Plans (2) FOR OFFICE USE ONLY—SITE ADDRESS: This form is recognized by most building departments in the Tri-County area for transmitting information. Please complete this form when submitting information for plan review responses and revisions. This form and the information it provides helps the review process and response to your project. City of Tigard • COMMUNITY DEVELOPMENT DEPARTMENT Transmittal Letter 13125 SW Hall Blvd. • Tigard,Oregon 97223 • 503.718.2439 • v.ww,tiaard-or.goy TO: I -T` DATE DEPT: BUIL15ING DIVISION " y ED JUL i >_ 2021 FROM: -' CITY OF TIGARD COMPANY: tt_ �L BUILDING DIVISION PHONE: �u ' C? t�—47 y7 7 2. RE: C ?2 S�� ca ` OVA , {''_- A c;2A Z, 69 k 1 t (Sit ddress) (Permit Number) PAL-u1P (Project name or subdivision name and lot number) ATTACHED ARE THE FOLLOWING ITEMS: Copies: Description: Copies: Description: Additional set(s)of plans. Revisions: Cross section(s) and details. Wall bracing and/or lateral analysis. Floor/roof framing. Basement and retaining walls. Beam calculations. )c Engineer's calculations. Other(explain):REMARKS: 'KQ,O1 5e.tk. cr� i "2—� '' k `ll' (1,A- ) �!b A.4.(t tz-ttl r & S ' Apt FOR OFFICE USE ONLY Rout to Permit Tec uian: Date: p_ ) L) �� Initials: Fees Due: Y No Fee Description: Amount Due: Special Instructions: Reprint Permit(per PE): []Yes ❑No ❑ Done Applicant Notified: r Date: Initials: 1:1BuildinglFonns\TransmittalLetter-Revisions o61316.doc , . OFFICE COPY VECTOR....) APPROVED 1=_ nG l n e E R s REVISION VSE Project Number:U4373.0009.211 F --,.‘ •o ) ^ 0 O July 7,2021 1 ----itPro-Slat Solar Group .7 J 9 - 2 1 1721 NE 64th Ave,Ste 120 Vancouver,WA 98661 RECEIVED REFERENCE: Palmrose Residence: 13265 Southwest Bull Mountain Road,Portland,OR 97224 Pro-Stat Solar Group Project: PNW0503 JUL 1 4 ZOZI Solar Array Installation CITY OF TIGARD To Whom It May Concern: BUILDING DIVISION Per your request, we have reviewed the existing structure at the above referenced site. The purpose of our review was to determine the adequacy of the existing structure of the home to support the proposed installation of solar panels on the roof as shown on the panel layout plan for the resident home,not the garage included in the array. Based upon our review,we conclude that the existing home structure is adequate to support the proposed solar panel installation. Design Parameters Code: Oregon Structural Specialty Code,2019 Edition(2018 IBC) Risk Category:II Design wind speed,Vult:97 mph (3-sec gust)per ASCE 7-16 Wind exposure category:B Ground snow load,Pg: 10 psf Minimum roof snow load,Pm:20 psf(not reducible) Seismic design category:D Existing Roof Structure Roof structure:2x4 rafters @ 24"o.c. Roofing material: composite shingles Roof slope: 18° Connection to Roof Mounting connection:(1)5/16"lag screw w/min.2" threaded embedment into framing at max.48"o.c.along rails (2)rails per row of panels,evenly spaced;panel length perpendicular to the rails not to exceed 71 in.Rail cantilever shall not exceed 50%of connection spacing. Conclusions Based upon our review, we conclude that the existing home structure is adequate to support the proposed solar panel installation. See attached calculations. 651 W.Galena Park Blvd.,Ste. 101/Draper, UT 84020/T(801)990-1775/F (801)990-1776/www.vectorse.com VSE Project Number: U4373.0009.21 l EC1 'O R Palmrose Residence 7/7/2021 E fl G I Cl E E R S The solar array will be flush-mounted (no more than 10" above the roof surface) and parallel to the roof surface. Thus, we conclude that any additional wind loading on the structure related to the addition of the proposed solar array is negligible. The attached calculations verify the capacity of the connections of the solar array to the existing roof against wind (uplift), the governing load case. Regarding seismic loads, we conclude that any additional forces will be small. Conservatively neglecting the weight of existing wall materials, the installation of the solar panels represents an increase in the total weight (and resulting seismic load) of 3.1%. Because the increase in lateral forces is less than 10%, this addition meets the requirements of the exception in Section 806.3 of the 2018 IEBC.Thus the existing lateral force resisting system is permitted to remain unaltered. Limitations Installation of the solar panels must be performed in accordance with manufacturer recommendations. All work performed must be in accordance with accepted industry-wide methods and applicable safety standards. The contractor must notify Vector Structural Engineering, LLC should any damage,deterioration or discrepancies between the as-built condition of the structure and the condition described in this letter be found. Connections to existing roof framing must be staggered,except at array ends, so as not to overload any existing structural member. The use of solar panel support span tables provided by others is allowed only where the building type, site conditions, site-specific design parameters, and solar panel configuration match the description of the span tables. The design of the solar panel racking(mounts,rails,etc.)and electrical engineering is the responsibility of others. Waterproofing around the roof penetrations is the responsibility of others. Vector Structural Engineering assumes no responsibility for improper installation of the solar array. VECTOR STRUCTURAL ENGINEERING,LLC 96640PE EXPIRES: 12/31.2022 07/07/2021 Coleman Larsen,P.E. Project Engineer Enclosures CDL/zrm 651 W. Galena Park Blvd.,Ste. 101/Draper, UT 84020/T(801)990-1775/F(801)990-1776/www.vectorse.com Ecr 0 R JOB NO.: U4373.0009.211 SUBJECT: CONNECTION ,' ,V E n G I rl E E R S PROJECT: Palmrose Residence Calculate Uplift Forces on Connection Pressure Max Trib. Max Uplift Max Trib. Width 2 (0.6 Dead -0.6 Wind) Area Force (psf) (ft) (ft2) (Ibs) Zone 1, 2e 16.7 4.0 11.8 197 Zone 2n, 2r, 3e 24.9 4.0 11.8 295 Zone 3r 30.2 4.0 11.8 358 Calculate Connection Capacity Lag Screw Size [in]: 5/16 Cd: 1.6 NDS Table 2.3.2 Embedment3 [in]: 2 Grade: SPF (G = 0.42) Nominal Capacity [Ibs/in]: 205 NDS Table 12.2A Number of Screws: 1 Prying Coefficient: 1.4 Total Capacity [Ibs]: 469 Determine Result Maximum Demand [Ibs]: 358 Lag Screw Capacity [Ibs]: 469 Result: Capacity > Demand, Connection is adequate. Notes 1. 'Max Trib. Width' is the width along the rails tributary to the connection. 2. 'Max Trib Area' is the product of the 'Max.Trib Width' and 1/2 the panel width/height perpendicular to the rails. (2) rails per row of panels. Length of panels perpendicular to the rails shall not exceed 71". 3. Embedment is measured from the top of the framing member to the beginning of the tapered tip of the lag screw. Embedment in sheathing or other material is not effective.The length of the tapered tip is not part of the embedment length. , , ECT 0 R E n G 1 fl E E R S JOB NO.: U4373.0009.211 SUBJECT: GRAVITY LOADS PROJECT: Palmrose Residence GRAVITY LOADS Roof Pitch: 3.9 :12 Design material Increase due to Material weight ROOF DEAD LOAD (D) weight [psf] pitch [psf] Composite Shingles 2.1 1.05 2.0 1/2" Plywood 1.1 1.05 1.0 Framing 3.0 3.0 Insulation 0.0 0.0 1/2" Gypsum Clg. 0.0 1.05 0.0 M, E & Misc 2.0 2.0 Total Existing Roof DL 8.2 PV Array DL 3.2 1.05 3 ROOF LIVE LOAD (Lr) Existing Design Roof Live Load [psf] 20 ASCE 7-16 Table 4.3-1 Roof Live Load With PV Array [psf] 0 2019 OSSC, Section 1607.13.5 SNOW LOAD (S): Existing w/ Solar Array Roof Slope [x:12]: 3.9 3.9 Roof Slope [°]: 18 18 Ground Snow Load, pg [psf]: 10 10 ASCE 7-16,Section 7.2 Terrain Category: B B ASCE 7-16,Table 7.3-1 Exposure of Roof: Fully Exposed Fully Exposed ASCE 7-16,Table 7.3-1 Exposure Factor, Ce: 0.9 0.9 ASCE 7-16,Table 7.3-1 Thermal Factor, Ct: 1.1 1.1 ASCE 7-16,Table 7.3-2 Risk Category: II II ASCE 7-16,Table 1.5-1 Importance Factor, Is: 1.0 1.0 ASCE 7-16,Table 1.5-2 Flat Roof Snow Load, pf [psf]: 7 7 ASCE 7-16, Equation 7.3-1 Minimum Roof Snow Load, pm [psf]: 20 20 ASCE 7-16,Section 7.3.4 Unobstructed Slippery Surface? No Yes ASCE 7-16,Section 7.4 Slope Factor Figure: Figure 7-2b Figure 7-2b ASCE 7-16, Section 7.4 Roof Slope Factor, Cs: 1.00 0.87 ASCE 7-16, Figure 7.4-1 Sloped Roof Snow Load, ps [psf]: 7 6 ASCE 7-16, Equation 7.4-1 Design Snow Load, S [psf]: 20 20 VECTOR E n G I n e E R s JOB NO.: U4373.0009.211 SUBJECT: WIND PRESSURE PROJECT: Palmrose Residence Components and Cladding Wind Calculations Label: Solar Panel Array Note: Calculations per ASCE 7-16 SITE-SPECIFIC WIND PARAMETERS: Basic Wind Speed [mph]: 97 Notes: Exposure Category: B Risk Category: II ADDITIONAL INPUT& CALCULATIONS: Height of Roof, h [ft]: 25 (Approximate) Comp/Cladding Location: Gable Roofs 7°<0<_ 20° Enclosure Classification: Enclosed Buildings Zone 1, 2e GCp: 2.00 Figure 30.3-2B Zone 1, 2e Ya: 0.77 Fig. Zone 2n, 2r, 3e GCp: 2.90 (negative coeff.) Zone 2n, 2r, 3e ya: 0.77 29.4-8 Zone 3r GCp: 3.47 Zone 3r ya: 0.77 a: 7 Table 26.11-1 zg [ft]: 1200 Table 26.11-1 Kh: 0.67 Table 26.10-1 Ke: 0.98 Table 26.9-1 Kn: 1 Equation 26.8-1 Kd: 0.85 Table 26.6-1 Velocity Pressure, qh [psf]: 13.3 Equation 26.10-1 yE: 1.50 Section 29.4.4 WIND PRESSURES: Equation 29.4-7 p = qh(GC1,)('E)(ya) Zone 1, 2e, p [psf]: 30.8 psf (1.0 W) Zone 2n, 2r, 3e, p [psf]: 44.6 psf (1.0 W) Zone 3r, p [psf]: 53.4 psf(1.0 W) (a = 3 ft) VECTOR E n G I n E E R s JOB NO.: U4373.0009.211 SUBJECT: SEISMIC LOADS PROJECT: Palmrose Residence CHECK INCREASE IN OVERALL SEISMIC LOADS Estimated Roof Dead Load 12.2 psf Solar Dead Load 3.0 psf % Roof Covered 13% Equiv. Total Dead Load 12.5 psf Addt'l Seismic Weight 3.1% Conservatively neglecting the weight of existing wall materials, the installation of the solar panels represents an increase in the total weight(and resulting seismic load)of 3.1%. Because the increase is less than 10%, this addition meets the requirements of the exception in Section 806.3 of the 2018 IEBC. Thus the existing structure is permitted to remain unaltered. Fs„ F,p, 9 VECTOR Abbrev GRADES (psi) (psi) E„(psi) (Ih/ft') JOB NO.: U4373.0009211 DF1x1 DFL#1 1.000 180 1.7oo.000 32 E m G I Il E E R S ['FLIP DFL#2 900 180 1,600,000 32 DF1(6X) DFL41 5X5 8 LARGER 1,350 170 1.600,000 32 SPF#2 SPF#2 875 135 1,400,000 26.2 SP#2 SP#2 1,100 175 1400,000 34.31,100 175 1400,000 34.3 PROJECT: Palmrose Residence SUBJECT: BEAMS 24F-V4 24F-V4 2.400 240 1,800,000 32 24F-V8 24F-V8 2400 240 1,800,000 40 LVL(1.9) LVL(1.9X106E) 2,60D 285 1,900,000 40 DESIGN LOADS: Load Types: Snow Live Dead LVL(2.0) LVL(2.OX106E) 2,200 285 2,000,000 42 Roof 20 20 8 CRITERIA(LI) DTI DLL D1)1 LSL LSL(1.3%106E) 1.700 400 1.300,000 42 R Solar 3.2 • (oLeNK) 120 180 STL36 GRADE 36 STEEL 21,600 14400 29,000,000 490 ST1_46 GRADE 46 STEEL 27,700 16.500 29,000,000 490 STL50 GRADE 50 STEEL 30,000 20,000 29,000,000 490 Point Point ID Add1 Add! A Live Dead m 0 Roof Floor Wall Live Solar Point $ Dist Load Load as ; A 1.5DL Length Trib Trib Trib Load Load Load y 'a' 'PLC 'PDC r9- =v A Mm„ Maio„. V . VNiw D-n DT1aya DLL DuIow. GLB Label 'L'(ft) (ft) (ft) (ft) (plf) (plf) From in (ft) (Ib) )lb) w Grade Size z —y C, Co CFv R.(Ib) Rs(Ib) (ft-Ib) (ft-lb) (Ib) (Ib) (in) (in) (In) (in) Camb Check Rafter 6 2 6.3 (1) SPF#2 2X4 1.15 1.15 1.50 188 188 282 443 170 543 0.243 0.600 0.155 0.400 0.64 M Home Detail )VECTOR �REo PROFFs Elevation z12"Section 3111.4.8.1 l E n 0 i n E E R 9 �5 �� N�F� S o <18"Section 3111.5.3.5 651 W.GALENA PARK SLED.STE. I0) PHONE(BB))990.I775 A 07/07/2021 O RAPER.LITAN B4OZO www.vEcroRSE.caN \ ; 9 96640PE — Vector Structural Engineering has reviewed the existing / / // 2 SE Project Number:U4373.0009.211 structure with loading from the solar array and screw _�, .1 18" connections to the existing framing.The design of the racking system,racking connections,and all other — structural is by others.Mechanical,architectural,and all 0 1/0 11111 �0 Z 24' other nonstructural aspects of the design are by others. 0� �, 10 D� r� Electrical is by others,unless stamped by Dean Levorsen. F414N p . \''' 23' 36"Pathway Section 3111.3.4.8.4(smoke vents) Ground to eve Ground to peak >_12"Section 3111.4.8.1 (ridge) EXPIRES: 12/31/2022 / chimney ��// Spans / Weight of solar<4.5 lb/sgft chirrney 36" Pathway Comp roof, single layer Section i 3111.3.4.8.4 2x4 Rafters 24" OC (smoke vents) sureye1 70r6" o J 1x6 ridge 2x4 rafters 24"OC L39.9'1 2x4 supports 24"OC 2x6 beam 2x8 joists 6 Solar Array Setbacks: �12" along all horizontal ridges per Section 3111.4.8.1 Suneye Legend (degrees): Page 2 of 4 36" Pathway around heat vents per Section 3111.4.8.4 1. Tilt= 18 Azimuth = 180 Job: Address: Solar Array Coverage: PNW503 Gerald Palmrose Solar Array Attachments: Solar racking attachments per Solar Array sgft=431 Rev: 13265 SW Bull Mountain Road 3111.3.5.3.3 24" OC within 3' of edge hip eve or ridge, 48" Roof Surface sgft= 3515 Portland, OR 97224 OC elsewhere Solar Array covers 12% of roof surface AM PROSTAT ELECTRIC & SOLAR Plot 103' VECTOR C n O I rl E E R S 651 W.GALENA PARK BLVD.STE. 701 PHONE(50]1 990-7775 DRAPER,UTAH 54020 WWW.VECTORSE.CUM R0 PRNFFS 96640PE . r- 11111LC: Barn ooF v ����`� tiiq N D EXPIRES: 12/31/2022 07/07/2021 VSE Project Number:U4373.0009.211 Utility Meter Vector Structural Engineering has reviewed the existing Main Panel home structure and not the garage structure with loading from the solar array and screw connections to the existing AC Disco framing.The design of the racking system.racking \ connections,and all other structuralis by others. Combiner i Mechanical,architectural,annall d all other nonstructural aspects of the design are by others.Electrical is by 357' others,unless stamped by Dean Leversen. Home ll eto �Io4 hie. Aio Job: Address: Page 1 of4 da PNW503 Gerald Palmrose • Rev: 13265 SW Bull Mountain Road Portland, OR 97224 AM PROSTAT ELECTRIC & SOLAR Comp Roof Attachments spaced so that 2x framing 24" Max on Center no point load exceeds 50 psf Solar Pane t 4.5PSF max "Il/ECTOR E n 0 1 f1 E E R 9 651 W.GALENA PARK BLVD.STE. 101 PHONE(6011 990-1775 • DRAPER,OTAN 84020 WWW.VEGTORSE.COM <�0:i PROFe. • J�. ��,� f,`F� s'0 Racking Details: Panel connected J 96640PE Manufacturer= Iron Ridge to rails with 1 connector ``_ - - �/ / Model = XR100 for each 8 Sq feet or less per rack manufacturer's specs `� ti�� o �^ o� o�• o `p`L �F Attachment Details: � ., F�iq N p �P� Manufacturer= Iron Ridge Aluminum Rails to alternate b Model = FlashFoot2 EXPIRES: 12/31/2022 roof framing 4' OC max. • • 07/07/2021 Two rails per min. per panel . VSE Project Number:U4373.0009.211 Vector Structural Engineering has reviewed the existing structure with loading from the solar array and screw connections to the existing framing.The design of the + racking system,racking connections,and all other r • structural is by others.Mechanical,architectural,and all other nonstructural aspects of the design are by others. Electrical is by others,unless stamped by Dean Levorsen. I I Panels 39.98"X 70.67" aprox. 2X joist/truss to meet Oregon Solar code span requirements 18rr Page 4 of 4 Min fg"SS lag embedded 2"min Max Job: Address: center of framing member 2 Layers or less of roof material PNW503 Gerald Palmrose Rev: 13265 SW Bull Mountain Road lashed and sealed Portland, OR 97224 roof penetration AM PROSTAT ELECTRIC & SOLAR