Report Zi-oct�-rs
- ME COPY RECEIVED 220
SYSTEM OJutF TIG 21
SENSOR' CITY AR
�-lJILDiNG DiGMSIoh�
Indoor Selectable- "
Output Strobes and
Horn Strobes for _==_
Ceiling Applications
r i,}
System Sensor L-Series audible visible notification
products are rich with features guaranteed to cut I,,
installation times and maximize profits with lower
current draw and modern aesthetics. A?'
Features The System Sensor L-Series offers the most versatile and
• Plug-in design with minimal intrusion into the back box easy-to-use line of horns,strobes,and horn strobes in the industry
with lower current draws and modern aesthetics.With white and red
• Tamper-resistant construction plastic housings,wall and ceiling mounting options,System Sensor
• Automatic selection of 12-or 24-volt operation L-Series can meet virtually any application requirement.
at 15 and 30 candela
• Field-selectable candela settings on ceiling units: The entire L-Series product line of ceiling-mount strobes and horn
15,30, 75,95, 115, 150,and 177 strobes include a variety of features that increase their application
versatility while simplifying installation.All devices feature a plug-in
• Horn rated at 88+dBA at 16 volts design with minimal intrusion into the back box,making installations
• Rotary switch for horn tone and two volume selections fast and foolproof while virtually eliminating costly and• time-
consuming ground faults.
Universal mounting plate for ceiling units
• Mounting plate shorting spring feature checks wiring continuity To further simplify installation,the L-Series utilizes a universal
before device installation mounting plate so installers can mount them to a wide array of back
• Electrically Compatible with legacy SpectrAlert and SpectrAlert boxes.With an onboard shorting spring, installers can test wiring
Advance devices continuity before the device is installed.
• Compatible with MDL3 sync module
Installers can also easily adapt devices to a suit a wide range of
• Listed for ceiling mounting only application requirements using field-selectable candela settings,
automatic selection of 12-or 24-volt operation,and a rotary switch
for horn tones with two volume selections.
Agency Listings
SIGNALING
LISTED APPROVED
55512 FM appeoved except 71251653'0504
S4C11 for ALERT models 7135-16530503
3057383
L-Series Specifications
Architect/Engineer Specifications
General
L-Series ceiling-mount strobes and horn strobes shall mount to a standard 4 x 4 x 11/2-inch back box,4-inch octagon back box,or double-
gang back box.Two-wire products shall also mount to a single-gang 2 x 4 x 17/8-inch back box.A universal mounting plate shall be used
for mounting ceiling and wall products.The notification appliance circuit wiring shall terminate at the universal mounting plate.Also,L-Series
products,when used with the Sync•Circuit'"'Module accessory,shall be powered from a non-coded notification appliance circuit output
and shall operate on a nominal 12 or 24 volts.When used with the Sync•Circuit Module,12-volt-rated notification appliance circuit outputs
shall operate between 8.5 and 17.5 volts;24-volt-rated notification appliance circuit outputs shall operate between 16.5 and 33 volts.Indoor
L-Series products shall operate between 32 and 120 degrees Fahrenheit from a regulated DC or full-wave rectified unfiltered power supply.
Ceiling strobes and horn strobes shall have field-selectable candela settings including 15,30,75,95,115,150,and 177.
Strobe
The strobe shall be a System Sensor L-Series Model listed to UL 1971 and shall be approved for fire protective service.The strobe
shall be wired as a primary-signaling notification appliance and comply with the Americans with Disabilities Act requirements for visible
signaling appliances,flashing at 1 Hz over the strobe's entire operating voltage range.The strobe light shall consist of a xenon flash tube and
associated lens/reflector system.
Horn Strobe Combination
The horn strobe shall be a System Sensor L-Series Model listed to UL 1971 and UL 464 and shall be approved for fire protective
service.The horn strobe shall be wired as a primary-signaling notification appliance and comply with the Americans with Disabilities Act
requirements for visible signaling appliances,flashing at 1 Hz over the strobe's entire operating voltage range.The strobe light shall consist
of a xenon flash tube and associated lens/reflector system.The horn shall have two audibility options and an option to switch between a
temporal three pattern and a non-temporal(continuous)pattern.These options are set by a multiple position switch.The horn on horn strobe
models shall operate on a coded or non-coded power supply.
Synchronization Module
The module shall be a System Sensor Sync•Circuit model MDL3 listed to UL 464 and shall be approved for fire protective service.The module
shall synchronize L-Series strobes al 1 Hz and horns at temporal three.Also,while operating the strobes,the module shall silence the horns
on horn strobe models over a single pair of wires.The module shall mount to a 4 1 V16 x 4 11/16 x 2 1/8-inch back box.The module shall also
control two Style Y(class B)circuits or one Style Z(class A)circuit.The module shall synchronize multiple zones.Daisy chaining two or more
synchronization modules together will synchronize all the zones they control.The module shall not operate on a coded power supply.
Physical/Electrical Specifications
Standard Operating Temperature 32°F to 120°F(0°C to 49°C)
Humidity Range 10 to 93%non-condensing
Strobe Flash Rate 1 flash per second
Nominal Voltage Regulated 12 VDC or regulated 24 DC/FWR1
Operating Voltage Range 8 to 17.5 V(12 V nominal)or 16 to 33 V(24 V nominal)
Operating Voltage Range(MDL3) 8.5 to 17.5V(12 V nominal)or 16.5 to 33 V(24V nominal)
Input Terminal Wire Gauge 12 to 18 AWG
Ceiling-Mount Dimensions(including lens) 6.8"diameter x 2.5'high(173 mm diameter x 64 mm high)
Ceiling-Mount Surface Mount Back Box Skirt Dimensions 6.9'diameter x 3.4 high(175 mm diameter x 86 mm high)
(SBBCRL,SBBCWL)
Notes:
1.Full Wave Rectified(FWR)voltage is a non-regulated,time-varying power source that is used on some power supply and panel outputs.
2.P,S,PC,and SC products will operate at 12 V nominal only for 15 and 30 cd.
AVU566800
UL Current Draw Data
UL Max.Strobe Current Draw(mA RMS)
8-17.5 Volts 16-33 Volts
Candela DC DC FWR
15 87 41 60
30 153 63 86
75 N/A 111 142
95 N/A 134 164
115 N/A 158 191
150 N/A 189 228
177 N/A 226 264
UL Max.Current Draw(mA RMS),2-Wire Horn Strobe
8-17.5 Volts 16-33 Volts
DC Input 15cd 30cd 15cd 30cd 75cd 95cd 115cd 150cd 177cd
Temporal High 103 167 71 90 143 165 187 217 254
Temporal Low 96 165 54 71 137 161 185 211 249
Non-Temporal High 106 173 71 90 141 165 187 230 273
Non-Temportal Low 95 166 54 71 124 161 170 216 258
3.1K Temporal High 111 164 69 94 147 163 184 229 257
3.1K Temporal Low 103 163 54 68 143 155 185 212 252
3.1K Non-Temporal High 111 172 69 94 144 164 202 229 271
3.1K Non-Temporal Low 103 169 54 88 131 155 187 217 259
16-33 Volts
FWR Input 15cd 30cd 75cd 95cd 115cd 150cd 177cd
Temporal High 107 135 179 198 223 254 286
Temporal Low 78 101 151 172 199 229 262
Non-Temporal High 107 135 179 198 223 254 286
Non-Temportal Low 78 101 151 172 199 229 262
3.1K Temporal High 108 135 179 200 225 255 289
3.1K Temporal Low 79 101 150 171 196 229 260
3.1K Non-Temporal High 108 135 179 200 225 255 289
3.1K Non-Temporal Low 79 101 150 171 196 229 260
Horn Strobe Tones and Sound Output Data
Horn and Horn Strobe Output(dBA)
8-17.5 16-33
Volts Volts
Switch Position Sound Pattern dB DC DC FWR
1 Temporal High 84 89 89
2 Temporal Low 75 83 83
3 Non-Temporal High 85 90 90
4 Non-Temporal Low 76 84 84
5 3.1 KHz Temporal High 83 88 88
6 3.1 KHz Temporal Low 76 82 82
7 3.1 KHz Non-Temporal High 84 89 89
8 3.1 KHz Non-Temporal Low 77 83 83
AVDSB6800
L-Series Dimensions
2.47
1.37 06.92 - 2.50 1
0'6.83
__ •pp,wrrn _li i \o O o\P -
I
I
0
1: goo ®g
_...y)
_ ��
Ceiling-Mount Horn Strobes Ceiling Surface Mount Back Box
jrp
Ceiling Mount Horn Strobes with Ceiling Surface Mount Back Box
L-Series Ordering Information
Model Description Model Description
Ceiling Horn Strobes Ceiling Strobes
PC2RL 2-Wire,Horn Strobe,Red SCRL Strobe,Red
PC2WL 2-Wire,Horn Strobe,White SCWL Strobe,White
SCWL-CLR-ALERT Strobe,White,ALERT
Accessories
TRC-2 Universal Ceiling Trim Ring Red
TRC-2W Universal Ceiling Trim Ring White
SBBCRL Ceiling Surface Mount Back Box,Red
SBBCWL Ceiling Surface Mount Back Box,White
_'' SYSTEM02017 System Sensor.
`_ ✓ I� 3825 Ohio Avenue•St.Charles,IL 60174 Product scearcaiionssubiecuc Orange without nano.Visit aystemsenso,.com
\_V SENSOR' Phone:800-SENSOR2•Fax:630-377-6495 f0f 00�ent product nformation Mauding the Wrest version of the date sheet
AVDS88801•03117