' GENERAL NOTES:
THE AMEREX INDUSTRIAL DRY CHEMICAL FIRE SUPPRESSION SYSTEM IS DESIGNED AND HAS BEEN TESTED TO PROVIDE FIRE
PROTECTION FOR INDUSTRIAL OPERATIONS CATEGORIZED AS LOCAL APPLICATION (OVERHEAD), TANKSIDE, TOTAL FLOODING, / Lk,.
VEHICLE PAINT SPRAY BOOTH, AND OPEN FRONT PAINT SPRAY BOOTH HAZARDS. IT IS MANUFACTURED BY THE AMEREX c M F RF X ;s
CORPORATION OF TRUSSVILLE, ALABAMA.
AMEREX INDUSTRIAL SYSTEMS ARE A PRE-ENGINEERED TYPE AS DEFINED IN NFPA 17- STANDARD FOR DRY CHEMICAL
EXTINGUISHING SYSTEMS. THE NFPA 17 DEFINITION STATES PRE-ENGINEERED SYSTEMS AS "HAVING PREDETERMINED FLOW
RATES, NOZZLE PRESSURES, AND QUANTITIES OF DRY CHEMICAL." IT ALSO STATES THAT "LIMITATIONS ON HAZARDS THAT ARE
PERMITED TO BE PROTECTED BY THESE SYSTEMS AND PIPING AND NOZZLE CONFIGURATIONS ARE CONTAINED IN THE
MANUFACTURERS LISTED INSTALLATION AND MAINTENANCE MANUAL, WHICH IS PART OF THE LISTING OF THE SYSTEM." AMEREX
Industrial Dry Chemical
IT IS ESSENTIAL THAT ALL INSTALLATIONS, MAINTENANCE, AND INSPECTIONS OF THE AMEREX INDUSTRIAL SYSTEM BE Fire Suppression System
PERFORMED IN COMPLIANCE WITH THIS MANUAL AND NFPA 17.
ALL PIPING LIMITATIONS, NOZZLE COVERAGE'S, DETECTOR PLACEMENTS, ETC. HAVE BEEN PROVEN AND ESTABLISHED THROUGH Tested and Listed by
EXHAUSTIVE TESTING BY UNDERWRITERS LABORATORIES, INC. USE OF COMPONENTS OTHER THAN THOSE REFERENCED IN THIS Underwriters Laboratories and Underwriters Laboratories Canada
MANUAL, OR INSTALLATIONS OUTSIDE THE LIMITATIONS STATED IN THIS MANUAL IS UNACCEPTABLE.
to UL Standard 1254
UL AND ULC LISTING
THE AMEREX INDUSTRIAL SYSTEM IS AN UNDERWRITERS LABORATORIES (UL) AND UNDERWRITERS LABORATORIES CANADA (ULC)
LISTED PRE-ENGINEERED EXTINGUISHING UNIT. THE SYSTEM HAS BEEN EVALUATED IN ACCORDANCE WITH UL STANDARD 1254.
TESTS REQUIRED FOR LISTING UNDER THIS STANDARD INVOLVE FIRE TESTS UNDER SPECIFIC CONDITIONS INVOLVING A VARIETY
OF LOCAL APPLICATION, TOTAL FLOODING, OR SCREENING. EACH TEST FIRE WAS ALLOWED TO REACH ITS MAXIMUM INTENSITY CITY OF TIGARDs
BEFORE AGENT WAS DISCHARGED. EACH TEST WAS REPEATED USING BOTH MAXIMUM AND MINIMUM PIPING, WITH VARIATIONS IN REVIEWED FOR CODE COMPLIANCEAGENT STORAGE PRESSURE TO SIMULATE MAXIMUM AND MINIMUM TEMPERATURE RATINGS. EACH TEST FIRE WAS EXTINGUISHED
WITHOUT SPLASHING OF THE LIQUID FUEL. Approved: 7
ABC DRY CHEMICAL OTC:
t l�
IT IS NECESSARY FOR THE SYSTEM DESIGNER TO CONSIDER THE COMBUSTIBLE MATERIAL FOUND IN THE HAZARD AREA TO ENSURE Permit#s F lsa n ,. ) - n n n L1,J3
PROPER PROTECTION. THE AGENT USED IN THE AMEREX INDUSTRIAL SYSTEM IS SUITABLE FOR CLASS A, B, AND C HAZARDS. Address: J`tgcer1 �91 � /3t
THE FOLLOWING ARE THE HAZARD CLASS DEFINITIONS:
State#: p
"A" CLASS - ORDINARY SOLID CARBONACEOUS COMBUSTIBLES. THESE INCLUDE WOOD, PAPER, CLOTH, FIBERGLASS, AND By: N f Date: Li
PLASTICS.
"B" CLASS - FLAMMABLE LIQUIDS AND GASES. THESE INCLUDE PAINTS, SOLVENTS, GASOLINE, OILS, AND HYDRAULIC FLUIDS. l
"C" CLASS - ELECTRICAL APPLIANCES. THESE INCLUDE COMPUTERS, POWER GENERATORS, AND POWER TRANSFORMERS. 11}1J1 � I�1111 UNITED FIRE & SAFETY
1 U 4611 NE MLK JR. BLVD PORTLAND, OR 97211
ABC (MONOAMMONIUM PHOSPHATE-BASED) IS SUITABLE FOR USE WITH ALL "A", `B", AND "C" CLASS HAZARDS. DRY CHEMICAL
TYPE EXTINGUISHING SYSTEMS ARE INAPPROPRIATE FOR THE PROTECTION OF CLASS D HAZARDS. AS PER NFPA 17, PRE- PLASTIC METAL TECHNOLOGIES
ENGINEERED DRY CHEMICAL SYSTEMS ARE NOT APPROVED FOR DEEP-SEATED OR BURROWING FIRES (SUCH AS ORDINARY 13950 SW 72"D - SUITE A
COMBUSTIBLES, WHERE THE AGENT CANNOT REACH THE POINT OF COMBUSTION), OR ON CHEMICALS THAT CONTAIN THEIR OWN TIGARD, OR 97213
OXYGEN SUPPLY (SUCH AS CELLULOSE NITRATE). DO NOT MIX DIFFERENT TYPES OF AGENTS, OR AGENTS FROM DIFFERENT SIZE DWG NO DWG REV
MANUFACTURERS. CHEMICAL REACTIONS MAY OCCUR WHEN INCOMPATIBLE CHEMICALS ARE MIXED. KEEP IN MIND THAT THE AGENT FIRE SYSTEM 1
USED FOR EACH SYSTEM MUST BE ACCEPTABLE TO THE AUTHORITY HAVING JURISDICTION (AHJ).
SCALE N/A 4/7/2021 SHEET I OF 9
s .- 27'_0"
48" 31 PIA BOOTH
�
MAST DUCT
\ \
' 13'-6" TF/ w� µ^ PIPE SIZES
-y JJJJ 3/4" 0 PIPE
It'-I *-----, 1`I rUi I x- 409'-0" 1" 0 PIPE
TFF TF►
64"
3/4'E
„RI TFP NOZZLES PLACEMENT♦/- 20 X OF
7'^�" /1'A PM „RI
MIDPOINT
—-—
FLRIRI
'-`1
LI r- 1 4I u FUSIBLE LINKS RATED AT
212 DEG F
RI NRTI Pull SOX— /
I
CONTROL HEM)-1
CONNECTION TO EXHAUST FAN SHUT
FAN SD DOWN. FAN SHALL SHUT DOWN UPON
ACTIVATION (CONNECTION BY OTHERS)
Cd TRD,MEAD
I
28' DIA
I EXHAUST DUCT
I�_r-- �/ (16' LONG)
r� FP , �'TFP NOZZLE LEGEND
SQUIRREL CAGE + DUCT / PLENUM NOZZLE - P/N 16190
FAN
T ' a�F + TOTAL FLOOD NOZZLE - P/N 16172
T TFI ( y ,i 33" + TOTAL FLOOD PERIMETER - P/N 17809
u
I AS 33"
i R L vlijIlb ;121 UNITED FIRE & SAFETY
Iu 4611 NE MLK JR. BLVD PORTLAND, OR 97211
REMOTE PULL STATION --PLENLRI
SHALL BE INSTALLED 42" - 40" ABOVE THE FINISHED FLOOR AND IT SHALL PLASTIC METAL TECHNOLOGIES
BE INSTALLED IN THE PATH OF EXIT AND REQUIRE A MAXIMUM FORCE OF 40 13950 SW 72m - SUITE A
LBS AND A MAXIMUM MOVEMENT OF 14" FOR ACTUATION
TIGARD, OR 97$2
SIZE DWG NO OWO REV
FIRE SYSTEM 1
PRE-ENGINEERED SYSTEM SHOP DRAWING ONLY - NOT TO SCALE SCALE N/A 4/72021 mint 2 OF
BOOTH COVERAGE & LIMITATIONS
3A.3.2 Module Perimeter Coverage,Total Flood IOCATE IDZSE AT WOW- E MArAAx1 ER0,1
OFADJACENTNOr1xE EDGE ENTRY PONE
SPRAY BOOTH NOZZLE CALCULATIONS
finders: �1 '
The Model IS45ABC is to be used for Module Perimeter Total Flooding applications. BOOTH COVERAGE USING MODULE PERIMETER WORK AREA
WNW
To ''/ ' T / COVERAGE & TFP NOZZLES
Thtal Flood Perimeter(TFP)Nozzle,(P/N 17809)is used in both one and two nozzle installations on the IS45ABC. mrE // BOOTH VOLUME = 27 x 14 x 9 = 3402 CU FT
The nozzle must be properly oriented at the upper perimeter of the module being protected.
MOcxr', MAX VOL PER NOZZLE = 2720 CU FT
NottleCoveraaes: 3402/ 2720 = 1.3 OR 2 NOZZLES REQUIRED
Maximum Module Volume: 2,720 ft.;per nozzle I
Maximum Module Area: 217.6ft.2per nozzle at12.5ft nozzle height % BOOTH AREA = 27 x 14 = 378 SQ FT
MaximumModuleHeight: 12.5ft. WIDE ; MAX AREA PER NOZZLE = 217.6 SQ FT
zi
Maximum Module Side length: 16 ft.(either dimension) �% 378 / 217.6 = 1.7 OR 2 NOZZLES REQUIRED
3A.a.1.2Moduk Perimeter Work Area Coverage.VPSBkonnnuedt TFP NOIZLEAS VIEWED DIRECTLY FROM BELOW 2 NOZZLES REQUIRED PER MANUAL — 2 PROVIDED
CRENTAEN ARROW,
MUST FONT AWAY ER'OS DUCT — 28 rr DIA
ADJACENT VODCLE EDGE
/ O MAX PERIMETER SINGLE NOZZLE — 46 IN.
40. OO REQUIRED AT PLENUM INTERFACE
TFP , REQ - 1 D/P NOZZLE
/
," PLENUM
/ ADJACENT AIMGIE EDGE
i
TFP j MAX DIMENSIONS = 4 X 15 X 10
/"//// // REQ — 1 TF NOZZLE — 1 PROVIDED
1406aereorm«Weft Mr,vrSa.naSraC.Two Trr Mom. VIIII
rpe9reN Maw... Num.. eofTnz I-J ��� UNITED FIRE & SAFETY
w*A mom. m..1 U 4611 NE MLK )R. BLVD PORTLAND, OR 97211
CMndertoTi I 1a 4 1
ntuMmk 1 10 1 0 PLASTIC METAL TECHNOLOGIES
Tod 1"PIP �rrrue old. Awn m.Mot d.rrso 13950 SW 72ro — SUITE A
rM
TIGARD, OR 97225
SIZE DWG NO DWG REV
FIRE SYSTEM 1
ue.szoa 4019.1013 SCALE N/A 4/7/2021 SHEET 30F9
EXHAUST DUCT & PLENUM COVERAGE & LIMITATIONS
3A.4.4 pining limitations.Plenum and DucL VPSB(continued). 3A.4.3 Duct Coverage,VPSB
The D/P Nozzle will protect either round or rectangular ducts up to 28 Net in length.My change in duct direction or
additional length requires an additional D/P nozzle.The duct nozzle must be centered at the duct entrance,pointed in
the direction of air flow,The tip of the duct nozzle must be within 6"of the duct entrance.
Round Ducts
Maximum Diameter.Sinsde Nozzle=46 Inches Rectangular Duch
Maximum Diameter.Two Nozzles=52 Inches The following table shows sample maximum rectangular
3/4 (nozzle spacirg..5 a duct diameter,located on the dimensions,based on the following two requirements:
same plane) Maximum Perimeter=144.5 Inches
s
/'I T I Maximum Diaconal 46 Inches
DPSpacing for two nozzles,protecting a duct
diameter larger than 46",up to 52"maximum Rectangular Ducts
3 ,4„ Side 1,Inches Side 2,ledges,
Maximum
12 44.4
��� ��--� 14 43.8
�/ \ 16 43.1
TF • i ,\ 18 42.3
D
—DM_-E iaP—'I I0 414
b 22 404
24 39.2
26 37.9
Vehide Paint Spray Booths, \
DUCT and STANDARD Plenum Coverages,IS1RARC,Two Nozzles \ 28 36.5
Cylinder Nozzle Nozzle Type Piping Pipe Maximum Maximum ', /, 30 31.3
Size Quantity Section Size,in. Length,ft. a of Elbows
32 33.0
ISIBABC Any of the following Cylinder % 36 4
2 combinations: to Ti. 5 32.5 32
-one 3-Way and one DIP; 34 31.0
-two D/P's; 36 28.6
-two TF's;
•one TF and one D/P 38 25.9
T1 to A 16 3 a 12'2
Nozzle 42 18.7
The maximum elevation of the DIP,TF and 3-way nozzles above cylinder is 23'4", W 134
������i,�T 1 UNITED FIRE SAFETY 4611 NE MLK JR. BLVD PORTLAND, OR 97211
PLASTIC METAL TECHNOLOGIES
13950 SW 72ND — SUITE A
TIGARD, OR 972
SIZE DWG NO DWG REV
FIRE SYSTEM 1
SCALE N/A 4/7/2021 SHEET 4 OF 9
EXHAUST DUCT & PLENUM COVERAGE & LIMITATIONS - CONTINUED
3A.4.2.1 Standard Plenum Coverage.VPSB
Plenum Type Nozzle Dimensions Maximum Nozzle Location Nozzle Nozzle
Used Per Nozzle Specifications Offset" Orientation
LxWxH
Backdraft(Option 1) TF 4'x 15'x 10' Volume=600ft3 12"x 12"Square, 0"to 6" Vertical,Pointing
Area=60ft2 Centered at Downward
Side=15' Ceiling
OPTION 1 :
TF
T- NOZZLE
10'
111.1
�°` J a1�1i � UNITED FIRE & SAFETY
J J J ]S 4611 NE MLK JR. BLVD PORTLAND, OR 97211
5' PLASTIC METAL TECHNOLOGIES
13950 SW 72mo — SUITE A
4 TIGARD, OR 97;
SIZE DwG NO DWG REV
FIRE SYSTEM 1
SCALE N/A 4/7/2021 SHEET 5 OF 9
AMEREX INDUSTRIAL SYSTEM TANKS
Aaiun Cylinder Assembly(Item 1):The agent cylinder is available In three configurations.Models 1518ABC P/N Mechanical Release Module II (Item 5): The new
16106),1535ABC(P/N 16207),and IS4SARC(P/N 1620e)are charged with AMEREX multi-purpose ABC dry
chemical agent.The cylinder assemblies are stored pressure designs with an operating pressure of 350 psi(2413 MRM II combines the same features and functionality of
KPa)at70'F(21'C).The cylinders are constructed of welded steel to DOT 48W 350 specifications.All three the 11977 MRM (see above) along with increased
•
models are 9 inches(22.9 cm)in diameter.The discharge valve,which is common to ell agent cylinders,is of
urged forged brass construction.The valve is equipped with a350 psi(2413KPa)pressure gauge and a fusible detection capabilities and a far simpler means of setting
element pressure relief plug.The valve controls agent discharge via a spring loaded,internal sealing stem that y the detection cable tension. The MRM II is available in the
must be depressed from the top of the valve to initiate agent discharge.The operating temperature of this and JO +'� following configurations, now pre-installed in its own
other listed system components is-40 F to 120'F(-40'C to 49'C)for Total Flood,-20'F m 120'F(-29'C to 49'C(for
Tankside Local Application,Vehicle and Open Front Paint Spray Booths,and 321 to 120'F(0'C to 49'C)for enclosure:
Overhead Local Application.Wanting:Agent cylinders are shipped horn the AMEREX factory fully charged with a �� / (
shipping plate Installed on the top of the vaNeto prevent accidental agent discharge and an anti-recoil plate on O �' lU 0 P/N 18000: MRM II with red-painted steel enclosure
the valve outlet to redirect chemical flow should an acddental discharge occur.Both of these plates must be ,a P/N 18001: MRM II with stainless steel enclosure
removed at installation.
,I ;� 11
P ��."v� The method of setting the detection cable tension on the
�� � II
Qo MRM II does not require the use of any tools (once the
�i►� cable is locked down into the large, knurled wind-up spool).
� i / A large lever to the right of the spool is used to increase
O the cable tension. Alignment of the bottom edge of the
1��� lever with markings on a label on the mounting plate
indicates when the proper tension has been reached. In
ti„ addition to being easier to set up, lowering cable tension to
--...t. (78.7cm)
31 change out detection links is now also much simpler.
•
110 17 13/16
(45.2cm)
.114111111111150/
IS 18 IS35 and 45
Dry Chemical Agent(Ilse I):For recharging of the Agent Minder Assemblies,following a discharge:
Ameres multi-purpose ARC Dry Chemical in 50lb.pails Is P/N 09761,(CM 535 Dry Chemical)
MSDS and HMIS information on these agents ere found In the Appendix Section of this manual.
T0.
Total Flood,Perimeter,TFP(P/N 1)609)
This nozzle Is designed to protect the Work Area in I y, 1 Duct and Plenum(D/P)Nozzle,(P/N 16190)
Q Vehicle Paint Spray Booth. It is also used in Total This nozzle is designed to protect exhaust ducts and
Flood applications. Nis to be installed at the upper certain plenums in Vehicle and Open Front Spray
i • perimeter of the module being protected. The TFP _
o nozzle contains,1"FPT as opposed to the%'MPT as Bootle(see Chapter 30.).
found on all the other IS nozzles(see Chapter 3A). NOZZLE BL11W
2375 NOZZLE BLOW-
Bo3,,) __ _ I--2.30' OFF CAP
(5.94 cm)
Total Flood(TF)Nozzle(P/N 16172) 44- JOB D 112 UNITED FIRE & SAFETY
n
— This nozzle is designed for Total Flooding Application of 4611 NE MLK JR. BLVD PORTLAND, OR 97211
Dry Chemical Agent into an enclosure with no more
ll than 5%total uncleseable openings. See Chapter 3A
PLASTIC METAL TECHNOLOGIES
_ for other limitations. It is also used in Vehicle Paint
- -_ Spray Booth and Open Front Spray Booth applications 13950 SW 72ND - SUITE A
z3a• NOZZLE P BLOW- (xeChapter 3A). TIGARD, OR 9721'j
(SC,srr
SIZE DWG NO DWG REV
FIRE SYSTEM 1
SCALE N/A 4/7/2021 SHEET 8 OF II
MICRO SWITCH ALL PIPING MUST BE SCHEDULE 40, HOT-DIPPED GALVANIZED STEEL PIPE, AND ALL
AMEREX P/N 12524 FITTINGS MUST BE 150 LB. CLASS. EXAMPLES OF ACCEPTABLE FITTING MATERIALS
SPDT, 21 AMPS, 125, 250 OR 277 VAC, , a ., INCLUDE HOT-DIPPED GALVANIZED MALLEABLE IRON, DUCTILE IRON, OR STEEL.
1HP 125, 250, 277 VAC; O= MIMI= COUPLINGS AND UNIONS MAY BE USED WHERE NECESSARY, AND REDUCING BUSHINGS OR
2HP, 250, 277 VAC - MIMI= REDUCING TEES CAN BE USED FOR CHANGES IN PIPE DIAMETER.
a i __ 7
MICRO SWITCHES, (P/N 12524), DESIGNED TO BE MOUNTED IN THE NOTE: BLACK STEEL PIPE AND FITTINGS CAN BE USED IN RELATIVELY NONCORROSIVE
MECHANICAL RELEASE MODULE (MRM / MRM II), THE ATMOSPHERES. ALL PIPE MUST BE REAMED AND BLOWN CLEAR. DIRT AND/OR CUTTING
PNEUMATIC RELEASE MODULE (PRM) AND ELECTRICAL RELEASE MODULE OIL MUST BE REMOVED FROM THE INSIDE OF ALL PIPE AND FITTINGS BEFORE
(ERM), ARE USED TO CONTROL VARIOUS OUTPUT FUNCTIONS. THESE ASSEMBLY. ASSEMBLE ALL PIPE AND FITTINGS TIGHT - 3 TURNS PAST HAND-TIGHT IS
OUTPUT FUNCTIONS MAY INVOLVE TURNING OFF OR TURNING ON POWER. RECOMMENDED. THE USE OF TEFLON TAPE, JOINT SEALANT, OR PIPE COMPOUND IS NOT
NECESSARY ON THE DISTRIBUTION PIPING NETWORK AND MUST NOT BE USED.
EXAMPLES OF OUTPUT FUNCTIONS ARE: SOUNDING A VISUAL OR AUDIBLE
ALARM, OPERATE AN ELECTRICAL GAS VALVE, SHUT OFF SUPPLY AIR FANS SECURE ALL PIPING TO A RIGID SURFACE USING APPROPRIATE HANGERS AND/OR CLAMPS
OR OTHER ELECTRICAL DEVICES DESIGNED IN ACCORDANCE WITH ACCEPTED PLUMBING TECHNIQUES. ONCE DISCHARGE NOZZLES ARE
INSTALLED, ENSURE THAT THE PLASTIC BLOW-OFF CAPS ARE IN PLACE.
TO SHUT OFF OR TURN ON UPON SYSTEM ACTUATION. TWO FIELD-USEABLE
P/N 12524 SPDT (SINGLE POLE, DOUBLE THROW) SWITCHES ARE PRE- THE FLOW OF THE MIXTURE OF DRY CHEMICAL AND GAS DOES NOT STRICTLY FOLLOW
INSTALLED IN THE BOTH THE MRM, THE PRM, AND THE ERM (A WIRE GENERAL HYDRAULIC PRINCIPLES BECAUSE IT IS A TWO-PHASE FLOW. CHANGES IN
GUTTER IS PROVIDED TO AID IN ELECTRICAL INSTALLATION). UP TO TWO DIRECTION OF FLOW CAUSE SEPARATION OF EXPELLANT GAS AND DRY CHEMICAL. TO
PROVIDE PROPER DISTRIBUTION OF DRY CHEMICAL UPON SPLITTING THE STREAM,
ADDITIONAL SPOT SWITCHES MAY BE ADDED TO THE MRM AND PRM (TWO SPECIAL ATTENTION MUST BE GIVEN TO THE METHOD IN WHICH AN APPROACH IS MADE
FOR THE ERM) FOR THE FOLLOWING CONFIGURATIONS: SPOT, DPDP, SPDT, TO A TEE AFTER A CHANGE IN DIRECTION. CERTAIN ACCEPTABLE METHODS ARE SHOWN
AND 4PDT (MRM). MICRO SWITCHES ARE INTENDED FOR INDOOR USE ONLY. BELOW, WHICH ARE TAKEN FROM NFPA 17, THE STANDARD FOR DRY CHEMICAL
ALL MICROS WITCH CONNECTIONS ARE TO BE MADE OUTSIDE THE MRM / EXTINGUISHING SYSTEMS:
PRM IN AN APPROVED JUNCTION BOX. MICRO SWITCH CONNECTIONS ARE
ALLOWED INSIDE THE ERM.
-; AoT LESS TH,N 20
iF DILAIETERS
COLOR CODE: RED = COMMON, YELLOW = N.O., BLACK = N.C. y � ;.
Xk�
ALARM-INITIATING MICRO SWITCH 0 �I
AMEREX P/N 18312
SPST 0.25A, 30 VDC, N.O. O E
�y�
THE OPTIONAL ALARM INITIATING MICRO SWITCH, (P/N 18312) IS ✓
USED WHEN IT IS REQUIRED TO BE ELECTRICALLY CONNECTED TO A FIRE �,„ _
ALARM SYSTEM PER NFPA 17 AND NFPA 72 IN A SUPERVISED, FOUR-WIRE
MANNER. IT IS DESIGNED TO BE MOUNTED IN THE MECHANICAL RELEASE
MODULE (MRM / MRM II) AND THE PNEUMATIC RELEASE MODULE (PRM) VnICIl 112' 4611 NE MLK JR.ITEBLVDFIRE
POSAFETY
RTLAND, OR 97211
ONLY FOR THE PURPOSE OF INITIATING AN ALARM IN A FIRE ALARM
SYSTEM. ALL MICRO SWITCH CONNECTIONS ARE TO BE MADE OUTSIDE THE
MRM / PRM IN AN APPROVED JUNCTION BOX. PLASTIC METAL TECHNOLOGIES
13950 SW 72ND - SUITE A
TIGARD, OR 97223
SIZE DWG NO DWG REV
FIRE SYSTEM 1
SCALE N/A 4/7f2021 SHEET 7 OF 9
MANUAL PULL STATION - MRM INSTALLATIONS (ITEM 31) : Rlpl
EVERY AMEREX INDUSTRIAL SYSTEM MUST USE AT LEAST Ca rFrc�
ONE MANUAL PULL STATION (P/N 11993). THIS DEVICE n 1" ��
PROVIDES A MEANS OF DISCHARGING THE SYSTEM 0 j%> � _i
MANUALLY. MANUAL PULL STATIONS SHOULD BE LOCATED IN ' ' ,e
A PATH OF EGRESS AND MOUNTED AT A HEIGHT CONFORMING \ �� „�
WITH THE LOCAL AUTHORITY HAVING JURISDICTION. THE 1 I
MANUAL PULL STATION MAY BE RECESSED OR SURFACE
�„.Pull na
MOUNTED �-z
J 5/B
I '445 MANUAL PULL STATION (OVERSIZED)- MRM INSTALLATIONS (ITEM 32): THIS
E Cr 1, " MANUAL PULL STATION MAY BE EITHER SURFACE OR RECESS MOUNTED. THE
ti� PULE PIN pP
iHLv „\ -= OVERSIZED COVER IS LARGE ENOUGH TO COVER THE SHEET ROCK ACCESS HOLE
Fv_l HlNr, F 1 (( - AND REMAIN ATTRACTIVE AND FUNCTIONAL. EVERY AMEREX INDUSTRIAL
I i � SYSTEM MUST USE AT LEAST ONE MANUAL PULL STATION (P/N 14320). THIS
al /IFI RE SYSSE MI\1
DEVICE PROVIDES A MEANS OF DISCHARGING THE SYSTEM MANUALLY. MANUAL
PULL STATIONS SHO
-4 ' i--+ -,i--
I! _j,n TM
UNIT
D
& SAFETY
7 +Di- ��s �� � 1JAill��b 10� 4611 NE MLK JR.E BLVD FIRE PORTLAND, OR 97211
'
7
I Y
PLASTIC METAL TECHNOLOGIES
U 13950 SW 72ND - SUITE A
TIGARD, OR 972,23)
SIZE DWG NO DWG REV
FIRE SYSTEM 1
SCALE N/A 4/7/2021 SHEET 8 OF 9
'JFT POR-3
1
),!,9 VAITID 1021
_-x \
SAFETY DATA SHEET pit .
Date of issue/Date of revision 8 January 2020
Version 17
Section 1 . Identification
Product name : 44GN098 BASE COMPONENT
Product code : 44GN098 BASE COMPONENT
Other means of : Not available.
identification
Product type : Liquid.
Relevant identified uses of the substance or mixture and uses advised against
Product use : Industrial applications.
Use of the substance/ : Coating.
mixture
Uses advised against : Not applicable.
Manufacturer : PPG Aerospace PRC-DeSoto
12780 San Fernando Road
Sylmar, CA 91342
Phone: 818 362 6711
Emeraencv telephone : (412)434-4515 (U.S.)
number (514)645-1320 (Canada)
01-800-00-21-400 (Mexico)
Section 2. Hazards identification
OSHA/HCS status : This material is considered hazardous by the OSHA Hazard Communication Standard
(29 CFR 1910.1200).
Classification of the : FLAMMABLE LIQUIDS-Category 2
substance or mixture EYE IRRITATION - Category 2A
CARCINOGENICITY- Category 1A
Percentage of the mixture consisting of ingredient(s)of unknown acute toxicity: 69.5%
(Oral), 85.8% (Dermal), 69.5% (Inhalation)
This product contains TiO2 which has been classified as a GHS Carcinogen Category 2
based on its IARC 2B classification. For many PPG products, TiO2 is utilized as a raw
material in a liquid coating formulation. In this case,the TiO2 particles are bound in a
matrix with no meaningful potential for human exposure to unbound particles of TiO2
when the product is applied with a brush or roller. Sanding the coating surface or mist
from spray applications may be harmful depending on the duration and level of
exposure and require the use of appropriate personal protective equipment and/or
engineering controls(see Section 8).
GHS label elements
United States Page: 1/14
SAFETY DATA SHEET pI .
Date of issue/Date of revision 16 February 2020
Version 15
Section 1 . Identification
Product name : 03GY292 BASE COMPONENT
Product code : 03GY292 BASE COMPONENT
Other means of : Not available.
identification
Product type : Liquid.
Relevant identified uses of the substance or mixture and uses advised aaainst
Product use : Industrial applications.
Use of the substance/ : Coating.
mixture
Uses advised against : Not applicable.
Manufacturer : PPG Aerospace PRC-DeSoto
12780 San Fernando Road
Sylmar, CA 91342
Phone: 818 362 6711
Fmeraencv telephone : (412)434-4515 (U.S.)
number (514) 645-1320 (Canada)
01-800-00-21-400 (Mexico)
Section 2. Hazards identification
OSHA/HCS status : This material is considered hazardous by the OSHA Hazard Communication Standard
(29 CFR 1910.1200).
Classification of the : FLAMMABLE LIQUIDS - Category 3
substance or mixture CARCINOGENICITY- Category 2
SPECIFIC TARGET ORGAN TOXICITY(SINGLE EXPOSURE) (Narcotic effects)-
Category 3
Percentage of the mixture consisting of ingredient(s) of unknown acute toxicity: 16.1%
(Oral), 16.1% (Dermal), 27.4% (Inhalation)
This product contains TiO2 which has been classified as a GHS Carcinogen Category 2
based on its IARC 2B classification. For many PPG products, TiO2 is utilized as a raw
material in a liquid coating formulation. In this case, the TiO2 particles are bound in a
matrix with no meaningful potential for human exposure to unbound particles of TiO2
when the product is applied with a brush or roller. Sanding the coating surface or mist
from spray applications may be harmful depending on the duration and level of
exposure and require the use of appropriate personal protective equipment and/or
engineering controls (see Section 8).
GHS label elements
United States Page: 1/15
SAFETY DATA SHEET
F63B12
Section 1 . Identification
Product name : POLANE®T Polyurethane Enamel
Carbide Black
Product code : F63B12
Other means of : Not available.
identification
Product type : Liquid.
Relevant identified uses of the substance or mixture and uses advised against
Not applicable.
Manufacturer : THE SHERWIN-WILLIAMS COMPANY
101 W. Prospect Avenue
Cleveland, OH 44115
Emergency telephone : US/Canada: (216) 566-2917
number of the company Mexico: SETIQ 01-800-00-214-00/(52)55-5559-1588 24 hours/365 days a year
Product Information : US/Canada: Not Available
Telephone Number Mexico: Not Available
Regulatory Information : US/Canada: (216) 566-2902
Telephone Number Mexico: Not Available
Transportation Emergency : US/Canada: (800)424-9300
Telephone Number Mexico: SETIQ 01-800-00-214-00/ (52)55-5559-1588 24 hours/365 days a year
Section 2. Hazards identification
OSHA/HCS status : This material is considered hazardous by the OSHA Hazard Communication Standard
(29 CFR 1910.1200).
Classification of the : FLAMMABLE LIQUIDS-Category 2
substance or mixture ACUTE TOXICITY(inhalation)-Category 4
SKIN CORROSION/IRRITATION -Category 2
SERIOUS EYE DAMAGE/EYE IRRITATION -Category 1
CARCINOGENICITY-Category 1A
TOXIC TO REPRODUCTION (Unborn child)-Category 2
SPECIFIC TARGET ORGAN TOXICITY(SINGLE EXPOSURE)(Respiratory tract
irritation)-Category 3
SPECIFIC TARGET ORGAN TOXICITY(SINGLE EXPOSURE)(Narcotic effects)-
Category 3
SPECIFIC TARGET ORGAN TOXICITY(REPEATED EXPOSURE)(lungs)-Category 1
ASPIRATION HAZARD-Category 1
Percentage of the mixture consisting of ingredient(s)of unknown oral toxicity: 12%
Percentage of the mixture consisting of ingredient(s)of unknown dermal toxicity: 21.8%
Percentage of the mixture consisting of ingredient(s)of unknown inhalation toxicity:44.
2%
GHS label elements
Hazard pictograms •
e •
Signal word : Danger
Date of issue/Date of revision :2/23/2018 Date of previous Issue :214/2018 Version :8 1/18
F63812 POLANE®T Polyurethane Enamel SHW-85-NA-GHS-US
Carbide Black