Report
OFFICE COPY ���2°2/-oaiz/ AGO/ irdilZ/ke2 i RED HAWK FIRE PROTECTION, LLCECEIVED 3801 NW Fruit Valley Road Suite D SE" 2 9 CA Vancouver, WA 98660 CITY OF TIGARD (360) 984-3712 BUILDING DIVISION 4,00000.0 (' fc OPERATION & MAINTENANCE MANUAL FOR Hunziker Warehouse Tigard, OR RHFP JOB NO. 240273 SECTION 1 Pipe and Fittings ;• rrrr�rrrrrr� Eddythread 40 A Lightweight Schedule 40 Replacement Pipe That Has a Corrosion Resistance Ratio of 1.0 Bull Moose Tube Company has been making pipe for a long time and is recognized as a producer of quality pipe products. Eddythread 40 is designed with the same thoroughness as our other fine pipe products and now our customers have an option to buy a carefully designed replacement for Schedule 40 that: • Has a Corrosion Resistance Ratio of 1.0 • Has a Pressure Rating of 300 psi • Is Lighter Weight Than Schedule 40 • Is Approved by Factory Mutual and Listed by Underwriters Laboratories • Is Produced in Accordance to ASTM A-135 and A-795 • Can be Used With Standard Schedule 40 Threaded Fittings, Couplings and Valves • Is Produced From Steel With Excellent Properties of Strength and Threadability • Can be Used in Wet, Dry, Preaction, and Deluge Type Sprinkler Systems* • Offers Lower Freight Costs wtr. EDDYTHREAD 40 SPECIFICATIONS NOMINAL PIPE SIZE (in) WEIGHT (Ibs/ft) I.D. (in) BUNDLE SIZE 1 1.461 1.083 70 1 1/4 2.070 1.418 51 1 1/2 2.547 1.654 44 2 3.308 2.123 30 CORROSION RESISTANCE RATIOS ii NOMINAL PIPE SIZE (in) 1111=11111 EDDYTHREAD 40 . 1 1.00 1.00 1 1/4 1.00 1.00 1 1/2 1.00 1.00 2 1.00 1.00 *Eddythread 40 can be hot dipped galvanized to meet FM's requirement for dry systems .ffitmw gmmtar 93iY:4Cm4°PSS7iwo.rorpwins ° fi ° Pm.:YB"Gh,1'C.ffW% 9 mmmvi RN AttriR'+,Pr �?:+4€m onlifmm irimim R+ }g453'a!,prowv,,,:, v,,T,-Twm kpww7YI#W$FR3mxr ,,,,,,,,,,, ,,, Chesterfield,ClarksonRoad For additional information, g �L Us (� MO 63017 contact your salesperson today at I l BULL(MOOSE TUBE COMPANY (800)325-4467 (800)325-4467 or(636)537-2600 LISTED FAX:(636)537-2645 in the USA,or from Canada www.bullmoosetube.com call(800)882-4666 41:› A C APAR company e-mail:sales@builnioosetube.com APPROVED All information contained herein is accurate as known at the time of publication. Bull Moose Tube reserves the right to change product specifications without notice and without incurring obligation. 8.08 Eddy Flow The Cost Effective Replacement for Schedule 10 Realizing the growing need of fire protection systems systems with a working pressure of 300 psi or less. in commercial and residential construction, Bull Please check with appropriate sources for up-to-date Moose Tube has added Eddy Flow to its listings and approval information. comprehensive line of sprinkler pipe products. As an added benefit, it is more economical to use than Eddy Flow is a specially engineered replacement for schedule 10 due to reduced delivery costs and ease schedule 10, offering better flow characteristics while of handling. Furthermore, Eddy Flow's larger ID providing design flexibility. This product is FM provides an opportunity for downsizing and further approved, as well as UL listed (for U.S. and Canada) cost savings. for roll grooving and welding for use in fire protection COMPARISON INSIDE DIAMETER C.R.R.* Nominal Pipe Eddy Flow Schedule 10 Schedule 40 U.D. (in) Eddy Flow Schedule 40 Sire in in in in 1 1/4 1.660 1.530 1.442 1.380 1.98 1.00 1 1/2 1.900 1.728 1.682 1.610 3.44 1.00 2 2.375 2.203 2.157 2.067 2.78 1.00 2 1/2 2.875 2.705 2.635 2.469 1.66 1.00 3 3.500 3.334 3.260 3.068 1.00 1.00 4 4.500 4.310 4.260 4.026 1.00 1.00 * Corrosion Resistance Ratio BENEFITS • Dual Certified to ASTM A135 and A795. • FM Approved for roll grooved,and welded,and plain-end application In wet systems. • UL Listed(for U.S.and Canada)for joining by welding or by listed rubber gasketed fittings for use in wet,dry, preactlon,and deluge type sprinkler systems. • UL Listed(for US and Canada)and FM Approved for use with Victaulle FITS'Fittings in plain end applications. • Lightweight-saves shipping costs,and offers easier handling. • Can be used with roll grooved couplings or welded outlets for pressures up to 300 psi. • Floor stock available in various lengths produced In Casa Grande(AZ),Gerald(MO),and Masury(OH).Also can be ordered In custom lengths.. • Can be used for wet and day systems. Eddy Flow can be hot dipped galvanized to meet FM's requirement for dry systems. PIPE PREPARATION For proper operation,all pipe surfaces should be cleaned prior to installation. In order to provide a leak-tight seat for the gasket,pipe surfaces should be free from indentations and projections from the end of the pipe to the groove. All loose paint,scale,dirt,chips,grease,and rust must be removed prior to installation. Failure to take these important steps may result in improper coupling assembly,causing leakage. Also,check the manufacturer's instructions for the specific fitting used. 1819 Clarkson Road For additional information, tf �L us A`•- Chesterfield,MO 63017 contact your salesperson today at LISTED •1 8 e,A.l✓1 Ll tt ig COMPANY (800)325-4467 (800)325=4467 or(636)537 26t�t� FAX;(636)537-2645 in the USA,or from Canada www,bulbnoosetubesQant call(800)882-4666 A =_111- company e=mail s les l ti tim tttbe,cpn tl (� 41 1 APPROVED All information contained herein in accurate as known at the lean cal publication. Bull Moose Tube reserves the right to change product specifications without notice and without incurring obligation. tt'U8 Bull Moose Tube EDDY FLOW Steel Pipe Joined by Threading, Bonding or Compression/Grooved Couplings Max Zone of Influence Load (Fpw) lbs. Max. Transverse and 4-way Brace Spacing (ft.) ***According to Pipe Transverse Brace Spacing* HLF for the 2006 &2009 IBC (ASCE 7-05 ) & Cp for NFPA-13 shown in BOLD TYPE Size 20 ft. 25 ft. 30 ft. 35 ft. 40 ft. 0.25 0.50 0.75 1.00 1.25 1.50 1.75 2.00 2.25 2.50 2.75 3.00 1 1/4 136 109 89 76 64 40 40 37 32 29 26 24 23 21 20 19 18 1 1/2 232 185 152 130 109 40 40 40 35 31 29 27 25 23 22 21 20 2 372 297 244 209 175 40 40 40 38 34 31 28 27 25 24 23 22 2 1/2 549 440 360 309 258 40 40 40 40 36 32 30 28 26 25 24 23 3 809 648 531 455 381 40 40 40 40 37 34 31 29 28 26 25 24 4 1544 1235 1012 867 726 40 40 40 40 40 37 34 32 30 29 28 26 Bull Moose Tube EDDYTHREAD 40 Steel Pipe Joined by Threading, Bonding or Compression/Grooved Couplings Max Zone of Influence Load (Fpw) lbs. Max. Transverse and 4-way Brace Spacing (ft.)***According to Pipe Transverse Brace Spacing* HLF for the 2006 &2009 IBC (ASCE 7-05 ) & Cp for NFPA-13 shown in BOLD TYPE Size 20 ft. 25 ft. 30 ft. 35 ft. 40 ft. 0.25 0.50 0.75 1.00 1.25 1.50 1.75 2.00 2.25 2.50 2.75 3.00 1 119 95 78 67 56 40 40 36 31 28 25 24 22 21 20 19 18 1 1/4 218 175 143 123 103 40 40 40 35 31 28 26 _ 25 23 22 21 20 1 1/2 312 250 205 175 147 40 40 40 37 33 30 28 26 25 23 22 21 2 518 414 339 291 243 40 40 40 40 36 33 30 29 27 26 24 23 Victaulic® Grooved End Fittings ✓ctaeuIicr 07.oi • • vise No.20 Tee No. 10 Elbow 1.0 PRODUCT DESCRIPTION Available Sizes • 3/4—60720— 1500 mm Maximum Working Pressure • Fitting pressure ratings are equivalent to the pressure ratings of the coupling used to install them. Application • Connects pipe, provides change in direction and adapts sizes or components. • Supplied with Victaulic OGS grooves. • Exclusively for use with Victaulic couplings, valves, accessories and pipe which feature ends formed with the Victaulic OGS groove profile. Pipe Materials • Carbon Steel or Stainless Steel NOTE • These fittings are not intended for use with Victaulic plain end couplings.Intended for use only in grooved piping systems.When connecting wafer or lug type butterfly valves directly to Victaulic fittings using Style 741 or Style 743 flange adapters,be sure to check disc clearance dimensions with I.D.dimension of 444104 fitting. ALWAYS REFER TO ANY NOTIFICATIONS AT THE END OF THIS DOCUMENT REGARDING PRODUCT INSTALLATION,MAINTENANCE OR SUPPORT. System No. Location [Spec Section Paragraph Submitted By Date I Approved Date— victaulic.com 07.01 1449 Rev AD Updated 02/2017 ©2017 Victaulic Company.All rights reserved. 1 �Ctiit.11rC" victaulic.com 1.0 PRODUCT DESCRIPTION (Continued) Other Fitting Styles AGS-Advanced Groove System from 14—60"/350—1500 mm Ductile Iron for AWWA size pipe Publication 20.05 Publication 23.05 Stainless Steel Publication 17.16 XL fittings for abrasive services Publication 07.07 Galvanized Publication 07.01 for Original Groove Fittings Publication 20.05 for AGS Fittings Aluminum Publication 21.03 Extra Heavy EndSeal"ES" Publication 07.03 Shouldered Ends Publication 07.06 41111 Copper Publication 22.04 Plain End Publication 14.04 1.1001 . • 07.01 1449 Rev AD Updated 02/2017 ®2017 Victaulic Company.All rights reserved. victauliic.com 2 victaulic.com • •2.0 CERTIFICATION/LISTINGS .0. ® LPCB vas 4100 NOTES • When supplied as"hot dip galvanized"the following fittings are UL Classified in accordance with ANSI/NSF 61 and for use on cold+86"F/+30"C potable water service and ANSI/NSF 372:No.10 90"Elbow,No.11 45"Elbow,No.12 22 1"Elbow,No.13 11 r/a"Elbow,No.100 90"Long Radius Elbow,No.110 45"Long Radius Elbow,No.20 Tee,No.25 Tee with Grooved Branch,No.30 45"Lateral,No.60 Cap,No.50 Concentric Reducers,No.51 Eccentric Reducers. • The following Victaulic fittings are VdS approved:No.10 90"Elbow,No.11 45"Elbow,No.20 Tee and No.60 Cap. • The following Victaulic fittings are LPCB approved:No.10 90"Elbow,No.11 45"Elbow,No.12 22 1 Elbow,No.13 11 Y"Elbow,No.30 45"Lateral,No.30-R Reducing Lateral,No.100 Long Radius Elbow,No.110 Long Radius Elbow,No.20 Tee,No.35 Cross,No.60 Cap,No.25 Reducing Tee,No.33 True Wye, No.50 Concentric Reducer,No.51 Eccentric Reducer and No.29M Tee with Threaded Branch. • The following Victaulic fittings are FM approved:No.10 90"Elbow,No.11 45"Elbow,No.12 22 1 Elbow,No.13 11 1/4"Elbow,No.30 45"Lateral,No.100 Long Radius Elbow,No.20 Tee,No.35 Cross,No.60 Cap,No.25 Reducing Tee and No.50 Concentric Reducer. 3.0 SPECIFICATIONS - MATERIAL Fitting: (specify choice) ❑ Standard: Ductile iron conforming to ASTM A-536, Grade 65-45-12. ❑ Optional: Segmentally welded steel as shown under nipples Nipples: (specify choice) ❑ 3/4-4720- 100 mm: Carbon steel, Schedule 40, conforming to ASTM A-53, Type F ❑ 5-67125- 150 mm: Carbon steel, Schedule 40, conforming to ASTM A-53, Type E or S, Gr. B ❑ 8- 127200-300 mm: Carbon steel, Schedule 30 or 40, conforming to ASTM A-53, Type E or S, Gr. B Flanged Adapter Nipples: (specify choice) ❑ Class 125 Flange: Cast iron conforming to ANSI B-16.1 ❑ Class 150 Flange: Carbon steel conforming to ANSI B-16.5, raised or flat face ❑ Class 300 Flange: Carbon steel conforming to ANSI B-16.5, raised or flat face Fitting Coating: (specify choice) ❑ Standard: Orange enamel ❑ Optional: Hot dip galvanized and others. Some fittings supplied electroplated as standard -see product specifications Flanged Adapter Nipple Coating: (specify choice) ❑ Standard: None(Unfinished) ❑ Optional: Orange enamel, hot dip galvanized and others • Nesoli 07.01 1449 Rev AD Updated 02/2017 0 2017 Victaulic Company.All rights reserved. victaulic.com 3 ✓ctauLc victaulic.com • • 4.0 DIMENSIONS Elbows No. 10 90° Elbow No. 11 45° Elbow 0 i u--c to E-.I No. 12221/z° Elbow EtoE No. 13 111/4° Elbow r-cLOEi .11 cro No. 100 90° Long _ 4 c co E'` #111 'Alt Radius Elbow ,_ C ctoE -L No. 110 45° Long to lc T-iik C to E Radius Elbow }-=rem, Standard and GSNK No. 100 No. 110 No. 10 No. 11 No. 12 No. 13 90°Long Radius 45°Long Radius Size 90"Elbow 45"Elbow 221 Elbow 11'/a Elbow Elbow Elbow Actual Approx. Approx. Approx. Approx. Approx. Approx. Outside Wgt. Wgt. Wgt. Wgt. Wgt. Wgt. Nominal Diameter C to E (Each) C to E (Each) C to E (Each) C to E (Each) C to E (Each) C to E (Each) inches inches inches lb inches lb inches lb inches lb inches lb inches lb DN mm mm kg mm kg mm kg mm kg mm kg mm kg 3/a 1.050` 2.25 0.5 1.50 0.5 1.63(sw) 1.38(sw) - 2.50(sw) 0.4 1.88(sw) 0.3 0N20 26.9 57 0.2 38 0.2 41 35 64 0.2 48 0.1 1 1.315 2.25 0.6 1.75 0.6 3.251 0.6 1.38(sw) 0.3 2.88(sw) 0.6 2.25(sw) 0.5 DN25 33.7 57 0.3 44 0.3 83 0.3 _ 35 0.1 73 0.3 57 0.2 'A 1 1.660 2.75 1.0 1.75 0.9 1.75- 0.8 1.38(sw) 0.5 3.25(sw) 1.1 2.38(sw) 0.7 DN32 42.4 70 0.5 44 0.4 44 0.4 35 0.2 83 0.5 60 0.3 1 1/2 1.900 2.75 1.2 1.75 0.9 1.75 0.8 1.38(sw) 0.5 3.63(sw) 2.2 2.50(sw) 1.3 DN40 48.3 70 0.5 44 0.4 44 0.4 35 0.2 92 1.0 64 0.6 2 2.375 3.25 1.8 2.00 1.3 1.88 1.2 138 1.0, 4.38 2.5 2.75 1.8 DN50 60.3 83 0.8 51 0.6 48 0.5 35 0.5 111 "1.1 70 0.8 21/2 2.875 3.75 3.2 2.25 2.2 4.001 2.3 1.50 1.1 5.13 3.4 3.00 2.8 73.0 95 1.5 57 1.0 102 1.0 38 0.5 130 1.5 76 1.3 DN65 3.000" 3.75 3.7 2.25 3.4 2.25: 1.50 76.1 95 1.7 57 1.5 57 _ 38 - - - 3 3.500 4.25 4.5 2.50 3.1 4.50' 3.1 1.50 2.1 5.88 6.0 3.38 4.9 DN80 88.9 108 2.0 64 1.4 114 1.4 38 1.0 149 2.7 86 2.2 3 V2 4.000 4.50 5.6 2.75 4.3 2.50(sw) 4.0 1.75(sw) 2.7 DN90 101.6 114 2.5 70 2.0 64 1.8 44 1.2 - - - 4 4.500 5.00 7.1 3.00 5.6 2.88 5.6 1.75 3.6 7.50 12.3 4.00 7.3 DN100 114.3 127 3.2 76 2.5 73 2.5 44 1.6 191 5.6 102 3.3 4.250 5.00 11.0 3.00 5.6 108.0 127 5.0 76 2.5 - - - - - - - 4'/2 5.000 5.25(sw) 10.0 3.13(sw) 6.0 3.50(sw) 6.6 1.88(sw) 4.2 - - DN120 127.0 133 _4.5 79 2.7 89 3.0 48 1.9 - 5 5.563 5.50 11.7 3.25 8.3 2.88(sw) 7.8 2.00(sw) 5.0 9.25(sw) 18.0 4.88(sw) 14.8 141.3 _ 140 5.3 83 3.8 73 3.5 51 2.2 235 8.2 124 6.7 5.250 5.50 11.7 3.25 8.3 _ _ _ 133.0 140 5.3 83 3.8 - - - 5.500 5.50 11.7 3.25 8.3 2.88 2.00 ON125 _ - - 139.7 140 5.3 83 3.8 73` - 51 - - 6 6.625 6.50 17.2 3.50 10.8 6.25' 12.2 2.00 7.0 10.75 30.4 5.50 17.4 DN150 168.3 165 7.8 89 4.9 159 5.5 51 3.2 273 13.8 140 7.9 6,250 6.50 18.6 3.50 10.8 159.0 165 8.4 89 4.9 - - - - - - - 6.500 6.50 15.5 3.50 9.8 3.13 11.4 2.00 7.4 10.75(sw) 29.0 5.50(sw) 19.0 165.1 165 7.0 89 4.4 79 5.2 51 3.4 273 13.2 140 8.6 ' Gooseneck design,end-to-end dimension fittings in this size,contact your nearest Victaulic sales representative. 2 For 147350 mm and larger roll grooved systems,Victaulic offers the Advanced Groove System(AGS).For pricing and availability of cut groove fittings in this size,contact your nearest Victaulic sales representative. 3 Chinese standard sizes (s)=Carbon Steel Direct Roll Groove(OGS) (sw)=Carbon Steel Segmentally Welded NOTE • All fittings are ductile iron unless otherwise noted with an(sw)or(s). 'es" • • 07.01 1449 Rev AD Updated 02/2017 0 2017 Victaulic Company.All rights reserved. victaulic.com 4 ✓ctaulic omvictaulic.c • • 4.0 DIMENSIONS (Continued) Elbows No. 10 90° Elbow No. 11 45° Elbow 0 i c toE-1 No. 12 221/2 Elbow E to E No. 13 111/4° Elbow ct°E ! II C to E till lif No. 100 90° Long _ I ctoE Radius Elbow '_ CtoE -� No. 110 45° Long toy�� c to En Radius Elbow =owe■ Standard and GSNK No. 100 No.110 No. 10 No. 11 No. 12 No. 13 90°Long Radius 45°Long Radius Size 90"Elbow 45"Elbow 221/2°Elbow 112/a Elbow Elbow Elbow Actual Approx. Approx. Approx. Approx. Approx. Approx. Outside Wgt. Wgt. Wgt. Wgt. Wgt. Wgt. Nominal Diameter C to E (Each) C to E (Each) C to E Each C to E (Each) C to E (Each) C to E (Each) inches inches inches lb inches lb inches lb inches lb inches lb inches lb DN mm mm kg mm kg mm kg mm kg mm kg mm kg 8 8.625 7.75 29.9 4.25, 20.4 7.751 20.0 2.00 10.1 14.25 66.0 7.25 36.0 DN200 219.1 197 13.6 108 9.3 197 9.1 51 4.6 362 30.0 184 16.3 10 10.750 9.00 63.3 4.75 37.5 4.38(sw) 30.0 2.13 11.8 15.00 107.0 6.25 57.0 DN250 273.0 229 28.7 121 17.0 111 13.6 54 _ 5.3 381 48.5 159 25.9 12 12.750 10.00 74.0 5.25 66.7 4.88(sw) 40.0 2.25 29.3 18.00 156.0 7.50 90.0 DN300 323.9 254 33.6 133 30.3 124 18.1 57 13.3 457 70.8 191 40.8 142 14.000 14.00 136.0 5.75 65.0 5.00(sw) 46.0 3.50(sw) 32.0 21.00(s) 164.0 8.75 82.0 DN350 355.6 356 61.7 146 29.5 1 127 20.9 89 14.5 533 74.4 222 37.2 14.843 14.84 149.3 6.13 82.0 377.0 377 67.7 156 37.2 - - - - - 162 16.000 16.00 171.0 6.63 88.0 5.00(sw) 58.0 4.00(sw) 42.0 24.00(s) 210.0 10.00(s) 100.0 DN400 406.5 406 77.6 168 39.3 127 26.3 102 19.1 610 95.3 254 45.4 16.773 16.75 198.6' 7.00 101.3 426.0` 425 90.1 178 45.9, 182 18.000 18.00 228.0 7.50 108.0 5.50(sw) 65.0 4.50(sw) 53.2 27.00(s) 273.0 11.25(s) 135.0 DN450 457.2 457 103.4 190 50.0 140 29.5 144 24.1 686 123.8 286 61.2 18.898 18.88 291.0 7.83 141.7 480.0 480 132.0 200 64.3 202 20.000 20.00 298.0 8.25 138.0 6.00(sw), 78.6 5.00(sw) 65.0 30.00(s) 343.0 12.50(s) 174.0 DN500 508.0 508 135.2 210 62.6 152 ' 36.0 127 29.5 762 155.6 318 78.9 20.866 20.88 355.0 8.63 179.0 530.0 530 161.0 219 81.2 - 242 24.000 24.00 438.0 10.00 221.0 7.00(sw) 140.0 6.00(sw) 60.0 36.00(s) 516.0 15.00(s) 251.0 DN600 609.6 610 198.7 254 100.2 178 63.5 152 27.2 914 234.1 381 113.9 24.803 24.80 545.0 10.25 255.2 630.0 630 247.2 261 115.7 - - - - For AGS fitting information,see publication 20.05 14-60 350-1500 AGS" v 1 Gooseneck design,end-to-end dimension fittings in this size,contact your nearest Victaulic sales representative. 2 For 14'/350 mm and larger roll grooved systems,Victaulic offers the Advanced Groove System(AGS).For pricing and availability of cut groove fittings in this size,contact your nearest Victaulic sales representative. (s)=Carbon Steel Direct Roll Groove(OGS) (sw)=Carbon Steel Segmentally Welded NOTE • All fittings are ductile iron unless otherwise noted with an(sw)or(s). • `yam 07.01 1449 Rev AD Updated 02/2017 ®2017 Victaulic Company.All rights reserved. victaulic.com 5 ✓ctaulic' victaulic.com 4.1 DIMENSIONS Reducing Base Support Elbow No. R-10G Grv. x Grv. No. R-10F Grv. x Flange rct°E m- rctoE1JO 1 L-- ; I Ili -.! 1._. B Dia. B Dia. No.R-10 Size Reducing Base Support Elbow Approx.Weight Each Nominal Size C to E H B Diameter Grv.x Grv. Grv.x Flange inches inches inches inches lb lb DN mm mm mm kg kg 6 4 9.00 1.25 1.50 19.0 33.0 DN150 x DN100 229 32 38 8.6 15.0 5 9.00 1.50 1.50 23.0 38.0 DN12S 229 38 38 10.4 17.2 8 6 10.50 2.13 1.50 33.0 52.0 DN200 x DN150 267 24 38 15.0 23.6 - 10 8 12.00 2.40 1.50 61.0 88.0 DN250 x DN200 305 61 38 27.7 39.9 4.2 DIMENSIONS Adapter Elbow No. 18 90"Adapter Elbow No. 19 45"Adapter Elbow ,r' GE 1 I C to'< GE r\ C to Cjfi TIE C o ill rw, ' L TE No. 18 No. 19 Size 90"Adapter Elbow4 45"Adapter Elbow" Actual Approximate Approx. Nominal Outside Weight Weight Size Diameter C to GE C to TE (Each) C to GE C to TE (Each) inches inches inches inches lb inches inches lb DN mm mm mm kg mm mm kg '/a 1.050 2.25 2.25 0.5 1.50 1.50 0.5 DN20 26.9 57 _ 57 0.2 � 38 38____-____ 0.2 ___ 1 1.315 2.25 2.25 0.5 - - - DN25 33.7 57 57 0.2 11 1.660 2.75 2.75 0.9 _ _ _DN32 42.4 70 70 0.4 1'/2 1.900 2.75 2.75 1.1 1.75 1.75 0.9 DN40 48.3 70 70 0.5 44 44 0.4 2 2.375 3.25 4.25 2.5` -DN50 60.3 83 108 1.1 - 21/2 2.875 3.75 3.75 3.0 2.25 2.25 2.3 73.0 95 95 1.4 57 57 1.0 3 3.500 4.25 6.00 5.8 2.50 4.25 5.0 DN80 88.9 108 _ 152 2.6- 64 108 2.3 3'/2 4.000 4.50 6.25 8.0 5.25 5.25 8.8 DN90 101.6 114 159 3.6 133 133 4.0 6 6.625 6.50 6.50 17.6 3.50 3.50 12.7 DN150 1 168.3 165 165 8.0 89 89 5.8 4 Available with British Standard Pipe Threads,specify"BSP"clearly on order. 'ci_• 07.01 1449 Rev AD Updated 02/2017 ©2017 Victaulic Company.All rights reserved. victaulic.com 6 ✓ctaulac victaulic.com 4.3 DIMENSIONS Tees, Crosses and True Wyes CtoE r-CtoEl �� TO(E Cto Illif "--GE1 ilipil to iiii4‘SE �'1 ii somi to C to TE No.20 No.35 No.33 No.29M Size Tee Cross(sw) True Wye(sw) Tee with Threaded Branch Actual Approx. Approx. Approx. Approx. Outside Weight Weight Weight Weight Nominal Dimeter C to E (Each) C to E (Each) C to LE C to SE (Each) C to GE C to TE (Each) inches inches inches lb inches lb inches inches lb inches inches lb DN mm mm kg mm kg mm mm kg mm mm kg 3/4 1.050 2.25 0.6 2.25 0.9 2.25 2.00 0.7 2.25 2.25(sw) 0.6. DN20 26.9 57 0.3 57 0.4 57 51 0.3 57 57 0.3 1 1.315 2.25 1.0 2.25 1.3 2.25 2.25 1.1 2.25 2.25 1.0 DN25 33.7 57 0.5 57 0.6 57 57 0.5 57 57 0.5 114 1.660 2.75 1.5 2.75 2.1 2.75 2.50 1.5 2.75 2.75 1.5 DN32 42.4 70 0.7 70 1.0 70 64 j 0.7 70 _ 70 0.7 1Y� 1.900 2.75 2.0 2.75 2.5 2.75 2.75 1.8 2.75 2.75 2.0 DN40 48.3 70 0.9 70 1.1 70 70 0.8 70 70 0.9 2 2.375 3.25 3.0 3.25 3.8 3.25 2.75 2.5 3.25 4.25 3.0 DN50 _ 60.3 - 83 1.4 ' 83 1.7 83 70 1.1 83 108 1.4 21/2 2.875 3.75 4.3 3.75 6.1 3.75 3.00 4.3 3.75 3.75 4.3 73.0 95 2.0 95 2.8 95 76 2.0 95 95 2.0 DN65 3.000 3.75 5.2 _ - 3.75 3.75(sw) 5.2 - 76.1 95 2.4 - - 95 95 2.4 3 3.500 4.25 6.8 4.25 10.5 4.25 3.25 6.1 4.25 6.00 6.8 DN80 88.9 108 3.0 108 4.8 108 83 2.8 108 152 3.1 31/2 4.000 4.50(sw) 7.9 4.50 11.5 4.50 3.50 9.6 4.50 4.50(sw) 7.9 DN90 101.6 114 3.6 114 5.2 114 89 4.4 114 114 3.6 4.250 5.00 15.5 5.00 5.00(sw) 15.5 108.0 127 7.0 - - - - - 127 127 7.0 4 4.500 5.00 11.9 5.00 15.8 5.00 3.75 9.8' 5.00 7.25 11.9 DN100 114.3 127 5.4 127 7.2 127 95 4.4 127 184 5.4 41/2 5.000 5.25(sw) 15.0 5.25 18.5 - _ _ 5.25 5.25(sw) 15.0 DN120 127.0 133 6.8 133 8.4 133 133 6.8 5.250 5.50 17.8 5.50 5.50(sw) 17.8 133.0 140 8.1 - - - - - 140 140 8.1 DN125 5.500 5.50 17.8 - - _ - _ 5.50 5.50(sw) 17.8 _ 139.7 140 8.1 140 140 8.1 5 r 5.563 5.50 17.8 5.50 20.0 5.50 4.00 15.0 5.50 5.50(sw) 17.8 141.3 - 140 8.1 140 ' 9.1 140, 102 6.8 140 140 8.1 6.250 6.50 27.1 6.50 6.50(sw) 27.1 159.0 165 12.3 165 165 12.3 6.500 6.50 22.0 6.50 28.0 6.50' 6.50(sw) 22.0 165.1 165 10.0 165 12.7 - - - 165 165 10.0 6 6.625 6.50 25.7 6.50 28.0 6.50 4.50 22.3 6.50 6.50(sw) 25.7 DN150 168.3 165 11.7 165 12.7 - 165 114 10.1 165 165 11.7 8 8.625; 7.75 47.6 7.75 48.0 7.75 6.00 36.0 7.75 7.75 47.6 DN200 219.1 197 21.6 197 21.8 197 _ 152 16.3 197 197 21.6 10 10.750 9.00 99.0 9.00 121.5 9.00 6.50 69.9 9.00 9.00 99.0 DN250 273.0 229 44.9 229 55.1 229 155 31.7 229 229 44.9 12 12.750 10.00 133.0 10.00 110.0 10.00 7.00 80.0 10.00 10.00 133.0 DN300 323.9 254 60.3 254 49.9 254 178 36.3 254 254 60.3 5 For 14"/350 mm and larger roll grooved systems,Victaulic offers the Advanced Groove System(AGS).For pricing and availability of cut groove fittings in this size,contact your nearest Victaulic sales representative. 6 Chinese standard sizes (s)=Carbon Steel Direct Roll Groove(OGS) (sw)=Carbon Steel Segmentally Welded NOTE • All fittings are ductile iron unless otherwise noted with an(sw)or(s). . + 07.01 1449 Rev AD Updated 02/2017 ©2017 Victaulic Company.All rights reserved. victaulic.com 7 ✓ctaulicr victaulic.com 4.3 DIMENSIONS (Continued) Tees, Crosses and True Wyes -CtoE,- �CtoE-� MINIM CtoLE �Cto GE-1 II," to1111 o TE- II �� i Cto Ct ismi _A No.20 No.35 No.33 No.29M Size Tee - Cross(sw) True Wye(sw) Tee with Threaded Branch Actual Approx. Approx. Approx. Approx. Outside Weight Weight Weight Weight Nominal Dimeter C to E (Each) C to E (Each) C to LE C to SE (Each) C to GE C to TE (Each) inches inches inches lb inches lb inches inches lb inches inches lb DN mm mm kg mm kg mm mm kg mm mm kg 145 14.000 11.00(sw) 145.0 11.00 198.0 11.00 7.50 134.2 DN350 355.6 279 65.8 279 89.8 279 191 60.8 - - 377.0 11.50 145.0 292 65.8 165 16.000 12.00(sw) 186.0 12.00 250.0 12.00 8.00 167.0 DN400 406.4 305 84.4 305 113.4 305 203 75.7 _ 13.00 186.0 426.0 300 84.4 - - - - - - - - 185 18.000 15.50(sw) 260.0 15.50 - 350.0 15.50 8.50 234.0 DN450 457.0 394 117.9 394 158.8 394 216 1061 - 480.0 14.63 256.0 - - 372 116.1 - 205 20.000`' 17.25(sw) 336.0 17.25 452.0 17.25 9.00 281.0 DN500 508.0 438 152.4 438 205.0 438 229 127.5 530.0 15.38(sw) 339.0 _ 391 153.8 245 24.000 20.00(sw) 592.0 20.00 795.0 20.00 10.00 523.0 DN600 610.0 508 268.5 508 360.6 508 254 237.2 _ 630.0 17.38(sw) 473.0 441 214.5 14-60 For AGS fitting information,see publication 20.05 DN350- A GS- DN1500 r 5 For 147350 mm and larger roll grooved systems,Victaulic offers the Advanced Groove System(AGS).For pricing and availability of cut groove fittings in this size,contact your nearest Victaulic sales representative. (s)=Carbon Steel Direct Roll Groove(OGS) (sw)=Carbon Steel Segmentally Welded NOTE • All fittings are ductile iron unless otherwise noted with an(sw)or(s). 4+' • • 07.01 1449 Rev AD Updated 02/2017 ®2017 Victaulic Company.All rights reserved. victaulic.com 8 ✓ctaulic victaulic.com • • 4.4 DIMENSIONS Reducing Tee t«CtoE1 CtoE- No. 25 Grooved Branch II No. 29T Threaded Branch 1111 rc IIII c to to 'f«CtoE CtoE E E 11,1: II1i C No.25 No.29T to f E No.Alli ; No.25 w/Thd. Size Std. Branch_ Approx. No.25 No.29T Weight No.29T Nominal Size C to E C to E (Each) No.25 w/Thd. inches inches inches lb Size SW. Branch Approx. DN mm mm kg Weight 4 4 3/4 5.00(sw) 5.00(sw) 8.0 Nominal Size C to E C to E (Each) DN100 x DN100 X DN20 127 127 3.6 inches inches inches lb 1 5.00 5.00 7.8 DN mm mm kg DN25 127 127 3.5 1 1 3/4 2.25(sw) 2.25(sw) 1.0 1'/4 5.00(sw) 5.00(sw) 9.6 DN25 X DN225 x DN20 57 57 0.5 DN32 127 127 4.4 1 1/4 1 3/4 1 2.75(sw) 2.75(sw) 1.3 1 1/2 5.00 5.00 10.2 DN32 X DN32 x DN25 70 70 0.6 DN40 127 127 4.6 1 Y 1'/a 3/4 2.75(sw) 2.75(sw) 1.5 2 5.00 5.00 11.2 DN40 x DN40 x DN20 70 70 0.7 DN50 127 127 5.1 1 2.75(sw) 2.75(sw) 1.5 21/ 5.00 5.00 11.4 DN25 70 70 0.7 127 127 5.2 1'/4 2.75(sw) 2.75(sw) 1.7 3 5.00' 5.00 11.6 DN32 70 70 0.8 DN80 127 127 5.3 2 2 3/4 3.25 3.25 2.5 5 5 1 5.50(sw) 5.50(sw) 14.0 DN50 x DN50 x DN20 83 83 1.1 DN125 x DN125 X DN25 140 140 6.4 1 3.25 3.25 2.7 1% 5.50(sw) 5.50(sw) 14.3 DN25 83 83 1.2 DN40 140 140 6.5 1 Y 3.25(sw) 3.25(sw) 1.8 2 5.50(sw) 5.50(sw) 14.5 ....l DN32 83 83 0.8 DN50 140 140 6.6 1'h 3.25 3.25(sw) 3.0 2' 5.50 5.50(sw) 15.2 DN40 83 83_ 1.4 140 140 6.9 2 Y2 X 21 X 3/4 3.75(sw) 3.75(sw) 3.9- 3 5.50 5.50(sw) 16.6 DN20 95 95 1.8 DN80 140 140 7.5 1 3.75 3.75(sw) 3.8 4 5.50 5.50(sw) 16.7 DN25 95 95 1.7 DN100 140 140 7.6 _1'/a 3.75 3.75 4.2 6 6 1 6.50(sw) 6.50(sw) 23.0 X X DN32 95 95 1.7 DN150 DN150 DN25 165 165 10.4 1 1/2 3.75 3.75 3.9 1''V2 6.50(sw) 6.50(sw) 24.0 DN40 95 95 1.8 DN40 165 165 10.9 2 3.75 3.75(sw) 4.5 2 6.50 6.50 21.6 DN50 95 95 2.0 DNSO 165 165 9.8 3 3 3/4 4.25(sw) 4.25(sw) 5.7 21/2 6.50 6.50 21.4 DN80 x DN80 x DN20 108 108 2.6 165 165 11.7 1 4.25 4.25 6.1 3 6.50 6.50 26.5 DN25 108 108 2.8 DN80 165 165 12.0 1% 4.25 4.25 8.0 4 6.50 6.50 25.0 DN32 108 108 3.6 DN100 165 165 11.3 1'Va 4.25 4.25(sw) 6.5 5 6.50 6.50 23.2 DN40 108 108 2.9 165 165 10.5 2 4.25 4.25(sw) 6.2 6 Y 6 Y 3 6.50 6.50(sw) 24.0 DN50 108 108 2.8 DN165.1 x DN165.1 x DN80 165 165 10.9 2'/2 4.25 4.25(sw) 6.4 4 6.50 6.50(sw) 25.0 108 108 2.9 DN100 165 165 11.3 7 For 147350 mm and larger roll grooved systems,Victaulic offers the ' For 147350 mm and larger roll grooved systems,Victaulic offers the Advanced Groove System(AGS).For pricing and availability of cut groove Advanced Groove System(AGS).For pricing and availability of cut groove fittings in this size,contact your nearest Victaulic sales representative. fittings in this size,contact your nearest Victaulic sales representative. 8 Cast fitting available.Contact Victaulic for details. 8 Cast fitting available.Contact Victaulic for details. (s)=Carbon Steel Direct Roll Groove(OGS) (s)=Carbon Steel Direct Roll Groove(OGS) (sw)=Carbon Steel Segmentally Welded (sw)=Carbon Steel Segmentally Welded • • " ' 07.01 1449 Rev AD Updated 02/2017 0 2017 Victaulic Company.All rights reserved. victaulic.com 9 ✓ctaulIc' victaulic.com • •4.4 DIMENSIONS (Continued) Reducing Tee No. 25 Grooved Branch �ctoE1 i ctoE- No. 29T Threaded Branch II,I: o II I�_to «CtoEi I CtoE. =�E E I 1 _ TCc II II c No.25 No.29T m E No.29T t 4 4 No.25 w/Thd. Size Std. Branch Approx. No.25 No.29T Weight No.29T Nominal Size C to E C to E (Each) No.25 w/Thd. inches inches inches lb Size Std. Branch Approx. DN mm mm kg Weight 12 12 1 10.00(sw) 10.00(sw) 77.0 Nominal Size C to E C to E (Each) DN300 x DN300 x DN25 254 254 34,9 inches inches inches lb 2 10.00(sw) 10.00(sw) 80.0 DN mm mm kg DN50 254 254 36.3 8 8 1 1/2 7.75(sw) 7.75(sw) 33.0 2 Y2 10.00(sw) 10.00(sw) 78,0 DN200 x DN200 x DN40 197 197 15.0 254 254 35.4 2 7.75(sw) 7.75(sw) 33.5 3 10.00(sw) 10.00(sw) 82.0 DN50 197 197 15.2 DN80 254 254 37.2 2 Y2 7.75(sw) 7.75(sw) 39.0 4 10.00(sw) 10.00(sw) 80.0 197 197 17.7 DN100 254 254 36.3 3 7.75(sw) 17.75(sw) 33.6 5 10.00(sw) 10.00(sw) 75.0 DN80 197 197 15.2 254 254 34.0 4 7.75 7.75 41.8 6 10.00(sw) 10.00(sw) 75.0 DN100 197 197 19.0 DN150 254 254 34.0 5 r7.75(sw) 7.75(sw) 34.0 8 10.00(sw) 10.00(sw) 80.0 197 197 15.4 DN200 254 254, 36.3 6 7.75 7.75 42.3 10 10.00(sw) 10.00(sw) 84.0 DN150 197 197 19.2 DN250 254 254 38.1 7.75(sw) 7.75(sw) 48.0 148 14 4 11.00(sw) 11.00(sw) 102.0 40446* 165.1 197 197 218 DN350 x DN350 x DN100 279 279 46.3 10 10 1 Y2 9.00 9.00 62.0 6 11.00(sw) 11.00(sw) 108.2 DN250 x DN250 x DN40 229 229 28.1 DN150 279 279 49.1 2 9.00(sw) 9.00(sw) 62.0 8 11.00 11.00 112.0 DNSO 229 229 28.1 DN200 279 279 50.8 2 1/2 9.00(sw) 9.00(sw) 62.4 10 11.00 11.00 120.0 229 229 28.3 DN250 279 279 54.4 3 9.00(sw) 9.00(sw) 60.0 12 11.00 11.00 129.1 DN80 229 229 27.2 _ DN300 279 279 58.6 4 9.00(sw) 9.00(sw) 61.0 168 16 4 12.00 12.00 130.0 DN100 229 229 27.7 DN400 x DN400 x DN100 305 305 59.0 5 9.00(sw) 9.00(sw) 52.0 6 12.00(sw) 12.00(sw) 133.5 229 229 23.6 DN150 305 i 305 60.6 6 9.00(sw) 9.00(sw) 59.0 8 12.00 12.00 145.0 DN150 229 229 26.8 DN200 305 305 65.8 8 9.00(sw) 9.00(sw) 64.7 10 12.00 12.00 149.5 DN200 229 229 29.3 DN250 305, 305 67.8 7 For 147350 mm and larger roll grooved systems,Victaulic offers the 12 12.00 12.00 154.0 Advanced Groove System(AGS).For pricing and availability of cut groove DN300 305 305 69.9 fittings in this size,contact your nearest Victaulic sales representative. 14 12.00(sw) 167.0 8 Cast fitting available.Contact Victaulic for details. DN350 305 75.8 7 For 147350 mm and larger roll grooved systems,Victaulic offers the (s)=Carbon Steel Direct Roll Groove(OGS) Advanced Groove System(AGS).For pricing and availability of cut groove (sw)=Carbon Steel Segmentally Welded fittings in this size,contact your nearest Victaulic sales representative. 8 Cast fitting available.Contact Victaulic for details. (s)=Carbon Steel Direct Roll Groove(OGS) (sw)=Carbon Steel Segmentally Welded • • 07.01 1449 Rev AD Updated 02/2017 ©2017 Victaulic Company.All rights reserved. victaulic.com 10 ✓ctaulic- victaulic.com •4.4 DIMENSIONS (Continued) Reducing Tee No. 25 Grooved Branch E.-ctoE-1 i ctoE 4411/ No. 29T Threaded Branch 11,11 Tc II II c to to hCtoE .-CtoE E E { 11,1: c 11,11 C No.25 29T to No.29T - f No.25 w/Thd. Size Std. Branch Approx. No.25 No.29T Weight No.29T Nominal Size C to E C to E (Each) No.25 w/Thd. inches inches inches lb Size Std. Branch Approx. DN mm mm kg Weight 24' x 24 x 8 20.00 20.00 340.0 Nominal Size C to E C to E (Each) DN600 DN600 DN200 508 508 154.2 inches inches inches lb 10 20.00 20.00 343.9 DN mm mm kg DN250 508 508 156.0 18' 18 4 15.50(sw) 15.50(sw) 194.0 12 20,00 20.00 352.8 DN450 x DN450 x DN100 394 394 88.0 DN300 508 508 160.0 6 15.50(sw) 15.50(sw) 200.0 149 20.00 - 360.0 DN15.0 - 394 394 90.7 DN350 508 163.3 8 15.50(sw) 15.50(sw) 202.0 16 20.00 _ 378.0 DN200 394 394 91.6 DN400 508 171.5 10 15.50 15.50 212.0 189 20.00 _ 380.0 DN250 394 394 96.2 DN450 508 172.4__ 12 15.50 15.50 222.6 20 20.00 373.0 DN300 394 394 101.0 DN500 508 169.2 14 15.50 - 230.1 For AGS fitting information,see DN350 394 104.4 DN14-60 publication 20.05 16 15.50 247.6 DN350-1500 AGO DN400 394 112.3 20' x 20 x 6 17.25 17.25 240.0 7 For 14'/350 mm and larger roll grooved systems,Victaulic offers the DN500 DN500 DN 150 438 438 108.9 Advanced Groove System(AGS).For pricing and availability of cut groove 8 17.25 17.25 244.0 fittings in this size,contact your nearest Victaulic sales representative. DN200 438 438 110.7 8 Cast fitting available.Contact Victaulic for details. 10 17.25 17.25 256.0 (s)=Carbon Steel Direct Roll Groove(OGS) DN250 438 438 116.1 12 17.25 17.25 264.0 (sw)=Carbon Steel Segmentally Welded DN300 438 438 119.8 NOTES 14 17.25 _ 275.0 • No.29T Threaded Outlet Reducing Tees are supplied NPT and are DN350 438 124.7 available with British Standard threads.For British Standard specify 16 17.25 _ 288.6 "BSP"clearly on order. DN400 438 130.9 • All fittings are ductile iron unless otherwise noted with an(sw)or(s). 18 17.25 _ 297.0 DN450 438 134.7 7 For 147350 mm and larger roll grooved systems,Victaulic offers the Advanced Groove System(AGS).For pricing and availability of cut groove fittings in this size,contact your nearest Victaulic sales representative. 8 Cast fitting available.Contact Victaulic for details. (s)=Carbon Steel Direct Roll Groove(OGS) (sw)=Carbon Steel Segmentally Welded • • 07.01 1449 Rev AD Updated 02/2017 ®2017 Victaulic Company.All rights reserved. victaulic.com 11 ✓ctaulic victaulic.com 4.5 DIMENSIONS • Bull Plug No. 61 E to E--I D No.61 No.61 Size Bull Plug(s) Actual Approx. Outside Weight Nominal Diameter E to E (Each) inches inches inches lb DN mm mm kg 2 2.375 4.00 2.5 DN50 60.3 102 1.1 21 2.875 5.00 3.0 73.0 127 1.4 3 3.500 6.00 4.5 DN80 _ 88.9 152 J 2.0 4 4.500 7.00 7.5 DN100 114.3 178 3.4 5 5.563 8.00 12.0 141.3 203 _ 5.4` 6 6.625 10.00 17.0 DN 150 168.5 254 7.7 (s)=Carbon Steel Direct Roll Groove(OGS) (sw)=Carbon Steel Segmentally Welded NOTES • Steel dish caps available through 24'/600 mm,contact Victaulic. • No.61 Bull Plugs should be used in vacuum service with Style 72 or 750 couplings • All fittings are ductile iron unless otherwise noted with an(sw)or(s). • • 07.01 1449 Rev AD Updated 02/2017 ©2017 Victaulic Company.All rights reserved. victaulic.com 12 jctaulic? victaulic.com • •4.6 DIMENSIONS 45"Lateral No. 30 Nook Ito to Li: 1i C toS /� Sto �� i_mum �� No.30 No.30 No.30 No.30 Size _ 45°Lateral Weight _ Size 45°Lateral Weight Actual Actual Outside Approx. Outside Approx. Nominal Diameter C to LE C to SE (Each) Nominal Diameter C to LE C to SE (Each) inches inches inches inches lb inches inches inches inches lb DN mm mm mm kg DN mm mm mm kg 3 1.050 4.50(sw) 2.00(sw) 1.0 6.500 14.00(sw) 4.50(sw) 43.6 _ DN20- 26.9 114 51 0.5 165.1 356 114 19.8 1 1.315 5.00(sw) 2.25(sw) 1.7 6 6.625 14.00(sw) 4.50(sw) 43.6 DN25 33.7 _ 127 57 0.8 DN150 168.3 356 114 49.8 1' 1.660 5.75 2.50 2.5(d) 8 8.625 18.00(sw) 6.00(sw) 72.0 DN32 42.4 146 64 1.1 _ DN200 219.1 457 152 32.7 11 1.900 6.25(sw) 2.75(sw) 3.5 10 10.750 20.50(sw) 6.50(sw) 105.0 DN40 48.3 159 70 1.6 DN250 273.0 521 165 47.6 2 2.375 7.00(sw) 2.75(sw) 5.0 12 12.750 23.00(sw) 7.00(sw) 165.0 DN50 60.3 178 70 2.3 DN300 323.9 584 178 74.8 21/2 2.875 7.75(sw) 3.00(sw) 9.0 149 14.000 26.50(sw) 7.50(sw) 276.0 73.0 _ 197 76 4.1 DN350 355.6 673 191 125.2 DN65 3.000 8.50(sw) 3.25(sw) 11.0 - 169 16.000 29.00(sw) 8.00(sw) 344.2 76.1 216 83 _ 5.0 DN400 406.4 737 203 156.1 - 3 3.500 8.50 3.25 11.7(d) 189 18.000 32.00(sw) 8.50(sw) 429.0 DN80 88.9 216 83 5.4 DN450 457.0 813 216 194.6 _ e+ 31/ 4.000 10.00(sw) 3.50(sw) 17.8 209 20.000 35.00(sw) 9.00(sw) 500.0 DN90 101.6 254 89 8.1 DN500 508.0 889 229 226.8 4 4.500 10.50 3.75 22.2(d) 249 24.000 40.00(sw) 10.00(sw) 715.0 DN100 114.3 267 95 10.1 DN600 610.0 1016 254 324.3 5 5.563 12.50(sw) 4.00(sw) 21.8 For AGS fitting information,see publication 20.05 141.3 318 102 9.9 DN14-60 9 For 147350 mm and larger roll grooved systems,Victaulic offers the DN350-1500 GS VI Advanced Groove System(AGS).For pricing and availability of cut groove fittings in this size,contact your nearest Victaulic sales representative. 9 For 14"/350 mm and larger roll grooved systems,Victaulic offers the (s)=Carbon Steel Direct Roll Groove(OGS) Advanced Groove System(AGS).For pricing and availability of cut groove fittings in this size,contact your nearest Victaulic sales representative. (sw)=Carbon Steel Segmentally Welded (s)=Carbon Steel Direct Roll Groove(OGS) (sw)=Carbon Steel Segmentally Welded NOTE • All fittings are ductile iron unless otherwise noted with an(sw)or(s). • • IOW 07.01 1449 Rev AD Updated 02/2017 t 2017 Victaulic Company.All rights reserved. victaulic.com 13 ✓ctaulic victaulic.com • 4.7 DIMENSIONS • 45"Reducing Lateral No. 30-R - 7 C1n I s LE ij> LE i /" Ii o, C C~ I// ow \ L` SE �/ S � el _ � No.30-R No.30-R No 30-R No 30-R I Size 45°Reducing Lateral Size 45°Reducing Lateral Approx. Approx. Weight Weight Nominal Size C to LE C to SE (Each) Nominal Size C to LE C to SE (Each) inches inches inches lb inches inches inches lb DN mm mm kg DN mm mm kg 3 3 2 8.50 3.25 9.8 1410 14 4 26.50 7.50 172.0 DN80 x DN80 x DN50 216 83 4.4 DN350 x DN350 x DN100 673 191 78.0 r 21/2 8.50 3.25 9.8 6 26.50 7.50 187.0 DN65 216 83 4.4 DN150 673 191 84.8 4 4 2 10.50 3.75 10.0 8 26.50 7.50 205.8 DN100 x DN100 x DN50 267 95 4.5 DN200 673 J 191 93.4 21/2 10.50 3.75 10.0 10 26.20. 7.50 235.0. DN65 267 95 4.5 DN250 673 191 106.6 3 10.50 3.75 18.3 12 26.50 7.50 250.0 DN80 267 95 8.3 DN300 673 i 191 113.4 5 x 5 x 2 12.50 4.00 24.0 1670 16 6 29.00 8.00 215.0 DN50 318 102 10.9 DN400 x DN400 x DN150 737 203 97.5 3 12.50 4.00 27.0 8 29.00 8.00 252.5 DN80 318 102 12.2 DN200 737 203 114.5 4 12.50 4.00 26.5 10 29.00 8.00 265.0 DN100 318 102 12.0 DN250 737 203 120.2 6 6 3 14.00 4.50 37.0 12 29.00 8.00 295.0 DN150 x DN150 x DN80 356 114 16.8 DN300 737 203 133.8 4 14.00 4.50 36.0 14 29.00 8.00 305.0 DN100 356 114 16.3 DN350 737 203 138.3 5 14.00 4.50 44.7 1810 18 6 32.00 8.50 274.0 356 114 20.3 DN450 x DN450 x DN150 813 216 124.3 8 8 4 18.00 6.00 62.0 8 32.00 8.50 275.0 DN200 x DN200 x DN100 457 152 28.1 DN200 813 216 124.7 5 18.00 6.00 75.5 12 32.00' 8.50 347.0 457 152 34.2 DN300 813 216 157.4 6 18.00 6.00 82.0 14 32.00 8.50 350.0 DN150 457 152 37.2 DN350 813 216 158.8 10 10 4 2050 6.50 104.8 16 32.00 8.50 362.0 DN250 x DN250 x DN100 521 165 47.5 _ DN400 813 216 164.2 5 20.50 6.50 99.0 2010 20 12 35.00 9.00 415.0 521 165 44.9 DN500 x DN500 x DN300 889 229 188.2 6 20.50 6.50 105.8 14 35.00 9.00 420.0 DN150 521 165 48.0 DN350 889 229 190.5 8 20.50 6.50 118.0 16 35.00 10.00 425.0 DN200 521 165 53.5 DN400 899 229 192.8 12 12 5 23.00 7.00 122.0 2410 24 16 40.00 10.00 425.0 DN300 x DN300 x 584 178 55.3 DN600 x DN600 x DN400 1016 254 192.8 6 23.00 7.00 137.0 20 40.00 10.00 570.0 DN150 584 178 62.1 DN600 1016 254 258.6 8 23.00 7.00 147.0 For AGS fitting information, DN200 584 178 66.7 14-60 see publication 20.05 10 23.00 7,00 167.0 DN350-DN1500 AGS" DN250 584 178 75.8 ..`•••/' 10 For 14"/350 mm and larger roll grooved systems,Victaulic offers the Advanced Groove System(AGS).For pricing and availability of cut groove fittings in this size,contact your nearest Victaulic sales representative. • • 07.01 1449 Rev AD Updated 02/2017 ®2017 Victaulic Company.All rights reserved. victaulic.com 14 ✓ctauihc' victaulic.com • • 4.8 DIMENSIONS 4.9 DIMENSIONS Tee Wye Adapter Nipple No. 32 No. 4012 Grv. x Thd. 44110 No. 42 Grv. x Bev. M No. 43 Grv. x Grv. T H 1. -1 r-EtoE1 1.-EtoE-1 E2 . - G 4_MAW. No.40 No.42 No.43 1.-E, No.40,42,43 No.32 Size Adapter Nipple(s) No.32 Approx. Size Tee Wye(sw) Actual Outside Weight ------------- Nominal Size Diameter E to E (Each) Approx. Weight inches inches inches inches Nominal Size G H Es E2 (Each) DN mm mm mm inches inches inches inches inches lb 3/4 1.050 3:00 0.3 DN mm mm mm mm kg __DN20 26.9 76 0.1 - 2 2 2 2.75 7.00 9.00 4.63 6.4 1 1.315 3.00 0.4 DN50 x DN50 x DN50 70 178 229 118 2.9 25 33.7 76 0.2 11/4 1.660 4.00 0.8 21/2 21/2 21/2 3.00 7.75 10.50 5.75 11.5 DN32 42.4, 102 0.4 x x 76 197 267 146 5.2 11/2 1.900 4.00 0.9 3 3 3 3.25 8.50 11.50 6.50 14.3 40 48.3 102 0.4 DN80 x DN80 x DN80 83 216 292 165 6.5 -2 2.375 4.00 1.2 3'/2 31/2 31/2 3.25 10.00 13.00 7.75 22.9 DN50 60.3 102 0.5 DN90 x DN90 x DN90 89 254 330 197 10.4 21/2 2.875 4.00 1.9 4 4 4 3.75 10.50 13.63 8.13 26.0 73.0 102 0.9 100 x DN100 x DN100 95 267 346 207 11.8 3 3.500 4.00 2.5 5 5 5 4.00 12.50 16.13 10.00 48.0 0N80 88.9 102 1.1 x x 102 318 410 254 21.8 3/2 4.000 4.00 2.1 6 6 6 4.50 14.00 18.25 11.50 60.5 DN90 101.6 I 102 0.9 DN150 x DN150 x DN150 114 356 464 292 27.4 4 4.500 6.00 5.5 8 8 8 6.00 18.00 23.25 15.25 127.1 DN100 114.3 152 2.5 DN200 x DN200 x DN200 152 457 591 387 57.7 5 5.563 6.00 7.4 10 10 10 6.50 20.50 27.25 18.00 190.0 141.3 152 3.4 DN250 x DN250 x DN250 165 521 692 457 86.2 6 6.625 6.00 9.5 12 12 12 7.00 23.00 31.00 20.50 240.0 DN150 168.3 152 4.3 DN300 x DN300 x DN300 178 584 787 521 108.9 8 8.625 6.00 14.2 DN200 219.1 152 6.4 (s)=Carbon Steel Direct Roll Groove(OGS) 10 10.750 8.00 27.0 (sw)=Carbon Steel Segmentally Welded DN250 273.0 203 12.2 12 12.750 8.00 33.0 DN300 323.9 203 15.0 11 Available with British Standard Pipe Threads,specify"BSP"clearly on order. (s)=Carbon Steel Direct Roll Groove(OGS) (sw)=Carbon Steel Segmentally Welded NOTES • All fittings are ductile iron unless otherwise noted with an(sw)or(s). • For pump package nipples with 11/2"/40 mm hole cut to receive Style 923 Vic-Let or Style 924 Vic-O-Well®request special No.40,42 or 43 nipples and specify No.40-H,42-H or 43-H on order.NOTE:4-12°/100-300mm diameter-8"/200mm minimum length required. • For roll grooved systems,Victaulic offers the Advanced Groove System (AGS).For pricing and availability of cut groove fittings in this size,contact your nearest Victaulic sales representativeWirt • • 07.01 1449 Rev AD Updated 02/2017 ©2017 Victaulic Company.All rights reserved. victaulic.com 15 ✓ctaul;c" victaulic.com 4.10 DIMENSIONS Cap ' ,,, No. 60 b br No.60 No.60 No.60 No.60 Size Cap Size Cap Actual Approx. Actual Approx. Outside Weight Outside Weight Nominal Diameter "T"Thickness (Each) Nominal Diameter "T"Thickness (Each) inches inches inches lb inches inches inches lb DN mm mm kg DN mm mm kg 1,4 1.050 0.88 0.2 6.250 1.00 6.8 DN20 26.9 22 0.1 159.0 25 3.1` 1 1.315 0.88 0.3 6.500 1.00 7.3 25 33.7 22 0.1 165.1 25 3.3 -- ----- ------ - 11 1.660 0.88 0.3 6 6.625 1.00 6.1 DN32 424 22 , 0.1 DN150 168.3 25 2.8 . 1/ 1.900 0.88 0.5 8 8.625 1.19 13.1 DN40 48.3 22 0.2 200 219.1 30 5.9 2 2.375 0.88 0.6 10 10.750 1.25 21.0 DN50 60.3 22 0.3 DN250 273.0 32 9.5 _ 21/2 2.875 0.88 1.0 12 12.750 1.25 35.6 73.0 22 0.5 DN300 323.9 32 16.2 76.1 mm 3.000 0.88 1.2 1412 14.000 9.50(s) + 76.1 22 0.5 DN350 355.6 241 3 3.500 0.88 1.2 1612 16.000 10.00(s) + DN80 88.9 22 0.5 DN400 406.4 254 3Y2 4.000 0.88 2.5 1812 18.000 11.00(s) + 0N90 101.6 22 Y 1.1 DN450 457.0 279 4, 4.250 1.00 2.3 2012 20.000 12.00(s) + 108.0 25 1.0 DN500 508.0 305 4 4.500 1.00 2.5 2412 24.000 13.50(s) DN100 114.3 25 1.1 DN600 610.0 343 ;, 5.250 1.00 4.5 For AGS fitting information,see publication 20.05 133.0 25 2.0 14-60 DN125 5:500 1.00 .--4.5 DN350-DN1500 AGS 139.7 25 2.0; 5 5.563 1.00 4.6 12 For 14"/350 mm and larger roll grooved systems,Victaulic offers the 141.3 25 2.1 Advanced Groove System(AGS).For pricing and availability of cut groove fittings in this size,contact your nearest Victaulic sales representative. • 12 For 14"/350 mm and larger roll grooved systems,Victaulic offers the Advanced Groove System(AGS).For pricing and availability of cut groove (s)=Carbon Steel Direct Roll Groove(OGS) fittings in this size,contact your nearest Victaulic sales representative. (sw)=Carbon Steel Segmentally Welded (s)=Carbon Steel Direct Roll Groove(OGS) +Contact Victaulic for details. (sw)=Carbon Steel Segmentally Welded NOTES +Contact Victaulic for details. • No.60 cap is not suitable for use in vacuum service with Style 72 or 750 couplings.No.61 bull plugs should be used. • All fittings are ductile iron unless otherwise noted with an(sw)or(s). 07.01 1449 Rev AD Updated 02/2017 CO 2017 Victaulic Company.All rights reserved. victaulic.com 16 jctaulic' victaulic.com • •4.11 DIMENSIONS Flanged Adapter Nipple No. 41 ANSI Class 125Y' No. 45F ANSI Class 150 Flat Face No. 45R ANSI Class 150 Raised Face No. 46F ANSI Class 300 Flat Face No. 46R ANSI Class 300 Raised Face No. 45RE PN10/PN16 Raised Face r- EtoE-- I-EtoE-- rEtoE-- I.-EtoEl rEtoE- ri.EtoE- - IOil No.41 No.45F No.45R No.46F No.46R No.45RE No.41 No.45F and No.45R No.46F and No.46R ANSI 125 ANSI 150 ANSI 300 No.45RE Size Flange Adapter Nipple Flanged Adapter Nipple(s) Flanged Adapter Nipple(s) Flanged Adapter Nipple Actual Approx. Approx. Approx. Approx. Outside Weight Weight Weight Weight Nominal Diameter E to E (Each) E to E (Each) E to E (Each) E to E (Each) inches inches inches lb inches lb inches lb inches lb DN mm mm kg mm kg mm kg mm kg 3/4 1.050 3.00 3.00 2.3'. 3.00 3.3 DN20 26.9" 76 76 1.0 76 1.5 - -_ _ 1 1.315 3.00 2.5 3.00 2.7 3.00 3.9 DN25 33.7 76 1.1 76 1.2 76 1.8 1' 1.660 4.00 3.0 4.00 3.3 4.00 4.8 DN32 42.4 102 1.4 102 1.5 102 2.2 iv, 1.900 4.00 3.5 4.00 3.9 4.00 6.9 DN40 48.3 102 1.6 102 1.8 102 3.1 2 2.375 4.00 5.5 4.00 6.0 4.00 8.2 2.50 5.3 DN50 60.3 102 2.5 102 2.7 102 3.7 64 2.4 viiir 2/2 2.875 4.00 8.0 4.00 9.9 4.00 11.9 _ _ 73.0 102 3.6 102 4.5 102 5.4 DN65 3.000 - _ 2.50 6.5 76.1 64 2.9 3 3.500 4.00 9.5 4.00 11.7 4.00 16.5 2.50 8.2 DN80 88.9 102 4.3 102 5.3 102 7.5 64 3.7 31/2 4.000 4.00 12.0 4.00 15.1 4.00 20.1 _ _ DN90 101.6' 102 5.4 102 w 6.8 102 9.1 4 4.500 6.00 16.7 6.00 18.5 6.00 27.4 2.75 10.0 DN100 114.3 152 7.6 152 8.4 152 12.4 70 45 5 5.563` 6.00 21.5 6.00 21.3 6.00 35.3 141.3 152 9.8 152 9.7 152 16.0 - DN125 5.500 _ _ - _ 2.75 16.3 139.7 70 7.4 6 6.625 6.00 26.5 6.00 27.5 6.00 47.5 2.75 16.3 DN150 168.3 152 12.0 152 12.5 152 21.5 70 7.4 6.500 165.1 - - - - - - - - 8 8.625 6.00 39.0 6.00 41.3 6.00 70.3 DN200 219.1 152 17.7 152 18.8 152 31.9 - 10 10.750 8.00 57.0 8.00 59.3 8.00 100.8 _ _ DN 250 273.0 203 25.9 203 27.1 203 45.7 12, 12.750 8.00 41.0 8.00 40.0 8.00 146.2 DN300 323.9 203 18.6 203 40.0° 203 66.3 _ 1413 14.000 8.00 - 8.00 8.00 DN350 355.6 203 203 + 203 + 1613 16.000 8.00 8.00 8.00 DN400 406.4 203 203 + 203 + - - 1813 18.000 8.00 _ 8.00 8.00 _ _ _ DN450 457.0 203 203 + 203 + 13 For 147350 mm and larger roll grooved systems,Victaulic offers the Advanced Groove System(AGS).For pricing and availability of cut groove fittings in this size,contact your nearest Victaulic sales representative. Is)=Carbon Steel Direct Roll Groove(DOS) (sw)=Carbon Steel Segmentally WeldedF • 07.01 1449 Rev AD Updated 02/2017 ©2017 Victaulic Company.All rights reserved. victaulic.com 17 ✓ctaulic' victaulic.com • 4.11 DIMENSIONS (Continued) • Flanged Adapter Nipple No. 41 ANSI Class 125 No. 45F ANSI Class 150 Flat Face No. 45R ANSI Class 150 Raised Face No. 46F ANSI Class 300 Flat Face No. 46R ANSI Class 300 Raised Face No. 45RE PN10/PN16 Raised Face .-EtoE-. . EtoE1 �EtoE- i.-EtoEl r___ EtoE-- �EtoE1 IN No.41 No.45F No.45R No.46F No.46R No.45RE No.41 No.45F and No.45R No.46F and No.46R ANSI 125 ANSI 150 ANSI 300 No.45RE Size Flange Adapter Nipple Flanged Adapter Nipple(s) Flanged Adapter Nipple(s) Flanged Adapter Nipple(s) Actual Approx. Approx. Approx. Approx. Outside Weight Weight Weight Weight Nominal Diameter E to E (Each) E to E (Each) E to E (Each) E to E (Each) inches inches inches lb inches lb inches lb inches lb DN mm mm kg mm kg mm kg mm kg 2013 20.000 8;00 800 800 DN500 508.0 203 203 + 203. + — — 2473 24.000 8.00 _ 8.00 8.00 DN600 610.0 203 203 + 203 + 14-60 For AGS fitting information see publication 20.05 DN350—DN 1500 A G$" 13 For 14"/350 mm and larger roll grooved systems,Victaulic offers the Advanced Groove System(AGS).For pricing and availability of cut groove fittings in this size,contact your nearest Victaulic sales representative. (s)=Carbon Steel Direct Roll Groove(OGS) (sw)=Carbon Steel Segmentally Welded +Contact Victaulic for details NOTE • All fittings are ductile iron unless otherwise noted with an(sw)or(s). i NOW • • 07.01 1449 Rev AD Updated 02/2017 0 2017 Victaulic Company.All rights reserved. victaulic.com 18 ✓ctaulil* victaUliC.COt11 • • 4.12 DIMENSIONS Swaged Nipple No. 53 Grv. x Grv. No. 54 Grv. x Thd. No. 55 Thd. x Grv. _ r___ EtoE1 1.--EtoE---1 r-- EtoE--1 1.- E to E-. f,-EtoE- 1.- EtoE---1 DinIII WI Dil 001 No.53 No 54 No 55 No 53 No.54 No. 55 ---- ------------------------------- -No.53,54,and 55 Swaged No.53,54,and 55 Swaged Size Nipples(s) Size Nipples(s) Approx. Approx. Weight Weight Nominal Sizes E to E (Each) Nominal Sizes E to E (Each) inches inches lb inches inches lb DN mm kg DN mm kg 2 1 6.50 2.0 5 2 11.00 11.5 DN50 x _ DN25 165 0.9 x DN50 279 5.2 - 11 6.50 � 2.0 3 11.00 11.3 DN32 165 0.9 DN80 279 5.1 11 6.50 2.0 4 11.00 11.5 DN40 165 0.9 DN100 279 5.2 21/2 1 7.00 3.0 6 1 12.00 17.0 x DN25 178 1.4 _ DN150 X DN25 305 7.7 1' 7.00 3.0 1 Y 12.00 17.0 DN32 178 1.4 DN32 305 7.7 11/2 7.00 3.0 11/2 12.00 17.2 DN40 - 178 1.4 _ DN40 305 7.8 2 7.00 3.0 2 12.00 17.4 DN50 178 1.4 DN50 305 7.9 3 1 8.00 4.5 21/2 12.00 17.4 DN80 x DN25 203 2.0 305 7.9 *14101 11 8.00 4.5 3 12.00 17.4 DN32 203 2.0 DN80 305 7.9 1' 8.00 4.5 31/2 12.00 17.4 DN40 203 2.0 DN90 305 7.9 2 8.00 4.5 4 12.00 17.5 DN50 203 2.0 DN100 305 7.9 21/2 8.00 4.5 4' 12.00 17.5 203 2.0 DN120 305 7.9 31/2 3 8.00 6.8 5 12.00 17.5 DN90 X DN80 203 3.1 305 7.9 4 1 9.00 7.5 8 6 20.0 DN100 x DN25 229 3.4 DN200 x DN150 + - 9.1 11/4 9.00 7.5 DN32 229 3.4 (s)=Carbon Steel Direct Roll Groove(OGS) 11/2 9.00 7.5 (sw)=Carbon Steel Segmentally Welded DN40 229 3.4 +Contact Victaulic for details 2 9.00 7.5 NOTE DN50 229 3.4 • All fittings are ductile iron unless otherwise noted with an(sw)or(s). 2' 9.00 7.5 229 3.4 3 9.00 7.5 DN80 229 _ 3.4 31/2 9.00 7.5 l L. DN90 229 3.4 - • , 07.01 1449 Rev AD Updated 02/2017 CO 2017 Victaulic Company.All rights reserved. victaulic.com 19 ✓ctaulic' victaulic.com • • 4.13 DIMENSIONS 4.14 DIMENSIONS Female Threaded Adapter Hose Nipple No. 80 No. 48 EtoEr- I•-EtoE--1 ln au IIIIIIOIIIIII No.48 No.80 Size No.48 Hose Nipple(s) Size No.80 Female Threaded Adapter Approx. Actual Approx. Actual Outside Weight Outside Weight Nominal Size Diameter E to E (Each) Nominal Diameter E to E (Each) inches inches inches lb inches inches inches lb DN mm mm kg DN mm_ mm kg 3/41.050 3.12 0.3 3/41.050 2.00 1.0 DN20 26.9 79 0.1 DN20 26.9 51 0.5 1 1.315 3.38 0.4 1 1.315 2.06 1.0 DN25 33.7 86 0.2 -- -------DN25 33.7 33.7 52 0.5 11/4 1.660 3.88 0.6 11/4 1.660 2.31(sw) 1.5 DN32 42.4 98 0.3 DN32 42.4 _ 59 0.7 ' 11 1.900 3.88 0.8 11/2 1.900 2.31(sw) 1.5 DN40 48.3 98 0.4 DN40 48.3 59 0.7 2 2.375 4.50 1.1 2 2.375- 2.50 1.4 DN50 60.3 114 0.5 DN50 60.3 64 0.6'_. 21/2 2.875 5.38 2.0 21 2.875 2.75 1.5 73.0 137 0.9 73.0 -------- ------- ----- 70 0.7 3 3.500 5.75 3.2 3 3500 2.75 2.9 DN80 88.9 146 1.5 DN80 88.9 70, 1.3 4 4.500 7.00 4.9 -- 4 4.500 3.25 4.5 DN100 114.3 178 2.2 DN100 114.3 83 2.0 5 5.563 8.75 ,-- 8.0 (s)=Carbon Steel Direct Roll Groove(OGS) 141.3 222 3.6 (sw)=Carbon Steel Segmentally Welded 6 6.625 10.13 14.3 DN150 168.3 257 6.5 NOTES 8 8.625 11.88 24.7 • Available with British Standard Pipe Threads,specify"BSP"clearly on _ DN200 219.1 302 11.2 order. 10 10.750 12.50 40.1 • All fittings are ductile iron unless otherwise noted with an(sw)or(s). DN250 273.0 318 18.2 12 12.750 14.50 62.0 DN300 323.9 368 28.1 (s)=Carbon Steel Direct Roll Groove(OGS) (sw)=Carbon Steel Segmentally Welded NOTE • All fittings are ductile iron unless otherwise noted with an(sw)or(s). aaw, • • 07.01 1449 Rev AD Updated 02/2017 ©2017 Victaulic Company.All rights reserved. victaulic.com 20 ✓ctaulid victaulic.com •4.15 DIMENSIONS Concentric/Eccentric Reducer No. 50 Concentric `- No. 51 Eccentric E E i`to Eli'to El --EtoE--01 to-EtoE-01 r-EtoE-ri la-EtoE� 14-EtoE-► --I re -1 , rrl DU [11Thd Fabricated Steel Fabricated Steel Fabricated Steel Fabricated Steel No.50 No.51 No.50 No.51 No.50 No.51 No.50 No.51 No.50 Concentric r No.51 No.50 Concentric No.51 Size Reducer Eccentric Reducer Size Reducer Eccentric Reducer Approx. Approx. Approx. Approx. Weight Weight Weight Weight Nominal E to E (Each) E to E (Each) Nominal E to E (Each) E to E (Each) inches inches lb inches lb inches inches lb inches Ib DN mm kg mm kg DN mm kg mm kg 1 Y 3/4 1.9 - - 1'/a 4.6 +DN32 x 0N20 0.9 DN32 + 2.1 1 1.9 11 3.00(sw) 2.6 10.00(sw) 8.1 DN25 + 0.9 DN40 76 1.2 254 3.7_ 11/2 3/a 1.4 2 3.00 2.4 4.00 3.3 DN40 x DN20 + 0.6 - - DN50 76 1.1 102 1.5 1 2.50 0.8 8.50(sw) 4.5 21/2 3.00 2.7 4.00 3.4 - DN25 64 0.4 216 2.0 76 1.2 102 1.5 11/4 2.50 1.0 _ _ 3 3.00 3.2 4.00 3.5 DN32 64 0.5 DN80 76 1.4 102 1.6 r 2 34 2.50 0.9 9.00(sw) 2.0 31/2 3.00 2.9 10.00(sw) 8.0 DN50 x DN20 64 0.3 229 0.9 DN90 76, 1.3 254 3.6 x 1 2.50 0.7 9.00(sw) 2.3 5 2 11.00(sw) 9.0 11.00(sw) 5.2 DN25 64 0.3 229 1.0_2_ x DN50 279 4.1 279 2.4 t€'� 11/4 2.50 1.2 9.00(sw) 4.6 2V2 4.00 4.3 11.00(sw) 10.8 DN32 64 0.5 229 2.1 102 2.0 279 4.9 11/2 3.50 1.0 3.50 1.1 3 4.00 5.5 11.00(sw) 11.1 DN40 89 0.5 89 _ 0.5 DN80 102 2.5 279 5.0 21/2 14 1.3 3.3 4 3.50 4.3 5.00 12.0 x DN20 + 0.6 + 1.5 DN100 89 1.9 127 5.4 1 2.50 1.1 9.50 3.5 6 1 4.00 5.0 11.50(sw) 14.5 DN25 64 0.5 241 1.6 DN150 x DN25 102 2.3 292 6.6 11/a 3.50 3.3 3.50 1.4 11/2 5.5 DN32 89 1.5 89 0.6 DN40 + 2.5 + + 1'h 2.50 3.6 9.50(sw) 3.7 2 4.00 6.6 11.50(sw) 14.5 DN40 64 _ 1.6 241 1.7 DNSO 102 - 3.0 292 6.6 2 2.50 3.9 3.50 4.3 21/2 4.00 6.4 11.50(sw) 14.2 DN50 64 1.8 89 2.0 102 2.9 292 6.4 3 3A 1.5 4.5 3 4.00 6.4 5.50 15.0 DN80 x DN20 + 0.7 + 2.0 DN80 102 2.9 140 6.8 i r;, 1 2.50 1.3 9.50(sw) 4.8 4 4.00 6.5 5.50 17.0 DN25 64 0.6 241 2.2 DN100 102 2.9 140 7.7 I 1'/a 2.50 1.4 + 4.8 5 4.00 6.4 5.50 17.0 i DN32 64 0.6 2.2 102 2.9 140 7.7 11/2 2.50 5.1 9.50(sw) 5.1 8 21/2 16.00 7.9 12.00(sw) 26.1 DN40 64 2.3 241 2.3 DN200 x 406 3.6 305 11.8 2 2.50 1.6 3.50 6.0 3 5.00 9.3 12.00(sw) 22.0 DN50 64 0.7 89 2.7 DN80 127 4.2 305 10.0 21/2 2.50 1.8 3.50 7.0 4 5.00 10.4 12.00(sw) 23.0 64 0.8 89 3.2 DN100 127 4.8 305 10.4 DN76.1 2.50 2.1 _ _ 5 5.00 11.6 12.00(sw) 23.0 64 1.0 127 5.2 305 10.4 31/2 3 2.50 2.0 9.50(sw) 7.0 6 5.00 11.9 6.00 24.0 DN90 x DN80 64 0.9 241 3.2 DN150 127 5.4 152 10.9 4 1 3.00 3.0 13.00(sw) 6.5 14 For 14V350 mm and larger roll grooved systems,Victaulic offers the DN100 x DN25 76 1.4 330 2.9 Advanced Groove System(AGS).For pricing and availability of cut groove fittings in this size,contact your nearest Victaulic sales representative. 07.01 1449 Rev AD Updated 02/2017 ®2017 Victaulic Company.All rights reserved. victaulic.com 21 '✓ctaulic • victaulic.com 4.15 DIMENSIONS (Continued) Concentric/Eccentric Reducer No. 50 Concentric No. 51 Eccentric El E �toE �EtoE1 r-E � EtoE� .to El r._EtoE ry EtoE >I EtoE Ell nd Fabricated Steel Fabricated Steel Fabricated Steel Fabricated Steel No.50 No,51 No.50 No.51 No 50 No 51 No.50 No.51 No.50 Concentric No.51 - No.50 Concentric No.51 ^ Size Reducer Eccentric Reducer Size Reducer Eccentric Reducer Approx. Approx. Approx. Approx. Weight Weight Weight Weight Nominal E to E (Each) E to E (Each) Nominal E to E (Each) E to E (Each) inches inches lb inches lb inches inches lb inches Ib DN mm kg mm kg DN mm kg mm kg 10 4 6.00 19.7 13.00(sw) 32.0 20 10 20.00 110.0 20.00 177.0 DN250 x DN100 152 8.9 330 14.5 _ DN500 x DN250 508 49.9 508 80.3 5 33.0 34.6 12 20.00 120.0 20.00 120.0 + 15.0 + _15.7 DN300 508 54.4 508 54.4 6 6.00 20.0 13.00(sw) 36.9 14 20.00 149.0 20.00 149.0 DN150 152 9.1 330 16.7 DN350 508 67.9 508 67,9 8 6.00 22.0 7.00 21.6 16 20.00 120.0 20.00 120.0 DN200 152 10.0 178 9.8 DN400 508 54.4 508 54.4 12 4 44.0 14.00(sw) 48.0 18 20.00 136.0 20.00 136.0 DN300 x DN100 + 20.0 356 21.8 DN450 508 61.7 508 61.7 6 7.00 24.6 14.00(sw) 50.0 24 10 20.00 142.0 20.00 142.0 DN150 178 11.2 356 22.7 DN600 x DN250 508 64.4 508 64.4 8 7.00 52.0 14.00(sw) 53.5 12 20.00 150.0 20.00 150.0 DN200 178 23.6 356 24.3 DN300 508 68.0 508 68.0 10 7.00 39.0 14.00(sw) 57.0 14 20.00 162.0 20.00 162.0 DN250 178 17.7 356 25.9 DN350 508 73.5 508 73.5 14 6 13.00 65.0 13.00 60.0 16 20.00 162.0 20.00 162.0 DN350 x DN150 330 29.5 330 27.2 DN400 508 73.5 508 73.5 8 13.00 65.0 13.00 60.0 18 20.00 162.0 20.00 162.0 DN200 330 29.5 _ 330 27.2 DN450 508 73.5 508 73.5 10 13.00 66.0 13.00 65.0 20 20.00 151.0 20.00 190.0 DN250 330 29.9 330 29.5 DN500 508 68.5 508 86.2 12 13.00 68.0 13.00 66.0 For AGS fitting information,see publication 20.05 DN300 330 30.8 330 29.9 14-6014 16 8 14.00 73.0 14.00 73.0 DN350-DN1500 AGS,. DN400 x DN200 356 33.1 355 33.1 10 14.00 73.0 14.00 73.0 14 For 14'7350 mm and larger roll grooved systems,Victaulic offers the DN250 356 33.1 355 33.1 Advanced Groove System(AGS).For pricing and availability of cut groove 12 14.00 73.0 14.00 73.0 fittings in this size,contact your nearest Victaulic sales representative. DN300 356 33.1 355 33.1 (s)=Carbon Steel Direct Roll Groove(OGS) 14 14.00 73.0 14.00 73.0 (sw)=Carbon Steel Segmentally Welded __ DN350 356 33.1 355 33.1 +Contact Victaulic for details. 18 10 15.00 91.0 15.00 91.0 NOTES DN450 x DN250 381 41.3 381 41.3 12 15.00 91.0 15.00 91.0 • Available with male threaded small end No.52. DN300 381 41.3 381 41.3 • Cast fitting available for JIS size.Contact Victaulic for details. 14 15.00 91.0 15.00 91.0 • Steel eccentric reducers available through 30'7750 mm,contact Victaulic DN350 381 41.3 381 41.3 for dimensions. 16 15.00 91.0 15.00 91.0 • All fittings are ductile iron unless otherwise noted with an(sw)or(s). DN400 381 41.3 381. 41.3 14 For 14'7350 mm and larger roll grooved systems,Victaulic offers the Advanced Groove System(AGS).For pricing and availability of cut groove fittings in this size,contact your nearest Victaulic sales representative. ,:••, ' 07.01 1449 Rev AD Updated 02/2017 0 2017 Victaulic Company.All rights reserved. victaulic.com 22 ✓ctaulic° victaulic.com 4.16 DIMENSIONS Small Threaded Reducer No. 52 No. 52F E E E E r-toEl r-toE1 r-toE-I rtoE-1 liru El It r No.52 No 52F No.52 No 52F No.52F Concentric No.52F Concentric No.52 Reducer with BSPT No.52 Reducer with BSPT _ Size Small Threader Reducer Female Threaded End Size Small Threader Reducer Female Threaded End Approx. Approx. Approx. Approx. Weight Weight Weight Weight Nominal Size E to E (Each) E to E (Each) Nominal Size I E to E (Each) E to E (Each) inches inches lb inches f inches lb DN mm kg mm kg DN mm kg mm kg 11/2 1 2.50 0.8 _ 4 1 3.00 2.3 DN40 x DN25 64 0.4 DN100 x DN25 76 1.0 11/4 2.50 0.9 1 1 3.00 2.7 DN32 64 0.4 i, s " DN40 76 1.2 2 �4 2.50 0.9 2 3.00 2.6 - - DN50 x DN20 64 0.4 DN50 76 1.2 1 2.50 0.7 - - 21/2 3.00 2.6 DN25 64 0.3 76 1.2 - 1% 2.50 1.2 _ _ 3 3.00 2.5 _ DN32 64 0.5 DN80 76 1.1 11/2 2.50 1.0 - - 108.0mm x 42.4mm 76 1.3 76 1.3 DN40 64 0.5 21/2 x 1 2.50 1.1 48.3mm 76 1.3 76 1.4 DN25 64 0.5 .4160111 11/4 2.50(sw) 1.2 - - - - DN32 64 0.5 60mm 76 1.4 11/2 2.50(sw) 1.3 114.3mm x 42.4mm 76 1.3 76 1.3 DN40 64 0.6 2 2.50 1.4 - DN50 64 0.6 - - 48.3mm 76 1.3 76 1.3 DN65 x D1N40 64 0.8 64 0.8 60mm 76 1.3 76 1.4 : :: N - 64 0.9 5 ME x DN100 + 2.0 3 1.5 x 3/4 +(sw) - - 133.Omm x 60mm - - DN80 0.7 1 2.50 1.3 _ - 139.0mm x 60mm - - 114 DN25 64 0.6 11/4 2.50 1.5 6 1 4.00 5.5 - DN32 64 0.7 DN150 x DN25 102 _ 2.5 1 1h 2.50(sw) 1.5 _ _ 2 4.00 5.7 _ DN40 64 0.7 DN50 102 2.6 2 2.50 1.5 _ _ 21/2 4.00 5.8 DN50 64 0.7 102 2.6 2 Yz 250 2.4 3 4.00 5.8 64 1.1 DN80 102 2.6 - 88.9mm x 42.4mm 64 0.9 64 0.8 6.5 100 +(sw) 2.9 - - 48.3mm 64 0.9 64 0.9 5 +(sw) 2.0 - - 0.9 60mm - - 64 0.9 159.0mm x 42.4mm 114 2.2 144 2.5 (s)=Carbon Steel Direct Roll Groove(OGS) 48.3mm 114 2.2 114 2.5 (sw)=Carbon Steel Segmentally Welded +Contact Victaulic for details. 60mm - - 114 2.6 • • 07.01 1449 Rev AD Updated 02/2017 ®2017 Victaulic Company.All rights reserved. victaulic.com 23 jictaulic" victaulic.com • • 4.16 DIMENSIONS (Continued) Small Threaded Reducer ,440.0. No. 52 No. 52F E E -toEl j-toEl iIr [ID No.52 No 52F No.52 No.52F Concentric Small Threader Reducer with BSPT Size Reducer Female Threaded End Approx. Approx. Weight Weight Nominal Size E to E (Each) E to E (Each) inches inches lb DN mm kg mm kg t �t +nun x 424mm 102mm 24 102 2.9 4$3in�n 102mrp, 2.6, ' 102 - 3.0 60mm = — 102 3.0 8 2 16.00 1.5 DN200 x DN50 406 0.7 2 Y2 16.00 1.7 406 0.8 —(s)=Carbon Steel Direct Roll Groove(OGS) (sw)=Carbon Steel Segmentally Welded NOTES • Available with British Standard Pipe Threads,specify"BSP"clearly on order. • All fittings are ductile iron unless otherwise noted with an(sw)or(s). • war • • 07.01 1449 Rev AD Updated 02/2017 ®2017 Victaulic Company.All rights reserved. victaulic.com 24 jotaulie A. victaulic.com 5.0 PERFORMANCE Flow Data (Frictional Resistance) The chart expresses the frictional resistance of various Victaulic fittings as equivalent feet of straight pipe. Fittings not listed can be estimated from the data given, for example, a 221/2"elbow is approximately one-half the resistance of a 45"elbow. Values of mid-sizes can be interpolated. Size Dimensions 90°Elbows 45°Elbows Tees Actual No. 100 No. 110 Nominal Outside No. 10 11/2 D Long No. 11 1'h D Long Size Diameter Std.Radius Radius Std.Radius Radius Branch Run inches inches feet feet feet feet feet feet DN mm meters meters meters meters meters meters 1 1.315 1.7 0.8 _ 4.2 1.7 DN25 33.7 0.5 0.2 1.3 0.5 2 2.375 �-.--_-- 3.5 2.5 1.8 1.1 8.5 3.5 DN50 60.3 1.1 0.8 0.5 0.3 2.6 1.1 - - - ---- ---- ----- ------- DN65 3.000 4.3 _ 2.1 _ 10.8 4.3 76.1 1.3 0.7 3.3 1.3 3 3.500 5.0 - 3.8 2.6 1.6 13.0 5.0 DN80 88.9 1.5 1.2 0.8 _ 0.5 4.0 1.5 - 4.250 6.4 - - 6.4 3.2 15.3 108.0 2.0 0.9 4.7 2.0 4 4.500 6.8 5.0 3.4 2.1 16.0 6.8 DN100 114.3 2.1 1.5 1.0 0.6 4.9 2.1 5.250 8.1 4.1 20.0 8.1 133.0 2.5 1.2 6.2 2.5 DN125 5.500 8.5 - 4.2 - 21.0 8.5 139.7 2.6 1.3 6.4 2.6 5 5.563 8.5 4.2 21.0 8.5 141.3 2.6 1.3 6.4 2.6 6.250 9.4 _ 4.9 _ 25.0 9.6 159.0 2.9 1.5 7.6 2.9 6.500 9.6 5.0 25.0 10.0 165.1 2.9 - 1.5 7.6 _- 3.0 6 6.625 10.0 7.5 5.0 3.0 25.0 10.0 DN150 168.3 3.0 2.3 1.5 0.9 7.6 3.0 8 8.625 13.0 9.8 6.5 4.0 33.0 13.0 DN200 219.1 4.0 3.0 2.0 1.2 10.1 - 4.0 10 10.750 17.0 12.0 8.3 5.0 41.0 17.0 DN250 273.0 5.2 3.7 2.5 1.5 12.5 5.2 12 12.750 20.0 14.5 10.0 6.0 50.0 20.0 DN300 323.9 _ 6.1 4.4 3.0 1.8 15.2 6.1 _ 14 14.000 24.515 15.8 18.575 11.0 70.0 23.0 0N350 355.6 7.5 4.8 5.6 3.4 21.3 7.0 16 16.000 28.015 18.0 21.0's 13.0 80.0 27.0 DN400 406.4 8.5 5.5 6.4 4.0 24.4 8.2 18 18.000 31.015 20.0 23.515 14.0 90.0 30.0 DN450 _ 457.0 _ 9.5 6.1 7.2 4.3 27.4 9.1 20 20.000 34.015 22.5 25.515 16.0 100.0 33.0 DN800 508.0 10.4 6.9 _ 7.8 4.9 30.5 10.1 24 24.000 42.015 27.0 29.5'5 19.0 120.0 40.0 DN600 610.0 12.8 8.2 9.0 5.8 36.6 12.2 -AGS fittings available up to 60 /1500 mm.Contact Victaulic for details. ' AGS" v '5 Fitting flow data for 14-24/350-600 mm size No.10 and No.11 Elbows is based on fittings for Style 07 and 77 couplings.For flow data an AGS fittings(No. W10 and No.W11 Elbows),refer to publication 20.05. void • • 07.01 1449 Rev AD Updated 02/2017 ©2017 Victaulic Company.All rights reserved. victaulic.com 25 ✓ctaulIc victaulic.com • • • • User Responsibility for Product Selection and Suitability Note Each user bears final responsibility for making a determination as to the suitability of This product shall be manufactured by Victaulic or to Victaulic specifications.All products 'Victaulic products for a particular end-use application,in accordance with industry to be installed in accordance with current Victaulic installation/assembly instructions. standards and project specifications,and the applicable building codes and related Victaulic reserves the right to change product specifications,designs and standard regulations as well as Victaullc performance,maintenance,safety,and warning equipment without notice and without incurring obligations. instructions.Nothing in this or any other document,nor any verbal recommendation, Installation advice,or opinion from any Victaulic employee,shall be deemed to alter,vary,supersede, Reference should always be made to the Victaulic installation handbook or installation or waive any provision of Victaulic Company's standard conditions of sale,installation instructions of the product you are installing.Handbooks are included with each shipment guide,or this disclaimer. of Victaulic products,providing complete Installation and assembly data,and are available Intellectual Property Rights in PDF format on our website at www.victaulic.com. No statement contained herein concerning a possible or suggested use of any material, Warranty product,service,or design is Intended,or should be constructed,to grant any license Refer to the Warranty section of the current Price List or contact Victaulic for details. under any patent or other intellectual property right of Victaulic or any of its subsidiaries or affiliates covering such use or design,or as a recommendation for the use of such Trademarks material,product,service,or design in the infringement of any patent or other intellectual Victaulic and all other Victaulic marks are the trademarks or registered trademarks of property right.The terms"Patented"or"Patent Pending"refer to design or utility patents Victaulic Company,and/or its affiliated entities,in the U.S.and/or other countries. or patent applications for articles and/or methods of use in the United States and/or other countries. %NW • • 07.01 1449 Rev AD Updated 02/2017 0 2017 Victaulic Company.All rights reserved. victaulic.com 26 ✓ctauhc" INSTAI CATION INSTRUCTIONS 1-009 H FireLock EZTM Rigid Coupling STYLE 009H -44 NOTICE 4 • Victaulic Style 009H Couplings are designed for use ONLY on wet and dry fire protection systems(temperatures greater than , .....4.... �� —40°F/-40°C). For rigid pipe connections in systems operating below 0°F/-18°C,Victaulic recommends Style 005 FireLock® Rigid Couplings with Grade"L"(silicone)gaskets. • Read and understand all instructions before attempting to • Victaulic Style 009H Couplings are provided with the install any Victaulic piping products. Vic-PIusTM gasket system.Additional lubrication is not required for the initial installation of wet pipe systems that are installed • Depressurize and drain the piping system before attempting at or continuously operating above 0°F/-18°C. Refer to Victaulic to install,remove,or adjust any Victaulic piping products. publication 05.03 in the G-100 General Catalog for the Vic-Plus • Wear safety glasses, hardhat,and foot protection. MSDS sheet. Failure to follow these instructions could result in serious Supplemental lubrication is required for Vic-Plus gaskets only if personal injury, improper product installation,and/or property any of the following conditions exist. If any of these conditions damage. exist,apply a thin coat of Victaulic lubricant or silicone lubricant to the sealing lips of the gasket interior only. • If the gasket has been exposed to fluids prior to installation INSTRUCTIONS FOR THE INITIAL INSTALLATION • If the surface of the gasket does not have a hazy appearance OF STYLE 009H COUPLINGS • If the gasket is being installed into a dry pipe system 1.DO NOT DISASSEMBLE THE • If the system will be subjected to air tests prior to being filledr ,. COUPLING:Style 009H Couplings with water are installation ready.These couplings • If the gasket was involved in a previous installation '. - are designed so that the installer does • If the gasket sealing surface of the pipe contains raised or ' not need to remove the bolts and nuts iz undercut weld seams,or cracks or voids at the weld seams. *x - . for installation.This design facilitates However, lubricated gaskets may not enhance sealing installation by allowing the installer to capabilities on all adverse pipe conditions. Pipe condition and 1 , f w` + directly install the grooved end of pipe/ pipe preparation must conform to the requirements listed in 3� mating components into the coupling. product installation instructions. ,t =s II 2.CHECK PIPE/MATING COMPONENT ENDS:The outside surface Ilia • Never leave a Style 009H Coupling of the pipe/mating component, between the groove and the pipe/ ' partially assembled.A partially mating component end, must be smooth and free from indentations, ti assembled Style 009H Coupling poses a projections(including weld seams),and roll marks to ensure a leak- drop hazard. tight seal.All oil,grease,loose paint,dirt,and cutting particles must be • removed. Measurements taken across grooved pipe/mating component Keep hands away from the pipe/mating ends must not exceed the maximum allowable flare diameter.Refer to component ends and the openings of the current Victaulic grooving specifications for the maximum allowable flare coupling when attempting to insert the diameter. grooved end of pipe/mating components into the coupling. Failure to follow these instructions could cause serious personal injury and/or property damage. u Gasket Grade Color Code Mark i 3.CHECK GASKET:Check the gasket to make sure it is suitable for the intended service.The color code identifies the gasket grade. Refer to the"NOTICE"on this page for details concerning operating r:, temperatures and other requirements. Refer to Victaulic publication 05.01 in the G-100 General Catalog or the"Gasket Selection"section in the 1-100 Field Installation Handbook for the color code chart. 4.ASSEMBLE JOINT:Assemble the joint by inserting the grooved end of a pipe/mating component into each opening of the coupling.The ends of the grooved pipe/mating components must be inserted Into the www.victaulic.com �Ctauli VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY.0 2011 VICTAULIC COMPANY.ALL RIGHTS RESERVED.PRINTED IN THE USA. REV F 1 00911 1 INSTALLATION INSTRUCTIONS 1-009H FireLock EZTM Rigid Coupling STYLE 009H coupling until contact with the center leg of the gasket occurs.A visual , i,... +,7, 0 ''' check is required to ensure the coupling keys align with the grooves in f K" the pipe/mating components.NOTE:The coupling may be rotated to zs. 1 ensure the gasket is seated properly. i GO CI` - , NOTE:When assembling Style 009H Couplings onto end caps,take ,, is I., additional care to ensure the end cap is seated fully against the center leg of the gasket. DO NOT use Non-Victaulic fittings with Style 009H , Couplings. Use only FireLock No.006 End Caps containing the"EZ" marking on the inside face or No.60 End Caps containing the"QV EZ" �ii' marking on the inside face. I I a • For Victaulic rigid,angle-bolt-pad couplings,the nuts must be tightened evenly by alternating sides until metal-to-metal contact occurs at the bolt pads. • For Victaulic rigid,angle-bolt-pad couplings,equal offsets must be present at the bolt pads. BAD • Keep hands away from coupling openings during tightening. ,` .$f. a Failure to follow these instructions could cause joint failure, • serious personal injury,and property damage. 1 ,, ), 1.' Y t 6.Visually inspect the bolt pads at each joint to ensure metal-to-metal ':1- contact is achieved. NOTICE Visual inspection of each joint is critical. Improperly assembled + 'x " joints must be corrected before the system is placed in service. '` Wi: EI GOOD 0 BAD ,,,,,,ik, i Pd ....,, . . *MOM PROPERLY PROPERLY IMPROPERLY IMPROPERLY ASSEMBLED JOINT ASSEMBLED ASSEMBLED ASSEMBLED POSITIVE OFF- JOINT JOINT JOINT SET WITH BOLT NEUTRAL OFFSET NEGATIVE BOLT PAD 5.TIGHTEN NUTS:Tighten the nuts evenly by alternating sides until PAD CONTACT WITH BOLT PAD OFFSET GAP metal-to-metal contact occurs at the angle bolt pads. Make sure the (PREFERRED) CONTACT housings'keys completely engage the grooves and the offsets are equal • "Negative"bolt pad offsets can occur when the nuts are not at the bolt pads.To ensure a rigid joint,equal and positive offsets are tightened evenly,which produces over-tightening of one side and preferred. NOTE: It is important to tighten the nuts evenly to prevent under-tightening of the other side. In addition,"negative"offsets gasket pinching.An impact wrench or standard socket wrench can be can occur if both nuts are under-tightened. used to bring the bolt pads into metal-to-metal contact. Refer to the "Impact Wrench Usage Guidelines"section on page 4. www.victaulic.com VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY.®2011 VICTAULIC COMPANY.ALL RIGHTS RESERVED.PRINTED IN THE USA. �Ctaulld I-009H 2 REV_.,E INSTALLATION INSTRUCTIONS I-0►09H _________-._.-_. FireLock EZTM Rigid Coupling STYLE 009H 4 INSTRUCTIONS FOR RE-INSTALLATION OF ,r STYLE 009H COUPLINGS , Since the coupling housings conform to the outside diameter of the illiOtettoMmillut N pipe/mating component during an initial installation,direct installation a, l '101.11.11 of the pipe/mating components into the coupling may not be possible mow— upon re-installation. If this is the case,refer to the following steps for ' I re-installing the coupling. i a 1.Make sure the system is depressurized and drained completely before attempting to disassemble any couplings. t 2.Follow steps 2—3 on page 1. i IIIMIIIPr P ..xr -, 5.JOIN PIPE/MATING COMPONENTS:Align the two grooved ends of � 4 "�' ' the pipe/mating components. Insert the other pipe/mating component end into the gasket until it contacts the center leg of the gasket. NOTE: ° Make sure no portion of the gasket extends into the groove of either - " d * pipe/mating component. 3.FOR RE-INSTALLATION OF STYLE 009H COUPLINGS, LUBRICATE GASKET:Apply a thin coat of Victaulic lubricant or silicone lubricant to the gasket sealing lips and exterior.It is normal for the gasket surface to have a hazy white appearance after it has been in service. d, r r +tC, ' t J 6.TO FACILITATE RE ASSEMBLY One bo:ccearnE:b.e:tiirie-s-rel rtedmtor t k, ,, the housings with the nut threaded loosely nto thbolt to allow for x 1 'x;'. ;' the"swing-over"feature,asshownabove. ut should be { ''''.4': 'IL backed off no further than flush with the end of the bolt. r f �x ,e. ,. Pipe End , ,:,,,,, gel• , Onter Mg tr ., -'''''ql'.-,,:-,,;',,,-. • of Gasket 4.INSTALL GASKET:Insert the grooved end of a pipe/mating , +,', ,, component into the gasket until it contacts the center leg of the gasket. 7. INSTALL HOUSINGS:Install the housings over the gasket.Make sure the housings'keys engage the grooves properly on both pipes/mating components. www.victaulic.com VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY,0 2011 VICTAULIC COMPANY.ALL RIGHTS RESERVED.PRINTED IN THE USA. ic'ta ullc' REV._.E 1-009H 3 INSTAL I ATION INSTRUCTIONS l-009 H FireLock EZTM Rigid Coupling STYLE OO9H IMPACT WRENCH USAGE GUIDELINES • Nuts must be tightened evenly by alternating sides until metal- to-metal contact occurs at the bolt pads.For angle-bolt-pad ,F.. - ,- couplings,even offsets must be present at the bolts pads to obtain pipe-joint rigidity. I .. • DO NOT continue to use an impact wrench after the visual installation guidelines for the coupling are achieved. hFailure to follow these instructions could cause gasket pinching and coupling damage,resulting in joint failure,serious personal injury,and property damage. s "" ,,, .;N - Due to the speed of assembly when using an impact wrench,the installer should take extra care to ensure nuts are tightened evenly by alternating sides until proper assembly is complete.Always refer to 8.INSTALL REMAINING BOLT/NUT: Install the remaining bolt,and the specific product installation instructions for complete installation thread the nut finger-tight onto the bolt. NOTE: Make sure the oval neck requirements. of each bolt seats properly in the bolt hole. Impact wrenches do not provide the installer with direct"wrench feel" 9.TIGHTEN NUTS:Follow steps 5 and 6 on page 2 to complete the or torque to judge nut tightness.Since some impact wrenches are assembly. capable of high output,it is important to develop a familiarity with the HELPFUL INFORMATION impact wrench to avoid damaging or fracturing bolts or coupling bolt Size Nut Size Socket Size pads during installation.DO NOT continue to use an impact wrench 1' `kctual Pipa 1' after the visual installation guidelines for the coupling are achieved. N f irK3f 1'a T e` t g Diartletcr ,neh s/ Inahes/ r rffm ;� , 04y �� , exr m, If the battery is drained or if the impact wrench is under-powered, 1.660-4.500 3/8 11/16 a new impact wrench must be used to ensure the visual installation 1/4-4 42.4-114.3 M10 17 guidelines for the coupling are achieved. 76.1-108.0 mm 3.000-4.250 3/8 11/16 Perform trial assemblies with the impact wrench and socket or torque 76.1-108.0 M10 37 wrenches to help determine the capability of the impact wrench. Using 133.0-139.7 mm 5.250 5.500 /° the same method, periodicallycheck additional nuts throughout the 133.0-139.7 M12 18 g 5.563 yz 3 system installation. 5 141.3 M12 18 For safe and proper use of impact wrenches,always refer to the impact 6.250 6.500 5/8 15/16 159.0-165.1 mm 159.0--165.t M16 24 wrench manufacturer's operating instructions. In addition,verify that proper impact grade sockets are being used for coupling installation. 6—8 6.625—8.625 5/8 15/16 168.3-219.1 M16 24 For complete contact information,visit www.victaulic.com I-009H 4079 REV E UPDATED 09/2011 2000009000 jctaulic° VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY.©2011 VICTAULIC COMPANY.ALL RIGHTS RESERVED.PRINTED IN THE USA. --- 1,OO9H Cast Iron Threaded Fittings Class 125, (Standard) (lir) u !AL,L.rM 221/2°Elbow Size A B Weight(Ibs) Figure 356A (NPS) (in) (in) black galv. 3/4 % 7/6 .52 • 1 7/16 1 .80 • 11/4 1/2 11/2 1.40 • 6 11/2 6/6 11/4 1.64 • A 2 3/4 17/16 2.50 21/2 3/4 1% 3.95 • •Not stocked Cast Iron Threaded Fittings Pressure-Temperature Ratings Pressure,(psig) Temp.(°F) Class 125 Class 250 -20° to 150° 175 400 200° 165 370 250° 150 340 300° 140 310 350° 125 300 400° -- 250 4.0 www.anvilintl.com (12/10/01) I Cast Iron Threaded Fittings .; Class 125, (Standard) C'TJ) d1AlIL. ER NATIONAL, INC. stlMti 45° Elbow Size A B Weight(Ibs) Figure 356 (NPS) (in) (in) black galv. 1/4 7,6 3/4 .16 .17 3/6 7/16 13/16 .23 — • 1/2 1/46 7/a .3 7 .3 8 ty 3/4 1/2 1 .55 .56 1* 9/16 11/6 .83 .88 11/4 5/6 11/4 1.33 1.36 11/2 7 3/16 17/16 1.79 1.83 ,r6,1\ 2 1 111/16 2.89 2.96 9 21/2 1'/16 115/16 4.29 4.35 3 13/16 23/16 6.44 6.65 BA 31/2 1% 2% 8.42 — 4 19/16 25/6 10.64 11.22 5 17/6 31/4 6 16.96 17.38 1 NPS size available in 6 23/16 3'/16 26.02 26.19 1 NPS x'A NPS reducing size, 8 27/a 41/4 50.17 52.00 black or galvanized. Cast Iron Threaded Fittings Pressure-Temperature Ratings Pressure, (psig) Temp.(°F) Class 125 Class 250 -20° to 150° 175 400 200° 165 370 250° 150 340 300° 140 310 350° 125 300 400° -- 250 www.anvilintl.com [12/10/01) Cast Iron Threaded Fittings twit) � � IClass 125, (Standard) INTERNATIONAL, INC 90° Elbow Straight Size A B Weight(Ibs) Figure 351 (NPS) (in) (in) black galv. 1/4 '/2 13/1 s .16 .17 a ...16, l'' 3/6 9/16 15/16 .25 .26 i /2 "A s 1'/s 40el .41 ����' 3/4 13/is 1 5/1 6 .60 .61 ' 1 15/16 11/2 .92 .95 1 1/4 1'/6 1 1/4 1.4 4 1.46 •-qB-1 1 1/2 1 5/16 115/16 1.95 2.00 2 19/16 21/4 3.13 3.21 21/2 1 t 3/16 21 Y16 4.94 5.13 - 3 23/16 31/6 7.21 7.40 4 2"//6 313/16 12.17 12.67 5 35/1 s 41/2 21.46 — 6 Vs 51/8 31.33 33.33 6 53/46 69/16 64.56 67.14 Cast Iron Threaded Fittings Pressure-Temperature Ratings Pressure,(psig) Temp.(°F) Class 125 Class 250 -20° to 150° 175 400 200° 165 370 250° 150 340 300° 140 310 350° 125 300 400° -- 250 411100 www.anvilintl.com (12/10/01) vww,uuuf++sxwxaN.�urtwatwuw+wwuuuuu�.w.wucuea+uui+iuwwl,,. Cast Iron Threaded Fittings tw* TMGlass 125, (Standard) 1 I L INT ERNATIONAI, INC. ."'""` Cap Size Weight(Ibs) Figure 381 (NPS) black galv. 21/2 2.55 — ;r' 3 4.10 — 4 6.40 — 5 10.70 — 6 14.20 14.60 8 27.23 28.35 0 '/s, '/4,3/8 NPS plugs furnished in steel A'/2 and 3/4 NPS countersunk plugs furnished in malleable iron •Not stocked Cast Iron Threaded Fittings Pressure-Temperature Ratings Pressure, (psig) Temp.(°F) Class 125 Class 250 -20° to 150° 175 400 200° 165 370 250° 150 340 300° 140 310 350° 125 300 400° 250 www.anvilintl.com (12/10/01) I Cast Iron Threaded Fittings /i�`„ ANVIL Class 125, (Standard) �� INTERNATIONAL, INC. Concentric Reducers Size A B Weight Figure 367 (NPS) (in) (in) (Ibs) black 3/4 1/2 5/8 19/16 .4 0 1 ■ 1/2 "/is 1"/A6 .54 • 3/4 'As 11/2 .63 1/2 8/46 1% .84 11/4 3/4 1 2'/8 1.07 1 15/16 2'/8 1.07 1/2 / 15/e 1.00 3/4 1/2 1% 1.20 1'/2 1 1/2 13/4 1.50 11/4 1 21/4 1.45 /2 3/8 2 2.00 ,I 3/4 3/4 2 1.90 2 1 3/4 2 1.83 11/4 "A 21/8 1.7 8 [4-8 11/2 7/8 23/16 1.98 w I 11/4 3/4 2 3.10 21/22 1 28/16 2.98 3/4 "As 2'/2 4.31 3 2 1 Yi6 23/4 3.96 21/2 "As s 213/16 4.40 2 1 3/4 6 215/16 6.50 4 21/2 13/is 31/8 7.78 3 11/26 31/8 7.01 5 4 11/46 35/16 10.48 4 11/s 3'/i s 13.83 6 5 1 Ys 38//6 15.53 8 6 11/4 3'/s 29.10 ■hex end Cast Iron Threaded Fittings Pressure-Temperature Ratings Pressure,(psig) Temp.(°F) Class 125 Class 250 -20° to 150° 175 400 200° 165 370 250° 150 340 300° 140 310 350° 125 300 400° -- 250 401104 www.anvilintl.com [12/10/01) I Cast Iron Threaded Fittings Class 125, (Standard) ellirll NVI�.. l� .� INTERNATIONAL, INC. 4410 Malleable Iron Threaded Pipe With Unions __ Pressure-Temperature Ratings Malleable Iron Threaded Fittings Pressure-Temperature Ratings Pressure,(psig) _ __ Temp Class Class Class Pressure, (psig) (°F) 150 250 300 Temp Class 300 -20° to 150° 300 500 600 (°F) Class 150 Sizes Sizes Sizes 200° 265 455 550 1/4"-1" 11/4"-2" 21/2"-3" 250° 225 405 505 -20° to 150° 300 2,000 1,500 1,000 300° 185 360 460 200° 265 1,785 1,350 910 350° 150 315 415 250° 225 1,575 1,200 825 400° 110 270 370 300° 185 1,360 1,050 735 450° 75 225 325 350° 150 1,150 900 650 500° 180 280 400° -- 935 750 560 550° - 130 230 450° -- 225 600 475 Note: Unions with Copper or Copper Alloy seats 500° 510 450 385 are not intended for use where 550° 300 300 300 temperature exceeds 450°F Anvil Class 150(Standard Weight)Malleable Iron Fire Protection Equipment and Materials"issued by the Underwrit- Fittings conform to ASME B16.3 and Unions conform to ASME ers'Laboratories,Inc. B16.39. ALL ELBOWS&TEES 3/e"AND LARGER ARE 100%GAS TESTED AT A MINIMUM Anvil standard weight banded pattern fittings in this catalog,sizes OF 100 PSI. '/8 NPS to 6 NPS inclusive,are included in the"List of Inspected °ui www.anvilintl.com (12/10/01j I Cast +�Iron Threaded ryFittings (*)/.11WIL Class 25, Standard) INTERNATIONAL, INC140 floor flange Size dia.of dia.of Weight bolt holes cored (NP flange no.of holes (lb) Figure 1006 holes S) (in) (in) black galv. 1/4 213/16 4 1/4 .39 .40 3/8 3 4 1/4 .43 .45 /2 3'/2 4 /4 .73 .74 3/4 31/2 4 1/4 .80 .81 1 4 4 1/4 1.13 1.14 11/4 4 4 1/4 1.14 1.15 11/2 41/3 4 5/16 1.55 1.56 2 51/2 4 5/16 2.40 2.43 0 '/8, '/4,3/s NPS plugs furnished in steel A 1/2 and 3/4 NPS countersunk plugs furnished in malleable iron •Not stocked Cast Iron Threaded Fittings Pressure-Temperature Ratings Pressure,(psig) Temp.(°F) Class 125 Class 250 -20° to 150° 175 400 200° 165 370 250° 150 340 300° 140 310 350° 125 300 400° -- 250 4411100 www.anvilintl.com (12/10/01) I Cast Iron Threaded Fittings Class 125, (Standard) TM /C�/� TER ! . Hex Bushing Size Weight(Ibs) Hex Bushing Size Weight(Ibs) Figure 383 (NPS) black galv.v. Figure 383 (NPS) black galv. 1/4 '/R .021* .022 IN 2 5.12 5.24 3/e 1/4 .038 .039 ■ 21/2 4.87 5.06 5 ■ 3 4.83 4.93 1/8 .060 .062 31/2 4.00 4.30 1/2 1/4 .070 .073 4 3.94 4.10 3/B .050 .053 _ ■ 2 8.00 8.32 1/8 .090 .093 ■ 21/2 7.72 7.78 3/4 1/4 .100 .105 6 ■ 3 ' 7.75 8.06 3/8 .119 .121 • 31/2 7.13 7.40 1/2 .103 .105 Continued from ■ 4 6.83 7.11 ■ 1/8 .208 .216 previous column. 5 5.24 5.45 • 1/4 .186 .192 ■ 3 15.50 15.8 1 ■ 3/3 .182 .188 8 III 4 13.93 15.0 1/2 .215 .220 ■ 5 13.65 14.0 6 13.19 13.5 3/4 .170 .174 ■ 4 27.5 - III 1/4 .290 .300 ■ 5 _ _ NI 3/3 .290 .295 10 • 6 24.5 - 11/4 ■ Y2 .300 .305 8 22.0 - 3/4 .385 .393 12 4 32.5 * 1 .296 .302 10 32.5 33.0 1/4 .470 .490 • 3/8 .470 .500 ■ 1/2 .420 .470 Note: Hexagon head or octagon head bushings 21/2NPS and smaller 11/2 III 3/4 .470 .500 reducing one size may be made of malleable iron, ductile iron or steel. .520 Other sizes may be made of cast iron, ductile iron, malleable iron or 1 .500 1 Y4 .327 .520 steel. Face bushings 21/2 NPS and smaller may be made of malleable iron, ductile iron or steel. Face bushings 3NPS and larger reducing one size ■ 11/4 .810 .830 may be made of malleable iron,ductile iron or steel. Face bushings 3NPS ■ 11/2 .667 .680 and larger reducing two sizes or more may be made of cast or malleable 1/4 .750 .800 iron, ductile iron, or steel. !., - % .750 780 According to specifications, hex bushings and cored plugs should be 2 ■ 1/2 .770 .780 used with 150#malleable iron and 125#cast iron. Solid plugs and face II 3/4 .710 .750 bushings should be used with#250 and#300 fittings. ■ 1 .730 .760 ■ 1'/4 .810 .830 ■ 1/2 1.280 - II 3/4 1.250 1.290 21/2 ■ 1 1.160 ' 1.230 ■ 1'/4 1.240 1.250 ■ 11/2 1.290 1.340 2 .920 .950 ■ 1/2 1.9 3 2.01 ■ 3/4 1.92 1.95 • 1 1.90 1.92 3 ■ 11/4 1.77 1.80 ■ 11/2 1.79 1.83 2 1.90 1.94 21/2 1.63 1.66 • 1 2.65 2.75 ■ 11/4 2.54 2.64 3'/2 ■ 11/2 2.32 2.38 • 2 2.42 2.48 21/2 2.56 2.61 3 1.96 1.98 ■ ' 1 3.59 3.63 ■ .11/4 3.54 3.60 ■ 11/2 3.44 3.50 %N,,. 4 ■ 2 3.11 3.24 ■ 21/2 3.29 3.33 3 ' 3.15 3.21 3Y2 2.50 2.58 www.anvilintl.com (12/10/01) I Cast Iron Threaded Fittings Class 125, (Standard) ��Z'J ,/,,�"�/f�.. INTERNATIONAL, INC. Malleable Iron Threaded Pipe With Unions Pressure-Temperature Ratings Malleable Iron Threaded Fittings — - Pressure-Temperature Ratings Pressure,(psig) Temp Pressure,(psig) (°F) Class Class Class 150 250 300 Temp Class 300 -20° to 150° 300 500 600 (°F) Class150 Sizes Sizes Sizes 200° 265 455 550 '/a"-1" 1h/4"-2" 2'/2"-3" 250° 225 405 505 -20° to 150° 300 2,000 1,500 1,000 300° 185 360 460 200° 265 1,785 1,350 910 350° 150 315 415 250° 225 1,575 1,200 825 400° 110 270 370 300° 185 1,360 1,050 735 450° 75 225 325 350° 150 1,150 900 650 500° -- 180 280 400° -- 935 750 560 550° -- 130 230 450° -- 225 600 475 Note: Unions with Copper or Copper Alloy seats 500° -- 510 450 385 are not intended for use where 550° 300 300 300 temperature exceeds 450°F Anvil Class 150(Standard Weight)Malleable Iron Fire Protection Equipment and Materials"issued by the Underwrit- Fittings conform to ASME B16.3 and Unions conform to ASME ers'Laboratories,Inc. B16.39. ALL ELBOWS&TEES 3/a"AND LARGER ARE 100%GAS TESTED AT A MINIMUM Anvil standard weight banded pattern fittings in this catalog,sizes OF 100 PSI, '/s NPS to 6 NPS inclusive,are included in the"List of Inspected Vie Cast Iron Threaded Fittings Pressure-Temperature Ratings Pressure,(psig) Temp.(°F) Class 125 Class 250 -20° to 150° 175 400 200° 165 370 250° 150 340 300° 140 310 350° 125 300 400° -- 250 411110 www.anvilintl.com (12/10/01) I Cast Iron Threaded Fittings /'; "!)'' I� I M Class 125, (Standard) �� INTERNATIONAL, INC. Square Head Size Weight(Ibs) PFigure 388lugs ) (NPS) black galv. 1/2 .100 .104 3/4 .169 .175 1 .320 .333 11/4 .531 .546 11/2 .760 .770 2 1.230 1.250 21/2 2.000 2.080 3 3.180 3.310 3'/2 4.380 • 0 '/a, %,3/8 NPS plugs furnished in steel A 1/2 and 3/4 NPS countersunk plugs furnished in malleable iron •Not stocked Cast Iron Threaded Fittings Pressure-Temperature Ratings Pressure,(psig) Temp.(°F) Class 125 Class 250 -20° to 150° 175 400 200° 165 370 250° 150 340 300° 140 310 350° 125 300 400° -- 250 "Tirr www.anvilintl.com (12/10/01) :arrrrrr . Cast Iron Threaded Fittings Class 125, (Standard) (7„ir), !LT:./� i INTERNATIONALINC411 Straight Tee Size A B Weight(Ibs) Figure 358 (NPS) (in) (in) black galv. 1/4 1/2 13/1 s .22 .23 f'l 3/s s/s 1 .35 .36 llll 1/2 11/i s 11/6 .56 .58 ,h 3/4 13/1 s 1 s/1 s .84 .85 '_lam 1 15/16 11/2 1.25 1.31 f 11/4 11/8 13/4 2.03 2.07 1.--8—,~B--1 11/2 is/,s 0/16 2.70 2.72 2 19/1 s 21/4 4.23 4.33 ;,.A--wA— 21/2 113/16 2111/46 6.67 6.79 -- --T-1 E---f 3 23/i6 31/8 10.00 10.16 A B 31/2 27/16 3'/i6 13.29 13.82 4 211/is 33/4 16.33 16.99 ' 5 35/16 41/2 27.33 27.67 6 37/s 5'/8 40.85 41.40 8 53/,6 69/,6 79.00 81.25 Cast Iron Threaded Fittings Pressure-Temperature Ratings Pressure,(psig) Temp.(°F) Class 125 Class 250 -20° to 150° 175 400 200° 165 370 250° 150 340 300° 140 310 350° 125 300 400° -- 250 www.anvilintl.com (12/10/01) I Cast Iron Threaded Fittings tlfri/INVILClass 125, (Standard) INTERNATIONAL, INC. Reducing Tee Figure 359 Reducing Tee:Figure 359 """' I Size(NPS) A BCDE F Wt.(Ibs) - f s x t x u (in) (in) (in) (in) (in) (in) black galv. 1 1/8 "At s 1'/B 1 1/4 1 13/1 s 1 9/1s 1 7/e 1.9 3 - 1/2 11/2 15/16 11/4 15/i s 115/16 113/4 s 115/1 6 2.14 3/4 1 1/2 t 5/16 1 1/4 15/16 1 15/16 1 3/4 115/1 s 2.18 - Reducing Tee:Figure 359 /2 1/26 3/4 1'/4 1'/,6 5/,e 111/4 6 1.75 - Size(NPS) A BCDE F Wt. (Ibs) 3/4 T/8 73/18 11/4 11/2 1% 13/4 1.7 - s x t x u (in) (in) (in) (in) (in) (in) black galv. 1 1 1 15/16 11/4 15/8 11/2 113/+s 1.72 - 1 1/e '3/1 s 1 1/8 1 1/4 1 1 3/1 6 1 1 to s 1'/8 2.0 8 1/4 "/i s ,y,s 1 3/i 6 1'/e 1'/8 11/e 0.5 7 11/2 15/16 11/4 '5/i s 1'S/1 s 1 3/6 1'5/1 s 2.29 3/8 1 1/1 s 11/16 3/4 1'/s 1'/B 1 1/8 0.5 7 1/2 /z 1/43/1 6 '3/1 s 1/1 s 1'/a 11/a 1/2s 0.6 8 - 2 11/2 17/1 s 15/i s 2'/8 2 2 2.91 - 1/2 13/1 s '1/16 1 1/4 1 2/16 "A B 1'1/1 s 1.6 7 1.7 3 1 1 1 '3/1 s 1'/i s 17/1 s 13/e 1 - 1'/2 3/4 '/a '3/1 s 11/4 11/2 17/16 13/4 1.7 9 1/4 3/4 1 3/1 6 15/16 13/16 15/18 1 1/4 1 5/1 6 0.7 9 - 1 1 15/16 11/4 15/s 19/1s 1'3/+s 1.97 2.05 1/2 11/16 11/16 1 3/1 6 13/16 1 Vs 11/4 0.64 - 11/e 3/4 '3/16 '3/16 '3/16 1 5/16 1 1/4 15/16 0.7 5 - 1 1/6 '3/16 1 1/8 1 1/4 1 13/16 1 1/4 1'/8 2.2 8 - 1 1/2 15/18 11/4 1 1/26 1 15/16 1 7/8 1 11/2 6 2.5 3/4 1/4 9/16 9/16 7/8 "A 1/16 13/16 0.6 2 - 3 11 11 15 13 13 1 2 1 1/2 1'As 15/16 21/s 2'/1s 2 3.0 7 - 3/4 /e /i s /i s /i s /i s /�s 1/a 0.7 5 - 1/2 "A 6 '3/16 11/4 17/16 1'/1 s 1'1/1 s 1.8 4 - 1/2 '1/16 11/16 13/16 13/16 t 3/16 1 1/4 0.7 6 - 1 "As '3/4s 3/1 s 1'/i s 17/1 s 13/e 0.9 9 - 3/4 '/8 7/8 11/4 11/2 11/2 13/4 1.9 5 - 1 1 1 11/4 1 5/8 1 5/B 1 t 3/1 6 2.13 2.17 1/4 1 '5/16 t 5/16 15/16 11/2 11/4 1 1/2 1.0 8 - 1 1/2 1 1/8 13/16 13/16 1 1/4 1 13/1 s 1'3/16 17/E 2.4 4 '/2 '1/16 3/4 15/16 1 I/4 13/16 1 3/8 0.9 2 1 1/2 11/2 'S/i 6 2'/e 2'/e 2 3.2 3 1/2 3/4 13/1 s 13/1 s 1 S/16 1 3/8 1 1/4 1 7/16 0.91 - - 1 s/i s 15/1 s 'S/1 s 1 1/2 1 3/e 1 1/2 1.0 8 - 21/2 1 13/16 1 13/16 IS/is 2 7/16 2 7/16 2 3/1 s 4.1 5 - 1/2 11/16 11/16 15/16 1 1/4 1 3/1 6 1 3/8 0.8 9 - 1/2 11/2 1 5/1 6 1 3/6 1 1/2 2 1'3/16 2'/8 2.9 5 - 3/4 3 13 13 15 3 15 7 2 1 9/1 s 1 7/16 1 9/16 21/4 1 7/8 21/4 3.3 - 1 /a /,s /,s /,s 1/e /,s 1 /,s 1 - 11/e "A s 11/2 17/1 s 17/6 13/4 21/1 s 2.5 - 1 15/i s 15/i s S/i s 11/2 1'/i s 11/2 1.13 - rtir 3/a 1'/2 t/s /s 1 / 2 113/16 2/ 3.4 - 1/4 '1/16 "A 6 1% 1% 11/4 13/8 1.01 - 2 19/1 s 17/1 s 19/1 s 21/4 1'S/,s 21/4 3.31 - 1/2 '1/16 "3/4 6 15/1 s 11/4 11/4 13/a 1.01 1.03 1 "A s "/,s 17/1 6 13/4 15/8 2 2.7 - 1 3/4 '3/16 13/16 15/16 1 3/6 1% 1 7/16 1.1 1 - 1'/8 "A 1'/e 1 1/2 1 7/e 1 3/4 2'/16 2.9 4 11/e 1'/s 11/8 1 5/1 6 1"A s 1"A s 19/1 s 1.4 9 - 1 11/2 '3/4 s 11/4 11/2 2 113/i s 2'/e 2.8 5 11/2 11/4 11/4 1 113/1 s 113/16 15/a 1.84 - 2 11/2 6 17/1 s 19/1 s 21/4 2 21/4 3.46 1/2 13/16 7 3/16 11/e 1 7/16 'S/i 6 1 5/8 1 - 21/2 17/8 1 13A 1 9/16 2 9/16 2% 27/16 4.8 8 1/2 1 '5/1s '5/1s 1Ye 19/1s 1% 1'1/2 6 1.38 - /2 "/,s 1 1'/,s 13/4 15/8 2 2.48 1'/s 1'/e 11/2 11/e 1 1/4 19/1 s 13/4 1.64 - 3/4 7/6 7/6 17/1 s 19/i 6 11/2 1'S/,s 2.5 3/4 13/16 '3/16 11/8 17/16 "A 1 5/8 1.2 7 - 1 11/2 s 1 1'/,6 13/4 15/8 2 2,7 3 3/4 1 5/1s 5/1s 1'/e 13/46 13/4s 1"A 1.43 - 1'/e 1'/e 73/,s 1'/B 1'/1s 1'/e 13/4 2'/1s 2.9 11/e 1'/e 1 Vs 11/e 13/4 15/e 13/4 1.73 - 11/2 'S/i 6 11/4 1'/2 2 1 7/8 2'/e 3.13 - '/2 11/1 s ' a 1'/e 15/16 1 1/4 1 9/16 1.2 7 1.3 2 2 1 9/1 s 17h s 19/1 s 21/4 2'/i s 21/4 3.71 3/4 7 3/16 '3/16 1 1/8 17/16 1% 1 5/8 1.3 6 - 21/2 1'/e 1 3/4 1 9/16 2 9/16 Z 3/8 27/16 4.5 4 11/8 1 1 15/16 'S/16 11/6 19A s 19/4 s 111A s 1.53 1.56 /z '3/1 1 3/1 s 1 7/i s 1 Yz 1 7/1 1'/e 2.3 4 2.38 11/e 1'/e 11/s 1 Ye 13/4 1"/i s 13/4 1.79 - 3/4 '/e '/a 1'/i s 19/i s 11/2 1'1/2 s 2.46 - 1 1/2 1 1/4 1 1/4 13/16 17/8 1 13/16 1,3/16 2.0 7 - 1 ++/16 1 1 2/1 s 1 3/4 1 5/B 2 2.6 6 2 1'/i s 17/1 s "As s 2'/i s 2 1'/B 2.66 - 11/2 11/s 13/1 s '3/1 s 17/18 1'/a 1'3/1 s 2'/i s 2.98 % i'/16 11/16 11/8 t 5/1 s 'S/16 1 9/16 1.4 7 - 1'/2 15/16 'S/is 11/2 2 1'S/is 2'/s 3.24 3/4 13/1s '3/16 1 Vs 17/1 s 1'/1 s 1% 1.5 7 - 2 19/1 6 1'/2 11/2 s 2'/4 21/8 21/4 3.7 11/2 1 '1/2 s 15/i 6 11/e 19/i 6 1 9/16 1 1 I/1 s 1.73 - 21/2 1'/a 1'S/i s 19/i s 29/1 s 29/i s 2'As 5.4 6 1 1/2 11/4 1 1/4 13/16 17/e 1 7/6 1'A 2.2 9 - +/2 '3/16 "A 1 7/16 1 1/2 11/2 17/9 2.7 4 2.81 2 17/16 13/4 6 "As s 21/16 23/4 s 17/6 2.81 3/4 '/e '/s 1'/i s 19/1 s 19/i s 1'5/1 s 2.6 6 - 1 "/,s 11/+s 17/16 13/4 13/4 2 3.05 3.14 2 1'/s t3/i6 13/is 171s 17/8 1'/e 21/is 3.38 - See additional sizes on following page. 1'/2 15/1s 5/16 1'/z 2 2 2'/B 3.59 3.74 Note:See last page for pressure-temperature ratings. 21/2 1'/e 17/8 19/is 29/is 29/16 2'/is 5.17 5.38 " 4 3 3 27/1 s 311/16 3"/i 6 31/2 16.0 7 - www.anvilintl.com (12/10/01) I Cast Iron Threaded Fittings (73r)/111%1%/1 : Class 125, (Standard) IMTERMAT1041AE Inn. Reducing Tee:Figure 359 Reducing Tee:Figure 359 Size(NPS) A B C D E F Wt.(Ws) Size(NPS) A B C D E F Wt•(ibs) 41111.1 s x t-x u (in) (in) (in) (in) (in) (in) black gaii, s x t x u (in) (in) (in) (in) (In) (in) black gaiv. 2J 19//6 1 11/16 17/a 27/1 s 21/a 29/16 5.29 - 1'/a 3 23/1 s 21/2 23/6 33/1 s 31/a 3% 12.54 - '/2 21/2 113/16 113/16 113/16 211/16 21/4 211/18 5.2 - 2.... 31/2 27/16 27/16 27/i a 3'/i 8 35/16 37/i s 1 2.9 3 3/4 2'/2 113/16 11/4 113/i 6 2"/16 21/4 2'1/1 s 5.1 - 21/2 115/16 1'5/16 23/a 2'/a 213/18 3/is 10.6 9 2 1 9/46 19/16 17/8 27/16 21/a 29/15 5.03 - 1 3 23/18 21/16 23/6 33/16 3 35/16 11.77 - 1 21/2 113/t 6 11/4 113/16 2''/16 25/16 -211/48 5.36 - 2/2 31/2 27/16 2 3/a 27/i s 37/16 35/16 3 7/i s 12.56 - 1 w 11/2 "As s 75/16 113/16 23/is 115/is 27/4 a 4.28 - 4 2"/i s 25/a 21/2 311/16 31116 31/2 15.27 - 1'/a 2 - 19/16 11/2 17/a 27/16 21/8 29/16 4.96 - - 11/2 13/a 13/a 27/16 23/6 25/16 31/is 8.33 - 21/2 1'3/46 13/4 113/16 2"/16 2 3/8 211/16 5.4 - 2 1 5/8 19/16 27/16 2 5/a 29/16 3 3/16 8.66 - 11/2 15/i 6 'S/16 113/i s 2 3/16 1 15/16 27/16 4.23 - ' 21/2 115/16 1'/a 2 3/8 2 7/a 213/16 3 5/16 1 0 - 11/2 2 T19/16 11/2 17/a 27/16 21/8 29/i6 4.85 - 3 - 3 23/16 21/8 23/a 33/i6 3'/a 33/6 11.33 - 21/2 113/16 1'3/i s 113/16 211/16 27/16 211/18 5.82 - 31/2 31/2 27/16 2 3/8 27/16 r 3 7/16 37/16 3 7/i s 1 3.9 5 - 1/2 3/4 'A 13/4 1"/i 6 11/2 r 23/18 3.57 - ' 4 ' 211/16 211/16 21/2 311/16 311/16 31/2 15.23 - 21/2 3/4 7/8 7/8 11/4 13/4 19/16 21/4 3.6 2 - 5 35/16 35/16 29/16 4 5/16 45/16 33/4 2 0.2 8 - 1 1 "/16 13/4 115/i 6 13/4 25/i s 3.92 - 1 "/i s 11/16 23/6 21/a 21/8 215/i s 8 - 2 11/a t3/18 13/16 13/4 21/1s 1'/a 23/a 4.26 - 11/a 11/4 11/4 23/a 21/4 21/4 3 8.63 11/2 15/46 '5/18 113/16 23/18 2 27/16 4.42 - 11/2 1 3/s 13/a 2 7/16 2 3/a 23/8 331/16 8.8 7 - 2 19/16 19/18 1'/8 27/16 2'/4 29/16 5.17 - 2 15/8 1% 2'/i8 25/8 25/s 33/is 9.94 - 1 21/2 113/18 1'/8 1'3/16 2'1/16 2 9/18 1 211/16 6 - 3/2 21/2 1 15/16 1'5/i s 2 3/8 2 7/a 2 7/8 35/16 10.95 - 1/2 3/4 r 3/4 13/4 1 11/16 1"/16 2 3/4 8 4 - 3 23/1 s 23/16 2 3/8 r 3 3/1 s 33/16 3% 12 - 3/4 7/6 7/0 13/4 11/4 13/4 21/4 4.29 - 4 2"/76 211/16 21/2 311/16 311/16 31/2 14.25 - 1 1 1 13/4 1 15/i s 115/16 2 5/i s 4.48 - 5 35/16 35/i s 29/16 45/16 45/16 31/4 1 9.6 6 - , 21/2 1'/a 13/i 8 13/16 1 3/4 21/16 ' 21/16 2 3/8 4.83 - 3/4 4 23/4 3 23/4 33/4 31/2 31/4 1 3.2 - 1 1/2 15/1 s 15/16 1 13/1 s 23/16 23/16 27/i s 5.1 4 - 1 4 23/4 2'5/16 23/4 33/4 31/2 31/4 13.52 - 2 19/18 19/16 17/a 27/16 27/16 29h6 5.88 6.02 11/8 4 23/4 27/8 23/4 33/4 31/2 33/4 14.35 - 4 23/4 213/16 27/16 311/i s 3"/16 31/2 14.03 - 11/2 4 23/4 27/8 23/4 33/4 31/2 33/4 13.47 Slit - 1/2 3 2'/a 21/4 21/a 31/a 211/16 31/a 7.6 - 2 1 11/16 17/a 23/4 211/16 29/16 31/2 11.34 - 3/4 3 21/a 21/8 21/a 31/2 2'1/16 3'/6 8.25 - 2 21/2 17/8 1'/8 25/8 2'5/i 5 2'3/18 39/16 11.6 - 1 3 21/a 21/s 21/a 31/a 211/i6 31/a 8.3 - 3 21/4 27/16 211/16 31/4 3'/8 35/a 13.44 - 1'/a 3 2'/8 21/8 21/a 31/6 213/1 s 3'/a - 8.46 - 4 , 23/4 23/4 23/4 33/4 31/2 33/4 13.19 - 11/2 21/2 17/8 1'/8 21/a 213/16 29/16 31/16 7.67 - 21/2 17/8 113/16 25/8 215/16 213/16 39/16 11.78 - 11/2 3 21/a 23/1s 2 1/2 31/a 2'3/i s 31/a 8.13 - 1 3 21/4 21/a 211/16 31/4 31/8 35/s 13.06 - 1 1/2 1 3/8 1'/2 2 3/i 6 2 5/i 6 23/16 2'3/16 6.8 3 - _ 2/2 4 2 3/4 23/s 23/4 33/4 35/a 3 3/4 15.75 - 2 19/16 19/18, 23/18 29/16 21/4 215/48 7.29 - 5 33/a 31/2 273/16 43/a 43/8 4 22.37 - 2 1 7/a 1 1 7 1 1 15 5 521/4 5 2/2 1 15/16 2/8 23/16 9 2/1 s 3/1 s 7.1 - 1/e /16 15/i 6 /e 2 2/16 3/i 6 9.7 - 3 21/a 23/16 21/a 31/8 215/16 31/8 8.79 - .. 11/2 17/16 17/16 211/16 27/16 23/8 35/i 6 1 0.2 - 1 1 15/is 21/8 21/is 115/16 211/is 5.51 - 3 2 111/ia 19/16 23/4 211/16 23/46 31/2 10.21 10.67 1 1/8 11/4 13/16 21/8 23/16 21/16 23/4 5.92 - 21/2 17/8 1'/8 25/8 215/16 213/16 39/i6 11.25 -J 11/2 13/a '5/is 23/t 5 25/16 23/16 213/i s 6.23 6.33 4 3 21/4 21/8 2"/i 6 31/4 31/a 3 5/8 12.5 - 3 21/22 19/7 s 11/2 23/i a 29/18 27/i s 215/15 6.81 - 4 23/4 2 11/16 23/4 33/4 35/a 33/4 15.04 - 21/2 17/8 113/16 21/a 213/16 211/16 31/I s 7.66 - 11/2 1 7/16 1 3/8 2 11/16 27/16 23/8 33/4 6 10.0 9 - 3 21/a 21/8 21/a 31/a 31/16 31/8 9.13 - 2 11/16 15/a 23/4 211/16 25/8 31/2 10.9 - 1/2 15/16 15/18 23/i 8 17/8 17/a 25/a 6.08 6.17 21/2 2 115/16 25/8 3 27/a 39/i s 11.84 - 3/4 15/16 15/16 21/8 17/a 17/8 25/a 6.06 6.17 31/2 3 21/4 23/16 211/i6 31/4 31/4 35/a 14.63 - 1 1 1 21/8 23/46 21/16 211/18 6.27 6.54 31/2 21/2 27/1s 211/16 31/2 37/16 311/16 14.38 - 1 1/a 11/4 11/4 21/a 23/1 s 23/1 s 23/4 6.75 - 4 23/4 2"/76 23/4 33/4 33/4 33/4 17.23 - 11/2 13/a 13/a 23/i s 25/1 s 25/i s 215/16 7.1 7.27 5 33/a 35/16 213/i 6 43/a 43/a 4 2 0.57 - 3 2 19/16 19/16 23/16 2 9/18 29/16 27/8 7.75 7.83 r 3/4 11/4 11/4 2'3/16 25/16 25/16 3 5/16 10.58 - 21/2 17/a 17/8 21/8 213/i s 213/1 s 31/i s 8.92 8.96 1 13/16 13/16 23/4 25/i s 25/16 35/16 10.4 10.81 31/2 23/13 2 3/8 23/18 3% 33/8 3 3/i s 11.1 - 1 1/8 15/16 15/16 25/8 25/16 25/16 35/16 10.38 10.54 4 211/16 211/is 27/18 311/16 311/16 31/2 12.8 - 11/2 17/16 17/18 2"/16 27/16 27/18 35/16 10.75 11.18 5 33/6 35/16 29/16 45/16 45/16 33/4 2 0.25 - 4 2 111/16 111/1 s 23/4 211/16 211/16 31/2 11.63 11.73 21/2 2 2 25/a 215/16 215/16 39/16 12.85 12.96 See additional sizes on previous and following page. 3 21/4 21/4 211/16 31/4 31/4 35/a 14.12 14.69 5 3% 33/a 213/16 43/6 43/a 4 '20.88 - Note:See last page for pressure-temperature ratings. _� T 15 '5 1 -`-636 - 6 f 3/e 37/e 2/a 4 /is 4 /is 4 hs 2 - www.anvilintl.com 112/10/01) I Cast Iron Threaded Fittings Class 125, (Standard) � ,_ �T� ,L. Reducing Tee:Figure 359 '""" Size(NPS) A B C D E F Wt.(Ibs) s x t x u (in) (in) (in) (in) (in) (in) black galv. 2 5 35/16 39//6 35/16 41/2 41/4 4'/2 22.41 - 21/2 5 35/16 33/8 35/16 41/2 41/4 41/2 22.12 - 3 4 23/16 23/16 3% 4 31/44% 23.53 - 6 3'3/16 41/16 3% 5 5 45/8 31.13 - 3 25/16 21/2 31/4 31/2 3'/2 41/4 23.22 - 31/2 4 213/16 2"/6 33/s 4 33/4 43/8 22.76 - 6 313/,6 4 33/e 5 5 45/8 29.26 - 21/2 21/16 2 33/16 33/16 33/16 41/4 21.81 - 3 26/16 21/4 6 31/4 31/2 31/2 41/4 24.05 - 5 4 4 2'3/16 23/4 3 3/e 4 3 3/4 43/e 2 0.5 8 - 5 35/16 33/8 35/16 41/2 43/e 41/2 26.33 - 6 313/16 37/8 33/8 5 5 46/e 33.51 - 1 1/2 1 9/16 1 9/16 35/16 211/16 211/16 4 16.21 - 2 13/4 13/4 37/6 215/16 275/16 41/8 17.43 - 2'/2 2 Y,s 21/16 33/e 33/16 33/16 41/4 18.84 - 5 3 26/1 s 2/,6 31/4 31/2 31/2 41/4 20 - 4 213/16 213/16 33/6 4 4 43/s 23.83 - 6 31 3/i s 313/16 3 3/8 5 5 45/s 32.91 - 8 53/16 53/16 43/16 63/8 63/8 59/,6 67.92 - 11/2 6 37/8 41/16 37/8 51/e 4 1/16 51/e 34.67 - 2 6 37/8 4 37/s 51/e 411/16 51/8 35.21 - 21/2 6 37/8 3'3/16 37/8 51/8 4 11/16 51/6 3 4.57 - 3 4 213/16 3 37/8 41/16 4 415/16 32.25 - 31/2 6 37/8 37/8 3 7/8 51/8 4'5/16 51/8 3 5.31 - .<0 3 25/16 21/2 37/s 39/16 39/16 413/16 31.75 - 4 4 27/8 2'5/16 3 7/8 41/16 4 4 15/1 6 3 0 - 6 37/8 37/8 3 7/8 51/8 4'5/16 51/8 3 4.2 2 - 11/2 15/8 19/i 6 37/8 23/4 23/4 41/2 2 5.81 - 6 5 31/2 25/8 29/16 313/16 37/8 33/4 47/e 30.34 - 6 37/8 315/16 37/8 51/8 5'/8 51/8 43.31 - 8 51/8 53/16 4 3/16 6 3/6 6 3/8 59/16 6 5.7 9 - 1 1/8 1 3/8 1 3/8 313/16 2 5/8 2 5/8 4 7/16 2 2.3 6 - 2 1 13/16 1 t 3/16 3 7/8 3 3 46/s 2 4.65 - 21/2 2 2 313/16 31/4 31/4 43/4 25.6 7 27 6 3 23/8 23/8 3t3/16 39/16 39/16 413/16 27.46 28.56 4 2% 27/8 37/8 41/16 41/16 415/16 32.44 33.74 5 3% 33/e 373/16 45/8 46/8 5 37 - 8 51/8 51/8 43/16 63/e 63/8 59/16 58.05 - 2 8 53/16 57/e 53/16 69/16 69/16 69/16 64 - 4 8 53/16 51/2 53/16 69/16 69/16 69/16 67 - 5 5 4 3/1 6 43/8 5 3/1 6 59/16 59/16 63/8 77.58 - 5 43/16 45/16 5 3/16 59/16 59/16 63/8 76.6 - 6 6 43/16 45/16 51/8 59/16 59/16 63/8 73.72 - 8 53/16 5'/8 5 3/1 6 69/,6 69/16 69/16 91.5 - 8 2 21/16 21/16 51/8 3 7/16 3 7/16 5'/8 44.4 9 - 21/2 25/16 25/,6 51/16 311/16 311/16 6 45.23 - 3 31/8 31/e 51/e 41/2 41/2 61/8 54.97 - 8 31/2 3'/8 31/8 51/8 41/2 41/2 6'/s 54.21 - 4 31/8 31/8 51/8 41/2 41/2 6'/8 5 3.6 2 - 5 43/16 43/16 53/18 55/16 59/16 63/8 67.81 - 6 43/16 43/16 51/8 59/16 59/16 63/e 66.22 - 4.1800, See additional sizes on previous page. www.anvilinacorn (12/10/01) I Cast Iron Threaded Fittings (wir" TM Class 125, (Standard) Ii INTERNATIONAL, INC. Cast Iron Threaded Fittings Pressure-Temperature Ratings Pressure,(psig) Temp.(°F) Class 125 Class 250 -20° to 150° 175 400 200° 165 370 250° 150 340 300° 140 310 350° 125 300 400° -- 250 vio www.anvilintl.com (12/10/01) Cast Iron Threaded Fittings (rifflP)AWIL !'y5� a .CiasS 12�J� (Standard] INTERNATIONAL, INC. 90° Reducing Size A B C D Weight Il"" Elbow-Figure 352 (NPS) (in) (in) (in) (in) (Ibs)- black 1/2 1/25/8 3/4 11/16 11/26 40 T____ 1/2 3/8 5/8 11/16 1 1/16 1 1/16 .34 3/4 1/2 11/16 13/16 1 3/4 6 11/4 .51 1 1/2 11/16 15/16 11/4 13/8 .67 1 3/4 '3/16 15/16 13/8 17/16 .76 11/4 1/2 '1/16 11/16 15/16 11/2 1.07 11/4 3/4 13/16 11/8 1 7/16 1 5/8 1.02 11/4 1 15/1 6 11/6 19/16 1'1/16 1.21 11/2 1/2 3/4 11/4 13/8 15/4 1.53 11/2 3/4 7/8 15/16 11/2 1'3/i s 1.55 11/2 1 1 11/4 15/8 1'3/16 1.44 11/2 11/4 13/4 6 11/4 113/16 17/8 1.7 4 2 1/2 13/16 17/16 11/2 1 3/8 2.22 2 3/4 15/46 11/2 15/e 2 2.20 �i„'i, 2 1 1'/16 17/46 13/4 2 2.08 it 2 11/4 13/4 6 17/16 17/8 21/16 2.33 4"'' ;; 2 11/2 15/16 11/2 2 21/8 2.59 21/2 2 1/is 1' 27/46 29/16 4.01 ':-..--B-..-i I 21/2 1 13 11/411 S/i s 25/16 2.93 21/2 11/4 13/18 13/4 2 Y76 23/8 3.41 .4_4__ _ 21/2 11/2 15/16 113/16 23/16 22/16 3.68 C A 3 11/4 1 5/8 25/16 29/16 215/16 5.98 _Li ------ - """' - 3 11/2 15/e 25/16 29/16 275/16 5.65 3 „2 1% 21/4 29/46 275/16 5.65 3 21/2 12/e 23/16 2 t 3/i s 31/16 6.44 31/2 3 23/16 27/16 33/16 33/8 8.95 4 2 23/46 275/16 31/4 35/8 11.89 4 21/2 23/16 23/4 31/4 35/6 11.27 4 3 23/16 211/16 31/4 35/8 10.63 4 31/2 22/16 21 1/46 31/2 311/46 11.8 9 5 4 213/4 6 35/4 6 4 43/6 16.47 5 2'/2 2 13/1 6 31/2 4 43/s 19.88 5 3 213/16 37/16 4 43/8 19.00 6 3 25/16 313/16 39/46 413/16 19.43 6 4 2'3/16 37/a 41/16 415/16 23.53 6 5 33/4 313/16 45/8 5 26.66 8 6 43/16 5% 59/46 63/8 51.11 Cast Iron Threaded Fittings Pressure-Temperature Ratings Pressure,(psig) Temp.(°F) Class 125 Class 250 -20° to 150° 175 400 200° 165 370 250° 150 340 300° 140 310 350° 125 300 400° -- 250 www.anvilintl.com (12/10/01) I SECTION 2 Hangers & Sway Bracing 300 Universal Beam Clamp — 3000037PL A NIOr TQ �,to ys . • .. , F-RS IFI IF2 • Conforms with Federal Specification WW-H-171 (Type 23), Manufacturers Standardization Society ANSI®/MSS-SP-58(Type 19 and 23) C CIO US 44> APPROVED Part Number 3000037P1 Material Steel Finish Plain Rod Size(RS) 3/8" Flange Thickness(FT) 13/16"Max A 1 1/8" Torque(TO) 5 ft lb Static Load 1.(F1) 500 lb Static Load 2(F2) 250 lb Standard Packaging Quantity 100 pc UPC 78285634900 UNSPSC 31162905 EAN-13 8711893090741 Certifications cULus FM Setscrew must be tightened and torqued onto the sloped side of the I-beam. Recognizing that torque wrenches are generally not used or available on many job sites,the setscrew should be tightened so it contacts the I-beam and then an additional 1/4 to 1/2 turn added. ANSI is a registered trademark of American National Standards Institute.FM is a registered certification mark of FM Approvals LLC,LTD.UL,UR,cUL,cUR,cULus and cURus are registered certification marks of UL LLC. WARNING ERICO products shall be installed and used only as indicated in ERICO's product instruction sheets and training materials.Instruction sheets are available at www.erico.com and from your ERICO customer service representative.Improper installation,misuse,misapplication or other failure to completely follow ERICO's instructions and warnings may cause product malfunction, property damage,serious bodily injury and death. Copyright©2015 ERICO International Corporation.All rights reserved. CADDY,CADWELD,CRITEC,ERICO,ERIFLEX,ERITECH,and LENTON are registered trademarks of ERICO International Corporation. GEED ERICD • All Thread Rod ..r.1 g #a".,°< �:x.: a�'�.�#4`a''$X':�,;jrtt4 k M-fs4rir ff'.�. 0 ,af .ti% .y� ' �+t�.�'� �.,,""?^ �T;"+° ,'s,,.:d. 'a1it r�k'�:>a..uy ^ S':�i�d7�' '�, �`" �•.i�u �a'a: 'k t' .G.s.�'' `i�r`'nr>-'6'+at rP. . ..�� CIS e �' � u �t � � y✓� h�t ..r.a.,�:�,. �,¢ �, �r" ... _. ,� r .".:.'�.'` .. .... Ferguson Alt 1 Size(in.x It) Black Galv SS 304 SS 316 1/2X10 BATRD10 GATRD10 1/2X12 BATRD12 GATRD12 SS4ATRD12 SS6ATRD12 1/2X6 BATRDU GATRDU SS4ATRDU SS6ATRDU 1/4X10 GATRB10 1/4X12 BATRB12 1/4X6 BATRBU GATRBU SS4ATRBU 1X10 GATRG10 All Thread Rod meets following specifications: 1X12 GATRG12 SS4ATRG12 ASTM A307 Domestic and Import All Thread Rod 1X6 BATRGU GATRGU SS4ATRGU 3/4X10 BATRF10 GATRF10 ASTM A36 Domestic All Thread Rod only 3/4X12 BATRF12 GATRF12 SS4ATRF12 SS6ATRF12 ATSM B 633 Domestic and Import Clear 3/4X6 BATRFU GATRFU SS4ATRFU Zinc Plated/Yellow Zinc Plated 3/8X10 BATRC10 GATRC10 SS4ATRC10 ASTM A 153 Domestic and Import Hot 144s. Dipped Galvanized 3/8X12 BATRC12 GATRC12 SS4ATRC12 ASTM A193-08B Import Stainless Steel T-304 3/8X12 SS6ATRC12 3/8X3 GATRCM ASTM Al 93-B8 Domestic Stainless Steel T-304 3/8X6 BATRCU GATRCU SS4ATRCU ASTM A193 B8M Domestic Stainless Steel T-316 3/8X6 SS6ATRCU 5/8X10 BATRE10 GATRE10 5/8X12 BATRE12 GATRE12 SS4ATRE12 5/8X3 SS4ATREM 5/8X6 BATREU GATREU SS4ATREU 7/8X10 BATR7810 GATR7810 7/8X12 BATR7812 GATR7812 SS4ATR7812 SS6ATR7812 7/8X3 SS4ATR78M 7/8X6 BATR78U GATR78U SS4ATR78U Distributed Exclusively by Ferguson and Wolseley Canada ©2014 Ferguson Enterprises,Inc. All Rights Reserved 20348 04/14 115 Standard Duty Loop Hanger ) 1 The 115 Standard Duty Loop Hanger is ideal for suspending stationary, non-insulated pipe lines, including CPVC pipes, in fire sprinkler systems.A knurled insert nut helps simplify vertical adjustments and flared edges on the base (1/2-to 4"sizes) help protect pipes from coming into contact with any sharp edges of the hanger. • Flared edges help prevent any sharp surfaces from coming into contact with the pipe (1/2"to 4" sizes) • Retained insert nut helps ensure the loop hanger and insert nut stay together • Recommended for the suspension of stationary non-insulated pipe lines • Manufactured to use the minimum rod size permitted by NFPA'for fire sprinkler piping • Conforms with Federal Specification WW-H-171 (Type 10), Manufacturers Standardization Society(MSS)SP-58 (Type 10) f-RS B A Material: Steel (21Finish: Pregalvanized C US APPMOVED Outer Diameter Rod Size Static Load Part Number Pipe Size OD RS A B C F Certifications 1150050EG 1/2" 0.840" 3/8" 2 13/16" 1 1/8" 1" 300 lb cULus ' 1150075EG 3/4" 1.050" 3/8" 3" 1 3/16" 15/16" 300 tb cULus,FM 1150100EG 1" 1.315" 3/8" 3 1/4" 1 3/8" 15/16" 300 lb cULus,FM 1150125EG 1 1/4" 1.660" 3/8" 3 9/16" 1 1/2" 15/16" 300 lb cULus,FM 1150150EG 1 1/2" 1.900" 3/8" 3 13/16" 1 5/8" 15/16" 300 lb cULus,FM 1150200EG 2" 2.375" 3/8" 4 1/4" 1 7/8" 15/16" 300 lb cULus,FM 1150250EG 2 1/2" 2.875" 3/8" 5 9/16" 2 13/16" 1 9/16" 525 lb cULus,FM 1150300EG 3" 3.500" 3/8" 6 9/16" 3 1/2" 1 15/16" 525 lb cULus,FM 1150350EG 3 1/2" 4.000" 3/8" 7 1/16" 3 3/4" 1 15/16" 585 lb cULus,FM 1150400EG 4" 4.500" 3/8" 7 9/16" 4" 1 15/16" 650 lb cULus,FM 1150500EG 5" 5.563" 1/2" 9 13/16" 43/4" 2 1/4" 1,000 lb cULus,FM 1150600EG 6" 6.625" 1/2" 11 5/16" 6 5/16" 3 5/16" 1,000 lb cULus,FM 1150800EG 8" 8.625" 1/2" 12 7/8" 6 7/8" 2 7/8" 1,000 tb cULus,FM 'thaw CADDY PENTAIR • FM is a registered certification mark of FM Approvals LLC,LTD.NFPA is a registered trademark of National Fire Protection Association,Inc.UL,UR,cUL,cUR,cULus and cURus are registered certification marks of UL LLC. WARNING Pentair products shall be installed and used only as indicated in Pentair's product instruction sheets and training materials.Instruction sheets are available at erico.pentair.com and from your Pentair customer service representative.Improper installation,misuse,misapplication or other failure to completely follow Pentair's instructions and warnings may cause product malfunction,property damage,serious bodily injury and death and/or void your warranty. ®2017 Pentair All rights reserved .40140 Pentair,CADDY,CADWELD,CRITEC,ERICO,ERIFLEX,ERITECH and LENTON are owned by Pentair or its global affiliates. All other trademarks are the property of their respective owners.Pentair reserves the right to change specifications without prior notice. ‘!1 GIDDY f PENTAIR Untversal Structural Attachment . , Nittow nu,. 4 ' i ' lit ., . . ...,„ ,,' 4. Univeraat dasigri 0 titi)**$it:Ine piredixr td a Ilea directly ro carac rate„*add,bar idiot ar I.bea rrt; * Snap-eff ball heal helps.aaatta 4,Nsy irks tallatiart and*patriot)i)f Setarrtic sway braces. . , ..,, • tOSe fipr bath lair teal mild tariciligarkal Soaky arace.appriCatioAS 4 WarkS With 1+Itirpagri 1'brace pipes arod '1/4'artale Iran bras No earruct awenIcary / Cetaer boll diots 114;4 ragvira lig bra ni n9 4 Metils 14P1PA40.0 3 taalairamola for aeisrtat sway tifkiCal ill! — ,...t . --.. ... .. . C _y OS 4111 ,V Malarial:Steel I) VI CISFIPD Finish; Ei atiragaltra mired C VSIN,If,Ir0,50Eri Htd •.csaLlil ' °l.'s"' 1 5 IA- I-- tit .. ., 8,-.4o*r'yper $.0vesoir F'q.t.4.litt,t4 r**t.41,11 . ....... ..... __„ . . _ . .. ... . _ .... , listoo,;n1.0tC:*Ir 14'011 lent sil4olan,10,40,0 ii-MIS' t1/1-41 , . . j j RI 4 4.r*011iV*4 tVt*P*4-110m et****•Of I'M apptawia.LIC,LID IttEth*to tolittwoitottt Ototoutok 44 moo*No Protitotoo Atoottotou,,ek° 01,Attt,4‘,-...Ott et.tt.us*to ctioqi tio If*gtowattd?ottlitt.504.040.1 motto of tit,14C *ARNO% Poot 14 orattoritt itt411 to 044144 VAI 4***#'04 4*inifit41114 01 IN40140.6 PrOdkilt Ailtrae NA 0444***4 4,10**41‘0401W4111 ittitatehlet 11404 to*dt******tit'WO tuttutiw ttou*4.1 **It root P*AriWir*0410froit 414RNIEli l'VI4NOLOntAltkV)*WOW ir4tAiStiMDO,P100400,M4,0,4*1 MAN*al'41101 itRik01`44 1.0 tzottivAttt oy kat..0**1.40-4„i 1141141,K*444*rig shOrY111114 114,44li 0 1444trAleellitil,114114 WV 4,91rti*.serituo*N.Hil!$irl loty left rittoOt***Co void oto*moo*" ett MI'Nuttor Mt 1441 ettovotki kiloetott**4,COO"i**,atr,b.call c,.,Outr1,1,tR Itt II*CM MC*deli ZAN WIN out'wood Ott Prolott to lu otatiot allttop04 ' Aft ottet okttem.sto,401 tt,,,prtl,f,tr.1,ht r ttproteftw,awort FtE,,Mao o"..***00*If*e rlitAllektOgIr,rlegketifirAl WiliWit pri,;11--.• '0 ,t41: 'It> PENTAIR in D Ouick Grip Lateral Sway Brace �'_ .. , The Quick'Grip t.ia1Cerai ?race.part of the CAO 1Y line oI tire*pririkier bracing e;r$te'i trarr,Pentair,is designed to help slrr pliCy iny,t ltleltiOn-%%ten Idracily$ervice pipe tor SetSittio<or oter attest rephic everts..It lee tr ires So innovative de sitgr,tsar quick eitichelee't Of brace pipe to service pipe savin9 time and'+r'lcs y + Easy i. i .step east H3tieri etroinales extra trips between sir"ect+jre and 9rat nice PiPl + 1 rrki,will 1"and 1 tI4"125 miser ent1 32 moil larece pipes to reduce inveAtalry of Yellow tips Provide a visual iralmator that the bolts have"been property torqued • Easy ihslaltsbon With en irrlparct wench trorr,the bottom side<A the r;i rrsp # Meets t4r r0'13 req4iferrierit15,for WIMP<vital braci l A__ 4 Material, C g'i /i15 .H P a. Finish;Etectrogatranllied '0:4,,.'.4 'I' ,r j: 4 I,44' 4,,,— 71,14- - I ,ry` I t petr Ca rY':. it , + !a 1,L'16-:. 137 Dp!#-0lu wlp ,UPS OP Pacts it r.°1a " ' , ID ',Cr15 Ib 1.el.,it ie Mp r_________ 7,d15 it: 3!,111�1t 'ta't�i >`aVcti .�3rr!pi �i i t,. ACV IWO- !r .:i',,E 'i!S'}I not 11= 4t Miltt1i 1,p1riill L'101,1 ti0 .plait ix,ttttitiw. ,..�, i sir , �'.p15 to ......, i:g 1 C =x ,tt. •PEP4TAIR Cs'{1.7f.,. :' UL loads l; Peet Number Service Pipe Schedule Lateral 1"Brace Pipe 1 1/4'Brace Pipe Mega-Flow 2,015 lb 2.015 lb f CS8QGG0600EG 10 2,0151b 2,0151b 40 2,015 lb 2.015 lb C`0060800EG 10 2,(]15 It 2,01S lb 40 2,015 lb 2.015 lb FM Loads 1 Lateral Part Number Service Pipe Schedule Horizontal Capacity per Installation Angle Pram Vertical 30°-44' 45'-59' 60'-74' 75'-90' Lighl'wafi 1,410 to 2,000 lb 2,450 lb 2,740 lb CSF,3QG0250EG 10 1,410 lb 2,000 lb 2,450 lb 2,740 lb 1 40 1,410 tb 2.000 lb 2,450 lb 2,740 Lb LrghtweLl 1,190 lb 1,620 lb 2,060 lb 2,300 lb - i CSBUG17300E0 10 1,190 lb 1,620 lb 2,060 lb 2,300 lb 40 1,190 lb 1,680 lb 2,060 lb 2,300 lb Lghrv;d!l 1,190 lb 1,690 lb 2,060 lb 2,30 tb CSBUGUo0UES '0 1,190 lb 1,680 lb 2,060 lb 2,300 lb 40 1,190 lb 1,620 tb 2,060 lb 2,3'30 lb Lightwell 870 lb 1,230 lb 1,510 lb 1,690 lb CSBQQGLJ600EG 10 870lb 1,230 tb 1.510 1b 1,690 lb 40 970 lb 1,370 lb 1,680 lb 1,270 lb - 0,188"Malt Thickness) 790 to 1,110 lb 1,360 lb 1,520 lb C586)00400E0 _ 40 790 lb 1,110 lb 1,360 lb 1,520 lb Vert•7"',14*4 it r4,ldtgr et trei144104. t t .;;id 14 it .:044.04 6*it-eebi,eW flri i;9:9i a +4tiees4 4101120140640 rat,01 I'M 44.000Ai L ,tl.'l*;i NITA s r frlt aire1d 1r.14#0 4rit 04 Idaitt-tl pint prtattgclranA ct4iion.lee ui,Lift ci1,,:r.Lii',c1-11.30, ditift0,atre*gr edaerelttiraloaaarrOr,wl I.Ll i t ttaot t*`oitu l 1h48 b*or4lle e16 I'd irto49444414Tirgatrid 41E44010#pre4eTt,e fe extort 4 lee±t irsei Ttpirrei r tr «)tit rid*T.ttrt,oe'€tWts'tt et#v #1 s lit it ft#0,.pdr44MP rpm,opi4i 3 pee' O Pill040 tilt4Offitdr csAirs4OR rrrprle eth4e *wow rr irr4riviTetIee treUlMrt,rtnae';wt;tira atat fort lrtr*taelwrer to To,'trver* UN*l,etdet'w+ree tom ToTTATitor 0210 Mit CAtligat 04404 a b14I*ele n It 4 0 e ttte l ieu Vt."ket4re.IeMetg lte e l' art!de**tioirtoT w®t1 polo*Tor**, V pill'rtAiritikie ATP hiltrrf erT or 1 iiiiPar'tt44,+ ,';Wit;Lt1,.CBt1' tth3 41,t#1tt LEJI<EMI trC!s AO E hill+#`a ornsd tat°P141Att O'1.41 4 alhll44ei ' .TI rather rrotileolervi,oa 1t'd ort=titTr -,-riiir*r rle ?to. *rrtivil tao+044.010 titp rblimy watanUtt) To' ' G* PEl�tll�J! IR SECTION 3 Valves and Accessories FireLock® Buterfly Valve jctatulid Style 705 with Weatherproof Actuator 10.81 Material Specifications: Body: Ductile iron conforming to ASTM A-536, grade >' 65-45-12 End Face, 2 —6750— 150 mm: Ductile iron conforming to ASTM A-536, grade 65-45-12 Seal Retainer, 8— 127200—300 mm: Ductile iron conforming to ASTM A-536, grade 65-45-12 Approvals/Listings: Coating: Black alkyd enamel cam0 vds LPCB Disc: Ductile iron conforming to ASTM A-536, grade#G410001 104j/04 65-45-12, with electroless nickel coating conforming to See Victaulic Publication 10.01 for more details. ASTM B-733 Product Description: — Seat: — ---��— ❑ Grade "E" EPDM The Series 705 Butterfly Valve features a weatherproof actuator housing Approved for indoor or outdoor use, a Stems: 416 stainless steel conforming to ASTM A-582 ductile iron body and disc with EPDM seats. Designed for fire protection services only.Victaulic FireLock Stem Seal Cartridge: C36000 brass Series 705 Butterfly Valve is cULus Listed, LPCB Listed, FM and VdS Approved for 300 psi/2068 kPa service. Bearings: Stainless Steel with TFE lining Contact Victaulic for details of agency approvals. Stem Seals: EPDM Stem Retaining Ring: Carbon steel Actuator: ❑ 2—8750—200mm: Brass or bronze traveling nut on a steel lead screw, in a ductile iron housing ❑ 10— 127250—300mm: Steel worm and cast iron quadrant gear, in a cast iron housing Job/Owner Engineer System No. —- Spec Section Location Paragraph Contractor Approved Submitted By Date Date - ---- ----- -_--__------------ --_—____— __—.. victaulic.com I Butterfly Valve I Series 705 I Publication 10.81 10.81 5662 Rev F Updated 11/2014 ®2014 Victaulic Company.All rights reserved. 1 ,ctaUIic" victaulic.com I Butterfly Valve I Series 705 I Publication 10.81 Approvals and Listings: Approval/Listing Service Pressures Series 705 Butterfly Valve Size cULus FM Vds LPCB 2"/50 mm up to 300psi/2068kPa n/a up to 300psi/2068kPa up to 300psi/2068kPa 21/2"/65 mm up to 300psi/2068kPa up to 300psi/2068kPa n/a up to 300psi/2068kPa 76.1 mm up to 300psi/2068kPa up to 300psV2068kPa up to 300psi/2068kPa up to 300psi/2068kPa 3"/80 mm up to 300psi/2068kPa up to 300psi/2068kPa up to 300psi/2068kPa up to 300psi/2068kPa 4"/100 mm up to 300psi/2068kPa up to 300psi/2068kPa up to 300psi/2068kPa up to 300psi/2068kPa 5"/125 mm up to 300psi/2068kPa up to 300psi/2068kPa n/a up to 300psi/2068kPa 139.7 mm up to 300psi/2068kPa up to 300psi/2068kPa up to 300psi/2068kPa up to 300psi/2068kPa 6'/150mm up to 300psi/2068kPa up to 300psi/2068kPa up to 300psi/2068kPa up to 300psi/2068kPa 165.1 mm up to 300psi/2068kPa up to 300psi/2068kPa n/a up to 300psi/2068kPa 8"/200mm up to 300psi/2068kPa up to 300psi/2068kPa up to 300psi/2068kPa up to 300psi/2068kPa 10"/250 mm up to 300psi/2068kPa up to 300psi/2068kPa n/a up to 300psi/2068kPa 12"/300 mm up to 300psi/2068kPa up to 300psi/2068kPa n/a up to 300psi/2068kPa 44 NYWd 10.81 5662 Rev F Updated 11/2014 0 2014 Victaulic Company.All rights reserved. victaulic.com 2 ✓ctaulic victaulic.com I Butterfly Valve I Series 705 I Publication 10.81 Dimensions: • ha Flllll�Cji A___ ,e �; y G E-.. . A i.-D NOTE:OPTIONAL 1/2715MM TAP AVAILABLE. CONTACT VICTAULIC FOR DETAILS. Actual Dimensions Nominal Outside E to E Size Diameter A B C D E F G DIA H J inches inches inches inches inches inches inches inches inches inches inches mm mm mm mm mm mm mm mm mm mm mm 2 2.375 4.25 2.28 6.41 - 4.00 4.22 4.50 2.12 - 60.3 60.3 108.0 57.9 162.8 101.6 107.2 114.3 53.8 2�/: 2.875 3.77 2.28 7.54 - _ 4.00 4.22 4.50 1.77 73 73.0 95.8 57.9 191.5 101.6 107.2 114.3 45.0 76.1 mm 3.000 3.77 2.28 7.54 - _ 4.00 4.22 4.50 1.77 76.1 95.8 57.9 191.5 101.6 107.2 114.3 45.0 3 3.500 3.77 2.53 7.79 _ _ 4.50 4.22 4.50 1.77 88.9 88.9 95.8 64.3 197.9 114.3 107.2 114.3 45.0 4.250 4.63 2.88 8.81 _ - 5.50 4.22 4.50 2.20 108 mm ' 108.0 117.6 73.2 223.8 139.7 107.2 114.3 55.9 4 4.500 4.63 2.88 8.81 _ _ 5.50 4.22 4.50 2.20 114.3 114.3 117.6 73.2 223.8 139.7 107.2 114.3 55.9 5.250 5.88 3.35 10.88 _ _ 6.56 6.19 6.30 2.58 133 mm 133.0 149.4 85.1 276.4 166.6 157.2 160.0 65.5 139.7 mm 5.500 5.88 3.35 10.88 - 6.56 6.19 6.30 2.58 139.7 149.4 85.1 276.4 166.6 157.2 160.0 65.6 5 5.563 5.88 3.35 10.88 _ _ 6.56 6.19 6.30 2.58 141.3 141.3 149.4 85.1 276.4 166.6 157.2 160.0 65.5 159mm 6.250 5.88 3.84 11.38 - 0.41 7.52 6.19 6.30 2.58 159.0 149.4 97.5 289.1 10.4 191.0 157.2 160.0 65.5 165.1mm 6.500 5.88 3.84 11.38 - 0.41 7.52 6.19 6.30 2.58 165.1 149.4 97.5 289.1 10.4 191.0 157.2 160.0 65.5 6 6.625 5.88 3.84 11.38 - 0.41 7.52 6.19 6.30 1.90 168.3 168.3 149.4 97.5 289.1 10.4 191.0 157.2 160.0 48.3 8 8.625 5.33 5.07 13.53 0.80 1.47 10.00 6.19 8.10 2.33 219.1 219.1 135.4 128.8 343.6 20.3 37.3 254.0 157.2 205.7 _ 59.2 10 10.750 6.40 6.37 15.64 1.41 1.81 12.25 8.10 9.00 _ 273 273.0 162.6 161.8 397.3 35.8 46.0 311.2 205.7 228.6 12 12.750 6.50 7.36 16.64 2.30 2.80 14.25 8.10 9.00 - 323.9 323.9 165.1 186.9 422.7 58.4 71.1 362.0 205.7 228.6 10.81 5662 Rev F Updated 11/2014 ®2014 Victaulic Company.All rights reserved. victaulic.com 3 Jctaulic victaulic.com I Butterfly Valve I Series 705 I Publication 10.81 Performance: The chart expresses the frictional resistance of Victaulic Series 705 Butterfly Valve in equivalent feet/ meters of straight pipe. Nominal Outside Equivalent Size Diameter mm mm Feet/m inches _ inches of pipe 2 2.375 6 50 60.3 1.8 2'h 2.875 6 65 73.0 1.8 76.1 mm 3.000 6 76.1 1.8 3 3.500 7 80 88.9 2.1 4 4.500 8 100 114.3 2.4 108 mm 108 mm 8 2.4 5 5.563 12 125 141.3 3.7 133mm 133mm 12 3.7 139.7 mm 5.500 12 139.7 3.7 6 6.625 14 150 168.3 4.2 159 mm 159 mm 14 4.3 165.1 mm 6.500 14 165.1 4.2 8 2 16 200 219.1 4.9 10 10.750 18 250 273.0 5.5 12 12.750 19 300 323.9 5.8 10.81 5662 Rev F Updated 11/2014 ®2014 Victaulic Company.All rights reserved. victaulic.com 4 ictaulib' victauiic.com I Butterfly Valve I Series 705 I Publication 10.81 Performance: Cv values for flow of water at+60°F/+16°C through a fully open valve are shown in the table below. For additional ' details, contact Victaulic. Formulas for C„values Formulas for IS,values AP=Q2/C 2 Where: AP=Q2/Kv2 Where: v Q=Cv x SAP Flow Coefficient C„ Q_Kv x JAP Flow Factor I(, Q(Flow) GPM Q(Flow) m'/hr AP(Pressure Drop) psi AP(Pressure) bar Valve Size Full Open Valve Size Full Open Actual Actual Nominal Outside Nominal Outside Size Diameter Flow Coefficient Size Diameter Flow Coefficient inches inches Cv inches inches IS mm mm mm mm 2 2.375 2 2.375 50 60.3 170 50 60.3 147 2 Y 2.875 2' 2.875 65 73.0 260 65 73.0 225 3.076.1 mm 7610 260 76.1 mm 3.000 5 225 3 3.500 3 3.500 80 88.9 440 80 88.9 380 4 4.500 4 4.500 100 114.3 820 100 114.3 710 108mm 108mm 820 108mm 108mm 710 5 5.563 5 5.563 125 141.3 1200 125 141.3 1040 4441.160 133mm 133 mm 1200 133 mm 133 mm 1040 0 50 139.7 mm 139 1200 1397 .7 mm 139 1040 7 6 6.625 6 6.625 150 168.3 1800 150 168.3 1560 159 mm 159 mm 1800 159 mm 159 mm 1560 165.1 mm 6fi5 1800 1651 .1 mm 6fi5 1560 8 8.625 8 8.625 200 219.1 3400 200 219.1 2940 10 10.750 10 10.750 250 273.0 5800 250 273.0 5020 12 12.750 12 12.750 300 323.9 9000 300 323.9 7790 err , 10.81 5662 Rev F Updated 11/2014 0 2014 Victaulic Company.All rights reserved. victaulic.corn 5 ictauliiC victaulic.com I Butterfly Valve I Series 705 I Publication 10.81 Switch and Wiring: JUNK , CONDOR ,�' 1. The supervisory switch contains two single pole, ►����•- a:-ii 1 ui• double throw, pre-wired switches. �' ���' - •wNP 14 tl I CONDIMCDNNECTOR 2. Switches are rated: 1 1 r WIRE NUR 10 amps @ 125 or 250 VAC/60 Hz 0.50 amps @ 125 VDC FIRE ALARM CON NC TORDN#WdOOR 0.25 amps® 250 VDC SUPERVISORY cacuR 3. Switches supervise the valve in the "OPEN" position. SWITCH CONTACT RATING: I DA AT'BAND 5. One switch has two#18 insulated wires per terminal, °SA2,uVDC which permit complete supervision of leads (refer °ssAT250VOCIMO - BELL ' _ OR to diagrams and notes below). The second switch VOLTAGE SOURCE HORN has one#18 insulated wire per terminal. This double Switch,:2 leads per biminN Switch 2:1 lead per terminal circuit provides flexibility to operate two electrical devices at separate locations, such as an indicating light and an audible alarm, in the area that the valve NOTE: The above diagram shows a connection between is installed. the common terminal (yellow—Si and yellow-with- orange stripe—S2)and the normally closed terminal 6. A#14 insulated ground lead (green) is provided. (blue—Si and blue-with-orange stripe—S2). In this Switch #1 =Sl example, the indicator light and alarm will stay on until the valve is fully open. When the valve is fully open, the For connection to the supervisory circuit of a UL indicator light and alarm will go out. Cap off any unused Listed alarm control panel wires (e.g. brown with orange stripe). Switch #2 =S2 Only Si (two leads per terminal) may be connected to Auxiliary switch that may be connected to auxiliary the fire alarm control panel. devices, per the authority having jurisdiction The connection of the alarm switch wiring shall be in accordance with NFPA 72 and the auxiliary switch per Normally Closed: (2) Blue NFPA 70 (NEC). Irate s1 Common: (2)Yellow Normally Closed: Blue with Orange Stripe S2 Normally Open: Brown with Orange Stripe Common: Yellow with Orange Stripe Installation Note Reference should always be made to the I-100 Victaulic Field Installation Handbook for This product shall be manufactured by Victaulic or to Victaulic specifications.All products the product you are installing.Handbooks are included with each shipment of Victaulic to be Installed in accordance with current Victaulic Installation/assembly Instructions. products for complete installation and assembly data,and are available in PDF format Victaulic reserves the right to change product specifications,designs and standard on our website at www.victaulic.com. equipment without notice and without Incurring obligations. Warranty Trademarks Refer to the Warranty section of the current Price List or contact Victaulic for details. Victaulic®is a registered trademark of Victaulic Company. 10.81 5662 Rev F Updated 11/2014 02014 Victaulic Company.All rights reserved. victaulic.com 6 ✓ctaulilCa Check Valves r FPPI° +L/ULC listed and FM approved Description Check valves feature cast brass** bodies with a spring loaded clapper assembly ° rioi; making this valve suitable for vertical or horizontal installations. Features metal faced clapper with 0-ring seat. Rated to 300 psi. Valve bodies are tapped and plugged '/2" IPS for additional equipment such as a ball drip valve when used in conjunction with a Fire Department Connection or a pressure gauge when used in a supply line. Installation Specifications Install in accordance with approved installation practices. Use an approved thread sealant such as PipeFit Thread Sealing Paste with PTFE on all threaded Material: Cast Brass** connections. Make sure that proper lubrication has been applied to groove coupling gaskets for groove end valves. Pressure Rated: 300psi Y ;4 —1 NOT OVER TIGHTEN THREADED CONNECTIONS. OVERTIGHTENING Size; ,1;,,,,,,,,, ,,,,,,AY CAUSE DISTORTION OF THE BODY AND THREADS OF THE VALVE 11" IPS* , LEADING TO IMPROPER PERFORMANCE AND PRODUCT FAILURE. 2" IPS 21/2" IPS 3" IPS 4" IPS Configurations: 1 MNPT x GRV MNPT x FNPT GRV x GRV FNPT x FNPT 1 1/2"only "Contains lead. Not for use in water systems intended for human consumption. *1 Y"size is UVULc listed but not FM approved III3198 LIONSHEAD AVE CARLSBAD, CA 92010 TEL+1 760 599-1168 +1 800 344-1822 FAX+1 800 344-3775 ©2015 Fire Protection Products,Inc. C US 1 LISTED APPROVED pF R G F P P 'r Material Specifications •��j 4 l � / / f 7 / r as.1(1941 -I ‘ i_ 2 • �: 1. BODY- BRASS-ASTM C37700 2. CLAPPER - BRASS-ASTM C37700 3. PIN BRASS ASTM C86300 . \ 4. SPRING -STAINLESS STEEL3 . �I 5 5. 0-RING -NBR-1052 6. THREADED PORT - BRASS NPT PLUG 6 '/a"ON 1 /2" 3"VALVES 1/2"ON 4"VALVES 1111.1111111.11111111 F PPr ttk : i Dimensions WIDTH I I 1 Illiiiii . LENGTH ___ ... .._.._ ____.___ , ,i...... 1.„_m______ I ,il„, ,......._ f - `� „......._.__________,_ ___ __ __ .... .._,_ .,_ „........_..... ..._.. .._ t,„,„ SIZE ITEM# CONFIGURATION f LENGTH ti ` WIDTH LENGTH WIDTH 3 (IN) (IN) . MM . MM 1 ) ( 1 i 1 1/2" , 09-574-00 MNPTXGRV ! 615/16 41/8 176 105 11/2" 09-575-00 MNPTXFNPT 6 1/16 41/8 154 105 4 09 576 00 GRV X GRV 6 15/16 4 1/8 176 3 105 1 1/2" 09-577-00 FNPT X FNPT 1 5 9/16 4 1/8 150 105 2" i 09-568-00 MNPTX GRV i 6 1/4 4 1/8 157 105 2" 09-570-00 MNPT X FNPT 5 3/4 4 1/8 146 105 I 2" i 09-572-00 GRV X GRV f 6 1/4 4 1/8 157 105 1 2 1/2" 09-562-00 MNPTX GRV 3 6 15/16 4 1/8 176 105 2 1/2" 09-564-00 MNPTXFNPT 6 1/4 4 1/8 159 105 2 1/2" 09-566-00 GRV X GRV 6 15/16 4 1/8 176 105 3" 09-556-00 MNPTX GRV ! 6 13/16 5 1/8 173 128 3" 09 558 00 MNPTXFNPT - 6 5/8 5 1/8 167 128 } 1 3" 09-560-00 GRV X GRV 6 13/16 5 1/8 173 128 • 4" ' 09-550-00 MNPT X GRV 8 1/8 5 5/8 206 142 4" 09 552 00 MNPTXFNPT i 8 5 5/8 202 142 4" 09-554-00 GRV X GRV 8 5 5/8 202 142 , T1 !l tt, II 10 SECTION 4 Sprinklers Worldwide www tyco-fire.com tqcii Contacts Model EC-25 (CMDA and CMSA Applications) 25.2 (360) K-factor (360) Upright Sprinkler Extended Coverage General storage and non-storage applica • - tions.When used in conformance with Description applicable FM Global Property Loss Prevention Data Sheets, the Model 4VI 7 �t ,, The TYCO Model EC-25, Extended EC-25 Upright Sprinkler provides low 44 Coverage 25.2K Upright Sprinkler hydraulic demand,the spacing advan- is a UL Listed, standard response, tages of extended coverage, and the extended coverage Control Mode obstruction benefits of an upright t 4 Density Area (CMDA) sprinkler for sprinkler. f 4: � storage applications. It is also FM For more information on applica- * g. ,; '" Approved as a quick response, tions and benefits of the Model EC-25 . extended coverage CMDA sprinkler Upright Sprinkler, refer to the available and as a Control Mode Specific Appli- White Papers at www.tyco-fire.com. ff._. cation (CMSA) sprinkler, as well as FM Approved for storage and non-stor- NOTICE • age applications. ■T echn►cal The Model EC-25 Upright Sprinklers When used in accordance with described herein must be installed Data National Fire Protection Association and maintained in compliance with this (NFPA) 13, smoke vents and draft cur- document, as well as with the applica- Approvals tains are not required as specified in the ble standards of the NFPA, in addition UL and C-UL Listed:CMDA 2015 edition of the International Building to the standards of any other authori- (Standard Response) . Code(IBC) and International Fire Code ties having jurisdiction. Failure to do so (IFC)for CMSA sprinklers with an RTI of may impair the performance of these FM Approved:CMDA and CMSA 50 or less and a design of 12 or fewer devices. (Quick Response) sprinklers. NYC Approved under MEA 355-01-E The owner is responsible for main- These sprinklers offer a maximum coy- taining their fire protection system Approvals only apply to the service condi- erage area of 196 ft2 (18,2 m2), which and devices in proper operating con tins Indicated in the Design Criteria section. is almost double the area offered by dition. Contact the installing contrac- Finish standard coverage sprinklers used for tor or sprinkler manufacturer with any Natural Brass similar applications. questions. Physical Characteristics The Model EC-25 Upright Sprinklers Frame Brass comply with the criteria for the pro- Sprinkler Deflector Copper tection of retail stores as described in Compression Screw Stainless Steel NFPA 13. Identification StrutH MMONEL ONEL Where the FM Approval is utilized, the Link Assembly Solder,Nickel Model EC-25 Upright Sprinkler has Number (SIN) Button Brass successfully undergone full-scale fire Sealing Assembly. Beryllium Nickel w/TEFLON testingat FM Global for ceiling-only Refer to Table A for sprinkler identifica- SpringDefiecon torut INCONEL 6 ass g y tion number. Response Time Index(RTI) IMPORTANT Less than or equal to 50(m-s)0.5 Refer to Technical Data Sheet Additional Technical Data TFP2300 for warnings pertaining to Refer to Table A for additional techni- regulatory and health information. cal data. Always refer to Technical Data Operation Sheet TFP700 for the "INSTALLER WARNING" that provides cautions The fusible link assembly is corn- with respect to handling and instal- prised of two link halves that are joined lation of sprinkler systems and com- together by a thin layer of solder.When ponents. Improper handling and the rated temperature is reached, the installation can permanently damage solder melts and the two link halves ,, a sprinkler system or its compo- separate,allowing the sprinkler to acti- nents and cause the sprinkler to fail vate and flow water. to operate in a fire situation or cause it to operate prematurely. Page 1 of 4 AUGUST 2018 TFP213 TFP213 Page 2 of 4 3 TEMPERATURE 2 9/16" DIA. 10 RATING (65,0 mm) C C C 44� 2 — 1 Frame �„-- SC _ 2- Deflector r�ll 'erica i' rig I r _r`�_ II I V i I 3- Compression Screw 4- Hook 4 3-3/4" 5- Strut II i ___.-- 5 (95,3mm) 6- Link Assembly 111 7- Button l 6 �, 9/16" 8- Gasketed Spring Plate �� a• �, (14,3 mm) IS 9- Ejection Spring ggyAY.4 9 = — WRENCH -. _ --- NOMINAL 8 10- Deflector Nut 11 FLATS MAKE-IN ISO 7-R1 pipe thread can be 4i �— provided on special request. 9 CR 7 / S\ 1 1"NPT" f FIGURE 1 MODEL EC-25 UPRIGHT SPRINKLER, 25.2K EXTENDED COVERAGE Design Item Description Criteria Sprinkler Identification Number(SIN) TY9128 K-factor(gpm/psi)(Ipm/bar) 25.2 gpm/psi% (362,9'pm/barn) UL and C-UL Listing Criteria Temperature Rating°F(°C) 165°F(74°C) 212°F(100°C) NFPA 13,Chapters 12 thru 20- Density/Area Design Thread Size 1 in.NPT or ISO 7-R 1 The TYCO Model EC-25 Extended Sprinkler Orientation Upright Coverage Upright Sprinklers (TY9128) are UL and C-UL Listed for installs- Maximum Working Pressure,psi(bar) 175 psi(12,1 bar) tion in accordance with the extended TABLE A coverage upright spray sprinkler MODEL EC-25 UPRIGHT SPRINKLER requirements of NFPA 13 or other appli- TECHNICAL DATA cable NFPA standards when used in conjunction with the following • Minimum distance between sprin- normally associated with high guidelines: klers is 8 ft(2,44 m). temperature sprinklers. As such, • Protection of extra hazard and high- • Minimum flow requirement is based the Model EC--25 Upright Sprinklers piled storage occupancies where on the design density applied are listed storage sprinklers having area/density design criteria are over the actual coverage area per a K-factor greater than 11.2 (161,4) provided. sprinkler. For example,when: and having ordinary and interme- diate temperature ratings of 165°F • Unobstructed or non-combustible A sprinkler spacing is14ftx12ft-6in. or 74°C and 214°F or 101°C. Conse- obstructed construction. (4,3 m x 3,8 m) or 175 ft2 (16,3 m2), quently, the Model EC-25 Sprin- • Model EC-25 Sprinklers, having and the design density is 0.6 gpm/ft2 klers, in accordance with NFPA 13, been specifically tested and Listed (24,4 mm/min), the sprinkler design may be used in conjunction with the for non-combustible obstructed flow rate is 105 gpm (397 Lpm) and density curves for high temperature construction, are suitable for use the required design pressure is sprinklers. within trusses or bar joists having 17.4 psi(1,2 bar). • NFPA obstruction rules for Extended non-combustible web members • The minimum clearance between Coverage Sprinklers must be utilized. greaterapplying than 14in.times obs25,4 truction when en the deflector and the top of storage System Type pp y g is 36 in. (0,9 m). For clearances of criteria rule defined under"Obstruc- 36 in. (0,9 m) up to 48 in. (1,21 m), Wet pipe, dry pipe, and pre-action tions to Sprinkler Discharge Pattern the minimum design pressure is systems are acceptable. Development." 22 psi (1,52 bar). For clearances FM Approval Criteria • Maximum coverage area per of 48 in. (1,21 m) and greater, the sprinkler is 196 ft2(18,2 m2). minimum design pressure is estab- FM Loss Prevention Data Sheets lished by the minimum flow require- 2-0,3-26,and 8-9 • Maximum distance between sprin- ment. However, the pressure can TYCO Model EC-25 Extended Cover- klers is 15 ft (4,6 m) when the never be less than 7 psi (0,5 bar). age 25.2K Upright Sprinklers(TY9128) coverage area does not exceed are FM Approved to be utilized in accor- 144 ft2(13,4 m2), and the maximum • Ordinary and intermediate temper- dance with the following guidelines. distance between sprinklers is ature rated Model EC-25 Upright . 14 ft (4,3 m) when the coverage Sprinklers have been investigated Application area does not exceed 196 ft2 for use in high-piled storage occu- The Model EC-25 Extended Coy- (18,2 m2). pancies at the hydraulic demand erage Upright Sprinklers are TFP213 Page 3 of 4 Storage Type NFPA FM Global 400, Sprinkler Type CMDA CMDA/CMSA Response Type SR QR System Type Wet/Dry/Preaction Wet Temperature Rating°F(°C) 165°F(74°C) 165°F(74°C) 212°F(100°C) 212°F(100°C) Open Frame(i.e.,no solid shelves),Single,Double,Multiple- Row, or Portable Rack Storage of Class I-IV and Group A or Refer to NFPA 13 Refer to FM 2-0 and 8-9 B Plastics Solid Pile or Palletized Storage of Class I-IV and Group A or Refer to NFPA 13 Refer to FM 2-0 and 8-9 B Plastics Idle Pallet Storage Refer to NFPA 13 Refer to FM 2-0,8-9,and 8-24 Rubber Tire Storage Refer to NFPA 13 Refer to FM 2-0 and 8-3 Roll Paper Storage Refer to NFPA 13 Refer to FM 8-21 (Refer to the Standard) Flammable/Ignitable Liquid Storage Refer to NFPA 30 Refer to FM 7-29 (Refer to the Standard) Aerosol Storage Refer to NFPA 30B Refer to FM 7-31 (Refer to the Standard) Automotive Components in Portable Racks Refer to NFPA 13 N/A (Control mode only;refer to the Standard) N/A-Not Applicable TABLE B MODEL EC-25 UPRIGHT SPRINKLER COMMODITY SELECTION AND DESIGN CRITERIA OVERVIEW FM Approved ceiling-level Storage 100 ft2(9,3 m2).The maximum distance NFPA 13-Alternative System Sprinklers for storage occupancy between sprinklers is 14 ft(4,3 m).The Design (CMSA) Criteria hazards and other similar high heat minimum distance between sprinklers The TYCO Model EC-25 Extended Coy - release type fires. When compared is 10 ft(3,05 m). erage Upright Sprinklers(TY9128)have with other FM Approved Storage Sprin- Note: When a wall or obstruction successfully undergone large-scale klers, the Model EC-25 Upright Sprin- makes a minimum spacing of 10 ft fire tests at FM Global to comply with kler provides low hydraulic demand, (3,05 m)impossible,consult FM Global the current edition of NFPA 13.As such, the spacing advantages of extended Property Loss Prevention Data Sheet NFPA 13 may be utilized for design coverage,and the FM Global obstruc- 2.0 for applicable guidelines. options with the Model EC-25 Upright tion benefits of an upright sprinkler. Model EC-25 Upright Sprinklers should Sprinkler Location Sprinklers for providing ceiling only Locate sprinklers with respect to protection. be used in conformance with applica the ceiling/roof in accordance with This allows for the protection of Pallet- ble FM Global Property Loss Preven FM Global Property Loss Prevention ized,Single, Double,and Multiple Row tion Data Sheets. Data Sheet 2.0. Open Racks. Protection is up to 30 ft Hydraulic Design (9,1 m) of Cartoned, Unexpanded Obstructions To determine the hydraulic design for Group A Plastic Commodities in a the Model EC-25 Upright Sprinkler refer Follow the obstruction requirements maximum 35 ft (11 m) ceiling con- to the applicable FM Global Property as detailed in FM Global Property Loss dition with extended spacing up to Loss Prevention Data Sheet. Prevention Data Sheet 2.0. 196 ft2 (18,2 m2). This protection is System Type Other Details delivered while maintaining very rea- Wet pipe systems only All other design details should be in sonable flow and pressure require- accordance with FM Global Property ments. Pipe sizes as well as water Sprinkler Spacing Loss Prevention Data Sheet 2.0 as well supply requirements can now be kept The maximum coverage area per as any other applicable FM Global Data to a minimum when compared to other sprinkler is 196 ft2 (18,2 m2). The Sheet. design methods for high piled storage minimum coverage area per sprinkler is challenges. TFP213 Page 4 of 4 Installation Inspection, testing, and maintenance must be performed as indicated below WRENCH The TYCO Model EC-25 Extended and in accordance with the local RECESS Coverage 25.2K Upright Sprinklers are requirements and/or national codes. to be installed in accordance with this Any impairment must be immediately section. corrected. N „� Damage to the fusible Link Assembly The owner is responsible for the inspec- tion,�� during installation can be avoided by tion,testing, and maintenance of their ;�� !(�)�I++� fire protection system and devices in vI handling the sprinkler using only the frame arms and the appropriate sprin compliance with this document,as well "FITTING SIDE" - kler wrench. Do not grip or apply any as with the applicable standards of any TOWARDS SPRINKLER ID force to the fusible Link Assembly. authorities having jurisdiction.Contact FITTING Damaged sprinklers must be replaced the installing contractor or product immediately. manufacturer with any questions. A leak tight 1 in. NPT sprinkler joint Automatic sprinkler systems are rec- FIGURE 2 should be obtained by applying a ommended to be inspected, tested, W-TYPE 1 minimum-to-maximum torque of and maintained by a qualified Inspec- SPRINKLER WRENCH 20 to 30 lb-ft(26,8 to 40,2 N•m). Higher tion Service in accordance with local levels of torque may distort the sprin requirements and/or national codes. When used in accordance with kler inlet with consequent leakage or Limited NFPA 13, smoke vents and draft cur- impairment of the sprinkler. tains are not required as specified in the Note:Install the Model EC-25 Upright 2015 edition of the International Building Sprinkler in the upright position. Warranty Code(IBC) and International Fire Code (IFC)for CMSA sprinklers with an RTI of Step 1. With pipe thread sealant For warranty terms and conditions,visit 50 or less and a design of 12 or fewer applied,hand-tighten the sprinkler into www.tyco-fire.com. sprinklers. the sprinkler fitting. Do not apply any tion Type force to the Link Assembly,and handle Ordering Construc accodance with NFPA 13 for the Model EC-25 Upright Sprinkler only In Extended Coverage Sprinklers for High by the Frame arms. Procedure Piled Storage. Step 3. Wrench-tighten the Model Contact your local distributor for avail- Obstruction Criteria avail- EC-25 Upright Sprinkler using only the ability.When placing an order,indicate Follow Sections 8.8.5.1, "Extended W-Type 1 Sprinkler Wrench(Ref.Figure the full product description and part 2) and by fully engaging (seating) the . 4 ''numberP/N Coverage Obstruction Guidelines for wrench on the sprinkler wrench flats. ( ) Sprinkler Discharge Pattern Develop- Sprinkler Assemblies ment"; 8.12.5.2 and 8.12.5.3, "ESFR Step 4. After installation, inspect the Specify:Model EC-25 Extended Cover- Obstruction Criteria," for obstructions Link Assembly of each Model EC-25 age 25.2K Upright Sprinklers(TY9128), that prevent the pattern from reaching Upright Sprinkler for damage. In par- the hazard below. ticular, verify that the Link Assembly (Natur I Brass peraturenish, (specify)with Exception: When usingModel EC 25 and Hook are positioned as illustrated P in Figure 1,and that the Link Assembly 165°F(74°C) P/N 58-450-1-165 EC-25 Upright Sprinkler, any con- has not been bent, creased, or forced 212°F(100°C) P/N 58-450-1-214 tinuous obstruction 4 in. (100 mm) or out of its normal position in any way. Special Order less shall be permitted to be ignored Damaged sprinklers must be replaced Sprinkler Assemblies with in accordance with NFPA 13, section immediately.21.5.3.2.3. ISO 7-R 1 Thread Connection Specify:Model EC-25 Extended Cover- Deflector Distance below Ceiling Care and age 25.2K Upright Sprinklers(TY9128) Follow NFPA 13, Section 8.8.4 for with ISO 7-R 1 thread connection, allowed deflector distances below Maintenance (specify temperature rating), with ceiling. Natural Brass finish, P/N(specify): Clearance to Storage The TYCO Model EC-25 Extended Cov 165°F(74°C) P/N 58-451-1-165 Minimum 36 in.(0,9 m)from the deflec- erage 25.2K Upright Sprinklers must be 212°F(100°C) P/N 58-451-1-214 tor to the top of storage required. maintained and serviced in accordance with this section. Sprinkler Wrench Maximum Distance Before closing a fire protection system Specify W-Type 1 Sprinkler Wrench, between Sprinklers main control valve for maintenance P/N 56 872 1 025 14 ft(4,3 m) work on the fire protection system Minimum Distance that it controls, obtain permission to between Sprinklers shut down the affected fire protection 10 ft(3,0 m) system from the proper authorities and notify all personnel who may be affected by this decision. 1400 Pennbrook Parkway,Lansdale,PA 19446 I Telephone+1-215-362-0700 n Oki ' '� 02018 Johnson Controls.All rights reserved.All specifications and other information shown were current as of document revision date and are subject to change without notice. Johnson ,i�/I NATIONAL FIRE PROTECTION ASSOCIATION and NFPA are registered trademarks of National Fire Protection Association; MONEL and INCONEL are registered trademarks of Spacial Metals Corporation; Controls TEFLON is a registered trademark of DuPont Worldwide www.tyco-fire.com trice® Contacts Series TY-FRB, 5.6 K-factor Upright, Pendent, and Recessed Pendent Sprinklers Quick Response, Standard Coverage General NOTICE - The TYCO Series TY-FRB Sprinklers °" Description described herein must be installed ,,,,, t and maintained in compliance with The TYCO Series TY-FRB,5.6 K-factor, this document, as well as with the Ft" - Upright (TY313) and Pendent (TY323) applicable standards of the National 0 , r . Sprinklers described in this data sheet Fire Protection Association, in addition ,' to 1t''" are quick response,standard coverage, to the standards of any other authori- i decorative 3 mm glass bulb-type spray ties having jurisdiction. Failure to do so sprinklers designed for use in light or may impair the performance of these ordinary hazard,commercial occupan- devices. 1.44t cies such as banks, hotels, and shop The owner is responsible for main- " ping malls. taining their fire protection system The recessed version of the Series and devices in proper operating con- TY-FRB Pendent Sprinkler, where dition. Contact the installing contrac- applicable, is intended for use in areas tor or product manufacturer with any with a finished ceiling. This recessed questions. I pendent sprinkler uses one of the following: Sprinkler , ° # • A two-piece Style 15 Recessed " itt, .ars` Escutcheon with recessed adjust- Identification N ment up to 5/8 in. (15,9 mm) from '' $?� ;r, . the flush pendent position. Number (SIN) • A two-piece Style 20 Recessed p y TY313. . . . Upright 5.6K, 1/2 in. NPT Escutcheon with recessed adjust- TY323. . . .Pendent 5.6K, 1/2 in. NPT ment up to 1/2 in. (12,7 mm) from the flush pendent position. Technical The adjustment provided by the Data Operation Recessed Escutcheon reduces the accuracy to which the fixed pipe drops The glass bulb contains a fluid which to the sprinklers must be cut. Approvals expands when exposed to heat.When Intermediate level versions of Series Refer to Table A the rated temperature is reached, the TY-FRB Sprinklers are described in Maximum Working Pressure fluid expands sufficiently to shatter the Technical Data Sheet TFP357. Sprin- 175 psi(12.1 bar) glass bulb, allowing the sprinkler to (17.2 bar)* activate and water to flow. 250 kler guards and shields are described psi in Technical Data Sheet TFP780. •The maximum working pressure of 250 psi(17.2 bar) Design only applies to the listing by Underwriters Laborato- ries,Inc.(UL). Discharge Coefficient Criteria IMPORTANT K=5.6 GPM/psi'i(80,6 LPM/bar'%) The TYCO Series TY-FRB,5.6 K-factor, Refer to Technical Data Sheet Temperature Rating Upright (TY313) and Pendent (TY323) TFP2300 for warnings pertaining to Refer to Table A Sprinklers are intended for fire protec- regulatory and health information. tion systems designed in accordance Always refer to Technical Data Finishes Sprinkler: the standard installation rules Sheet TFP700 for the "INSTALLER Sprinkler: Refer to Table B recognized by the applicable Listing or WARNING" that provides cautions Recessed Escutcheon:White Coated, Approval agency (such as, UL Listing with respect to handling and instal- Black Coated,Chrome Plated,or Brass is based on the requirements of NFPA lation of sprinkler systems and corn- Plated 13, and FM Approval is based on the ponents. Improper handling and Physical Characteristics requirements of FM's Loss Prevention installation can permanently damage Frame Bronze Data Sheets).Only the Style 15 or Style a sprinkler system or its compo- Button Brass/Copper 20 Recessed Escutcheon is to be used nents and cause the sprinkler to fail Sealing Assembly ...Stainless Steel w/TEFLON for recessed pendent installations. to operate in a fire situation or cause Bulb Glass compression Screw Bronze it to operate prematurely. Deflector Bronze Page 1 of 4 AUGUST 2018 TFP172 TFP172 Page 2 of 4 Components: *Temperature rating is ** Pipe thread connections per ISO 7-1 1 - Frame 4 - Bulb indicated on Deflector. can be provided on special request. 2 - Button 5 - Compression STYLE 15 or 20 3 - Sealing Screw ESCUTCHEON PLATE 1/2" 7/16"(11,1 mm) RECESSED Assembly 6 - Deflector* DEFLECTOR* SEATING SURFACE NPT** NOMINAL MAKE-IN ESCUTCHEON 6* ;;rigr-- �� I 1 5 Cl 7/16" (11,1 mm) t 4 ( NOMINAL 2° 0I 17 MAKE IN (50,8 mm) "� 2 ir ` 3 id �, (50,8 mm) (34,9 mm) / , i WRENCH 1 I FLATS 1/2" NPT** DEFLECTOR* 2-7/8"(73,0 mm)DIA. -- CROSS SECTION UPRIGHT PENDENT RECESSED PENDENT FIGURE 1 SERIES TY-FRB UPRIGHT(TY313)AND PENDENT(TY323)SPRINKLERS 5.6 K-FACTOR, 1/2 INCH NPT, QUICK RESPONSE Installation Step 2. With pipe-thread sealant applied to the pipe threads, hand- The TYCO Series TY-FRB,5.6 K-factor, tighten the sprinkler into the sprinkler WRENCH RECESS Upright (TY313) and Pendent (TY323) fitting. (USE ONLY Sprinklers must be installed in accor- Step 3. Tighten the sprinkler into the END"A") dance with this section. sprinkler fitting using only the W-Type General Instructions 6 Sprinkler Wrench(Figure 2).With ref- FIGURE 2 Do not install any bulb-type sprin erence to Figure 1,apply the W-Type 6 W-TYPE 6 kler if the bulb is cracked or there is Sprinkler Wrench to the wrench flats. SPRINKLER WRENCH a loss of liquid from the bulb. With the Torque sprinklers 7 to 14 lb-ft (9,5 to sprinkler held horizontally, a small air 19,0 N m). bubble should be present. The diam- Recessed Pendent Sprinklers WRENCH eter of the air bubble is approximately The Series TY-FRB Recessed Pendent RECESS 1/16 in.(1,6 mm)ft °F °C)and must be insta in ac 3/32 in. (2,4 mm)for the 286°F(141°C) dance with the following instructions. �,1 temperature ratings. Step A. After installing the Style 15 A leak-tight 1/2 in. NPT sprinkler joint or Style 20 Mounting Plate over the 7ri should be obtainedorhe 1b3y5°applying(57 a sprinklerSprinklers threads,andi with pipe-threadlled cor- minimum to maximum torque of 7 to sealant applied to the pipe threads, t• 14 lb-ft(9,5 to 19,0 N•m). Higher levels hand-tighten the sprinkler into the '�`�, of torque can distort the sprinkler Inlet sprinkler fitting. with consequent leakage or impairment Step B. Tighten the sprinkler into the PUSH WRENCH of the sprinkler. sprinkler fitting using only the W-Type IN TO ENSURE Do not attempt to compensate for 7 Recessed Sprinkler Wrench (Figure ENGAGEMENT insufficient adjustment in the Escutch- 3).With reference to Figure 1,apply the WITH SPRINKLER eon Plate by under- or over-tightening W-Type 7 Recessed Sprinkler Wrench WRENCHING AREA the sprinkler. Re-adjust the position of to the sprinkler wrench flats. Torque FIGURE 3 the sprinkler fitting to suit. sprinklers 7 to 14 lb-ft(9,5 to 19,0 N•m). W-TYPE 7 RECESSED SPRINKLER WRENCH Upright and Pendent Sprinklers Step C. After ceiling installation and The Series TY-FRB Upright and finishing, slide on the Style 15 or Style Pendent Sprinklers must be installed 20 Closure over the Series TY-FRB in accordance with the following Sprinkler and push the Closure over the instructions. Mounting Plate until its flange comes in Step 1.Install Pendent sprinklers in the contact with the ceiling. pendent position. Install upright sprin- klers in the upright position. TFP172 Page 3 of 4 Care and 2-7/8"DIA. (73,0 mm) Maintenance 2 1/4"DIA. The TYCO Series TY-FRB,5.6 K-factor, FACE OF (57,2 mm) Upright (TY313) and Pendent (TY323) SPRINKLER Sprinklers must be maintained and ser- FITTING 5/8"(15,9 mm) viced in accordance with this section. + 1 FLUSH Before closing a fire protection system 3/8±5/16" I main control valve for maintenance (9,5±7,9 mm) 7 0 % I work on the fire protection system } I that it controls, obtain permission to i shut down the affected fire protection MOUNTING 1/8" systems from the proper authorities SURFACE (3,2 mm) and notify all personnel who may be CLOSURE SERIES MOUNTING 1-3/8"(34,9 mm) affected by this action. TY-FRB PLATE 3/4"(19,1 mm) Absence of the outer piece of an escutcheon, which is used to cover FIGURE 4 a clearance hole, can delay sprinkler SERIES TY-FRB RECESSED PENDENT SPRINKLER ASSEMBLY(TY323) operation in a fire situation. WITH TWO PIECE 5/8 INCH TOTAL ADJUSTMENT STYLE 15 RECESSED ESCUTCHEON The owner must assure that the sprin- klers are not used for hanging any objects and that the sprinklers are only - 2-7/8" DIA. cleaned by means of gently dusting (73,0 mm) with a feather duster; otherwise, non- FACE OF operation in the event of a fire or inad- SPRINKLER 2-1/4"DIA. vertent operation may result. FITTING (57,2 mm) Sprinklers which are found to be 5/16±1/4" 1/2" leaking or exhibiting visible signs of (7,9±6,4 m 12,7 mm)m) ( corrosion must be replaced. + FLUSH Automatic sprinklers must never be 1 ' ,7 painted, plated, coated, or other- , L 1-1 L .,a, wise altered after leaving the factory. t / 4 Modified sprinklers must be replaced. MOUNTING 1/8" J Sprinklers that have been exposed to SURFACE (3,2 mm) corrosive products of combustion, but have not operated,should be replaced 1 if they cannot be completely cleaned CLOSURE SERIES MOUNTING 1-3/8"(34,9 mm) by wiping the sprinkler with a cloth or TY-FRB PLATE 7/8"(22,2 mm) by brushing it with a soft bristle brush. FIGURE 5 Care must be exercised to avoid SERIES TY-FRB RECESSED PENDENT SPRINKLER ASSEMBLY(TY323) damage to the sprinklers before, WITH TWO PIECE 1/2 INCH TOTAL ADJUSTMENT STYLE 20 during, and after installation. Sprin- RECESSED ESCUTCHEON klers damaged by dropping, striking, wrench twist/slippage,or the like,must Limited Recessed Escutcheon be replaced. Also, replace any sprin- Specify: Style 15 Recessed Escutch- kler that has a cracked bulb or that has Warrant eon with(specify")finish,P/N(specify*) lost liquid from its bulb. (Ref. Installa- y tion Section.) Specify: Style 20 Recessed Escutch- For warranty terms and conditions,visit eon with(specify*)finish, P/N(specify*) The owner is responsible for the www.tyco-fire.com. *Refer to Technical Data Sheet TFP770 inspection,testing,and maintenance of their fire protection system and devices Ordering Sprinkler Wrench in compliance with this document, as Specify: W-Type 6 Sprinkler Wrench, well as with the applicable standards Procedure P/N 56-000-6-387 of the National Fire Protection Asso- Specify: W-Type 7 Sprinkler Wrench, ciation (e.g., NFPA 25), in addition to Contact your local distributor for avail- P/N 56-850-4-001 the standards of any other authorities ability.When placing an order,indicate having jurisdiction.Contact the install- the full product name and Part Number ing contractor or product manufacturer (P/N). with any questions. Sprinkler Assemblies with NPT Automatic sprinkler systems are rec- Thread Connections ommended to be inspected, tested, Specify: Series TY-FRB Upright or and maintained by a qualified Inspec- Pendent (specify) Sprinkler, SIN ,.-' tion Service in accordance with local (specify), m e.a, QuickResponse, requirements and/or national codes. (specify) temperature rating, (specify) finish, P/N(specify, refer to Table A). TFP172 Page 4 of 4 SPRINKLER FINISH(See Note 7) K TYPE TEMPERATURE BULB LIQUID NATURAL CHROME POLYESTERC FACTOR COLOR BRASS PLATED 135°F(57°C) Orange UPRIGHT 155°F(68°C) Red (TY313) and 175°F(79°C) Yellow 1,2,3,4,5,6 PENDENT(TY323) 200°F(93°C) Green 5.6 286°F(141°C) Blue 1/2 in.NPT 135°F(57°C) Orange RECESSED 155°F(68°C) Red PENDENT 1,2,3,4 (TY323) 175°F(79°C) Yellow Figures 4a and 5b 200°F(93°C) Green Notes: 1. Listed by Underwriters Laboratories,Inc.,(UL)as Quick Response Sprinklers. 2. Listed by Underwriters Laboratories,Inc.,for use in Canada(C-UL)as Quick Response Sprinklers. 3. Approved by Factory Mutual Research Corporation(FM)as Quick Response Sprinklers. 4. Approved by the City of New York under MEA 354-01-E. 5. VdS Approved(For details,contact Johnson Controls,Enschede,Netherlands,Tel.31-53-428-4444/Fax 31-54-428-3377.) 6. Approved by the Loss Prevention Certification Board(LPCB Ref.No.094a/06)as Quick Response Sprinklers. 7. Where Polyester Coated Sprinklers are noted to be UL and C-UL Listed,the sprinklers are UL and C-UL Listed as Corrosion-Resistant Sprinklers. a. Installed with Style 15(1/2 in.NPT)5/8 in.Total Adjustment Recessed Escutcheon,as applicable. b. Installed with Style 20(1/2 in.NPT)1/2 in.Total Adjustment Recessed Escutcheon,as applicable. c. Frame and Deflector only.Listings and approvals apply to color(Special Order). TABLE A LABORATORY LISTINGS AND APPROVALS FOR 5.6 K-FACTOR SPRINKLERS P/Na 77 — XXX — X — XXX SIN SPRINKLER TEMPERATURE FINISH RATINGS 370 5.6K UPRIGHT(1/2 in.NPT) TY313 1 NATURAL BRASS 135 135°F(57°C) 371 5.6K PENDENT(1/2 in.NPT) TY323 3 PURE WHITE(RAL9010)a 155 155°F(68°C) POLYESTER Notes: SIGNAL WHITE(RAL9003) a. Use suffix"I"for ISO 7-1 connection;for example, 4 POLYESTER 175 175°F(79°C) 77-370-4-175-I 5 JET BLACK(RAL9005) 200 200°F(93°C) POLYESTER 9 CHROME PLATED 286 286°F(141°C) Notes: a. Eastern Hemisphere sales only TABLE B SERIES TY-FRB UPRIGHT AND PENDENT SPRINKLERS PART NUMBER SELECTION 1400 Pennbrook Parkway,Lansdale,PA 194461 Telephone+1-215-362-0700 OP' R01e Johnson Controls.All rights reserved.All specifications and other information shown were current as of document revision date and are subject to change without notice. Jol Ia11nsoI n l NATIONAL FIRE PROTECTION ASSOCIATION and NEPA are registered trademarks of National Fire Protection Association; Controls TEFLON is a registered trademark of DuPont 1 Worldwide www.tyco-fire.com trice® Contacts Series TY-FRB — 5.6 K-factor Horizontal and Vertical Sidewall Sprinklers Quick Response, Standard Coverage General of copper alloy sprinklers beyond that which would otherwise be obtained Description when exposed to corrosive atmo- spheres. Although corrosion resistant The Series TY-FRB, 5.6 K-factor, Hori coated sprinklers have passed the s zontal and Vertical Sidewall Sprinklers standard corrosion tests of the appli i e,;,� described in this data sheet are quick cable approval agencies,the testing is response standard coverage, dec not representative of all possible cor- orative 3 mm glass bulb type spray rosive atmospheres. Consequently, i �,.,, 'r .w sprinklers designed for use in light and it is recommended that the end user r, : , '�- be consulted with respect to the suit- ordinary hazard, commercial occu ability of these coatings for any given °I pancies such as banks, hotels, shop- corrosive environment. The effects of ping malls, etc. They are designed for ,_, installation along a wall or the side of ambient temperature,concentration of a beam and just beneath a smooth chemicals, and gas/chemical velocity, ceiling. Sidewall sprinklers are com should be considered, as a minimum, monly used instead of pendent or along with the corrosive nature of the upright sprinklers due to aesthetics or chemical to which the sprinklers will be building construction considerations, exposed. 1-+ where piping across the ceiling is not * desirable. NOTICE ,,, The recessed version of the Series The Series TY-FRB Sprinklers TY-FRB Horizontal Sidewall Sprinkler described herein must be installed is intended for use in areas with a fin- „and maintained in compliance with ished wall. It uses a two-piece Style this document, as well as with the 10 Recessed Escutcheon with 1/2 in. applicable standards of the National - ; (12,7 mm)of recessed adjustment or up Fire Protection Association, in addition to 3/4 in.(19,1 mm)of total adjustment to the standards of any other authori- .-�' from the flush sidewall position, or a ties having jurisdiction. Failure to do so '`� two-piece Style 20 Recessed Escutch- may impair the performance of these e eon with 1/4 in. (6,4 mm) of recessed devices. adjustment or up to 1/2 in. (12,7 mm) The owner is responsible for main- I,of total adjustment from the flush side- taining their fire protection system wall position.The adjustment provided and devices in proper operating con- by the Recessed Escutcheon reduces dition. Contact the installing contrac- Technical the accuracy to which the fixed pipe for or product manufacturer with any nipples to the sprinklers must be cut. questions. Data Corrosion resistant coatings, where applicable,are utilized to extend the life Spr►nkler Approvals UL and C-UL Listed Identification FM Approved IMPORTANT LPCB Approved Refer to Technical Data Sheet Numbers NYC Approved TFP2300 for warnings pertaining to (Refer to Table A for complete approval regulatory and health information. TY3331 Horizontal information including corrosion resistant Always refer to Technical Data TY3431 Vertical status.) Sheet TFP700 for the "INSTALLER Maximum Working Pressure WARNING" that provides cautions Refer to Table B with respect to handling and instal Discharge Coefficient lation of sprinkler systems and com Disc GPM/ LPM/barli2) ponents. Improper handling and installation can permanently damage Temperature Ratings a sprinkler system or its compo- Refer to Table A nents and cause the sprinkler to fail to operate in a fire situation or cause it to operate prematurely. Page 1 of 6 JULY 2018 TFP176 . TFP176 Page 2 of 6 1 Frame DEFLECTOR 1 Frame DEFLECTOR 2 - Button HAT \ 5 2 - Button HAT 5 3 - Sealing 3 - Sealing Assembly it Assembly if4 - Bulb 4 - Bulb 5 - Compression / 5 - Compression Screw Z Screw 6 - Deflector* 6* 4 2 3 1 6 - Deflector* 6* 4 2 3 1 9/16" WRENCH 1/2"** 9/16" WRENCH 1/2" (14,3 mm) FLATS NPT (14,3 mm) FLATS NPT . I II�O� ��� ��� -vow 1-13/16" 7/16" 1-13/16" 7/16" (46,0 mm) (11,1 mm) (46,0 mm) (11,1 mm) CENTERLINE NOMINAL CENTERLINE NOMINAL OF SPRINKLER MAKE-IN OF SPRINKLER MAKE IN WATERWAY 1 1/2" WATERWAY 1 1/2" -"—(38,1 mm)~ (38,1 mm)y ESCUTCHEON ESCUTCHEON PLATE SEATING 2-3/16" — PLATE SEATING 2-3/16" SURFACE (55,6 mm) SURFACE (55,6 mm) — STYLE 10 or 20 I STYLE 10 1 I RECESSED RECESSED ESCUTCHEON 11111 ESCUTCHEON N .,. *Temperature rating is � 111 *Temperature rating is I M � indicated on Deflector itereinil Indicated on Deflector I•,r.�,�IIIIIIIII�II** Pipe thread connections per ISO 7-1 can be provided on special 2-7/8„ DIA. 2-7/8" DIA. request (73,0 mm) (73,0 mm) ALL FINISHES EXCEPT POLY-STAINLESS POLY-STAINLESS FINISH ONLY FIGURE 1 5.6 K-FACTOR QUICK RESPONSE SERIES TY-FRB HORIZONTAL SIDEWALL (TY3331)SPRINKLERS Finishes Poly-Stainless Design Sprinkler:Refer to Table C Physical Characteristics Recessed Escutcheon:Signal or Pure Frame Bronze Criteria Button L316 Stainless Steel* White,Jet Black,Grey Aluminum,Chrome Bulb Glass Plated,or Brass Plated Compression Screw L316 Stainless Steel" The Series TY-FRB, 5.6 K-factor, Hor- HSW Deflector Copper/Bronze izontal and Vertical Sidewall Sprin- Physical Characteristics Sealing Assembly.Gold Plated Beryllium Nickel p Frame Bronze w/TEFLON klers are intended for fire protection Button Brass/Copper 'Type L316 stainless steel(UNS 31603)per ASTM systems designed in accordance with Sealing Assembly..Beryllium Nickel w/TEFLON A479/479M or BS EN 1008 WN1.4404, the standard installation rules rec- Bulb Glass ognized by the applicable Listing or Compression Screw Bronze Operation Approval agency (e.g., UL Listing is HSW Deflector Bronze VSW Deflector Copper based on the requirements of NFPA The glass bulb contains a fluid which 13, and FM Approval is based on the expands when exposed to heat.When requirements of FM's Loss Prevention the rated temperature is reached, the Data Sheets). Only the Style 10 or 20 fluid expands sufficiently to shatter the Recessed Escutcheon, as applicable, glass bulb, allowing the sprinkler to is to be used for recessed horizontal activate and water to flow. installations. TFP176 Page 3 of 6 Installation *Temperature ** Pipe thread 1 - Frame 4 - Bulb 7 - Ejection rating is connections 2 - Button 5 - Compression Spring .,.. The Series TY-FRB,5.6 K-factor, Hori- indicated on per ISO 7-1 can 3 - Sealing Screw zontal and Vertical Sidewall Sprinklers Deflector. be provided on Assembly 6 - Deflector* must be installed in accordance with special request. this section. General Instructions ARROW MUST POINT AWAY _----4— Do not install any bulb type sprinkler 7/16" FROM AND BE if the bulb is cracked or there is a loss ESCUTCHEON (11,1 mm) PERPENDICULAR O of liquid from the bulb. With the sprin- PLATE SEATING NOMINAL TO THE BACK kler held horizontally,a small air bubble SURFACE NPT** MAKE-IN WALL SURFACE should be present.The diameter of the air bubble is approximately 1/16 in. I I 6* (1,6 mm) for the 135°F (57°C) to s���i�ti 3/32 in. (2,4 mm)for the 286°F(141°C) I \ ��� 41.1 temperature ratings. FLOW b 5 A leak tight 1/2 in. NPT sprinkler joint 2-3/16" 2-3/16" 4 should be obtained with a torque of (55,6 mm) 1 (55,6 mm) 7 to 14 lb-ft (9,5 to 19,0 N•m). Higher 1-1/2" \ �I 2 levels of torque may distort the sprin- (38,1 mm) � � kler and cause leakage or impairment WRENCH 7 of the sprinkler. FLATS 3 Do not attempt to make-up for insuf- 1 ficient adjustment in the escutcheon SHOWN SHOWN CROSS plate by under-or over-tightening the PENDENT UPRIGHT SECTION sprinkler. Readjust the position of the sprinkler fitting to suit. FIGURE 2 5.6 K-FACTOR QUICK RESPONSE Series TY-FRB Horizontal and SERIES TY-FRB VERTICAL SIDEWALL(TY3431)SPRINKLERS Vertical Sidewall Sprinkler Installation Series TY-FRB Recessed The Series TY-FRB Horizontal and Horizontal Sidewall Sprinkler Care and Vertical Sidewall Sprinklers must be Installation installed in accordance with the fol- The Series TY-FRB Recessed Horizon Maintenance lowing instructions. tal Sidewall Sprinklers must be installed Hori- Step 1. Horizontal sidewall sprinklers in accordance with this section. The Series Vertical id5. all Sprictor,nklers s are to be installed in the horizontal zontal and Sidewall Sprinklers position with their centerline of Step A. Recessed horizontal sidewall must be maintained and serviced in sprinklers are to be installed in the hori- accordance with this section. way perpendicular the back wall water- parallel to the ceiling.The word "TOP" zontal position with their centerline of Before closing a fire protection system on the Deflector is to face towards the waterway perpendicular to the back main control valve for maintenance ceiling. wall and parallel to the ceiling. The work on the fire protection system that word"TOP"on the Deflector is to face it controls,permission to shut down the Vertical sidewall sprinklers are to be towards the ceiling. affected fire protection system must be installed in the pendent or upright Step B.After installing the Style 10 or obtained from the proper authorities position with the arrow on the Deflec- 20 Mounting Plate over the sprinkler and all personnel who may be affected tor pointing away from the wall. threads,hand tighten the sprinkler into by this action must be notified. Step 2. With pipe thread sealant the sprinkler fitting. Absence of an escutcheon, which is applied to the pipe threads, hand Step C. Tighten the sprinkler into the used to cover a clearance hole, may tighten the sprinkler into the sprinkler sprinkler fitting using only the W-Type delay the time to sprinkler operation in fitting. 7 Recessed Sprinkler Wrench (Ref. a fire situation. Step 3. Tighten the sprinkler into the Figure 6). With reference to Figure Sprinklers that are found to be leaking sprinkler fitting using only the W-Type 1, the W-Type 7 Recessed Sprinkler or exhibiting visible signs of corrosion 6 Sprinkler Wrench(Ref.Figure 5),With Wrench is to be applied to the sprin- must be replaced. reference to Figure 1 or 2,the W-Type kler wrench flats. 6 Sprinkler Wrench is to be applied to Step D. After the ceiling has been Automatic sprinklers must never be the wrench flats. installed or the finish coat has been painted, plated, coated or other- slide on 10 or 20 wise altered after leaving the factory. applied,over thethe Style 10B orSp 20in- Modified sprinklers must be replaced. Closure and push the Series TY-F the Sprinklers that have been exposed to kle Plate until its Cto u ego overco the corrosive products of combustion, but Mounting t with theu ceiling. have not operated,should be replaced inif they cannot be completely cleaned by wiping the sprinkler with a cloth or by brushing it with a soft bristle brush. Care must be exercised to avoid damage to the sprinklers before, during, and after installation. Spriklers TFP176 Page 4 of 6 5/8±1/4" (15,9±6,4 mm) MOUNTING FACE OF ANCH RECESS SURFACE SPRINKLER "A"USED FOR FITTING NPT MODELS) A CLOSURE r 1 FIGURE 5 W-TYPE 6 SPRINKLER WRENCH 2-7/8" DIA. (73,0 mm) SERIES TY-FRB 2-1/4" DIA. WRENCH (57,2 mm) RECESS MOUNTING ___ !• PLATE l 1 y I 1/8" rr (3,2 mm) 1011111 WRENCH USH 1-1/4"(31,8 mm) 3/4"(19,1 mm) PIN TO ENSURE 3/4"(19,1 mm) 1/4"(6,4 mm) ENGAGEMENT WITH SPRINKLER FIGURE 3 WRENCHING AREA SERIES TY-FRB RECESSED HORIZONTAL SIDEWALL SPRINKLER FIGURE 6 WITH TWO-PIECE 3/4 INCH TOTAL ADJUSTMENT W-TYPE 7 RECESSED STYLE 10 RECESSED ESCUTCHEON SPRINKLER WRENCH 1/2±1/8" (12,7±3,2 mm) MOUNTING FACE OF SURFACE ------ --_ SPRINKLER FITTING A CLOSURE 2-7/8" DIA. (73,0 mm) SERIES TY-FRB 2-1/4" DIA. (57,2 mm) MOUNTING PLATE /1 y I 1/8' Ir (3,2 mm) 1-1/4"(31,8 mm) 1/2"(12,7 mm) 1"(25,4 mm) 1/4"(6,4 mm) FIGURE 4 SERIES TY-FRB RECESSED HORIZONTAL SIDEWALL SPRINKLER WITH TWO-PIECE 1/2 INCH TOTAL ADJUSTMENT STYLE 20 RECESSED ESCUTCHEON TFP176 Page 5 of 6 SPRINKLER FINISH(See Note 11) K TYPE TEMP. BULB NATURAL CHROME pOLYESTERc POLY- LEAD LIQUID BRASS PLATED STAINLESSc COATED 135°F(57°C) Orange HORIZ. 155°F(68°C) Red SIDEWALL 175°F(79°C) Yellow 1,2,3,4,9, 10 1,2,3,9 1,2 1,2,3,9 (TY3331) 200°F(93°C) Green 286°F(141°C) Blue 5.6 RECESSED 135°F(57°C) Orange 1/2 in. HORIZ. 155°F(68°C) Red NPT SIDEWALL 1,2,4,9, 10 1,2,9 1,2 N/A (TY3331)a 175°F(79°C) Yellow Figure 3 200°F(93°C) Green RECESSED 135°F(57°C) Orange HORIZ. 155°F(68°C) Red SIDEWALL 1,2,3,4,9 N/A N/A (TY3331)b 175°F(79°C) Yellow Figure 4 200°F(93°C) Green VERTICAL 135°F(57°C) Orange SIDEWALL 155°F(68°C) Red 5.6 (TY3431) 1/2 in. Installed 175°F(79°C) Yellow 5,6,7,8,9 N/A 5,6,7,9 NPT Pendent or 200°F(93°C) Green Upright 286°F(141°C) Blue NOTES: 1. Listed by Underwriters Laboratories,Inc.(UL)as Quick Response Sprinklers for use in Light and Ordinary Hazard Occupancies at a 4 to 12 in.(100 to 300 mm)top of deflec- tor to ceiling distance. 2. Listed by Underwriters Laboratories Inc.for use in Canada(C-UL)as Quick Response Sprinklers for use in Light and Ordinary Hazard Occupancies at a 4 to 12 in.(100 to 300 mm)top of deflector to ceiling distance. +4itiow 3. Approved by Factory Mutual Research Corporation(FM)as Quick Response Sprinklers for use in Light Hazard Occupancies at a 4 to 12 in.(100 to 300 mm)top of deflector to ceiling distance. 4. Approved by the Loss Prevention Certification Board(LPCB Ref.No.007a/04)at a 4 to 6 in.(100 to 150 mm)top of deflector to ceiling distance.The LPC does not rate the thermal sensitivity of horizontal sidewall sprinklers. 5. Listed by Underwriters Laboratories,Inc.as Quick Response Sprinklers for use in Light and Ordinary Hazard Occupancies. 6. Listed by Underwriters Laboratories for use in Canada(C-UL)as Quick Response Sprinklers for use in Light and Ordinary Hazard Occupancies. 7. Approved by Factory Mutual Research Corporation(FM)as Quick Response Sprinklers for use in Light Hazard Occupancies. 8. Approved by the Loss Prevention Certification Board(LPCB Ref.No.094a/06&007a/04)as Quick Response Sprinklers. 9. Approved by the City of New York under MEA 354-01-E. 10.Approved by the Loss Prevention Certification Board(LPCB Ref.No.094a/06)at a 4 to 6 in.(100 to 150 mm)top of deflector to ceiling distance.The LPC does not rate the thermal sensitivity of horizontal sidewall sprinklers. 11.Where Polyester Coated and Lead Coated Sprinklers are noted to be UL and C-UL Listed,the sprinklers are UL and C-UL Listed as Corrosion Resistant Sprinklers. Where Lead Coated Sprinklers are noted to be FM Approved,the sprinklers are FM Approved as Corrosion Resistant Sprinklers. a. Installed with Style 10(1/2 in.NPT)3/4 in.Total Adjustment Recessed Escutcheon. b. Installed with Style 20(1/2 in.NPT)1/2 in.Total Adjustment Recessed Escutcheon. c. Frame and deflector only. TABLE A LABORATORY LISTINGS AND APPROVALS damaged by dropping,striking,wrench Thereafter, annual inspections per ing contractor or product manufacturer twist/slippage, or the like, must be NFPA 25 should suffice; however, with any questions. replaced. Also, replace any sprikler instead of inspecting from the floor It is recommended that automatic that has a cracked bulb or that has lost level, a random sampling of close-up sprinkler systems be inspected,tested, liquid from its bulb. (Ref. Installation visual inspections should be made, so and maintained by a qualified Inspec- Section). as to better determine the exact sprin- tion Service in accordance with local The owner must assure that the sprin kler condition and the long term integ requirements and/or national codes. klers are not used for hanging any rity of the corrosion resistant coating, objects and that the sprinklers are only as it may be affected by the corrosive cleaned by means of gently dusting conditions present. with a feather duster; otherwise, non- The owner is responsible for the operation in the event of a fire or inad- inspection,testing,and maintenance of vertent operation may result. their fire protection system and devices Frequent visual inspections are rec in compliance with this document, as ommended to be initially performed well as with the applicable standards for corrosion resistant coated sprin of the National Fire Protection Asso- klers, after the installation has been ciation (e.g., NFPA 25), in addition to completed, to, verify the integrity the standards of any other authorities of the corrosion resistant coating. having jurisdiction. Contact the install- TFP176 Page 6 of 6 SPRINKLER FINISH K TYPE NATURAL BRASS CHROME PLATED POLYESTER LEAD COATED 250 PSI(17,2 BAR) HORIZONTAL SIDEWALL(TY3331) or 175PSI(12,1 BAR) 5.6 RECESSED HORIZ. 1/2 in. SIDEWALL(TY3331) (SEE NOTE 1) NPT VERTICAL SIDEWALL 175 PSI(12,1 BAR) (TY3431) NOTES: 1. The maximum working pressure of 250 psi(17,2 bar)only applies to the Listing by Underwriters Laboratories,Inc.(UL);the Listing by Underwriters Laboratories,Inc.for use in Canada(C-UL);and,the Approval by the City of New York. TABLE B MAXIMUM WORKING PRESSURE P/N 57 — XXX — X — XXX ( I SIN SPRINKLER TEMPERATURE FINISH RATINGS 378 HORIZONTAL SIDEWALL TY3331 1 NATURAL BRASS 135 135°F(57°C) 375 VERTICAL SIDEWALL TY3431 POLY-STAINLESS GREY 155 155°F(68°C) 2 ALUMINUM(RAL9007)1 POLYESTER 175 175°F(79°C) 3 PURE WHITE(RAL9010)2 POLYESTER SIGNAL WHITE(RAL9003) 200 200°F(93°C) 4 POLYESTER 286 286°F(141°C) 5 JET BLACK(RAL9005)3 POLYESTER 7 LEAD COATED 9 CHROME PLATED NOTES: 1. Available for TY3331 only. 2. Eastern Hemisphere sales only. 3. Available in 155°F(68°C)or 200°F(93°C temperature rating only. TABLE C PART NUMBER SELECTION SERIES TY-FRB HORIZONTAL AND VERTICAL SIDEWALL SPRINKLERS Limited Ordering Recessed Escutcheon Specify: Style (10 or 20) Recessed WarrantyProcedure Escutcheon with (specify') finish, P/N (specify") For warranty terms and conditions,visit Contact your local distributor for avail- Refer to Technical Data Sheet TFP770 www.tyco-fire.com ability.When placing an order,indicate Sprinkler Wrench the full product name and Part Number Specify: W-Type 6 Sprinkler Wrench, (P/N). P/N 56-000-6-387 Sprinkler Assemblies with NPT Specify: W-Type 7 Sprinkler Wrench, Thread Connections: P/N 56-850-4-001 Specify: Series TY-FRB(specify SIN), (specify K-factor),(specify) Horizontal Sidewall or Vertical Sidewall Sprinkler, Standard Response,Standard Coverage,(specify)temperature rating, (specify)finish or coating, P/N (specify from Table C) 1400 Pennbrook Parkway,Lansdale,PA 19446 I Telephone+1-215-362-0700 (L7/� /� /'��' 0 2018 Johnson Controls.All rights reserved.All specifications and other information shown were currant as of document revision date end are subject to change without notice. Johnson ISOI I %1 NATIONAL FIRE PROTECTION ASSOCIATION and NFPA are registered trademarks of National Fire Protection Association; Controls TEFLON Ise registered trademark of DuPont SECTION 6 Miscellaneous kfi' a a 121416\di, GUARANTEED FIRE SPRINKLER SPARE HEADBOXES 3 Need Box 12 Hoed Box i i 9,6 32` aG'P 6(LLV3J + Heavy duty 20 gauge steel u.. _ " construction 16510152) (6510150) Red powder coated finish 6 Hood Box Large Head Box r-_ Knockouts and shelf to accommodate any 1/2" or 3/4" sprinkler head All-welded construction and full ^ length hinge I .� « , y 1 Slotted for easy mounting with ,I _ _. _.._,__. 3,�5 screws, rivets or - . �t25' rts x:s+ CP CP._.__ strapping (6510151) <14 (6510151A) The information contained herein is produced in good faith and is believed to be reliable but is for guidance only.ARGCO and its agents cannot assume liability or responsibility for results obtained in the use of its product by persons whose methods are outside or beyond our control. It is the user's responsibility to determine the suitability of any of the products, methods of use,or preparation prior to use, mentioned in our literature. It is the user's responsibility to observe and adapt such precautions as may be advisable for the protection of personnel and property in the handling and use of any of our products. FOR MORE INFORMATION CALL ARGCO AT 1-800-854-1015 OR LOG ONTO WWW.ARGCO.COM illHydraulic Summary Il Job Number:240273-240273 Report Description:REMOTE AREA 1 Job Job Number Design Engineer 240273 AHoffman lob Name: State CertficatiordLicense Number 'unziker Warehouse 1 Nfess 1 AHJ 8001 SW Hunziker Street Address 2 Job Site/Building Tigard,OR 97223 Address 3 Drawing Name Hunziker Warehouse System Remote Area(s) Most Demanding Sprinkler Data Occupancy Job Suffix 25.2 K-Factor 138.03 at 30.000 CMSA 240273 Hose Allowance At Source Pressure Area of Application 250.00 30.000 NA Additional Hose Supplies Number Of Sprinklers Calculated Number Of Nozzles Calculated Coverage Per Sprinkler Node Flow(gom) 6 0 196.00ft2 AutoPeak Results:Pressure Far Remote Aree(sj Adjacent To Most Remote Area Left:90.599 Right:90.854 PROF6,S'S r...0 G1NE�c, %Total nose Bheama 99 �r 250.00 (li • ,. • System Flow Demand Total Water Required(Including Hose Allowance) �(rv�" v( 833.06 1083.06 s OREGO co Maximum Pressure Unbalance In Loops 0.000 ATF41SER 13 Lo Maximum Velocity Above Ground 17.78 between nodes 20 and 105 tif9jS L. DE-NI\Ga Hum Velocity Under Ground `40604.77 between nodes 17 and 15 EXPIRES: 12-31-2021 Volume capacity of Wet Pipes Volume capacity of Dry Pip, 3989.86ga1 Supplies Hose Flow Static Residual Flow Available Total Demand Required Safety Margin Node Name (gpm) (psi) (psi) @ (gpm) (psi) @ (gpm) (psi) (psi) 18 Water Supply 250.00 106.000 102.000 1555.00 103.951 1083.06 91.003 12.948 Contractor Contractor Number I Contact Nome Contact The 1 August Hoffman Designer Name of Contractor Phone Extension Red Hawk Fire Protection 360.984.3712 227 3801 Fruit Valley Road FAX Address 2 E-mail Vancouver Washington 98660 augusth©redhawkfp.com Address 3 Web-Site Suite D www.redhawkfp.com [.M,,©M.E.P.CAD,Inc. .MAutoSPRINK 2019 v15.1.13.0 9/27/2021 10:49:19AM Page 1 411 Hydraulic Graph Job Number:240273-240273 Report Description:REMOTE AREA 1 Water Supply at Node 18 150 _.._.__.__.__ _ 135 120 =Static Pressure 106.000 105 -- • 555.00 @ 102.000 833.06 91.003 90 1083.06 with hose streams J75 60 System demand curve 10 45 30 15 • 0 111111111 111111111 11 1 1 11 1 1 1 1 1 1 1 1 1 1 1 1 111111111 111111111 111111111 111111111 1 1 1 1 1 1 1 I I 0300 600 900 1200 1500 1800 2100 2400 2700 3000 Water flow,gpm Hydraulic Graph Water Supply at Node 18 Static:Pressure 106.000 Residual:Pressure 102.000 @ 1555.00 Available Pressure at Time of Test 103.951 @ 1083.06 System Daman 91.003 @ 833.06 ��}� System Demand(Inducting Hess Allowance at Source) 91.003 @ 1083.06 M.E.P.CAD,Inc. AutoSPRINK 2019 v15.1.13.0 9/27/2021 10:49:21AM Page 2 glii Node Analysis Job Number:240273-240273 Report Description:REMOTE AREA 1 Node Elevation(Foot) Fittings Pressure(psi) Discharge(gpm) 18 -3'-6 S 91.003 833.06 100 29'-4 Spr(-30.000) 30.000 _ 138.03 101 29'-4 Spr(-30.453) _ 30.453 139.06 "u"' 102 29'-4 Spr(-30.519) 30.519 139.22 103 29'-3 Spr(-30.065) 30.065 138.18 104 29'-3 Spr(-30.517) 30.517 139.21 105 29'-3 Spr(-30.588) 30.588 139.37 1 26'-11 P0(13'-8) 66.679 2 26'-10 P0(13'-8) 66.744 3 26'-9 P0(13.-8) 66.864 4 26'-7 P0(13'-8) 66.998 5 26'-6 P0(13'-8) 67.116 7 26'-4 P0(13'-8) 67.375 8 26'-3 P0(13'-8) 67.556 9 26'-2 P0(13'-8) 67.754 10 26'-1 P0(13'-8) 67.969 11 25'-11 P0(13'-8) 68.202 12 25'-10 P0(13'-8) 68.418 13 25'-9 P0(13'-8) 68.652 14 25'-8 P0(13'-8) 68.885 15 0'-6 83.870 17 -3'-6 E(31'-7) 90.989 19 26'-11 P0(13'-8),C(13'-8) 62.426 20 26'-10 P0(13'-8),C(13'-8) 62.617 21 26'-9 P0(13'-8),C(13'-8) 63.188 23 26'-4 P0(13'-8),C(13'-8) 64.501 24 26'-3 P0(13'-8) 64.771 25 26'-2 P0(13'-8),C(13'-8) 64.987 26 26'-1 P0(13'-8),C(13'-8) 65.158 27 25'-10 P0(13'-8),C(13'-8) 65.846 =u;,,• 28 25'-9 P0(13'-8),C(13'-8) 65.906 29 26'-7 P0(13'-8),C(13'-8) 63.668 30 26'-6 P0(13'-8) 63.983 31 25'-11 P0(13'-8),C(13'-8) 65.762 32 25'-8 P0(27'-10),C(27'-10) 65.980 ( ,©M.E.P.CAD,Inc. in AutoSPRINK 2019 v15.1.13.0 9/27/2021 10:49:22AM Page 3 ill 4 x l }R 4 5(��3?F Job Number:240273-240273 Report Description:REMOTE AREA 1 Pipe Type Diameter Flow Velocity HWC Friction Loss Length Pressure Downstream Elevation Discharge K-Factor Pt Pn Fittings Eq.Length Summary Upstream Total Length ill Route 1 BL 2.2030 66.47 5.59 120 0.032361 14'-0 Pf 0.453 100 29'-4 138.03 25.2 30.000 Sprinkler Pe 101 29'-4 30.453 14'-0 Pv BL 2.2030 205.53 17.30 120 0.261220 107'-5 Pf 35.177 101 29'-4 139.06 25.2 30.453 Sprinkler, 27'-3 Pe 1.048 1 26'-11 66.679 2P0(13'-8) 134.-8 Pv CM 6.3570 205.53 2.08 120 0.001498 14'-0 Pf 0.021 1 26'-11 66.679 Pe 0.044 2 26'-10 66.744 14'-0 Pv CM 6.3570 411.07 4.16 120 0.005402 14'-0 Pf 0.076 2 26'-10 205.54 66.744 Flow(q)from Route 3 Pe 0.044 3 26'-9 66.864 14'-0 Pv CM 6.3570 452.25 4.57 120 0.006446 14'-0 Pf 0.090 3 26'-9 41.18 66.864 Flow(q)from Route 15 Pe 0.044 4 26'-7 66.998 14'-0 Pv CM 6.3570 491.30 4.97 120 0.007513 11'-0 Pf 0.083 4 26'-7 39.04 66.998 Flow(q)from Route 16 Pe 0.035 5 26'-6 67.116 11'-0 Pv CM 6.3570 530.09 5.36 120 0.008647 22'-0 Pf 0.190 5 26'-6 38.80 67.116 Flow(q)from Route 2 Pe 0.070 7 26'-4 67.375 22'-0 Pv CM 6.3570 566.15 5.72 120 0.009766 14'-0 Pf 0.137 7 26'-4 36.06 67.375 Flow(q)from Route 7 Pe 0.044 8 26'-3 67.556 14'-0 Pv CM 6.3570 602.58 6.09 120 0.010961 14'-0 Pf 0.153 8 26'-3 36.43 67.556 Flow(q)from Route 14 Pe 0.044 9 26'-2 67.754 14'-0 Pv CM 6.3570 637.90 6.45 120 0.012179 14'-0 Pf 0.171 9 26'-2 35.32 67.754 Flow(q)from Route 6 Pe 0.044 10 26'-1 67.969 14'-0 Pv CM 6.3570 673.50 6.81 120 0.013466 14'-0 Pf 0.189 10 26-1 35.60 67.969 Flow(q)from Route 5 Pe 0.044 t' 11 25'-11 68.202 14'-0 Pv CM 6.3570 709.85 7.18 120 0.014841 12'-0 Pf 0.178 11 25'-11 36.35 68.202 Flow(q)from Route 11 Pe 0.038 12 25'-10 68.418 12'-0 Pv CM 6.3570 748.54 7.57 120 0.016372 12'-0 Pf 0.196 12 25'-10 38.69 68.418 Flow(q)from Route 8 Pe 0.038 13 25'-9 68.652 12'-0 Pv CM 6.3570 788.62 7.97 120 0.018031 11'-0 Pf 0.198 13 25'-9 40.08 68.652 Flow(q)from Route 9 Pe 0.035 14 25'-8 68.885 11'-0 Pv CM 6.3570 833.06 8.42 120 0.019956 127'-11 Pf 4.058 14 25'-8 44.44 68.885 Flow(q)from Route 13 75'-5 Pe 10.926 15 0'-6 83.870 2LtE(11'-4),2f(-0.000),CV(40'-3 203'-4 Pv ),BV(12'-7) FR 8.4500 833.06 4.77 140 0.003752 221'-7 Pf 5.386 15 0'-6 83.870 94'-10 Pe 1.734 17 -3'-6 90.989 3E(31'-7),BFP(-4.198) 316'-5 Pv UG 12.5200 833.06 2.17 150 0.000487 28'-5 Pf 0.014 17 -3'-6 90.989 Pe 18 -3'-6 91.003 Water Supply 28'-5 Pv 250.00 Hose Allowance At Source 18 1083.06 wo Route 2 BL 2.2030 71.56 6.02 120 0.037092 14'-0 Pf 0.519 100 29'-4 138.03 25.2 30.000 Sprinkler Pe 102 29'-4 30.519 14'-0 Pv BL 2.2030 210.77 17.74 120 0.273670 71'-10 Pf 30.859 102 29'-4 139.22 25.2 30.519 Sprinkler, 40'-11 Pe 1.048 19 26'-11 62.426 2P0(13'-8),C(13'-8) 112'-9 Pv CM 4.3100 210.77 4.63 120 0.010418 14'-0 Pf 0.146 **11110 19 26'-11 62.426 Pe 0.044 20 26'-10 62.617 14'-0 Pv CM,©M.E.P.CAD,Inc. p y AutoSPRINK 2019 v15.1.13.0 9/27/2021 10:49:23AM Page 4 At ill 2'i 17' j� i(f�r€)a 'i Job Number.240273-240273 Report Description:REMOTE AREA 1 Pipe Type Diameter Flow Velocity HWC Friction Loss Length Pressure Downstream Elevation Discharge K-Factor Pt Pn Fittings Eq.Length Summary Upstream Total Length "M 4.3100 421.99 9.28 120 0.037632 14'-0 Pf 0.527 26'-10 211.22 62.617 Flow(q)from Route 4 Pe 0.044 1 26'-9 63.188 14'-0 Pv CM 4.3100 380.81 8.37 120 0.031121 14'-0 Pf 0.436 21 26'-9 63.188 Pe 0.044 29 26'-7 63.668 14'-0 Pv CM 4.3100 341.77 7.52 120 0.025477 11'-0 Pf 0.280 29 26'-7 63.668 Pe 0.035 30 26'-6 63.983 11-0 Pv RN 2.2030 38.80 3.27 120 0.011951 207'-7 Pf 3.133 30 26'-6 63.983 P0(13'-8) 54'-7 Pe 5 26'-6 67.116 3P0(13'-8) 262'-2 Pv Route 3 BL 2.2030 66.33 5.58 120 0.032236 14'-0 Pf 0.451 103 29'-3 138.18 25.2 30.065 Sprinkler Pe 104 29'-3 30.517 14'-0 Pv BL 2.2030 205.54 17.30 120 0.261233 107'-5 Pf 35.179 104 29'-3 139.21 25.2 30.517 Sprinkler, 27'-3 Pe 1.048 2 26'-10 66.744 2P0(13'-8) 134'-8 Pv Route 4 BL 2.2030 71.85 6.05 120 0.037369 14'-0 Pf 0.523 103 29'-3 138.18 25.2 30.065 Sprinkler Pe 105 29'-3 30.588 14'-0 Pv BL 2.2030 211.22 17.78 120 0.274744 71'-10 Pf 30.980 105 29'-3 139.37 25.2 30.588 Sprinkler, 40'-11 Pe 1.048 20 26'-10 62.617 2P0(13'-8),C(13'-8) 112'-9 Pv v Route 5 CM 4.3100 266.92 5.87 120 0.016127 14'-0 Pf 0.226 23 26'-4 302.97 64.501 Flow(q)from Route 10 Pe 0.044 24 26'-3 64.771 14'-0 Pv CM 4.3100 230.48 5.07 120 0.012292 14'-0 Pf 0.172 24 26'-3 64.771 Pe 0.044 ,5 26'-2 64.987 14'-0 Pv CM 4.3100 195.16 4.29 120 0.009036 14'-0 Pf 0.127 25 26'-2 64.987 Pe 0.044 26 26'-1 65.158 14'-0 Pv RN 2.2030 35.60 3.00 120 0.010193 207'-7 Pf 2.811 26 26'-1 65.158 P0(13'-8),C(13'-8) 68'-2 Pe 10 26'-1 67.969 3P0(13'-8) 275'-9 Pv Gb Route 6 RN 2.2030 35.32 2.97 120 0.010046 207'-3 Pf 2.767 25 26'-2 64.987 P0(13'-8),C(13'-8) 68'-2 Pe 0.000 9 26'-2 67.754 3P0(13'-8) 275'-5 Pv v Route 7 RN 2.2030 36.06 3.03 120 0.010437 207'-3 Pf 2.875 23 26'-4 302.97 64.501 P0(13'-8),C(13'-8),Flow(q) 68'-2 Pe 7 26'-4 67.375 from Route 10 275'-5 Pv 3P0(13'-8) v Route 8 RN 2.2030 38.69 3.26 120 0.011891 148'-1 Pf 2.572 27 25'-10 123.21 65.846 P0(13'-8),C(13'-8),Flow(q) 68'-2 Pe 0.001 12 25'-10 68.418 from Route 12 216'-3 Pv 3P0(13'-8) e= Route 9 CM 4.3100 84.52 1.86 120 0.001922 12'-0 Pf 0.023 27 25'-10 123.21 65.846 Flow(q)from Route 12 Pe 0.038 28 25'-9 65.906 12'-0 Pv RN 2.2030 40.08 3.37 120 0.012693 148'-1 Pf 2.745 28 25'-9 65.906 P0(13'-8),C(13'-8) 68'-2 Pe 0.001 13 25'-9 68.652 3P0(13'-8) 216'-3 Pv v Route 10 CM 4.3100 302.97 6.66 120 0.020387 22'-0 Pf 0.449 10 26'-6 38.80 63.983 Flow(q)from Route 2 Pe 0.070 ` ✓3 26'-4 64.501 22'-0 Pv o Route 11 CM 4.3100 159.57 3.51 120 0.006226 73'-2 Pf 0.560 26 26'-1 35.60 65.158 Flow(q)from Route 5 16'-9 Pe 0.044 31 25'-11 65.762 2LtE(8'-4) 89'-11 Pv (1,©M.E.P.CAD,Inc. MAutoSPRINK 2019 v15.1.13.0 9/27/2021 10:49:23AM Page 5 4111144, 40 -ill Hydraulic Analysis ` Job Number:240273-240273 Report Description:REMOTE AREA 1 Pipe Type Diameter Flow Velocity HWC Friction Loss Length Pressure Downstream Elevation Discharge K-Factor Pt Pn Fittings Eq.Length Summary Upstream Total Length RN 2.2030 36.35 3.06 120 0.010597 148'-5 Pf 2.440 • 31 25'-11 65.762 P0(13'-8),C(13'-8) 81'-10 Pe 0.000 11 25'-11 68.202 3P0(13'-8),C(13'-8) 230'-3 Pv Route 12 CM 4.3100 123.21 2.71 120 0.003859 12'-0 Pf 0.046 31 25'-11 36.35 65.762 Flow(q)from Route 11 Pe 0.038 27 25'-10 65.846 12'-0 Pv cb Route 13 CM 4.3100 44.44 0.98 120 0.000585 11'-0 Pf 0.039 28 25'-9 40.08 65.906 Flow(q)from Route 9 55'-9 Pe 0.034 32 25'-8 65.980 P0(27.-10),C(27'-10) 66'-9 Pv RN 2.2030 44.44 3.74 120 0.015368 148'-1 Pf 2.904 32 25'-8 65.980 40'-11 Pe 0.001 14 25'-8 68.885 3P0(13'-8) 189'-0 Pv Route 14 RN 2.2030 36.43 3.07 120 0.010641 207'-3 Pf 2.786 24 26'-3 64.771 P0(13'-8) 54'-7 Pe 8 26'-3 67.556 3P0(13'-8) 261'-9 Pv cb Route 15 RN 2.2030 41.18 3.47 120 0.013346 207'-3 Pf 3.676 21 26'-9 63.188 P0(13'-8),C(13'-8) 68'-2 Pe -0.000 3 26'-9 66.864 3P0(13'-8) 275'-5 Pv Route 16 RN 2.2030 39.04 3.29 120 0.012092 207'-3 Pf 3.331 29 26'-7 63.668 P0(13.-8),C(13'-8) 68'-2 Pe 0.000 4 26'-7 66.998 3P0(13'-8) 275'-5 Pv Equivalent Pipe Lengths of Valves and Fittings(C=120 only) \ C Value Multiplier Actual Inside Diameter 4.87 Value Of C 100 130 140 150 ( Schedule 40 Steel Pipe Inside Diameter ) =Factor Multiplying Factor 0.713 1.16 1.33 1.51 Nov (/,,',,©M.E.P.CAD,Inc. wnAutoSPRINK 2019 v15.1.13.0 9/27/2021 10:49:23AM Page 6 ilk 1 Hydraulic Analysisi Job Number:240273-240273 Report Description: REMOTE AREA 1 Pipe Type Diameter Flow Velocity HWC Friction Loss Length Pressure Downstream Elevation Discharge K-Factor Pt Pn Fittings Eq.Length Summary Upstream Total Length Pipe Type Legend Units Legend Fittings Legend r ,, ,A0 Arm-Over Diameter Inch ALV Alarm Valve BL Branch Line Elevation Foot AngV Angle Valve CM Cross Main Flow gpm b Bushing DN Drain BalV Ball Valve DR DropDischarge gpm BFP Backflow Preventer DY Dynamic Velocity fps BV Butterfly Valve FM Feed Main Pressure psi C Cross Flow Turn 90° FR Feed Riser Length Foot cplg Coupling MS Miscellaneous Friction Loss psi/Foot Cr Cross Run OR Outrigger HWC Hazen-Williams Constant CV Check Valve RN Riser Nipple DelV Deluge Valve Pt Total pressure at a point in a pipe SP Sprig DPV Dry Pipe Valve ST Stand Pipe Pn Normal pressure at a point in a pipe E 90°Elbow UG Underground Pf Pressure loss due to friction between points EE 45°Elbow Pe Pressure due to elevation difference between indicated Eel 111/4°Elbow points Ee2 22'//Elbow Pv Velocity pressure at a point in a pipe f Flow Device fd Flex Drop FDC Fire Department Connection fE 90°FireLock(TM)Elbow fEE 45°FireLock(TM)Elbow flg Flange FN Floating Node fT FireLock(TM)Tee g Gauge GloV Globe Valve GV Gate Valve Ho Hose Hose Hose HV Hose Valve Hyd Hydrant LtE Long Turn Elbow mecT Mechanical Tee Noz Nozzle ,i,,,, P1 Pump In P2 Pump Out PIV Post Indicating Valve PO Pipe Outlet PRV Pressure Reducing Valve PrV Pressure Relief Valve red Reducer/Adapter S Supply sCV Swing Check Valve Spr Sprinkler St Strainer T Tee Flow Turn 90° Tr Tee Run U Union WirF Wirsbo WMV Water Meter Valve Z Cap ,I to, 0,,©M.E.P.CAD,Inc. ynAutoSPRINK 2019 v15.1.13.0 9/27/2021 10:49:23AM Page 7 NFPA 13 2019 Seismic Bracing Calculations Project Name: Hunziker Warehouse Brace Design: 6" Long Address: 8001 SW Hunziker St Contractor Name: Red Hawk Fire Protection City, State, Zip: Tirgard, Oregon 97223 Address: Prepared By: Hoffman,August City, State,Zip: , : 27-Sep-2021 Fax: Phone: Brace Information Per Table 18.5.11.8(b) Seismic Brace Attachments Maximum Length of Brace: 7'-0" Structure Attachment Fitting: Universal Structural Bracket, EG, 9/16" Hole Brace Length (ft): 5.82 Make: CADDY Model: CSBU1 Size of Brace (in): 1" - UL Load Rating (Ibs): 3000 Adjusted Per 18.5.2.3 (Ibs): 2121 Type of Brace: Sch 40 Pipe Structure Attachment Adapter: Steel Flange Adapter for 1/4"-3/4" Flange Brace Angle Range: 45-59 Degrees electrogalvanized Maximum Brace Spacing(ft): 80.00 Make: CADDY Model: CSBS1 Least Radius of Gyration* (in): 0.421 UL Load Rating (Ibs): 2765 Adjusted Per 18.5.2.3 (Ibs): 1955 kl/r Value:* 200 Sway Brace Fitting: 6" Single Pipe/Conduit Rigid Universal Sway Brace, Maximum Horizontal Load (Ibs): 1310 electrogalvanized Make: CADDY Model: CSB0600 UL Load Rating (Ibs): 2600 Adjusted Per 18.5.2.3 (Ibs): 1838 Fastener Information CSBSI CSBU1 Fastener Orientation: B 1 Structure: Bar Joist ` ‘er �>r 45-59 Degrees Fastener Qty: n/a Ro2DPRO \ FFS G N 0 Fastener Type: n/a � 799 ¢ ener Size: n/a s OR(EGO' F' ` tener Embedment: n/a Fastener Max. Load (Ibs): n/a :iboo 0, TF 18ER 13 4 Brace Orientation: Longitudinal tiq/s L oEJ1G Brace I.D. (on plan): New Configuration EXPIRES: 12-31-2021 Sprinkler System Zone of Influence (ZOI) Load Calculation(Fpw=Cp x Wp) Pipe Wt/ft 15%for Total Length Cp=0.50 per Pipe Description Total Wt Size (Ibs) Fittings Wt ft (ft) NFPA 13 2019 6" Sch 10 23.03 3.45 26.48 80.00 2,118.76 2018 IBC Sway Brace Attached to 6" Sch10 Pipe Horizontal Earthquake Load Weight of Misc. ZOI Valves and Fittings 0.00 Fpw=Cp x Wp Total Zone of Influence (ZOI) Weight ( Wp ) 2,118.76 Fpw=0.50 x 2,118.76 Fpw= 1,059.00 lbs *Excludes tension-only bracing systems !►r flV nt ©2018 nVent All rights reserved nVent,nVent CADDY,nVent ERICO,nVent ERIFLEX,and nVent LENTON are owned by nVent or its global affiliates. All other NFPA 13 2019 Seismic Bracing Calculations Project Name: Hunziker Warehouse Brace Design: 4" Long Address: 8001 SW Hunziker St Contractor Name: Red Hawk Fire Protection City, State, Zip: Tirgard, Oregon 97223 Address: Prepared By: Hoffman,August City, State, Zip: , Date: 27-Sep-2021 Fax: Phone: Brace Information Per Table 18.5.11.8(b) Seismic Brace Attachments Maximum Length of Brace: 7'-0" Structure Attachment Fitting: Universal Structural Bracket, EG, 9/16" Hole Brace Length (ft): 5.82 Make: CADDY Model: CSBU1 Size of Brace (in): 1" - UL Load Rating (Ibs): 3000 Adjusted Per 18.5.2.3 (Ibs): 2121 Type of Brace: Sch 40 Pipe Structure Attachment Adapter: Steel Flange Adapter for 1/4"-3/4" Flange Brace Angle Range: 45-59 Degrees electrogalvanized Maximum Brace Spacing (ft): 80.00 Make: CADDY Model: CSBS1 Least Radius of Gyration* (in): 0.421 UL Load Rating (Ibs): 2765 Adjusted Per 18.5.2.3 (Ibs): 1955 kl/r Value:* 200 Sway Brace Fitting: 4" Single Pipe/Conduit Rigid Universal Sway Brace, Maximum Horizontal Load (Ibs): 1310 electrogalvanized Make: CADDY Model: CSB0400 UL Load Rating (Ibs): 2600 Adjusted Per 18.5.2.3 (Ibs): 1838 Fastener Information CSBCSBSI Fastener Orientation: B � �\�,1� Structure: Bar Joist /AI.4 45-59 DegreesFastener Qty: n/a , Fastener Type: n/a • Fastener Size: n/a Fastener Embedment: n/a Fastener Max. Load (Ibs): n/a :1400 Brace Orientation: Longitudinal Brace I.D. (on plan): New Configuration Sprinkler System Zone of Influence (ZOI) Load Calculation(Fpw=Cp x Wp) Pipe Wt/ft 15%for Total Length Cp=0.50 per Pipe Description Total Wt Size (Ibs) Fittings Wt/ft ((ft) NFPA 13 2019 4" EDDY Flow 11.29 1.69 12.98 80.00 1,038.68 2018 IBC Sway Brace Attached to 4" EDDY_Flow Pipe Horizontal Earthquake Load Weight of Misc. ZOI Valves and Fittings 0.00 Fpw=Cp x Wp Total Zone of Influence (ZOI) Weight ( Wp ) 1,038.68 Fpw=0.50 x 1,038.68 Fpw= 519.00 Ibs *Excludes tension-only bracing systems `VIA Ir nVent 0 2018 nVent All rights reserved nVent,nVent CADDY,nVent(RICO,nVent ERIFLEX,and nVent LENTON are owned by nVent or its global affiliates, All other NFPA 13 2019 Seismic Bracing Calculations Project Name: Hunziker Warehouse Brace Design: 6" Lat Address: 8001 SW Hunziker St Contractor Name: Red Hawk Fire Protection City, State, Zip: Tirgard, Oregon 97223 Address: Prepared By: Hoffman, August City, State, Zip: , 27-Sep-2021 Fax: Phone: Brace Information Per Table 18.5.11.8(a) Seismic Brace Attachments Maximum Length of Brace: 3'-6" Structure Attachment Fitting: Universal Structural Bracket, EG, 9/16" Hole Brace Length (ft): 1.61 Make: CADDY Model: CSBU1 Size of Brace (in): 1" - UL Load Rating (Ibs): 3000 Adjusted Per 18.5.2.3 (Ibs): 2121 Type of Brace: Sch 40 Pipe Structure Attachment Adapter: Steel Flange Adapter for 1/4"-3/4" Flange Brace Angle Range: 45-59 Degrees electrogalvanized Maximum Brace Spacing (ft): 40.00 Make: CADDY Model: CSBS1 Least Radius of Gyration* (in): 0.421 UL Load Rating (Ibs): 3000 Adjusted Per 18.5.2.3 (Ibs): 2121 kl/r Value:* 100 Sway Brace Fitting: 6" Pipe/Conduit Rigid Quick Grip Lateral Sway Brace, Maximum Horizontal Load (Ibs): 4455 electrogalvanized Make: CADDY Model: CSBQG0600EG UL Load Rating (Ibs): 2015 Adjusted Per 18.5.2.3 (Ibs): 1425 Fastener Information CSBSI Fastener Orientation: B CSBUI Structure: Bar Joist 45-59 Degrees • - Cl�'--- Fastener Qty: n/a Fastener Type: n/a 'ener Size: n/a CSBQG0600EG I' tener Embedment: n/a Fastener Max. Load (Ibs): n/a `J Brace Orientation: Lateral Brace I.D. (on plan): 6" Lat Sprinkler System Zone of Influence (ZOI) Load Calculation(Fpw=Cp x Wp) Pipe Wt/ft 15%for Total Length Cp=0.50 per Pipe Description Ibs Fittings Wt/ft (ft) Total Wt Size (lbs) g NFPA 13 2019 6" Sch 10 23.03 3.45 26.48 40.00 1,059.38 2018 IBC Sway Brace Attached to 6" Sch10 Pipe Max Fpw Based on 6" Sch10 Pipe Horizontal Earthquake Load Weight of Misc. ZOI Valves and Fittings 0.00 Fpw=Cp x Wp Total Zone of Influence (ZOI) Weight ( Wp ) 1,059.38 Fpw=0.50 x 1,059.38 Max Fpw per NFPA 13 2019, Section 18.5.5.2 including Section 18.5.5.2.4 1900 lbs Fpw= 530.00 lbs *rycludes tension-only bracing systems 1r nVent 2018 nVent All rights reserved nVent,nVent CADDY,nVent ERICO,nVent ERIFLEX,and nVent LENTON are owned by nVent or its global affiliates. All other NFPA 13 2019 Seismic Bracing Calculations Project Name: Hunziker Warehouse Brace Design: 4" Lat Address: 8001 SW Hunziker St Contractor Name: Red Hawk Fire Protection City, State, Zip: Tirgard, Oregon 97223 Address: Prepared By: Hoffman,August City, State, Zip: , Date: 27-Sep-2021 Fax: Phone: Brace Information Per Table 18.5.11.8(b) Seismic Brace Attachments Maximum Length of Brace: 7'-0" Structure Attachment Fitting: Universal Structural Bracket, EG, 9/16" Hole Brace Length (ft): 5.82 Make: CADDY Model: CSBU1 Size of Brace (in): 1" - UL Load Rating (lbs): 3000 Adjusted Per 18.5.2.3 (Ibs): 2121 Type of Brace: Sch 40 Pipe Structure Attachment Adapter: Steel Flange Adapter for 1/4"-3/4" Flange Brace Angle Range: 45-59 Degrees electrogalvanized Maximum Brace Spacing (ft): 40.00 Make: CADDY Model: CSBS1 Least Radius of Gyration* (in): 0.421 UL Load Rating (Ibs): 3000 Adjusted Per 18.5.2.3 (Ibs): 2121 kl/r Value:* 200 Sway Brace Fitting: 4" Pipe/Conduit Rigid Quick Grip Lateral Sway Brace, Maximum Horizontal Load (Ibs): 1310 electrogalvanized Make: CADDY Model: CSBQG0400EG UL Load Rating (Ibs): 2015 Adjusted Per 18.5.2.3 (Ibs): 1425 Fastener Information CSBS I Fastener Orientation: B CSBU1 Structure: Bar Joist 45-59 Degrees 4111Z- 1 IF" Fastener Qty: n/a it Fastener Type: n/a Fastener Size: n/a ' CSBQG0400EG Fastener Embedment: n/a Fastener Max. Load (Ibs): n/a Brace Orientation: Lateral Brace I.D. (on plan): New Configuration Sprinkler System Zone of Influence (ZOI) Load Calculation(Fpw=Cp x Wp) Pipe Wt/ft 15%for Total Length Cp=0.50 per Pipe Description Total Wt Size (Ibs) Fittings Wt/ft (ft) NFPA 13 2019 4" EDDY Flow 11.29 1.69 12.98 40.00 519.34 2018 IBC Sway Brace Attached to 4" EDDY_Flow Pipe Max Fpw Based on 4" EDDY_Flow Pipe Horizontal Earthquake Load Weight of Misc. ZOI Valves and Fittings 0.00 Fpw=Cp x Wp Total Zone of Influence (ZOI) Weight (Wp ) 519.34 Fpw= 0.50 x 519.34 Max Fpw per NFPA 13 2019, Section 18.5.5.2 including Section 18.5.5.2.4 726 lbs Fpw= 260.00 lbs *Excludes tension-only bracing systems to n /ent ©2018 nVent All rights reserved nVent,nVent CADDY,nVent ERICO,nVent ERIFLEX,and nVent LENTON are owned by nVent or its global affiliates. All other i 4 IMPORTANT: READ CAREFULLY your use of the nVent CADDY®Bracing Systems Calculator(the"Calculator")is subject to the Terms of Use(the"Agreement")you cepted prior to your use of the Calculator software. Subject to the terms and conditions of the Agreement,nVent grants to you a ononexclusive,nontransferable license to use this software on only one computer at any one time.You may not copy,alter,decompile, disassemble,reverse engineer,sublicense,rent,lease, sell,loan,assign or otherwise distribute the software.nVent may terminate this ._ Agreement and your license grant if you fail to comply with the terms and conditions of this Agreement,in which event you must destroy all copies of the software and your rights to use this software will immediately end. # This Calculator and other materials are provided as a design aid for use by qualified persons who take full responsibility for the design of seismic and other bracing systems.The Calculator is based on the parameters and the criteria specified in the applicable fire sprinkler codes,effective as of the date of software release,you select.You assume sole responsibility to review and confirm the accuracy and correctness of the formula,the accuracy,completeness and currentness of the applicable fire sprinkler codes,the information used in the calculations and all results from the calculations.nVent is not responsible to perform these actions for you.To assist you in checking your work,hard copies of the calculations can be printed for your review and acceptance.Failure by you to review the calculations to your satisfaction may result in improper design specifications that could adversely affect the integrity of the bracing system being designed and built.nVent shall not be responsible for,among other things and all things whatsoever,(a)errors in,and your failure to review and assure the correctness of,the Calculator's formula,information,calculations or results; (b) modifications in the Calculator made by any person other than nVent;(c)the effect on the user's computer hardware,software or systems;(d)providing future updates to the Calculator regardless of possible changes to existing codes;or(e)otherwise. THE CALCULATOR AND OTHER MATERIALS,INFORMATION,SOFTWARE,PRODUCTS,SERVICES AND OTHER CONTENT CONTAINED IN THIS SOFTWARE OR PROGRAM ARE PROVIDED TO YOU"AS IS"AND WITHOUT REPRESENTATIONS,WARRANTIES OR CONDITIONS OF ANY KIND,WHETHER EXPRESS OR IMPLIED,INCLUDING, BUT NOT LIMITED TO,THE IMPLIED WARRANTIES OR CONDITIONS OF MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE,TITLE,NONINFRINGEMENT,SECURITY,CURRENTNESS OR ACCURACY.NVENT HAS MADE REASONABLE EFFORTS TO PROVIDE INFORMATION THAT IS CURRENT AND ACCURATE AS OF THE SOFTWARE RELEASE DATE ON THIS SOFTWARE OR PROGRAM,HOWEVER,NVENT ASSUMES NO RESPONSIBILITY FOR ANY ERRORS,OMISSIONS OR INACCURACIES WHATSOEVER.UNDER NO CIRCUMSTANCES WILL NVENT,ITS SUBSIDIARIES AND AFFILIATES,AND ITS OR THEIR OFFICERS,DIRECTORS,EMPLOYEES AND REPRESENTATIVES, `E LIABLE FOR ANY LOSS OR DAMAGE CAUSED BY YOUR USE OF THE SOFTWARE OR PROGRAM OR YOUR LIANCE ON INFORMATION OBTAINED THROUGH THIS SOFTWARE,PROGRAM,MATERIALS,INFORMATION, SERVICES AND OTHER CONTENT.IT IS YOUR RESPONSIBILITY TO EVALUATE THE ACCURACY,COMPLETENESS, CURRENTNESS AND USEFULNESS OF ANY INFORMATION PROVIDED,AND USE OF THIS SOFTWARE OR PROGRAM IS SOLELY AT YOUR OWN RISK. IN NO EVENT SHALL NVENT BE LIABLE FOR ANY SPECIAL,INCIDENTAL,DIRECT,INDIRECT,PUNITIVE OR CONSEQUENTIAL DAMAGES OF ANY KIND,OR ANY DAMAGES WHATSOEVER,WHETHER IN CONTRACT,TORT, STRICT LIABILITY OR OTHERWISE(INCLUDING,WITHOUT LIMITATION,THOSE RESULTING FROM(I)RELIANCE ON THE SOFTWARE,PROGRAM OR MATERIALS PROVIDED,(II)COSTS OF REPLACEMENT GOODS,(III)LOSS OF USE,DATA OR PROFITS,(IV)DELAYS OR BUSINESS INTERRUPTIONS,AND(V)ANY OTHER THEORY OF LIABILITY),ARISING OUT OF OR IN CONNECTION WITH THE USE OF,OR INABILITY TO USE THE CALCULATOR,WHETHER OR NOT NVENT HAS BEEN ADVISED OF THE POSSIBILITY OF SUCH DAMAGES. Upon reasonable request by nVent,you agree to defend,indemnify,and hold harmless nVent and its employees,contractors,officers and directors from any and all liabilities,losses,claims and expenses,including reasonable attorneys' fees,that arise from your use or misuse of this Calculator,information,products,software,materials or program and/or any nVent services,your non-compliance or compliance with these Terms of Use,or your violation of any third-party rights.nVent reserves the right,at its own expense,to assume the exclusive defense and control of any matter otherwise subject to indemnification by you,in which event you will cooperate with nVent in asserting any available defenses. Neither you nor anyone acting on your behalf,including your employees,acquire any intellectual property or other proprietary rights, including patents,designs,trademarks,copyright or trade secrets,relating to the Calculator,software,programs and materials,except t as otherwise expressly granted herein.Any rights not expressly granted herein are reserved. You agree to comply with all applicable laws,regulations,orders and rules,including those related to export of this software, ( programs or materials.Your use of other nVent products must be in accordance with the nVent documentation applicable to such products including instruction sheets,data sheets,warnings,application drawings and user manuals. nVent CADDY,nVent ERICO,nVent ERIFLEX,and nVent LENTON are either registered trademarks or trademarks of nVent in the f.iiik S.and/or other countries. 11 contents of the software,program and other materials are©2018 nVent.All rights reserved. ,U nVent t J 2018 nVent All rights reserved nVent,nVent CADDY,nVent ERICO,nVent ERIFLEX,and nVent LENTON are owned by nVent or its global affiliates, All other trademarks are the property of their respective owners nVent reserves the right to change specifications without prior notice.