Energy Code: 2012 IECC
Project Title: AFC Tigard
Location: Tigard, Oregon
Climate Zone: 4c
Project Type: Addition
Vertical Glazing/Wall Area: 21%
Construction Site: Owner/Agent: Designer/Contractor:
11675 SW Pacific Hwy Wilsal LLC CIDA, Inc
Tigard, OR 97223 7286 SW Ascot Ct 15895 SW 72nd Ave., Suite 200
Portland, OR 97225 Portland, OR 97224
(503) 709-6975 503-226-1285
lesliej@cidainc.com
Building Area Floor Area
1-Health care clinic : Nonresidential 864
Envelope Assemblies
Assembly Gross Area Cavity Cont. Proposed Budget U-
or R-Value R-Value U-Factor Factorial
Perimeter
Floor 2:Slab-On-Grade:Unheated,Vertical 1 ft.,[Bldg. Use 1 -Health 121 --- 10.0 0.580 0.540
care clinic](c)
Roof 1:Attic Roof with Wood Joists, [Bldg. Use 1 -Health care clinic] 886 49.0 0.0 0.021 0.027
NORTH
Exterior Wall 1:Concrete Block:8", Partially Grouted,Cells Empty, Light 332 13.0 0.0 0.071 0.078
Density, Furring:Wood,[Bldg.Use 1 -Health care clinic]
Window 1:Metal Frame:Fixed, Perf.Specs.:Product ID Arcadia 156 --- --- 0.390 0.380
AG451T,SHGC 0.41,[Bldg.Use 1 -Health care clinic](b)
Exterior Wall 5:Wood-Framed, 16"o.c.,[Bldg. Use 1 -Health care 6 21.0 0.0 0.062 0.064
clinic]
Exterior Wall 3:Wood-Framed, 16"o.c.,[Bldg.Use 1 -Health care 22 26.0 0.0 0.056 0.064
clinic]
EAST
Exterior Wall 6:Wood-Framed, 16"o.c.,[Bldg.Use 1 -Health care 236 21.0 0.0 0.062 0.064
clinic]
WEST
Exterior Wall 4:Wood-Framed, 16"o.c.,[Bldg. Use 1 -Health care 236 21.0 0.0 0.062 0.064
clinic]
Door 1:Insulated Metal,Swinging,[Bldg.Use 1 -Health care clinic] 21 --- --- 0.200 0.370
(a) Budget U-factors are used for software baseline calculations ONLY,and are not code requirements.
(b) Fenestration product performance must be certified in accordance with NFRC and requires supporting documentation.
(c) Slab-On-Grade proposed and budget U-factors shown in table are F-factors.
Project Title: AFC Tigard Report date: 07/29/21
Data filename: F:\GENADMINIPROJECTS121\0085.01 AFC Tigard Landlord (jhc)1COMCheck.cck Page 1 of 12
l
Envelope PASSES: Design 3%better than code
Envelope Compliance Statement
Compliance Statement: The proposed envelope design represented in this document is consistent with the building plans,
specifications, and other calculations submitted with this permit a plication.The proposed envelope systems have been
designed to meet the 2012 IECC requirements in COMcheck V on 4.1. .3 and to comply with any applicable mandatory
requirements listed in the Inspection Checklist.
ILS ivnes kssoc $ of-zO2-)
Name-Title Si ture Date
Project Title: AFC Tigard Report date: 07/29/21
Data filename: F:\GENADMIN\PROJECTS121\0085.01 AFC Tigard Landlord (jhc)\COMCheck.cck Page 2 of 12
` COMcheck Software Version 4.1.5.3
ilInspection Checklist
Energy Code: 2012 IECC
Requirements: 0.0% were addressed directly in the COMcheck software
Text in the "Comments/Assumptions" column is provided by the user in the COMcheck Requirements screen. For each
requirement, the user certifies that a code requirement will be met and how that is documented, or that an exception
is being claimed. Where compliance is itemized in a separate table, a reference to that table is provided.
Section
# Plan Review Complies? Comments/Assumptions
& Req.ID
C103.2 Plans and/or specifications provide all NComplies
[PR1]1 information with which compliance ❑Does Not
can be determined for the building
envelope and document where ❑Not Observable
exceptions to the standard are ❑Not Applicable
claimed.
C406 Plans, specifications, and/or ❑Complies
[PR9]1 calculations provide all information ❑Does Not
with which compliance can be
determined for the additional energy ❑Not Observable
efficiency package options. LAJNot Applicable
C402.3.1 The vertical fenestration area <= 30 'XComplies
[PR10i1 percent of the gross above-grade wall ❑Does Not
area.
❑Not Observable
❑Not Applicable
C402.3.1 The skylight area <= 3 percent of the ❑Complies
[PR11]1 gross roof area. ❑Does Not
['Not Observable
ICINot Applicable
C402.3.2 In enclosed spaces > 10,000 ft2 ❑Complies
[PR14]1 directly under a roof with ceiling ❑Does Not
heights >15 ft. and used as an office,
lobby, atrium, concourse,corridor, ❑Not Observable
storage, gymnasium/exercise center, XNot Applicable
convention center, automotive
service, manufacturing, non-
refrigerated warehouse, retail store,
distribution/sorting area,
transportation, or workshop,the
following requirements apply: (a)the
daylight zone under skylights is >=
half the floor area; (b) the skylight
area to daylight zone is >= 3 percent
with a skylight VT>= 0.40; or a
minimum skylight effective aperture
>= 1 percent.
C402.3.2. Skylights in office, storage, ❑Complies
2 automotive service, manufacturing, ❑Does Not
[PR15]1 non-refrigerated warehouse, retail ❑Not Observable
store, and distribution/sorting area
have a measured haze value > 90 C&INot Applicable
percent unless designed to exclude
direct sunlight.
Additional Comments/Assumptions:
1 High Impact(Tier 1) 2 Medium Impact (Tier 2) 3 Low Impact(Tier 3)
Project Title: AFC Tigard Report date: 07/29/21
Data filename: F:\GENADMIN\PROJECTS\21\0085.01 AFC Tigard Landlord (jhc)\COMCheck.cck Page 6 of 12
Section
Footing / Foundation Inspection Complies? Comments/Assumptions
& Req.ID
C104 Installed slab-on-grade insulation type :❑Complies See the Envelope Assemblies table for values.
[FO312 and R-value consistent with insulation ❑Does Not
specifications reported in plans and ❑Not Observable
COMcheck reports.
®Not Applicable
C303.2 Slab edge insulation installed per 1NIComplies
[FO4]2 manufacturer's instructions. ❑Does Not
❑Not Observable
ONot Applicable
C402.2.6 Slab edge insulation depth/length. ®Complies See the Envelope Assemblies table for values.
[FO5]2 Slab insulation extending away from ❑Does Not
building is covered by pavement or ❑Not Observable
>= 10 inches of soil.
ENot Applicable
C403.2.8. Exterior insulation protected against ®Complies
1 damage, sunlight, moisture, wind, ❑Does Not
[FO6]3 landscaping and equipment ❑Not Observable
maintenance activities.
DNot Applicable
C402.2.8 Bottom surface of floor structures ❑Complies See the Envelope Assemblies table for values.
[FO12]3 incorporating radiant heating ❑Does Not
insulated to >=R-3.5. ❑Not Observable
NNot Applicable
Additional Comments/Assumptions:
1 High Impact(Tier 1) 2 Medium Impact (Tier 2) 3 Low Impact(Tier 3)
Project Title: AFC Tigard Report date: 07/29/21
Data filename: F:\GENADMIN\PROJECTS\21\0085.01 AFC Tigard Landlord (jhc)\COMCheck.cck Page 7 of 12
Section
# Framing /Rough-In Inspection Complies? , Comments/Assumptions
& Req.ID
C402.4.1, The building envelope contains a [XComplies
C402.4.2 continuous air barrier that is sealed in ❑Does Not
[FR16]1 an approved manner and either ❑Not Observable
constructed or tested in an approved
manner. Air barrier penetrations are ❑Not Applicable
sealed in an approved manner.
C402.4.3, Factory-built fenestration and doors ®Complies
C402.4.4 are labeled as meeting air leakage ❑Does Not
[FR18]3 requirements.
['Not Observable
❑Not Applicable
C402.4.7 Vestibules are installed on all building ❑Complies
[FR17]3 entrances. Doors have self-closing ❑Does Not
devices.
❑Not Observable
21Not Applicable
C402.3.3, Vertical fenestration U-Factor. ®Complies See the Envelope Assemblies table for values.
C402.3.4 ❑Does Not
[FR8]1
[Not Observable
❑Not Applicable
C402.3.3 Vertical fenestration SHGC value. ®Complies See the Envelope Assemblies table for values.
[FR1O]1 ❑Does Not
❑Not Observable
❑Not Applicable
C303.1.3 Fenestration products rated in IX Complies
[FR12]2 accordance with NFRC. ❑Does Not
❑Not Observable
❑Not Applicable
C303.1.3 Fenestration products are certified as DAComplies
[FR13]1 to performance labels or certificates ❑Does Not
provided.
[Not Observable
❑Not Applicable
Additional Comments/Assumptions:
1 High Impact(Tier 1) 2 Medium Impact(Tier 2) 3 Low Impact(Tier 3)
Project Title: AFC Tigard Report date: 07/29/21
Data filename: F:\GENADMIN\PROJECTS\21\0085.01 AFC Tigard Landlord (jhc)\COMCheck.cck Page 8 of 12
Section
Insulation Inspection Complies? I Comments/Assumptions
& Req.ID
C402.4.1. All sources of air leakage in the XComplies
1 building thermal envelope are sealed. EDoes Not
[IN1]1 caulked, gasketed, weather stripped ❑Not Observable
or wrapped with moisture vapor-
permeable wrapping material to ENot Applicable
minimize air leakage.
C402.4.2. Roof R-value. For some ceiling CRComplies See the Envelope Assemblies table for values.
1 systems, verification may need to ❑Does Not
[IN2]1 occur during Framing Inspection. [Not Observable
❑Not Applicable
C303.2 Roof insulation installed per ®Complies
[IN3]1 manufacturer's instructions. Blown or ❑Does Not
poured loose-fill insulation is installed [Not Observable
only where the roof slope is <=3 in
12. ❑Not Applicable
C303.2 Above-grade wall insulation installed XComplies
[IN7]1 per manufacturer's instructions. EDoes Not
❑Not Observable
❑Not Applicable
C104 Installed floor insulation type and R- ❑Complies See the Envelope Assemblies table for values.
[INB]2 value consistent with insulation EDoes Not
specifications reported in plans and ❑Not Observable
COMcheck reports.
( Not Applicable
C303.1 Building envelope insulation is labeled {Complies
[IN10]2 with R-value or insulation certificate EDoes Not
providing R-value and other relevant ❑Not Observable
data.
❑Not Applicable
C303.2.1 Exterior insulation is protected from ®Complies
[IN14]2 damage with a protective material. EDoes Not
Verification for exposed foundation ❑Not Observable
insulation may need to occur during
Foundation Inspection. ❑Not Applicable
Additional Comments/Assumptions:
1 High Impact (Tier 1) 2 Medium Impact(Tier 2) 3 Low Impact(Tier 3)
Project Title: AFC Tigard Report date: 07/29/21
Data filename: F:\GENADMIN\PROJECTS\21\0085.01 AFC Tigard Landlord (jhc)1COMCheck.cck Page 10 of 12
Q
Section
# Final Inspection Complies? Comments/Assumptions
& Req.ID
C402.4.6 Weatherseals installed on all loading ❑Complies
[FI37]1 dock cargo doors. ❑Does Not
['Not Observable
KINot Applicable
C402.4.8 Recessed luminaires in thermal ❑Complies
[F126]3 envelope to limit infiltration and be IC ❑Does Not
rated and labeled. Seal between
interior finish and luminaire housing. ❑r�Not Observable
yty Not Applicable
Additional Comments/Assumptions:
I. [High Impact (Tier 1) 2 Medium Impact(Tier 2) 3 Low Impact(Tier 3)
Project Title: AFC Tigard Report date: 07/29/21
Data filename: F:\GENADMIN\PROJECTS\21\0085.01 AFC Tigard Landlord (jhc)\COMCheck.cck Page 11 of 12
Project Title: AFC Tigard Report date: 07/29/21
Data filename: F:\GENADMIN\PROJECTS\21\0085.01 AFC Tigard Landlord (jhc)\COMCheck.cck Page 12 of 12