TIOZG s TABULAR DATA SHEEt10N
LX SERIES SPLIT SYSTEM AIR CONDITIONERS
13.0 SEER - R-410A- 1 PHASE - 1.5 TO 5 NOMINAL TONS
MO ELS: TC3B18 TO 60
PHYSICAL AND ELECTRICAL DATA •
MODEL TC3B1822S TC 2423S I TC383022S I TC3B3623S J TC384223S I TC3B4821S TC3B6022S
Unit Supply Voltage 208-230 V, 10,60 Hz
Normal Voltage Rangel 187 to 252
Minimum CircuitAmpacity 12.9 11.4 18.4 19.8 21.1 28.5 29.1
Maximum Overcurrent Device(A)2 20 15 30 30 35 50 50
Minimum Overcurrent Device(A)3 15 15 20 20 25 30 30
Type4 Scroll Rotary Scroll Scroll Scroll Scroll Scroll
Compressor Rated Load 9.7 8.4 14.1 14.7 15.9 21.8 22.2
Locked Rotor 46.0 53.0 73.0 75 112.3 117.0 127.9
Crankcase Heater No No No No No No No
Factory External Discharge Muffler No No No No No No No
HS Kit Required with TXV No n/a No No No No No
HS Kit Part Number(S1-2SA067 )' 21806 n/a 10106 10106 10206 10106 10206
Fan Diameter(in.) - 18 18 18 18 22 22 22
Rated HP 1/8 1/8 1/8 1/4 1/4 1/4 1/4
Fan Motor Rated Load(A) 0.80 0.80 0.80 1.50 1.30 1.30 1.30
Nominal RPM 1075 1075 1075 1100 850 850 850
Nominal CFM 1950 1950 2150 2575 2925 3225 3350
Face Area(ft2) 9.78 9.78 11,07 12.37 13.83 13.83 17.37
Coil Rows Deep 1 1 1 1 1 1 1
Fins per Inch 23 23 23 23 23 23 23
Liquid Line Set OD(Field Installed) 3/8 3/B 3/8 3/8 3/8 3/8 3/8
Vapor Line Set OD(Field Installed)6 3/4 3/4 3/4 3/4 7/8 7/8 1-1/81
UnitCharge(lb-oz)7 2-13 3-7 3-10 3-12 4-6 4-8 5-1
Charge(oz/ft) 0.62 0.62 0.62 0.62 0.67 0.67 0.75
Operating Weight(lb) 125 130 140 165 175 165 190
1. Rated in accordance with AHRI Standard 110-2012,utilization range'A'.
2. Dual dement fuses or HACR circuit breaker.Maximum allowable overcurrent protection.
3. Dual dement fuses or HACR circuit breaker.Minimum recommended overcurrent protection,
4. Rotary compressor models are limited to en equivalent length of lineset 01100 ft with no exceptions.
5. Use S1-2SA067 series kit. Refer to the Hard Start Kit Accessory Installation Manual,
6. For applications with non-standard vapor line sizes,refer to the APPLICATIONS AND ACCESSORIES section In the Technical Guide.
7. The unit charge is correct for the outdoor unit,smallest matched indoor unit,and 15 ft of refrigerant tubing.For tubing lengths ether than 15 ft,add or subtract the
amount of refrigerant,using the difference in actual linesel length(not the equivalent length)multiplied by the per foot value.
DIMENSIONS
=- - Dimensions Refrigerant Connection
� Unit
�! Model (1°) Service Valve Size
1 frt�*-I A 6 C Liquid Vapor
~`` - �, TC3B1822S 26 314 24 2A
� + ":� TC3B2423$ 26 3/4 24 24
TC3B3022S 30 24 24
�= % =` TC3B3623S 33 1/4 24 24 3/8 3/4
A _`�.1` :i:�+�.'�'v, TC3B4223S 30 291/4 291/4
� ` ry may- TC3B4621S 30 291/4 291/4 7/8
�.
vi == i 7C3660225 361/4 291/4 291/4 7/8$
� �.Y1Y�l-�
,' L 1 +j r+ t Adapter fitting must be field installed for the required 1 1/8-in.fine set.
`��-�-, i +'; All dimensions are in Inches and are subject to change without notice.
i i. F, .ice =��� Overall height is from the bottom of the base pan to the lop of the fan guard.
�..t? g Overall length and width include screw heads.
ewuvm
Johnson Controls Ducted Systems 5717290-BTD-C-1220
20 - 7
SYSTEM CHARGE FOR VARIOUS MATCHED SYSTEMSf6;,
Outdoor Unit TC3B18225 TC3B2423S TC3830225 TC3B3623S TC3B42238 TC3B4B21S TC386022S
Required Orifice or TXV" 0.049/BHI 0.057/BH1 0.061/BA1 0.070/BA1 0.0751 BC1 0.077/BC1 0.0841 BD1
Indoor Unit3'4'5 Additional Charge(oz)
AP18B 0 - - - _ _ _
AP24B 3 0 - - - - -
AP306 - 7 2 - - - -
AP366 - - - 0 - - -
AP36C - - 2 2 - - -
AP37C - - - 5 _ _ -
AP42C - - - _ - - -
AP48C - - - 5 2 0 -
AP48D - _
. - - 2 0
AP60(C,D) - - - -
2 -
AE18B 0 - - - - - -
AE246 3 0 - - - - -
AE3OB S 5 0 - - - -
AE38(B,C) - 7 2 0 - - -
AE42C - - - 5 2 - -
AE48(C,D) - - - 5 2 0 -
AE60C - - - - 9 2 0
AE60D - - - - 29 oz TXV ONLY 22 oz TXV ONLY 20 az TXV ONLY
AVC18B 0 - - - - - -
AVC24B 3 0 - - - - -
AVC3OB 8 5 0 - - - -
AVC36(B,C) - 7 2 0 - - -
AVC42C - - - 5 2 - -
AVC48(C,D) - - - 5 2 0 -
AVC60C - - -
- - 2 0
AVC6OD - - - - 29 oz TXV ONLY 22 oz TXV ONLY 20 oz TXV ONLY
CF/CM/CU18(A,B) 0 - - - - - -
CF/CMICU24(A,B) 3 0 - - - - -
CF/CM/CU30(A,B,C) 8 5 0 - - - -
CF/CM/CU36(A,B,C,D) 10 7 2 0 - - -
CF/CM/CU42(B,C,D) - 11 2 2 0 - -
CF/CMICU48(C,D) - - - 5 2 0 -
CF/CM/CU60(C,D) - - - - 9 2 0
CF/CM64D - - - - 29 oz TXV ONLY 22 oz TXV ONLY 20 oz TXV ONLY
Note:Some of the combinations shown in this table require Advanced Main Air Circulating Fan indoor product.For approved coil only matches,refer
to the COOLING CAPACITY-Upflow,Downflow,and Horizontal Furnaces and Coils(Coil Only Ratings)table in the Technical Guide.
1. For applications requiring a TXV,use S1-1TVM^'series kit.
2. Approved orifice(s)shipped with outdoor unit.
3. Systems matched with furnaces or air handlers not equipped with blower-off delays may require 60-s time delay.
4. CF cots cannot be used in horizontal applications.
5. Charge adders shown above do not Indicate that coils are rated for every application.Reler to the performance data tables in the Technical Guide for actual perfor-
mance for specified system matches.Obtain certified system ratings from pvtw.ahridirectory.oro
CHARGING PROCEDURES
1. Check the factory unit charge Usted on the unit nameplate to verify the refrigerant charge for the outdoor unit,the smallest matched Indoor unit,and the 15 ft of inter-
connecting lineset.
2. Verify the indoor metering device and additional charge required for the specific matched Indoor unit In the system using the SYSTEM CHARGE FOR VARIOUS
MATCHED SYSTEMS table.
3. Add additional charge for the amount of interconnecting lineset tubing greater than 16 ft at the rate specified in the PHYSICAL AND ELECTRICAL DATA table.
4, For installations requiring additional charge,weigh in refrigerant for the specific matching indoor unit and actual llneset length.
5. After weighing in the charge adders for the matched indoor unit and lineset,verify the system operation against the temperatures and pressures in the charging chart
for the outdoor unit,Locate the charging charts on the outdoor unit and also in the Service Data Application Guide on mar.simnlvoettinetheiobdones_om.Follow the
subcool or superheat charging procedure in the Installation Manual according to the type of indoor metering device In the system,and allow 10 min after each
charge adjustment for the system operation to stabilize.Record the charge adjustment made to match the Charging chart.
6. Permanently stamp the unit nameplate with the TOTAL SYSTEM CHARGE defined as follows:TOTAL SYSTEM CHARGE=base Charge(as shipped)+charge
adder for matched indoor unit+charge adder for actual Ilneset length+charge adjustments to match the charging chart.
Subject to change without notice.Published in U.S.A. 5717290-BTD-C-1220
Copyright®2020 by Johnson Controls.All rights reserved. Supersedes:5717290-BTD-B-0420
York International Corp.
5 York 6 9-
730 Norman, �OK 73069 .
•
lob g SL,Lf �tt( �j ��, (03
Goodman GMEC80 / GCEC80
Air Conditioning&Heating
HEATING INPUT: 40,000-120,000BTU/H TWO-STAGE, MULTI-SPEED ECM
GAS FURNACE
80%AFUE
Contents
Nomenclature 2
Product Specifications 3
I Goodman
Dimensions 5
Accessories 6
G oddmo Airflow Data 7
Wiring Diagram 24
Standard Features Cabinet Features
• Two-stage gas valve provides quiet, • Fully insulated,heavy-gauge steel cabinet
economical heating with durable baked-enamel finish
• Efficient and quiet multi-speed ECM circulator motor • Multi-position installation:
• SureStart®Silicon Nitride igniter GMEC80:upflow,horizontal left or right
designed for long igniter life GCECSO:downflow,horizontal left or right
• Self-diagnostic control board • Removable bottom for side-or
• Low constant fan speed circulates air bottom-return applications
throughout the home • Convenient left or right connection
• Quiet,two-speed induced draft blower for gas/electric service
• California Low NOx emissions-compliant • Cabinet air leakage 5 2%
models available • Coil and furnace fit flush
• Can no longer be installed in California's for most installations
South Coast Air Quality Management District
(SCAQMD)on or after October 1,2019.
• AHRI Certified;ETL listed
ILIFETIME 1 O UNITI 10 PARTS
NfiAT EXCXANOER LIMITED LIMITED A.
LIMITta WARRANTY' YEAR WARRANT,' YEAR WARRANT!
���:1.......t. emBaM'MTM 1.1111coManrsnvN BI3Ei
C 11• nrii.,5y41d rvmUA0000 000I.
_ - cramra••1111. scan glUt Rmu •-�-�_
Intertek .aemor. .ae rw•
•tomplein wauaniy[kWh ayarlalde from you; afal dttdrxr as at wwytgoodnt mmfi['Mtn to lemma
lhr ldethne Hoot Exchange(tlrmrod Warranty(gwd Ief as long as you own your Iwtn✓).101Cn
1.0•1111 fIJ,4men1I nmX•d Warraolo and 10V¢ar Pans LlrMtcd wartanty online rmjitt4 W n must be
(VmdeNrl wdtan(N)dns of rs,rallaUtln adlrM regntfalbn n not rayWccl Ui CaldWma w()miter
SS-GMEC80/GCECSO www.goodmanmfg.com 2/21
YUWOMLR FIIO
I0f l3 S'bk-} �° li' j Lp 72
SPECIFICATIONS
1
A
IGMEC80 GMEC80 I GMEC80 I GMEC80 I GMEC80 GMEC80 1 GMEC80 I GMECBD I GMEC80 i GMEC80 I GMEC80
0403A• 0603A* 06038* 08036• 08048* 0804C• 0805C• 0805D• 1004C* 1005C* 1205D*
HEATING CAPACITY
High Fire Input(BTU/h)' 40,000 60.000 60,000 80,000 80,000 80,000 80,000 80000 100,000 100,000 120,000
High Fire Output(BTU/h)':
Natural Gas 32.000 43,000 48,000 64,000 64,000 64,000 64,000 64,000 30,000 80,000 96,000
LP Gas 32,000 48,000 48,000 64,000 64,000 64,000 64,000 64,000 80,000 80,000 96,000
Low Fire Input(BTU/h)' 28,000 42,000 42,000 56,000 56.000 56,000 56,000 56,000 70,000 70,000 84,000
Low Fire Output(BTU/h)':
Natural Gas 22,400 33.600 33,600 44,800 44,800 44,800 44,800 44,800 56,000 56,000 67,200
LP Gas 22,400 33,600 33,600 44,800 44,800 44,800 44.800 44,800 56,000 56,000 67,200
AFUE2 Bo 80 80 80 80 80 80 80 8D 80 80
Available AC@ 0.5'ESP 1.5.3.0 1.5-4.0 1.5-4.0 3.0-4.0 2.0-5.0 2.5-5.0 2.5-5.0 2.5-5.0 2.0:5.0 2.0.5.0 2.0-5.0
Temperature Rise Range(°F) 15-45/ 20-50/ 15.45/ 30-60/ 30-60/ 25-55/ 25-55/ 20-50/ 25-55/ 20-50/ 40-70/
15-45 20-50 15-45 30-60 30-60 25.55 25-55 20-50 25-55 20-50 40-70
CIRCULATOR BLOWER
Size (Dx W) 10"x 6" 10"x 6' 10'x8" 10"x8" 10'x 10' 10"x 10" 10"x1o" 11"x 10'' 10"x 10" 10"x 10' 11"x 10"
Horsepower-RPM 1/2 1/2 1/2 1/2 3/4 3/4 3/4 3/4 3/4 1 1
Speed 5 5 5 5 5 5 5 5 5 5 5
Vent Diameter' 4" 4" 4" 4" 4' 4" 4' 4" 4" 4" 4"
No,of Burners 3 3 3 4 4 4 4 4 5 5 6
ELECTRICAL DATA
Min.Grout Ampacity' 8.7 3.7 8.7 8.7 12.45 12.45 15.32 15.32 12.45 15.32 15.32
Max Gvercurrent Device lamps)' 15 15 15 15 15 15 20 20 15 20 20
SHIP WEIGHT(1133) 105 10 107 118 121 129 129 129 124 124 124
' Natural Gas BTU/h:for altitudes 0-4500'above see level.reduce input rating by 4%for each 1000'above 4500'altitude
' DOE AFUE based upon Isolated Combustion system IICSI
' Minimum Circuit Ampacity=(1.25 a Circulator Blower Amps).ID Blower amps,Wire size should be determined in accordance with National Electrical Codes.Extensive wire
runs will require larger wire sizes.
" Maximum Overcommit Protection Device refers to maximum recommended fuse or circuit breaker size.May use fuses or HACK-type circuit breakers of the same size as noted.
NOTES
• All furnaces are manufactured for use on 315 VAC 6014z.singk-phase electrical supply.
• Gas Service Connection W'MT
• Important:Size fuses and wires properly and make electrical connections in accordance with the National Electrical Code and/or all
existing local codes.
•
•
•
SS-GMEC80/GCEC80 wwwgoodmanmlg.com 3