEL B. a 11. EXTERIOR WALL PACK REQUIRED PER 2019 CALIFORNIA BUILDING CODE. CONTRACTOR SHALL PROVIDE SURFACE MOUNT CONDUIT TO EXTERIOR FIXTURE AS REQUIRED. COORDINATE FINAL LOCATION WITH PROJECT MANAGER. Til r oiim\ ® ca . ii. _____2 in I- 0 1- ceM a0W L- o 4 _I aCN W FACADE SIGN oc.) 4 LrL 1.2KVA,120VTPN N 0, COORDINATE EXACTCI Q. -1 -- CX)% LOCATION WITH SIGN J VENDOR AND CHASEi # M Z O o PROJECT MANAGER 0 � Wp� Uo B-6\;c1j; L6A N 1e L6A 1/2"C,1#10,#10N,#10G L6A LEA aui 4 Q L4 L4 0H 2 TL21B O _ O H - - -- - I I `T ' , 1 Z O ----. - - , 1 ' LLI -I 4 ,,,i-- / (Typ, . dt? + / L11 L11EM L11 • 1 . / 0 LI tf� Z . 4 Z2 8 "' `�•L11 Li Z1 Z1 I11 • NLL11 .- 0- ICE me Im r L504 L504 72- . lZ21L2 I �, - Y♦ L410 0 (CIS (g i NL LI - - L- v-TEik----- 1 = rt2E / 0 1 _L308(TYP) I - - - L504 I \3 / T �NL502 11 - - __y Z5 ,1 177111 ;4.7 Z5 Z5f--------1.,. / ARCHITECT! ENGINEER OF RECORD 4 I Z3 ZI„� L5017 h _.- PM i ,f.p4 / , - -i II L504 L504 L516 Z'�• ' '• Z5 L2 L6A J f _ Z5 % 4 it >•ILLUMINATED OCTAGO Ti DESIGN 1 N I4 L11 �/ / M B-Q Z4 ,0 Z3 1 L410 I -J 4 r�J Architectural _ NL_ 04�- Z5 L506E /Z5 ��' L2 Solutions Group - \ i z4 Zak �� •/ B-9 TYP) 24/ �, L2 _� -�� "APM ')} �, FACADE SIGN 19120 SE 34TH STREET, SUITE 115 - = Z WAPM t)) 1.2KVA,12OVIP2W VANCOUVER, WA 98683 J WAPM 1)) COORDINATE EXACT These drawings and specficationsare the confiidentialand proprietary propery L506 Z5 L506 Z5 $T 0 LOCATION WITH SIGN of JP Morgan Chase and shall not be copied«reproduced produced without written ,� -_. authorization. the contract documents were prepared for use on this specific 1 � L2E VENDOR AND CHASE PM site in conjunction with its issue date and are not suitable for use on a different LY 013i. site or at a tater time. Use of these drawings for reference or example on 0 r anotherinproject requiresucn the services of properly is orearon cts and NL engineers. Reproduction the contract documents for reuse on another i A0 A projecta not auth i S B-4 S O s L503-6 Z6 / Ec 5 L504 L504/ �� �L506E Z6 SEAL L502 L2E F - 1 i 2 . Ep PRpFF Z6 O" S2 n N G I N ee 1/45>o NJ'}) f \�� 15,423 )_ E L50P Zo L50► Z6. 1- L I I I O o0 i SOL ► DRIVE UP LANE STATUS B_.1 I �/\ I 4/ ac• 31 2 1. L504 L504 / QL(f SIGNAGE CONTROL SWIT;HES; I Rk D ROB`S O4/14/20 `7 I"N NOT WITHIN BMS SCOP L2 L2E N L502 #3 ~ 7Si' \L504E Z6 I J ,L41NL IF r Iy i.._,,,,c7kiRoBIsoN 1 Z6 \ i--i-i-L - ENGINEERING, INC B-5 1 9401 40TH AVE W SUITE 302.LYNNWOOD.WA 98036 B-3 L11 L11 TEL:206-364-3343 FAX:425-835-0098 (Tr) `i --/ CONTACT:SHANE MCCLuHE 413 - 1L2E i f I ISSUE DATE DESCRIPTION L2E rI I I I MAIN O RMAX .WIT -!I 01 \ 444_. `t`i�c+ MC ;T_ ' � ' 6°6MST AST B-7 L2 L22 J ____fi_l_iL5D�Einw. i L2 L2 L2 CD �IL2E 4 OS2 (3L2 111 , - 1 --SEF • 34• li 1H n0£ 42" H I I LOW VOLTAGE OPEN LOOP l EXTERIOR PHOTOCELL MOUNTED t ! TO CONTROL ALL EXTERIOR 4-13-20 PERMIT SUBMISSION L3 - - -- L'3 -13 1 I L� T ______/t +A\73-1-1-7/ 1t-eaC3-1 LOADS. WIRE TO NEAREST WA100-PM. COORDINATE EXACT 4-3-20 90% SET --- - - - --- - - - LOCATION WITH PM. 4 3-20-20 PLANNING B-2 1/2"C,1#1Q#ION,#10G PROJECT INFORMATION BLOCK 7 JOB# JPM19010.0 DATE: 1/20/2020 FACADE SIGN DRAWN BY: GH 1.2KVA,120V1P2W CHECKED BY: PR COORDINATE EXACT LIGHTING PLAN LOCATION WITH SIGN VENDOR AND CHASE PM MODEL SCALE: 1/4" = 1'-0" 0' 4' 8' 16' DRAWING STANDARDS v20. 1 DSHEET TITLE N LIGHTING PLAN SHEET NUMBER E1 . O NOTES: NOTE TO ELECTRICAL DEVICE FINISHES LUMINAIRE SCHEDULE CALLOUT SYMBOL MOUNTING DESCRIPTION MODEL MODEL 2 VOLTAGE TYPE LAMPING WATTAGE NOTES il EC TO COORDINATE DEVICE COLOR FINISH WITH PROJECT MANAGER AND VENDOR, BEFORE — MEANS OF EGRESS ILLUMINATION LEVEL SHALL BE NOT LESS THAN 1-FOOT ORDERING COVER PLATES.. L2 RECESSED RECESSED 2X2 GRID LAY IN TYPE LUMINATION - BT22A033MM835VQLTWHTE 120 0-10V DIMMING 34W LED 34 VERIFY EXACT FIXTURE WITH OWNER/ARCHITECT PRIOR CANDLE AT THE WALKING SURFACE AND EQUIPPED WITH NOT LESS THAN FIXTURE, FROSTED PRISMATIC LENS, TO ORDERING 90-MINUTE BATTERY BACKUP, 2016 CRC, SECTION 1006. AND INTEGRAL 0-10V DIMMING DRIVER. L2ERECESSED SAME AS 'L1' EXCEPT EQUIPPED WITH LUMINATION - LUMINATION - BT22A033MM835VQLTWHTE EL 120 0-10V DIMMING 34W LED 34 VERIFY EXACT FIXTURE WITH OWNER/ARCHITECT PRIOR — EXIT SIGNS SHALL BE ILLUMINATED AT ALL TIMES AND EQUIPPED WITH NOT ELCTRICAL DEVICE FINISHES ,pr INTEGRAL 90 MINUTE BATTERY TO ORDERING. LESS THAN 90-MINUTE BATTERY BACKUP. 2016 CBC, SECTION 1011.5.3. BACK-UP (1400 LUMENS). L3 SURFACE 19" UNDER CABINET TASK LIGHT WITH PHILIPS DAY-BRITE: - LINCS 100 L19 120 WHG OSC RSH 120 LED (1) 4.9W LED 4.9 VERIFY EXACT FIXTURE/LENGTH WIN OWNER/ARCHITECT tn INTEGRAL OCCUPANCY SENSOR PRIOR TO ORDERING WALL DEVICE COLOR WATTSTOPPER IVORY L4 SURFACE EXTERIOR UP/DOWN SCONCE WITH LUMIERE: LANTERRA 120 ELECTRONIC (2) 10W LED 20 VERIFY EXACT FIXTURE WITH OWNER/ARCHITECT PRIOR INTEGRAL LED DRIVER 9004-W2-RW-LED408O-W-W-CS-LI-UNV-WIS TO ORDERING CEILING DEVICE COLOR WATTSTOPPER WHITE Lii O CEILING 4" ROUDND LENSED LED DOWNLIGHT GE: D14R10935 1V/2V 10 + RDI4RWPTWTWTWR +BH3(OPTIONAL) 120 0-10V DIMMING (1) 14W LED 14 WET RATED GREEN CODE NOTES: L11EM 0 CEILING 4" ROUDND LENSED LED DOWNLIGHT GE: D14R10935EL 1V/2V 10EL + RDI4RWPTWTWTWR 120 0-10V DIMMING (1) 14W LED 14 WET RATED GENERAL NOTES W/ EMERGENCY BATTERY BACKUP +BH3(OPTIONAL) I — INTERIOR AND EXTERIOR LIGHTING SHALL BE DESIGNED SUCH THAT ZERO DIRECT-BEAM ILLUMINATION LEAVES THE L20 ® SURFACE LED UNIVERSAL-MOUNT EXIT SIGN WIN BEST LTG - EZXTE 1 RW EMRC 120 LED 5W LED 5 EXIT SIGN FOR BACK OF HOUSE SPACES. COLOR AND U BUILDING SITE." (5.106.8) PROVIDE FULLY OPERATIONAL LIGHTING CONTROL SYSTEM BY 90-MINUTE BATTERY BACK-UP MOUNTING TYPE TO BE SPECIFIED BY ARCHITECT. MANUFACTURER WATTSTOPPER. NO EXCEPTIONS. L21B SURFACE WALL MID EXTERIOR LIGHT, FULL CUT LUMARK - XTOR6B W BZ PC1/2 MS DIM L20 CBP 120 ELECTRONIC (1) 58W LED 58 VERIFY EXACT FIXTURE LENGTH WITH OWNER/ARCHITECT o — ALL EXTERIOR LUMINAIRES SHALL BE SHIELDED SYSTEM PROGRAMMING AND START-UP BY MANUFACTURER H OFF W/ PHOTOCELL AND 50% PRIOR TO ORDERING W 4R BE CUTOFF LUMINAIRS AS DEFINED IN SECTION 132 (B) OF THE WATTSTOPPER. NO EXCEPTIONS. DIMMMING MOTION SENSOR AND Q 90-MINUTE BACKUP BATTERY w CALIFORNIA ENERGY CODE." (5.106.8) IF REQUIRED BY CITY: ELECTRICAL CONTRACTOR TO PROVIDE a THIRD PARTY TITLE 24 ACCEPTANCE TESTING. L22I I SURFACE 2' LED LINEAR LOW PROFILE LENSED LITHONIA - ZL1N L24 15001_14 FST MVOLT 35K 80CRI WH LSXR 120 ELECTRONIC (1) 18W LED 18 VERIFY EXACT FIXTURE WITH OWNER/ARCHITECT PRIOR FIXTURE W/ OCCUPANCY SENSOR TO ORDERING. — INTERIOR LIGHTING SHALL BE CONTAINED ELECTRICAL DEVICE FINISHES: VERIFY WITH ARCHITECT AND WITHIN EACH SOURCE." (5.106.8) PROJECT MANAGER PRIOR TO BID AND ORDERING. L308 WALL eW COVE QLX POWERCORE, 12", 120V, PHILIPS COLOR KINECTICS: 223-000004-02: 12" eW COVE QLX 120 LED 6W LED 6 VERIFY EXACT FIXTURE WITH OWNER/ARCHITECT PRIOR BLUE, WIDE BEAM, UL. POWERCORE' RIGID BLUE 120V STRIP, WHERE MOUNTED ABOVE TO ORDERING. NOTE: PROVIDE LENGTHS AS INDICATED BUILDING LIGHTING OPERATION SCHEDULE: ACT-3, USE MOUNTING MODEL #120-000125-00 OR EQ. ON PLAN. 11 — NO MORE THAN .01 HORIZONTAL FOOTCANDLES COVE BLUEIWHITE LIGHTING = 24/7 OPERATION. SHALL ESCAPE 15 FEET BEYOND THE SITE BOUNDARY." (5.106.8) VESTIBULE/ATM LIGHTING =24/7 OPERATION. L404 PENDANT/SURFACE PENDANT BESA: BES00298-182 120 ELECTRONIC (1) 5W LED 5 VERIFY EXACT FIXTURE LENGTH WITH OWNER/ARCHITECT r t— OFFICE FAB PENDANT LTS= 2417 OPERATION. PRIOR TO ORDERING TRANSOM LTS/ INFILL LTS = 24/7 OPERATION. 00 W L410 PENDANT/SURFACE PENDENT - BLACK POWDER COAT KUZCO: PD46216-BK 120 ELECTRONIC (1) 40W LED 40 VERIFY EXACT FIXTURE LENGTH WITH OWNER/ARCHITECT ALL EXTERIOR LIGHTING SHALL HAVE CONTROLS MONDAY- FRIDAY: LIGHTS ON AT 8:30 AM -OFF AT 7:00 PM FINISH, INTEGRAL LED DRIVER, PRIOR TO ORDERING CD I— THAT AUTOMATICALLY TURN OFF OR LOWER LIGHT LEVELS DURING SATURDAY: LIGHTS ON AT 8:30 AM -OFF AT 5:00 PM INSTALLED +82" A.F.F. TO B.D. FIXT in IMMO ❑ INACTIVE PERIODS FROM DUSK TO DAWN." (5.106.8) SUNDAY: LIGHTS OFF I te L412 PENDANT/SURFACE PENDENT - 9" DIAMETER, BLACK SONNEMAN: KOMA EDO PENDANT 120 ELECTRONIC (1) lOW LED 10 VERIFY EXACT FIXTURE WITH OWNER/ARCHITECT PRIOR CI THE SITE PLAN SHALL BE PLANNED AND DEVELOPED TO KEEP SURFACE SATIN FINISH, ELV DIMMNG, INSTALLED TO ORDERING 0 W >- M DAVIS AT SUPERIOR SOLUTIONS GROUP FOR AT 82" AFF. TO BD. FIXTURE CONTACT KYLEE WATER FROM ENTERING BUILDINGS. CONSTRUCTION PLANS SHALL INDICATE HOW SITE GRADING ORA DRAINAGE SYSTEM WILL MANAGE SUPPORT: L502 CEILING 2' RECESSED LINEAR LED (6W/FT) FOCAL POINT: SEEM 4-LP, ALTERNATE: AMERLUX: GRUV4-HE-GRID-A16 PL 5 35 HW 120 120 0-10V DIMMING (1) 12W LED 12 VERIFY EXACT FIXTURE LENGTH WITH OWNER/ARCHITECT Q � �W N ALL SURFACE WATER FLOWS. CONTOUR LINES, ELEVATION POINTS, (813)464 5075 FSM4LP-FL-625LF-35K-1C-UNV-LD1-T6TZ-WH-2 2' IND 0-10 (5W/FT) PRIOR TO ORDERING 0 cm) 4 LL CV No,AND/OR SLOPE ARROWS MAY BE USED TO SHOW COMPLIANCE WITH THIS kdavis��superiorsolutionsgroup.com - REQUIREMENT. (5.106.10) 1_503-6 CEILING 3'-6" RECESSED LINEAR LED (6W/FT) FOCAL POINT: SEEM 4-LP, ALERNATE: AMERLUX: GRUV4-HE-GRID-A16 PL 5 35 HW 120 120 0-10V DIMMING (1) 21W LED 21 VERIFY EXACT FIXTURE LENGTH WITH OWNER/ARCHITECT Nv) 0, ' ' FSM4LP-FL-625LF-35K-1C-UNV-LD1-T6TZ-WH-3'-6" 3'-6" CUS 0-10 (5W/FT) PRIOR TO ORDERING Q 00 CO J L504 CEILING 4' RECESSED LINEAR LED (6W/FT) FOCAL POINT: SEEM 4-LP, ALTERNATE: AMERLUX: GRUV4-HE-GRID-A16 PL 5 35 HW 120 120 0-10V DIMMING (1) 24W LED 24 VERIFY EXACT FIXTURE LENGTH WITH OWNER/ARCHITECT Z 0 0 NOTE TO LUMINAIRE SCHEDULE: 1 FSM4LP-FL-625LF-35K-1 C-UNV-LD1-T6Tz-WH-4 4' IND/CON 0-10 (5W/FT) PRIOR TO ORDERING Q = ' L504E CEILING 4' RECESSED LINEAR LED (6W/FT) W/ FOCAL POINT: SEEM 4-LP, ALTERNATE: AMERLUX: GRUV4-HE-GRID-A16 PL 5 35 HW 120 120 0-10V DIMMING (1) 24W LED 24 VERIFY EXACT FIXTURE LENGTH WITH OWNER/ARCHITECT * ILI w V ❑ ALL LIGHTING FIXTURES SHALL BE ORDERED FROM THE NATIONAL ACCOUNT VENDOR. r il EMERGENCY BATTERY BACKUP FSM4LP-FL-625LF-35K-1C-UNV-LD1-T6TZ-EM-WH-4 4' IND/CON 0-10 EMB (5W/FT) PRIOR TO ORDERING ISAIAH RAMDEEN Vn = FSG L506 CEILING 6` RECESSED LINEAR LED (6W/FT) FOCAL POINT: SEEM 4-LP, - - ALTERNATE: AMERLUX: GRUV4-HE-GRID-A16 PL 5 35 HW 120 120 0-10V DIMMING (1) 36W LED 36 VERIFY EXACT FIXTURE LENGTH WITH OWNER/ARCHITECT W 4 Q EMAIL: JPM00-34 -5530 I.COM r r FSM4LP FL-625LF 35K-1CUNV-LD1-T6TZ-WH 6 6' IND/CON 0-10 (5W/FT) PRIOR TO ORDERING PHONE: 1-800-347-5530 EXT. 12137 ZNCI L506E CEILING 6' RECESSED LINEAR LED (6W/FT) W/ FOCAL POINT: SEEM 4-LP, ALTERNATE: AMERLUX: GRUV4-HE-GRID-A16 PL 5 35 HW 120 120 0-10V DIMMING (1) 36W LED 36 VERIFY EXACT FIXTURE LENGTH WITH OWNER/ARCHITECT H CD "� EMERGENCY BATTERY BACKUP FSM4LP-FL-625LF-35K-1C-UNV-LD1-T6TZ-EM-WH-6 6' IND/CON 0-10 EMB (5W/FT) PRIOR TO ORDERING 0 Z 0 L508E CEILING 8' RECESSED LINEAR LED (6W/FT) W/ FOCAL POINT: SEEM 4-LP, AMERLUX: GRUV4-HE-GRID-A16 PL 5 35 HW 120 8' IND/CON 120 0-10V DIMMING (1) 48W LED 48 VERIFY EXACT FIXTURE LENGTH WITH OWNER/ARCHITECTla -II r EMERGENCY BATTERY BACKUP FSM4LP-FL-625LF-35K-1C-UNV-LD1-T6TZ-EM-WH-8 0-10 EMB (5W/FT PRIOR TO ORDERING 4 N II L516 CEILING 1'-6" RECESSED LINEAR LED (6W/FT) FOCAL POINT: SEEM 4-LP, ALTERNATE: AMERLUX: GRUV4-HE-GRID-A16 PL 5 35 HW 120 120 0-10V DIMMING (1) 9W LED 9 VERIFY EXACT FIXTURE LENGTH WITH OWNER/ARCHITECT Cl) Z CI FSM4LP-FL-625LF-35K-1C-UNV-LD1-T6TZ-WH-1'-6" 1'-6" IND 0-10 (5W/FT) PRIOR TO ORDERING 4 - 11111.11 i CA U ARCHITECT/ENGINEER OF RECORD Ad DESIGN Architectural Solutions Group 19120 SE 34TH STREET, SUITE 115 VANCOUVER, WA 98683 These drawings and specifications are the contidenlial and proprietary property of JP Morgan Chase and shall not be copied or reproduced without written authorization. The contract documents were prepared far use on this specific site in conjunction with its issue date and are not suitable tar use on a different site or al a later time. Use of these drawings for reference or example on another project requires the services of properly licensed architects and engineers. Reproduction of the contract documents for reuse on another project is not authorized. SEAL , ED PROPe C GINfc,', '6) 15,423 - r a: e. �q -C 31 205�� Rk O R08` 04/14/20 4D:I iRoBIsoN ENGINEERING, INC 1 9401 40TH AVE W SUITE 302,LYNNWOOD,WA 98036 TEL:206-364-3343 FAX:425-8350098 CONTACT:SHANE MCCLURE ISSUE DATE DESCRIPTION 4-13-20 PERMIT SUBMISSION 4-3-20 90% SET 3-20-20 PLANNING PROJECT INFORMATION BLOCK JOB# JPM19010.0 DATE: 1/20/2020 DRAWN BY: GH CHECKED BY: PR MODEL DRAWING STANDARDS v20. 1 SHEET TITLE LUMINAIRE SCHEDULE AND COVER PLATES FINISHES SHEET NUMBER E1 . 1 - - - - -�-{ J } - y TO ELEC. DISTR. PANEL DAINTREE LIGHTING CONTROL WIRE WAC TO CELLULAR MODEM DATA ROOM FOR CONTROLSCOPE IRRIGATION CONTROLLER WITH 1. INSTALLER IS RESPONSIBLE FOR THE FINAL LOCATION OF ALL SENSORS, SWITCHES AND CONTROLLERS AND TO BMS SYMBOLS cQN�vECTIVITY /- _CONFORM WITH THE MANUFACTURER'S RECOMMENDATIONS AND MEET THE FUNCTIONAL REQUIREMENTS OF THE (/ A_________,- / NETWORK CARD DEDICATED 120V 120A ( { IRC SYSTEM. DUPLEX ELECTRICAL 0-0 �\ _ BMS AND OTHER CONTROL DEVICES TO BE ORDERED FROM THE OUTLET 2. CONTROLSCOPE UTILIZES DISTRIBUTED CONTROL FOR ON/OFF AND DIM STATE. EXISTING RELAY PANELS AND BMS EQUIPMENT VENDOR- REFER TO SHEET E5- COORD. W/ I LINE-SIDE SWITCHES MUST BE OVERRIDDEN OR REMOVED. ALL WIRELESS ADAPTER MUST BE PROVIDED WITH PROJECT ELECTRICIAN - WIRELESS AREA C UNINTERRUPTED/UNSWITCHED POWER. LWAL) CONTROLLER(WAC) iJ POWERED VIA 120V TYPICAL TIMER/PHOTOCELL LIGHTING ZONE ((( BMS WIRELESS THERMOSTAT: RECEPTACLE. REFER TO MFRS. FIGURE 2 AND BMS LIGHTING CONTROL SCHEDULE 111 3. DURING INSTALLATION THE LAST 4 DIGITS OF THE IEEE ADDRESS FOR EACH WIRELESS COMPONENT MUST BE 01 ZONE DAINTREE NETWORKS #WTS10 r..-1 WAPM I) O )) I 10 LIGHT FIXT.I RECORDED ON THE SHOP DRAWING SET CORRESPONDING TO THE LOCATION OF THE COMPONENT. 0 o ' [ 20A MAX. / BMS WIRELESS REMOTE TEMP. SENSOR: - INCOMING - uPSPOWERs11111 4. DURING WIRELESS ADAPTER INSTALLATION FOLLOW THESE STEPS AS DEFINED IN THE DEVICE INSTALLATION GUIDE IN CTS ELECTRICAL SERVICE C S RECEPTACLE FOR ZONE DAINTREE #TPZRS/HA1 .2 (WALL MOUNT) FROM UTILITY METER l P CELL MODEM AND TYPICAL 24-HOUR LIGHTING ZONE TYPICAL MECHANICAL EQUIPMENT ZONE THE FOLLOWING ORDER. OR EMERGENCY I WAC. REFER TO MFRS. FIGURE 2 PROVIDE PHOTOCELL I REFER TO MFRS. FIGURE 8 AND MECHANICAL ZONE PLAN. SHEET M-1 a. CONFIRM WIRELESS ADAPTER DIP SWITCHES ARE SET CORRECTLY. TRANSFER SWITCH BMS WIRELESS REMOTE TEMP. SENSOR: DAYLIGHT SENSOR AS RTU OR b. RESET ADAPTER (ALL ADAPTERS) �( Ts PM 7l WAPM I)) 110 LIGHT FIXT.I READ. BY ZONE CONTROL SPLIT SYSTEM PROBE DUCT TEMP. SENSOR c. PERFORM PROPER TEST SUITE. ZONE DAINTREE #TPZRS/HA1 .2 (CEILING MOUNT) ,,� POWER METER SHALL I 20A MAX. CONDENSER I BE CONNECTED TD , WAC VIA MODBUS REMOTE TEMPERATURE 5. INSTALLER MUST BECOME FAMILIAR WITH THE PUBLISHED INSTALLATION GUIDES FOR THE PRODUCTS IN THE USB CABLE SENSORS AS INDICATED IN PLAN IEEE BMS EXTERIOR WIRELESS TEMP. SENSOR: I TYPICAL LIGHTING ZONE WITH OVER RIDE CONTROL r PROJECT SCOPE. DAINTREE INSTALLATION GUIDES CAN BE FOUND AT: ((( OTS ZONE TITAN #TPZOS/O/HA1 .2 CT X3 FOR MAINS REFER TO MFRS. FIGURE 1 (FIGURE 5 FOR DIMMING) https://products.currentbyge.com/control-systems/daintree-enterprises-wireless-conrols. I I POWER MONITORING WAPM (K) /� ® 1°, ))f �({ TS \�( TS \�{ TS))) 110 LIGHT FIXT. I \ ( S Zt \ 4 4BMS WIRELESS DUCT TEMP. SENSOR: I 1 20AMAX. J ci 6. DO NOT INSTALL BATTERIES IN WIRELESS DEVICES PRIOR TO APPROVAL FROM GE/S COMMISSIONING LIAISON. ((( iDUCT DAINTREETHERMOSTATWIREDTOUINSTALLING BATTERIES MORE THAN 10 DAYS PRIOR TO COMMISSIONING CAN RESULT IN PREMATURE BATTERY IEEE TITAN #TPZDS-S OR SIMILAR w FAILURE. ZONE MAIN LIGHTING I TYPICAL LIGHTING ZONI=WITH > 10 FIXTURE 120A LOAD/ J STANDARD 8 CONDUCTOR WIRING BMS LOW VOLTAGE WIRED HUMIDITY SENSOR: ELECTRICAL DISTRIBUTION I REFER TO MFRS. FIGURE 3A `{( RM ((( � I WSA I) RTU TERMINAL BLOCK VIA w 7. TO AVOID FALSE TRIGGERS FROM OCCUPANTS WALKING PAST OPEN DOORS, CARE SHOULD BE TAKEN TO PLACE HSZONE VARIS #HEW3VSTA, WIRED TO WSA10 SERVICE PANEL I ) STANDARD HUMIDISTAT WIRED a_w SENSORS WITH NO OR MINIMAL VIEWING ANGLE THROUGH DOORWAY. IF THE DISTANCE BETWEEN THE DOORWAY AND PANEL r� WAPM I))) 120VAC 110 LIGHT FIXT. 10 LIGHT FIXT. CO2 PROVIDE WSA10 TO WIRE CO2 OR THE CENTER OF THE ROOM IS LESS THAN 12', IT IS ADVISABLE TO MOVE SENSOR TOWARDS CORNER OF ROOM TO 1CONTACTORJ DIRECTLY TO RTU -OR- 120A MAX. 120A MAX. HUMIDISTAT F02 DAINTREE REDUCE THE VIEWING ANGLE THROUGH THE DOORWAY. LD BMS LOW VOLTAGE WIRED LEAK DETECTOR: MONITORING (IF IDENTIFIED ON ZONE BAR #RBA-BA/LDT1 -PS-BB, WIRED TO WGA100 MECH. PLANS) DAINTREE POWER/RECEPTACLE CONTROL TYPICAL EXTERIOR WIRED SENSORS REFER TO MFRS. FIGURE 4 CO2 WIRED TO WSA10(IF IDENTIFIED 1 IEEE BMS HARDWIRED CO2 SENSOR: ON MECH. PLANS) onoi, 1. INSTALLER IS RESPONSIBLE FOR THE FINAL LOCATION OF ALL SENSORS, SWITCHES AND CONTROLLERS AND TO CO2 ZONE BAPI #BS4-DCD1O-BNK, WIRED TO WSA10 POWER r4 WAPM I)) PS EX CONFORM WITH THE MANUFACTURERS RECOMMENDATIONS AND MEET THE FUNCTIONAL REQUIREMENTS OF THE SYSTEM. - DISTRIBUTION I I SELF-POWEREDEQUIPMENTFAN CTPOWER FOR W WIRED TO IT PANEL I I WGA I)} WGA100 CO F. 2. CONTROLSCOPE UTILIZES DISTRIBUTED CONTROL FOR ON/OFF AND DIM STATE. EXISTING RELAY PANELS AND LINE-SIDE (( WIRELESS WALL SWITCH: TYPICAL DAYLIGHT HARVESTING LIGHTING ZONE(ONLY WHERE READ. BY CODE) 11". 0 SWITCHES MUST BE OVERRIDDEN OR REMOVED. ALL WIRELESS ADAPTER MUST BE PROVIDED WITH ZONE DAINTREE NETWORKS #WWD1 , FUNCTIONS AS REFER TO MFRS. FIGURE6 In TYPICAL TEMPERATURE SENSOR I Ce UNINTERRUPTED/UNSWITCHED POWER. SWITCH AND/OR DIMMER, USE AS MANUAL r1 WARM I))' 110LIGHTFIXT./ (((CI S REFER TO MFRS. FIGURE (� ON/OFF, MANUAL ON / AUTO OFFCU I 20A MAX. ((( WIX 3. DURING INSTALLATION THE LAST 4 DIGITS OF THE IEEE ADDRESS FOR EACH WIRELESS COMPONENT MUST BE RECORDEDWIRELESS OCCUPANCY SENSOR CEILING Ts IX ON ON THE SHOP DRAWING SET CORRESPONDING TO THE LOCATION OF THE COMPONENT. TYPICAL LIGHTING 1 POWER ZONE WITH OVER-RIDE CONTROL 0 d J N (( OZ0NE RECESSED-MOUNT: DAINTREE NETWORKS WREFER TO MFRS. FIGURE 9A O U N 4. DURING WIRELESS ADAPTER INSTALLATION FOLLOW THESE STEPS AS DEFINED IN THE DEVICE INSTALLATION GUIDE IN #WOS2-RM-E, PIR, 1000 SF COVERAGE 0 Q I: THEFOLLOWINGWAPM I))) 10 LIGHT FIXT.I / FOR LIGHT TYPICAL EXHAUST FAN (RESTROOM/JANITOR/LOUNGE) N i/� ORDER. �/ WIRELESS PHOTOSENSOR, CEILING-MOUNT: 20A MAX. {{ S FIXT. ONLY REFER TO MFRS. FIGUREI CONTROL EXHAUST FAN Ci J a. CONFIRM WIRELESS ADAPTER DIP SWITCHES ARE SET CORRECTLY. Cps VIA NON NETWORKED J Ce b. RESET ADAPTER (ALL ADAPTERS) � ZONE DAINTREE NETWORKS #WPS1 I AUX OUTLETS: ((( RM SHARED N cv N DUAL-RELAY WALL Z 0 QT T 20A MAX O S o S o S a S oSENSOR AND TIMER 0 c. PERFORM PROPER ES SUITE. I EXHAUST FAN DAINTREE NETWORKS #RWS-BZ-200 RELAY ELECTRICAL PANEL AREA I LOAD 1 SWITCH W W U ❑ 5. INSTALLER MUST BECOME FAMILIAR WITH THE PUBLISHED INSTALLATION GUIDES FOR THE PRODUCTS IN THE PROJECT AUX PACK INSTALLED IN ACCESSIBLE JUNCTION TYPICAL RECEPTACLE IPOWER ZONE WITH OVER-RIDE CONTROLCe SCOPE. DAINTREE INSTALLATION GUIDES CAN BE FOUND AT: BOX ABOVE CEILNG REFER TO MFRS. FIGURE 9A H DAINTREE.NET/RESOUTCES/DEVELOPMENT-TOOLS/ WGA _. LLI 04 Q � WIRELESS ADAPTER: U)� OUTLETS: 1 WAPM I ) AUX /J DAINTREE NETWORKS #WA100-PM 15A LINE 20A MAX Z CI t/1 DAINTREE MECHANICAL CONTROL RELAY, 5mA DIMMING DRIVER CAPACITY (10 O TYPICAL MULTI-POLE (277V) LIGHTING ZONE Z 0 1. ALL WIRELESS ADAPTERS MUST BE PROVIDED WITH UNINTERRUPTED/UNSWITCHED POWER. WSA10 WIRELESS SENSOR DRIVERS TYP.) REFER TO MFRS. FIGURE 3B W J ADAPTERS REQUIRE 24V POWER. � El WGA I))) I 277VAC I Q CV WIRELESS GENERAL ADAPTER. I' WGA ) I 1 CONTACTOR FIXTURE CIRCUITS 2. DURING INSTALLATION THE LAST 4 DIGITS OF THE IEEE ADDRESS FOR EACH WIRELESS COMPONENT MUST BE RECORDED // DAINTREE NETWORKS #WGA100 GENERALICE gm m ON THE SHOP DRAWING SET CORRESPONDING TO THE LOCATION OF THE COMPONENT. PURPOSE 15A LINE RELAY TYPICAL LEAK SENSOR I CA 3. FOR ANY SENSORS ATTACHED TO A WIRELESS SENSOR ADAPTER (WSA10) THE LAST 4 DIGITS OF THE IEEE ADDRESS SENSOR ADAPTER: REFER TO MFRS. FIGURE 7 FOR THE RESPECTIVE WSA10 MUST BE RECORDED. THE SPECIFIC WSA10 PORT MUST ALSO BE RECORDED PER SENSOR. WSA )/ DAINTREE NETWORKS #WSA10 WARM I)}) dPS Ex NOTE: 0 1 . GC TO OBTAIN DAINTREE CERTIFICATION ON 4. DURING WIRELESS ADAPTER INSTALLATION FOLLOW THESE STEPS AS DEFINED IN THE DEVICE INSTALLATION GUIDE IN HVAC/ELEC THE FOLLOWING ORDER. LD LEAK DETECTION SENSOR: DAINTREE RBA-BA LDT1 -PS-BB; TYPICAL ACCESSORY HEATING ZONE a. CONFIRM WIRELESS ADAPTER DIP SWITCHES ARE SET CORRECTLY. # / _ � 2. FINAL DAINTREE DESIGN INCLUDING ARCHITECT/ ENGINEER OF RECORD PROVIDE AT ROOMS WITH WATER HEATERS, REFER TO MFRS. FIGURE 3 AND MECHANICAL ZONE Ir.e 1 b. RESET ADAPTER (ALL ADAPTERS) EQUIPMENT REQUIREMENTS TO BE FINALIZED c. PERFORM PROPER TEST SUITE. SUMP/EJECTOR PITS, OR THE LIKE r...l WGA I))) BASEBOARD OR 1 WITH CLEARLIGHT SOLUTIONS. DUCT HEAT pm 5. INSTALLER MUST BECOME FAMILIAR WITH THE PUBLISHED INSTALLATION GUIDES FOR THE PRODUCTS IN THE PROJECT O CURRENT TRANSFORMER: SCOPE. DAINTREE INSTALLATION GUIDES CAN BE FOUND AT: FP DAINTREE #CR9580-10-M WIRED TO WGA100 DAINTREE.NET/RESOUTCES/DEVELOPMENT-TOOLS/ SINGLE PHASE DESIGN 6. ELECTRICAL CONTRACTOR IS RESPONSIBLE FOR PROCUREMENT AND INSTALL OF DAINTREE AND RELATED COMPONENTS (((p)) CELLULAR MODEM: PERTAINING TO IT DATA, LIGHTING, POWER AND HVAC. ( ) DAINTREE #CELL-MDM-VZ-1 WAC Architectural IT/DATA, LIGHTING ZONE CONTROL SCHEDULE Solutions Group BMS LIGHTING AND POWER CONTROL AND SENSOR DESIGNER NOTES OWNER'S IRRIGATION SYSTEM CONTROL CONTROL FUNCTION 19120 SE 34TH STREET, SUITE 115 IRC PANEL: WEATHERMATIC ENABLED FOR ZIGBEE ZONE LOCATION 1 ROOM ! FUNCTION REMARKS t WIRELESS PROTOCOL, BY OWNER'S ON OFF DIM OVER-RIDE TYPE OVER-RIDE LOCATION VANCOUVER, WA 98683 • COORDINATION WITH THE BMS VENDOR FOR IS REQUIRED. THE ARCHITECT / ENGINEER OF RECORD SHALL ADVISE THE I VENDOR 30 DAYS IN ADVANCE OF THE BID DATE THAT PROJECT DESIGN HAS COMMENCED. SUBMITTAL FOR VENDOR LANDSCAPER DRIVE-UP CANOPY DOWNLIGHTS PHOTOCELL SCHEDULE --- WALL SWITCH WIRELESS AT OR NEAR TELLER LINE These drawings and specificat ons are the confidential and proprietary grope ty of JP Morgan Chase and shall not iue copied ar reproduced without written authorization. The contract documents were prepared for use on this specific REVIEW AND COORDINATION MUST BE EXECUTED WITH ADEQUATE TIME TO ALLOW COORDINATION AND ADJUSTMENTS BUILDING AND POLE-MOUNT EXTERIOR AREA LIGHT FIXTURES (SUB-ZONES site In con;unct an with ifs issue date and°re not salable far use one di%e en, WIRELESS OPEN LOOP PHOTO CELL: PHOTOCELL SCHEDULE WALL SWITCH WIRELESS AT OR NEAR TELLER LINE site a at a ester time. °se of these dawings res rliensed ar example an BETWEEN THE ARCHITECT, MECHANICAL ENGINEER, AND ELECTRICAL ENGINEER BEFORE BID. AS REQUIRED) °"°'he project rdgaires the services at draper" '``eased archllecfs and engineers. Reproduction of the conhacl docurnenk lu reuse on ono#her EX PS DAINTREE #CES/OD-24-0-10 PLC 24V EXT. project is not authorized. • DESIGNER SHALL CLEARLY INDICATE IN CONSTRUCTION DOCUMENTS THAT THE WIRELESS DEVICE CONTROLS REPLACE I PHOTOCELL- WIRE TO WA100-PM EXTERIOR ENTRANCE DOWNLIGHTS AND SITE MONUMENT / PYLON SIGNS PHOTOCELL PHOTOCELL --- WALL SWITCH WIRELESS AT OR NEAR TELLER LINE TYPICAL HARDWIRED SWITCHING AND WIRING REQUIREMENTS, AND THAT THE CONDUIT SYSTEM IS NOT REQUIRED FOR EXTERIOR BUILDING SIGNAGE PHOTOCELL SCHEDULE --- WALL SWITCH WIRELESS AT OR NEAR TELLER LINE SEAL THE CONTROL DEVICES ASSOCIATED W1TH THE BMS EXCEPT AS NOTED. ) WIRELESS AREA CONTROLLER: EXTERIOR DECORATIVE LIGHT FIXTURES SCHEDULE SCHEDULE --- WALL SWITCH WIRELESS AT OR NEAR TELLER LINE , E� PROFFs, , WAC DAINTREE WAC60 N fF 'o • WHERE REQUIRED BY AUTHORITY HAVING JURISDICTION, PROVIDE CONTROL DEVICES AND CIRCUITING AS REQUIRED TO / # VESTIBULE (ALWAYS ON) SCHEDULE SCHEDULE PHOTOCELL* WALL DIMMER WIRELESS AT OR NEAR TELLER LINE 1 �P 15,423 COMPLY WITH ENERGY EFFICIENCY CODES(S) WHERE APPLICABLE. OCC. SENSOR, UNINTERRUPTABLE POWER SUPPLY: PRIVATE OFFICE (PCS/CCS) GENERAL LIGHTING (SUB-ZONES AS REQUIRED) OCC. SENSOR SCHEDULE MANUAL WALL DIMMER WIRELESS AT OR NEAR TELLER LINE 2 • ZONE Z5 FOR EXTERIOR-FACING INTERIOR SIGNAGE NOT PROVIDED WITH THIS PLAN, BUT WOULD BE REQUIRED FOR UPS 120V, 350VA MIN., PROVIDED BY G.C. a' WALL-WASH RECESSED CANS AIMED AT SIGNAGE, ILLUMINATED LETTER SETS, ETC. 1 CONFERENCE ROOM GENERAL LIGHTING OCC. SENSOR OCC. SENSOR, SCHEDULE MANUAL WALL DIMMER WIRELESS IN ROOM ��P�• 31, Lp`Lo' 7----\ POWER METER: PRIVATE OFFICE (PCS/CCS) AND BOOTH DESK PENDANTS (ALWAYS ON) MANUAL WALL DIMMER* WIRELESS AT OR NEAR TELLER LINE 2 �Rk R - 04/14/20 • EMERGENCY LIGHT FIXTURES WITH BATTERY PACKS ARE NOT INDICATED FOR SEPARATE ZONE CONTROL, BUT SHALL PM 3-POLE: DAINTREE #RDN-PS3037-S-N BE PROVIDED WITH CONTROL DEVICES AS REQUIRED TO SYNCHRONIZE FIXTURE SWITCHING WITH OTHER FIXTURES ` I l 24-POLE: DAINTREE #RDN-P524-D LOBBY GENERAL LIGHTING (SUB-ZONES AS REQUIRED) SCHEDULE SCHEDULE PHOTOCELL* WALL SWITCH* WIRELESS AT OR NEAR TELLER LINE 1 WITHIN THE SPECIFIED ZONE. VESTIBULE AND LOBBY ACCENT LIGHTING- COVE STRIPS, ETC. SCHEDULE SCHEDULE --- WALL SWITCH WIRELESS AT OR NEAR TELLER LINE ROB ISON OCCUPANCY SENSOR, CEILING-MOUNT, ENGINEERING, INC • FIXTURES WITH INTEGRAL OCCUPANCY SENSORS (UNDERCABNET, ETC.) DO NOT REQUIRE ZONE CONTROL SWITCHING. OC1 CONFERENCE ROOM ACCENT LINGTING SCHEDULE SCHEDULE WALL SWITCH WIRELESS IN ROOM PASSIVE INFRARED, WITH 3-WAY MANUAL 19401 40TH AVE W SUITE 302,LYNNWOOD.WA 98036 TEL:206-364-3343 FAx:425-835-0098 • EXIT LIGHT FIXTURES ARE EXCLUDED FROM BMS ZONE CONTROL. OVER-RIDE SWITCH: WATTSTOPPER #CI-355 CONFERENCE ROOM PENDANT(S) (ALWAYS ON, WITH IN-ROOM OVER-RIDE) SCHEDULE SCHEDULE MANUAL WALL DIMMER* WIRELESS IN ROOM 4 CON3343 HANEMC25-83 REMARKS: ISSUE DATE DESCRIPTION • ROOF CENTRIFUGAL EXHAUST FAN IS NOT CONTROLLEDBY BMS. REFER TO DETAIL 3/EO-2, DESIGN-INTENT EXHAUST OCCUPANCY SENSOR, CEILING-MOUNT, FAN CONTROL DIAGRAM, FOR HARDWIRED LINE-VOLTAGE CONTROL REQUIREMENTS. I::@ DUAUAL-TECHNOLOGY: 1 ONLY INCLUDE AUTOMATIC DIMMING CONTROL FOR THIS FIXTURE GROUP IN JURISDICTIONS REQUIRING DAYLIGHT HARVESTING. WATTSTOPPER #RWS-DT-305 2 PROVIDE SINGLE WIRELESS MANUAL DIMMER CONTROLLING ALL PRIVATE OFFICE AND BOOTH PENDANTS. PROGRAM FOR 50% DIMMING DURING BRANCH HOURS AND 10% DIMMING AFTER BRANCH HOURS. • LARGE FIXTURE GROUPS TAGGED WITH A COMMON ZONE, SUCH AS THE SITE AREA LIGHT FIXTURES OR LOBBY TROFFERS, ARE TO BE CONTROLLED SIMULTANEOUSLY. CONTROL SUB-ZONES ARE TO BE PROVIDED AND CONTROLLEDWALL-MOUNT SINGLE-RELAY OCCUPANCY 3 PROVIDE SINGLE WIRELESS MANUAL DIMMER CONTROLLING ALL PRIVATE OFFICE GENERAL LIGHT FIXTURES. PROGRAM FOR 50% DIMMING DURING BRANCH HOURS AND OFF AFTER BRANCH HOURS. BY RELAY CIRCUITS AS DETERMINED BY THE MAXIMUM NUMBER OF FIXTURES PERMITTED ON A SINGLE CIRCUIT. r1 0C SENSOR WITH COMBINED SWITCH: 4 PROVIDE WIRELESS MANUAL DIMMER FOR CONFERENCE ROOM PANDANT(S). PROGRAM FOR 50% DIMMING DURING BRANCH HOURS AND 10% DIMMING AFTER BRANCH HOURS. LEVITON ODS10-IDW • REFER TO SHEET M1 FOR MECHANICAL EQUIPMENT REPORTING AND CONTROL DEVICES. NOTE: CONTRACTOR SHALL REFERENCE SHEET E1.0 LIGHTING PLAN FOR ZONING WALL-MOUNT SINGLE-RELAY OCCUPANCY • LIGHTING AND SIGNAGE ZONE TIMER / PHOTO CELL PROGRAMS SHALL BE SET PER THE BMS LIGHTING CONTROL [[OC2 SENSOR WITH COMBINED SWITCH: SCHEDULE BY THE CHASE FACILITY MANAGER THROUGH THE REMOTE CONTROLSCOPE / ALLSITES INTERFACE. WATTSTOPPER DSW-302 CONTROLSCOPE COMMISSIONING 4-13-20 PERMIT SUBMISSION 4-3-20 90% SET • MULTI-POLE CONTACTORS AND RELAYS SHALL BE PROVIDED AS REQUIRED BY THE ELECTRICIAN TO EXECUTE THE [ PUSH-BUTTON LINE VOLTAGE 5/10/15/30-MINUTE 1. CONTRACTOR IS RESPONSIBLE FOR CORRECT WIRING, TESTING, 3-20-20 PLANNING DESIGN-INTENT CONTROL CIRCUITING INDICATED IN PLAN. T TIMER: WATTSTOPPER TS-400 AND DOCUMENTATION OF ALL IEEE DEVICES ADDRESSES IN A PROJECT INFORMATION BLOCK FORMAT REQUIRED BY THE CONTROLS SUPPLIER. JOB# JPM19010.0 • WHERE REQUIRED BY AUTHORITIES HAVING JURISDICTION, PROVIDE CONTROL DEVICES AND CIRCUITING AS REQUIRED TO PUSH--BUTTON LOW VOLTAGE 5/10/15/30-MINUTE DATE. 1/20/2020 COMPLY WITH ENERGY EFFICIENCY CODE(S) ONLY WHERE APPLICABLE. [TLV TIMER: WATTSTOPPER TS-400-24 2. CONTRACTOR IS RESPONSIBLE FOR COORDINATING INSTALLATION DRAWN BY: GH AND COMMISSIONING EFFORTS WITH THE CONTROLS PROVIDER CHECKED BY. PR • CONTROLLED OUTLETS TO BE PROVIDED ONLY TO THE MINIMUM EXTENT REQUIRED BY APPLICABLE ENERGY CODES. TO SATISFY THE CONSTRUCTION TIMELINE. CONTROL SHALL BE PROVIDED BY NEAREST OCCUPANCY SENSOR. OFFICES, AND SIMILAR SPACES SHALL RECEIVE A [TLV 120 V UNIVERSAL MANUAL LINE DIMMER: MODEL SINGLE CONTROLLED DUPLEX OUTLET OVER THE DESK. CONFERENCE ROOMS SHALL RECEIVE A SINGLE CONTROLLED LEGRAND RH703PTUW 3. CONTRACTOR IS RESPONSIBLE FOR PROVIDING FIELD LABOR DRAWING STANDARDS v20. 1 DUPLEX WALL OUTLET. ALL LOBBY AND PRINT ROOM CONVENIENCE RECEPTACLES (NOT ADJACENT TO EQUIPEMENT) ASSISTANCE TO FACILITATE THE COMMISSIONING EFFORT, SHALL BE SPLIT-WIRED TO THE NEAREST OCCUPANCY SENSOR. SHUNT RELAY FOR 0-10V AND LINE VOLTAGE INCLUDING BUT LIMITED TO REPAIRING INCORRECT WIRING, SHEET TITLE EM FOR USE WITH WA-100PM WATTSTOPPER LOCATING DEVICES WHERE THE ADDRESSES WERE NOT • PROVIDE ONE LEAK DETECTOR IN EACH ROOM WITH A WATER HEATER, SUMP/EJECTOR PUMP, OR THE LIKE. BZ-200 PLUG LOAD AND ETC. POER PACK: DOCUMENTED OR NOT LOCATED PROPERLY, AND RESETTING LIGHTING CONTROL LVS RLC-RRU-X-UNV DEVICES. DETAILS • PROVIDE ONE TEMPERATURE SENSOR IN EACH ROOM WITH ATMS OR SIMILAR TRANSACTION EQUIPMENT, EXCEPT THE LOBBY OR ANY SIMILAR OPEN SPACE. UNIVERSAL VOLTAGE NON-PLUG LOAD POWER BZ50 PACK: WATTSTOPPER BZ-50 • CONTROL AND SENSOR DEVICES MUST NOT BE PLACED ON ANY WALL DESIGNATED FOR AN ACCENT FINISH. DEVICES ARE TO BE PLACED AS AS NEAR THE ENDS OF WALLS AS POSSIBLE, SO AS NOT TO INTERFERE WITH MARKETING SHEET NUMBER MATERIAL POSITIONING. ESPD PHASE DIMMING CONVERTER TO 0-10V DIMMING: ECOSENSE LDCM-PL • LANDSCAPE IRRIGATION CONTROLLER SHALL BE COMPATIBLE WITH THE BMS SYSTEM, AND BE PROVIDED WITH WI-FI CONNECTIVITY. COORDINATE CONTROLLER SPECIFICATION WITH DAINTREE AND LANDSCAPE IRRIGATION SYSTEM VENDOR. E 1 FIGURE 1: LIGHTING CIRCUIT CONTROL FIGURE 4: WA100-PM WITH EXTERI❑R PHOTOCELL FIGURE 7: WGA100 WITH LEAK DETECTI❑N SENSOR illia6 DIP Switches DIP Switches DIP Switches Switchinga 20A Branch Circuit, Ballast Type. Wired Ballast Type. i Wired OFF Ballast Type• 1 , 1 Wired EFF-.61.-twl Load limit On/Off + 0-10V j11,i1i Sensor. EFF-6 Switching a 20A Branch Circuit, Load limit On/Off + o-1ov 1iKij Sensor. �e_� On/Off + 0-10V 'jlli Sensor. 15Ai dimming (#4 ON) None 15A' dimming (#4 ON) None dimming (#4 ON) None This configuration allows the WA100-PM to to Perform Installation Test Suite 1 This configuration allows the WA100-PM to to Perform Installation Test Suite 1 WHITE Neutra. Perform Instnitntion Test Suite 1 LLI provide On/Off provide On/Off ii BLACK Hat , switching of a brach circuit. switching of a brach circuit. ,,,,,I, ) WHITE Neutral WHITE Neutral. Crone Voltage r 7 111 G ,' i i Wes BLACK jHot ` BLACK OI L. -t--12"7"114C Line Voltage r-. Line VoltageWires Wes - 01 `� 01 - '� a ® Low Voltage r Wires D Da etwrrk� "��M row \�\�,.,......, � Low Voltage � Low Voltage I �w•T WGA100 Dunused El Wires \ LI rr Wires w .,r •`rcif.-Nehre,ks �"«I. Ne[.raks \ �� `r Wk'e>f RED �... mow. i ... w. ',:" — ) sed 14AWG ® ."----7*-- ` . _.. W A 10 0 P M WOS ,. .�.. W A 10 0 P M 30 J-Box or Switched �.. ettN' .'�",r, w ... ' .mow" Equivalent Load RED - = 0. 0 RED ws «..14AWG 0111111 _ 120-277VAC 14AWG U J-Box or Switched '_-� Bax Switched `-+ 01 10, * \ Equivalent Load Equivalent Load 24VDC RED 24 VDC Power Output p _ 120-277VAC _ 120-277VAC Digital (bina.ry) Sensor'Eo l l aL ,_„...1 , o! T �, l a1, ,.1 , Corson BLACK Ground/Common o Leak detection sensor :111 --'''' d BLUE 81r►aryt (active high, enabled with DIF Q s�.r. ,, YELLOW BinaryInput (active h1�1h, enabled EC Hot ., Hot 24VDC 24V ia/ RED 24VDC Power V With DIP switch 5 a. BLACK Gro und, if V Ballast hotosensor Command Neutrc IarnDriveNeutr tpBal.lat* (� (0-10 VDC0 (0-10 VDC) lOV Qut u Contro( * ORANGE 0-1OV Analog input Hot Dlwpra Ballast ( Hot DMr,Yip Ballast Neutr l OD-10 VDC) III Neuer lroL1EOb v ON\ FIGURE 8: WGA100 FOR TEMPERATURE AND HUMIDITY SENSORS CW v 4,0 1 Lc) Imm Ci IN. Ix FIGURE 2: LIGHTING CIRCUIT CONTROL FIGURE 5: WA100-PM DIMMING C❑NFIGURATI❑N �, . ,�, M > 0-1Ov Sensors DC Powers -A• Sr1 a CL W �/ Sensor 1 Shy °S 10K Type 2 (xl) Thermistor• M DIP Switches DIP Switches •ower 24V Cable 10K Type2 (x3) CC -1 A' Ballast Type. :� Wired OFT-6IBallast T e� Wired OFF l -OV U O W " yp . r ' rCable Shielc I Cable Switching a 20A Branch Circuit, Load limit On/Off + 0-10v j11e11� Sensor. e-i� Switching a 20A Branch Circuit, Load limit On/Off + o-lov jj�.�i� sensor. �e-� d � II 4 Thelerter8�p ;;;: Dajntree 1�lputpll4VAIYeCGrrenb +� `camps rta0 Q LL N dimming C#4 ON) None dimming (#4 ON) None Networks mr.i►...c lottery s'dr4'M sav �" 0 15Ai15A1 «A �;_ - �24 1 u a Irlo.rt) T a.- ae v +� we C - This configuration allows the WA100-PM to to This configuration allows the WA100-PM to to Sensor i'• �— - ♦.u„so a Band) w'a'r "++� ""^'�°' t ��� I y Perform Installation Test Suite 1 Perform Installation Test Suite 1 = m ICT OPEN 1EV10E CO Q 13. provide On/Off provide On/Off - I aelrreres Ground) C switching of a brach circuit, • switching of a brach circuit. " - - e4 v t� C - ma IX +I.. • =- - e� v"c - near()b0 O O - Shield 1� / Z o 0 WHITE Neutral WHITE Neutral Drain W Drain wire / BLACK Hot > / BLACKHot O ) Line Voltage Line Voltage 014t ILI w U 0 tin i= °I L a Wq a Low Voltage � Low Voltage N t �!' a..w.rr Wires LI •••• nfreoN•we , — �w,.bP Wire0> Z C I s Na „"' �. '" WA100-PMFIGURE 9: WA100 DIMMING CONFIGURATION� �~ WA100-PM utd -�:-- =- urdZ o p RED = — •-' ri• 140111Pri� Whew REDI MI „•wriebblebb - .� �" "'' W/ AUXILIARY RELAY FOR PLUG LOAD W J 14AWG p — 14AWG — 4_ a N J-Boxor. Switched J-Box or CONTROL en Z quivalent Load � Switched DIP Switches a IM - 120-277VAC _ 120-277VAC �, On/Off +y0 lOV �jlj�il���c� Sensor. 01 I o o I -� I o WHITE Neutral Ballast T . Wired 1 -i e 441 , . I BLACK Hot dimming (#2,3 ON) NoneI L. ,_.,,1 rex. `�Vf ' T Perform Installation Test Suite 1 Sty Hot D ip 01 Line `�-�'-' 12, �, . 0 y • Neutr l or LED �Y (-)c GRAY Analog Ground W� - CO-10 VDC) VELET (40 ^ VIOLET 0-10V Analog Output (dnwinq Wires E1 \ Daln..,..K vorkc Low Voltage 7 �, �� _ .y - M Wires ARCHITECT/ ENGINEER OF RECORD Hot Hot ,rte Ballast GRAY (-) ,� ap• II �m 3� Lim "sr Neutrc l or LED Driver - .m. Neutr l 4 (0-10 VDC) VDLET < C} ..,,.,,�.� �+ - vl/ `JI/ �l 0-lOv Diming output q 5nA available J-Box or ••%./ u Up to 10 LED drivers or fly . _ ballasts typical, the chance of low voltage errors increases with Equlvnlrrrt more. RED Switched 01 T 120-277VAC I0r L ,_„,1 DESIGN FIGURE 31 15A N❑N--LIGHTING LOAD C❑NFIGURATI❑N FIGURE 6, WGA100 ANALOG INPUT C❑NFIGURATI❑N WITH SELF-POWERED FAM CT Architectural Hot GRAY (-),- GRAY Analog Ground Solutions Group nap Switches or LLQ VIOLET (4.) VIOLET 0-10V Analog Output (dimming Ballast Type. r Wired ccr Swl•6d.rs (., (0`tO VDC) control) On/Off + 0-lOV .j1111J Sensor. a Driver Type• ilii{ , Wired -We dimming C41 ON) None �' on�f + 0-10V •1111;,, Sensor~ 19120 S E 34TH STREET, SUITE 1 15 WHITE Neutral dimming None �' VANCOUVER, WA 98683 WHITE Neutral Perform Installation Test Suite 1 �j Perform InstnUation Test Sults 1 Hot p 'Warty= GRAY <-) w l/ / BLACK Hot Or LEb ur•iv.r 0-10v Dimming output These drawings and specifications are the confidential and proprietary property BLACK Hot 5mA avallnble of JP Mo gpn Chase pad shall not be coped orrep oduced without wnitert =Arm,,vim. ,..w, Neutra (0-10 VIa ET ( aufhoriwiion. The conkad documents we a prepared For use on the specific U Up to 10 LED drivers or Line Voltage r M~ L I c t ballasts typical, the site in conjunction with its issue date and are not suitable for use on a different I ill.. ..►_: site or al a later time. Use of these drawings fa reference or example on W.V.r %fi • chance of low voltage errors another project requires the services of properly licensed architects and I Increases with more. engineers. Reproduction of the contract documents for reuse on another 01 --• - �1 01 �� �� V project is not authorized. \I:, it......... i C] WHITE Neutral Low Voltage rr��II 40::. Low Voltage !--.r: �... Wires IJ �•-° r- ;...,.. Wires BLACK Hot ) SEAL Dam tree Network. i .rl • �� lQr—C//Y/M. Dalnlrnu Nrrwor.s ) ... PR w`.` _ `� WGA100 O .J:.w- �� `Wes ,r �' WGA100 30 m ND I N FF Sso eife low14AVG e" `� RED ® ,ra..f.•'�:"` —I Line Vol•,.- 15,423 - 14AWG #.>quiva orSwitched '--i \ a Switched ` ` Equivalent Load ]]] Equivalent Load _ 120-277VAC 120-277VAC1 sir rt RED 24VDC Power �B; f• 01 to [I)([1n .0 o I I o Digital e� e 0 Switched -- GREEN La output �1,9Rk 31 0 \ScS L ,....,1 #., \ • Q 04/14/20 Switched Ho Switched line *INIp >�ac O11d^�'`""'0Y1 BZ200 Cep 24v2e Output ae"-'d) Common c voltage SR!(�eCT Power Pack [I) Netrtrld Power Outlet, Pump, Motor, etc. 0-WV Uu ORANGE � Input a.uv ) 11 Eq.rvnlent // (I] J_�x °� _ RoBIsoN (1) +� ` « l used for ,01 L la, ENGINEERING, INC „ 19401 40TH AVE W SUITE 302,LYNNWOOD,WA 98036 TEL:206-364-3343 FAx:425-835-0098 CONTACT:SHANE MCCLURE ISSUE DATE DESCRIPTION FIGURE 1: EXHAUST FAN CIRCUIT CONTROL DIP Switches CJD OS EXHAUST CONTROL DIAGRAM TYPICAL SINGLE-CIRCUIT SINGLE-POLE OCCUPANCY SENSOR SWITCH Ballast Type' :344[1111i Wired 17 Switching a 20A Branch Circuit, Load limit On/Off + 0-10V1iSensor. e-o T 15AI dimming (#4 ON) None Cr) 3-WAY PRE-SET 5-10-15-30 MINUTE PUSH-BUTTON TIMER SWITCH, LEVITON LTB30-1LZ OR SIMILAR This configuration allows the WA100-PM to to ROOF-MOUNTED UP-BLAST CENTRIFUGAL FAN- provide On/Off Perform Installation Test Suite 1 OS switching of a brach circuit, DUAL-CIRCUIT OCCUPANCY SENSOR- LUTRON MS-OPS6-DDV OR SIMILAR BACKDRAFT DAMPER (TYP.) • GRENHECK G-075HP-VGI6IG-X OR SIMILAR 4-13-20 PERMIT SUBMISSION 314 OS • APPROX. 11 H , 1 RPM, 4-3-20 90% SET WHITE Neutral EXHAUST DUCTWORK l BLACK Hot ; . WITH BACKDRAFT DAMPER 3-20-20 PLANNING vAc > Line Voltage PROJECT INFORMATION BLOCK r ^fite"" Wires JOB# JPM19010.0 0l L JANITOR'S WOMEN'S MEN'S DATE: LOUNGE DATE: 1/20/2020 DRAWN BY: GH CLOSET RESTROOM RESTROOM CHECKED BY: PR� Low Voltage \ JJ Wires MODEL ~rfreeNs,works ,� ����~r \ �f11MUt��a�wsw. apes b �� ' N�� WA100PM D •� -.rm. a �.+ - - N m. 1Y� •ter 120V unusedvb. X DRAWING STANDARDS v20.1 REDC ewe L-2 L-2 L-2 L-2 14AWG 120V 120V , 120V C •}� or. Switched ® ilmoNNIIN , C C C SHEET TITLE Equivalent Load C 120-277VAC OS ADDL. FIXT. OS ADDL FIXT, OS ADDL. FIXT. - ADDL. FIXT. LIGHTING CONTROL of log I CIS _ c DETAILS ~M~ Switched Switched line 3 S '1 CJS 1 bS I T� voltage "tf°i Exhaust Fan, 120V 15 x/lhp maFxagi.m C SHEET NUMBER 4-WAY CIRCUIT WIRING E1 . 3 COPYRIGHT-2016, . a. a , ii. 9iCg1JRE F:\.RFI\.QUISE BAN*\230-1716 CHASE ORANGE CIRCLE - ORANGE. A'J) 3DNG 02-16-2018 0&42 1 1 in) w tin < 1 i POWER PLAN KEYED NOTES IL 1. CONCRETE FLOOR SLAB BLOCK-OUT AS REQUIRED TO PRECISELY POSITION JUNCTION BOX-INFILL WITH CONCRETE PRIOR TO FLOOR TILE INSTALLATION. 2 U ,0Lu 2. ROLL-UP DOOR MOTOR WITH OVERHEAD COILING DOOR KEY SWITCH AND EXIT RELEASE. EC TO VERIFY EXACT LOCATION AND REQUIREMENTS WITH VENDOR AND PROJECT MANAGER PRIOR TO ROUGH-IN. cL a 3. PROVIDE AN EMPTY 3/4" FLEXIBLE CONDUIT WILL A PULL LINE FROM CEILING CAVITY DOWN THE DOOR MULLION TO FACILITATE DOOR CONTACT INSTALLATION. 4. CONTRACTOR SHALL PROVIDE ELECTRIC STRIKE TO CONTROL THE RIGHT DOOR ONLY. 0 ® A� 5. THE ELECTRICAL CONTRACTOR SHALL PROVIDE A RACEWAY TO THE FRONT OUTER VESTIBULE DOOR FRAMES FOR THE PURPOSE OF RUNNING WIRES FOR 11 THE ELECTRIC DOOR STRIKE, OVERRIDE KEY SWITCH AND ASSOCIATED EQUIPMENT. THE ELECTRICAL CONTRACTOR SHALL FURNISH AND INSTALL ALL CONDUITS AND JUNCTION BOXES INCLUDING FLEXIBLE CONDUIT, IF REQUIRED AS WELL AS PULL WIRES AS REQUIRED. r on\ 6. AUTOMATIC DOOR KEY SWITCH. VERIFY FINAL LOCATION WITH PM/ARCHITECT. CO LLI 7. CONTRACTOR SHALL PROVIDE FLUSH TYPE DUPLEX RECEPTACLE MOUNTED VERTICALLY BELOW LAVATORY FOR AUTOMATIC SENSOR FAUCET. MOUNT AS tO IMI- 0 HIGH AND CLOSE TO LAV AS POSSIBLE TO CONCEAL FROM CUSTOMER VIEW. COORDINATE EXACT REQUIREMENTS AND LOCATION PRIOR TO ROUGH-IN. 10� 8. FOR EACH ATM PROVIDE A DUPLEX OUTLET AT +18" AFF, A DATA OUTLET MOUNTED AT +18" AFF, AND A SECURITY JUNCTION BOX MOUNTED AT +18" rig IMI Ee AFF. THE POWER, SECURITY, AND DATA OUTLETS SHALL BE ON THE RIGHT SIDE OF THE ATM (FACING THE ATM FROM THE BACK) FIELD VERIFY O Clm W I� CONDITIONS BEFORE ROUGH-IN. THE ATM SECURITY CIRCUIT SHALL BE HARD WIRED BY THE SECURITY VENDOR. O 4 1 ceCO N 9. INTERNALLY ILLUMINATED CABINET EC TO WIRE AND CONNECT LAMPS. FIELD COORDINATE EXACT REQUIREMENTS AND LOCATION PRIOR TO ROUGH-IN LLII (y AND ADJUST ACCORDINGLY. MULLION WITH ® MOTORIZED SHADE 0 (•) ka IIS ELECTRIC STRIKE FHP,12OV1 P2W N N 0 10. ELECTRICAL CONTRACTOR TO PROVIDE (3) 3/4" CONDUIT FOR SEPARATE POWER/DATA/SECURITY FEEDS. RUN POWER/DATA CONDUITS/FEEDERS FROM MOTORIZED SHADE CI J ABOVE CEILING DOWN THRU WALL, INTO ATM. SEE DETAILS ON SHEET E2.1. FIELD VERIFY EXACT LOCATION AND REQUIREMENTS WITH PROJECTNev. FHP,120V1P2W PUSH BUTTON /-ILLUMINATED SURROUND CO ce MANAGER/"eATM" VENDOR AND ADJUST ACCORDINGLY. MOTORIZED SHADE +66" g M Z Q O 11. PROVIDE WALL MOUNTED eATM SECURITY KEYPAD. COORDINATE EXACT LOCATION WITH CHASE PM. SEE DETAIL ON THIS SHEET. ® FHP,120VI P2W � 12. PROVIDE (2) 4" DATA CABLE SLEEVES PROVIDED BY OWNER AND INSTALLED BY G.C. -- 0' -�.� [0 N'IF -1- - - :(" 4.6 -:. -1 0 4t og v a " ,�-i, :►!�l _���_ T lye' . +44 !!� 0r % 1 I i +184 ;0n +2fi a • r, ♦ O •• KEY IG 13. PROVIDE LEGRAND EFB45 FLOOR-RECESSED JUNCTION BOX W/ ALUM. COVER AND INTERNAL ACCESSORIES AS REQUIRED FOR THE FOLLOWING (2) 120V +18"yY IC 22 CD ► O�, r 'f" �� �� t, j gwi 1 4' I v 0+�8 Cl- WI ct < DUPLEX, (1) BLANK COVER PLATES, ONE PLATE WITH TWO DATA JACKS AND 3/4" IN-FLOOR CONDUIT TO ADJACENT WALL JUNCTION BOX AND 011 '1I♦♦TIN IJ V 1.1 1 �-I , Y . 1 16 Z 0 ♦� O CONDUIT TO OPEN CEILING. VERIFY EXACT LOCATION WITH ARCHITECT. 26 _ f 11 i`�, �_ _I i 8 # N 1 r.../ T� A-15 ..t► O CD imm 14. RUN POWER DATA CONDUITS/FEEDERS FROM ABOVE CEILING DOWN THRU WALL IN TRENCH AND UP INTO FLOOR BOX. VERIFY EXACT LOCATION WITH I - I I I I ~ , Z PROJECT MANAGER. Ii LI I i-' r _I IL1 -3 TA- w -I 4 15. PROVIDE (1) DUPLEX, (1) DATA, (1) GANG BACK BOX. FOR DIGITAL DISPLAY ABOVE PROVIDE (1) RECESSED DUPLEX, (1) GANG BACK BOX, AND 1 1/4" / 1 QAC //� 01CONDUIT STUB UP WITH PULL STRING ABOVE CEILING TO OFE RACK. COORDINATE EXACT LOCATION REQUIREMENTS WITH CHASE PROJECT MANAGER AND al' A-23 AFE FC-1 V♦ Z AV VENDOR. / r � I REFRIG. - :: I - - - a 16. J-BOXES, CONDUITS, AND COVER PLATES FOR POWER AND ALARM. ALARM CONDUIT AND BOX TO REMAIN OPEN FOR WIRING BY OWNER'S ALARM 16 11 1B eDED +18iX (n CONTRACTOR. +18"i' r�'��I �+ 17. PROVIDE (2) 1-1/4"C DOWN THE WALL INTO A JUNCTION BOX UNDER TELLER COUNTER FOR VOICE/DATA/SECURITY FEEDS. PROVIDE A 1"C DOWN THE / +18"'i' fr .,,•__:-,-,' , � , 0 c, WALL INTO A JUNCTION BOX UNDER THE TELLER COUNTER FOR SECURITY CABLING. Of ii-nil#11 . - rn 18. RECEPTACLES ARE EXEMPT FROM THE CIRCUIT CONTROLS FOR 120V RECEPTACLES. PRINTERS, COPIERS, IT EQUIPMENT, 24/7 FUNCTION/SECURITY, it A- ...r.--,..• ; W KITCHEN APPLIANCES PER CEC 8.5. ����'�I ____ / . A-91 _ ARCHITECT/ ENGINEER OF RECORD 19. REFER TO TELLER SECTION ON SHEET E4.00 DETAIL 2. [V f? +62" e� • It A-19 . J icr �- t/fi- r100:1--+ER..\ . 20. CONTROL FOR MOTORIZED SCRIMS. VERIFY EXACT LOCATION WITH PROJECT MANAGER. J J A47IPH 36"111 m BZ { Iti C0 ID- A-20 pAN 21. SECURITY J-BOX OUTLET. VERIFY EXACT LOCATION WITH PM. - 18 '"' � �' 22. PROVIDE PLUG LOAD CONTROLLER "WAPM" AND "BZ RELAY PACK" FOR CONTROL DUPLEX RECEPTACLE. CONNECT TO EACH ROOM DIMMING ROOM +26'0 -„ IG �.._-, 0 A-16 `lllr DESIGN CONTROLLER, SEE E0.1 FOR PLUG LOAD CONTROL DIAGRAM. FOR EACH ROOM, THE SAME "WAPM" WILL CONTROL THE LIGHT FIXTURES AND THE H COFFEE r MICR AVE n - " "` :•:� ->. 11 10 eATM *26'e +18 CREDENZA . 11 .,.... CONTROLLED RECEPTACLES. IN EVERY OFFICE, ONLY THE +26" RECEPTACLE SHALL BE CONTROLLED; THE RECEPTACLES AT EACH OFFICE DESK +18" lis DED GFC _ MOUNTED AT 18", SHALL NOT BE CONTROLLED BY THE PLUG LOAD CONTROLLER. EVERYWHERE ELSE, RECEPTACLES MUST BE EITHER SPLIT WITH .! - V _ _ +44 H Architectural (1)CONTROLLED CIRCUIT AND (1) UNCONTROLLED, OR EVENLY SEPARATE CONTROLLED AND UNCONTROLLED RECEPTACLES WITHIN SPACE. 1 �� A-17 �^ cn , SECURITY MONITOR Solutions Group I O 0�_1 ❑o +96' 23. PROVIDE APPROPRIATE ROUGH-IN AND FINAL CONNECTION TO MOTORIZED SHADES, FIELD COORDINATE EXACT REQUIREMENTS WITH INSTALLING `� (ry 19120 SE 34TH STREET, SUITE 1 15 CONTRACTOR AND ADJUST ACCORDINGLY. CONDUIT FED DOWN FROM ACCESSIBLE CEILING TO BOX MOUNTED IN WINDOW RETURN GYP BOARD WITH A , FLEXIBLE GREENFIELD CONDUIT UP TO BOX MOUNTED IN WINDOW FRAME HEADER CONSTRUCTION BELOW BEAM. REFER TO TYPICAL POWER OPERATED J -, /PEW' • 4 VANCOUVER, WA 98683 �z WINDOW SHADE ROUGH-IN DETAIL THIS SHEET FOR ADDITIONAL INFORMATION. FIELD COORDINATE OPERATED W/ PROJECT MANAGER AND ARCHITECT Al / These drawings andSpeGlca+an5are,hecanfidenliaEandpap�e,arypaper� AND ADJUST ACCORDINGLY. + - //����� of JP Morgan Chase and shall not be copied or reproduced without written authorization. The contract documents were prepared for use an this Specific site in conjunction with its issue date and ore not suitable tar use on a different 24. MAINTAIN REQUIRED CLEARANCES FOR ALL RECESSED ELECTRICAL PANELS PER CALIFORNIA ENERGY CODE. Ak, ' B slfe h a,a late time. Use of these draw ngs far reference ar example on another project regVir@; the services of Profiled), iCgrlSetl architects and engineers. Reproduction of the contract documents for reuse on another n r project is not authorRd. e 25. WALL-MOUNTED OR CEILING MOUNTED AC UNIT: PROVIDE POWER WIRING FEED FROM ROOFTOP CONDENSING UNIT PER MFR. CUT SHEET. REFER TO +18 I I MECHANICAL FOR EXACT LOCATION AND REQUIREMENTS. SEE SHEET E0.3 FOR WIRELESS CONTROLS. t +18" H .� GFC/ I I �' A A-51 ; +44" ----C...4 26. 26. MOTORIZED SHADE CONTROL: EC TO CONNECT TO A SINGLE REMOTE CONTROL HAND HELD DEVICE, THAT WILL BE PLACED IN THE BRANCH MANAGER MOTORIZED SCRIMS 24"+1 A-1G�` �L DP In SEAL 0 PROF OFFICE. COORDINATE EXACT LOCATION WITH PROJECT MANAGER. SO LCD FHP,120V1P2W o ------------ 27. ` E G I N FSs, ��/�', MOTORIZED SCRIMS SPD �r1 f i 27. EC TO PROVIDE 1 1/2" INNERDUCT W/ PULL TAPE IN (1) OF THE (2) 4" CONDUIT FOR TELECOM SERVICE W/ 3 CELL MAXCELL INNERDUCT. ROUTE // ��.� j • FHP 120V1P2W J I A-14 QUAD F OI CONDUIT SLEEVE THRU CEILING WITH PLASTIC BUSHINGS FROM MAIN TELCO BOARD AND DOWN INTO CHASE DATA ROOM. COORDINATE WITH UTILITY. r '` 3 I I ELECTRIC 15,423 3 ,� I� ii _' TSr� INTERCOM/PIN PAD A 3 WATER +18" I Gj r 28. COORDINATE EXACT LOCATION OF ALL POWER AND DATA OUTLETS PRIOR TO ROUGH-IN. SEE SHEET E4.1 FOR FLOOR PLAN AND ELEVATIONS OF DATA H _ r CASH RECYCLER COOLER ROOM. / CBI ` 1 alt 2" CONDUIT GF I ��: • 29. PROVIDE WIREMOLD G4000 WITH DIVIDER FOR POWER AND COMMUNICATIONS MOUNTED ON WALL. RUN ENTIRE LENGTH OF LINE STOPING 12" FROM EACH . ?1,6, U ►'+18"i'IG ���J I PRINTER I S 4ip O WATER HEATER �Rk D Ra�`S 04/14/20 WALL. • jrCQ _ J'i't► 30 v� +44" A+33 �; 1 �i.! J -- �:- it`iil•►ri:;IG r/ a ice' 3KVA,208V2P2W 30. PROVIDE ON/OFF SWITCH WITH OUTLET FOR CONDENSATE PUMP, RECESSED ON WALL FOR AC UNIT. VERIFY EXACT LOCATION WITH PROJECT MANAGER 25 COND. I I 29ilk , ®iRoBIsoN �. . AND MECHANICAL CONTRACTOR PRIOR TO ROUGH-IN. PRINTER n 21 LL ■ A-22 $ PUMP 1 34" H +18 +18 K `� , I cq ENGINEERING, INC 31. PROVIDE (1) 4" SLEEVE AND (1) 2" SLEEVE FOR SECURITY CABLES. ROUTE ABOVE CEILING AND INTO DATA ROOM. CABLE SLEEVES PROVIDED BY I ' A_31 j ' ST 1 w ' 1k►A-2,4 19401 40TH Avg WSurre302.LVNNwoNG, I9NC36 OWNER AND INSTALLED BY G.C. A-55 44 A-39 A-35 (11 <c +38',i, I - TEL:20FrCONTACT:SHAE M4-3343 FAx:Cu8EOo9e 32. ESL TRANSFER SWITCH, VERIFY FINAL LOCATION WITH PROJECT MANAGER/ARCHITECT. A-45A-41 A-37 - - - ISSUE DATE DESCRIPTION INTERCOM/PIN PADI } iv11CR ► +18 y n I I A-21 1$ 19 (TYP PRINTER - - - 33. PROVIDE 1-AVP1 BELDEN 2413E SHIELDED (OR EQUIVALENT) TO IDE MEDIA PLAYER RACK, 1-1/4" CONDUIT STUB UP WITH PULL STRING ABOVE CEILING / ( cDn A-5 I I CO TO OFE RACK IDE CLOSET, AND (1) RECESSED DUPLEX POWER DEDICATED 15A 120VAC. COORDINATE EXACT LOCATION/REQUIREMENT WITH PROJECT 3s = Solt l'■'I1 A , MANAGER AND CHASE AV VENDOR. °� - 34" HT 18" ‘‘ 42+, H -44"o 0. _, '-411111141 r _ -_ - -- o oo •._.f o 34. PROVIDE (1) PORT DATA, (1) PORT AV STRUCTURED CABLING BELDEN 2413E OR EQUIVALENT TO IDE MEDIA PLAYER WITH 1 1/4" CONDUIT TO OFE ��I pi +44"- „_,, .+18:., A• h18" 50711 :.1 ' GFC/ RACK IDE CLOSET AND 1 1/4" CONDUIT TO ACCESSORY STORAGE LOCATION (AVP2). COORDIANTE EXACT LOCATION/REQUIREMENTS WITH PROJECT �; v� �' " 1 ' - !' 18" '1 'ir C/ ; VZ V LI +44"'i' MANAGER AND CHASE AV VENDOR. r4 36. PROVIDE (1) 1" CONDUIT TO ROOF LOCATION FOR FUTURE ANTENNA CABLING. COORDINATE EXACT LOCATION WITH PROJECT MANAGER. CASH VAULT K +68" 4-13-20 PERMIT SUBMISSION 4-3-20 90% SET NOTES: 3-20-20 PLANNING PROJECT INFORMATION BLOCK 1. G.C. & E.0 SHALL COORDINATE ALL WALL OUTLETS HEIGHTS JOB# JPM19010.0 WITH ARCHITECTURAL PLANS AND ELEVATIONS. DATE: 1/20/2020 DRAWN BY: GH 2. G.C. & E.C. SHALL COORDINATE ALL FLOOR BOX LOCATIONS CHECKED BY: PR WITH ARCHITECTURAL SLAB PLANS. MODEL RECEPTACLE NOTE DRAWING STANDARDS v20. 1 SHEET TITLE ELECTRICAL CONTRACTOR TO STICK-ON CIRCUIT LABELS TO ALL RECEPTACLES, INCLUDING CONTROLLED OUTLETS AND DATA OUTLETS. POWER PLAN POWER PLAN SCALE: 1/4" = 1'-0" Ca SHEET NUMBER 0' 4' 8' 16' a -1-1 E2 . O 11 1111 II 11 ELEC.JUNCTION BOX ATM CORE UNIT DATA/SECURITY JUNCTION BOX POWER DOOR OPERATOR SYSTEM OPERATIONLI.I 71:77.- 1 1 ATM'SIDE CAR' rT ,� 1. POWER DOOR OPERATOR PROVIDES POWER TO zy_ POWER, DATA AND SECURITY - - 1 STRIKE CONDUITS CONCEALED1 DOOR ACTIVATION LOCK ELECTRIC STRIKE TO ENSURE STRIKE IS UNLOCKED INTERIOR PARTITION WITHIN WALL FRAMING INTERIOR PARTITION TERMINALS POWER OUTPUT PRIOR TO DOOR OPERATION. in i RELAY ) - 1$ © g" POWER TRANSITION BOX *)O 0 2. THE "ENTER" PUSH PLATE AT THE VESTIBULE SIDE K DD 21OF THE VESTIBULE DOOR AND THE EXIT PUSH �� ATM CORE UNIT / O (-)O 0/ PLATE IN THE LOBBY ACTIVATE THE VESTIBULE /7 SECURITY KEYPAD I ATM 'SIDE CAR' 6 O O 19 DOOR OPERATOR. POWER TRANSITION BOX NEAR PERIMETER 3. DURING BUSINESS HOURS, KEY SWITCH IS TURNED ALARM KEYPAD TO "AUTO", CLOSING THE CIRCUIT AND ALLOWING TERMINATE WALL BASE AT I I BOTH PUSH PLATES TO TRIGGER THE OPERATOR. �. 5,7—FACE OF POWER TRANSITION ' L-�� 4. AFTER BUSINESS HOURS, KEY SWITCH IS TURNED I _ BOX — — TO "OFF" (AS SHOWN), OPENING THE CIRCUIT AND 1 ENTER - EXIT - DISABLING THE POWER OPERATOR TO PREVENT J` PUSH PLATE - PUSH PLATE DAMAGE WHILE THE DOOR IS LOCKED. 4_ ATM CORE UNIT 2U 01 / POWER 1 .'j TRANSITION CAMERA(S)AT ccQ \ BOX(PTB) r9'-0'AFF HOLD OPEN Lu BEHIND ATM CAPTURING AFTER-HOURS �, I 7 - I - Irh ATM VAULTS& CUSTOMERS OPERATOR %,..# I CONTROL REMOTE AUTO Oa 4 KEY SWITCH OFF h . a. . -• ! ATMv3 .OELEC/DATA/SEC . PLAN l o t p e a NOT TO SCALE AUTOMATIC VESTIBULE DOOR CONTROL DIAGRAM t ,. Co W or �'o' NOT TO SCALE , co I. III II in I CI III 11 I '„ 1 I It \ I M 9/4" R16ID OPEN CONDUIT STUB TO a DM W WINDOW OPENING BY ELECTRICAL te CONTRACTOR- TERMINATE FLUSH 0 4 -I r> e N WITH FINISH HEAD- GOORD. STUB IW p —1 POSITION WITH MOTORIZED SHADE (� PRODUCT INFO 0 0 4 ATM /�^ SURFACE-MOUNT .UNCTION BOX N N ELEC, DATA AND I ~,I/I 111TH TO66L.E SWITCH AT EACH COri CI 0. ip•mir .1 Ie TB SECURITY DEVICES � RrF Win., CMOT CONNECTION. ABOVE r, 7 I CONCEALED WITHIN -s DOr� O L - POWER TRANSITION c,, �� Nor SUSPENDED FINISH CEILN6 MZ O 0 -1 BOX mir _ it LLI 1Z U 0i I I I s x I TERMINATE WALL f I r I= ~ ~ 1 MOTORIZED SHADE POWER CABLE CL y 4 fl I BASE AT FACE OF W 4 AND CONNECTIONS BY SHADE I I POWER TRANSITION BOX CONTRACTOR t 1� ® � Z 12 V) II POWERED MECHANICAL ROLLER 0 O 11 z SHADE ENCLOSURE BY OWNER'S O SHADE CONTRACTOR (N.I.C,)- W REFER TO ARCHITECTURAL —I 01 / DRAWIN.SS FOR LOCATIONS a C/) Zr TOALY3 . OELEVATIONS6LAZ1N6 SYSTEM4 H 6YP. BOARD WINDOW JAMB AND ....______> WALL FINISH I Ch ...opWINDOW STOOL (III) TYPICAL POWER OPERATED WINDOW SHADE ARCHITECT/ENGINEER OF RECORD ROUGH IN DETAIL PM DESIGN Architectural Solutions Group 19120 SE 34TH STREET, SUITE 115 VANCOUVER, WA 98683 These drawings and specifications are the confidential and proprietary properly of JP Morgan Chase and shall not be copied or reproduced without written authorization. The contract documents were prepared lor use on this specific site in conjunction with its issue date and ore not suitable for use on a different site or at a later time. Use of these drawings for reference or example on another project requires the services of properly Icensed architects and engineers. Reproduction of the contract documents for reuse on another project is not authorized. SEAL 0 PRQ . �N G I N ti, os 15,423 ? ;:-- ..- a 41: e' 4,4q:c 31, 1,--',0"Rk R RI(OD 04/14/20 le/I RoBisoN ' ENGINEERING, INC 19401 40TH AVE W SUITE 302,LYNNW000,WA 98036 TEL:206-364.3343 FAX:425.8350098 CONTACT:SHANE MCCLURE ISSUE DATE DESCRIPTION 4-13-20 PERMIT SUBMISSION 4-3-20 90% SET 3-20-20 PLANNING PROJECT INFORMATION BLOCK JOB# JPM19010.0 DATE: 1/20/2020 DRAWN BY: GH CHECKED BY: PR MODEL DRAWING STANDARDS v20.1 SHEET TITLE POWER PLAN DETAIL SHEET NUMBER E2 . 1 GENERAL NOTES: i <EYED N C TES il 1. THERE SHOULD BE NO EXPOSED CONDUIT AT ROOF. 1. PROVIDE WEATHER PROOF J-BOX AND 3/4" SEALTITE CONDUIT FOR MECHANICAL CONTROLS 2. ALL CONDUIT TO PENETRATE THROUGH ROOF WITH APPROPIATE PIPE SLEEVE AND BOOT ASSEMBLY. CONNECTION. COORDINATE WITH MECHANICAL CONTROLS CONTRACTOR. 3. ALL "NEW" ROOF PENETRATIONS SHALL BE APPROVED BY LANDLORD PRIOR TO WORK BEING DONE. 2. PROVIDE POWER TO FAN COIL UNIT BELOW FROM CONDENSING UNIT PER MANUFACTURER REQUIREMENTS. 1111 4. SERVICE RECEPTACLES SHALL BE EXTRA DUTY, WEATHER RESISTANT, GFCI, AND WEATHER PROOF. 5. CONTRACTOR SHALL COORDINATE ALL MECHANICAL EQUIPMENT WITH MECHANICAL PLANS AND MECHANICAL VENDOR. PROVIDE ALL CONDUIT, WIRES, AND BREAKERS AS REQUIRED. InI 0 LL w ly D a OC �B (A w ct r CO W % I I # (0 I- in H ❑ I- =M a ILW L- o a J ix N o a LN v 0 - T, MN 0 a, v ct• 11 - - - - - - - - - I O CI Z 0 O RTU-1 16.93KVA,208V3P3W it la rg V ❑ DP-1,3,5 W 4 Q I\7____-_.6..---40-3/4"C,3#6,#10G t 1� li > WP Z0 N 11 I GFCI 0 — Z0 ' 0 AJ DP-23 W r Ca Z aN CU-2 aII- - 2.29KVA,2O8V2P2W Z (11) CU-1 2.29KVA,208V2P2W i LI) 1 1 AWP 1 -13:11h I P WP , CONDENSING PLATFORM UNIT F 323 , • I P J 3OAS 0 j 30AS 15AF 5AF ARCHITECT/ ENGINEER OF RECORD DP-13,15 2 3/4"C. A %J i DP-17,19 PAM RTU-2 3/4"C. DESIGN i► 16.93KVA,208V3P3W �.,.. Architectural I1 SPO • DP-7,9,11 Solutions Group 3/4"C,3#6,#10G r - - C2-H � I w>a 19120 SE 34TH STREET, SUITE 115 IV 1 VANCOUVER, WA 98683 I HpI DP-21These Cr and specifications ore the confidential andpro proprietaryproperty DP-23 EF-1 of JP Morgan Chase and shalt not be copied or reproduced without written authorization. The contract documents were prepared for use on this specific FHP,120V1 P2W site in conjunction with its issue date and are not suitable for use on a different site or ata bier time. Use of these drawings for reference ar example on 1 another project requires the services of property icensed architects and engineers. Reproduction of the contract documents for reuse on another L J project is not authored. SEAL 0 PROFF I ' c GINEFSS/o 2 15,423 0. d[•: e. 4/ '14C• 31, '1. �pZ R( D Rd�\- 04/14/20 _ _ RoBIsoN j ENGINEERING, INC _) 19401 40TH AVE W SurrE 302,LYNNWOOD,WA 98036 TEL:206-364-3343 FAx:425-8350098 CONTACT:SHANE MCCLURE • ISSUE DATE DESCRIPTION l — 4 . 00F POWER PLANCi D 4-3-20 90% SET 4-13-20 PERMIT SUBMISSION SCALE: 1/4" = 1'-O" 3-20-20 PLANNING 0' 4' 8' 16' PROJECT INFORMATION BLOCK JOB# JPM19010.0 DATE: 1/20/2020 DRAWN BY: GH CHECKED BY: PR MODEL DRAWING STANDARDS v20. 1 SHEET TITLE ROOF POWER PLAN SHEET NUMBER E2 . 2 3 A DP 1111lel ROOM VOLTS 208Y/120V 3P 4W AIC 22,000 ROOM VOLTS 208Y/120V 3P 4W AIC 22,000 ROOM VOLTS 208Y/120V 3P 4W AIC 42,000 MOUNTING RECESSED BUS AMPS 200 MAIN BKR 150 MOUNTING FLUSH BUS AMPS 200 MAIN BKR 200 MOUNTING RECESSED BUS AMPS 200 MAIN BKR MLO FED FROM A NEUTRAL 100% LUGS STANDARD FED FROM MSB NEUTRAL 100% LUGS STANDARD FED FROM MSB NEUTRAL 100% LUGS STANDARD111 NOTE NOTE ISO GND BUS NOTE CKT CKT LOAD KVA CKT CKT LOAD KVA CKT CKT LOAD KVA CKT CKT LOAD KVA CKT CKT LOAD KVA CKT CKT LOAD KVA # BKR CIRCUIT DESCRIPTION A B C # BKR CIRCUIT DESCRIPTION A B C # BKR CIRCUIT DESCRIPTION A B C # BKR CIRCUIT DESCRIPTION A B C # BKR CIRCUIT DESCRIPTION A B C # BKR CIRCUIT DESCRIPTION A B C 1 20/1 LOBBY & VESTIBULE LIGHTING 0.741 2 20/1 FACADE SIGN 1.2 1 20/1 ILLUMINATED SURROUND, RECEPTACLE 0.702 2 20/2 WATER HEATER 1.5 1 40/3 R1U-1 5.64 2 30/3 SURGE PROTECTOR 0.067 tin 3 20/1 NIGHT LIGHTING 0.19 4 20/1 FACADE SIGN 1.2 3 20/1 AHD RECEPTACLE 0.36 4 I 1.5 3 I 5.64 4 1 0.067 5 20/1 OFFICE UGHTING 0.192 6 20/1 FACADE SIGN 1.2 5 20/1 RECEPTACLE 0.54 6 20/1 DRIVE-THRU ATM, DRIVE-THRU ATM 1.5 5 I 5.64 6 I 0.067 7 20/1 BOH LIGHTING 0.799 8 20/1 SPARE 0 TOPPER 7 50/3 RTU-2 5.64 8 20/1 SPARE 0 9 20/1 EXTERIOR LIGHTING 0.724 10 20/1 SPARE 0 7 20/1 OFFICE RECEPTACLE 0.72 8 20/1 SPARE 0 9 I 5.64 10 20/1 SPARE 0 11 20/1 SPARE 0 12 20/1 SPARE 0 9 20/1 OFFICE CONTROLLED RECEPTACLE 0.36 10 20/1 RECEPTACLE 0.72 11 I 5.64 12 20/1 SPARE 0 13 20/1 SPARE 0 14 20/1 SPARE 0 11 20/1 OFFICE RECEPTACLE 0.72 12 20/1 RECEPTACLE 0.36 13 15/2 CU-1 1.14 14 20/1 SPARE 0 15 20/1 SPARE 0 16 20/1 SPARE 0 13 20/1 OFFICE CONTROLLED RECEPTACLE 0.36 14 20/1 DRINKING FOUNTAIN, RECEPTACLE 0.36 15 I 1.14 16 20/1 SPARE 0 I 17 20/1 SPARE 0 18 20/1 SPARE 0 15 15/1 MOTORIZED SHADE 0.3 16 20/1 MIRCOWAVE, RECEPTACLE 1.54 17 15/2 CU-2 1.14 18 20/1 SPARE 0 19 20/1 SPARE 0 20 20/1 SPARE 0 17 20/1 RECEPTACLE 0.3 18 20/1 REFRIGERATOR 0.5 19 I 1.14 20 20/1 SPARE 0 21 20/1 SPARE 0 22 20/1 SPARE 0 19 20/1 FLOOR BOX 0.36 20 20/1 RECEPTACLE 0.36 21 20/1 EF-1 0.1 22 20/1 SPARE 0 23 20/1 SPARE 0 24 20/1 SPARE 0 21 20/1 PRINTER, RECEPTACLE 1.04 22 20/1 RECEPTACLE 0.18 23 20/1 RECEPTACLE 0.72 24 20/1 SPARE 0 2 25 20/1 SPARE 0 26 20/1 SPARE 0 23 20/1 FLOOR BOX 1.08 24 30/2 TWIST LOCK - L14-30 1.75 25 20/1 SPARE 0 26 20/1 SPARE 0 0 27 20/1 SPARE 0 28 20/1 SPARE 0 25 20/1 FLOOR BOX 0.36 26 I 1.75 27 20/1 SPARE 0 28 20/1 SPARE 0 cr 29 20/1 SPARE 0 30 20/1 SPARE 0 27 20/1 eATM 0.54 28 30/2 TWIST LOCK - L14-30 1.75 29 20/1 SPARE 0 30 20/1 SPARE 0 Lli a. 31 20/1 SPARE 0 32 20/1 SPARE 0 29 20/1 eATM 0.54 30 I 1.75 31 20/1 SPARE 0 32 20/1 SPARE 0 I. 33 20/1 SPARE 0 34 20/1 SPARE 0 31 20/1 PRINTER 0.5 32 20/1 MUSAK 0.2 33 20/1 SPARE 0 34 20/1 SPARE 0 35 20/1 SPARE 0 36 20/1 SPARE 0 33 20/1 PRINTER 0.5 34 20/1 RECEPTACLE 0.18 35 20/1 SPARE 0 36 20/1 SPARE 0 37 20/1 SPARE 0 38 20/1 SPARE 0 35 20/1 RECEPTACLE 0.36 36 20/1 TWIST LOCK - L5-20R 0.54 37 20/3 SPARE 0 38 20/3 SPARE 0 39 20/1 SPARE 0 40 20/1 SPARE 0 37 20/1 INTERCOM/PIN PAD 0.18 38 20/1 TWIST LOCK - L5-20R 0.54 39 I 0 40 I 0 41 20/1 SPARE 0 42 20/1 SPARE 0 39 20/1 CASH RECYCLER 0.36 40 20/1 RECEPTACLE 0.18 41 1 0 42 I 0 V 41 20/1 RECEPTACLE 0.36 42 20/1 RECEPTACLE 0.18 t�� TOTAL CONNECTED KVA BY PHASE 2.74 2.11 1.39 43 20/1 MOTORIZED SCRIMS 0.2 44 20/1 RECEPTACLE 0.36 TOTAL CONNECTED KVA BY PHASE 13.6 12.6 13.2 r TOTAL CONNECTED AMPS BY PHASE 22.8 17.6 11.6 45 20/1 INTERCOM/PIN PAD 0.18 46 20/1 RECEPTACLE 0.36 TOTAL CONNECTED AMPS BY PHASE 114 105 110 00 LLI 47 20/1 RECEPTACLE 0.3 48 20/1 SPARE 0 mii CONN KVA CALC KVA CONN KVA CALC KVA 49 20/1 SPARE 0 50 20/1 SPARE 0 CONN KVA CALC KVA CONN KVA CALC KVA W im ❑ LIGHTING 6.25 7.81 (125%) CONTINUOUS 0 0 (125%) 51 20/1 RECEPTACLE 0.3 52 20/1 SPARE 0 LIGHTING 0 0 (125%) CONTINUOUS 0 0 (125%) If) Im LARGEST MOTOR 0 0 (N/A) HEATING 0 0 (N/A) 53 20/1 SPARE 0 54 20/1 RECEPTACLE 0.18 LARGEST MOTOR 16.9 21.2 (125%) HEATING 0 0 (N/A) el OTHER MOTORS 0 0 (100%) COOLING 0 0 (N/A) 55 20/1 CONDENSATE PUMP 0.18 56 150/3 PANEL B 2.74 OTHER MOTORS 21.6 21.6 (100%) COOLING 0 0 (N/A) RECEPTACLES 0 0 (50%>10) NONCONTINUOUS 0 0 (100%) 57 20/1 SPARE 0 58 I 2.11 RECEPTACLES 0.92 0.92 (50%>10) NONCONTINUOUS 0 0 (100%) KITCHEN EQUIP 0 0 (N/A) DIVERSE 0 0 (N/A) 59 20/1 SPARE 0 60 I 1.39 KITCHEN EQUIP 0 0 (N/A) DIVERSE 0 0 (N/A) O a -I IIS 01 METERBANK 0 0 (0%) METERED DEMAND 0 0 (125%) TOTAL CONNECTED KVA BY PHASE 11.4 12.5 12.4 METERBANK 0 0 (0%) METERED DEMAND 0 0 (125%) ELI 0 CV TOTAL KVA 6.25 7.81 TOTAL CONN CTED AMPS Y PHA TOTAL KVA 39.5 43.7 0 E B SE 94.8 104 103 N N BALANCED 3-PHASE AMPS 21.7 BALANCED 3-PHASE AMPS 121 O 13. J ct• CONN KVA CALC KVA CONN KVA CALC KVA CO J W LIGHTING 6.25 7.81 (125%) CONTINUOUS 0 0 (125%) M Z 0 0 0 LARGEST MOTOR 3 3.75 (125%) HEATING 0 0 (N/A) FAULT CURRENT SCHEDULE OTHER MOTORS 0.5 0.5 (100%) COOLING 0 0 (N/A) ; M V 0 CONTROL FUNCTION DEFINITIONS RECEPTACLES 24.9 17.5 (50%>10) NONCONTINUOUS 1.5 1.5 (100%) V) Ce KITCHEN EQUIP 0 0 (N/A) DIVERSE 0 0 (N/A) DEVICE FAULT AIC FED FROM TOTAL O ENERGIZE AT STORE OPENING (ENABLING OF LOCAL CONTROLS). METERBANK 0 0 (0%) METERED DEMAND 0 0 (1 25%) RATING DEVICE FAULT MOTOR am w 04 < DE-ENERGIZE AT STORE CLOSING (DISABLING OF LOCAL CONTROLS). FAULTn> Q N v TOTAL KVA 36.2 31 Z 1111111.. O ENERGIZE AT DUSK VIA INPUT FROM PHOTOCELL BALANCED 3-PHASE AMPS 86.1DP 12,344 42,000 MSB 30,000 467 ~ DE-ENERGIZE AT DAWN, VIA INPUT FROM PHOTOCELL. A 11,116 22,000 DP 11,877 386 Z �O 11 la A O PROVIDE "HACR" CIRCUIT BREAKER. B 10,926 22,000 DP 11,877 367 a N 03 ii 4 PROVIDE LOCKABLE DEVICE ON CIRCUIT BREAKER Z O MULTI-WIRE aIM O SIMULTANEOUSLY Y DISCONNECH T ALL OUNDERGROUNVIDE (3) LDEDE RCONDUCTORS FEEDER SCHEDULE 1 Cl)EAKER TO O6 SWITCH RATED FOR "NIGHT-LIGHTS" . 0 FEEDER CONDUIT AND FEEDER FEEDING 0 LIGHTING CIRCUITS CONTROLLED BY LIGHTING CONTROL. AMPS THESE DEVICES 150 1-1/2"C,3#1/0,#1/ON,#6G B 200 2"C,3#3/0,#3/0N,#6G DP ARCHITECT/ENGINEER OF RECORD NOTES: 1. CONTRACTOR SHALL PROVIDE COMPLIANCE WITH NEC 110.26 200 2"C,3#3/0,#3/0N,#6G,#61G A "SPACES ABOUT ELECTRICAL EQUIPMENT" 2. CONTRACTOR SHALL PROVIDE COMPLIANCE WITH NEC 408.4 SIZING METHOD: COPPER, 6ITC #12 THROUGH #1, 75'C 1/0 AND ABOVE Pititil "CIRCUIT DIRECTORY OR CIRCUIT IDENTIFICATION" 3. PROVIDE ARC FLASH WARNING LABELS PER NEC 110.16. 4. ALL CONDUCTORS SHALL BE TYPE THHN, SOLID COPPER, UNLESS DESIGN OTHERWISE NOTED. 5. ELECTRICAL CONTRACTOR SHALL ON DAY ONE ON THE PROJECT, OPEN THE EXISTING ELECTRICAL GEAR, INSPECT INTERNAL Architectural CONFIGURATION AND IMMEDIATELY NOTIFY ENGINEER IF CONDITIONS Solutions Group ARE NOT AS SHOWN IN THE ONE-LINE DIAGRAM OR IF THE DESIGN IS NOT WORKABLE. CONTAC: ROBISON ENGINEERING 206-364-3343. 19120 E 34TH STREET, SUITE 115 VANCOUVER, WA 98683 These drawings and specifications are the confidential and proprietary Property of JP Morgan Chase and shall not be copied or reproduced without written authorization. The contract documents were prepared for use on this specific site in conjunction with its issue date and are not suitable for use on a different PANELS NOTE: site or at a later time. Use at these drawings tor reference or example on another project requires the services of properly Rcensed architects and engineers. Reproduction of the contract documents far reuse on another project is not authorized. EC TO STICK-ON LABEL TO ALL BREAKERS. BLANK BREAKERS LABEL SPARE, ON EACH PANEL. SEAL , ED PROF-F ANG I NFFSS% EQUIPMENT NOTES: 15,423 THE ENTIRE ELECTRICAL SYSTEM SHALL BE FULLY RATED, NOT SERIES RATED Oec. 31, '1OO' � Q).Rk O RGO 04/14/20 NOTE TO ELECTRICAL CONTRACTOR: ROBISON ENGINEERING, INC ALL MAIN SWITCHBOARD/DISTRIBUTION AND PANEL BOARDS ON THE 1 9401 40TH AVE W SUITE 302,LYNNWpOD,WA 98036 PROJECT SHALL BE SUPPLIED AND ORDERED THROUGH THE TEL:206-364-3343 FAX:425-835-0098 FOLLOWING SUPPLIER ONLY: CONTACT:SHANE MC ,LURE JOE FERGUSON ISSUE DATE DESCRIPTION INDUSTRIAL CONTROL PHONE: (562) 692-0228 EXISTING MAIN SWITCHBOARD EMAIL: JOE@FERGIEMAN.COM i ONE- LINE DI A G R A tv NOTES 120/208V 3P 4W 400A 1. SURGE PROTECTIVE DEVICE SEE SHEET E4.0 DETAIL #1. ALL GROUNDING TO BE ROUTED BACK TO MAIN PANEL INCLUDING LOW VOLTAGE. 2. CONTRACTOR SHALL PROVIDE ARC FLASH WARNING LABELS FOR THIS EQUIPMENT. cy-200A 3. PHOTOCELL, SLEEVE WALL AND SEAL WATERTIGHT. 0200/3 1 4. SEE LIGHTING BMS DIAGRAM ON E0.1, p 4-13-20 PERMIT SUBMISSION 200/3 � HsPD 4-3-20 90% SET A� i) 1 150A 3-20-20 PLANNING PROJECT INFORMATION BLOCK -iSPD 150/3 JOB# JPM19010.0 EXISTING UTILITY ) DATE 1/20/2020 200 (N) PANEL A V V DRAWN BY: GH 208/120V 3P 4W CHECKED BY: PR 225A o LC • MODEL (N) PANEL DP AEXISTING & NEW 208/120V 3P 4W 225A DRAWING STANDARDS v20. 1 ONE-LINE DIAGRAMSHEETTETLE 1201208V,3 PHASE,4 WIRE 2 208/120V 3P 4W ONE-LINE DIAGRAM 225A A N D APANEL SCHEDULES SHEET NUMBER E3 . 0 il VOLTAGE DROP SCHEDULE111 DEVICE FEEDER BRANCH CIRCUIT TOTAL VOLTAGE DROP in VOLTAGE DROP WIRE MAX VOLTAGE DROP WIRE SIZE SIZE A 0.88% #3/0 2.9% (CKT 6) #10 3.77% A-1: 0.53% #12 A-3: 0.31% #12 A-5: 0.65% #12 A-7: 1.12% #12I A-9: 0.35% #10 A-11: 1.04% #12 0 w A-13: 0.54% #12 0 i A-15: 0.41% #12 a¢. w A-17: 0.35% #12 a A-19: 0.39% #12 A-21: 1.25% #12 A-23: 1.33% #12 A-25: 0.22% #12 V V` omili A-27: 0.31% #12 CO LLI A-29: 0.34% #12 w inin I= A-31: 0.43% #12 in ❑ I- w A-33: 0.4% #12 CI A-35: 0.2% #12 0. 0. Wiii A-37: 0.1% #12 0 4 .1 ce CO A-39: 0.21% #12 0 u N A-41: 0.24% 12 # NO � JQ, A-43: 0.12% #12 J Cle A-45: 0.13% #12 M Z CI O 0 A-47: 0.18% #12 k W rt V ❑ A-51: 0.24% #12 H Ce A-55: 0.22% #12 0W a Q A-2 4: 0.48% #12 V Q 2 A-6: 2.9% #10 go Z Q ~ A-10: 0.39% #12 o A-12: 0.5% #12 la -I 4 r 01 A-14: 0.19% #12 Cn4 IZ i A-16: 0.89% #12 CO A-18: 0.34% #12 Z A-20: 0.13% #12 (111) A-22: 0.09% #12 A-24,26: 1.08% #10 A-28,30: 1.07% #10 ARCHITECT/ENGINEER OF RECORD A-32: 0.29% #12 A-34: 0.27% #12 Pm A-36: 0.79% #12 A-38: 0.79% #12 DESIGN A-40: 0.25% #12 . ...:,..... , Architectural A-42: 0.25% #12 Solutions Group A-44: 0.56% #12 A-46: 0.56% #12 19120 SE 34TH STREET, SUITE 115 A-54: 0.47% #10 VANCOUVER, WA 98683 These drawings and speatcations are the confidential and propnelary property B 0.9% #1/0 1.05% (CKT 6) TO 1.95% of JP Morgan Chase and shall not be copied ow reproduced without woitten authorization. The contract documents were prepared for use on this specific site in conjunction with its issue date and ore not suitable for use on a different 8-1: 0.62% #1 a site or at a later time. Use of these drawings for reference or example on U /o another project requires the services of properly licensed architects and o engineers. Reproduction of the contract documents for reuse on another 8-3: 0.19% #10 project is not outhorized. 6-5: 0.22% #10 8-7: 0.51% #10 SEAL i Ep PROFeS B-9: 0.55% #10 ANG I NfF,p `rio 15,423 B-2: 0.72% #10 r'-- .- B-4: B-4: 0.21% #12 AO: ., B-6: 1.05% #10 0 0 "tiPc• 31 `P'(-, R �S DP 1.22% #3/0 1.15% (CKT 1,3,5) #6 2.37% k 0 IR 04/14/20 DP-1,3,5: 1.15% #6 DP-7,9,11: 0.78% #6 ROBISON DP-13,15: 0.77% #12 ENGINEERING, INC 19401 40TH AVE W SUITE 302,LYNNWOOD.WA 98036 DP-17,19: 0.72% #12 TEL:206-364-3343 FAX:425-835-0098 CONTACT:SHANE MCCLURE DP-21: 0.04% #12 ISSUE DATE DESCRIPTION DP-23: 0.79% #12 DP-2,4,6: 0% #10 NOTE: THE MAXIMUM COMBINED VOLTAGE DROP ON BOTH INSTALLED FEEDER CONDUCTORS AND BRANCH CIRCUIT CONDUCTORS TO THE FARTHEST CONNECTED LOAD OR OUTLET SHALL NOT EXCEED 5 PERCENT. VOLTAGE DROP CALCULATIO \ PERFORMED WITH " DESIGN V A S T E P O G A M " 4-13-20 PERMIT SUBMISSION www. designmaster.biz 4-3-20 90% SET 3-20-20 PLANNING PROJECT INFORMATION BLOCK JOB# JPM19010.0 DATE: 1/20/2020 DRAWN BY: GH CHECKED BY: PR MODEL DRAWING STANDARDS v20. 1 SHEET TITLE VOLTAGE DROP CALCULATIONS SHEET NUMBER E3 . 1 l'p .. IY t' CilLnill0 u- a:w w w w iii ASTMST oni, AM 7 COaro A5.4.1 w im f F., 1 ,, f Fr., 1, lin Im 1. 2 _____)r- r, II 1 � M L.' Orr_ r rrrrrr� �i r IMO o. as W SOFFIT EXTENDS AT LINEAR RECESSED LIGHT FIXTURE I 0 4 ce N II PROTOTYPES TELLER BRG INTERCOM III \ IJJ �RECESSED LIGHT FIXTURE 0 0 LL f;,.1 SPEAKER \ 4 c' 8 I� NOTES CO 1:1 °- vjJ IX SOFFIT EXTENDS AT LINEAR I— A5.4.1 I A1524 1. CONNECT SPD TO BREAKER AS M Z 0 O 0 PROTOTYPES FOLLOWS:2P30 FOR 1 PHASE `_ 3P30 FOR 3 PHASE *k WI rg V ❑ 2. RELOCATE BREAKER IN PANEL AS in C/ U NEUTRAL NECESSARY TO PROVIDE THE SHORTEST k 8U5 WIRE LENGTH TO SPD. IL W a t r‘*< BULLET-RESISTANT GLAZING �/� WHERE REQUIRED SUPPORTED SECURITY CAMERA BY ur r-1 BULLET-RESISTANT GLAZING Q o 3. DIRECT CONNECTION TO BUS IS NOT Z �/ AT WALLS OWNER'S SECURITY VENDOR WHERE REQUIRED SUPPORTED u m PERMITTED. Cil F 2-t - i AT WALLS a O oe Z o J • u 0 4. USE A CHASE NIPPLE CONNECTION VIA DEAL TRAY AT B.R.G. p m KNOCKOUT. W �` TELLER BRG INTERCOM I I LJ __ \ =, n LJ _ INSTALLATIONS a /NEUTRAL A 4 N MICROPHONE I I /� I m 5. USE #10 AWG OR LARGER In Z SECURITY CAMERA BY I -�— ! I �- l u'' CONDUCTORS. �__--'I _� I�i� SPD4 OWNER'S SECURITY VENDOR _ _ .�' I _ - -o -- - - ��� I �- 2"DIAM.PVC CONDUIT BY . 6. LIMIT WIRE LENGTH TO 18" OR LESS. CA I 1 STEEI_CASE MANUAL Z DEAL TRAY AT B.R.G. ( / 3'-9 MAX �� 1.-10:-'-'---, -I0� `~ ' 1 -� G.C.FOR COIN DISPENSER TRANSACTION MILLWORK INSTALLATIONS ./l ,� (OBSTRUCTEDIG(t' I�I 1 ��' CABLE TO CASH RECYCLER 1, PHASES 7. KEEP WIRE FREE OF ANY SHARP BENDS. __.i__- FORWARcrotACH)... I4'"V/////////////, ////F 0 SECURE WITH PERIMETER �� GROUND A,B,C STEELCASE MANUAL ,' - I iI it SEALANT BEAD TO GYP.BD. I.P. ~~—BULLET-RESISTANT PANEL 8. SPD TO BE MODULAR, UL 1449 3RD TRANSACTION MILLWORK— ,'/ --f------ _-Lt._ EACH END �' Ia. s•Jr r-r I / ��-. WHERE REQUIRED EDITION LISTED, !I li • > -,,,,,/,..„,,,,,,,,,,,,,/,,,, `�iix I __� OPENING IN MILLWORK w / GROMMET wI DOUG MOCKET 9. 100 KA PER PHASE, 600V CLAMPING. l I / PANEL BY FURNITURE MFR. ARCHITECT/ENGINEER OF RECORD BULLET-RESISTANT PANEL ti ' _ R�i/�r I 1 l , r / 'BRKIT 1'WIRE MGMT.KIT Y - 4'-$"±(VERIFY WI MILLWORK OPENING) / I 1 = I S t / -. WHERE REQUIRED _ L rte---- 1 I >< 1 0 3`v" , r �, ��. �__w_ �� - — ` (1/I 1- z ---r.," I�(' %t = / % BULLET RESISTANT PANEL -r-- - �� — // II , 16 I( \ III A I c)j I— — — — —' - to WHERE REQUIRED ��:�,11�. 1� f /r '�� , % II I 10 1 Iii U = iv1 / / , , Pm ,� I IgE �" I \ O I ` I I % II 1 I>< I III O co - I c -. u,t7 x + �` 1 2E. / -ELEC I DATA/SECURITY SYSTEM ELEC I DATA f SECURITY$YSTE >1 0 \ / / spa v bT..I'....--- 0`X11�I I * % �g <a I I o I �/ % JUNCTION BOXES WITH FLEXIBLE JUNCTION BOXES WITH FLEXIBLEr___- IS 1 / �,.•^•y I , V / �-__ I I b, / / i--. `I r I I CONDUIT WHIPS TO JUNCTION CONDUIT WHIPS TO JUNCTION-- + / j ILL I ( \ ; /_ BOXES MOUNTED AS REQUIRED DES I G N BOXES MOUNTED AS REQUIRED.;TV'1 _4'I r I I ` I 1 I „ I I 11,1 I j TO BACKSIDE OF TELLER LINE ! �L TT o / 1 41 I I , r / TO BACKSIDE OF TELLER LINE��7'; L - — — J `/ % I ;, I I r>r L J f/ -4— MILLWORK PANEL `.' ' -� 3'11- ` 3'"�' 1 I I '00i MILLWORK PANEL �`�/` ,. - _r f �r 'T � } I 1 — Architectural . .`,,f_ 1 1 yam,, l ��= +r• II q r — J i r • �_a�,, i � . — nij ` _ iltj— - - • s Solutions Group 19120 SE 34TH STREET, SUITE 1 15 VANCOUVER, WA 98683 I TELLER SECTION AT AST AND MST SCALE 2 SPD PANELBOARD SCHEMATIC SCALE 1 These drawings and5pandshaHnotare the cpedrreprand ucedwi without of JP Morgan Chase and shah not be copied a reproduced ielaty written NTS I NTS authorization. The contract documents were prepared to use on this specific site in conjunction with its issue date and are not suitable for use on a different site or al a later time. Use of these drawings for reference or example on another protect requires the services of property licensed architects and engineers. Reproduction of the contract documents for reuse on another project is not authorized. SEAL— . . _.._.. _..... _ — — I - - - -- c_p P Ropy. 4000 Series Raceway System Layout PROVIDE WIREMOLD G4000 WITH POWER/DATA AS OUTLINED BELOW !� NG I NE�,`sS) 4010DF0 2„ P 1 TELLER STATION : (2) DUPLEX RECEPTACLE l ' • 15,423 ® , il I 11 4075DA (2) DATA/VOICE ao17 �1_ 40108 (1) HOLDUP BUTTON asou 1 ' ��: •• 10 4 , 4b.. ill 5785 ' 11 ec. 31' -IR WINIV CASH RECYCLER: 1) DUPLEX RECEPTACLE '�S9Rk �`S�� (1) DATA D. RO 04/14/20 4017F0 qilM 4047RH 111111 40478x 4047RF Nil 1[0), 40150 5507RJ FoBISc'r1 4011 4047Jx PROVIDE RACEWAY FOR ROUTING OF SECURITY CABLE. (SECURITY 4018 4050 VENDOR TO PULL CABLE FOR HOLDUP BUTTONS AND AND TCD ENGINEERING, INC PROTECTION PACKAGES. ) 19401 40TH AvE W SurrE 302,t-YNNWOOD,WA 98036 ii:t1NOTE: DIMENSIONS ARE APPROXIMATE. ADJUST PLACEMENT OF TEL:206-364-3343 FAx:425-6350098 CONTACT:SHANE MCCLURE .�__ 401sFo DEVICES AFTER EQUIPMENT IS INSTALLED IF NECESSARY. ISSUE DATE DESCRIPTION NOTE:Illustration is for showing product applications only. 4000 Series Racewa Ordering Information Catalog No./Item Description/Specifications Catalog No./Item Description/Specifications V4000B-10 Base-.050" galvanized steel V4000C315 31.5"(775mm)Pre-Cut Cover-. p G4000B-10 Packed five 10' (3.050m) G4000C315 For mounting devices on 36" lengths per carton. Base has (915mm)centers with 4007, - / two 9/32"pc (7.1 mm)diameter 4046,4047,4048,and 4050 Series 14" KOs on centers of approximately 44, plates.Spacing will be 36 1/4"(mm) lyl,,,,,,1 18" (457mm)throughout. (121mm) with 4050. I 4 3/0 (121mm) G4000D Divider-.040" (1.0mm)galvanized V4000C Cover-.040" (1.0mm)galvanized steel.One side painted buff G4000C steel. Packed ten 5'(1.5mm) primer to provide identification 4-13-20 PERMIT SUBMISSION 1Th lengths per carton. � of compartments.`Packed ten 5' I o 4314' 1 17132, / (1.5m) lengths(50' (15.2m))per 4-3-20 90/o SET (121mm) 17132 carton. 1 V40000075 7.5"(191 mm)Pre-Cut Cover-For - NOTE: 4001 DA Divider Clips (---- 0 3-20-20 PLANNING G40000075 mounting devices on 12" (305mm) are required to hold � _ centers with 4007,4046,4047, divider in place. J _ ( 1 PROJECT I N E RMA N BLOCK JOB# JPM19010.0 ' 4048,and 4050 Series plates. rya') Spacing will be 12 1/4" (311 mm) 1WE-S Spray Paint-Used for touching O + o DATE: 1/20/2020 with 4050. GWE-S up large areas.Contains 12 oz. I 1 DRAWN BY: GH of paint. I I — CHECKED BY: PR V4000C135 13.5"(343mm)Pre-Cut Cover-For NOTE: Can only be shipped via 04000C135 mounting devices on 18" (457mm) ... ground transportation. O centers with 4007, 4046,4047, I I MODEL iii 4048,and 4050 Series plates. IWE-P GWE-P Touch Up Paint Pen-Used for o p Al I I • p p 4314' ' Spacing will be 18 1/4" (464mm) touching up small areas. ®� " (121mm) with 4050. Contains 0.3 oz. of paint. -1 -- . DRAWING STANDARDS v20. l ® V4000C195 19.5"(496mm)Pre-Gut Cover- i SHEET TITLE O G40000195 For mounting devices on 24" . . (610mm)centers with 4007, Co 4046,4047,4048, and 4050 Series 43/4• ' plates.Spacing will be 24 1/4" TELLER POWER 1121mm) (616mm)with 4050. i Download this product's PEP ecopassporta DETAILS '- environmental product declaration at - �` PASS Thg' lar n onfsrrn with SO140255end POWER VOICE/DATA f PORT-- 14040 and isinalignmrnnst EN,5804. OUTLET OUTLET SHEET NUMBER 2 WIRE MOLD DETAIL AT TELLER LINE FIELD VERIFY EXACT LOCATION SCALE 3 NTS E4 . 0 DATA ROOM DIAGRAM KEY E-1 ELEC PANEL: MAIN (NOT IN DATA ROOM) E-2 ELEC. PANEL: DISTRIBUTION (NOT IN DATA ROOM) il E-3 ELEC. PANEL: DISTRIBUTION (NOT IN DATA ROOM) E-4 SURGE PROTECTION DEVICE (NOT IN DATA ROOM) E-5 120V/20A ELEC. OUTLET- DUPLEX OR QUADRUPLEX AS SHOWN- RECESSED OR SURF. MTD. LII E-6 (2) DEDICATED 208V/30A ELEC OUTLETS - TWIST-LOCK, NEMA L14-30 E-7 (2) DEDICATED 120V/20A ELEC OUTLETS - TWIST-LOCK, NEMA L5-20R I E-8 IN-FLOOR CONDUIT TERMINATIONS- REFER TO ELECTRICAL DRAWINGS E-9 MANUAL TOGGLE LIGHT SWITCH a UJ CC Q a UJ CC T-1 TELECOM CARRIER #1 : 36"W X 36"H a_ T-2 TELECOM CARRIER #2: 36"W X 36"H 1 " CONDUIT TO ROOF LOCATION FOR FUTURE ANTENNA T-3 CABLING. Tin (2) 4" CONDUITS FOR TELECOM SERVICE W/ 3-CELL r t^ T-4 CO W MAXCELL INNERDUCT- COORD. LOCN. WI UTILITY im in ImCI im ite D-1 DATA RACK / CABLE TRAY COMPONENTS M a W >- D-2 Q Q(2) 4" DATA CABLE SLEEVES PROVIDED BY OWNER AND J l>,C CO N INSTALLED BY G.C. O w 0aLA- [V LOCATE DATA ROOM CLG. HGT. 1'-O" 0 a J S-1 SECURITY EQUIPMENT: 48"W x 66"H MIN. ABOVE (1--3) CO J Ce III LJ LJ 4` ADJACENT ROOM CLG. TO ENSURE U CI Z CI O 0 S-2 2" SECURITY CABLE SLEEVE PROVIDED BY OWNER AND ®® (a2) SLEEVES ARE W 2 0 INSTALLED BY G.C. UNOBSTRUCTED T w V ce 4" SECURITY CABLE SLEEVE PROVIDED BY OWNER AND ; E-s .)11 I1I 1 I f l T Ii N S-3 DED. ,_�. I 4 INSTALLED BY G.C. DED. -:- DED. jjl l�f l 3 t 0 to) 2 DED. . - !r� 1 1 C-CHANNELO QUNISTRUT w/ \ C-CHANNEL �' : �I oFAN COIL UNIT AND CONDENSATE PUMP - PROVIDE SIDE--MOUNTED \ uNISTRUT w/ ki. W .■, 11DEDICATED SYSTEM THAT MEETS ROOM TEMPERATURE OUTLETS AT \ SIDE-MOUNTED `�° Q N DATA RACKS - \ '' _ M-1 SEE ELEC. PLAN \ OUTLETS AT 111 l I [�.I� I �' Z AND HUMIDITY REQUIREMENTS IN JPMC RETAIL \ DATA RACKS - I ;� � ii— u IM STRUCTURED CABLING STANDARDS, APPENDIX B �' ,� ti,5 \ SEE ELEC. PLAN l W 1 f •EJ ti Q ®U (ii)4M\ i 4 � Q QI _ � T > = t� M-2 SECURITY MOTION SENSOR `� a Eo m 1 l ! l 11v1� f i i ��E 3)pE1. — @==' / )M-3 MOOD MUSIC EQUIPMENT: 15"W X 24"H E-9 // Q M-s t / I� , ' M-4 SURFACE-MOUNT DATA NETWORK JACK / �'�1 p _ o /' 1 � ' riE7. ' 4 V M-5 WALL BRACKET FOR REMOTE THERMOSTAT EI IARCHITECT/ENGINEER OF RECORD 1 \vii / i. / pit . ,, f Il:p�`1 _? i 11 I I F It I I - .. .. .. . M-6 DRAWING STORAGE TUBE ,/ nun n n M-7 STRUCTURED CABLING FLOOR PLAN: 48"W X 36"H Es (i.4 ) ELEVATION- A ELEVATION- B ELEVATION- C ELEVATION- D DESIGN B-1 BMS EQUIPMENT: 15"W X 54"H Architectural Solutions Group DATA ROOM ELEVATIONS SCALE 1 2 19120 SE 34TH STREET, SUITE 115 1/2" - 11-0 VANCOUVER, WA 98683 FIELD VERIFY EXACT LOCATION The JP drawMorgan and WALL s e anand shall not be copied or re WITH MECHANICAL CONTRACTOR. authorization. The contract documents were prepared for use on this specific Site in conjunction with its issue dote and ore not suitable for use oft a dtferent SEESHEET E2.0 FOR CIRCUITING. sFe or at a filer time. ase aF these draw ngs Far reference a example on (1)-4" SECURITY CABLE SLEEVE another project requires the services at property `•tensed architects and engineers. Reproduction of the contract documents for reuse on another PROVIDED BY OWNER AND (2)-4" DATA CABLE SLEEVES Bprojectisnolauthor¢ed- NOTES: INSTALLED BY G.C. _ OVIINSTALLED BY OWNER AND — C-CHANNEL UNISTRUT 1. ALL CARRIER AND SECURITY CABLING MUST (1)-2"SECURITY D BY CABLE SLEEVESEAL PROFFS PROVIDED OWNER AND AT 90" AFFEp BE AFFIXED TO WALL AND/OR CONVEYANCE INSTALLED BY G.C. NG I N£ S`4 WITH HANGERS, VELCRO, AND TIES NO `�1A Oy HANGING CABLES. / - -If i r r-1 _A 15,423 . r IliI y I it 2. REFER TO JPMC RETAIL STRUCTURED i ' CABLING STANDARD FOR ADDITIONAL INFO. 1 i 1 I I I I I I L�+34"� +54" O a CONTACT MARTIN MCMURRAY AT CHASE GTI ,/' I +60"- - - - - J .1). \ �q e�• 31, (,'- 614-2175572; k Q Rosa) 04/14/20 MARTIN.MCMURRAYC�JPMCHASE.COM IG \ R +68" +68" I I 3. TELECOM SERVICE FLOOR AND CEILING54=' 4 IG + OPTIONS TO BE COORDINATED WITH P.M. AND IG "ill `1 ROBISON UTILITIES. �`� 4ti ENGINEERING INC J f A-12 TWIST LOCK 19401 40TH AVE W SURE 302.LYNNWOOo.WA 98036 TEL:206-364-3343 FAX:425-835-0098 A-42 L5-20R CONTACT:SHANE MCCLURE A-40 +90" ISSUE DATE DESCRIPTION A-38 TWIST LOCK �\ A L5 20R IN-FLOOR CONDUIT A,-36 +90" X TERMINATIONS FOR , I , 4 _ EXTERIOR ATM l � 1/2" ,2#1,30 0,#10G = 0 D B (1) 1" CONDUIT TO ROOF 4 'P ! T, ST LOCK m LOCATION FOR FUTURE I A U4-30 ANTENNA CABLING TWIST LOCK - �� C 71 L14-30 (2)-4" CONDUIT FOR TELECOM -- • / I�2 +90" 34 H SERVICE W/ 3-CELL MAXCELL / ) I i fl ,�' INNERDUCT. COORDINATE WITH "F I" k A-32A-34 1=1 �� 4-13-20 PERMIT SUBMISSION TELEPHONE UTILITY. +12" - - IG t► 4-3-20 90% SET - - - A-44 I A 3-20-20 PLANNING 3/4" x 96" HIGH B-C FIRE-RATED _ A-46 I 1/2 C,2t10,#10 117+34' I I PROJECT INFORMATION BLOCK PLYWOOD WHERE INDICATED AT A I a1k'Am■ JOB# JPM19010.0 INTERIOR WALLS- MIN. OF 1 LABEL DATE: 1/20/2020 INDICATING FIRE-RESISTANCE 1 - DRAWN BY: GH COMPLIANCE MUST REMAIN MUSAK +1$" UNPAINTED AND CLEARLY VISIBLE +72" IG 3/4" x 96" HIGH B-C FIRE-RATED CHECKED BY: PR FOR FUTURE INSPECTION IG PLYWOOD WHERE INDICATED AT INTERIOR WALLS- MIN. OF 1 LABEL MODEL INDICATING FIRE-RESISTANCE COMPLIANCE MUST REMAIN DRAWING STANDARDS v20.1 UNPAINTED AND CLEARLY VISIBLE FOR FUTURE INSPECTION SHEET TITLE ENLARGE DATA ROOM & ELEVATIONS SHEET NUMBER SCALE E4 . 1 DATA ROOM FLOOR PLAN 1/2" 1, Q , 1 SECURITY SYMBOLS _ 0 ALARM KEYPAD WITH AREA NUMBER: 2 = PERIMETER (LOCATE NEAR Q ALARM LAMP EMPLOYEE ENTRANCE) _ 3 = CASH SAFE 4 = SAFETY DEPOSIT BOX CEILING-MOUNT DOME CAMERA 5 = THRU-WALL ATM O 6 = DRIVE-UP ATMs 9 = LOBBY ATM WALL-MOUNT BOX CAMERA (NO DOME) III COW i , DOOR CONTACT ND CEILING-MOUNT BOX CAMERA (NO DOME) IIIn 360 DEG. CEILING-MOUNTED MOTION DETECTOR O WALL-MOUNT DOME CAMERA WITH ARM AT $'-6" D❑ A.F.F. W NOTE: CONTRACTOR SHALL COORDINATE WITH CEILING-MOUNTED 'CURTAIN' MOTION DETECTOR CHASE SECURITY VENDOR FOR ALL FINAL C tai INTERIOR WALL-MOUNT DOME CAMERA LOCATIONS PRIOR TO ROUGH-IN. O SAFE ALARM PACKAGE EXTERIOR CEILING-MOUNT 180-DEGREE DOME CD EBR A EXTERIOR CEILING MOUNT 180 DEGREE DOME o NO NIGHT DEPOSITORY PACKAGE CAMERA inLU EXTERIOR WALL-MOUNT 180-DEGREE DOME x G' CAMERA, 9'-6" AFF a O INSTANT ISSUE PRINTER ALARMS W w a ® WIP WALL-MOUNT MINIATURE IP CAMERA AT HOLD-UP BUTTON 5'-2" A.F.F., MOUNTED TO STOREFRONT MULLION OR WALL FINISH- CONCEAL CABLE % WIRELESS HOLD-UP BUTTON: ONLY AT OVAL BCM DESKS. BY EXCEPTION ONLY AT ACCESS MVIDEO SYSTEM MONITOR BARS. Tr pp CAMERA INTEGRATED WITHIN TRANSACTION T' iliiiii ce INT EQUIPMENTM SECURITY CABLE TERMINATION FOR toMN ST CONNECTION TO EQUIPMENT Q Iin D • �B A co, a. aL W L- 0 4 A ceN CI 0 a LN N 0 0 rii o% MZI Op o = . * WpCV0 I 1 I ] C ] 7 \ a. liii 4 < ,., \__, ,, „ WIRELESS HUB ONLY AT > 1 > Z CI N V .1 OVAL BCM DESK CD II— M 0 N Z y o W J 0 Z Ii— .� cx c,, 1 .. _CJ D , I.:;7 '41 I ... g iill: S g a I . o o OINKco gth I t CAMERA MOUNTED i - 7 (111)* TO PAR11TlON � /> ' ilip 117 glir �� 3 L'J IIIIII� Ci) V ��. \ 2E1 - ARCHITECT/ ENGINEER OF RECORD � 9 © cp 0 0 /Oil PAA II 0 \ AL- ,:,7\''vle 61,/, /. .. CO 33 mDflor .1 0 \ i itt.- . o i DESIGN mi " _ 0 \ Architectural NT N ' Solutions Group (1:1 M mpm • �� �F- O/06) Orr H n it 0 fr 1 f 1, 7:21iNT M • ~ 0 a 3fi m 19120 SE 34TH STREET SUITE 115 m '� Z "` �;, VANCOUVER, WA 98683 •• ••11)11\ -I r proprietary properly � 0 These drawings and specifications are the confidential and o to COFFEEof JP Morgan Chase and shall not be copied orreproduced without written - Z CREDENZA authaaation. the contract documents were prepared for use on this specific (ISN.!' _� I stee'orn aataonnlo}ter} i15Useatthesendd ore rawingst euse on a drfierent terence or example on 1111 another project requires the services of properly licensed architects and 0 engineers. Reproduction of the contract documents for reuse on another proiec a notau . , 1 r : : 00 0 o 11 0 —113 SEAL . _��� ,00.1110 id .„,„. _ _ _ _ 0 .CO ., p PI\IROFFS 4-e zio 15,423 1111101r C. 1 II z I I A•: e. 0 0 I I �,9R c• 31, 2°So) � 1 _I k 0 RO0 04/14/20 S0 1 I� W _ cc,r/ � ° c - - £MdRoBIsoN 0/y#3. II E - = - W.-- I ' 41 .1..,, ir7s I I ENGINEERING, INC 1 9401 40TH AVE W SUITE 302,LYNNWOOD,WA 98036 - TEL:206-364-3343 FAX:425-835-0098 C°Op � — 1) v; I I B o oCONTACT:SHANE MCCLURE : I rW= ISSUE DATE DESCRIPTION 9 l \ -e- ° 0.10 li , I ` I ids: 34" H 11M1 ` 'IVIT S u A�S'T ©7-1® 3 GIND I I � y _��— op � /N\ MICR IT ® 3 ��1� 14v [+ 4-13-20 PERMIT SUBMISSION • iirco .\--*- 4'rH _ 'H rroGiii AT 1 , 4241 \ - - - - - - �' � - - , - - -�� - -° 11156 o 4-3-20 90% SET El S :; A dZ yZ 3-20-20 PLANNING II l 1 ��� t. - © G Z11 �1 r i r/_b -e LJ C'.4 PRBOJECT INFORMATION aPQsoD.D O DATE: 1/20/2020 DRAWN BY: GH CHECKED BY: PR MODEL DRAWING STANDARDS v20. 1 SECURITY PLAN FOR REFERENCE. REFER TO FINAL PLANS ISSUED BY CHASE irb SHEET TITLE - SCALE: 1/4"=1'-0" N SECURITY 0' 4' 8' 16' PLAN SHEET NUMBER E5 . O dm. CONDUIT TO ABOVE CEILING T DDD ~ABOVEIT THEO I CEILING ..1 FINISHED CEIUNG FINISHED CEILING 3/4" C., PULL STRING 3/4" C., PULL STRING III DOUBLE-GANG BACKBOX ® I L 1 tin n REMOTE INDICATOR LIGHT. ' USE SINGLE-GANG ATM MAX. 18 T I BACKBOX 3/4" C., PULL STRING I I ATM MACHINE - t i_ I 3/4" C., PULL STRING I-.411--WALL MOUNTED HOLD-UP BUTTON USE SINGLE-GANG BACKBOX o O I I in w Lt HB Q USE 3/ 4" SEALT1TE TO ct DRESS SEALTITE CONDUIT INTERCONNECT BOXES DOUBLE-GANG BACKBOX a NEATLY FOLLOWING 1 CONTOUR OF SAFE AND T- - WALL. USE APPROPRIATE I FASTENERS. 0 'T 1 I I r FINISHED FLOOR CO w � � FINISHED FLOOR im MOUNT 4" SQUARE BOX inI 0 01 OVER PRE-INSTALLED ATM WALL MOUNTED HOLD UP INDICATOR LIGHT I." CABLES SCALE: NONE O 0 w > TYPICLAL ALARM CONDUIT TO ATM MACHINE VERIFY FINAL LOCATIONS WITH ARCHITECTURAL SET AND SECURITY VENDOR 0 4 J ccsi w N SCALE: NONE El 1L:/ a 1 \ 0 a, 421 0% VERIFY FINAL LOCATIONS WITH ARCHITECTURAL SET AND SECURITY VENDOR 00 _. oc (4) Z0 o0 ItWwoo WIRE LEGEND cn CABLE DESCRIPTION JACKET COLOR PAIGE WIRE PART emjiw 4 Q TYPE � , n A 22 AWG 4 COND. STRANDED WHITE 454650AWH .... SECURITY RESPONSIBILITIES 110V CKT - Ir ZCI I„. PLAN SYMBOL DEVICE CONTRACTOR ADT NAVCO DIEBOLD T T T B 22 AWG 8 COND. STRANDED WHITE 454689AWH 0 CONDUIT TO I I CONDUIT TO ABOVE 0 N L� ABOVE I I CEILING C 22 AWG 12 COND. STRANDED WHITE 454653AWH w 4 r CCTV CAMERA RACEWAY, BOXES, PROVIDE & WIRE CEILING PULL STRING I II FINISHED CEILING Cn Z r I I 0 18 AWG 4 COND. STRANDED WHITE 454644AWH e CAMERA WITH DOME RACEWAY, BOXES, PULL STRING PROVIDE & WIRE 3/4" C., PULL STRING I 3/4" CONDUIT FOR 110VAC I I 3/4" C., PULL STRING E 18 AWG 2 COND. STRANDED WHITE 454641AWH 4 — I— KEYPAD RACEWAY, BOX, PROVIDE & WIRE SOFFIT TO NIGHT DEPOSIT SAFE. I KP PULL STRING I (BY CONTRACTOR) I I = INDICATOR LIGHT RACEWAY, BOX, PROVIDE & WIRE I I F 16 AWG 2 COND. STRANDED WHITE 454649AWH SIL I SINGLE-GANG BACKBOXSINGLE-GANG FLUSH I I SINGLE-GANG BACKBOX PULL STRING I MOUNTED WALL BOX FOR I ND I G 24 AWG - 4 PR. CAT 5E GRAY 710536E CARD READER RACEWAY, BOX, PROVIDE & WIREUTP CR PULL STRING - USE 3/ 4" SEALTITE TO 110VAC CONNECTION. 1 1 DRESS SEALTITE CONDUIT H RG59 COAXIAL W/ 1 INTERCONNECT BOXES NEATLY AGAINST NIGHT 18 AWG WHITE 454820AWH KS KEY SWITCH OVERRIDE RACEWAY, BOX, PROVIDE & WIRE ITII DEPOSIT SAFE. USE ("SIAMESE") PULL STRING ALARM JUNCTION BOX AND J 22 AWG 8 COND. STRANDED, 454 1AWH APPROPRIATE FASTENERS. WHITE 90 ARCHITECT!ENGINEER OF RECORD MOTION DETECTOR CEILING MTD SEE NOTE PROVIDE & WIRE RACEWAY, BOX, PULL STRING PRE-INSTALLED NIGHT SHIELDED IF REQUIRED BY LOCAL CODE DEPOSIT ALARM CABLES MOTION DETECTOR WALL MTD SEE NOTE PROVIDE & WIRE RACEWAY, BOX, PULL STRING q ALARM CONNECTION WIRE MANUFACTURER AND PART NUMBERS MAY ONLY BE SUBSTITUTED WITH EQUIVILENT. ,w IF REQUIRED BY LOCAL CODE PANEL SEE NOTE PROVIDE & WIRE SEE DATA ROOM WALL piiil SCTY ELEVATIONS. DWG E 4.1 NOTES HOLD-UP BUTTON DESK MTD RACEWAY, BOX, PROVIDE & WIRE AU.. WIRES TO BE "HOME-RUN- BACK TO THE HEAD-END EQUIPMENT LOCATION, EXCEPT WHERE NOTED DESIGN HB PULL STRING BUILDING EXTERIOR HB HOLD-UP BUTTON WALL MTD RACEWAY, BOX, PROVIDE & WIRE ALL WIRES SHALL BE CONCEALED/FISHED WHEN POSSIBLE. ANY EXPOSED WIRE SHALL BE IN EMT CONDUIT. Architectural PULL STRING w NIGHT DEPOSIT SAFE NIGHT DEPOSIT SAFE WIRES CONCEALED IN WALLS SHALL EXIT THROUGH "RETRO-FIT"" OR "OLD-WORK" TYPE BOXES. APPROPRIATE Solutions G r a u p DOOR CONTACT RACEWAY, BOX, PROVIDE & WIRE SIDE VIEW FRONT VIEW COVERS TO BE USED ON ALL BOXES. SEE APUCABLE DRAWINGS FOR DETAILS. PULL STRING 16-CHANNEL DVR SEE NOTE PROVIDE SEE DATA ROOM WALL 0 LJ EC TO FURNISH AND INSTALL CCTV CABLE IN THE NY, NJ & CT. ALL WIRES SHALL BE LABELED ON BOTH ENDS, 19120 SE 34TH STREET, SUITE 115 DVR USING ACCEPTABLE WIRE-MARKING METHODS. ELEVATIONS. DWG E 4.1 VANCOUVER, WA 98683 MONITOR RACEWAY, BOXES, PROVIDE IN BREAK ROOM EC TO FURNISH AND INSTALL 110VAC RECEPTACLES AS REQUIRED. COORDINATE WITH ALARM & CCTV VENDORS. MON 110V, PULL STRING These drawings and specifications are the confidential and proprietary property Cl JP Morgan Chase and shall not be copied or reproduced without w6lien CELLULAR BACK-UP RACEWAY, BOXES, INSTALL & WIRE GENERAL CONTRACTOR ( GC )" " TO FURNISH AND INSTALL 3/4" PLYWOOD FOR MOUNTING HEAD-END EQUIPMENT, authorization. rhe contract doer enfs were pepared far ase an this specific TG4 110V PULL STRING site in conjunction with its issue date and are nat suitable tar use on a different site or ata cater time. Use of these drawings for reference or example on SECURITY VENDOR TO PROVIDE THE FOLLOWING: SECURITY DEVICES, CONTROL PANELS AND TECHNICAL another praec, requires the services of propery licensed architects and TCD TCD PROTECTION RACEWAY, BOXES, INSTALL & WIRE SUPPORT TO EC IF REQUIRED. engineers. Rep oduction of the ontractd nfs far reuse on another PACKAGE PULL STRINGot ATM PROTECTION RACEWAY, BOXES, INSTALL & WIRE CCTV VENDOR WILL PROVIDE ALL CCTV RELATED EQUIPMENT. ATM PACKAGE PULL STRING NIGHT DROP PROTECTION RACEWAY, BOXES, INSTALL & WIRE FINISHED FLOOR SECURITY/CCTV VENDORS TO FURNISH & INSTALL ALL SECURITY CABLES, DEVICES, CONTROL EQUIPMENT AND SEAL ND TERMINATE ALL WIRE CONNECTIONS. DRAWINGS CONTAINED HEREIN ARE TO BE USED AS AN INSTALLATION GUIDE ONLY. • ED PROFFS PACKAGE 110V, PULL STRING SPECIFIC ITEMS NOT COVERED IN THE DRAWINGS OR ANY DETAILS THAT REQUIRE CLARIFICATION OR EXPLANATION SHOULD N G I N F s) SAFE PROTECTION RACEWAY, BOX, INSTALL & WIRE BE DIRECTED TO THE APPUCABLE VENDOR. F, Ftp o SP PACKAGE PULL STRING TYPICAL DEVICE CONNECTIONS TO NIGHT DEPOSIT SAFE 15,423 ? DRAWINGS ARE NOT TO SCALE AND SHALL NOT BE USED FOR CONSTRUCTION PURPOSES. � � i • ALL REQUIRED RACEWAYS, RACEBOXES, JUNCTION BOXES, PULL STRINGS ARE TO BE PROVIDED BY CONTRACTOR SCALE: NONE • ALL REQUIRED 110V POWER (RECEPTACLES OR HARDWIRE CONNECTIONS) ARE TO BE PROVIDED BY CONTRACTOR r CONDUIT TO ABOVE THE CEILING De�,• • O • CONTRACTOR IS RESPONSIBLE FOR COORDINATION OF ALL OF THE ABOVE WORK ITEMS FINISHED CEILING II ,�c• 31, `L��k D. Rdg\Sp 04/14/20 22 AWG 8 COND. STRANDED, SHIELDED (CABLE TYPE "J") I ACS-2 CABINET SEE KEY NOTE 13, E4.0 43/4" C., PULL STRING R OBISON Ifell 11 USE COVER PLATE WITH ENGINEERING, INC CARD READER HOLE (1" ABOVE DOOR TO BOTTOM 19407 40TH AVE W SUITE 302,LYNNWOOD.WA 98036 r� TEL:206-364-3343 FAX:425-835-0098 OF COVER PLATE). PROVIDED BY CONTACT:SHANE MCCLURE Q SECURITY VENDOR ISSUE DATE DESCRIPTION ULLIONS 18 AWG 2 COND. STRANDED I 18 AWG 2 COND. STRANDED (LEVITON MODEL PJ11, TYPICAL) (WIRE TYPE "E") (WIRE TYPE "E") 0 - 1 I CENTER DOOR CONTACT / / / / WITH PRE-INSTALLED KEY SWITCH I I SPLICE BOX 18 AWG 2 COND. STRANDED I _ _ _ El (WIRE TYPE "E") L li- I LOCK POWER SEE KEY NOTE 14, E4.0 i\H MAGLOCK SUPPLY 1$ AWG 2 COND. STRANDED I 4-13-20 PERMIT SUBMISSION EXIT (WIRE TYPE "E") J 4-3-20 90% SET O o 3-20-20 PLANNING I PROJECT INFORMATION BLOCK EXIT BUTTON 1 18 AWG 2 GOND. STRANDED I JOB# JPM19010.0 EXIT I DATE: 1/20/2020 (4NRE TYPE "E"} 18 AWG 2 COND. STRANDED (WIRE TYPE "E") DRAWN BY: GH I CHECKED BY: PR EXIT BUTTON/2 18 AWG 2 COND. STRANDED I (WIRE TYPE CO. J E") J I MODEL I CR I DRAWING STANDARDS v20. 1 TOUCH BAR EXIT SENSOR SHEET TITLE TYPICAL DOOR CONTACT INSTALLATION DMP XR500 ALARM PANEL VESTIBULE ACCESS CONTROL WIRING RISER SCALE: NONE SECURITY SCALE: NONE FOR REFERENCE NOT ALL NOTES APPLY DETAILS VESTIBULE ACCESS READER & KEYSWITCH MOUNTING HEIGHT SCALE: NONE SCALE: NONE VERIFY FINAL LOCATIONS WITH ARCHITECTURAL SET AND SECURITY VENDOR SHEET NUMBER E5 . 1 T CONDUIT TO ABOVE THE CEILING _ NOTES: WHERE PERMITTED, WIRES CONCEALED WITHIN EXTERIOR WALLS. DO NOT FINISHED CEILING LEAVE 6 FT OF CABLEI NEED TO BE RUN IN EMT CONDUIT UNLESS LOCAL CODES REQUIRE. 'MU COILED ABOVE CEILING-----_,...I DO NOT INSTALL A JUNCTION BOX BEHIND WALL-MOUNTED MOTION DETECTORS. THE PHYSICAL SIZE WILL NOT COVER A JUNCTION BOX. MAKE A HOLE IN THE SHEETROCK AS SMALL AS POSSIBLE TO SNAKE WIRE OUT OF AND ROUTE WIRE 1111 FINISHED CEILING I DIRECTLY INTO HOUSING OF MOTION DETECTOR. NOTE: WHEN INSTALLING BACKBOX, 3/4" C., PULL STRING PLAN TO KEEP THE FINISHED KEYPAD OUT OF THE CUSTOMERS C CONCEAL CABLE VIEW WITHIN CHANNEL OF SEE NIFING DETAIL SIDE VIEW HOLLOW CHANNEL DOOR FRAME T © CONDUIT TO ABOVE CEILINGI -4IzFINISHED CEILING o DOOR SWING I SINGLE-GANG BACKBOX w J WHERE NECESSARY AND WITH THE APPROVAL OF CHASE 3/4" C., PULL STRING BANK, DRILL APPROPRIATE cr I I HOLE IN FRAME TO ACCOMMODATE CABLE - FRAME INSTALLATION. a COVER HOLE WITH A 0 /1 DRILL HOLE DECORATIVE COVER AFTER / INSTALLATION. KP V // ii I 1 9 ©W . — CO LW INSTALLATION DETAIL SIDE VIEW co I I— in FINISHED FLOOR I.- DRILL 3/4" HOLE IN FRAME 4" ce FROM DOOR CENTER AND M PRE-WIRE FOR DOOR CONTACT KEYPAD VI 0 U N TI N G DETAIL o 4 J w N SCALE: NONE oV""4 WN VIEWED FROM PROTECTED SIDE OF DOOR N 13, J °' FINISHED FLOOR Ci .1 re MZ o0 RECESSED DOUBLE DOOR CONTACTS SCALE: NONE FINISHED FLOOR W V Q VERIFY FINAL LOCATIONS WITH ARCHITECTURAL SET AND SECURITY VENDOR WALL MTD MOTION DETECTOR0- Wa < OE SCALE: NONE 0 N 2 O Z 0 1- VERIFY FINAL LOCATIONS WITH ARCHITECTURAL SET AND SECURITY VENDOR — Z o W J � Z aN , 4 - I- CAT 6 PATCH CABLE •/ / \ Cl) IP DROP r CONDUIT TO ABOVE CEILING I \ 1 FINISHED CEILING FINISHED CEILING / \ r1 MARCH NETWORKS I 3/ 4" C., PULL STRING .7 \ SINGLE-GANG BOX DVR I PROVIDE 3/4" SEALTITE TO INTER CONNECT / \ REMOTE / 2 T \ USE SIAMESE IF PLAIN COAXIAL CABLE IS NOT AVAILABE >�ONiroR 1 /7 BOTH BOXES AND DRESS CABLES ACCORDINGLY ARCHITECT/ENGINEER OF RECORD RACK MOUNTED SP lel ALARM JUNCTION BOX AND - PRE-INSTALLED SAFE ALARM / 11O VAC OUTLET CABLES / > 3. ---I ,T..-1,_ 1 / 110 VAC OUTLET BREAK ROOM [ \ DES!GN / \ Architectural 110 VAC OUTLET \ CONDUIT TO Solutions Group I� F-1) FREE STANDING CASH SAFE / ABOVE CEILING j \ 19120 SE 34TH STREET, SUITE 115 L / \ VANCOUVER, WA 98683 VIDEO SYSTEM POWER CORD, TYPICAL / \ These drawings and specifications are the confidential and p oprietary properly POWER SUPPLY o 0 El / \ JP Morgan Chase and shall not be copied or reproduced without written \ authorization. The contract documents were prepared For use on this specific / \ site in c a k t later with its issue date and are not svitabe for use on a different SINGLE-GANG RECESSED site h at a later time. Use at these drawings far reference or exacts nn / another project requires the services of property kensed architects and BACKBOX engineers. Rep oduct on Prolect is not authorized. nts for reuse on anothe WALL MOUNTED LEGEND CCTV NOTESL RG59U COAXIAL CABLE IP DROP AND 110 VAC OUTLETS '/' - BELDEN PART # 643948 PROVIDED AND INSTALLED BY EC. LOCATE AS PER CHASE. \ 16DO NOT USTIUZE RACK POWER STRIPS. \ SEAL , ED PROFF 18 GAUGE 2 CONDUCTOR DVR WILL BE RACK-MOUNTED. / O I S3, BELDEN PART # 6300UE \ \A f i TYPICAL WIRING FOR ALL CAMERAS LAN ROOM j 15,423 r \ ' CCTV SCHEN ATI C FINISHED FLOOR \ NOTE: ALL WORK TO BE INSTALLED PER 04•' °c 31 ��� SCALE: NONE 2 16 CEC C 4RK ,D�\So TYPICAL ALARM WIRING TO CASH SAFE \ 04/14/20 VERIFY FINAL LOCATIONS WITH ARCHITECTURAL SET AND SECURITY VENDOR T SCALE: NONE Lc METAL RoBIsoN CONDUIT TO ABOVE CEILING VERIFY FINAL LOCATIONS WITH ARCHITECTURAL SET AND SECURITY VENDOR TG-4MVI ENCLOSURE ENGINEERING, INC 19401 40TH AvE W Sulu`302.LYNNWOOD.WA 98036 FINISHED CEILING TEL:206-364-3343 FAx;425-835-0098 CONTACT:SHANE MCCLURE 110VAC 20A DUFiLEX OUTLET BY CONTRACTOR7 3/4" C., ISSUE DATE DESCRIPTION PULL STRING al W I 1 \ BUILDING EXTERIOR \ 4-13-20 PERMIT SUBMISSION DRILL 1" HOLE IN TG-4 METAL ENCLOSURE AT LOCATION • \ SHOWN FOR CABLE ENTRANCE, THEN POSITION HOLE 4-3-20 90% SET OVER 1-GANG WALL BOX AND MOUNT TO WALL. TG-4 3-20-20 PLANNING PRIOR TO DRILLING CABLE OPENING, ALLOW FOR / CELL \ PROJECT INFORMATION BLOCK BACK-UP JOB# JPM19010.0 MOUNTING HOLES AND BATTERY INSTALLATION. INSTALL / 12VDC 7AH DATE 1/20/2020 CABLE BUSHING IN CUT-OUT . BATTERY DRAWN BY: GH \ CHECKED BY: PR \ , • MODEL // SINGLE-GANG BACKBOX TG4 SIDE ELEVATION DETAIL FO TG- 4 FLUSH MOUNTED JUNCTION BOX DRAWING STANDARDS v20. 1 TG-4 METAL ENCLOSURE SCALE: NONE SHEET TITLE EQUIPMENT TO BE INSTALLED BY SECURITY VENDOR VERIFY FINAL LOCATIO \ S WITH ARCHITECTURAL SET AND SECURITY VENDOR SECURITY ATM ROOM TG- 4 MOUNTING DETAIL DETAILS FOR REFERENCE ONLY UNDER SEPARATE LOW VOLTAGE PERMIT SCALE: NONE SCALE: NONE VERIFY FINAL LOCATIONS WITH SECURITY VENDOR SHEET NUMBER E5 . 2 i 1 11111 li.1 ❑ 17.Medical task lighting or art/history display lighting claimed to be exempt from compliance has a control device independent of the control 2)an occupant sensor that shall turn lighting off within 30 minutes of an occupant leaving a space;or Complies:YES of the nonexempt lighting. 3)a signal from another control or alarm system that indicates the area is unoccupied. Mandatory Requirements: Exception(s): Plans reference page/section: 0 2. Exit signs. Internally illuminated exit signs shall not exceed 5 watts per side. ❑ Sleeping units, patient care areas;and spaces where automatic shutoff would endanger safety or security. L COM cheek Software Version 4.1.1.0 NA j 18.Each dwelling unit in a building is metered separately. E1 -0 Plans reference page/section: Plans reference page/section: interior Lighting Compliance Plans reference pagelsection: 3. Daylight zone control.All daylight zones are provided with individual controls that control the lights independent of general area lighting Lill ❑ 10.Occupancy sensors in rooms that include daylight zones are required to have Manual ON activation. in the non-daylight zone. In all individual daylight zones larger than 350 sq.ft.,automatic daylight controls is provided.Automatic E1-0 daylight sensing controls reduce the light output of the controlled luminaires at least 50 percent,and provide an automatic OFF control, Certificate Interior Lighting PASSES Design 38%better than code Plans reference page/section: IIIC:IC while maintaining a uniform level of illumination.Contiguous daylight zones adjacent to vertical fenestration may be controlled by a j 11.An occupant sensor control device is installed that automatically turns lighting off within 30 minutes of all occupants leaving a space. single controlling device provided that they do not include zones facing more than two adjacent cardinal orientations(i.e.,north,east, Section 5: Compliance Statement Exception(s): south,west).Daylight zones under skylights shall be controlled separately from daylight zones adjacent to vertical fenestration. Exception(s): Section 1: Project Information ❑ Classrooms and lecture halls_ Retail spaces adjacent to vertical glazing(retail spaces under overhead glazing are not exempt). Compliance Statement: The proposed lighting design represented in this document is consistent with the building plans,specifications and ❑ >I Conference,meeting and training rooms. Display,exhibition and specialty lighting Energy Code: 2014 Oregon Energy Efficiency Specialty Code I other calculations submitted with this permit application.The proposed lighting system has been designed to meet the 2014 Oregon Energy ❑ inEmployee lunch and break rooms. ❑ HID lamps 150 watts or less. Project Title: Chase-Tigard Efficiency Specialty Code requirements in COMcheck Version 4.1.1.0 and to comply with the mandatory requirements in the Requirements Project Type: New Construction Checklist. ❑ Rooms used for document copying and printing. ❑ Spaces required to have occupancy sensors. Construction Site: Owner/Agent: Designer/Contractor: ❑ Office spaces up to 300 square feet. Plans reference page/section: El-0 12100 SW Scholls Ferry Rd. Robison Engineering INC MARK ROBISON 3/20/20 Restrooms. - � Tigard,OR 97223 19401 40th Ave.W,Suite 302 ] 4. Interior righting controls.At least one local shutoff lighting control has been provided for every 2,000 square feet of lit floor area and Lynnwood,WA 98036 Name Title Signature Date ] Dressing,fitting and locker roams. each area enclosed by walls or floor-to-ceiling partitions.The required controls are located within the area served by the controls or are 206-364-3343 O0 a remote switch that identifies the lights served and indicates their status. 0 Plans reference page/section: Exception(s): w j 12.Additional controls.An occupant sensor control device that automatically turns lighting off within 30 minutes of all occupants leaving a ❑ Lighting systems serving areas designated as security or emergency areas that must be continuously lighted. Section 2: Interior Lighting and Power Calculation Q space or a locally activated switch that automatically turns lighting off within 30 minutes of being activated is installed in all storage and ❑ Lighting in public areas such as concourses,stairways or corridors that are elements of the means of egress with switches that uut supply rooms up to 1000 square feet. are accessible only to authorized personnel. A B C D CC Plans reference page/section: El-0 ] Lighting for warehouses,parking garages or spaces using less than 0.5 watts per square foot. Floor Area Allowed Allowed Watts J Lighting for contiguous,single-tenant retain spaces. Watts I ft2 ] 13.Occupant override.Automatic lighting shutoff operating on a time-of-day scheduled basis incorporates an override switching device E1_0 Bank(Retail) 2380 1.32 3142 that: 1)is readily accessible,2)is located so that a person using the device can see the lights or the area controlled by that switch,or Plans reference page/section: Total Allowed Watts- 3142 so that the area being lit is annunciated,3)is manually operated,4)allows the lighting to remain on for no more than 2 hours when an NAJ 5. Sleeping unit controls. Master switch at entry to hotel/motel guest room. override is initiated, and 5)controls an area not exceeding 2,000 square feet. Section 3: Interior Lighting Fixture Schedule Exception(s): Plans reference page/section: Nt In malls and arcades,auditoriums,single-tenant retail spaces,industrial facilities and arenas,where captive key override is zi 6. Egress lighting. Egress illumination is controlled by a combination of listed emergency relay and occupancy sensors to shut off during A 8 C D E= utilized,override time is permitted to exceed 2 hours. periods that the building space served by the means of egress is unoccupied. Fixture ID: Description I Lamp i Wattage Per Lamp i Ballast Lamps! #of Fixture (C X D) I T J In malls and arcades,auditoriums,single-tenant retail spaces,industrial facilities and arenas,the area controlled shall not exceed Exception(s): Fixture Fixtures Watt. 20,000 square feet. J Building exits as defined in Section 1002 of the Oregon Structural Specialty Code. Bank(Retail 2380 sq.ft.) E1-C LED 1:L2:2X4 TROFFER:Other: 1 12 34 408COIIIM Plans reference page/section: Plans reference page/section: LED 2:L2E:2X4 TROFFER WI EM:Other: 1 7 34 238 Q ❑ 14.Holiday scheduling. Automatic lighting shutoff operating on a time-of-day scheduled basis has an automatic holiday scheduling feature a7. Additional controls. Each area that is required to have a manual control shall have additional controls that meet the requirements of LED 3: L3: UNDER CABINET LIGHT:Other. 1 12 4.9 58.8 in I- i_ that turns off all loads for at least 24 hours,then resumes the normally scheduled operation. Sections 505.2.2.1 and 505.2.2.2. LED 4:L11:4"DOWNLIGHT: Other: 1 12 14 168 Exception(s): El-0 LED 5: DIEM:4"DOWNLIGHT W/EM:Other: 1 1 14 14 M Plans reference page/section: ❑ Retail stores and associated malls, restaurants,grocery stores, places of religious worship.theaters and exterior lighting zones. LED 6: L22:2'LINEAR: Other: 1 1 18 18 W Single zone electronic time control devices and self-contained wall box preset lighting controls. 8. Light reduction controls.Each space required to have a manual control also allows for reducing the connected lighting load by at least Ii LED 7: L410:PENDANT:Other: 1 4 40 16001) 50 percent by either LED 8:L412:PENDANT:Other: 1 3 10 30 0 4 _1 le N Plans reference page/section: E1-2 AND EL-3 1)controlling(dimming or multi-level switching)alt luminaires;or 2)dual switching of alternate rows of luminaires,alternate luminaires,or alternate lamps:or LED 9: L502:2'LINEAR LED:Other: 1 3 12 36 W a 15.Exterior lighting controls.Lighting not designated for dusk-to-dawn operation shall be controlled by either a combination of a 3)switching the middle lamp Luminaires independently of other lamps;or LED 10:L503-6:3'-6"LiNEAR LED:Other: 1 1 21 21 0 0 4 Li. ,,,cs,i photosensor and a time switch,or an astronomical time switch.Lighting designated for dusk-to-dawn operation shall be controlled by 4)switching each luminaire or each lamp. LED 11:L503:3'LINEAR LED:Other: 1 2 18 36 an astronomical time switch or photosensor. Exception(s): LED 12:L504:4'LINEAR LED:Other: 1 10 24 240 p 13., .1 (2% E1-2 AND EL-3 ❑ Only one luminaire in space. LED 13:L505:5'LINEAR LED:Other: 1 1 30 30 COce Plans reference page/section: .13 An occupant-sensing device controls the area. LED 14:L506:6'LINEAR LED:Other: 1 5 36 180 O 0 NA❑ 16.Tandem [j wiring.The following luminaires located within the same area shall be tandem wired: The area is a corridor,storeroom,restroom,public lobby or sleeping unit. LED 15:L508E:8'LINEAR LED W/EM:Other: 1 1 48 48 (.4) Z CI 1, Fluorescent luminaires equipped with one,three or odd-numbered lamp configurations,that are recess-mounted within 10 feet Zli Electrical and mechanical room. LED 16:L506E:6'LINEAR LED W/EM:Other: 1 3 36 108 center-to-center of each other. U 0 Q 2. Fluorescent luminaires equipped with one,three or any odd-numbered lamp configuration,that are pendant-or surface-mounted ❑ Areas that use less than 0.6 Watts/sq.ft. LED 17:L516:BLUE COVE LIGHT:Other. 1 26 6 15611111 within 1 foot edge-to-edge of each other. Plans reference page/section: El-0 LED 18:L516: 1'-6"LINEAR LED:Other: 1 1 9 9 rX V Exception(s): Total Proposed Watts= 1959 N Ilii Where electronic high-frequency ballasts are used. 0 9. Buildings larger than 2,000 square feet are equipped with an automatic control device to shut off lighting in those areas.This automatic CIE la 4 control device shall function on either: • Luminaires on emergency circuits. Section 4: Requirements Checklist C, 9 cY 1)a scheduled basis, using time-of-day,with an independent program schedule that controls the interior lighting in areas that do not Q ?iihiP Z❑ Luminaires with no available pair in the same area. exceed 10,000 square feet and are not more than one floor,or Q N �` In the following requirements.blank checkboxes identify requirements that the applicant hes not acknowledged as being met. Checkmarks Plans reference page/section: identify requirements that the applicant acknowledges are met or excepted from compliance. 'Plans reference page/section'identities where in O the plans/specs the requirement can be verified as being satisfied. Z O Lighting Wattage: ❑ 1. Total proposed watts must be less than or equal to total allowed watts. W i 4 ^ii Allowed Wattage: 3142 Proposed Wattage: 1959 0 Z Project Title: Chase -Tigard Report date: 03!20120 Project Title: Chase-Tigard Report date: 03/20/20 Project Title: Chase-Tigard Report date: 03/20/20 Project Title: Chase-Tigard Report date: 03/20/20 4 I- Data filename: FeePedro+McCrackenl_Chase Banks1424-1360 Chase Tigard&Greenway-Tigard, OR1CaIcs1Lighting.eck Page 4 of 6 Data filename:Fe_Pedro+McCrackere_Chase Banks1424-1360 Chase Tigard&Greenway-Tigard,OR1Calcs1Lightrng.cck Page 3 of 6 Data filename: F:1Pedro+McCrackenlChase Banks1424-1360 Chase Tigard&Greenway-Tigard, OR1CaicslLighting.cck Page 2 of 6 Data filename: Fe_Pedro+McCrackenl_Chase Banks1424-1360 Chase Tigard&Greenway-Tigard, OR1CaIcs1Lighting.cck Page 1 of 6 I COI NA 2, Mercury vapor and incandescent lighting is not permitted for use as exterior lighting. (11) EXception(s): ❑ Incandescent lighting controlled by motion sensors and having total power less than 150 watts. ❑ Incandescent lighting used in or around swimming pools,water features,or other locations subject to the requirements of Articlerill‘iiirCOMcheck Software Version 4.1.1.0 1.1.0 680 of the National Electric Code. ■ ] 3. Exempt lighting fixtures are equipped with a control device independent of the control of the nonexempt lighting and are identified in Exterior Lighting Compliance ARCHITECT! ENGINEER OF RECORD Section 3 table above. Plans reference page/section: C e rt i f i c a to p_ .__1, Exterior Lighting PASSES: Design 1%better than code Section 1: Project Information Section 5: Compliance Statement Energy Code: 2014 Oregon Energy Efficiency Specialty Code ` Project Title: Chase-Tigard DESIGN Compliance Statement: The proposed exterior lighting design represented in this document is consistent with the building plans,specifications Project Type: New Construction and other calculations submitted with this permit application.The proposed lighting system has been designed to meet the 2014 Oregon Exterior Lighting Zone: 3(Other) Energy Efficiency Specialty Code requirements in COMcheck Version 4.1.1.0 and to comply with the mandatory requirements in the Construction Site: Owner/Agent: Designer/Contractor: Architectural Requirements Checklist. 12100 SW Scholls Ferry Rd. Robison Engineering INC S 0 I U ti O n S Group Tigard,OR 97223 19401 40th Ave.W,Suite 302 Mark Robison ---2 \ --------Z----- 3/20/2020 Lynnwood,WA 98036 Name-Title Signature Date 206-364-3343 19120 SE 34TH STREET, SUITE 115 VANCOUVER, WA 98683 Section 2: Exterior Lighting Area/Surface Power Calculation These drawings and spectIcations ore the confidential and proprietary property of JP Morgan Chase and shall not be copied or reproduced without written A B C D E F authorization. The contract documents were prepared for use on this specific Exterior Area/Surface Quantity Allowed Tradable Allowed Proposed site in conjunction with is!cue date and are not suitable for use on a different site or at a tater time. Use of these drawings for reference or example on Watts Wattage Watts Watts another project requires the services of property licensed architects and /Unit (B x C) engineers. Reproduction of the contract documents for reuse on another project is not authorized. FRONT CANOPY(Entry canopy) 615 ft2 0.4 Yes 246 608 ATM/DRive Tho,ATM(ATM/Night depository 2 machines 90 No 360 741 location)*** Total Tradable Watts"= 246 608 SEAL Total Allowed Watts= 606 , 01) PROF, Total Allowed Supplemental Watts"= 750 \,‘G I N 4r�`P Si$'/O2 *Wattage tradeoffs are only allowed between tradable areas/surfaces. ' **A supplemental allowance equal to 750 watts may be applied toward compliance of both non-tradable and tradable areas/surfaces. 15,423 "`ATM/Night depository sites have a base allowance of 180 W per site. Ct Section 3: Exterior Lighting Fixture Schedule 4I .. A B C D E "711).4„. R C 31 >ZO\4' ' Fixture ID: Description I Lamp!Wattage Per Lamp I Ballast Lamps! #of Fixture (C X 0) K Q ROB 04/1 4/20 Fixture Fixtures Watt, FRONT CANOPY(Entry canopy 615 tTradable Wattage ROBISON LED 1: L6A: CANOPY FIXTURE:Other: 1 5 110 550 LED 2:L21B:WALL PACK:Other: 1 1 58 58 ATM/DRive Thru ATM(ATM/Night depository location 2 machines): Non-tradable Wattage ENGINEERING, I N C LED 3:L21B:WALL PACK:Other: 1 2 58 116 19401 40TH AVE W SUITE 302, LYNNWOOD,WA 98036 LED 4: SF2:AREA LIGHT:Other: 1 5 125 625 TEL:206-364-3343 Fax:425-835-0098 Total Tradable Proposed Watts= 608 CONTACT:SHANE MCCLURE ISSUE DATE DESCRIPTION Section 4: Requirements Checklist In the following requirements, blank checkboxes identify requirements that the applicant has not acknowledged as being met. Checkmarks identify requirements that the applicant acknowledges are met or excepted from compliance. 'Plans reference page/section'identifies where in the plans/specs the requirement can be verified as being satisfied. Controls, Switching, and Wiring: NA j 1. Lighting designated to operate more than 2000 hours per year for Uncovered Parking Areas shall be equipped with motion sensors that will reduce the luminaire power by thirty-three percent or turn off one-third the luminaires when no activity is detected. Plans reference page/section: Exterior Lighting Restrictions and Exceptions: 4-13-20 PERMIT SUBMISSION Project Title: Chase - Tigard Report date: 03/20/20 Project Title: Chase-Tigard Report date: 03/20/20 4-3-20 900/T SET Data filename:F:\_Pedro+McCrackenl_Chase Banks1424-1360 Chase Tigard&Greenway-Tigard, OR1Calcs\Lighting.cck Page 6 of 6 Data filename: F:1_Pedro+McCrackere_Chase Banks1424-1360 Chase Tigard&Greenway-Tigard,OR1Calcs\Lighting.cck Page 5 of 6 3-20-20 PLANNING PROJECT INFORMATION BLOCK • JOB# JPM19010.0 DATE: 1/20/2020 DRAWN BY: GH CHECKED BY: PR MODEL DRAWING STANDARDS v20. 1 SHEET TITLE ENERGY COMPLIANCE FORMS SHEET NUMBER E6 . O il w tn I O itLI Lu a f_ Lu ct 0 II V' om\ C LLI rnI-1 CHASE 2 CHASE CHASE CHASE SECTION 265000-LIGHTING M CHASE SECTION 260500-COMMON WORK RESULTS FOR ELECTRICAL SECTION 260500-COMMON WORK RESULTS FOR ELECTRICAL SECTION 260500--COMMON WORK RESULTS FOR ELECTRICAL SECTION 260500-COMMON WORK RESULTS FOR ELECTRICAL • • E. Conductor Splices: Keep to the minimum and comply with the following: 3" Welding to steel structure may be used only for threaded studs, not for conduits, pipe straps,or IX M G. Underground Line Warning Tape: Permanent, bright-colored,continuous-printed, vinyl tape with the 1. Installs splices and taps that any other items. PART 1 -GENERAL O 4 _I ce t.,4 following features: p p possess equivalent or better mechanical strength and insulation 4. In partitions of light steel construction use sheet-metal screws. W 1. Size: Not less than 4 mils thick by 6 inches wide. ratings than unspliced conductors. 1.1 RELATED DOCUMENTS pi! PART 1 GENERAL 2. Uses Ince and tap5. Drill holes in concrete beams so holes more than 1-1/2 inches deep do not cut main reinforcing a. Compounded for permanent direct-burial service. P connectors that are compatible with conductor material. bars A. The General Conditions of the Contract for Construction,A.I.A.A201, Latest Edition, 1.1 1 -GENERAL ALS 2. Embedded continuous metallic strip or core. F. Wiring at Outlets: Install with at least 12 inches of slack conductor at each outlet. 6. Drill holes in concrete so holes more than 3/4 inch deep do not cut main reinforcing bars. SupplementaryGeneral Conditions and the A. o s area part of the Contract for this work. Contractor shall consultI� Submit Product Data for supporting devices and electrical identification. a. Printed Legend: Indicates type of underground line. G. Connect outlets and components to wiring systems and to ground as indicated and instructed by 7. Fill and seal holes drilled in concrete and not used. them and the General Requirements, Division 1,for instructions pertaining to work under this section. "f.i) 1.2QUALITY ASSURANCE H. Tape Markers:Vinyl or vinyl cloth, self-adhesive,wraparound type with preprinted numbers and manufacturer.Tighten connectors and terminals,including screws and bolts,according to equipment 8. Select fasteners so the load applied to any fastener does not exceed 25 percent of the proof-test All notes on the drawings applying to this work are also a part of this Section. ...J letters. manufacturers load. 1.2 WORK INCLUDEDCO A. Comply with NFPA 70 for components and installation. torque requirements are notindicated,tightenlconnectorsuand terminals connectors. ccording to tightening rets 3.8 CONCRETE PADS AND METERING EQUIPMENT 9Labeling: productspacified in this Section that are listed and labeled. I. Color-Coding Cable Ties:Type 6/6 nylon,self-locking type.Colors to suit coding scheme. 0 B. requirements specified in UL 486A. A. Furnishing and installing lighting fixtures,with lamps,trims,extension trims, collars,hangers,supporI Zts 0 Listing and Provide sA. Install concrete pads and bases according to requirements of Division 3 Section"Cast-in-Place and controls as required for a complete andproper installation. g PPv 1. The Terms"Listed and Labeled As defined in the CEC, T24 J. Interior Warning and Caution Signs: Preprinted,aluminum, baked-enamel finish signs, punched for H. Install devices to securelyand permanentlyfasten and supportQ ie fasteners,with colors, legend, and size appropriate to the application. electrical components. Concrete." B. The Electrical Contractor shall refer to the Architectural Room Finish Schedules and Architectural and I. Raceway Supports:Comply with NFPA 70 and the following requirements: B. Install utility-metering equipment according to utility company's written requirements. Provide Structural details it lig rt 0 ° PART 2-PRODUCTS K. Exterior Warning and Caution Signs:Weather-resistant,non-fading, preprinted,cellulose acetate to determine conditions and finishes affecting the installation of this wo • 1. Install individual and multiple raceway hangers and riser clamps to supportgroundingempty conduits as required by utility company shall include all items of labor and materials necessaryor required forand he butyrate signs with 0.0396-inch,galvanized steel backing.Colors, legend,and size appropriate to the P raceways. Provide U roundiand eqadjustment of fixtures due to Ow Lill acir (I< 2.1 BUILDING WIRE application and 1/4-inch grommets in corners for mounting. bolts,clamps,attachments, and other hardware necessary for hanger assembly and for securing 3.9 IDENTIFICATION surrounding finished construction. hanger rods and conduits. A. Single conductor,copper. Solid conductor for No. 10 AWG and smaller, stranded conductor for larger L. Fasteners for Metal Signs:Self-tapping stainless-steel screws or No. 10/32 stainless-steel machine 2. Support parallel runs of horizontal raceways together on trapeze-or bracket-type hangers. A. Install identification devices where required. C. All li htin fixtures shall "Lighting e e lighting a be ordered and installed based on both the Fixture Schedule and than No. 10 AWG. screws with nuts and flat and lock washers. 3. Spare Capacity: Size supportsthe electricsl drawings and the architect's"Reflected CeilingPlan". See Reflected P P tY for multiple conduits so capacity can be increased by a 25 percent 1. Install labels where indicated and at locations for best convenience of viewing without Ceiling Plan for { A 1. Thermoplastic Insulated Wire:Conform to NEMA WC 5. minimum in the future. interference with operation and maintenance of equipment. location,type and thickness of ceiling material. ' �•/ 2. Cross-Linked, Polyethylene Insulated Wire:Conform to NEMA WC 7. M. Meter Sockets:Comply with serving utility company requirements. 4. Support individual horizontal raceways with separate, malleable iron pipe hangers or clamps. 2. Coordinate names,abbreviations,colors,andZCli �""" 3. Cann other designations used for electrical identification D. Contractor to coordinate for proper application of IC rated and non-IC rat Connectors an Splices: Units of size,ampacity rating, material,type,and class suitable far 5. Hanger Rods: 114-inch diameter or larger threaded steel,except as otherwise indicated. with corresponding designations indicated on the Contract Documents or required by codes and area riot to r rated recessed fixtures for each service indicated. Select to comply with Project's installation requirements. p ordering fixtures. O 0 PART 3-EXECUTION 6. Spring Steel Fasteners: Specifically designed for supporting single conduits or tubing. May be standards. Use consistent designations throughout the Project. 22 GENERAL SUPPORT FOR ELECTRICAL COMPONENTS used in lieu of malleable iron hangers for 1-1/2-inch and smaller raceways serving lighting and 3. Self-Adhesive Identification Products:Clean surfaces of dust, loose material,and oily films E. Contractor to provide appropriate enclosure around fixtures when required to comply with I Lu inix O 3.1 GENERALnational code requirements. P Y oval and/or receptacle branch circuits above suspended ceilings and for fastening raceways to channel and before applying. A. Channel and angle support systems, hangers,anchors,sleeves, brackets,fabricated items,and A. Install components and equipment to provide the maximum slotted angle supports. 4. Tag or[abet power circuits for future connection and circuits in raceways enclosures fasteners are designed to provide secure support from the building structure for electrical possible headroom where mounting 7" In vertical runs,Arran CA Z 4. P P Y with F. Contractor to provide appropriate ceiling thickness and adaptors as required for proper installation of components. heights or other location criteria are not indicated. arrange support so the load produced by the weight of the raceway and the other circuits. Identify source and circuit numbers in each cabinet, ail box, unction box,and r enclosed conductors is carried entirelybythe conduit weight P 1 recessed light fixtures and trim. 1. Material: Steel,except as otherwise indicated, protected from corrosion with zinc coating or with B. Install items level,plumb,and parallel and ebuilding systemssupports,with no load on racewayoutlet box.Color-coding may be used for voltage and phase indication. perpendicular to other and components, terminals, 5. Identify Paths of Underground Electrical Lines: During trench backfilling,for exterior undergroundlig IIM 1.3 RELATED WORK treatment of equivalent corrosion resistance using approved alternative finish or inherent material except where otherwise indicated. power,control, signal,and communication lines, install continuous undergroundplastic line J. Miscellaneous Supports: Install metal channel racks for mounting cabinets, panelboards,disconnects, g A. Related work not covered bythis Cli) characteristics. C. Install equipment to facilitate service, maintenance, and repairmarker located directly above power and communication lines. Locate 6 to 8 inches 1 Section includes, but is not necessarilylimited to, the following: I 2. Metal Items for Use Outdoors or in Damp Locations: Hot-dip galvanized steel,except as or replacement of components. control enclosures, pull boxes,junction boxes, transformers,and other devices except where ( 50 to 200 Section 260000" g"See Connect for ease of disconnecting,with minimum interference with other installations. components are mounted directly to structural features of adequate strength. mm)below finished grade. Where multiple lines installed in a common trench or concrete otherwise indicated. envelope do not exceed an overall width of 16 inches,use a single line marker. 1A SUBMITTALS 2.3 STEEL CHANNEL SUPPORTS D. Give right of way to raceways and piping systems installed at a required slope. K. In open overhead spaces, cast boxes threaded to raceways need not be separately supported,except 6. For panelboards, provide framed,typed circuit schedules with explicit description and supports0 have 9116 inch diameter holes at a maximum of 8 inches o.c.,in at least 1 E. The complete electrical installation, light fixtures, conduit, boxes,wiring,etc. in plenum ceiling areas where used for fixture support; support sheet-metal boxes directly from the building structure or by bar identification of items controlled byeach individual breaker. P A. Shop drawings for all lighting fixtures and controls shall be submitted for `� pertinent provisions of Division 1. approval. Comply with Steel channel shall be done in strict compliance with all state, national and local codes which have jurisdiction over hangers.otWhere bary hangers are used, attach the bar more raceways on opposite sides of the box and 3.10 CUTTING AND PATCHING surface. this project. support the raceway with an approved fastener not than 24 inches from the box. B. Shop drawings shall include the following data: 1.A. Fittings and accessories mate and match with channels and are from the same manufacturer. 1. Catalog 2.4 NONMETALLIC CHANNEL AND ANGLE SYSTEMS 3.2 FEEDERS 3.5 SLEEVES A. Cut,channel,chase,and drill floors,walls, partitions,ceilings,and other surfaces necessary for data: Manufacturers literature and illustrations. electrical installations. Perform cutting by skilled mechanics of the trades involved. Repair disturbed 2. Dimensions. A. Feeders:Type THHNlfHWN or XHHW,copper conductor, in raceway, A. Install for cable and raceway penetrations of concrete slabs and walls, except where core-drilled holes surfaces to match adjacent undisturbed surfaces. 3. Materials and construction. A. Structural-grade,factory-formed, fiberglass resin channels and angles with 9116-inch diameter holes PPe except as otherwise indicated. are used. Install for cable and raceway penetrations of masonryand fire rated gypsum4. Ballast data. walls and of all ata maximum of8 inches o.c., in at least 1 surface. B. Underground Feeders:Type XHHW,copper conductor,90C insulation, in raceway,except as other fire-rated floor and wall assemblies. Install sleeves during erection of concrete and masonry 5. Lamp data. 1. Fittings and accessories mate and match with channels or angles and are from the same otherwise indicated. walls. END OF SECTION ARCHITECT/ ENGINEER OF RECORD manufacturer. 3.3 CIRCUITS 3.6 FIRESTOPPING PART 2-PRODUCTS 2. Fitting and Accessory Material; Same as channels and angles, except metal items may be pail stainless steel. A. Branch Circuits:Type THHNITHWN, in raceway. A. Apply to cable and raceway penetrations of fire-rated floor and wall assemblies. Perform firestopping 2.1 MATERIALS 2.5 ACCESSORIES B. Class 2 and Class 3 Control Circuits:Type THHNITHWN, in raceway. as specified in Division 7 Section"Penetration Firestopping"to reestablish the original fire-resistance rating of the assembly at the penetration. A. Lighting fixtures are identified - the Drawings by type letters adjacent to the symbol on the Plan,or A. Sheet-metal sleeves: 0.0276-inch or heavier galvanized sheet steel, round tube,closed with welded 3.4 WIRING,RACEWAYS AND SUPPORTS by area location on the Fixture-Schedule.Fixtures are identified in the foregoing and Designated by longitudinal joint. 3.7 FASTENING manufacturers number on the Fixture Schedule and Drawings. Color and finishes to be as specified A. Damp Locations and Outdoors Supports: Hot-dip galvanized materials or nonmetallic,U-channel A. Unless otherwise indicated, securely fasten electrical items and their supporting in the Fixture Schedule. B. Pipe Sleeves:ASTM A 53,Type E,Grade A,Schedule 40, galvanized steel, plain ends. system components. ppnrting hardware to the building structure. Perform fastening according to the following: B. Alf fixtures shall comply with the rules and regulations of the CEC An material C. Expansion Anchors: Carbon steel wedge or sleeve type. B. Dry Locations Supports: Steel materials. 1. Fasten by means of wood screws or screw-type nails on wood;toggle bolts on hollow masonry required in connection with the installation of all fixtures in a rigid and efficient manner shally DESIGN D. units; threadedhate inserts studs,or spring-tensionpring bolts clampsn concrete on a solid masonry;and by machine screws, furnished and installed whether or not same is specifically mentioned herein.Wiring for final Toggle Bolts:All-steel springhead type. C. Strength of Supports:Adequate to carry all present and future loads,times a safety factor of at least welded re steel. 4;200-lb-minimum design load. connection shall be minimum#14 solid type THHN wire.All fixtures shall bear Underwriters' Architectural p E. Powder-Driven Threaded Studs: Heat-treated steel, 2. Threaded studs driven by a powder charge and provided with lock washers and nuts may be Laboratories labels. D. Install wires in raceway according to manufacturers written instructions and NECA's"Standard of used instead of expansion bolts, machine screws,or wood screws. Solutions G I 0 U F. Colored Adhesive Marking Tape for Raceways,Wires,and Cables: Self-adhesive vinyl tape,not less Installation." than 3 mils thick by 1 inch wide. 2so5oa 1 xwxx/xx 2605ao 2 XX/XX/XX 260500-3 XX/XX/XX 260500-0 XX/XX/XX 265000-1 ,�„�, 19120 SE 34TH STREET, SUITE 115 VANCOUVER, WA 98683 UXX These drawings and specifications are the confidential and proprietary property - - CHASE CHASE CHASE CHASE of JP authorization. Morgan Chase and shall not be copied or reproduced without written - CHASE authorization, The contract documents were prepared for use on this specific SECTION 260526 GROUNDING FOR ELECTRICAL SYSTEMS SECTION 260526-GROUNDING FOR ELECTRICAL SYSTEMS SECTION 260519-LOW VOLTAGE CONDUCTORS AND CABLES SECTION 260519-LOW VOLTAGE CONDUCTORS AND CABLES site in conjunction with its issue date and are not suitable for use on a deterrent SECTION 265000-LIGHTING site or ata later time. Use of these drawings For relerence or example on anothergproject requires the services of property licensed architects and -- - - - - i engineers. Reproduction of the contract documents far reuse on another project is not authorized. C. All fluorescent fixtures shall be provided with electronic ballasts of proper wattage,and voltage rating, high power factor Type"A"sound rating and ETUCBM approval. Ballast to incorporate all T 11. For panelboards,cabinets,wireways, switches and equipment assemblies, neatly form and tie A main building ground, bare copper conductor CEC sized but in no case less than#3/0,shall be run the wiring with sturdy cable ties and straps which will withstand substantial temperature rises PART 1 -GENERALD. internal protection.All 32 Watt R.S.ballasts shall be as manufactured by G.E.,Advance or Type "P"niversal, in conduit from the main service panel to a driven ground field outside the building.This ground shall PART 1 -GENERAL without becoming loose. be extended to the main water service metal pipe and to a main structural steel member of the 12. Branch circuit conductors shall be color-coded as follows: 1.1 RELATED DOCUMENTS D. Lamps:All lamps shall be furnished and installed by this Contractor. SEAL building. Provide a properly sized bonding shunt strap around the meter and all dielectric unions in the 1.1 DESCRIPTION 120(2A8 Volts Phase A. The General Conditions of the Contract for Construction,A.LA.,A201, Latest Edition,and the . ED P��F water pipe, A. Provide a completely grounded system.All electrical equipment,conduits,supports, Black F eq p pports,cabinets, A Supplementary General Conditions area PART 3-EXECUTION N G 1 N E `S'' E. Tests:The resistance between ground and absolute earth shall not exceed 25 ohms and shall be panelboards shall be grounded in accordance with theCEC and/or as shown on the Drawings.The Red Bpart of the Contract for this work. Contractor shall consult • O them and General Requirements, Division 1,for instructions pertaining to work under this Section. All A. Fixture T /- water measured by the Electrical Subcontractor in the presence of the Architect before equipment is placed intent is a system and an equipment ground. Blue C notes on the Drawings applying to this work are also a part of this Section. Types:The Contractor shall famish the various types of fixtures as indicated in the Fixture • 15,423 White Neutral Schedule on the Drawings. See Fixture Schedule for fixtures furnished by this contractor.All fixtures r in operation. B. Extent of Work is as shown on the Drawings or herein specified in Division 26. Green Ground 1.2 WORK INCLUDED shall be located to suit the Architectural details of the areas involved. 1.2 QUALITY ASSURANCE 13. Wire Pulling Lubricant: Use of wire pulling lubricant is optional, but if needed to prevent damage A. Furnish all labor, materials,tools and equipment, including incidental items required for a complete B. Recessed Fixture Installation: Recessed fixtures shall be of type suitable far mounting in the Pe of END OF SECTION to the conductors, it must be listed by Underwriters'Laboratories, Inc., and be of such and proper installation. ceiling as scheduled on the Drawings.Variations to catalog numbers indicated shall be made to ��: A. Codes and Standards: consistency that it will leave no obstruction nor tackiness that will prevent pulling out old wires or assure proper mounting and fitting arrangements, prior to fabrication O p 0. 1. NFPA 70. pulling in new wires or additional wires. 1.3 QUALITY ASSURANCEQ �O� 2. NEMA. 14, Conductors larger than#8 shall be thoroughly cleaned to bright metal and joined with indenture- C. Supports: ,� e 31, 3. U.L. Listed. A. All wire and cable shall be listed by Underwriters Laboratories, Inc.,and bear the Underwriters' 1. Each lighting fixture shall be rigidly su compression type connectors. Laboratories, Inc. (U.L.)label. g 9e pported from the building construction,and the Electrical ARK Rflg`S 04/14/20 15. Special attention shall be given to connections and terminations where dissimilar metals are Contractor shall wherebe responsible for providing suspension hangers,stems and extra steel work for PART 2-PRODUCTS used as copper to aluminum. Only the use of pressure type solderless connectors that are B. All conductors shall be not less than indicated on Drawings and not less than required by the CEC fixture support required. suitable for the use shall be installed. 2. Electrical Contractor shall confer with Ceiling Contractor to determine modifications required to C. All wire and cable shall be copper,98%conductivity,with 600 volt insulation. make fixtures suitable for ceiling as installed. 2.1 MANUFACTURERS 16. Prior to final inspection,test the installed cables and wires. Prior to energizing the wires and A. Connectors: cables,check them for correct connections and test them for short circuits,ground faults, 3. Where recessed fixtures are called for,each shall be provided with the proper plaster frame or ROBISON 1. Burndy Corp. 17. Final connections to all light continuity and insulation. PART 2-PRODUCTS suitable adapter to receive the finished ceiling construction. ENGINEERING, I N C fixtures shall be made with minimum#12 THHN solid copper wire. 2.1 MATERIALS 4. Where suspended acoustical tile ceilings on steel channels occur,outlets and fixtures shall be 2. O.Z. Electrical Mfg.Co. 18. Home runs over 100 feet for 120v, 1 phase shall have a minimum size of#10 AWG for home run, supported on members resting on the channel framework. In no case shall fixtures be supported 3. Buchanan Electrical Products Corp. 19. Main service and feeder connections shall be made using two bolt lugs with back washer. A. Wire and cable for building interior:Sizes#14 through#10 shall be from plaster or acoustic material. 940 4orri AVEw suiTE 3oz,L rrvNw000,wA 98036 4. Penn Union Electric. type THHNITHWN solid copper; 5. Suspended fixtures shall be hung on suspension hangers famished by the fixture manufacturer TEr-2o�3e4-3343 Fax:428350098 5. Anderson Electric Corp. 20. Minimum size branch circuit conductor shall be#12 AWG. sizes#8 and larger shall be type THHNITHWN or XHHW stranded copper. COrJTACT:SHANE Mcc�unE and shall be adjusted as necessary during installation to insure that all fixtures in the same room Ground rods; B. Where light fixtures are wired in continuous rows,wire pulled through fixtures shall be THHN 90 or area are at uniform height from the floor. Mounting height shall be as specified, detailed orB. 1SSlIE DATE DESCRIPTION 1. Anderson Electric Corp. END OF SECTION degrees Centigrade copper,600 volt insulation. noted on the Drawings.Any electrical lighting fixture that weighs more than 50 lbs shall be 2. Copperweld Corp. 2.2 MANUFACTURERS supported independently of the outlet box. 3. Penn Union Electrical Corp. A. Wire and cable to be Glenne Co.,Triangle, Rome or Phelps-Dodge copper products. D. Fixture Wiring: 2.2 MATERIALS 1. Fixtures shall be wired with white wire for the neutral and color wire for phase wires;See Section 260519(Low-Voltage Electrical Power Conductors and Cables.) A. Ground rods shall be copper weld rods 3/4"in diameter as specified or required length as noted on PART 3-EXECUTION 2. Housing of all fixtures must be grounded to conduit system the Drawings. 3.1 INSTALLATION 3. Each fixture to becomplete with holders, screws,sockets,wires, lamps,etc.,as is necessary for B. Connectors shall be industry standard type for connecting grounds, splicing,taping and the like. a complete installation. A. Wire and Cables: 4. Fluorescent lighting shall be wired as circuited on the Plan Drawings. C. Electrode cl ,connectors, mechanical lugs or wire terminals shall be used to bond ground wires 1. All wiring shall be installed in approved meta!raceway systems. together or aampsmpstion and panel boxes. matter.2. Wire shall not be installed in conduit or raceways until they are free from moisture and foreign E. Operation and Controls: 1. Local switches as shown and wired. 3. Where exterior conduits enter the inside of the building,the end of the conduit must be sealed 2. Panel switched lighting as indicated on Drawings. T 3-EXECUTION after all conductors have been installed. 3. Emergency lighting for egress purposes shall be provided. PAR3.1 INSTALLATION 4. All joints shall be made in boxes where they will be accessible. 5. Exit and directional signs shall be provided. Provide battery operated exit and directional signs 4. Momentary contact switches as indicated on the drawings. 5. Pull or junction boxes as required by the N.E.C. must be provided as required to facilitate g A. All contact surfaces shall be thoroughly cleaned before connections are made to insure good metal installation of conductors. where shown. 4-13-20 PERMIT SUBMISSION contact. 6. Support of vertical conductors shall be in accordance with the CEC 6. Provide emergency and exit lighting systems as required to conform to Code Emergency and B. Grounding conductors shall be so installed as to permit shortness and most direct path from 7. #8 and smaller conductor joints shall be thoroughly cleaned to bright metal and joined with exit lighting shall be provided on separate circuits where required. 4-3-20 9r]% SET equipment to ground;be installed in metal conduit with both conductor and conduit bonded at each indenture-compression or screw-on compression type connectors as permitted by the CEC• 3-20-20 PLANNING end; have connections accessible for inspection and made with approved solderless connectors Sizes shall be as recommended by the manufacturers of the connectors for the quantities and END OF SECTION sizes of wires being connected. braced(or bolted)to the equipment or structure to be grounded;in NO case be a current carrying conductor; have a green acket unless it is bare co 8. All exposed wires,clamps or connectors shall be completely insulated with vinyl plastic tape. PROJECT NFORMATION BLOCK i peer; be run in conduit with power conductors or in 9. All branch circuit wires shall be permanently identified with circuit numbers,securely fastened to DAT# JPM1901 Q.0 the case of multi-conductor cable run inside the cable sheath. JOB wire at cabinets at the time the wires are pulled in and tested. DATE: 112012020 10. I exterior grade mounted equipment shall have their enclosures grounded directly to a separate Sufficient wire shall be left at each junction box and outlet to accommodate future taps. Leave driven ground at the equipment in addition to the building ground connection.This includes grademinimum 6"loops or ends at each location. DRAWN BY: GH C. mounted light fixtures. CHECKED BY: PR MODEL 1 260526-2 XX/XX/XX 260526 1 XX/XX/XX 260519 2 XX/XX/XX 260519-1 XX/XX/XX 265000-2 XX/XX/XX DRAWING STANDARDS v20.1 SHEET TITLE SPECIFICATIONS SHEET NUMBER E7 . O 4• SAICCLURE F:\iHIA_GHASE BANKS\230-1674 CHASE SUNRISE &DOUGLAS - RANCHO CORDOVA, CA\DWG\E6-2DWG 07-25-2017 14;45 I I 111 , 1.111 In IY 0 U- U:C d w 1:Q 0_ L1J CC 0 1 ‘M 011111111% CO W tfl . rt) � 0 M � a WL- 0 L oQ .1wN CHASE CHASE CHASE CHASE CHASE 0LLI 110) ICC hy N SECTION 260531 -CONDUITS SECTION 260531 -CONDUITS SECTION 260531 -CONDUITS SECTION 260532-BOXES FOR ELECTRICAL SYSTEMS SECTION 260532-BOXES FOR ELECTRICAL SYSTEMS 9. For gang installations: Switches mounted in a common box for gang installation shall be so 5 Supply exposed conduits with galvanized metal straps or clips.Where grouped,conduit shaft be arranged that the voltage between adjacent switches does not exceed 300 volts,or permanent the necessary cutting and patching later,at his own expense and to the satisfaction of the neatly racked, supported by suitable trapeze or pipe hangers; run parallel with and at right angles PART 1 -GENERAL barriers must be installed between the adjacent switches. 0 0 Z 6. If Contractor does not properly install all sleeves and inserts required, he will be required to do ell) PART 1 GENERAL Engineer and Owner, to beams and walls. Perforated straphangers are not approved. 10. Mount all boxes at height shown on the drawings,or as directed. Q 1.1 RELATED DOCUMENTS 7. Do not obstruct openings or passageways. E. Flexible Conduit 1.1 RELATED DOCUMENTS 11. The approximate location of outlet boxes is shown on the Drawings, but care shall be taken to B. Where conduit passes through floors,or through smoke and fire walls, perform firestopping as 1. Provide liquid-tight flexible metallic conduit connections to all motors and movableequipmentA. The General Conditions of the contract for Construction AIA.A201, install all outlets with proper r Latest Edition,and the p pe elation to equipment or material to be installed by other trades. A. The General Conditions of the Contract for Construction,A.f.A.A201, Latest Edition,and the specified in division 7,section"Firestopping"as reestablish the original fire resistance rating of and where required toprevent transmission Supplementary 1111t , qss n of vibration or to permit flexibility for movement ofpart the Contract for this work. Contractor shall consultV PP ry General Conditions area a12. Where required by local code, provide special gasketed outlet boxes with special knockouts in Supplementary General Conditions are a part of the Contract for this Work.Contractor shall consult the assembly at the penetration. equipment. them and the General Requirements, Division of for instructions pertaining to work under this Section. plenum ceiling areas. them and the General Requirements, Division 1,for instructions pertaining to work under this Section. 9. Radius of bends shall be not less than six(6)internal diameters.Any run of conduit shall not 2. Flexible connections to recessed fixtures in drylocations All notes on the drawings applying Ce may be flexible metallic tubing without 9 PP Yrng to this work are also a part of this section. 13. In Fan and Machinery Rooms and areas,exact locations and mounting height of fixtures shall be notes on the Drawings applying to this work are also a part of this Section. include more than the equivalent of three(3)quarter bends. Provide pull box if a greater number liquid-tight jackets. coordinated so reas tor clear ail ducts,fan housings,tanks,pipes,etc.,and obtain l bue runrm light Hi 4 a 1.2 WORK INCLUDED distribution;therefore,all outlets and conduits serving same in these rooms shall be run exposed All 1.2 WORK INCLUDED of bends are required. 3. Provide bonding jumper wire where required by code. 10. All conduits shall be concealed,except where specifically indicated as exposed. 4. Where required by local code, provide liquid-tight flexible conduit in plenum ceilingareasA. Furnish all labor, materials,tools and equipment, iin a neat symmetrical for n,an as incidental items required for work of this Y manner after this equipment is installed in place. A. Furnish all labor, materials,tools and equipment,including incidental items required for work of their 11. Outside diameter of any conduit run in concrete slab shall not exceed 113 of thickness of slab. connection to lighting fixtures,speakers, etc. Section as shown on the drawings,specified herein,and required for a complete and proper N Section as shown on the Drawings specified herein,and as required for a complete and proper 12. Install accessible pull boxes in all conduit runs exceeding 150 ft. installation. ZCI F. Surface Metal Raceway: 1. Furnish and install outlet boxes as called for,where required and as shown on the Drawings. END OF SECTION 0 installation. 13. All conduits install under concrete slab in grade shall be encased in 3"concrete envelope. 1, Where indicated on the Drawings, provide surface metal raceways with associated fittings, O 1. Furnish and install conduits for all wiring of type called for and as required for this project. 14. Conduits crossing building expansion joints shall be provided with approved groundingboxes,devices and supports as manufactured by Wiremold,Walker Duct or National Electric Co. 1.3 QUALITY ASSURANCEuu ...1 iict NMI Z O expansion fittings where theyRaceways shall be sized in accordance with NEC to accommodate the number and size of 1.3 QUALITY ASSURANCE 15. Undergroundndcoconduits shaoltlcross be blolown and swabbed before conductors are pulled.s these joints. 2. hll A. Dimensions shall be not less than required by CEC and not less than indicated on the drawings. 16. Provide fish wire in elf emptyconductors being installed. A. All conduits shall bear label of the Underwriters'Laboratories, Inc.,and sized in accordance with the '/2and spare conduits. B. Underwriters'Laboratories, Inc. shall list all outlet boxes, CEC Cn r.. 17. Conduit shall be a minimum of 1/2". 18. All wiring shall be run in conduit.Where heavy wall galvanized rigid steel(GRS)is not required, END OF SECTION Z thin wall(EMT)may be used. PART 2-PRODUCTS I• PART 2-PRODUCTS 19. Provide concrete encasement of service conduits when required by local authorities and/or utilityIMI 2.1 MATERIALS 2.1 MATERIALS companies. ICC 20. Install raceway sealing fittings according to the manufacturers written instructions. Locate fittings A. Boxes shall be 12 gauge or heavier steel, sheradized or galvanized to prevent rusting and shall have A. Conduit: at suitable, approved,accessible locations and till them with UL-listed sealing compound.For readilyble k 1. Galvanized rigid steel(GRS): Hot dipped galvanized rigid steel with threaded ends.Meet ASTM concealed raceways, install each fitting in a flush steel box with a blank cover plate having a `r removanockouts. Cast metal boxes shall be rustproof. standard A-153 galvanized after fabrication. finished similar to that of adjacent plates or surfaces. Install raceway sealing fittings at the B. Boxes shall: 2. Intermediate Metal Conduit(IMC): Rigid mild steel tube with welded seams, hot dipped following points and elsewhere indicated: 1. Match conduit construction. 0 1 3. galvanized with threaded ends. a. Where conduits enter or leave hazardous locations. 2. Be provided with more conduit terminations than required. I Thin Wall: Electro-galvanized electrical metallic tubing(EMT). b. Where conduits pass from warm locations to cold locations,such as the boundaries of 3. Accommodate required joints and conductors. 4. Flexible: Hot dipped galvanized material of mild steel of uniform width and thickness. refrigerated spaces and air-conditioned spaces. 4. In or on wall(not WP)-galvanized steel one gang box for one conduit termination;two gang 5. Flexible Liquid Tight: Hot dipped galvanized material of mild shell of uniform width and thickness c. Where otherwise required by the National Electrical Code. boxes or larger or deep masonry box for conductors,conductor joints and conduit terminations; with extruded moisture and oil proof PVC jacket. cover as required for device. A. Conduit Fittings: B. Cuffing: 5. In or on ceiling(not WP)-galvanized steel;4"octagonal(or larger)for one fixture; fixture studs; RS Conduit:Threaded type, Measure and cut conduit from job site conditions, not from Drawings. supported independently of conduit. ARCHITECT/ENGINEER OF RECORD 6. G7. IMC Conduit Threaded 2. Conduit shall be cut square, reamed and butted solidly into fittings. 6. In or on walls of damp locations, rooms below 50 degrees F, in or on exterior side of wall,floor or type 3. Onr GRS and!MC conduit,cut tothreadfull and clean with sharp dies. Ream ends of pipe after roof-gasketed,watertight(WP),galvanized, cast iron or non-ferrous. 8. Thinwall or EMT: Rain tight and concrete tight,gland compression type, insulated nylon throat adingGRS and MC re assembly remove ndrrs, with die-cast body and steel nut,Appleton type 86T series or equal. For conduit sizes 3"and 4. Ream thin-wall conduit(EMT)after it is cut. 2.2 MANUFACTURERS larger(where not required to be rain or concrete tight)set-screw type is acceptable. 5. Use tapered threads where conduit cannot be coupled using standards couplings;use OZ or 9. Flexible Conduit:Single or two piece squeeze type. A. Outlet boxes to be Appleton, Raco or Steel City Erickson split 10. Flexible Liquid Typo:Compression type. 6Threaded joints in pe lconcrete slabs or underground shall receive a coat of pipe sealant or pipe 2.2 MANUFACTURERS jointing compound.. PART 3-EXECUTION A. Conduit to be Republic Steel Corporation,Triangle,Youngstown Sheet and Tube, or Allied. 7. All conduit ends shall be plugged with an approved device to prevent the entrance of foreign 3.1 INSTALLATION DESIGN material. B. Conduit fittings to be Appleton Electric Co., Raco, Inc.,or Thomas&Betts Co. A. Outlet Boxes: C. Type of Conduit: Conduit buried in floors on or below grade,service conduit, and conduit on building exterior or exposed to moisture shall be GRS or IMC;other conduit may be IMC or thinwall(EMT). 1. Boxes for concealed conduits and EMT shall be flush mounted. Other boxes may be flush or surface type. Architectural PART 3-EXECUTION Conduit must be installed as a complete system,continuous from outlet to outlet and shall be 2. Install plaster rings at plastered surfaces. mechanically and electrically connected.The entire conduit system must be grounded. Minimum size 3. install tile cover rings(extensions)for devices at non-plastered surfaces. Solutions Group 3.1 PREPARATION,INSTALLATION,APPLICATION conduit shall be Y inch conduit. 4. In addition to boxes indicated, install enough boxes to prevent damage to cables and wires A. Conduit Installation-Conduit Layout: D. Supporting of Conduit: during pulling operations. 1. Where conduit is exposed,give special attention to appearance of completed installation. 1. Supports to be at least ten feet(10')maximum intervals. 5. Remove only knockouts as required and plug unused openings. Use threaded plugs for cast 19120 SE 34TH STREET, SUITE 1 15 2. Run parallel or perpendicular to exterior walls of buildings. 2. Conduit to be independently supported from building structure and not from water piping, metal boxes and snap in metal covers for sheet metal boxes. 3. Locate to avoid equipment,fixtures,ductwork,piping, etc. ductwork,etc. 6. Boxes shall be supported independently of conduit. VANCOUVER, WA 98683 4. Lay out and install work in advance of the laying of floors,walls, etc.,and furnish and install all 3. Conduit shall be installed to avoid moisture traps. 7. Fit boxes into available space,construction and surface materials. sleeves that may be required for openings through floors,walls,etc. 4. Where conduit is to be installed in poured concrete floors or walls,securely fasten conduits to 8. For additional conduit termination,more conductors and more conductor joins, provide additional ,hese drawings and specifications are the confidential and proprietary props y 5. Where Plans call for conduit to be run exposed,furnish,and install all inserts and clamps for the boxes in keeping with code requirements. Thof h Morgan Chase and shall not ntbe copied e erredreprf use without Pewristen supporting of conduit. p forms or reinforcing to prevent conduit misplacement. authorization. The contract documents were prepared for on this specific site in conjunction with its issue date and are not suitable for use on a different site or at a later lime. Use of these drawings for reference or example on 260531-1 XXIXXIXX 260531-2 XX/XX/XX 260531 3 XX/XX/XX 260532-1 XX/XX/XX 260532-2 XX/XX another project requires the services of property sforlicensed architects and engineers. Reproduction of the contract documents for reuse on another project isnot authorized. SEAL .,p PRQ1c CHASE • `., G j N Ee„i, G CHASE 15,423 CHASE SECTION 260534-SWITCHES AND RECEPTACLES i CHASE SECTION 260533-PULL AND.!UNCTION BOXES CHASE SECTION 260534-SWITCHES AND RECEPTACLES SECTION 262813-FUSES SECTION 262001 LOW-VOLTAGE ELECTRICAL DISTRIBUTION B. Receptacles shall be: AO: •. 1. Duplex Convenience Receptacle(Fed. Spec,WC-590-F). PART 1 -GENERAL PART 1 -GENERAL qR 31, `)-09p� 15 AMP Devices(NEMA#5-15R1 20 AMP Devices(NEMA#5-20R1 kR 0�S PART 1 -GENERAL PART 1 -GENERAL P&S #5262 P&S #5362 1.1 RELATED DOCUMENTS 1.1 RELATED DOCUMENTS 04/14/20 A. Submittals:Submit product data according to the Conditions of the Contract and Division 1 1.1 RELATED DOCUMENTS Hubbell #5262 Hubbell #5362 A. The General Conditions of the Contract for Construction,A.I.A. A201, Latest Edition,and the A. The General Conditions of the Contract for Construction,A.I.A.A201,Latest edition,and the Eagle #5262 Eagle #5362 Supplementary General Conditions are a part of the Contract for this work. Contractor shall consuit Supplementary General Requirements, iv" Specification Sections. A. The General Conditions of the Contract for construction,M.A.A201, Latest Edition,and the Supplementary General Conditions area 2. Isolated Ground Type Duplex Receptacle PP rYDivision 1,for instructions pertaining to work under this B. Comply with NFPA 70"National Electrical Code"for components and installation, part of the Contract for this work.Contractor shall consult 15 AMP Devi NEMA#5-15R1 20 AMP Devices NEMA#5-20R). Aero and one General gs applying Division 1,ler instructions is Section. to work under this Section. Section.All notes on the Drawings apply to this work re J J PP Y a also part of this Section. ROBISON them and the General Requirements,Division 1,for instructions pertaining to work under this Section. P&S All notes on the Drawings applying to this work are also part of this Section. 1.2 WORK INCLUDED C. Listing and Labeling:Provide products specified in this Section that are listed and labeled. All notes on the Drawings applying to this work are also a pari of this Section. P&S #IG6200 P&S #lG6300 1. The Terms"Listed"and"Labeled":As defined in the"National Electrical Code,"Article 100. Hubbell #IG5262 Hubbell #IG5362 1.2 WORK INCLUDED A. Famish all labor, materials,tools,and equipment,including incidental items required for work of this ENGINEERING, INC 2. Listing and Labeling Agency A"Nationally Recognized Testing Laboratory" 1.2 WORK INCLUDED Eagle #IG5262 Eagle #lG5362 A. Furnish all Tabor, materials,tools and equipment, including incidental items required for work of this Section as shown an the Drawings,specified herein,and as required far a complete and proper 3. GFI Receptacle p p 19401 40Trt AVE W SuirE 302,LYNNwOOD,WA 98036 (NRTL)as defined in OSHA Regulation Qualifications:1910.7, A. The work under this section of the specifications includes the furnishing of all labor,equipment, Section as shown on the Drawings, specified herein,or as required for a complete and proper installation, TEL:206 364 3343 FAX:4258350098 material and performing all operations for the connection and installation of all distribution systems as 15 AMP Devices(NEMA#5-15R] 20 AMP DPvicesfNEMA#5-20R1 installation. 1.3 QUALITY ASSURANCE CONTACT:SHANE MCCLURE shown on the drawings hereinafter s ecified. P&S #1591-FI P&S #2091-F 1. Provide wiring devices as scheduled herein and as called for on the Drawings. PART 2-PRODUCTSg p Hubbell #GF-5262-I Hubbell #GR-5362 g Dimensions shall be not less than required by CEC and not less than indicated on the Drawings. ISSUE DATE DESCRIPTION 1.3 SUBMITTALS Eagle #646-2 Eagle #647-2 2. Provide device plates for all wiring devices. A. Cartridge Fuses:NEMA FU 1 nonrenewable cartridge fuse,class as specified or indicated,current A. Underwriters'Laboratories,Inc.standards shall apply. rating as indicated,voltage rating consistent with circuit voltage. A. Shop Drawings for all distribution equipment shall be submitted fora approval. 1.3 QUALITY ASSURANCE PP C. Wolf plates shall be: 1. Motor Branch Circuits:Class RK1 time delay. 1. P&S 2. Other Branch Circuits:Class RK5 non-time delay. B. Shop Drawing shall include the following: A. Wiring devices shall be Underwriters'Laboratories, Inc.listed and ratedper PART 2-PRODUCTS 1. Panelboards. 2. Hubbell CEO. 3. Eagle 2.1 MATERIALS Dimensions. PART 2-PRODUCTS 2.PART 3-EXECUTION 3. Material and construction. A. Boxes shall be made of galvanized sheet steel of code thickness with screw covers,unless otherwise A. Install fuses in fusible devices as required.Arrange fuses so that fuse ratings are readable without Contactors4. and relays. PART 3-EXECUTION 2.1 MATERIALS specified_ removing fuse. 3.1 WIRING DEVICE INSTALLATION A. Wall Switches: Single unit,toggle, butt contact,quiet type with integral mounting strap,rated for 15 or B. Boxes shall be cast metal where required by code or where indicated on the Drawings.Cast metal PART 2-PRODUCTS 20 amps, 120/277 volts, installed 48 inches above finished floor,or as noted,(specification grade). boxes shall be rustproof. B. Install typewritten labels on the inside door of each fused switch to indicate fuse replacement A. Each outlet, device or piece of equipment of every kind shall be located approximately as called for information. 2.1 PANELBOARDS and as directed. Outlet locations shall be checked for interference with all plumbing,heating, B. Receptacles: 2.2 MANUFACTURERS 1. Duplex convenience receptacles shall be polarized grounding type, rated 20 amps at 120 volts A. Junction and A. Panelboards shall be dead front,dead rear flush-mounted or surface-mounted as noted on the ventilating,other work and with Architectural Drawings.Outlets must be located in harmony withpull boxes shall be Appleton,Arlington Sheet Melat Corp.,Crouse-Hlndes,EPI-Electrical END OF SECTION drawings with main circuit breaker,main lugs and branch circuit breakers as shown on panel architectural design of ceilings,wall sand floors.Switches shall be located on latch side(jamb)of and installed 15"above finished floor, unless noted otherwise(specification grade). Enclosures or Hoffman. schedule, hinged,lockable doors,typewritten index card-holders,proper bussing and main lugs, door. Receptacles must be located to avoid interference with all other equipment provided under all 2. Isolated ground receptacles,equipment grounding contacts are connected to the green groundingrscrew terminal of the device and have inherent electrical isolation from the mounting double lugs or main breakers as required. Lugs shall be sized for feeders. other divisions. s B. a pPART 3-EXECUTION 4-13-20 PERMIT SUBMISSION Devices: Listed and labeled as isolated shall be copper,full panel height,and shall be rigidly supported with bus supports and all B. Any outlet and/or device,which does not conform to the above, shall be relocated by the Electrical a. ground receptacles. phase busses shall be identified.Solderless,silver-plated lugs shall be provided for all required cable Contractor at no increase in Contract price. bIsolation Method: Integral to the receptacle construction and not dependent on removable 3.1 INSTALLATION 4-3-20 90% SET connections.Minimum bus rating shall be as large as the setting of the feeder protective devices. parts. Incoming service panelboard shall be service entrance labeled and braced for a minimum interrupting C. Unless otherwise noted or directed, switches, receptacles,devices etc., shall be carefully recessed 3. Ground-fault circuit interrupter(GFCI)receptacles, UL standard 943,"Ground A. Junction and Pull Boxes: capacity of 42,000 amps RMS.Actual available short-circuit current to be coordinated with utility with boxes and plates properly arranged to cover all cracks or spaces between box and wall finish. Fault Circuit 1. Pull or junction boxes shall be installed in all conduit runs having the equivalent of three(3)90 3-20-20 PLANNING Interrupters",feed-through type,with integral NEMA 5-20 R Duplex receptacle. bends,and/or more than 150 feet in length.This shall be the minimum requirement.Additional company and adjusted accordingly. D. All outlets 15"above floor shall be mounted horizontally.All outlets mounted 48"and higher shall be C. Wall Plates: pull boxes shall be installed as required for a workmanlike job and/or as to prevent damage to PROJECT INFORMATION BLOCK Provide oversize gutters for feed-through,where indicated1. Plates for boxes, switches, outlets,devices,etc., in all finished areas shall be identical and shall cables and wires during pulling operations. permitted by local code,provide suitable pull box or gutter required.Where double lugs are not mounted vertically.All receptacles above counter-top height shall be mounted horizontally and adjacent to panels for connections. switches above counter-top height shall be mounted vertically. be of white high impact plastic material, unless noted otherwise or as directed. 2. Install pull or junction boxes concealed except in unfinished areas or exposed work. JOB# JPM 19010.0 D. All panelboards shall have flush catch and corbin lock and shall be keyed to operate from one key. E. Switches shall be installed maximum 48"to top of switch plate. 2. Plates in unfinished areas shall be galvanized steel. 3. Field drill the boxes for conduit sizes and locations as required. DATE: 1/2012020 E. panelboard trim and door shall be finished shop prime where exposed to public view(e.g.,corridors, 3. Plates in toilet areas shall be stainless steel. 4. All cables entering or leaving metal boxes shall be protected by the use of insulated throat bushing and double lockouts on GRS or IMC conduit,and by insulation throat box connectors for DRAWN BY: GH offices,etc.)and hammertone gray in equipment rooms. END OF SECTION D. Device Color: Ali wiring devices shall be white in color, unless noted otherwise or as directed. Final EMT conduit. CHECKED BY: PR F. Panelboards(other than the service entrance panelboard)shall incorporate circuit breakers with a color selection to be coordinated with the Architect prior to ordering devices. 5. Common boxes used for gang installation shall include barriers between power and low voltage minimum interrupting rating of 10,000 AMP RMS. 2.2 MANUFACTURER'S&CATALOG NUMBERS circuits. G. Lighting Panel.Shall have galvanized cabinets with a minimum width of 20".Rating shall be of the A. Wall Switches(Fed. Spec. WS 896E). MODEL voltage,phase and number of wires as indicated on schedules and panel shall have a solid neutral 1, Single pole,toggle type: END OF SECTION bar. 15 AMPDevi ,c 20 AMP Devices DRAWING STANDARDS v20.1 H. Circuit Breakers.Shall be automatic,molded case,trip free,quick-make,quick break,thermal- #1221 or#1201 Hubbell #1221 P&S #20AC1 P&S #20AC1 magnetic type, bolted to the bus,with handles clearly indicating tripped position.Breaker handles shall indicate size.Breakers shall be of size and arrangements as shown on schedules.Multiple Eagle #1201 Eagle #2221 SHEET TITLE breakers shall have common internal trip.Breakers shall be sequenced phased with odd numbers on 2. 3-way toggle type: the left and even numbers on the right. 15 AMP Devices 20 AMP Devices P&S #20AC3 P&S #20AC3 SPECIFICATIONS Hubbell #1223 Hubbell #1221 Eagle #1203 Eagle #2223 262813-1 XX/XX/XX 262001-1 XX/XX/XX 260533-1 X?U)CX1XX 260534-2 XX/XX/XX 260534-1 XX/XX/XX SHEET NUMBER E7 • 1 r S&4CCWRE F:\J*L\_CHASE BANKS\230-1674 CHASE SUNRISE &DOUGLAS - RANCHO CORDOVA, CA\DWG\E6-3.DWG 07-25-2017 14:45