SUBMITTAL DATA
Order#: Date: 07/26/2021
Project: Cost Plus World Market
Project#: NN07262103
Submitter: Noah Noaker
North West Branch Region(UST/IPA)
22745 29th Dr. SE Ste-100,
Bothell, Washington 98021
425-398-6997
CITY OP TIGABfl
REVIEWED FOR CODE COMPLIANCE
Approved I
OY
OTC: [ j
Permit#: rnP a1 � fl<) '7 et 7
Address: 0 4 io W ‘ck,
Suite#:
• By: Date: Jo -21 -.2'
VALIDITY OF PERMIT
THE ISSUANCE OF A PERMIT
BASED ON CONSTRUCTION
DOCUMENTS AND OTHER
DATA SHALL NOT PREVENT
THE CODE OFFICIAL FROM
REQUIRING THE CORRECTION
OF ERRORS. OSSC 105.4
Information is subject to change without notice.Check local codes. Printed 07/26/2021
W . ..
Date
07/26/2021 , •,
- Project Name
Cost Plus World Market
Johnson ,A'•
Project Number Controls
NN07262103
Client/Purchaser
Submittal Summary Page
Qty Tag# Model#/Material# Description
1 Direct Repl- XN060C00A2C1AAA1A1 5 Ton, Single Packaged R-410A Heat Pump, Two Stage Cooling,
On Order- 11.0 EER/ 14.0 SEER, 208/230-3-60, Factory installed Dry Bulb
ETA to Fife Economizer and Hood (No Barometric Relief Damper)with
Branch-Sept Economizer Fault Detection & Diagnostic(Meets ASHRAE 90.1-
15th 2013, IECC 2015, California Title 24,AMCA 511), 1 HP Direct Drive
Blower, Direct Drive, Indoor Fan Motor wNFD, 1" Throwaway
Filters, Smart Equipment Controller including Discharge Air, Return
Air, and Outdoor Air Temperature Sensors., Copper Tube/Aluminum
Fin Condenser Coil, Copper Tube/Aluminum Fin Evaporator Coil,
Galvanized Steel Drain Pan, Standard Access Doors
1 2EH04511025 10 kW 208/230-3 Electric Heat-Field install
1 1 RD0410 Barometric Relief Damper with Hood Kit(Downflow Unit or Duct
Mounted)
NOTES:
McKinstry Co-Brian Erdahl
Equipment start-up and commissioning by a factory trained technician is recommended.
Contact your supplying distributor or sales representative for additional information &guidance.
WARNING:Cancer and Reproductive Harm-www.P65Warnings.ca.gov
Information is subject to change without notice.Check local codes. Printed 07/26/2021
Small Sunline 3-6 Ton Page:3
iill
YORK Package
York Single Package R-410A Heat Pump
r Project Name: Cost Plus World Market Unit Model#: XN060C00A2C1AAA1A1
I Quantity: 1 Tag#:Direct Repl-On System: XN060C00A2C1AAA1A1
Order-ETA to Fife Branch-Sept 15th
Cooling Performance
Total gross capacity 58.4 MBH
Sensible gross capacity 43.3 MBH fl , #,
Total net capacity 55.3 MBH
Sensible net capacity 40.2 MBH �/r
Seasonal Efficiency(at ARI) 14.00 SEER �'' a1"!ft€.i.
Efficiency(at ARI) 11.00 EER ' ., o;;o t 4' I
Ambient DB temp. 91.8 °F l )Z jtji ELF
Entering DB temp. 80.0 °FtI rl)f,: £
Entering WB temp. 67.0 °F
Leaving DB temp. 59.1 °F t IA
Leaving WB temp. 57.4 °F "
Leaving air temp dew point 56.30 °F a. ''/,.
Power input(w/o blower) 4.20 kW Iltiiki4, i k I
Sound power 80 dB(A) ,I /
Refrigerant """ i"" `,,,
Refrigerant type R-410A
Sys1 11 lbs 10 oz
Heat Pump Performance 5 Ton
Ambient DB temp. 47 °F • York Units are Manufactured at an ISO 9001 Registered Facility and Each
Design Gross Capacity 52.4 MBH Rooftop is Completely Computer-Run Tested Prior to Shipment.
Design Power Input 3.49 kW Unit Features
HSPF 8 • Two Stage Cooling
Capacity @ 47°F 51.50 MBH • Either Supply and/or Return can be Field Converted from Vertical to
COP @ 47°F 3.35 Horizontal Configuration without Cutting Panels.
Capacity @ °F 32. 4 MBH
COP @ 17°FF 2.14
• Full Perimeter Base Rails with Built in Rigging Capabilities
Applied electric heat 8 kW • Unit Cabinet Constructed of Powder Painted Steel,Certified At 750 Hours
Heating Performance Salt Spray Test(ASTM B-117 Standards)
Entering DB temp. 60 °F • Scroll Compressor
Heating output capacity(Max) 27.3 MBH • Dry Bulb Economizer and Hood(No Barometric Relief Damper)with
Nominal electric heat 10 kW Economizer Fault Detection&Diagnostic(Meets ASHRAE 90.1-2013, IECC
Applied electric heat 8.0 kW 2015,California Title 24,AMCA 511)
Installed Field • Indoor Fan Motor wNFD
Supply air 1922 CFM • 1 HP Direct Drive Blower
Leaving DB temp. 73.1 F
Air temp.rise 13.1 °F • Unit Ships with 1"Throwaway Filters
Stages 1 • Solid Core Liquid Line Filter Driers
Supply Air Blower Performance • Replacement Filters:2-(15"x 20"x 1"or 2")and 1-(14"x 25"x 1"or 2").
Supply air 1922 CFM Unit accepts 1"or 2"wide filters.
Ext.static pressure 0.6 IWG • Through-the-Curb and Through-The-Base Utility Connections
Addl.Unit Losses(Options/Accessories) 0.25 IWG • Short Circuit Current:5kA RMS Symmetrical
Blower speed 1117 RPM • Single Point Power Connection
Blower speed description HI • Copper Tube/Aluminum Fin Condenser Coil,Copper Tube/Aluminum Fin
Duct location Bottom
Motor rating 1.00 HP Evaporator Coil
Actual required BHP .99 HP • Galvanized Steel Drain Pan
Power input 0.92 kW • Standard Access Doors
Elevation ft.
Drive type DIRECT Standard Unit Controller: Smartq P E ui ment Control Board
p
Speed tap 5 • An Integrated Low-Ambient Control,Anti-Short Cycle Protection,Lead-Lag,
Electrical Data Fan On and Fan off Delays,Low Voltage Protection,On-Board Diagnostic
Power supply 208-3-60 and Fault Code Display.Allows all units to operate in the cooling mode down
Unit min circuit ampacity 58.8 Amps to 0°F outdoor ambient without additional components or intervention.
Unit max over-current protection 60 Amps • Safety Monitoring-Monitors the High and Low-Pressure Switches,the
Dimensions&Weight Freezestats,the Gas Valve,if Applicable,and the Temperature Limit Switch
Hgt 33 in. Len 83 in. Wth 45 in. on Gas and Electric Heat Units.The Unit Control Board will Alarm on Ignition
Weight with factory installed options 675 lbs. Failures,Safety Lockouts and Repeated Limit Switch Trips.
Clearances BAS Controller
Right 24 in. Front 24 in. Rear 12 in. • Smart Equipment Controller including Discharge Air,Return Air,and Outdoor
Top 72 in. Bottom 0 in. Left 24 in. Air Temperature Sensors.
Note: Please refer to the tech guide for listed maximum static pressures Warranty
• One(1)Year Limited Warranty on the Complete Unit
rr-.
AMERICAN. I • Five(5)Year Warranty-Compressors and Electric Heater Elements
M�CERTIFIED-*nu +c,.,.aT,
o.:......
Information is subject to change without notice.Check local codes. Printed 07/26/2021
Small Sunline 3-6 Ton Page:4
PORK® Package
York Single Package R-410A Heat Pump
Project Name: Cost Plus World Market Unit Model#: XN060C00A2C1AAA1A1
Quantity: 1 Tag#:Direct Repl-On System: XN060C00A2C1AAA1A1
Order-ETA to Fife Branch-Sept 15th
Factory Installed Options
XN060C00A2C1AAA1A1
Equipment Options Option(s) Selected
Product Category: XN Single Packaged R-410A Heat Pump
11.0 EER/14.0 SEER
5 Ton
Nominal Cooling Capacity: 060
Two Stage Cooling
Heat Type and Nominal Heat Capacity: COO
1 HP Direct Drive Blower
Blower Option: A Direct Drive
Indoor Fan Motor w/VFD
Voltage: 2 208/230-3-60
Dry Bulb Economizer and Hood(No Barometric Relief
Damper)with Economizer Fault Detection &Diagnostic
Outside Air Option: C
(Meets ASHRAE 90.1-2013, IECC 2015, California Title
24,AMCA 511)
Service Options: 1
Sensor Options: A
Smart Equipment Controller including Discharge Air,
Controls: A
Return Air,and Outdoor Air Temperature Sensors.
Refrigeration: A
Copper Tube/Aluminum Fin Condenser Coil, Copper
Tube/Aluminum Fin Evaporator Coil
Additional Options: 1 1"Throwaway Filters
Galvanized Steel Drain Pan
Cabinet Options: A
Standard Access Doors
Product Generation: 1
Field Installed Accessories
• 2EH04511025- 10 kW 208/230-3
Electric Heat(16.0 Ibs)
• 1 RD0410- Barometric Relief
Damper with Hood Kit(Downflow
Unit or Duct Mounted) (6.0 lbs)
Information is subject to change without notice.Check local codes. Printed 07/26/2021
R,./6- Small Sunline 3-6 Ton Package gage:
�RK5
York Single Package R-410A Heat Pump
Project Name: Cost Plus World Market Unit Model#: XN060C00A2C1AAA1A1
Quantity: 1 Tag#: Direct Repl-On Order-ETA to Fife
Branch-Sept 15th
Consolidated Drawing
a ., , 1 1? 1 Id 15 I:.
T CENTER OF GRAVITY
/ICSTOR OUTDOOR USE CI.• N ' ODERATING 1 LOCATION (BASE UNI"1 4 POINT CORNER LOADS tLB51 (SASE SNIT(
IIONNA6E I Rt IG M' (CR51)
2. WE2GNTS SHOWN ARE :I' COOLING ONLY UNITS. T (BASE UNIT( 6 Y A B C D
? MIN. CLEARANCES T!) 1 R 3 IE118 470 12131 34.5 1876,31 8 25 1443,63 III E501 80(343 1.1 :531 62 (731
RIGHT SIDE: 24 16-• 61 -31.62
LEFT SIDE; 24 (6i9 61 (LESS ECONOMIZER) 1 IE/70 598 12711 36 1114.43 18.50 1469,11 139 1631 108 1493 154 i701 :RS (90)
36 t914,41 (WITH ECONOMIZER) [803,37
[ �•�„-6 12 5 ECM 632 Heil 37.5 19 R,51 18.2 t462,33 139 MI 1171533 171 :181 2041931
FRONT. 24 1609.61 (COOLING!ELECTPIC HEA`1
32 1812,81 (SAS NEAT, '155,51 6 I£1ID 655 13021 15,5 190.71 i7.731450.61 1301601 ILA 1521 1'3 :761 226 11031
HLAH: 12 1304,81 (LESS ECONOMILERI 7.25 --.- 18.26 3 59/KT 610 (2711 18.3 1912,81 '8.15 14 6.11 106 1621 119 1541 165 :151 90 I861
J 36 (914,41 (WITH ECONOMIZER OR FAXED 1154.01 (463.71 4 YN/YT 616 (2791 38.2 1974,31 18,4 :467,41 135(611 117 (531 169 :771 '.95(881 3
AIR/MOTORIZED DAMPER)
TOP. 72 11828.81 1.80 ..-27.54 I 5 Y9/81 620(2611 18.6 1984,41 16 [457,21 132 (661 117 1531 1'4 :191 :97 1891
BOTTOM; 0 (01 (45,81 (699,61
4. FOR SMALLER SERVICE AND OPERATIONAL CLEARANCES
CONTACT YOUR APPLICATION ENGINEERING DEPARTMENT. I REAR
5. DOWNFLOW DUCTS DESIGNED TO BE ATTACHED TO ACCESSORY
ROOF CURB ONLY IF UNIT IS MOUNTED SIDE SUPPLY, IT
H IS RECOMMENDED THAT -HE DUCTS ARE SUPPORTED BY -5.89 H
CROSS BRACES, AS DONE ON ACCESSORY ROOF CURBS. 5 51 `` 1149,6
N. SIDE DUCT FLANGES ARE 0.875' 122,21 HIGH. (140,01 i A T
BOTTOM DUCTS CO NOT NAVE FLANGES. ,, ,
1. MINIMUM CONOENSA11ON TRAP HEIGHT SHALL BE 1.5 TIMES 1-
THE LOWEST NEGATIVE STATIC.
8. DIMENSIONS N I 1 ARE IN MILLIMETERS OR KI'_OGRAMS. f ; 12.26 1 PI II 50 '
9. OP(10NAL CO GUARD, GAS HEAT, ECONOMIZEH HOOD, POWER HIRING 16 1311,31 I vi 1292,11 i - -
OUTLET/INLE' HOOD SHOWN. BETTOR ENTRY N___ ___: r ___1-.-- l�:
'
G DISCONNECT SWITCH, CONVENIENCE OUTLET, AND
Yp2.00 [5D,8) 1 --� I' 50 " NHT r
A EXCEPT NNWIHEA1 PUMP) UNITS. 4.00 co /[d44,51 • 11,30
E101,61 1 I • 578,
I;II I;. E
orA 7627 1292,11
F -i► DIRECTION OF AIRFLOW Y • I.
tfl 73 R.�'-.-5 I RETU6N , 11.59 19.12
:209,21 ! 11• 0/0 �` 1292.11 1485.8;
S CENTER OF GRAVITY t D/////fr
I l' SUPPEY
II06 6.48 Lr������-L-1
L64.71
[281,0] 650
CONTROL WIRING BOTTOMFNTRY-
32.09 AS SUPPLY BOT'ON ENTRY 01.50 138,11 N.O. 165 }
(165,1; 11111 4,62
F 00.88 [22,21 1815,21 (0 50 (12,71 NPT AT GAS VALVE 11.50 }- - 7,62 (1�1,5]
[444,5J 1193,67 F
ECONOMIZER HOOD yS'.9! S.U. VENT AIR OUTLET HOOD A 14,40 31.62 -+[444 5J [803,21
(OPT OVAL) :50,01 / OMBUSTION AIR INLET HOOD
ARTIAL Wit
\ DISCONNECT SNITC 11 - - ��� /I
CO'JER (OPTIONAL) 1IIi PAIN HOODNC" i tr In tH 5 VIEW)
CAS
/ �` I FILTER RI OWE
4---25C(2828,21 CONVENIENCE CUTLET .IUmrER ACCESS AlLP: Ill toil Y !l�.0 Ml IN lilillj$llN1i
D l ACCES CCYER (OPTIONAL( -1-------------
ACC S. �..�1 34.55 i I' - --
r '',
27.35 E > Its �lllpl, I626,n �IHNilll�ilE/tl�lhisl011
(694,71 `_ H( 11 INi?lfi IIR �PItIN
1(.0. ��' 1141 �IIIIM)�il 14lRA�l�l l E� �-r III N'1J1 MIIIICI'I11� R1lIGl
c Illt- - -- - -- 110:1ti -r
.11A
3.78 + 4.38 6.94
IB 5b 196.01 [111,11 1176,21 44 88
\\--'G
C471,91 31.89 AS SUPPLY ENTRY A [1139,8J
OILGUARD
I810,07 1.63 141,41 L )
tOPTu IONA
B 0.75 (19,1] 1439,73 2.55 ---.. - 82.19 -1 RGHT y1at a
PVC FPT 164,71 12081,61 EROLT MEIN
COND. DRAIN v I •x nD AR4[r P90411T10El•[ [. x�o•u. *K ew .c.e« <KaC••u.xD xD.[«Sae�o. fA7En Aro SEr -'AAv� GATE REVISION RECORD EC 10;DR £A INS "
LFV 1 [aAx[n ro VI.1 Y1tt i[n Px[r [[CR .PAxi oII ri...1 xar a S V CNAR.K(ETV el 1 PER
A I2 21-ID NEW BROIL - LO RUN-- Y MANE
urox .o o+xw ..rm mc.K h>o+ncx COMMAS 8[MTR ATERIAL
6 LI
LEFT VEW I ORA6I YE PFA ADEE YIi S 1161 NAI CAIAL
8 09-08•11 CHANGED OPERAT NIG S CORNER WEIGHTS FOR 3,4 8 ST IGEN 21 19126I LO RCF MAK '+ UMW MU mom ow ma SUBMI I"AL DWG, SM SUNLINF, TYPE NO1 APPLICABLE
C 1125 14 ADDED ZG16 MAT MODELS 30683 i LO RDH HNC 3-6 TORS ram NOT APPLICA6LE •
c 0'07-30-18 ADDED 4U20 6 ION 400EL B REMOVED OBSOLETE DA'A 60466 1SMD LOP CB all 0H P8M[61Ak- :I 61 E A
CNN (OEM IT-71.14 9 KPa D1:1n = I.6D OPG W. REV
,..1. _- CNN t.... n•11•l6 696416 rx[Ir4: 3.410 JOHNSON rONTROL.S
EYG A6l[6• 3r 6R1-Aer PRCCLCIS 6R06P UST SSl IGDf32H
1 MEG DIAp11016 AN II INKS PART x0. 1
_ I SCALE 0.085 10 cT wTE>Pnt 008045. 73069 SNT MO;OF I
d - - 8 i 10 I.T .. IS
Information is subject to change without notice.Check local codes. Printed 07/26/2021
Small Sunline 3-6 Ton Page:
Li Y�RK Package
9►
York Single Package R-410A Heat Pump
- Project Name: Cost Plus World Market Unit Model#: XN060C00A2C1AAA1A1
Quantity: 1 Tag#:Direct Repl-On
Order-ETA to Fife Branch-Sept 15th
Component Location
Component Location
Electric/Electric and Heat Pump
IiACR l\��l(( Gt'f( ".ny)))) VP) �Cmixigh Efficiency
Hood r ''',......,,,1 •
•
� I Fii9rth'Efficient
' ‘., . \ :„.
r '1 Enhanced Copper
� � Tube!Enhanced
.?' Aluminum Fin
Or
Knockout `1..'illi4k
m,s'. �T t rr.ri r I"" + , ; 1'1 Micro-Channel
For Side ` ar - -- f Aluminum
Power Entry ,, lA r `"�.!...l �.1 - Tube/Aiunxnum
Slide In � • s. 11 [[ Fin Condenser
Economizer II - I�.• j I
Smoke 0/�'
Demme«
c
I i �i 4,* 'I iii° Full Pe aas...
., ,A•i '1 1s • _i ���� M Nth Forklift Slots And
\"`�` [ ' Q tj
-0VCemae .il _ EkcrHe Accessory Location
GFCI \ -.J Simplicity '
Convenience Outlet ��� ri fp Ben Dove Or Or
Knockout " DitsU Drive SimpliatyOS:SE
For Site Blower Control Board
Control Entry
Information is subject to change without notice.Check local codes. Printed 07/26/2021
° Small Sunline 3-6 Ton Image: '
llyORK
Package
g
York Single Package R-410A Heat Pump
- Project Name: Cost Plus World Market Unit Model#: XN060C00A2C1AAA1A1
Quantity: 1 Tag#:Direct Repl-On
Order-ETA to Fife Branch-Sept 15th
Typical Application
' ROOF JACK
/ INSTALLATION
; N
I 1 i ff
": \\\N\
1 I
g � ROOF CURB
li o INSTALLATION
•
1 i ! I
I I 1 1 I I ` I
1 1 1 1 1 I I I 1
I 1 1 1 I I T Lam.•-�+ Lam- --1
1 I I 1 1 I _ 1 1 1 SLAB ON GROUND
I 1
I 1 I I I I INSTALLATION
i T ) I I 1 /
c r
1 it
TT _� T I_ f)
-r-T r_ -�- �I, o Rt
I..-L if •�'r�.� de.;i— +ram..-" r� 1 r f 1 l I 1 I .r-
1
—
-- AO
I
-
"Iiillu. : -
— -- # '
AO
FIELD-SUPPLIED ����_�, �— -
DISCONNECT SWITCH ii` •,- • 9 w` -„
si"
!- f���` �� \ 4 - -fir, 0
.-� ;� ol' w.b _ ' tom.`� ..�I '/ .- -- - 1 P- i:44's; .,
ii
x . r J, i ,-, y,,, h ..A.
111
- .--._, I�ujiOAOp .fib// i 1 1 /P /11�11'.0/
ROOF CURB
ross) I CONDENSATE
TRAP
�CI", j SUPPLY AIR
11
TO C NTROL WIRING
ORETURN
POWER TO INDOOR AIR
SUPPLY THERMOSTAT DUCT
Information is subject to change without notice.Check local codes. Printed 07/26/2021
3 YQRR® Small Sunline 3-6 Ton Page:8
Package
York Single Package R-410A Heat Pump
Project Name: Cost Plus World Market Unit Model#: XN060C00A2C1AAA1A1
Quantity: 1 Tag#:Direct Repl-On
Order-ETA to Fife Branch-Sept 15th
.. Typical Field Power and Control Wiring
TYPICAL POWER WIRING
CONTACTOR
0 FIELD-SUPPLIED CONTACTOR
r cj`�'Q DISCONNECT B , 0
Y
, , �-' i SINGLE in. FIELD-SUPPLIED
y L -1--0--i O--r-> PHASE _ (C1 0 0 DISCONNECT
L -' -6" 0--I-- POWER -- Y V r
GROUND L SUPPLY _ L ; _0--1 - - THREE
LUG - 1 L L o-=i> PHASE
REFER TO THE ELECTRICAL DATA GROUND L -I L- POWER
TABLES TO SIZE THE DISCONNECT LUG SUPPLY
SWITCH.OVER CURRENT L J
PROTECTION AND WIRING.
TYPICAL COOL/HEAT CONTROL WIRING
COOLING ONLY (24 VOLT THERMOSTAT) COOLING/ HEATING (24 VOLT THERMOSTAT)
THERMOSTAT' UNIT TERMINAL THERMOSTAT1
TERMINALS STRIP TB1 TERMINALS
RV - ----- 0 'V
,(R^H) UNIT TERMINAL
24 VOLT
ADD STRIP T81
vc "' 0 TRANSFORMER JUMPER 0
0E 0_'_..._-"'-"" - Y1 24 VOLT
�\
TRANSFORMER
-0 Y2
\J
... E
....
CO \�.J/C� 0 �124 VOLT THERMOSTAT TO CONTROL THE ECONOMIZER ON SECOND W 2
STAGE COOLING.USE A 2 STAGE COOLING THERMOSTAT
COOLING /HEATING (ELECTRONIC THERMOSTAT) Q
MULTI STAGE '24 VOLT THERMOSTAT.TO CONTROL THE ECONOMIZER ON THE SECOND
THERMOSTATI STAGE COOLING OR TO HAVE AN ELECTRIC HEAT ACCESSORY WITH TWO
STAGES OF HEAT,USE A 2 STAGE COOL AND HEAT THERMOSTAT.
TERMINALS UNIT TERMINAL
RC STRIP TB1 24 VOLT
ADD
JUMPER ��' TRANSFORMER COOLING/ HEATING (ELECTRONIC THERMOSTAT)
Y, Y, SINGLE STAGE
Y2 2 Y2 4-
.
4 wz 3 W2 THERMOSTAT''
TERMINALS UNIT TERMINAL
G -•--•-------"'-___ G
RH STRIP TB1
LED t ------------------ X ADD
LED 2 NOT ------ QCc JUMPER ®__.._.-•-------- Y 1
COM USED 4~ W --•------------ y.1 ,m.
ADD Al G GA.
JUMPER A2 C
TO REMOTE SENSOR 24 VOLT
T IF USED TRANSFORMER
'ELECTRONIC PROGRAMMABLE THERMOSTAT TYPICAL. 'ELECTRONIC PROGRAMMABLE THERMOSTAT TYPICAL..TO CONTROL THE
ECONOMIZER ON SECOND STAGE COOLING.USE A 2 STAGE COOL AND
'SECOND STAGE COOLING IS NOT REQUIRED ON UNITS LESS ECONOMIZER. HEAT THERMOSTAT.
'SECOND STAGE HEATING IS ONLY REQUIRED ON UNITS WITH A TWO STAGE
ELECTRIC HEATER OR 2 STAGE GAS HEAT.
•REMOVE JUMPER J2 FROM TERMINALS 4 AND 9 ON JUMPER PLUG CONNECTOR
P6 ON UNITS WITH ECONOMIZER.TERMINALS Al AND A2 PROVIDE A RELAY
OUT-PUT TO CLOSE THE OUTDOOR ECONOMIZER DAMPERS WHEN THE
THERMOSTAT SWITCHES TO THE SET-BACK POSITION.
Information is subject to change without notice.Check local codes. Printed 07/26/2021
;YWY .. .. _ . .W .... .. ._ - W.
Page:9
Date
07/26/2021 0/0
Project NameCost Plus World Market
Johnson
Project Number Controls
NN07262103
Client/Purchaser
Guide Specification Summary Page
Product Series Models and Unit Tags
Small Sunline 3-6 Ton Package XN060C00A2C1AAA1A1 Direct Repl-On Order-ETA to Fife Branch-
Sept 15th
Information is subject to change without notice.Check local codes. Printed 07/26/2021
YORK® Guide Specification for
York Sunline Page: 10
GENERAL UNIT CABINET
York Sunline units are convertible single package units. Unit cabinet shall be constructed of galvanized steel, with
Although the units are primarily designed for curb exterior surfaces coated with a non-chalking, powdered
mounting on a roof, they can also be slab-mounted at paint finish, certified at 750-hour salt spray test per
ground level or set on steel beams above a finished roof. ASTMB117 standards. Indoor blower section shall be
Cooling only, cooling with gas heat, cooling with electric insulated with a minimum 1/2"thick insulation, coated on
heat and heat pump with electric heat models are the airside. Aluminum foil faced insulation shall be used in
available with a wide variety of factory mounted options the furnace compartment and be fastened with ridged
and field-installed accessories to make them suitable for fasteners to prevent insulation from entering the air
almost every application. All units are self-contained and stream. Cabinet panels shall be"large" size, easily
assembled on full perimeter base rails with holes in the removable for servicing and maintenance. Full perimeter
four corners for overhead rigging. Every unit is base rails shall be provided to assure reliable transit of
completely piped, wired, charged and tested at the equipment, overhead rigging and proper sealing on roof
factory to simplify the field installation and to provide curb applications. Disposable 1"filters shall be furnished
years of dependable operation. All models(including and be accessible through a removable access door,
those with an economizer)are suitable for either bottom sealed airtight. Units filter track shall be designed to
or horizontal duct connections. Models with power accommodate either 1"or 2"filters. Fan performance
exhaust are suitable for bottom duct connections only. measuring ports shall be provided on the outside of the
For bottom duct, remove the sheet metal panels from the cabinet to allow accurate air measurements of evaporator
supply and return air openings through the base of the fan performance without removing panels or creating air
unit. For horizontal duct, remove the supply and return by-pass of the coils. Condensate pan shall be internally
air panels on the rear of the unit. sloped and conform to ASHRAE 62-89 selfdraining
standards. Condensate connection shall be a minimum of
All non-Scroll compressors include crankcase heaters and 3/4" I.D. female and be a ridged mount connection.
all compressors have internal pressure relief. Every
refrigerant circuit includes a liquid line filter-drier, a INDOOR(EVAPORATOR) FAN ASSEMBLY
discharge line high pressure switch and a suction line with The indoor fan shall be a factory installed direct-drive or
a freezestat and low pressure/loss of charge switch.The beltdrive assembly that includes an adjustable pitch motor
unit control circuit includes a 75 VA transformer, a 24-volt pulley. Job site selected brake horsepower(B.H.P.) shall
circuit breaker and a relay board with a compressor not exceed the motors nameplate horsepower rating, plus
lockout circuit, a terminal strip for thermostat wiring, plus the service factor. Units shall be designed not to operate
an additional set of pin connectors to simplify the interface above service factor. Fan wheel shall be double-inlet type
of additional field controls. All models are CSA listed.All with forward-curved blades, dynamically balanced to
models include a 1-year limited warranty on the complete operate smoothly throughout the entire range of operation.
unit. Compressors and factory installed electric heater Airflow design shall be constant air volume. Bearings shall
elements carry a 5-year warranty. Aluminized steel and be sealed and permanently lubricated for longer life and
Stainless steel tubular heat exchangers carry a 10-year no maintenance.
warranty.
DESCRIPTION OUTDOOR (CONDENSER) FAN ASSEMBLY
Units shall be factory assembled, single packaged, The outdoor fan shall be of the direct-drive propeller type
Electric Cooling/Gas Heat, Electric Cooling/Optional (3-5 ton units), discharge air vertically, have aluminum
Electric Heat, Heat Pump/Optional Electric Heat and are blades riveted to a corrosion resistant steel spider bracket
designed for outdoor mounted installation and shall be dynamically balanced for smooth operation.
The outdoor fan motor shall be totally enclosed with
The 3 ton, 4 ton, and 5 ton units shall have minimum permanently lubricated bearings, internally protected
SEER rating of 14.0 with heat pumps having a 8.0 H.S.P.F. against overload conditions and staged independently.
The 6 ton units shall have a minimum IEER rating of 14.2. REFRIGERANT COMPONENTS
They shall have built-in field convertible duct connections
for down discharge supply/return or horizontal discharge Compressors:
supply/return, and be available with factory installed
options or field installed accessories. The units shall be a. Shall be internally protected with internal high-
factory wired, piped, charged with R-410A refrigerant and pressure relief and over temperature protection.
factory tested prior to shipment. All unit wiring shall be b. Shall have internal spring isolation and sound
both numbered and color coded. All units the cooling muffling to minimize vibration and noise, and be
performance shall be rated in accordance with DOE and externally isolated on a dedicated, independent
AHRI test procedures. Units shall be CSA listed, classified mounting.
to ANSI Z21.47, UL 1995/CSA No. 236 standards.
Information is subject to change without notice.Check local codes. Printed 07/26/2021
YORK Guide Specification for
York Sunline Page: 11
Coils: j. Control board shall monitor each refrigerant safety
a. Evaporator coils shall have aluminum plate fins switch independently.
mechanically bonded to seamless internally enhanced k. Control board shall retain last 5 fault codes in non
copper tubes with all joints brazed. Special Phenolic volatile memory which will not be lost in the event of a
coating shall be available as a factory option. power loss.
b. Evaporator coils shall be of the direct expansion, draw ELECTRIC HEATING SECTION
thru design.
c. Condenser coils shall have aluminum plate fins An electric heating section, with nickel chromium
mechanically bonded to seamless internally enhanced elements, shall be provided in a range of 5 thru 30 KW,
copper tubes with all joints brazed or Micro-Channel offering two stages of capacity- 16 KW and above on
aluminum tube, aluminum fins. 208/230 volt heaters and 20 KW and above on 460 and
d. Condenser coils shall be of the direct expansion, draw- 575 volt heaters. The heating section shall have a
thru design. primary limit control(s) and automatic reset to prevent
the heating element system from operating at an
excessive temperature. The heating section assembly
Refrigerant Circuit and Refrigerant Safety Components shall slide out of the unit for easy maintenance and
shall include: service. Units with Electric Heating shall be wired for a
a. Independent fixed-orifice or thermally operated single point power supply with branch circuit fusing
expansion devices. (where required).
b. Filter drier/strainer to eliminate any moisture or foreign UNIT OPERATING CHARACTERISTICS
matter.
Unit shall be capable of starting and running at 125°F
c. Accessible service gage connections on both suction outdoor temperature, exceeding maximum load criteria
and liquid lines to charge, evacuate, and measure of AHRI Standard 210/240. The compressor, with
refrigerant pressure during any necessary servicing or standard controls, shall be capable of operation down to
troubleshooting, without losing charge. 0°F outdoor temperature.
d. The refrigeration system shall provide at least 15°F of ELECTRICAL REQUIREMENTS
sub-cooling at design conditions.
All unit power wiring shall enter unit cabinet at a single
Unit Controls: factory provided location and be capable of side or
a. Unit shall be complete with self-contained low-voltage bottom entry, to minimize roof penetrations and avoid
control circuit protected by a resettable circuit breaker unit field modifications. Separate side and bottom
on the 24-volt transformer side. openings shall be provided for the control wiring.
b. Unit shall incorporate a lockout circuit which provides STANDARD LIMITED WARRANTIES
reset capability at the space thermostat or base unit,
should any of the following standard safety devices trip • Compressor 5 Years
and shut off compressor. • Heat Exchanger 10 Years
c. Loss-of-charge/Low-pressure switch. • Factory Installed Electric Heat Element 5 Years
d. High-pressure switch. • Other Parts 1 Year
e. Freeze-protection thermostat, evaporator coil.
f. Unit shall incorporate "AUTO RESET"compressor OPTIONAL OUTDOOR AIR
over temperature, over current protection.
g. Unit shall operate with conventional thermostat
designs and have a low voltage terminal strip for easy
hook-up.
h. Unit control board shall have on-board diagnostics and
fault code display.
i. Standard controls shall include anti-short cycle and low
voltage protection, and permit cooling operation down
to 0°F.
Information is subject to change without notice.Check local codes. Printed 07/26/2021
r Guide Specification for Page: 12
yoRK® York Sunline
Dry Bulb Automatic Economizer—Outdoor and return
air dampers that are interlocked and positioned by a
fullymodulating, spring-return damper actuator. The
maximum leakage rate for the outdoor air intake dampers
shall be designed to meet ASHRAE 90.1, AMCA 511
Class 1A damper, and the International Energy
Conservation Code (IECC)certification requirements by
achieving leakage rates of 3 cfm/sq. ft. at 1"of static
pressure. Changeover from compressor to economizer
operation shall be provided by an integral electronic
enthalpy control that feeds input into the basic module.
The outdoor intake opening shall be covered with a rain
hood that matches the exterior of the unit. Water
eliminator/filters shall be provided. Simultaneous
economizer/compressor operation is also possible.
Dampers shall fully close on power loss. Available with
barometric relief and power exhaust.
ADDITIONAL FACTORY INSTALLED OPTIONS
• BAS Controls
FIELD INSTALLED OPTIONS
• Electric Heaters-wired for single point power supply.
These nickel chromium heater elements are provided
with limit and automatic reset capability to prevent
operation at excessive temperatures.
• Barometric Relief Damper—This damper accessory
can be used to relieve internal building air pressure on
units with an economizer without power exhaust. This
accessory includes a rain hood, a bird screen and a
fully assembled damper. With bottom duct
connections, the damper should be mounted over the
opening in the return air panel. With horizontal
ductwork, the accessory should be mounted on the
return air duct.
Information is subject to change without notice.Check local codes. Printed 07/26/2021
Page: 13
Date
07/26/2021 .,
Project Name �/
(•Plus ,k
Cost World Market
Project Number Controls
NN07262103
Client/ Purchaser
Control Summary Page
Control Models and Unit Tags
Standard Simplicity Control XN060C00A2C1AAA1A1 Direct Repl-On Order-ETA to Fife Branch-
Sept 15th
Information is subject to change without notice.Check local codes. Printed 07/26/2021
SSE Guide Spec Page: 14
YORK
23 09 23 Direct-digital Control system for HVAC
23 09 23. 13 Decentralized,Rooftop Units:
23 09 23. 13.A. Unit Control Board
1. ASHRAE 62-2001 compliant. BTL certified.
2. Shall accept 20-30 VAC input power,50/60Hz. 24 VAC nominal.
3. Operating temperature range from-40F to 158F; 10-90%RH(non-condensing UI),and-4F to 158F; 10-90%Rh(non-
condensing),with a storage temperature range from-40F to 194F;5-95%RH(non-condensing).
4. Shall include an option of and Economizer microprocessor controller which communicates directly with the Unit Control Board
and has 8 Analog outputs,2 Analog inputs,2 Binary outputs,3 Binary outputs.
5. Controller shall accept the followinginputs:space temperature,return air temperature sensor,setpointadjustment,outdoor air
temperature,indoor air quality,outdoor air quality,indoor relative humidity,compressor lock-out,fire/smoke shutdown,single
and dual enthalpy,fan status,remote time clock,SA Bus communicated temperature/humidity/CO2 values from Network sensors,
FC Bus Network Overrides for space temperature,outdoor air temperature,space humidity,outdoor air quality,Indoor air quality,
System purge.
6. Shall accept a single CO2 sensor or multiple CO2 sensors networked together via communication bus in the conditioned space,and
be Demand Control Ventilation(DCV)ready.
7. Shall provide the following outputs:economizer,fan,cooling stage 1,cooling stage 2,heat stage 1,heat stage 2,heat stage 3/
exhaust/reversing valve/dehumidify/occupied.
8. Unit shall provide surge protection for the controller through a circuit breaker.
9. Shall be Internet capable,and communicate at a Baud rate of 38.4K or faster.
10. Shall have an LED display independently showingthe status of activity on the communication bus,and processor operation.
11. Unit shall incorporate a lockout circuit which provides reset capability at the space thermostat or base unit should any of the
following standard safety devices trip and shut off compressor. If any of these safety devices trip,the LCD screen will display
alarm message indicating the specific safety device that caused the lockout.
a. Loss of charge/Low-pressure switch.
b. High-pressure switch.
c. Freeze condition sensor on evaporator coil.
12. Unit control board must support each usage case:
a. Conventional thermostat with low voltage input terminals for easy installation
b. Communicating network sensors in the occupied space to provide feedback on space conditions for unit control
board to compare with associated setpoints
c. Communication via BACnet MS/TP, Modbus RTU, N2 protocols for integration into a building
automation/management system
13. Anti-short cycle and low voltage protection features included.
14. Internal occupied/unoccupied scheduling
15. Unit control board shall permit cooling operation down to a selectable value as low as 0 degrees F.
16. Shall allow for start-up,commissioning,troubleshooting,parameter adjustment,setpoint adjustment via onboard
display and navigable menu with no additional interface tool or controls technician required.
17. The unit control board shall run a self-test diagnostics algorithm at startup that operated the cooling cycle, heating
cycle,fan operation.A status report shall be provided upon completion of the diagnostic self-test.
18. Utilize any wi-fi enabled smart device to access the HVAC or multiple HVAC units if communication wiring between
them is present(FC Bus or SA Bus). Remote access shall allow complete ability to perform start-up,commissioning,
troubleshooting, parameter adjustment,setpoint adjustment.
19. Local embedded trending and scheduling.Trending data and occupancy scheduling predefined from the factory.
Occupancy schedule to be modified via control board joystick menu navigation and remotely using a smart device
(cellular phone,laptop,tablet)
20. A menu on the onboard screen shall display the unit status and allow changing parameters where applicable.These
include but are not limited to:
a. Demand Ventilation Mode—enable or disable
b. Operational Setpoint—display current value
c. Supply Air Temperature(SAT)—display current value
d. Return Air Temperature(RAT)—display current value
Information is subject to change without notice.Check local codes. Printed 07/26/2021
® SSE Guide Spec Page: 15
YORK
e. Operational Supply Humidity(OprSH)—display current value as provided by a 0-10VDS input, SA Bus Network
Sensor,or FC Bus communicated value
f. Return Air Humidity(RAH)—display current value
g. Operational outdoor Air Temperature(OprOAT)—enthalpy calculated from OAH 0-10VDC input to Economizer
board and OprOAT only if economizer is present
h. Operational Outdoor Air Humidity(OprOAH)—the buffered outdoor air humidity. May be from economizer boards
OAH 0-10VDC input or FC Bus communicated value
i. Operational outdoor Air Quality(OprOAQ)—the buffered outdoor air quality in use. May be from economizer
boards OAQ 0-10VDC input or FC Bus communicated value
j Operational Indoor Air Quality(OprIAQ)—the buffered indoor air quality in use. May be from economizer board
IAQ 0-10VDC input, SA Bus Network Sensor, or FC Bus communicated value
21. A menu shall display and allow modification to the following operations and settings:
a. HVAC Zone Fan
b. Cooling
c. Heating
d. Economizer
e. Demand Ventilation
f. Power Exhaust
g. Sensors
h. Network
22. A menu shall display and allow modification to the following operations and settings:
a. HVAC Zone—Occupied status
b. Indoor Fan status
c. Cooling status
d. Heating status
e. Economizer indication whether free-cooling is available or not
f. Enabling or disabling of Demand Ventilation
g. Power Exhaust
1) Enable/disable hot-gas reheat if available
2) Warmup/Cooldown
3) Title 24 Load Shed
4) Defrost
23. A menu shall display and allow modification to the following operations and settings:
a. Firmware version(of UCB, Economizer,other peripheral boards)
b. Setting time zone
c. Network information
1) Device name that will appear on the FC Bus
2) Selection of communication protocol
3) Operational Baud Rate
4) Device ID
24. A menu shall display and allow modification to the following operations and settings:
a. Version of firmware
b. Ability to Load new firmware
c. Create a backup file of the firmware and parameter setting via USB port
d. Restore factory default parameter values and setup
e. Full and Partial Cloning of parameter setpoints from or to other units
f. Data trend exporting
25. A menu shall display and allow modification to the following operations and settings:
Information is subject to change without notice.Check local codes. Printed 07/26/2021
_ YORK® SSE Guide Spec Page: 16
a. Unit serial number, model number and name
b. Ability to reset Lockouts
c. Controller name
d. Displays the current values of all setpoints in use
e. Displays all current values for the indoor and outdoor zones
f. Displays current values related to:
1) Indoor Fan
2) Cooling
3) Heating
4) Heat Pump operation
5) Economizer operation
6) Power Exhaust
7) Demand Ventilation
8) Air monitoring station
9) Hot Gas Reheat
10) Smoke Control
g. Current information for inputs;including
1) Sensors
2) Coil Sensors
3) Thermostat
4) Binary Inputs
5) Unit Protection
6) Network Inputs
7) All outputs(relay and binary)
h. Self-Test
1) A patented self-test system that runs through a series of algorithms to provide a report of all functioning
characteristics of the system at time of startup and commissioning.
23 09 23. 13.B. Auxiliary Control Boards
1. ASHRAE 62-2001 compliant. BTL certified.
2. Economizer controller CEC Title 24 Compliant
a. Display alarms if the following occur
1) Economizer is economizing when conditions do not support
2) Economizer is not economizing when conditions do support
3) Damper Stuck
4) Excess Outdoor Air
5) Failed Sensor
3. Refrigeration Fault Detection&Diagnostics
a. There is insufficient refrigerant in any circuit
b. There is excessive refrigerant in any circuit
c. There is excessive refrigerant flow
d. There is insufficient refrigerant flow(restriction)
e. Inefficient compressor
f. Insufficient High-side heat transfer
g. Excessive High-side heat transfer(low ambient control problem, low AP)
h. Insufficient Low-side heat transfer
i. Excessive Low-side heat transfer
Information is subject to change without notice.Check local codes. Printed 07/26/2021
_ YORK SSE Guide Spec Page: 17
j. Sensor fault-The liquid temperature is greater than the condenser temperature(Could also be triggered if
refrigerant level is very low in the system)
k. Sensor fault-Sensor data is not available
I. The unit is off
m. The ambient temperature is too low
n. The ambient temperature is too high
o. The return air wet-bulb temperature is too low
p. The return air wet-bulb temperature is too high
q. Sensor fault-The condensing temperature is lower than the ambient temperature(Could also be triggered when
the condenser is wet)
r. The suction line temperature is less than the evaporator temperature
s. The evaporator temperature is greater than the ambient temperature
t. The liquid temperature is lower than the ambient temperature
u. Sensor fault-Suction temperature or ambient temperature is invalid
v. Sensor fault-The return air dry-bulb or wet-bulb temperature is invalid
w. Sensor fault-The liquid pressure or suction pressure is invalid
x. Sensor fault-The suction line temperature is invalid
y. The return air dry-bulb temperature is too low
z. The return air dry-bulb temperature is too high
aa. The Efficiency Index is below 75%of ideal
bb. The Capacity Index is below 75%of ideal
23 09 23. 13.0 Remote Accessibility:,
1. ASHRAE 62-2001 compliant. BTL certified.
2. Provide the ability to adjust parameter values, setpoints, limits remotely
3. Connectivity to an Ethernet network via static IP address or Dynamic Name Server(DNS)
4. Allow a maximum of 100 devices on the same FC bus trunk and accessed by one remote device
Information is subject to change without notice.Check local codes. Printed 07/26/2021
Page: 18
START-UP & SERVICE DATA INSTRUCTION
COMMERCIAL PACKAGE UNITS
3.0 To 40.0 TONS
START-UP CHECKLIST
Date:
Job Name:
Customer Name:
Address:
City: State: Zip:
Model Number: Serial Number:
Qualified Start-up Technician: Signature:
HVAC Contractor: Phone:
Address:
Contractor's E-mail Address:
Electrical Contractor: Phone:
Distributor Name: Phone:
WARRANTY STATEMENT This start-up sheet covers all startup check points common to all
package equipment. In addition it covers essential startup check
Johnson Controls/UPG is confident that this equipment will points for a number of common installation options. Depending
operate to the owner's satisfaction if the proper procedures are upon the particular unit being started not all sections of this startup
followed and checks are made at initial start-up.This confidence is sheet will apply.Complete those sections applicable and use the
supported by the 30 day dealer protection coverage portion of our notes section to record any additional information pertinent to your
standard warranty policy which states that Johnson Controls/UPG particular installation.
will cover parts and labor on new equipment start-up failures that Warranty claims are to be made through the distributor from whom
are caused by a defect in factory workmanship or material,for a the equipment was purchased.
period of 30 days from installation. Refer to current standard
warranty policy and warranty manual found on UPGnet for details. EQUIPMENT STARTUP
In the event that communication with Johnson ControlslUPG is
required regarding technical and/or warranty concerns,all parties Use the local LCD or Mobile Access Portal(MAP)Gateway to
to the discussion should have a copy of the equipment start-up complete the start-up.
sheet for reference.A copy of the original start-up sheet should be A copy of the completed start-up sheet should be kept on file
filed with the Technical Services Department. by the distributor providing the equipment and a copy sent to:
The packaged unit is available in constant or variable air volume Johnson Controls/UPG
versions with a large variety of custom options and accessories Technical Services Department
available.Therefore,some variation in the startup procedure will 5005 York Drive
exist depending upon the products capacity,control system, Norman, OK 73069
options and accessories installed.
Information is subject to change without notice.Check local codes. Printed 07/26/2021
•
Page: 19
SAFETY WARNINGS
AWARNING
The inspections and recording of data outlined in this procedure --- -- -
are required for start-up of Johnson Controls/UPG's packaged
products. Industry recognized safety standards and practices Lethal voltages are present during some start-up
must be observed at all times.General industry knowledge and checks. Extreme caution must be used at all times.
experience are required to assure technician safety. It is the
responsibility of the technician to assess all potential dangers
and take all steps warranted to perform the work in a safe A
manner. By addressing those potential dangers,prior to I WARNING
beginning any work,the technician can perform the work in a
safe manner with minimal risk of injury. Moving parts may be exposed during some startup
checks. Extreme caution must be used at all times.
NOTE: Read and review this entire document before beginning
any of the startup procedures.
DESIGN APPLICATION INFORMATION
This information will be available from the specifying engineer full open position and the frequency drive is operating at 60 HZ.
who selected the equipment. If the system is a VAV system the Do not proceed with the equipment start-up without the
CFM will be the airflow when the remote VAV boxes are in the design CFM information.
Design Supply Air CFM: Design Return Air CFM:
Design Outdoor Air CFM At Minimum Position:
Total External Static Pressure:
Supply Static Pressure:
Return Static Pressure:
Design Building Static Pressure:
Outside Air Dilution:Economizer Position Percentage: _ CFM:
Supply Gas Pressure After Regulator W/o Heat Active Inches
ADDITIONAL APPLICATION NOTES FROM SPECIFYING ENGINEER:
Information is subject to change without notice.Check local codes. Printed 07/26/2021
•
Page:20
REFERENCE
General Inspection Completed See Notes
Unit inspected for shipping,storage: or rigging damage 0 0
Unit installed with proper clearances 0 0
Unit installed within slope limitations 0 0
Refrigeration system checked for gross leaks(presence of oil) ❑ 0
Terminal screws and wiring connections checked for tightness 0 0
Filters installed correctly and clean ❑ 0
Economizer hoods installed in operating position 0 0
Condensate drain trapped properly, refer to Installation Manual 0 ❑
Economizer damper linkage tight 0 0
Gas Heat vent hood installed 0 ❑
All field wiring(power and control)complete 0 0
Air Moving Inspection Completed See Notes
Alignment of drive components ❑ 0
Belt tension adjusted properly 0 0
Blower pulleys tight on shaft, bearing set screws tight,wheel tight to shaft 0 0
Pressure switch or transducer tubing installed properly 0 ❑
Exhaust Inspection Powered 0 Barometric Relief 0 Completed See Notes
Check hub for tightness 0 0
Check fan blade for clearance 0 ❑
Check for proper rotation 0 0
Check for proper mounting(screen faces towards unit) 0 0
Prove operation by increasing minimum setting on economizer 0 0
Economizer Inspection Standard 0 BAS 0 Completed See Notes
CO2 sensor installed Yes 0 No 0 0 0
Check economizer setting(Reference SSE Control Board LCD menu location) 0 0
Prove economizer open/close through SSE Board Setting 0 0
Reheat Mode Normal❑ or Alternate 0 Not Applicable❑
Humidity Sensor(2SH0401)
Information is subject to change without notice.Check local codes. Printed 07/26/2021
Page:21
P -
Operating Measurements -Air Flow
Fan operates with proper rotation ID Fans 0 Exh. Fans 0 Cond. Fans 0
Pressure drop across dry evaporator coil(At maximum design CFM) 1 IWC
External Static Pressure IWC
Return Static Pressure IWC
Supply Static Pressure IWC
Supply Air CFM Using Dry Coil Chart CFM
Final Adjusted Supply Air CFM2 CFM
1. Consult the proper airflow to pressure drop table to obtain the actual airflow at the measured pressure differential.
2. Was a motor pulley adjustment or change required to obtain the correct airflow?
Was it necessary to increase of decrease the airflow to meet the design conditions?
If the motor pulley size was changed:measure the outside diameters of the motor and blower pulleys and record those diameters here:
Blower Motor HP FLA RPM
Pulley Pitch Diameter Turns Out Final Turns Out
Blower Pulley Pitch Diameter Fixed Sheave
ELECTRICAL DATA
T1 -T2 Volts T2-T3 Volts
Control Voltage Volts T1 -T3 Volts
Device Nameplate Measured
List All Three Amperages
Supply Fan Motorl 2 AMPS AMPS
Exhaust Motor(Dampers 100%) AMPS AMPS
Condenser Fan#1 AMPS AMPS
Condenser Fan#2(if equipped) AMPS AMPS
Condenser Fan#3(if equipped) AMPS AMPS
Condenser Fan#4(if equipped) AMPS AMPS
Compressor#1 AMPS AMPS
Compressor#2(if equipped) AMPS AMPS
Compressor#3(if equipped) AMPS AMPS
Compressor#4(if equipped) AMPS AMPS
1. VAV units with heat section-simulate heat call to drive VAV boxes and VFD/IGV to maximum design airflow position.
2. VAV units without heat section-VAV boxes must be set to maximum design airflow position.
Information is subject to change without notice.Check local codes. Printed 07/26/2021
iW' ... ,.... ___ , v . . ...
Page:22
OPERATING MEASUREMENTS -COOLING
Stage Discharge Discharge Liquid Line Subcooling2 Suction Suction Superheat
Pressure Temp. Temp. Pressure Temp.
First # 0 #
Second(if equipped) # #
Third(if equipped) # ° #
Fourth(if equipped) # #
Reheat 1st Stage # #
1. Liquid temperature should be taken before filter/drier.
2. Subtract 10 psi from discharge pressure for estimated liquid line pressure
Outside air temperature °F db °F wb %RH
Return Air Temperature °F db °F wb %RH
Mixed Air Temperature °F db °F wb %RH
Supply Air Temperature °F db °F wb %RH
REFRIGERANT SAFETIES
Action Completed See Notes
Prove Compressor Rotation(3 phase only)by gauge pressure 0 0
Prove High Pressure Safety,All Systems 0 0
Prove Low Pressure Safety, All Systems 0 0
OPERATING MEASUREMENTS -GAS HEATING
Fuel Type: 0 Natural Gas 0 LP Gas
Action Completed See Notes
Check for gas leaks 0 0
Prove Ventor Motor Operation 0 0
Prove Primary Safety Operation 0 0
Prove Auxiliary Safety Operation 0 0
Prove Rollout Switch Operation 0 0
Prove Smoke Detector Operation 0 0
Stage 1 IWC 0
Manifold Pressure Stage 2(If Equipped) IWC 0
Stage 3(If Equipped) IWC 0
Supply gas pressure at full fire IWC 0
Check temperature riser 0 measured at full fire •F 0
1- Input X Eff.(BTU output)
1.08 X Temp.Rise
Information is subject to change without notice.Check local codes. Printed 07/26/2021
Page:23
OPERATIONAL MEASUREMENTS -STAGING CONTROLS
Verify Proper Operation of Heating/Cooling Staging Controls
Create a cooling demand at the Thermostat. BAS System or Simplicity SE
Verify that cooling/economizer stages are energized. 0
Create a heating demand at the Thermostat, BAS System or Simplicity SE
Verify that heating stages are energized. 0
Verify Proper Operation of the Variable Frequency Drive(If Required)
Verify that motor speed modulates with duct pressure change. ❑
FINAL -INSPECTION
Verify that all operational control set points have been set to desired value ❑
Scroll through all setpoints and change as may be necessary to suit the occupant requirements.
Verify that all option parameters are correct
Scroll through all option parameters and ensure that all installed options are enabled in the software and all 0
others are disabled in the software. (Factory software settings should match the installed options)
Verify that all access panels have been closed and secured ❑
OBSERVED PRODUCT DIFFICIENCIES & CONCERNS:
Information is subject to change without notice.Check local codes. Printed 07/26/2021