Report 13UP202-I - 00111
81=C6 Haas Wiz tz..p .
OFFICE COPY RECEIVED
Date: 12/29/20
Time: 03:00 pm CITY OF TIGARD
Job Number: LK 5448 BUILDING DIVISION
Technician: Dylan Harvey
estern States
Fire Protection Co.
Ploteetal 4u. tad Plafterty
a subsidiary of API ,
JOB SITE INFORMATION
Company Name: Biamp
Street Address: 8005 SW Hunziker street
City,State,ZIP: Tgard,OR.97223
Phone Number: 503.536.5520(Brent)
Fax Number: Nicole@deeringmanagementgroup.com
Site Contact: Brent Kearsly/Nicole Cristoforo
BILLING INFORMATION
Company Name:
Street Address:
City, State,ZIP:
Phone Number:
Fax Number:
Site Contact:
WESTERN STATES FIRE PROTECTION
17500 SW 65th Ave.Lake Oswego,OR.97035
Phone Number 503.657.5155 Fax Number 503.657.5182 A 2
R
API Group Inc. is a member of the U.S. Green Building Council ®Ef;
Western States Fire Protection
Albuquerque, NM: Centennial, CO: Fort Collins, CO: Pflugerville, TX: San Antonio,TX: Nampa, ID: Casper, WY:
Lakewood, CA: Colorado Springs, CO: Houston, TX: Phoenix, AZ: Spokane, WA: Missoula, MT: Glenwood Springs, CO:
Black Hawk, SD: Grand Prairie,TX: Oregon City, OR: Redmond,WA: Sacramento, CA: Upland, CA: El Paso, TX:
National Fire Suppression
Decatur,IL:Kansas City,KS:Maryland Heights,MO:
Statewide Fire Protection
Las Vegas, NV
ittP6 Western States
Fire Protection Co.
Pitereete49 Zeeea aid Pub
a subsidiary of API Croup,aw.
Date: 12/29/2020 Job Number: LK5448
►.GENERAL ,.. _ - - ct .1.= =• = 'tES( NA NC3'
A.(To be answered by the Owner or the Owner's representative) Was owner available? Owner/Rep.Signature
1. Have there been any changes in the occupancy classification,machinery or operations since the last inspection? V
2. Have there been any changes or repairs to the fire protection systems since the last inspection? V
3. If a fire occurred since the last inspection,have all damaged sprinkler system components been replaced? ✓
4. Has the piping in all dry systems been checked for proper pitch within the past five years? V
Date last checked
5. Has the piping in all systems been checked for obstructive materials?
Date last checked 109/15/16
6. Have all fire pumps been tested to their full capacity through the use of hose streams or flow meters within the ✓
past 12 months?
7. Are gravity,surface or pressure tanks protected from freezing? V
8. Are any of the sprinklers 50 years old or older? (Testing and/or replacement is recommended for such sprinklers.) ✓
9. Are any extra high temperature solder sprinklers regularly exposed to temperatures near 300°F? V
B.'To be answered by the inspector)
1. Have the sprinkler systems been extended to all visible areas of the building? ✓
2. Does there appear to be proper clearance between the top of all storage and the sprinkler deflector? V
3. In building areas protected by a wet system,does it appear to be heated,including its blind attics and perimeter ✓
areas,where accessible?
4. Does it appear that visible exterior openings are protected against the entrance of cold air? ✓
2.CONTROL VALVES
A.Are sprinkler system main control valves readily visible and in the appropriate open or closed position? ✓
B. If the valve(s)had seals were they broken in order to operate the valves? ✓
C. Was the Owner or the Owners representative notified that the seal(s)were removed if they could not be replaced? ✓
Easily Access ble Signs Valve Open Supervision
No.of Sealed,Supervised or operational
Control Valves Valves Type Locked
Yes No Yes No Yes No Yes ' i NO I:
North riser 1 BFV ✓ V V Supervised
South riser 1 BFV V _ ✓ V Supervised V
Backflow 2 OS&Y ✓ ✓ ✓ Locked
3.WATER SUPPLIES Pressure Fire Pump&Tank N/A
A. Weser supply source,City or Private? Cify Pressure Fire Pump&City N/A
Pressure Fire Pump&Pond N/A
Other N/A
Water flow Test Results Made During This Inspection
Size Test Static Flow Static Static Flow Static
Test Pipe Located Pressure Psi Test Pipe Located Size Test Pipe Pressure Pressure
Pipe Pressure Pressure After
Before After Before
S. Riser 2.00 105 90 97 ---.._..
N. Riser 2.00 102 90 107
4.TANKS,PUMPS,FIRE DEPT.CONNECTIONS YES NA NO
A.Do fire pumps,gravity,surface or pressure tanks appear to be in good external condition? ✓
B.It appears that gravity,surface and pressure tanks are at the proper pressure and/or water levels? _ ✓
C.It appears that fire department connections are in satisfactory condition,couplings free,caps or plugs in place and check valves tight? ✓
D.Are fire department connections visible and accessible? ✓
Page 1 Fire Sprinkler Inspection
Western States
Fire Protection Co.
Ppiteavit9. 44Le4 add Pe
a subsidiary al AP!poop,inc.
Date: 12/29/2020 Job Number: LK5448
5.WET SYSTEMS YES NIA I NO
A. No.of Systems 2 Make&Model 8"shotgun with flow switch
B. Was the date of the gauge(s)checked,since gauges are required to be tested with a calibrated gauge or replaced every five years?
ri :
If tested with a calibrated gauge and the gauge was not within 3%over the full scale they must be recalibrated or replaced ✓
C. If applicable,have any dry type heads more than 10 years old had a representative sample tested ✓
D. Have all known and readily apparent antifreeze systems been tested? ✓
E. Date antifreeze systems were tested
F. The antifreeze tests indicate protection to temperature: Sys.1 Sys.2 Sys.3 Sys.4 Sys.5
G. Did alarm valves,water flow alarm indicators and retards test satisfactorily? I V I I
1 6.DRY SYSTEMS Qtly.
A. No.of systems N/A Make&Model
Partial Full 11.117
B.Are the air pressure and priming water levels normal?
C. Did the air compressor operate satisfactorily?
D.Were readily accessible and visible low points drained during this inspection?
E. Were dry system trip tests performed? (If yes,see DPV Trip Test Report)
F. Do dry valves appear to be protected from freezing?
1-1
G.Is the dry valve house heated?
7.SPECIAL SYSTEMS Qtly.
A. No.of systems N/A Make&Model
Type BFV
B. Were all known valves tested as required?
C. Did all heat responsive systems operate satisfactorily:
D. Did the supervisory features operate during testing?
Heat Responsive Devices Type Type of Test
Valve No. 1 2 3 4 5 6 Valve No. 7 8 9 10 11 11
Valve No. 12 13 14 15 16 17 Valve No. 18 19 20_ 21 22 23
Valve No. 24 25 26 27 28 29 Valve No. 30 31 32_ 33_ 34_ 35
Auxiliary Equipment No. Type
Location
Testing Results
8.ALARMS YES N/A NO
A. Did the water motor(s)and gong(s)operate during testing? V
B. Did the electric alarm(s)operate during testing? V
C. Did the supervisory alarm service test satisfactorily? V
D.Was the alarm panel free of alarm and trouble signals upon your arrival If no,please explain below V
E. Was the alarm panel clear of alarm and trouble signals upon your departure If no,please explain below ✓
9.SPRINKLERS•PIPING
A. Do sprinklers generally appear to be in good external condition? V
B. Do sprinklers generally appear to be free of corrosion or loading and visible obstructions? ✓ ,
C.Are extra sprinklers available on the premises? ✓
D. Does the exterior condition of the fire sprinkler system appear to be satisfactory? V
E. Does hand hose on the sprinkler system appear to be in satisfactory condition? V
EXPLANATION OF ANY PREVIOUS ANSWERS ABOVE THAT MAY REPRESENT A PROBLEM..OR COMMENTS FROM THE INSPECTOR.
Page 2 Fire Sprinkler Inspection
titi6 Western States
Fire Protection Co.
ptitateefief 444e4 aod polefuntf
a subsidiary of ISM GPOUP,
Date: 12/29/2020 Job Number: LK5448
THE INSPECTOR SUGGESTS THE FOLLOWING IMPROVEMENTS.
HOWEVER,THESE SUGGESTIONS ARE NOT THE RESULT OF AN ENGINEERING SURVEY:
Deficiencies:
No FDC sign with building address(Need to add 8005 on the FDC. It serves both 8001 and 8005 buildings)
Missing chrome 401 trim inside office by S riser room.
'no sprinkler coverage under north roll up door
No indication of sprinkler gauges being calibrated or replaced.Required to be tested every 5 years in service
11101
;t s t 4xj'
Notes: � -`:._.
Building Site Notes:
1. Backflow located in vault by 8001 bldg on Hunziker
2.5-year sprinkler internal pipe inspection due in 9/2021,on the wet South system,32ft lift needed.
3.Sprinkler gauges due for replacement or calibration in 2020(x2)
4. FDC check valve flush/hydro test due in 9/2021. Grooved check inside vault,also serves 8001 building
5. Is a scissor lift rental needed to reach sprinkler pipe?Yes, t °"
47'4-
F r
ALL LISTED CHANGES IN THE OCCUPANCY HAZARD OR FIRE PROTECTION EQUIPMENT,AS ADVISED BY THE OWNER IN SECTION:
Signature of Owner or Owner's Representative
Printed Name Date: 12/29/2020
Does the owner/owner's representative want a copy of this report sent to another location? (i.e.Insurance,Main Office,etc.)
DUPLICATE TO:
STREET: ZIP:
CITY&STATE:
ATTN:
Page 3 Fire Sprinkler Inspection