Loading...
Report (2) OFFICE CGI�y �i(0(00 alcS'r� UR/0 RECEIVED APR 2021 CITY OF TIGARD 'BUILDING DIVISION 111411111.11(11 FIRE PROTECTION PO BOX 1705 OREGON CITY, OR 97045 503-593-9791 www.centurionfirepro.com SUBMITTAL PACKAGE HIGHKEY LABORATORY 9600 SW OAK STREET TIGARD,OR 97232 yTURto+ FIRE PROTECTIO\ .. n ■ roc - _,.... _ _ Z . " n.n... _. c 16RY : - C VW We -i tw a x a. .Z., L w {uG o... ® - s w i RIN PIP . , g. Trust Bull Moose when it comes to protecting your most valuable assets. As the leading manufacturer of steel sprinkler pipe, we understand that there are no second chances in fire suppression. You need products of enduring quality and exceptional strength—plus reliable service. You need Bull Moose. • UL listed(US&Canada)and FM approved • We have the most stocking locations in industry,for best delivery and availability • ASTM A135 and A795 Type E, Grade A Certified • Plain end or roll groove • Complies with NFPA-13,13R and 14 • Eddy Guard II''bacterial-resistant internal coating • Industry-leading hydraulic characteristics. • Custom length options • CRR of 1.0 and greater • Hot dipped galvanization • All pipe NDT weld tested • Reddi-Pipe®red pipe to eliminate field painting Exclusive maker of ReddiPipe® • Compatible for use in wet,dry, preaction red painted pipe. and deluge sprinkler systems c us LISTED O APPROVED ; ion NFPA >o k!. jfj - 800.325.4467 BULL NEEDS salesc bullmooseindustries.eom TUBE :u IMooseTube•com Bull Moose Fire Sprinkler Pipe Product Information . Ni ,M 11 n 2" O n 11 /4 1-1/2 2-V2 3 4 0.0.(in) 1.660 1.900 2.375 2.875 3.500 4.500 I (in) 1.530 1.128 2.203 2.705 3.334 4.310 rty Weight(II 1.222 1.844 2330 2.809 3.361 4.968 CJ •r (Ib/ft) 2.019 2.860 3.982 5.299 7.144 11.290 U- ›, C R R. 1.98 3.44 2.78 1.66 1.00 1.00 G G •erLi . 61 61 37 30 19 19 W Weight(Ibs)2 1,565 2,362 1,810 1,770 1,341 1,982 Lift Weight(Ibs)24'Ien• 1,789 2,700 2,069 2,022 1,533 2,265 Lift Weight(Ibs)25'lengths 1,864 2,812 2,155 2,107 1,596 2,360 O.D.(in) 1.315 1.660 1.900 2.375 2.875 3.500 4.500 6.625 8.625 I .(in) 1.097 1.442 1.682 2.157 2.635 3.260 4.260 6357 8.249 C 0 EmptyWeiight(If/ft) 1.410 1.810 2.090 2.640 3.530 4.340 5.620 9.290 16.940 W J Water Filled Weight(Ib/ft) 1.820 2.518 3.053 4.223 5.893 7.957 11.796 23.038 40.086 Q C.R.R. 15.27 9.91 7.76 6.27 4.92 3.54 2.50 1.158 1.805 W = Pieces per Lift 91 61 61 37 30 19 19 10 7 1-1 vi Lift Weight(Ibs)21'lengths 2,695 2,319 2,677 2,051 2,224 1,732 2,242 1,951 2,490 Lift Weight(Ibs)24'lengths 3,079 2,650 3,060 2,344 2,542 1,979 2,563 2,230 2,848 Lift Weight(Ifs)25'lengths 3,208 2,760 3,187 2,442 2,648 2,062 2,670 ) 11111(in) 1.295 1.650 1.900 2.375 pI.E. n) 1.083 1.418 1.645 2.123 Rzr Weight1.461 2.010 2.547 3.308 1 Q 1.860 2.754 3.468 4.842 W c . 1.00 1.00 1.00 1.00 ~ P. 70 51 44 30 } Geight(Ib2,148 2,217 2,353 2,084 GWWeight(Ib2,454 2,534 2,690 2,382 Lift Weight(Ibs)25 lengths 2,557 2,639 2,802 2,481 0.D.(in) 1.315 1.660 1.900 2.375 2.875 3.500 4.500 I.D.(in) 1.049 1.380 1.610 2.061 2.469 3.068 4.026 C CrEmpty Weight(lb/ft) 1.680 2.270 2.720 3.660 5.800 7.580 10.800 W Water Filled Weight(lb/ft) 2.055 2.918 3.602 5.114 7.875 10.783 16.316 J =G C.R.R. 1.00 1.00 1.00 1.00 1.00 1.00 1.00 W 2 Pieces per Lift 70 51 44 30 30 19 19 1.J VILift Weight(Ibs)21'lengths 2,470 2,431 2,513 2,306 3,654 3,024 4,309 Lift Weight(Ibs)24'lengths 2,822 2,778 2,872 2,635 4,176 3,456 4,925 Lift Wright(Ifs)2 lengths 2,940 2,894 2,992 2,745 4,350 3,601 5,130 '_I. ,jt 800.325.4467 .axa DULL T/[OOSE" sales® hullmooseindustries.com TUBE :u IMooseTube.com FIG. ITT-'I Threaded Mechanical Branch Tee =)AUK= SPF/FINVIL" Mechanical branch connections for reducing branch outlets without welding. The MT-1 is a bolted saddle type fitting with NPT female threaded outlets. Design assures superior sealing, full pipe support, excellent stability and easy installation. For the latest UL/ULC listed, LPCB, VdS and FM Approved pressure ratings versus pipe schedule, see www.anvilintl.com or contact your local Anvil Representative. cam EM a [vds] LISTED APPROVED For Listngo1Approval Details and Limitations,visit our website at www.arrvilintl.com or contact an Anvil Sales Representative. MATERIAL SPECIFICATIONS HOUSING: GASKETS: Materials Ductile Iron conforming to ASTM A-536,Grade 65-45-12 Properties as designated in accordance with ASTM D-2000. ANSI BOLTS & HEAVY HEX NUTS: ❑Grade"E"EPDM(Green color code) Heat treated,oval-neck track head bolts conforming to ASTM A-183 -40°F to 230°F(Service Temperature Range)(-40°C to 110°C) Grade 2 with a minimum tensile strength of 110,000 psi and heavy hex nuts Recommended for water service,diluted acids,alkalies solutions, of carbon steel conforming to ASTM A-563 Grade A or Grade B,or SAE oil free air and many chemical services. J995 Grade 2.Bolts and nuts are provided zinc electroplated as standard. NOT FOR USE IN PETROLEUM APPLICATIONS. METRIC BOLTS & HEAVY HEX NUTS: Heat treated,zinc electroplated oval-neck track head bolts made of carbon steel with mechanical properties per ISO 898-1 Class 8.8.Hex nuts and bolts are zinc electroplated followed by a yellow chromate dip. COATINGS: ❑Rust inhibiting paint Color:ORANGE(standard) ❑Hot Dipped Zinc Galvanized(optional) ❑Other available options: Example:RAL3000 or RAL9000 Series For other coating requirements contact an Anvil Representative. LUBRICATION: ❑Standard Gruvlok ❑Gruvlok XtremeT"'required For dry pipe systems and freezer applications. PROJECT INFORMATION APPROVAL STAMP Project: DApproved Address: ['Approved as noted Contractor: ❑Not approved Engineer: Remarks: Submittal Date: Notes 1: Notes 2: FP-4.12 FIG. MT-1 Threaded Mechanical Branch Tee 0 ANIVIL )FF/ NVIL" T t .Q• \ V t { 1 , MT-1 THREADED MECHANICAL BRANCH TEE Nominal Hole Dimensions Max. Dimensions Bolt Approx. Size 0.0. Working V Size WI.Ea. Min.Diameter Max.Diameter Pressure♦ T Threaded W Y Z In./DN(mm) In./mm In./mm Inimm PSI/bar InJmm In.1mm In./nun In./mm In/mm In./mm Lbs./Kg 2x1 2.375x1.315 1/ 1s/6 300 1's/i6 2% 11/46 45 21/2 3/ax2 1.7 50x25 60.3x33.7 38 41 20.7 50 67 40 Ill 63 0.8 2x11/4 2.375x1.660 13/4 1% 300 1'Y16 2% 19/6 4% 2'h Ysx2 1.7 50 x 32 60.3 x 42.4 44 48 20.7 49 67 40 117 63 0.8 2 x 11/2 2.375 x 1.900 13/4 12/e 300 1'Y16 2% 19/6 4% 2% 3/e x 2 1.7 50x40 60.3x48.3 44 48 20.7 49 67 40 117 73 0.8 21/2x1 2.875x1.315 11/2 1Ye 300 21/46 31/2 111/46 59/16 3% 1/2x2% 3.6 65x25 73.0x33.7 38 41 207 62 79 46 141 86 1.6 21/2 x 1/4 2.875 x 1.660 2 2'/s 300 21/26 3'/a 113A6 59/16 3% 12 x 23/4 3.6 65x32 13.0142.4 51 54 20.7 62 79 46 141 86 1.6 21/2 x 11/2 2.875 x 1.900 2 2'/a 300 216 3'// 1"/16 59/16 3% '/x 23/4 3.6 65 x 40 13.0 x 48.3 51 54 207 62 79 46 141 86 1.6 3 x 1 3.500 x 1.315 11/2 1 h 300 23/4 32/i6 21/2 61/4 315/16 12 x 23/4 3.8 80x25 88.9x33.7 38 41 20.7 71 87 55 159 99 1.7 3 x 11/4 3.500 x 1.660 2 21/2 300 21 32%6 21/2 61/4 315/16 /2 x 23/ 3.8 80x32 88_9x424 51 54 20.7 70 87 55 159 99 1.7 3 x 11/2 3.500 x 1.900 2 2/ 300 23/4 32/6 21/2 61/4 315/16 h x 23/4 3.8 80 x 40 88.9 x 48.3 51 54 20.7 70 87 55 159 99 1.7 3x2 3.500x2.375 21/2 2% 300 23/ 31/46 21/2 61/4 315/6 1/2x23/4 4.4 80x50 88.9x60.3 64 67 20.7 70 87 55 159 99 2.0 4x1 4.500 x 1.315 11/2 1% 300 31/46 4 2% 71/4 313/6 12x23/4 4.6 100 x 25 114.3 x 33.7 38 41 20.7 85 102 67 184 97 2.1 4 x 11/4 4.500 x 1.660 2 21e 300 35/Is 4 2% 71/4 311/46 12 x 2% 4.6 100 x 32 114.3 x 42.4 51 54 20.7 84 102 67 184 97 2.1 4 x 11/2 4.500 x 1.900 2 2/ 300 35/16 4 2% 7'// 373/16 1/2 x 23/4 4.6 100x40 114.3x48.3 51 54 20.7 84 102 67 184 97 2.! 4 x 2 4.500 x 2.375 21/2 2% 300 3%s 4 2% 71 41/2 12 x 23/4 4.8 100 x 50 114.3 x 60.3 64 67 20.7 84 102 67 184 115 2.2 4 x 21/2 4.500 x 2.875 2% 2% 300 3'A6 4 2% 11/4 41/2 /2 x 23/4 5.4 100 x 65 114.3 x 73.0 70 73 20.7 78 102 67 184 115 2.4 4 x 3 4.500 x 3.500 31/2 3% 300 3 4/ 2% 71/2 51/2 /2 x 2% 5.4 100 x 80 114.3 x 88.9 89 92 20.7 76 105 67 184 130 2.4 5 x 11/2 5.563 a 1.900 2 2/ 300 41/46 43/4 31/46 8%s 313/16 %x 4 7.4 125x40 141.3x48.3 51 54 20.7 /03 121 Si 211 97 3,4 5 x 2 5.563 x 2.375 21/2 2% 300 4/6 43/4 33/i6 8%6 313/16 %x 4 7.9 125x50 141.3x60.3 64 67 20.7 103 121 Si 211 97 3.6 5 x 21/2 5.563 x 2.875 23/4 2% 300 31116 43/4 31/46 8/6 313/6 %x 4 7.9 125x65 1473x730 70 73 20.7 97 121 Si 211 97 3.6 6 x 11/4 6.625 x 1.660 2 21/ 300 313/16 415/16 311/16 9% 3'/e %x 4 8.0 150 x 32 168.3 x 42.2 51 54 20.7 97 126 94 238 98 3.6 6 x 11/2 6.625 x 1.900 2 2/ 300 47/i6 5/ 3II/ 93/e 3% 5/9 x 4 7.5 150x40 168.3x48.3 51 54 20.7 113 130 94 238 98 3.4 6 x 2 6.625 x 2.375 21/2 2% 300 49/i6 5/ 3"/i6 9% 42%6 %a 4 8.0 150x50 168.3x60.3 64 67 20.7 112 130 94 238 112 3.6 6 x 21/2 6.625 x 2.875 2%< 292 300 43/46 51/2 3"/6 9% 4%o Y x 4 8.0 150 x 65 168.3 x 13.0 70 73 20.7 106 130 94 238 112 3.6 6 x 3 6.625 x 3.500 31/2 3% 300 41/2 51/4 3"/i6 9% 55/e %x 4 9.7 150 x 80 168.3 x 88.9 89 92 20.7 105 133 94 238 143 4.4 8 x 2 8.625 x 2.375 21/2 2% 300 5%6 61/4 42% 103%6 4'/i6 3/4 x 41/4 10.2 200x50 219.1x60.3 64 67 20.7 138 159 123 312 112 40 All sizes may be used as mechanical crosses. Threads are NPT per ANSI/ASME B1.20.1 A WARNING A-Working Pressure Ratings are for reference only and based on Sch.40 pipe.For the latest UL/ULC,FM,VdS and LPCB pressure For dry pipe systems and freezer applications ratings versus pipe schedule,please visit anvilind.com or contact your local Anvil Representative. lubrication of the gasket is required, Gruvloke XtremeTe"Lubricant is required. FP-4.1 2 Ductile Iron Threaded Fittings . . . .... . ...,;:, ....,,,,,,,,„,.,2„.,.... .... __.......... ............... \.. .. . ,. ., ,;• ....... „:„ :: ,... , .., ax 4715t. J Ce I ',/p.7 .F' iY V�_"'a4+wr`" ➢'m'.Pp''Y r t +6 p /•t .T; - w �u ,�•. LyP : Ate. 4 ii• .., n3 - S ITH„ C OO Pit r R� INTERNATIONAL Ductile Iron Threaded Fittings Specifications • branded ductile iron threaded fittings are UL Listed and FM Approved at 500 psi • Rated to 300 WSP C el US • Ductile iron castings conform to ASTM A536 LISTED • Fitting dimensions conform to ASME B16.3 • Bushings and plugs conform to ASME B16.14 41> • Fittings are 100% air tested APPROVED • NPT threads on all fittings conform to ASME B1.20.1 • Independent lab verification that fittings meet applicable chemical &physical properties • Manufacturing facilities are ISO 9001:2008 and ISO 14001 Temperature Working Pressure, Nonshock psiG Degrees F 300# Class Threaded Fittings -20 to 100 500 150 500 200 480 250 460 300 440 350 420 400 400 450 380 500 360 550 340 600 320 650 300 - ~i Ductile Iron Fittings- Class 300 UL/FM I !).!WIT/?LUZ C ® US APPROVED Fig. 35E 3- 90°Elbow LISTED IIIA Size A Packing Weight Part Number -111 in in Inner Master Ib ___� 1/2 3563004 1.13 100 200 0.2 3/4 35E 3006 1.31 70 140 0.3 A I 35E 3010 1_50 40 80 0.5 j��; I 1/4 35E 3012 1.75 25 50 0.8 1-1/2 35E 3014 1-94 18 36 1.1 2 35E 3020 2.25 10 20 1.8 2-1/2 35E 3024 2.70 4 8 3.2 7Fig. 35RE3-90°Reducing Elbow f B Size Part Number A B Packing Weighi in in in Inner Master Ib �4 x 1/2 358E3006004 1.20 1.22 80 160 0.3 1 x 1/2 35RE3010004 1.26 1.36 70 140 0.4 nail A 1 x 3/4 35RE30100D6 1.38 1.45 50 100 0.4 1-1/4 xi/2 35RE3012004 1.34 1.53 35 70 0.5 1-1/4 x 3/4 35RE3012006 1.45 1.63 35 70 0.6 1-1/4 x 1 35RE3012010 1.58 1.67 30 60 0.7 1-1/2 x 1/2 35RE3014004 1.52 1.75 30 60 0.6 1-1/2 x 3/4 35RE3014006 1.52 1.75 25 50 0.7 1-1/2 x 1 35RE3014010 1.65 1.80 20 40 0.8 1-1/2 x 1-1/4 35RE3014012 1.82 1.88 18 36 1.0 2 x 112 35RE3020004 1.60 1.97 18 36 1.0 2 x 3/4 35RE3020006 1.60 1.97 18 36 1.0 2 x 1 35RE3020010 1.73 2.02 16 32 1.2 2 x 1-1/4 35RE3020012 1.90 2.10 12 24 1.3 D 2 x 1-1/2 35RE3C20014 2.02 2.16 10 20 1.5 U 2-1/2 x 1-1/2 35RE3024014 2.16 2.51 6 12 2.2 C 2-1/2 x 2 35RE3024020 2.39 2.60 6 12 2.5 T I Fig. 35F 3-45°Elbow L Size A Packing Weight E in Part Number in Inner Master lb / 1/2 35F3004 0.88 150 300 0.2 le3/4 35F 3006 0.98 80 160 0.3 a 1 35F 3010 13 40 80 0.5 1-1/4 35F 3012 1.29 25 50 0.7 I�,i TA 1-1/2 35F 3014 1.44 20 40 1.0 � 1 2 35F 3020 1.69 10 20 1.6 2-1/2 35F3024• 1.95 4 8 2.7 Fig. 35T 3- Tee Size A Packing Weight Part Number ,OI in in Inner Master Ib A 1 i2 35T 3004 L 13 80 160 0.3 3!4 35T 3006 1.31 30 60 0.5 35T 301 25 50 0.7 I I y 1-1/4 35T 3012 1.76 10 20 1.1 - A >I< A • 1-1/21 35T 3014 1.94 10 20 1.5 2 35T 3020 2.25 6 12 2.4 2-1/2 35T 3024 2.70 4 8 4.3 111 SMITH-COOPER INTERNATIONAL' • TOLL FREE 1-800-766-0076 • FAX(323)890-4456 • www.smithcooper.com \::, _ Ductile Iron Fittings-Class 300 UL/FM Q€ALIT`1 PLf35 c ® us APPROVED Fig. 35RT3-Reducing Tee LISTED Size A B C Packing Weight Part Number illisi �oE in n in in Inner Master lb - 1 VC 3/4 x 1/2 35RT30060D4 1.70 1.20 1.22 6D 120 0.4 1 x 1/2 35RT3010004 1.26 1.26 36 30 60 0.6 -��--1- 1 x 1/2 xl 35RT3010D04010 1-50 1.36 1.50 30 60 0.6 1 x 3/4 358T3010006 1.38 1.38 1.45 25 50 0.6 B 3 1 x 3/4 x 3/4 35R13010006006 1.38 1.31 1.45 35 70 0,6 1 x 3/4 x 1 35RT3010006010 1.50 1.45 1.50 25 50 0.7 1-1/4x 1/2 35RT3012004 1 34 1-34 1.53 20 40 0.8 1-1/4 x 1/2 x 1-1/4 35RT3012004012 1.75 1.53 1.75 25 50 0.9 1-1/4 x 3/4 35RT3012006 1 45 1.45 1.62 15 30 0.9 1-1/4 x 3/4 x 1-1/4 35RT3012006012 1.75 1.62 1.75 20 40 1.0 1-1/4x1 35RT3012010 1.58 1.58 -..67 15 30 1.0 1-1/4 x 1 x 1/2 35RT3012010004 1.34 1.26 1.53 25 50 0.7 1-1/4 x 1 x 3/4 35RT3012010000 1.45 1.38 1-63 20 40 0.8 1-1/4 x 1 x 1 35RT3012010010 1.58 1.50 1.69 20 40 0.9 1-1/4 x 1 x 1-1/4 35RT3012010012 1.75 1.69 1.75 15 30 1.0 1-1/2 x 1/2 35RT3014004 1.41 1.41 1.66 16 32 1.0 1-1/2 x 1/2 x 1-1/4 35RT3014004012 1.81 1.56 1-88 24 48 1.1 1-1/2 x 1/2 x 1-1/2 35RT3014004014 1.94 1.66 1.94 12 24 1.2 1-1/2 x 314 35RT3014006 1.52 1.52 1.75 16 32 1.1 1-1/2 x 3/4 x 1-1/4 35RT3014006012 1.94 1.66 1.88 20 40 1.1 1-1/2 x 3/4 x 1-1/2 35RT3014006014 1.94 1.75 1.94 18 36 1.2 1-1/2x1 35RT3014010 1.65 1.65 1.80 12 24 1.2 1-112 x 1 x 1/2 35RT3014010004 1.44 1.25 1.69 20 40 0.8 1-1/2 x 1 x 3/4 35RT3014010006 1.50 1.44 1.75 16 32 0.9 1-1/2 x 1 x 1 35RT3014010010 1.65 1.50 1.8C 16 32 1.0 1-1/2 x 1 x1-1/4 35RT3014010012 1.82 1.67 1.88 12 24 1.2 1-1/2 x 1 x 1-1/2 35RT3014010014 1.94 1.80 1.94 12 24 1-3 1-1/2x1-1/4 35RT3014012 1.82 1.82 1.88 12 24 1.4 k 1-1/2 x 1-1/4 x 1/2 35RT3014012004 1.41 1.34 1.66 16 32 0.9 1-1/2 x 1-1/4 x 3/4 35813014012006 1.52 1.45 1.75 16 32 1-1/2 x 1-1/4 x 1 35RT3014012010 1.65 1.58 1.80 16 32 1.1 i_. 1-1/2 x 1-1/4 x 1-1/4. 35RT3014012012 1.82 1.75 1.88 14 28 1.3 r 1-1/2 x 1-1/4 x 1-1/2 35RT3014012014 1.94 1.88 1.94 14 28 1-4 t 2 x 1/2 35RT3020004 1.49 1 49 1.88 10 20 1.5 h ' 2 x 3/4 35313020006 1.60 1.60 1.97 10 20 1.6 2 x 1 35RT3020010 1.73 1.73 2.02 8 16 1.7 2 x 1 x 2 35RT3020010020 2.25 2.02 2.25 8 16 1.9 2 x 1-1/4 35RT3020012 1.90 1.90 2.10 8 16 1.9 2 x 1-1/4 x 2 35RT3020012020 2.25 2.10 2,25 8 16 2.0 2 x 1-1/2 35RT3020014 2.02 2.02 2.16 8 16 2.1 2x1-1/2x 1/2 35RT3020014004 1 49 1.41 1.88 10 20 1,3 2 x 1-1/2 x 3/4 35RT3020014006 1.60 1.52 1.97 10 20 1.4 2 x 1-1/2 x 1 35313020014010 1.73 1.65 2.02 8 16 1.5 2 x 1-1/2 x 1-1/4 35RT3020014012 1.90 1.82 2.10 8 16 1.7 2 x 1-1/2 x 1-1/2 35RT3020014014 2.02 1.94 2.16 8 16 1.8 Fig. 35BT3-Bull Head Tee 1 Size A B C Packing Weight I..ip® in Part Number in in in Inner Master lb `' _ CI 33/4 x 1 35B13006010 1.45 1.45 1.37 30 60 0.6 0 ling 1 x 1-1/4 35BT3010012 1.67 1.67 1.58 20 40 0.9 1 x 1-1/2 35B13010014 1.80 1.80 1.65 15 30 1.0 A >�( B ) 1-1/4 x 1 x 1-1/2 35BT3012010014 1.88 1.80 1.82 15 30 1.2 1-1!4 x 1-1/2 35873012014 1.88 1.88 1.82 15 30 1.3 1-1/4 x 2 35BT3012020 2.10 2.10 1.90 10 20 1.6 1-1/2 x 1-1/4 x 2 35BT3014012020 2,16 2.10 2.02 10 20 1-8 1-1/2x2 35313014020 2,16 2.16 2.02 8 16 1.8 SNI TH-COOPER INTERNATIONAL' • TOLL FREE 1-800-7666-0076 • FAX(323)890-4456 • www.smitlicooper.com 112 I - 1 ucti e ron ittings- ass I I I Y QUALM'FMB 1 c ® us APPROVED A Fig. 35CP3 -Straight Coupling with Ribs LISTED Size part Number A Packing Weight Illa nill - in in Inner Master Ib 1/2 35CP3004 38 200 200 0 3/4 35CP3006 1.63 100 200 0.2 1 35CP3010 1.75 60 120 0.4 1-1/4 35CP3012 2.00 35 70 0.5 1-1/2 35CP3014 2,19 25 50 0.7 2 35CP3020 2.62 15 30 1.2 2-1/2 35CP3024 3,00 9 18 2.2 Fig. 35RC3 -Hex Reducing Coupling Size Part Number A Packing Weight in in Inner Master lb A 1 x 1/2 35RC3010004 1,69 80 160 0 3 1 x 3/4 35R03010006 1.69 60 120 0.4 1-1/4 x 3/4 35RC3012006 2.06 40 80 0.6 - 2 x 1 (not hex) 35RC3020010 2.81 20 40 1.0 Fig. 35HB3 -Hex Bushing Size Part Number A Packing Weight B in in Inner Master lb - - 1 x 1/2 35HB3010004 1.06 180 360 0.2 I l01 A 1 x 3/4 35H83010006 1.06 180 360 0.1 ICI 1-1/4 x 1 35HB3012010 1.19 90 180 0.2 i 1-1/2x 1 35HB3014010 1.25 75 150 0.4 1-1/2x1-1/4 35HB3014012 1-25 75 150 0-3 i 2 x 1 35H/33520010 1.38 40 80 0.6 2 x 1-1/4 351-183020012 1.38 40 80 0.6 2 x 1-112 35HB3020014 1.38 40 80 0.6 i' Fig. 35SP3 -Square Head Plug Size Part Number A Packing Weight in in Inner Master lb i 1/2 35S23004 0.94 600 1200 0.07 iiii i A 3/4 35SP3006 1.12 350 700 0.1 1 1 35S03010 125 200 400 0.1 1-1/4 .35SP3012 1.37 100 200 0.3 1-1/2 35SP3014 1.44 80 160 0.4 2 35SP3020 1.50 45 90 0.6 Fig. 35U 3-Union with Brass Seat A Size A Packing Weight Part Number Poi in in Inner Master lb {, r 'nyFa* _am 1 35U 3010 2.19 20 40 1.0 h� 1 1-1/4 35U 3012 2.50 15 30 1.2 1-1/2 35U 3014 2.62 10 20 1.7 gffili�llirig aill 2 35U 3020 3.12 6 12 2.4 113 SMITH-COOPER INTERNA"I'IONAL"' • POLL FREE 1-800-766-0076 • FAX(323)890-4456 • www.smithcooper.com • L ,T Ductile Iron Fittings-Class 300 UL/FM tivarn?>Ha c ® us APPROVED Fig. 35X 3- Cross LISTED E ,If A A ' Size A Packing Weight A n Part Number in Inner Master lb v elm I � _ 1 35X 3010 1.50 20 40 0.9 1-1/4 1-1/2 35X3012 35X3014 1.75 1.94 12 8 246 1.4 � �� �� 1.8 . 2 35X 3020 225 6 12 2.8 in B B Fig. 35RX3-Reducing Cross Size A B Packing Weighs �� ! Part Number A in in n Inner Master lb \ I --L 1-1/4x1 35RX3012010 1.67 1.58 15 30 1.2 1-1/2 x 1 35RX3014010 1.80 1.65 12 24 1.4 IA 2 x 1 35RX3020010 2.02 1.73 8 16 2.0 ihnotr Fig. 35C 3- Cap Size Part Number A Packing Weight in in Inner Master lb A 1/2 350 3004 0.87 300 600 0.1 3/4 350 3006 0.97 200 400 0.1 1 350 3010 1.16 110 220 02 1-1/4 35C 3012 1.28 70 140 0.4 1-1/2 35C 3014 1.33 50 100 0.5 2 35C 3020 1.45 25 50 0.8 2-1/2 35C 3024 1.70 18 36 1 6 Fig. 35BC3-Beam Clamp Size A Packing Weight Part Number A n n Inner Master lb 3/6 35B03003 0.75 100 200 0-3 1/2 35BC3004 0.75 80 160 0:7, i SMITH-COOPER INTERNATIONAL` • TOLL FREE 1-800-766-0076 • FAX(323)890-4456 • www.smit11 coo pcccom 114 Victaulic° FirelockTM Rigid Coupling ✓ctaulic Style 009N 10.64 I Patented 1.0 PRODUCT DESCRIPTION Available Sizes • 11/4— 12"/32—300 mm Pipe Material • Carbon steel, Schedule 10, Schedule 40. For use with alternative materials and wall thicknesses please contact Victaulic. Maximum Working Pressure • Up to 365 psi/2517 kPa. Function • Joins carbon steel pipe. • Provides a rigid pipe joint designed to restrict axial or angular movement. 2.0 CERTIFICATION/LISTINGS r©a ® LPCB VdS C104-1a/36 ALWAYS REFER TO ANY NOTIFICATIONS AT THE END OF THIS DOCUMENT REGARDING PRODUCT INSTALLATION,MAINTENANCE OR SUPPORT. System No. Location Spec Section Paragraph Submitted By Date Approved Date victaulic.com 10.64 7072 Rev I Updated 01/2017 ®2017 Victaulic Company.All rights reserved. \Ctaulicr 1 victaulic.com 3.0 SPECIFICATIONS- MATERIAL Housing: Ductile iron conforming to ASTM A 536, Grade 65-45-12. Ductile iron conforming to ASTM A 395, Grade 65-45-15, is available upon special request. Housing Coating: (specify choice) ❑ Orange enamel (North America, Asia Pacific) ❑ Red enamel (Europe) ❑ Hot dipped galvanized Gasket: (specify choicer) ❑ Grade"E" EPDM (Type A) FireLock EZ products have been Listed by Underwriters Laboratories Inc., Underwriters Laboratories of Canada Limited, and Approved by Factory Mutual Research for wet and dry (oil free air) sprinkler services within the rated working pressure. ' Services listed are General Service Guidelines only.It should be noted that there are services for which these gaskets are not compatible.Reference should always be made to the latest Victaulic Gasket Selection Guide for specific gasket service guidelines and fora listing of services which are not compatible. Bolts/Nuts: (specify choice2) J Standard: Carbon steel oval neck track bolts meeting the physical and chemical requirements of ASTM A449 (imperial) and ISO 898-1 Class 9.8 (metric). Carbon steel hex nuts meeting the physical and chemical • requirements of ASTM A563 Grade B (imperial - heavy hex nuts) and ASTM A563M Class 9 (metric- hex nuts). Track bolts and hex nuts are zinc electroplated per ASTM B633 ZN/FE5, finish Type III (imperial) or Type II • (metric). ❑ Optional: Stainless steel oval neck track bolts meeting the requirements of ASTM F593, Group 2 (316 stainless steel), condition CW. Stainless steel heavy hex nuts meeting the requirements of ASTM F594, Group 2 (316 stainless steel), condition CW, with galling-resistant coating.2 I Optional bolts/nuts are available in imperial size only. • • 10.64 7072 Rev I Updated 01/2017 ®2017 Victaulic Company.All rights reserved. victaulic.com 2 _ataulid victaulic.com 4.0 DIMENSIONS Style 009N Y Ira ir �� L' Style 009N Pre-Assembled Style 009N Joint Assembled (Push On Condition) Bolt/Nuts Dimensions Weight Actual Maximum Maximum Allow. Pre-assembled (Push On Condition) Joint Assembled Nominal Outside Working End Pipe End Approx. Size Diameter Pressure3 Load3 ,Separation's Qty. Size X Y X Y Z (Each) inches inches psi lb inches inches inches inches inches inches inches lb mm mm kPa N mm mm mm mm mm mm 1 mm kg 1% 1.660 365 790 0.10 3a x 2 3.13 5.00 2.75 5.00 2.00 1.4 32 42.4 2517 3514 2.54 2 M10x2 79 127 70 127 51 0.6 1 Y4 1.900 365 1035 0.10 '.a x 2 3.38 5.13 3.00 5.13 2.00 1.5 40 48.3 2517 4604 2.54 2 M10x2 86 130 76 130 51 0.7 2 2.375 365 1616 0.12 1/2 x21/2 4.00 5.63 3.50 5.63 2.00 1.9 50 60.3 2517 7193 3.05 2 M10 x 21/2 102 143 89 143 51 0.9 21/2 2.875 365 2370 0.12 Vs x 21 4.50 6.13 4.00 6.13 2.00 2.1 65 73.0 2517 10542 3.05 ' 2 M 10 x 21/2 114 156 102 156 51 1.0 76.1 mm 3.000 365 2580 0.12 2 '/e x 2'h 4.63 6.00 4.13 6.13 2.00 2.1 76.1 2517 11476 3.05 M1O x 21/2 118 152 105 156 51 1.0 3 il 3.500 365 3512 0.12 2 a x 2'/2 I 5.13 6.75 4.63 6.75 2.00 2.3 • 80 88.9 2517 15622 ' 3.05 M10 x 21/2 130 171 117 171 a 51 1.0 4 1 4.500 365 5805 0.17 Vs x 21/2 I 6.00 7.88 5.63 7.50 2.13 2.9 ' 100 114.3 • 2517 25822 4.32 2 M10x21/2 152 200 143 - ( 191 54 1.3 4.250 ' 365 5175 1 0.17 3/a x 2't/a 5.63 7.38 5.38 7.38 2.13 3.1 108.0 mm • 108.0 2517 23020 ! 4.32 2 M10x2'/ 152 1.87 137 187 54 1.4 5 5.563 365 8870 0.171/2 x3 7.25 9.25 6.75 9.13 2.25 5.0 125 141.3 2000 39456 4.32 2 M12 x 3 184 235 171 232 57 2.3 5.250 I 365 7897 0.17 1/2x 3 6.63 9.00 6.38 9.00 2.25 4.8 133.0 mm 133.0 2517 35106 4.32 2 M12x3 168 229 162 229 57 2.2 5.500 I 365 8667 0.17 V.x 3 6.88 1 9.25 6.75 9.13 2.25 4.9 139.7 mm 139.7 , 2517 38529 4.32 2 M12x3 175 I 235 171 232 57 2.2 159.0mm 6.250 365 l 11192 0.17 2 1/2 x 3'V. 7.88 I 10.00 7.38 9.88 2.25 5.6 159.0 ' 2517 49753 4.32 I M12 x 3 4i 200 254 187 251 57 2.5 165.1 mm 6.500 365 12105 0.17 2 1/2x 3�/4 8.00 1 10.25 7.75 10.13 2.25 6.0 -_ 165.1 2517 53813 4.32 M12 x 31/4 203 260 197 257 57 2.7 6 6.625 365 12582 0.17 1/2x 3 tk 8.38 10.38 7.88 10.13 2.25 6.0 150 168.3 2000 44469 4.32 2 'M12 x 3 V. 213 264 200 257 57 2.7 8.500 365 20712 0.17 V.x 4 10.63 13.25 10.25 10.13 2.63 11.4 216.0 mm 216.0 2517 55968 4.32 2 M16 x4 270 337 260 I 257 67 5.2 8 8.625 �,i 365 21326 , 0.17 %X4 10.88 13.38 10.25 13.13 2.50 11.4 200 219.1 1620 94863 I 4.32 2 M16 x4 i 276 340 260 333 64 5.2 10 10.750 300 27229 0.25 1/2x 6'h 13.75 17.00 13.25 T-17.13 2.75 22.6 250 273.0 2068 121121 ' 6.4 2 M22 x 165 349 432 337 I. 435 70 10.3 12 12.750 300 38303 0.25 '/a x6'h I 16.00 19.00 , 15.50 19.13 2.75 27.6 300 323.9 ' 2068 170380 6.4 2 I M22 x 165 I 406 483 1 394 486 i 70 12.5 3 Working Pressure and End Load are total,from all internal and external loads,based on standard weight(ANSI)steel pipe,standard roll or cut grooved in accordance with Victaulic specifications.See the Listings/Approvals section of this publication for ratings on other pipe. 4 The allowable pipe separation dimension shown is for system layout purposes only.FireLock EZ1A9 couplings are considered rigid connections and will not accommodate expansion or contraction of the piping system. s Number of bolts required equals number of housing segments. NOTES • When assembling FireLock EZTC couplings onto end caps,take additional care to make certain the end cap is fully seated against the gasket end stop.For FireLock EZT"Style 009N couplings,use FireLock No.006 end caps containing the"EZ"marking on the inside face or No.60 end caps containing the"QV EZ"marking on the inside face.Non-Victaulic end cap products shall not be used with Style 009N couplings.IMPORTANT:Gaskets intended for the Style 009 or Style 009V couplings cannot be used with the Style 009N coupling.There is no interchanging of gaskets or housings between coupling styles. • Use Of Flushseal Gaskets For Dry Pipe Systems FireLock EZT""couplings are supplied with FireLock EZT"Grade"E"Type A gaskets.These gaskets include an integral pipe stop,that once installed provides the similar benefits as a FlushSeal gasket for dry pipe systems.It should be noted that standard Victaulic Flush-SealoM gaskets are not compatible and cannot be used with the FireLock Er"couplings. 10.64 7072 Rev I Updated 01/2017 0 2017 Victaulic Company.All rights reserved. victaulic.com 3 ✓otauliC victaulic.com_ 5.0 PERFORMANCE6 • Listings/Approval The information provided below is based on the latest listing and approval data at the time of publication. Listings/Approvals are subject to change and/or additions by the approvals agencies. Contact Victaulic for performance on other pipe and the latest listings and approvals. Nominal Size cULus12 FM Vds LPCB Sch.5 Sch. 10 Sch.40 Sch. 5 Sch. 10 Sch.40 inches psi psi psi psi psi psi psi psi mm kPa kPa kPa I kPa kPa kPa kPa kPa 1,4 232 365 365 175 363 363 363 363 32 1600 2517 2517 1205 2502 2502 2500 • 2500 1Yz 232 365 365 175 363 363 363 363 40 1600 I 2517 2517 1205 2502 2502 2500 2500 2 363 365 365 175 363 ! 363 363 363 50 2502 2517 2517 i 1205 2502 � 2502 2500 2500 2' N/A 365 365 175 363 363 363 363 65 2517 2517 1205 2502 2502 2500 2500 76.1mm N/A 365 N/A I N/A 363a ' N/A 363 j 363 2517 25028 2500 2500 3 365 365 175 363 363 363 1 363 80 N/A 2517 2517 1205 2502 2502 2500 2500 4 N/A 365 365 ! 175 363 363 363 363 100 2517 2517 � 1205 2502 2502 _.� 2500 j 2500 '6 108.0 mm N/A N/A N/A 1205 25a2 2502 N/A N/A 5 290 365 363 363 232 125 N/A 2000 2517 N/A 2502 2502 1 1600 N/A 133.0 mm N/A N/A N/A N/A 2502a N/A N/A N/A 290 9 3638 232 139.7mm N/A 2 009 N/A N/A - 2502a N/A 1600 N/A 159.0 mm N/A N/A N/A N/A 2502a N/A N/A N/A 165.1 mm N/A T 2000�O N/A N/A �50 8 N/A N/A N/A 6 —--- 290 365 - -- --_ --� ---363 N/A N/A 363 232 N/A 150 2000 2517 2502 I 2502 1600 • 3638 216.0 mm N/A N/A N/A N/A 2502e N/A N/A N/A 8 N/A 290 365 N/A 363 363 232 N/A 200 2000 2517 i 2502 2502 1600 I 3636 216.0mm _..._ N/A N/A N/A N/A 2502" N/A N/A N/A 8 290 365 363 363 232 200 N/A 2000 2517 N/A 2502 2502 1600 N/A 10 N/A _._ 300 __. 300._. N/A _.. 300 300 N/A N/A 250 2068 2068 2068 2068 12 N/A 300" 300 N/A 250 I 300 N/A N/A 300 2068" 2068 1724 2068 6 Listed/Approved for wet and dry pipe systems Is-40°F/-40°C)for continuous use in freezing conditions,use of Style 005H Coupling with Silicone Gasket is recommended. Please see the Victaulic Installation Manual 1-009N/009H for details concerning when supplemental lubrication is required. cULus listed for DIN 2458 2.6 mm pipe wall. 8 FM approved for BS 1387 Medium 3.6 mm pipe wall. 9 cULus listed for EN 10220 4.0 mm pipe wall. 10 cULus listed for EN 10255 4.5 mm pipe wall. u cUL listed to 250 psi. 12 With optional stainless steel fasteners,cULus Listed to 175psi. 10.64 7072 Rev I Updated 01/2017 ct 2017 Victaulic Company.All rights reserved. victaulic.com 4 Jiataulic victaulic.com • • 5.1 PERFORMANCE2 • Listings/Approval • Speciality Pipe Pipe Size Pressure Rating Pipe Size Pressure Rating I Pipe Size Pressure Rating cULus FM ' cULus FM cULus FM inches • psi psi inches psi psi inches psi psi ' kPa kPa • kPa kPa I kPa kPa BLT 11/4-2 300 365 EZT 1'/a-2 300 365 MT lYa_2 • 300 365 2068 2517 2068 2517 2068 2517 300 365 300 365 365 DF 1Y<-4 FF P/a-4 1 MLT 1Yu-2 N/A 2068 2517 2068 2517 J, ,..,� 2517 DT 1 Y-2 300 365 FLF 1'.b-4 N/A 365 5T 1 V<-2 N/A 365 2068 2517 2517 2517 • 175 175 365 365 EF 1 Ya-4 FLT 1 Y-2 N/A STF 1 V< 4 N/A 1206 1206 2517 2517 300 365 365 365 I�, EL 1 Ya-2 2068 2517 FLTL 1 V, 2 N/A __• 2517 TF 2�k-4 N/A 2517 300 365 300 1 365 300 365 ET40 1 /a-2 2068 2517 :300 365 GL 1 ' -Z.... 2068300 I 2517 :365.-.-� WLS 1'/a-2_-- 20 8_-- 367 EZF 3-4 MF 1/a-4 WST 1/n-2 N/A 2068 2517 2517 _ 2068 2517 .�..._. XL P/n-2... 300 365. 2068 2517 NOTES • BLT=BLT steel pipe manufactured by Allied Tube&Conduit Corp. • DF=DYNA-FLOW steel pipe manufactured by Allied Tube&Conduit Corp. • DT=DYNA-FLOW steel pipe manufactured by Allied Tube&Conduit Corp. • EF=EDDY FLOW steel pipe manufactured by Bull Moose Tube Co. • EL=EDDYLITE steel pipe manufactured by Bull Moose Tube Co. • ET40=Eddythread 40 steel pipe manufactured by Bull Moose Tube Co. • EZF=EZ-Flow steel pipe manufactured by Northwest Pipe Co. • EZT=EZ-Thread steel pipe manufactured by Youngstown Tube Co. • FF=Fire-Flo steel pipe manufactured by Youngstown Tube Co. • FLF=Fire-Line Flow steel pipe manufactured by Western International Forest Products Inc. • FLT=Fire-Line Threadable steel pipe manufactured by Western International Forest Products Inc. • FLTL=Fire-Line Threadable Light steel pipe manufactured by Western International Forest Products Inc. • GL=GL steel pipe manufactured by Wheatland Tube Co. • MF=Mega-Flow steel pipe manufactured by Wheatland Tube Co. • MT=Mega-Thread steel pipe manufactured by Wheatland Tube Co. • MLT=MLT steel pipe manufactured by Wheatland Tube Co • ST=STD wall pipe in accordance with ASTM A53. • STF=Steady Flow steel pipe manufactured by AMS Tube Corp. • TF=Tex-Flow steel pipe manufactured by Tex-Tube Co. • WLS=WLS steel pipe manufactured by Wheatland Tube Co. • WST=WST steel pipe manufactured by Wheatland Tube Company. • XL=XL steel pipe manufactured by Allied Tube&Conduit Corp. • • 10.64 7072 Rev I Updated 01/2017 ®2017 Victaulic Company.All rights reserved. victaulic.com 5 ✓Otatulic victaulic.com • 6.0 NOTIFICATIONS Not applicable—contact Victaulic with any questions. 7.0 REFERENCE MATERIALS 05.01:Sena i ,.:on Guide I-009Nl009:I. Installation Instructions FireLock EZT°Rigid Coupling • • User Responsibility for Product Selection and Suitability Note Each user bears final responsibility for making a determination as to the suitability of This product shall be manufactured by Victaulic or to Victaulic specifications.All products Victaulic products for a particular end-use applicaton,in accordance with industry to be installed in accordance with current Victaulic installation/assembly instructions. standards and project specifications,and the applicable building codes and related Victaulic reserves the right o change product specifications,designs and standard regulations as well as Victaulic performance,maintenance,safety,and warning equipment without notice and without incurring obligations. instructions.Nothing in this or any other document,nor any verbal recommendation, Installation advice,or opinion from any Victaulic employee,shall be deemed to alter,vary,supersede, Reference should always be made to the Victaulic installation handbook or installation or waive any provision of Victaulic Company's standard conditions of sale,installation instructions of the product you are installing.Handbooks are included with each shipment guide,or this disclaimer. of Viclaulic products,providing complete installation and assembly data,and are available Intellectual Property Rights in PDF format on our website at www.victaulic.com. No statement contained herein concerning a possible or suggested use of any material, Warranty product,service,or design is intendec,or should be constructed,to grant any license Refer to the Warranty section of the current Price List or contact Victaulic for details. under any patentor other intellectual property right of Victaulic or any of its subsidiaries or affiliates covering such use or design,or as a recommendation for the use of such Trademarks material,product,service,or design in the infringement of any patent or other intellectual Victaulre and all other Victaulic marks are the trademarks or registered trademarks of property right.The terms"Patented"or"Patent Pending"refer to design or utility patents Victaulic Company,and/or its affiliated entities.in the U.S.and/or other countries. or patent applications for articles and/or methods of use in the United States and/or other countries. • • 10.64 7072 Rev I Updated 01/2017 ®2017 Victaulic Company.All rights reserved. victaulic.com 6 jot:swim' FireLock® Fittings ✓ctaulic` 10.03 Material Specifications: Fitting: Ductile iron conforming to ASTM A-536, grade 65-45-12. 4110 Fitting Coating: ❑ Orange enamel ❑ Red enamel in Europe, Middle East, Africa, and India ❑ Optional: Hot dipped galvanized Approvals/Listings: c®us O ILPCBI VdS Product Description: FireLock® products comprise a unique system specifically designed for fire protection services. FireLock full-flow elbows and tees feature CAD- developed, hydrodynamic design, affording a shorter center-to-end dimension than standard fittings. A noticeable bulge allows the water to make a smoother turn to maintain similar flow characteristics as standard full flow fittings. FireLock fittings are designed for use exclusively with Victaulic couplings that have been Listed or Approved for Fire Protection Services. Use of other couplings or flange adapters may result in bolt pad interference. Refer to the appropriate listing agency or approval body for pressure ratings. Pressure ratings vary by agency. Job/Owner Engineer System No. Spec Section Location Paragraph Contractor Approved Submitted By Date Date victaulic.com I FireLock® Fittings I Publication 10.03 10.03 1539 Rev M Updated 12/2014 et 2014 Victaulic Company.All rights reserved. 1 ictaul.c` victaulic.com I FireLock® Fittings I Publication 10.03 Dimensions: l CtoE� C l _ i to P I J p Cto % _0 D 7-r-°0_z T t;E _ 1 Y+!o �i t; NO.001 NO.003 NO.002 No.006 No.001 No.003 No.002 No.006 90°Elbow 45°Elbow Straight Tee Cap Actual Approx. Approx. Approx. Approx. Nominal Outside Weight Weight Weight Weight Size Diameter C to E Each C to E Each C to E Each C to E Each inches inches inches Lbs. inches Lbs. inches Lbs. inches Lbs. mm mm mm kg mm kg mm kg mm kg 1 t/e 1.660 0.82 0.3 32 42.4 21 0.1 116 1.900 - - 0.82 0.4 40 48.3 - - - 21 0.2 2 2.375 2.75 1.7 2.00 1.8 2.75 2.4 0.88 0.6 50 60.3 70 0.8 51 0.8 70 1.1 22 0.3 21/2 2.875 3.00 3.1 2.25 2.2 3.00 3.6 0.88 1.0 65 73.0 76 1.4 57 1.0 76 1.6 22 0.5 3.000 3.00 3.30 2.25 2.4 3.00 3.8 76.1 mm - - 76.1 76 1.5 57 1.1 76.2 1.7 3 3.500 3.38 4.0 2.50 3.1 3.38 5.3 0.88 1.2 80 88.9 86 1.8 64 1.4 86 2.4 22 0.5 108 mm 4.250 4.00 5.7 3.00 5.1 4.00 7.5 - - 108.0 102 2.6 76 2.3 102 3.4 4 4.500 4.00 6.7 3.00 5.6 4.00 8.7 1.00 2.4 100 114.3 102 3.0 76 2.5 102 3.9 25 1.1 5 5.563 4.88 12.6 3.25 8.3 4.88 15.7 1.00 4.1 125 141.3 124 5.7 83 3.8 124 7.1 25 1_9___ 139.7 mm 5.500 4.88 12.4 3.25 8.2 4.88 15.4 - - 139.7 124.0 5.6 82.6 3.7 124.0 6.9 159mm 6.250 5.50 12.6 3.50 9.2 5.50 17.9 - - 158.8 140 5.7 89 4.2 140 8.0 6 6.625 5.50 18.3 3.50 11.7 5.50 22.7 1.00 5.9 150 168.3 140 8.3 89 5.3 140 10.3 25 2.7 165.1 mm 6.500 5.43 17.6 3.50 11.4 5.50 22.0 - - 165.1 139.7 7.9 88.9 5.2 139.7 9.9 8 8.625 6.81 25.5 4.25 20.4 6.94 38.7 1.13 12.7 200 219.1 173 11.6 108 9.3 176 17.6 29 5.8 10.03 1539 Rev M Updated 12/2014 ©2014 Victaulic Company.All rights reserved. �Ct:aU�rC` victaulic.com 2 victaulic.com I FireLock® Fittings I Publication 10.03 Flow Data: Frictional Resistance Actual Equivalent Feet/meters of Straight Pipe' Nominal Outside No.002 Size Diameter Elbows Straight Tee inches inches No.001 No.003 mm mm 90°Elbow 45°Elbow Branch Run 11/4 1.660 - - - - 32 42.4 1 1 1.900 40 48.3 - - - - 2 2.375 3.5 1.8 8.5 3.5 50 60.3 1.1 0.5 2.6 1.1 2 th 2.875 4.3 2.2 10.8 4.3 65 _73.0. 1.3 0.7 3.3 1.3 76.1 mm 3.000 4.5 2.3 11.0 4.5 76.1 1.4 0.7 3.4 1.4 3 3.500 5.0 2.6 13.0 5.0 80 88.9 1.5 0.8 4.0 1.5 108mm 4.250 6.4 3.2 15.3 6.4 __ _ 108.0 2.0 0.9 4.7 2.0 4 4.500 6.8 3.4 16.0 6.8 100 114.3 2.1 1.0 4.9 2.1 5 5.563 8.5 4.2 21.0 8.5 125 141.3 2.6 1.3 6.4 2.6 139.7mm 5.500 8.3 4.1 20.6 8.3 139.7 2.5 1.3 6.3 2.5 159mm 6.250 9.4 4.9 25.0 9.6 158.8 2.9 1.5 7.6 2.9 6 6.625 10.0 5.0 25.0 10.0 150 168.3 3.0 1.5 7.6 3.0 165.1 mm 6.500 9.8 4.9 24.5 9.8 165.1 3.0 1.5 7.5 3.0 8 8.625 13.0 5.0 33.0 13.0 200 219.1 4.0 1.5 10.1 4.0 ' The flow data listed is based upon the pressure drop of Schedule 40 pipe. General Notes: NOTE: When assembling FireLock EZ couplings onto end caps, take additional care to make certain the end cap is fully seated against the gasket end stop. For FireLock EZ Style 009N/009H couplings, use FireLock No. 006 end caps containing the "EZ" marking on the inside face or No. 60 end caps containing the "QV EZ" marking on the inside face. Non-Victaulic end cap products shall not be used with Style 009/009V/009H couplings. Installation Nole Reference should always be made to the 1-100 Victaulic Fleic Installation I land book for This product shall be manufactured by Victaulic or to Victaulic specifications.All products the product you are installing.Handbooks are included with each shipment of Victaulic to be•nstalled in accordance with current Victaulic installation/assembly instructions. products for complete installation and assembly data,and are available in PDF format Victaulic reserves the right to change product specifications,designs and standard on our website at www.victaulic.com. equipment without notice and without incurring obligations. Warranty Trademarks Refer to the Warranty section of the current Price List or contact Victaulic for details. Victaulic®is a registered trademark of Victaulic Company. 10.03 1539 Rev M Updated 12/2014 ®2014 Victaulic Company.All rights reserved. victaulic.com 3 .ctaulic RING HANGERS "Iir)A�! Fig. 69 (Formerly Afcon Fig. 300) Adjustable Swivel Ring,Tapped Per NFPA Standards Size Range:1/2'through 8" __ Material:Carbon steel Finish:Strap is Pre-Galvanized Zinc Material. Nut is Zinc Plated. Service:Recommended for suspension of non-insulated stationary pipe line. ;_' Maximum Temperature:450°F Approvals:Complies with Federal Specification A-A-1192A(Type 10), WW-H-171-E(Type 10), < and ANSI/MSS SP-58(Type 10).UL Listed and FM Approved(Sizes3/4"-8"). .+.' Features: • 1/2'-2"sizes designed for use with steel and CPVC piping and manufactured with FBC System Compatible oil. t • Threads are countersunk so that they cannot become burred or damaged. • Knurled swivel nut provides vertical adjustment after piping is in place. • Captured swivel nut in the 1/2"through 6"sizes.The capture is permanent in the bottom , 00 portion of the band,allowing the hanger to be opened during installation if desired,but not allowing the nut to fall completely out. Ordering:Specify size,figure number and name. A"through 2"Size Non-captured nut also available upon request. . A Rounded Edge Design .� 11 _ ` F 1UI CDS '0' SED APPROVED A 71 --Al F B F B Al ii IiIi:;I.: /u„ ii n G G GA.. 1/2"through 1"pipe 1 1/4"through 2"pipe 21/2'through 8"pipe ., 44" FIG. 69: DIMENSIONS (IN) • LOADS (LBS) • WEIGHT (LBS) 7 Pipe Size Max Load Weight R0 A 12e B C F Width 1/2 0.10 2% 2 19/e 3/4 0.10 23/4 17/8 15/s J 1 0.10 29/16 111/16 1 5 11/4 300 0.10 2% 13/4 �/e /8 11/2 0.10 3/4 23/4 1% 2 0.11 3% 2% 1% 2Y2 525 0.20 4 23/4 15/16 . 3 0.20 311/46 215/6 13/6 4 650 0.30 417/6 3t3/6 19/s 314 5 0.54 55/6 43/e 6 1,000 0.65 1/2 671/6 59/s 21/4 21/i'through 8"Size 8 1.00 89/6 79/e 31/a PROJECT INFORMATION APPROVAL STAMP Project: U Approved Address: ['Approved as noted Contractor: ❑Not approved Engineer: Remarks: Submittal Date: Notes 1: Notes 2: PH-1.18 .?owers. FASTENERS PRODUCT INFORMATION Mini Dropin Mini Dropin Internally Threaded Expansion Anchor SECTION CONTENTS Page No. Utri ce PRODUCT DESCRIPTION General Information 1 0 Material and Installation a The Mini Dropin is a carbon steel machine bolt anchor for use in shallow embedment Specifications 1 1 U applications. In addition to solid concrete and precast hollow core plank, it can be used Performance Data 2 U Z in post-tensioned concrete slabs and concrete pours over steel deck. Design Criteria 3 CWC Q GENERAL APPLICATIONS AND USES Ordering Information 4 G • Suspending Conduit • Fire Sprinkler /....+.•r....r • Cable Trays and Strut • Utilities • Pipe Supports • Suspended Lighting FEATURES AND BENEFITS Mini Dropin + Internally threaded anchor for easy bolt removability and service work +Ideal for precast hollow core plank and post-tensioned concrete slabs THREAD VERISON UNC Thread +Lip provides flush installation and consistent embedment +Setting tool scores flange when set to verify proper expansion depth ANCHOR MATERIALS Zinc Plated Carbon Steel APPROVALS AND LISTINGS Tested in accordance with ASTM E 488 and AC01 criteria ROD/ANCHOR SIZE RANGE(TYP.) 1/4"diameter to 1/2"diameter Factory Mutual Research Corporation(FM Approvals)—File No.J.I. 3002071 See listing for applicable sizes-www.fmglobal.com SUITABLE BASE MATERIALS Normal-weight Concrete GUIDE SPECIFICATIONS Structural Lightweight Concrete CSI Divisions:03151-Concrete Anchoring and 05090-Metal Fastening. Anchors shall be Precast Hollow Core Plank Mini Dropin anchors as supplied by Powers Fasteners, Inc., Brewster, NY. Concrete Over Steel Deck MATERIAL AND INSTALLATION SPECIFICATIONS Material Specification Installation Specification Anchor Component Carbon Steel Rod/Anchor Diameter,d Anchor Body SAE 1009 Dimension 114" 3/8" 1/2" Plug SAE 1009 ANSI Drill Bit Size dbit(in.) 3/8 1/2 5/8 Zinc Plating ASTM B633,SC1,Type III(Fe/Zn 5) Maximum Tightening Torque,T,,,(ft-lbs) 3 5 10 Thread Size(UNC) 1/4-20 3/8-16 1/2-13 Thread Depth(in.) 3/8 13/32 5/8 Overall Anchor Length(in.) 5/8 314 1 Installation Guidelines Drill a hole into the base \II % Blow the hole clean of dust If using a fixture,position it,insert bolt and material to the depth it and other materials. Insert tighten.Most overhead applications utilize of embedment required. the anchor into the hole threaded rod. Minimum thread engagement The tolerances of the drill '. - .- 1/' and tap flush with surface. mg should be at least one anchor diameter. bit used must meet the v 1/ v. Using a Powers setting �� requirements of ANSI I. ' % ' tool specifically, set the I 0 1 1 Standard B212.15. • ° -' %i•. ° anchor by driving the tool �r 1 .. : '% with a sufficient number 1 In post-tensioned concrete -v. . 4 . of hammer blows until j slabs,take care to avoid - • the shoulder of the tool is _ mI `_ =='„_- drilling into the post-tensioned seated against the anchor. . v tW cables. Anchor will not hold P:- • P; ; a. " a 1 •• , a . allowable loads required if _ a VI, 771, ' s shoulder of Powers setting ° ° ° tool does not seat against anchor. f Powers USA:(800)524-3244 or(914)235-6300 Canada:(905)673-7295 or(514)631-4216 www.powers.com 1 -?owers Mini Dropin PRODUCT INFORMATION FASTENERS 3) m PERFORMANCE DATA zin xy .tea 0 z Ultimate Load Capacities for Mini Dropin in Normal-Weight Concrete1'2 ° xi pi 0 > Rod/Anchor Minimum Minimum Concrete Compressive Strength(I') Embedment 3,000psi(20.7 MPa) 4,000 psi(27.6 MPa) 6,000 psi(41.4 MPa) Size Depth d Tension Shear Tension Shear Tension Shear in. lbs. lbs. lbs. lbs. lbs. lbs. (mm) in. (mm) (kN) (kN) (kN) (kN) (kN) (kN) 1/4 5/8 1,100 1,260 1,150 1,650 1,200 1,650 (6.4) (15.9) (6.3) (5.7) (5.1) (7.4) (5.3) (7.4) 3/8 3/4 1,980 2,700 2,120 4,220 2,270 4,220 (9.5) (19.1) (8.9) (12.2) (9.5) (19.0) (10.2 (19.0) 1/2 1 3,360 4,400 3,360 4,875 3,750 4,875 (12.7) (25.4) (15.1) (19.8) (15.1) (21.9) (16.9) (21.9) • 1.Tabulated load values are for anchors installed in concrete.Concrete compressive strength must be at the specified minimum at the time of installation. 2.Ultimate load capacities must be reduced by a minimum safety factor of 4.0 or greater to determine allowable working load. Allowable Load Capacities for Mini Dropin in Normal-Weight Concrete" Rod/Anchor Minimum Minimum Concrete Compressive Strength(1",) Size Embedment 3,000 psi(20.7 MPa) 4,000 psi(27.6 MPa) 6,000 psi(41.4 MPa) d Depth Tension Shear Tension Shear Tension Shear in. lbs. lbs. lbs. lbs. lbs. lbs. (mm) n. (mm) (kN) (kN) (kN) (kN) (kN) (kN) 1/4 5/8 275 315 285 415 300 415 (6.4) (15.9) (1.2) (1.4) (1.3) (1.9) (1.3) (1.9) 3/8 3/4 495 675 530 1,055 570 1,055 (9.5) (19.1) (2.2) (3.0) (2.4) (4.7) (2.6) (4.7) 1/2 1 840 1,100 840 1,220 940 1,220 (12.7) (25.4) (3.8) (5.0) (3.8) (5.5) (4.2) (5.5) 1.Allowable load capacities listed are calculated using and applied safety factor of 4.0. 2.Linear interpolation may be used to determine allowable loads for intermediate compressive strengths. Ultimate and Allowable Load Capacities for Mini Dropin Installed Through Steel Deck into Structural Lightweight Concrete'•z•3 Installation Detail for Mini Dropin Installed Lightweight Concrete Over Min.20 Ga.Steel Deck. Through Soffit of Steel Deck into Concrete Minimum f',z 3,000 psi(20.7 MPa) Rod/Anchor Embed. Minimum 1-3/4"Wide Deck STRUCTURAL SAND-LIGHTWEIGHT CONCRETE Size Depth OR NORMAL wEIGNT CONCRETE OVER STEEL DEC( d Ultimate Load Allowable Load (MINIMUM 3,000 PS0 h in. Tension Shear Tension Shear UPPER FLUTE(VALLEY] (mm) in. (mm) lbs. lbs. lbs. lbs. (kN) (kid) (kN) (kN) tLUTE EDGE ° ' a 1/4 5/8 740 1,880 185 470 v a ANCHOR , a_ (6.4) (15.9) (3.3) (8.5) (0.8) (2.1) 4 'TIP) 1 4 as a 3/8 3/4 880 2,040 220 510 (9.5) (19.1) (4.0) (9.2) (1.0) (2.3) • '°'■ 1/2 1 1,380 2,120 345 530 NO MIN.EDGE DISTANCE (12.7) (25.4) (6.2) (9.5) (1.6) (2.4) (UPPER FLUTE) MIN.MP(LOWER FLUTE) 1.The metal deck shall be No.22 gage to No.18 gage thick steel 10.030-inch to 0.047-inch base metal thickness LOWER FLUTE(RIDGE) (0.75 mm to 1.20 ram)]. NO.32 m NO.IR GAGE STEEL DEIX 2.Allowable load capacities listed are calculated using and applied safety factor of 4.0. 3.Tabulated load values are for anchors installed with a minimum edge distance of 7/8"when installed through the lower flute.Anchors installed through the upper flute may be in any location provided the proper installation procedures are maintained. f 2 www.powers.com Canada:(905)673-7295 or(514)631-4216 Powers USA:(800)524-3244 or(914)235-6300 -Powers FASTENERS PRODUCT INFORMATION Mini Dropin J PERFORMANCE DATA Q IA Vpe ,fief Z O Ultimate and Allowable Load Capacities for Mini Dropin f Q 2 in Precast Hollow Core Concrete Plank1 z = Z Rod/ Minimum Min.Concrete Compressive Strength NJ Q Minimum f;a 5,000 psi(34.5 MPa) Installation Detail for Mini Dropin Anchor Embed. Minimum Edge Installed in Precast Hollow Core Size Depth Spacing Distance Ultimate Load Allowable Load Concrete plank d h, in. in. Tension Shear Tension Shear in. in. (mm) (rum) lbs. lbs. lbs. lbs. a< (mm) (mm) (kN) (kN) (kN) (kN) 10< O 6.4 5/8 3 3 1,4006. ) (8.3) 50 460 (6.4) (15.9) (76.2) (76.2) (6.2) (8.3) (1.6) (2.1) 3/8 3/4 4-1/2 4-1/2 2,600 3,400 650 850 MIN.1-1/2" 1 (9.5) (19.1) (114) (114) (11.7) (15.3) (2.9) (3.8) ANCHOR(TYP) 1 1 6 6 2,600 3,540 650 885 (12.7) (25.4) (152.4) (152.4) (11.7) (15.9) (2.9) (4.0) 1.Tabulated load values are for anchors installed in concrete.Concrete compressive strength must be at the specified minimum at the time of installation. 2,Allowable load capacities listed are calculated using and applied safety factor of 4.0. DESIGN CRITERIA (ALLOWABLE STRESS DESIGN) Combined Loading For anchors loaded in both shear and tension,the combination of loads should be proportioned as follows: Where: Nu=Applied Service Tension Load Nu + Vu s < 1 OR (Nu ) + IVu ) 1Nn=Allowable Tension Load Nn Vn t Vn Vu=Applied Service Shear Load Vn=Allowable Shear Load Load Adjustment Factors for Spacing and Edge Distance12'3 Anchor Installed in Normal-weight Concrete Anchor Dimension Load Type Critical Distance Critical Load Factor Minimum Distance Minimum (Full Anchor Capacity) (Reduced Capacity) Load Factor Spacing(s) Tension and Shear so.,3.0h, FNc=FV=1.0 smin=1.5h, FN,=Fv,=0.50 Tension ccr=12d FN,=FVc=1.0 cmin=6d FNc=0.90 Edge Distance(c) • Shear' ccn=12d FNc.=FVc.=1.0 cmin=6d FVc=0.75 1.Allowable loads for anchors loaded in shear parallel to the edge have no load factor fV=1.0 when installed at minimum edge distances. 2,Allowable load values found in the performance data tables are multiplied by reduction factors when anchor spacing or edge distances are less than critical distances,Linear interpolation is allowed for intermediate anchor spacing and edge distances between critical and minimum distances.When an anchor is affected by bath reduced spacing and edge distance,the spacing and edge reduction factors must be combined(multiplied).Multiple reduction factors for anchor spacing and edge distance may be required depending on the anchor group configuration. Anchor Installed in Through Steel Deck Structural Lightweight Concrete Anchor Dimension Load Type Critical Distance Critical Load Factor Minimum Distance Minimum (Full Anchor Capacity) (Reduced Capacity) Load Factor Spacing(s) Tension and Shear Scr=3.0h, FN,=FVs=1.0 smin=1.5h, FN,=Fv,=0.50 3.Allowable load values found in the performance data tables are multiplied by reduction factors when anchor spacing is less than critical distances.Linear interpolation is allowed for intermediate anchor spacing between critical and minimum distances.Multiple reduction factors for anchor spacing may be required depending on the anchor group configuration. f Powers USA:(800)524-3244 or(914)235-6300 Canada:(905)673-7295 or(514)631-4216 www.powers.com 3 • ?owers.. Mini Dropin PRODUCT INFORMATION FASTENERS Er a m DESIGN CRITERIA (ALLOWABLE STRESS DESIGN) n Z Load Adjustment Factors for Normal-weight and Lightweight Concrete n = 9 = a Spacing,Tension(Fr,)&Shear(Fv,)(Normal-weight and Lightweight Concrete over deck) Notes:For anchors loaded in tension and shear, 0 2 Dia.(in.) 1/4 3/8 1/2 the critical spacing(sea is equal to 3 embedment 21 In,(in.) 5/8 3/4 1 depths(3h,)at which the anchor achieves 100% V1 D of load. s,(in.) 1-1I6 2-114 3 Minimum spacing(s,,,,)is equal to 1.5 embedment s,"„,(in.) 1 1-1/8 1-1/2 depths(1.5hv(at which the anchor achieves 50% 1 0.50 of load. N _ t/a a6D DSD 1-1/2 0.80 0,67 0.50o. N . 75 4/44t. n 21/4 1.00 _ D00 O83 3 1.00 Edge Distance,Tension(F,vj(Normal-weight concrete only) Notes:For anchors loaded in tension,the critical Dia.On.) 1/4 3/8 1/2 edge distance(cc)is equal to 12 anchor diameters (120)at which the anchor achieves 100%of load. cO(in.) 3 4-1/2 6 Minimum edge distance(cm/n)is equal to 6 anchor siw On.) 1-7/8 2-114 3 diameters(60 at which the anchor achieves 90% 1-1/2 0.90 of load. :.5. 2 0.93 N 21/4 0.95 D.90 El 2-1/2 0.97 0.91 m 3 _ 1.00 0.9 _ 0.91111%41114,000 - 0 4 0.98 _ 0.93 $ 4-1/2 1.00 0.95 C 5 0.97 6 1.00 Edge Distance,Tension(Fvc)(Normal-weight concrete only) Notes:For anchors loaded in shear,the critical Dia.(in.) 1/4 3/8 1/2 edge distance(cyr)is equal to 12 anchor diameters (120 at which the anchor achieves 100%of load. cv(in.) 3 4-1/2 6 Minimum edge distance(cm(n)is equal to 6 anchor cm;"(in.) 1-1/2 2-1/4 3 diameters(60 at which the anchor achieves 75% of load. 1-1/2 0.75 2 0.83 . �% 2-114 0.88 0.75 a 2-1/2 0,92 0.78 3 -,DO 0.83 075AP 0 4 0.94 0.83 -o' 4-1/2 1.00 0.88 C 5 0.92 6 1.00 ORDERING INFORMATION Carbon Steel Mini Dropin Cat No. Rod/Anchor Dia. Drill Diameter Overall Length Standard Box Standard Ctn. 6335 1/4" 3/8" 5/8" 100 1,000 6322 3/8" 1/2" 314" 100 1,000 6337 1/2" 5/8" 1" 50 250 Setting Tool for Mini Dropin Cat No. Mini Dropin Size Standard Box Standard Cartoon 6336 1/4" 1 50 ._. �.__.. 6323 3/8" 1 50 6338 1/2" 1 50 Accu-BitTM Drill Stop for Mini Dropin Cat No. Rod/Anchor Size Standard Box 00392 3/8"Accu-Bit for 1/4"Mini Dropin 1 00398 1/2"Accu-Bit for 3/8"Mini Dropin 1 00411 5/8"Accu-Bit for 1/2"Mini Dropin 1 ©2012 Powers Fasteners,Inc. All Rights Reserved, Dropin and Accu-Bit are a Trademark of Powers Fasteners,Inc.For the most current information visit www.powers.com f 4 www.powers.com Canada:(905)673-7295 or(514)631-4216 Powers USA:(800)524-3244 or(914)235-6300 Page 1 of 2 Fastenal Product Standard REV-03 Date: December 1,2010 Jl'7q(' TROD.LC.Z Threaded Rod,Low Carbon, Zinc Plated The information below lists the required dimensional,chemical and physical characteristics of the products in this purchase order. If the order received does not meet these requirements,it may result in a supplier corrective action request,which could jeopardize your status as an approved vendor. Unless otherwise specified,all referenced consensus standards must be adhered to in their entirety. Sintintal I. L to Diameter Nominal Size D(Major Diameter) Max. Min. 4-40 * .1120 .1112 .1061 6-32 ' .1380 .1372 .1 31 2 8-3 2 * .1640 .1631 .1571 10-24 ' .1900 .1890 .1818 10-32 * .1900 .1891 .1831 12-24 * .2160 .2150 .2078 1/4-20 .2500 .2489 .2367 1/4-28 .2500 .2490 .2392 5/16-18 .3125 .3113 .2982 5/16-24 .3125 .3114 .3006 3/8-16 .3750 .3737 .3595 I 3/8-2 4 .3 75 0 .3739 .3631 7/16-14 .4375 .4361 .4206 7/16-20 .4375 .4362 .4240 1/2-13 .5000 .4985 .4822 1/2-20 .5000 .4987 .4865 I 9/16-12 .5625 .5609 .5437 9/16-18 .5625 .5611 .5480 5/8-11 .6250 .6233 .6051 5/8-18 .6250 .6236 .6105 3/4-10 .7500 .7482 .7288 3/4-16 .7 50 0 .7485 .7 34 3 7/8-9 .8750 .8731 .8523 7/8-14 .8750 .8734 .8579 1-8 1.000 .9980 .9755 1-14 ' 1.000 .9984 .9881 1 1/8-7 1.125 1.1228 1.0982 1 1/8-12 1.125 1.1232 1.1060 1 1/4-7 1.250 1.2478 1.2232 1 1/4-12 1.250 1.2482 1.2310 1 3/8-6 .375 1.3 726 1.3453 1 1/2-6 1.500 1.4976 1.4703 1 1/2-12 1.500 1.4981 1.4809 1 3/4-5 .750 1.7473 1.7165 2-4.5 2.000 1.9971 1.9641 `Class 2A threads shall be used for sizes where 1A Is not applicable Length I Tolerance 3' +/- 1/4" 6' - 12' +/- 1/2" Length shall be measured form end to end TycoWorldwide Fire Protection Contacts ww tyco-fire.com Products Series TY-FRB — 2.8, 4.2, 5.6, and 8.0 K-Factor Upright, Pendent, and Recessed Pendent Sprinklers Quick Response, Standard Coverage General when exposed to corrosive atmo- spheres. Although corrosion-resistant Description coated sprinklers have passed the p standard corrosion tests of the appli- The TYCO Series TY-FRB, 2.8, 4.2, cable approval agencies,the testing is 5.6,and 8.0 K-factor,Upright,Pendent, not representative of all possible corFtERIM - and Recessed Pendent Sprinklers rosive atmospheres. Consequently, described in this data sheet are quick it is recommended that the end user response, standard coverage, deco- be consulted with respect to the suit- native 3 mmglass bulb-type s ra ability of these coatings for any given yP P y corrosive environment. The effects of sprinklers designed for in light or p s de g o use g zi ambient temperature,concentration of ordinary hazard,commercial oc shop- chemicals andgas/chemical velocity, - — ' y, . y} .1i F cies such as banks hotels and shop- . P ping malls. should be considered, as a minimum, along with the corrosive nature of the The recessed version of the Series chemical to which the sprinklers will be TY-FRB Pendent Sprinkler, where exposed. applicable,is intended for use in areas An intermediate level of the Series with a finished ceiling. This recessed TY-FRB Pendent Sprinklers is detailed pendent sprinkler uses one of the in Technical Data Sheet TFP356, and following: Sprinkler Guards are detailed in Tech- • A two-piece Style 10 (1/2 inch NPT) nical Data Sheet TFP780. or Style 40(3/4 inch NPT) Recessed Escutcheon with 1/2 inch (12,7. mm) NOTICE �, 4 .•., of recessed adjustment or up to 3/4 The Series TY-FRB, 2.8, 4.2, 5.6, inch (19,1 mm) of total adjustment from the flush pendent position,or a and 8.0 K-factor, Upright, Pendent, ' i and Recessed Pendent Sprinklers 1 • A two-piece Style 20(1/2 inch NPT) described herein must be installed or Style 30(3/4 inch NPT)Recessed and maintained in compliance with Escutcheon with 1/4 inch (6,4 mm) this document and with the applica- e:-,7S If is of recessed adjustment or up to 1/2 ble standards of the National Fire Pro- '', ` '0 inch (12,7 mm) of total adjustment tection Association, in addition to the from the flush pendent position. standards of any authorities having The adjustment provided by the jurisdiction.Failure to do so may impair Recessed Escutcheon reduces the the performance of these devices. Sprinkler accuracy to which the fixed pipe drops The owner is responsible for maintain- Identification to the sprinklers must be cut. ing their fire protection system and Corrosion-resistant coatings, where devices in proper operating condition. Number (SIN) applicable,are utilized to extend the life The installing contractor or sprinkler of copper alloy sprinklers beyond that manufacturer should be contacted with TY1131 -Upright 2.8K,1/2"NPT which would otherwise be obtained any questions. TY1231 -Pendent 2.8K,1/2"NPT TY2131 -Upright 4.2K, 1/2"NPT TY2231 -Pendent 4.2K,1/2"NPT IMPORTANT TY3131 -Upright 5.6K,1/2"NPT Always refer to Technical Data TY3231 -Pendent 5.6K,1/2"NPT Sheet TFP700 for the "INSTALLER TY4131 -Upright 8.0K,3/4"NPT WARNING"that provides cautions TY4231 -Pendent 8.0K,3/4"NPT with respect to handling and instal- TY4831 -Upright 8.0K, 1/2"NPT lation of sprinkler systems and corn- TY4931 -Pendent 8.0K, 1/2"NPT ponents. Improper handling and installation can permanently damage a sprinkler system or its compo- nents and cause the sprinkler to fail to operate in a fire situation or cause it to operate prematurely. Page 1 of 10 NOVEMBER 2015 TFP171 TFP171 Page 2 of 10 *Temperature rating ** Pipe thread connections per 1 - Frame 3 - Sealing 5 - Compression is indicated on ISO 7-1 can be provided on ESCUTCHEON 2 - Button Assembly Screw Deflector. special request. PLATE SEATING 4 - Bulb 6 - Deflector* SURFACE 7 - Bushing _ / mw_ ..,usr.=--------=-- ,r,„ rgu7 1111 ll�r MAKE MINAL N 21/4" 1"� OM 2 2-3/16" (57,2 mm) j (55,6mm) i� 1 1-9/16" 4i 4 . (39,7 mm) . c 5 \ �R 1/2"NPT** I WRENCH STYLE 10 or 20 2-7/8"(73,0 mm)DIA. FLATS RECESSED UPRIGHT PENDENT ESCUTCHEON RECESSED PENDENT CROSS SECTION FIGURE 1 QUICK RESPONSE SERIES TY-FRB UPRIGHT(TY1131)AND PENDENT(TY1231)SPRINKLERS 2.8 K-FACTOR, 1/2 INCH NPT *Temperature rating ** Pipe thread connections per 1 - Frame 3 - Sealing 5 - Compression is indicated on ISO 7-1 can be provided on ESCUTCHEON 2 - Button Assembly Screw Deflector. special request. PLATE SEATING 4 - Bulb 6 - Deflector* SURFACE W s 1 3 0111 NOMINAL1,1 - ; MAKE-N I I } (55,6�mm) �� = 2 r�r 2-3/16" I 4 i (55,6 mm) 1 1 1-1/2 410 III 6* 1/2" NPT** I WRENCH STYLE 10 or 20 2-7/8"(73,0 mm)DIA. - FLATS RECESSED UPRIGHT PENDENT ESCUTCHEON RECESSED PENDENT CROSS SECTION FIGURE 2 QUICK RESPONSE SERIES TY-FRB UPRIGHT(TY2131)AND PENDENT(TY2231)SPRINKLERS 4.2 K-FACTOR, 1/2 INCH NPT *Temperature rating ** Pipe thread connections per 1 - Frame 3 - Sealing 5 - Compression is indicated on ISO 7-1 can be provided on 2 - Button Assembly Screw Deflector. special request. ESCUTCHEON 4 - Bulb 6 - Deflector* PLATE SEATING SURFACE a if W7/16" ____„------------; 1 / � 1 0 3 NOMINAL 1 - '� 2 MAKE-IN 2-3/16" �' �` r A ii Till (55,6 mm) ��� 1 `�1 2-3/16" 4 1-1/2" (55,6 mm) (36,1 mm) (c4-------5 6* 1/2"NPT** f WRENCH ^ STYLE 10 or 20 —2-7/8"(73,0 mm)DIA. - FLATS RECESSED UPRIGHT PENDENT ESCUTCHEON RECESSED PENDENT CROSS SECTION FIGURE 3 QUICK RESPONSE SERIES TY-FRB UPRIGHT(TY3131)AND PENDENT(TY3231)SPRINKLERS 5.6 K-FACTOR, 1/2 INCH NPT TFP171 Page 3 of 10 *Temperature rating ** Pipe thread connections per 1 - Frame 3 - Sealing 5 - Compression is indicated on ISO 7-1 can be provided on ESCUTCHEON 2 - Button Assembly Screw Deflector. special request. PLATE SEATING 4 - Bulb 6 - Deflector* SURFACE 1 1/2" 0mr (12,7 mm) � / � �� Ofr 3 MAKE-NL ��� 2-5/16" L- F A 4 2 1 (58,7-5 mm) 2-1/4" J11� 1-9/16" 4i0 ' 4 (57,2 mm) I (39,7 mm) NPT** STYLE 30 or 40 r� la. 6* 3/4" } WRENCH FLATS RECESSED 2-7/B"(73,0 mm)DIA. UPRIGHT PENDENT ESCUTCHEON RECESSED PENDENT CROSS SECTION FIGURE 4 QUICK RESPONSE SERIES TY-FRB UPRIGHT(TY4131)AND PENDENT(TY4231)SPRINKLERS 8.0 K-FACTOR,3/4 INCH NPT CEILING PLATE 1 - Frame 5 - Compression SEATING SURFACE 2 - Button Screw 1 3 - Sealing 6 - Deflector* rr ---; �a Assembly ` g 4 Bulb tim ( 1,1mm) 2-1/4" ,� ^OMINAL1 (52-1mm) ;/ ! 27'2 MAKE-IN I * Temperature rating is �� 2-3/16" �) 1-9/16" 4 indicated on Deflector. (55,6 mm) (39,7 mm) \ . 1 ��5 ** Pipe thread connections mac., ` 6 * per ISO 7-1 can be 1/2" NPT** WRENCH eque tdonspecial 1 FLATS UPRIGHT PENDENT CROSS SECTION FIGURE 5 QUICK RESPONSE SERIES TY-FRB UPRIGHT(TY4831)AND PENDENT(TY4931)SPRINKLERS 8.0 K-FACTOR, 1/2 INCH NPT 4C,-; WRENCH RECESS W RECESS (END"A"USED FOR /�r� / RENCH 1/2" NPT MODELS) o ) t WRENCH RECESS (END"B"USED FOR �� 3/4"NPT MODELS) PUSH WRENCH IN TO ENSURE ENGAGEMENT WITH SPRINKLER WRENCHING AREA FIGURE 6 FIGURE 7 W-TYPE 6 SPRINKLER W-TYPE 7 RECESSED WRENCH SPRINKLER WRENCH TFP171 Page 4 of 10 Technical Design Do not attempt to compensate for insufficient adjustment in the Escutch- Data Criteria eon Plate by under- or over-tightening the sprinkler. Re-adjust the position of Approvals The TYCO Series TY-FRB, 2.8, 4.2, the sprinkler fitting to suit. UL and C-UL Listed 5.6,and 8.0 K-factor,Upright,Pendent, Series TY-FRB Upright and Pendent FM,LPCB,and NYC Approved and Recessed Pendent Sprinklers are Sprinklers Refer to Table A and B for complete intended for fire protection systems The Series TY-FRB Pendent and approval information including corrosion- designed in accordance with the stan- Upright Sprinklers must be installed resistant status. dard installation rules recognized by in accordance with the following Maximum Working Pressure the applicable Listing or Approval instructions. Refer to Table C. agency (such as, UL Listing is based on the requirements of NFPA 13, and Step 1.Install Pendent sprinklers in the Discharge Coefficient FM Approval is based on the require- pendent position. Install upright sprin- K=2.8 gpm/psi' (40,3 Ipm/bar') ments of FM's Loss Prevention Data klers in the upright position. K=4.2 gpm/psis(60,5 Ipm/bard) Sheets). Only the Style 10, 20, 30, or Step 2. With pipe-thread sealant K=5.6 gpm/psis(80,6 Ipm/bar') 40 Recessed Escutcheon, as applies- applied to the pipe threads, hand- K=8.0 gpm/psis(115,2 Ipm/bard) ble,is to be used for recessed pendent tighten the sprinkler into the sprinkler Temperature Rating installations. fitting. Refer to Table A and B. Step 3. Tighten the sprinkler into the Finishes Installation sprinkler fitting using only the W-Type Sprinkler:Refer to Table D. The TYCO Series TY-FRB,2.8,4.2,5.6, 6 Sprinkler Wrench(Figure 6).With ref and 8.0 K-factor,Upright,Pendent,and erence to Figures 1 through 5, apply Recessed Escutcheon:Signal or Pure Recessed Pendent Sprinklers must the W-Type 6 Sprinkler Wrench to the White,,Jet Black,Chrome Plated,or p sprinkler wrench flats. Natural Brass be installed in accordance with this section. Series TY-FRB Recessed Pendent Physical Characteristics Sprinklers Frame Bronze General Instructions The Series TY-FRB Recessed Pendent Button Brass/Copper Do not install any bulb-type sprinkler Sprinklers must be installed in accor- Sealing Assembly..Beryllium Nickel w/TEFLON if the bulb is cracked or there is a loss p Bulb Glass of liquid from the bulb.With the sprin- dance with the following instructions. Compression Screw Bronze kler held horizontally,a small air bubble StepA.After installingthe Style 10,20, Deflector Copper/Bronze Y Bushing(K=2.8) Bronze should be present.The diameter of the 30, or 40 Mounting Plate, as applica- air bubble is approximately 1/16 inch ble,over the sprinkler threads and with Operation (1,6 mm)for the 135°F(57°C)and 3/32 pipe-thread sealant applied to the pipe inch(2,4 mm)for the 286°F(141°C)tern- threads, hand-tighten the sprinkler into The glass bulb contains a fluid that perature ratings. the sprinkler fitting. expands when exposed to heat.When A leak-tight 1/2 inch NPT sprinkler Step B. Tighten the sprinkler into the the rated temperature is reached, the joint should be obtained byapplying a s sprinkler fittingusingonlythe W-Type fluid expands sufficiently to shatter the p Yp glass bulb, allowing the sprinkler to minimum to maximum torque of 7 to 7 Recessed Sprinkler Wrench (Figure activate and water to flow. 14 ft.-lbs.(9,5 to 19,0 Nm).A leak tight 7). With reference to Figures 1 to 4, 3/4 inch NPT sprinkler joint should be apply the W-Type 7 Recessed Sprinkler obtained with a torque of 10 to 20 ft.- Wrench to the sprinkler wrench flats. lbs. (13,4 to 26,8 Nm). Higher levels of torque can distort the sprinkler Inlet Step C. After ceiling installation and with consequent leakage or impairment finishing, slide on the Style 10, 20, 30, of the sprinkler. or 40 Closure over the Series TY-FRB Sprinkler and push the Closure over the Mounting Plate until its flange comes in contact with the ceiling. TFP171 Page 5 of 10 SPRINKLER FINISH(See Note 5) K TYPE TEMPERATURE BULB LIQUID NATURAL CHROME POLYESTER*** FACTOR COLOR BRASS PLATED 135°F(57°C) Orange PENDENT 155°F(68°C) Red (TY1231) and 175°F(79°C) Yellow 1,2,3,4 UPRIGHT °°200F 93C (TY1131) ( ) Green 286°F(141°C) Blue 135°F(57°C) Orange 2.8 RECESSED °155°F(68C 1/2"NPT PENDENT 155 (68°C) Red (TY1231)* 175°F(79°C) Yellow Figure 8 200°F(93°C) Green 1,2,4 135°F(57°C) Orange RECESSED PENDENT 155°F(68°C) Red (TY1231)** 175`F(79°C) Yellow Figure 9 200°F(93°C) Green 135°F(57°C) Orange PENDENT 155°F(68°C) Red (TY2231) and 175°F(79°C) Yellow UPRIGHT (TY2131) 200'F(93°C) Green 286°F(141°C) Blue 135°F(57°C) Orange 4.2 RECESSED °°155F 68C 1/2"NPT PENDENT ( ) Red 1,2 (TY2231)* 175°F(79°C) Yellow Figure 10 200°F(93'C) Green 135°F(57°C) Orange RECESSED )PENDENT (155°F 68°C Red (TY2231)** 175°F(79°C) Yellow Figure 11 200°F(93°C) Green NOTES: 1. Listed by Underwriters Laboratories,Inc.,(UL)as Quick Response Sprinklers. 2. Listed by Underwriters Laboratories,Inc„for use in Canada(C-UL)as Quick Response Sprinklers- 3. Approved by Factory Mutual Research Corporation(FM)as Quick Response Sprinklers. 4. Approved by the City of New York under MEA 354-01-E. 5. Where Polyester Coated Sprinklers are noted to be UL and C-UL Listed,the sprinklers are UL and C-UL Listed as Corrosion-Resistant Sprinklers. •Installed with Style 10(1/2"NPT)or Style 40(3/4"NPT)3/4"Total Adjustment Recessed Escutcheon,as applicable, "Installed with Style 20(1/2"NPT)or Style 30(3/4"NPT)1/2"Total Adjustment Recessed Escutcheon,as applicable. "'Frame and Deflector only. N/A Not Available TABLE A LABORATORY LISTINGS AND APPROVALS FOR 2.8 AND 4.2 K-FACTOR SPRINKLERS TFP171 Page 6 of 10 SPRINKLER FINISH(See Note 8) K BULB LIQUID NATURAL CHROME LEAD FACTOR TYPE TEMPERATURE COLOR BRASS PLATED POLYESTER"` COATED 135°F(57°C) Orange PENDENT(TY3231) 155°F(68°C) Red and 175°F(79°C) Yellow 1,2,3,4,5,6,7 1. 2 3,5 UPRIGHT 200°F(93°C) Green (TY3131) 286°F(141°C) Blue 135°F(57°C) Orange RECESSED 155°F(68°C) Red 5.6 PENDENT 175°F(79°C) Yellow 1,2,4,5 N/A 1/2"NPT (TY3231)* • Figure 12 200°F(93°C) Green 286°F(141°C) Blue 135°F(57°C) Orange RECESSED 155°F(68°C) Red PENDENT 175°F(79°C) Yellow 1,2,3,4,5 N/A (TY3231)°° Figure 13 200°F(93°C) Green 286°F(141°C) Blue 135°F(57°C) Orange PENDENT(TY4231) 155°F(68°C) Red and 175°F(79°C) Yellow 1,2,3,4,5,6,7 1,2,5 UPRIGHT 200°F(93°C) Green (TY4131) 286°F(141°C) Blue 135°F(57°C) Orange RECESSED 155°F(68°C) Red 8.0 PENDENT 175°F(79°C) Yellow 1,2,5 N/A 3/4"NPT (TY4231)' Figure 14 200°F(93°C) Green 286°F(141°C) 81ue 135°F(57°C) Orange RECESSED 155°F(68°C) Red PENDENT 175°F(79°C) Yellow 1,2,3,5 N/A (TY4231)°° Figure 15 200°F(93°C) Green 266°F(141°C) Blue 135°F(57°C) Orange PENDENT 155°F(68°C) Red 8.0 (TY4931) 1/2"NPT and 175°F(79°C) Yellow 1,2,4,5,6 1. 2. 5 UPRIGHT 200°F(93°C) Green (TY4831) 286°F(141°C) Blue • NOTES: 1. Listed by Underwriters Laboratories,Inc.,(UL)as Quick Response Sprinklers. 2. Listed by Underwriters Laboratories,Inc.,for use in Canada(C-UL)as Quick Response Sprinklers. 3. Approved by Factory Mutual Research Corporation(FM)as Quick Response Sprinklers. 4. Approved by the Loss Prevention Certification Board(LPCB Ref.No.007k/04)as Quick Response Sprinklers.However,LPCB does not rate the thermal sensitivity of recessed sprinklers. 5. Approved by the City of New York under MEA 354-01-E. 6. VdS Approved(For details,contact Tyco Fire Suppression&Building Products,Enschede,Netherlands,Tel.31-53-428-4444/Fax 31-53-428-3377.) 7. Approved by the Loss Prevention Certification Board(LPCB Ref.No.094a/06)as Quick Response Sprinklers. 8. Where Polyester Coated and Lead-Coated Sprinklers are noted to be UL and C-UL Listed,the sprinklers are UL and C-UL Listed as Corrosion-Resistant Sprinklers. Where Lead-Coated Sprinklers are noted to be FM Approved,the sprinklers are FM Approved as a Corrosion-Resistant Sprinklers. Installed with Style 10(1/2"NPT)or Style 40(3/4"NPT)3/4"Total Adjustment Recessed Escutcheon,as applicable. "Installed with Style 20(1/2"NPT)or Style 30(3/4"NPT)1/2"Total Adjustment Recessed Escutcheon,as applicable. ""Frame and Deflector only. N/A:Not Available TABLE B LABORATORY LISTINGS AND APPROVALS FOR 5.6 AND 8.0 K-FACTOR SPRINKLERS TFP171 Page 7 of 10 SPRINKLER FINISH K TYPE NATURAL CHROME POLYESTER LEAD FACTOR BRASS PLATED COATED PENDENT(TY1231) and 2.8 UPRIGHT(TY1131) 1/2"NPT 175 PSI(12,1 BAR) N/A RECESSED PENDENT(TY1231) PENDENT(TY2231) and 4.2 UPRIGHT(TY2131) 1/2"NPT 175 PSI(12,1 BAR) N/A RECESSED PENDENT(TY2231) PENDENT(TY3231) and 5.6 UPRIGHT(TY3131) 250 PSI(17,2 BAR) 1/2"NPT OR 175 PSI(12,1 BAR) RECESSED (SEE NOTE 1) PENDENT(TY3231) PENDENT(TY4231)and (12175,1 BARPSI ) 8 UPRIGHT(TY4131) 3/4"NPT 175 PSI(12,1 BAR) RECESSED N/A PENDENT(TY4231) PENDENT(TY4931) 1/2$.0 NPT and 175 PSI(12,1 BAR) 175 PSI UPRIGHT(TY4831) (12,1 BAR) NOTES: 1. The maximum working pressure of 250 psi(17,2 bar)only applies to the Listing by Underwriters Laboratories Inc.(UL);the Listing by Under- writers Laboratories,Inc.for use in Canada(C-UL);and,the Approval by the City of New York. TABLE C MAXIMUM WORKING PRESSURE Care and have not operated,should be replaced Care must be exercised to avoid if they cannot be completely cleaned damage to the sprinklers -before, Maintenance by wiping the sprinkler with a cloth or during, and after installation.by brushing it with a soft bristle brush. Sprin- klers damaged by dropping, striking, The TYCO Series TY-FRB must be Care must be exercised to avoid wrench twist/slippage,or the like,must maintained and serviced in accordance damage to the sprinklers before, be replaced. Also, replace any sprin- with this section. during, and after installation. Sprin- kler that has a cracked bulb or that has Before closing a fire protection system klers damaged by dropping, striking, lost liquid from its bulb. (Ref. Installa- main control valve for maintenance wrench twist/slippage,or the like,must tion Section). work on the fire protection system be replaced. Also, replace any sprin- Initial and frequent visual inspections of that it controls, obtain permission to kler that has a cracked bulb or that has random samples are recommended for shut down the affected fire protection lost liquid from its bulb. (Ref. Installa- corrosion-resistant sprinklers to verify systems from the proper authorities tion Section.) the integrity of the corrosion-resistant and notify all personnel who may be The owner is responsible for the material of construction. Thereafter, affected by this action. inspection,testing,and maintenance of annual inspections per NFPA 25 should Absence of the outer piece of an their fire protection system and devices suffice. escutcheon, which is used to cover in compliance with this document, as Inspections of corrosion-resistant a clearance hole, can delay sprinkler well as with the applicable standards sprinklers are recommended at close operation in a fire situation. of the National Fire Protection Asso- range, instead of from the floor level ciation (e.g., NFPA 25), in addition to per NFPA. Inspection at close range Sprinklers which are found to be the standards of any other authorities can better determine the exact sprin- leaking or exhibiting visible signs of having jurisdiction.Contact the install- kler condition and the long-term integ- corrosion must be replaced. ing contractor or sprinkler manufac- rity of the corrosion-resistant material, Automatic sprinklers must never be turer regarding any questions. which can be affected by the corrosive painted, plated, coated, or other- Automatic sprinkler systems are rec- conditions present. wise altered after leaving the factory. ommended to be inspected, tested, Modified sprinklers must be replaced. and maintained by a qualified Inspec- Sprinklers that have been exposed to tion Service in accordance with local corrosive products of combustion, but requirements and/or national codes. TFP171 Page 8 of 10 2-7/8"DIA. 2-7/8" DIA. (73,0 mm) 3/4" (19,1 mm) (73,0 mm) 5/Bt1/4" 1/2t1/8" 1/2"(12,7 mm) (15,9±6,4 mm) 1/4"(6,4 mm) (12,7±3,2 mm) 1/4"(6,4 2-1/4"DIA. 2-1/4"DIA. mm) / FACE OF (57,2 mm) / (57,2 mm) MOUNTING FACE OF MOUNTING SPRINKLER PLATE SPRINKLER PLATE ii--- FITTING FITTING (3,2 mm) �771 (3,2 mm) I =1� �I I T c PT]r �A r i �, I % � - / \ �1 MOUNTING II, I' MOUNTING ,:, SURFACE II SURFACE �4,m, HiImr� CLOSURE SERIES 1-5/16"(33,3 mm) CLOSURE SERIES 1-5/16"(33,3 mm) TY-FRB 13/16"(20,6 mm) TY-FRB 1-1/16"(27,0 mm) FIGURE 8 FIGURE 9 SERIES TY-FRB RECESSED PENDENT SERIES TY-FRB RECESSED PENDENT WITH TWO-PIECE 3/4 INCH TOTAL ADJUSTMENT WITH TWO-PIECE 1/2 INCH TOTAL ADJUSTMENT STYLE 10 RECESSED ESCUTCHEON STYLE 20 RECESSED ESCUTCHEON 2.8 K-FACTOR, 1/2 INCH NPT 2.8 K-FACTOR, 1/2 INCH NPT 2-7/8"DIA. - 2-7/8"DIA. 5/8x1/4" (73,0 mm) 3/4"(19,1 mm) (73,0 mm) 1/2" (12,7 1/2t1/8" mm) (15,9±6,4 mm) "(1/4 1/4"(6,4 mm) (12,7±3,2 mm) 6,4 2-1/4"DIA. 2-1/4"DIA. y mm) / FACE OF (57,2 mm) MOUNTING / FACE OF (57,2 mm) MOUNTING SPRINKLER PLATE SPRINKLER PLATE ' FITTING FITTING (3,2 mm) ii---(3,2 mm) t T = �� P77.i. . li To11111 , 'IMOUNTING , MOUNTING SURFACE ' SURFACE .., .. .. CLOSURE SERIES 1-1/4"(31,8 mm) CLOSURE SERIES 1-1/4"(31,8 mm) TY-FRB 3/4"(19,1 mm) TY-FRB 1"(25,4 mm) FIGURE 10 FIGURE 11 SERIES TY-FRB RECESSED PENDENT SERIES TY-FRB RECESSED PENDENT WITH TWO-PIECE 3/4 INCH TOTAL ADJUSTMENT WITH TWO-PIECE 1/2 INCH TOTAL ADJUSTMENT STYLE 10 RECESSED ESCUTCHEON STYLE 20 RECESSED ESCUTCHEON 4.2 K-FACTOR, 1/2 INCH NPT 4.2 K-FACTOR, 1/2 INCH NPT TFP171 Page 9 of 10 2-7/8"DIA. - 2-7/8" DIA. 5/8±1/4" (73,0 mm) 3/4" (19,1 mm) 1/2±1/8" (73,0 mm) 1/2"(12,7 mm) (15,9±6,4 mm) 2-1/4"DIA. 1/4"(6,4 mm) (12,7±3,2 mm) 2-1/4" DIA. 1/4"(6,4 mm) / FACE OF ~ (57,2 mm) MOUNTING / FACE OF (57,2 mm) SPRINKLER MOUNTING PLATE SPRINKLER PLATE FITTING FITTING / 1/8" / 1----- 1/8" (3,2 mm) (3,2 mm) �� li T G� Ij 1777 . T =l r r �� 'I, MOUNTING ,1!_ MOUNTING \SURFACE , f SURFACE CLOSURE SERIES 1-1/4"(31,8 mm) CLOSURE SERIES 1-1/4"(31,8 mm) TY-FRB 3/4"(19,1 mm) TY-FRB 1"(25,4 mm) FIGURE 12 FIGURE 13 SERIES TY-FRB RECESSED PENDENT SERIES TY-FRB RECESSED PENDENT WITH TWO-PIECE 3/4 INCH TOTAL ADJUSTMENT WITH TWO-PIECE 1/2 INCH TOTAL ADJUSTMENT STYLE 10 RECESSED ESCUTCHEON STYLE 20 RECESSED ESCUTCHEON 5.6 K-FACTOR, 1/2 INCH NPT 5.6 K-FACTOR, 1/2 INCH NPT 2-7/8" DIA. _ 2-7/8"DIA. 5/8t1/4" (73,0 mm) 3/4"(19,1 mm) y12t1/B" (73,0 mm) 1/2"(12,7 mm) (15,9±6,4 mm) 2-1/4" DIA. 1/4"(6,4 mm) (12,7±3,2 mm) 2-1/4"DIA. 1/4"(6,4 mm) FACE OF (57,2 mm) MOUNTING / FACE OF (57,2 mm) MOUNTING SPRINKLER PLATE SPRINKLER PLATE FITTING FITTING 1/8" 1/8" / (3,2 mm) / (3,21mm) 4 .7 r � � � , MOUNTING MOUNTING '�• f SURFACE lilt! SURFACE �� 1 CLOSURE SERIES 1-5/16"(33,3 mm) CLOSURE SERIES 1-5/16"(33,3 mm) TY-FRB 13/16"(20,6 mm) TY-FRB 1-1/16"(27,0 mm) FIGURE 14 FIGURE 15 SERIES TY-FRB RECESSED PENDENT SERIES TY-FRB RECESSED PENDENT WITH TWO-PIECE 3/4 INCH TOTAL ADJUSTMENT WITH TWO-PIECE 1/2 INCH TOTAL ADJUSTMENT STYLE 40 RECESSED ESCUTCHEON STYLE 30 RECESSED ESCUTCHEON 8.0 K-FACTOR, 3/4 INCH NPT 8.0 K-FACTOR,3/4 INCH NPT TFP171 Page 10 of 10 P/N 57 - XXX - X - XXX SPRINKLER TEMPERATURE SIN FINISH RATINGS 330 2.8K UPRIGHT(1/2"NPT) TY1131 1 NATURAL BRASS 135 135°F(57°C) 331 2.8K PENDENT(1/2"NPT) TY1231 3 PURE WHITE 155 1 155°F(fi6°C POLYESTER(RAL9010) (68°C) 340 4.2K UPRIGHT(1/2"NPT) TY2131 4 SIGNAL WHITE 175 175°F 79°C POLYESTER(RAL9003) ( ) 341 4.2K PENDENT(1/2"NPT) TY2231 5 JET BLACK 200 200°F(93°C) POLYESTER(RAL9005)2 370 5.6K UPRIGHT(1/2"NPT) TY3131 7 LEAD COATED 286 286°F(141°C) 371 5.6K PENDENT(1/2"NPT) TY3231 9 CHROME PLATED 390 8.0K UPRIGHT(3/4"NPT) TY4131 NOTES: 1. Eastern Hemisphere sales only. 391 8.0K PENDENT(3/4"NPT) TY4231 2. Available in only2.8K,4.2K,and 8.0K,155`F(58°C) and 200°F(93°C);requires lead time to manufacture. 360 8.0K UPRIGHT(1/2"NPT) TY4831° 361 8.0K PENDENT(1/2"NPT) TY4931` TABLE D SERIES TY-FRB PENDENT AND UPRIGHT SPRINKLERS PART NUMBER SELECTION Limited Ordering Warranty Procedure For warranty terms and conditions,visit Contact your local distributor for www.tyco-fire.com. availability. When placing an order, indicate the full product name and Part Number(P/N). Sprinkler Assemblies with NPT Thread Connections Specify: Series TY-FRB (Specify SIN), (specify K-factor), (specify Pendent or Upright)Sprinkler(specify)temperature rating, (specify) finish or coating, P/N (specify from Table D) Recessed Escutcheon Specify: Style (10, 20, 30, or 40) Recessed Escutcheon with (specify') finish, P/N(specify') Sprinkler Wrench Specify: W-Type 6 Sprinkler Wrench, P/N 56-000-6-387 Specify: W-Type 7 Sprinkler Wrench, P/N 56-850-4-001 Refer to Technical Data Sheet TFP770 GLOBAL HEADQUARTERS 11400 Pennbrook Parkway,Lansdale,PA 19446 I Telephone+1-215-362-0700 Copyright©2015 Tyco Fire Products,LP. All rights reserved. truce TEFLON is trademark of The DuPont Corporation. Fire Protection Products Seismic Bracing T0LC0r" Fig. 980 - Universal Swivel Sway Brace Attachment- 3/B" to 3/4" (UL Listed) Size Range: One size fits bracing pipe 1"(25mm)thru 2" (50mm), B-Line series OPM C ® us 12 gauge(2.6mm)channel, and all structural steel up to 1/4"(31.7mm)thick. LISTED rn w. Material: Steel •5. Function: Multi-functional attachment to structure or braced pipe fitting. `�� m Features: This product's design incorporates a concentric attachment g. opening which is critical to the performance of structural seismic connections. '12 NFPA 13 12016) 9.3.5.8.4 indicates clearly that fastener table load values are kN714\‘..../. based only on concentric loading. Mounts to any surface angle. Break off bolt head assures verification of proper installation. Installation: Fig.980 is the structural or transitional attachment component A B of a longitudinal or lateral sway brace assembly. It is intended to be combined with the"bracing pipe"and TOLCO'braced pipe"attachment, Fig. 1000, 1001, 2002,3000, 4L,4LA,4A or approved attachment to pipe to form a complete Set Bolt bracing assembly. NFPA 13 guidelines should be followed. Included Mounting Hardware To Install: Place the Fig. 980 onto the"bracing pipe".Tighten the set bolt until Is Not Included the head breaks off.Attachment can pivot for adjustment to proper brace angle. • Approvals:—Underwriters Laboratories Listed in the USA(UL)and Canada (cUL). Included in our Seismic Engineering Guidelines approved by the State of California Office of Statewide Health Planning and Development ,, (OSHPD). For additional load, spacing and placement information relating to OSHPD projects, please refer to our Seismic Engineering Guidelines, • OPM-0052-13. • • For FM Approval information refer to FM Approved page 61. • Note: Fig. 980 Swivel Attachment and Fig. 1001, 1000, 2002,4A, 4L,4LA, or • • approved attachment to pipe that make up a sway brace system of UL Listed • attachments and bracing materials which satisfies the requirements of Underwriters Laboratories and the National Fire Protection Association (NFPA) Finish: Plain, Electro-Galvanized or Stainless Steel. Contact customer service for alternative finishes. Fig.1001 Order By: Figure number and finish. Fig.9e0 Fig.960 Pat.#6,273,372, Pat.#6,517,030,Pat.#6,953,174, Pat.#6,708,930, Pat.#7,191,987,Pat.#7,441,730, , Pat.#7,669,806 Brace F1A•N 4 A Lateral Brace Longitudinal Brace Fig.9B shown Part Mtg.Hdw. Mounting Hole Max.Design Approx. Number Size A B D Load(cULus) WtJ100 in. Imml in. (mm) in. (mm) in. (mml in. Imml lbs. (kg) 980 3/8 3/8" (9.5) 51/4" (133.31 17/8" (47.6) 13/32" (10.3) 2015 (8.96) 149 (67.6) 980-1/2* 1/2" (12.7) 51/4" (133.31 17/8" 147.6) 17/32" (13.51 2015 (8.961 148 (67.1) • 980-5/8 5/8" (15.9) 51/4" (133.3) 17/8" (47.6) 11/16" (17.5) 2015 (8.96) 147 (66.7) 980-3/4 3/4" (19.0) 51/4" (133.3) 17f8" (47.6) 13/16" (20.51 2015 (8.961 146 (66.2) • * Standard size. • • Important! -For load information when using Fig. 980 with pre-installed or post-installed concrete anchors in compliance with NFPA 13(2016)or ASCE 7-10,including prying factors,see load tables on pages AL-1 thru AL-21. Eaton's B-Line series seismic bracing components are designed to be compatible only with other B-Line series bracing components, resulting in a listed seismic bracing assembly. Eaton B-Line Division warranty for seismic bracing components will be the warranty provided in Eaton B-Line Division standard terms and conditions of sale made available by Eaton,except that, in addition to the other exclusions from Eaton B-Line Division warranty, Eaton makes no warranty relating to B-Line series seismic bracing components that are combined with products not provided by Eaton. All dimensions in charts and on drawings are in inches.Dimensions shown in parentheses are in millimeters unless otherwise specified. Eaton 60 B-Line series Fire Protection Solutions Seismic Bracing TOLCO'Fig.980- Universal Swivel Sway Brace Attachment-3/s"to 3/4" (FM Approved) 144> OPM APPROVED Size Range: One size fits bracing pipe 1"(25mm)thru 2"(50mm), B-Line series 12 gauge(2.6mm1 channel,and all structural steel up to 1/4"(31.7mm)thick. a) Material:Material: Steel - E CaiI )o Function: Multi-functional attachment to structure or braced pipe fitting. tn` Features: This product's design incorporates a concentric attachment opening which is critical to the performance of structural seismic connections. ,> ,, , \ 0 y NFPA 13 (2016)9.3.5.8.4 indicates clearly that fastener table load values are based only on concentric loading. Mounts to any surface angle. Break off bolt .` head assures verification of proper installation. A Installation: Fig.980 is the structural or transitional attachment component — B of a longitudinal or lateral sway brace assembly. It is intended to be combined with the"bracing pipe'and TOLCO"braced pipe"attachment, Fig. 1000, 1001, Set Bolt 3000, 4L, 4LA,or other TOLCO approved attachment to pipe to form a complete Includes bracing assembly. NFPA 13 guidelines should be followed. Mounting Hardware Is Not Included To Install: Place the Fig.980 onto the "bracing pipe".Tighten the set bolt until the head breaks off.Attachment can pivot for adjustment to proper brace angle. a'- Approvals:—Approved by Factory Mutual Engineering(FM). Included in our Seismic Engineering Guidelines approved by the State of California Office of Statewide Health Planning and Development(OSHPDI• For additional yam' load, spacing and placement information relating to OSHPD projects, please refer to our Seismic Engineering Guidelines, OPM-0052-13. For UL Listed information refer to UL Listed page 60. Note: Fig. 980 Swivel Attachment and Fig. 1000, 1001, 4L,4LA or other TOLCO approved attachment to pipe that make up a sway brace system of • bracing materials which satisfies the requirements of Factory Mutual Engineering and the National Fire Protection Association(NFPA) Fu0.9e0 Finish: Plain, Electra-Galvanized or Stainless Steel. Fig.1001 Contact customer service for alternative finishes. Fig.999 Order By: Figure number and finish. ,i Pat.#6,273,372,Pat.#6,517,030,Pat.#6,953,174, Fig.4t Pat.#6,708,930,Pat.#7,191,987,Pat.#7,441,730, / % Brace ' ' Pat.#7,669,806 1 Designed to meet or exceed requirements of FM DS 2-8. Lateral Brace #!� J Longitudinal Brace Part Mtg.Hdw. Mounting Hole Max.Design Load**(FM) Approx. Number Size A B D 30'-44° 45°-59° 60°-74° 75°-90° Wt./100 in. (mm) in. (mm) in. Item) in. (mm) lbs./(kN) lbs./(kN) Ibs.l)kN) lbs./l(N) lbs. (kg) 9803/8 3/8" (9.5) 51/4"(133.31 17/8" (41.6) 13/32" (10.31 1 149 (67.61 980-1/2* 1/2 (12.7) 51/4"(133.31 17/8" 147.61 t7/32" (13.5) i 1320 1970 2310 2550 148 (67.11 980-5/a 5/t"(15.9) 51/4"(133.3) 17/3" 147.6) 11/16" (17.5) ! (5.87) (8.76) (10.27) (11.34) 147 (66.7) 980-3/4 3/4"(19.0) 51/4"(133.3) 17/e" (47.6) 13/i6" (20.5) 146 (66.2) " Standard size. ** Installed with 1" or 11/4" Schedule 40 brace pipe. FM Approved design loads are based on ASD design method. Important! -For load information when using Fig.980 with pre-installed or post-installed concrete anchors in compliance with NFPA 13 (2016) or ASCE 7.10,including prying factors,see load tables on pages AL-1 thru AL-21. Eaton's B-Line series seismic bracing components are designed to be compatible only with other B-Line series bracing components, resulting in a listed seismic bracing assembly. Eaton B-Line Division warranty for seismic bracing components will be the warranty provided in Eaton B-Line Division standard terms and conditions of sale made available by Eaton,except that, in addition to the other exclusions from Eaton B-Line Division warranty, Eaton makes no warranty relating to B-Line series seismic bracing components that are combined with products not provided by Eaton. All dimensions in charts and on drawings are in inches.Dimensions shown in parentheses are in millimeters unless otherwise specified. B-Line series Fire Protection Solutions 61 Eaton Seismic Bracing TOLCO' Fig. 1001 - Sway Brace Attachment (UL Listed) Size Range: Pipe size to be braced: 1"125mm)thru 8" (200mm) IPS. OPM c us Pipe size used for bracing: 1" (25mm)and 11/4"132mm)Schedule 40 IPS. Material: Steel LISTED m E. Function: For bracing pipe against sway and seismic disturbance. The pipe attachment component of a sway brace system: 1 Fig. 1001 is used in conjunction with a Fig. 900 Series fitting and 2. joined together with bracing pipe per NFPA 13, forming a complete a sway brace assembly. Features: Can be used to brace schedule 7 through schedule 40 IPS. Field adjustable, making critical pre-engineering of bracing pipe r. length unnecessary. Unique design requires no threading of bracing �- pipe. Comes assembled and ready for installation. Fig. 1001 has built-in visual verification of correct installation. See installation note below. Installation Note: Position Fig. 1001 over the pipe to be braced r Set Bons and tighten two hex head cone point set bolts until heads bottom t i Included out.A minimum of 1"125mm1 pipe extension is recommended. Brace pipe can be installed on top or bottom of pipe to be braced. Approvals: Underwriters Laboratories Listed in the USA(UL) and Canada(cUL). Included in our Seismic Engineering Guidelines approved by the State of California Office of Statewide Health Planning and a< Development(OSHPD). For additional load, spacing and placement �. information relating to OSHPD projects, please refer to our Seismic Engineering Guidelines, OPM-0052-13. '' For FM Approval information refer to FM Approved page 67. .7i Finish: Plain or Electra-Galvanized. Contact customer service for alternative finishes and materials. e� Order By: Order by figure number, pipe size to be braced, followed by pipe size used for bracing(1'(25mm)or 11/4"(32mm)),and finish. Important Note: Fig. 1001 is precision manufactured to perform its function as a critical component of a complete bracing assembly.To ensure performance,the UL Listing requires that Fig. 1001 must be used only with other TOLCO bracing products. Pipe Part Number&Approx.Wt./100 Design Load-Lbs. Size 1"(24mm)Brace Pipe 11/4"(32mm)Brace Pipe For Brace Pipe Size 1"/11/4" Sch.7 Sch.10 Sch.40 in. (mm) Lbs. (kg) Lbs. (kg) 1"/11/4" 1"/11/4" 1"/P/4" 1" 125) 1001-1 X 1 100.0 (45.3) 1001.1 X 11/4 118.0 (53.5) -•/-- 1000/1000 1000/1000 11/4"132) 1001-11/4 X 1 100.0 (45.3) 1001.11/4 X 11/4 114.0 (51.7) : 1000/1000 1000/1000 1000/1000 11/2"1401 1001-11/2 X 1 100.0 (45.3) 1001-11/2 X 11/4 115.0 (52.1) 1000/1000 1500/1500 1500/1500 2" (501 1001-2 X 1 108.0 (49.0) 1001-2 X 11/4 121.0 (54.8) 1000/1000 2015/2015 2015/2015 21/2"1651 1001.21/2 X 1 138.6 (62.8) 1001-21/2 X 11/4 160.4 (72.7) 1600/1600 2015/2765 2015/2765 3" (80) 1001-3 X 1 147.2 (66.7) 1001-3 X 11/4 168.7 (76,5) 1600/1600 2015/2765 2015/2765 4" 1100) 1001-4 X 1 160.9 (73.0) 1001-4 X 11/4 182.4 (82.7) 1600/1600 2015/2765 2015/2765 6" (150) 1001-6 X 1 190.0 (86.2) 1001-6 X 11/4 211.4 (95.9) 1600/1600 2015/2765 2015/2765 8" (200) 1001-8 X 1 217.4 (98.6) 1001-8 X 11/4 238.8 (108.3) 1600/1600 2015/2765 2015/2765 Note: Metric sizes are available, contact factory. 111111 �1r i (PA CI g.111o1 All dimensions in charts and on drawings are in inches.Dimensions shown in parentheses are in millimeters unless otherwise specified. Eaton 66 B-Line series Fire Protection Solutions Seismic Bracing 1.OLCOrM Fig. 1001 - Sway Brace Attachment (FM Approved) Size Range: Pipe size to be braced: 1" (25mm)thru 8" (20omm) IPS. OPM 11> Pipe size used for bracing: 1"125mm) and 11/4"(32mm)Schedule 40 IPS. APPROVED Material: Steel Function: For bracing pipe against sway and seismic disturbance. wu The pipe attachment component of a sway brace system: 15 Fig. 1001 is used in conjunction with a Fig. 900 Series fitting and al 9. joined together with bracing pipe per NFPA 13, forming a complete E sway brace assembly. e7 Features: Can be used to brace schedule 7 through schedule 40 IPS. Field adjustable, making critical pre-engineering of bracing pipe length unnecessary. Unique design requires no threading of bracing pipe. Can be used as a component of a four-way riser brace. Comes assembled and ready for installation. Fig. 1001 has built-in Set Bolts visual verification of correct installation. See installation note below. Included Installation Note: Position Fig. 1001 over the pipe to be braced and tighten two hex head cone point set bolts until heads bottom out.A minimum of 1'(25mm)pipe extension is recommended. Brace pipe can be installed on top or bottom of pipe to be braced. r Approvals: Approved by Factory Mutual Engineering(FM). r= Included in our Seismic Engineering Guidelines approved by the State of California 4 4' Office of Statewide Health Planning and Development(OSHPD). For additional load, spacing and placement information relating to OSHPD projects, please refer °K' to our Seismic Engineering Guidelines, OPM-0052-13. ` t; For UL Listed information refer to UL Listed page 66. Finish: Plain or Electro-Galvanized.Contact customer service for alternative fin- ishes and materials. Order By: Order by figure number, pipe size to be braced,followed by pipe °`- ' size used for bracing (1"(25mm)or 11/4" 132mm)) ,and finish. Important Note: Fig. 1001 is precision manufactured to perform its ty. function as a critical component of a complete bracing assembly. To ensure performance, the FM Approval requires that Fig. 1001 must be used only with other TOLCO bracing products. Designed to meet or exceed requirements of FM DS 2-8. Design Load-For Sch.7,Sch.10,&Sch.40 Pipe Pipe Part Number&Approx.wt/100 Allowable Horizontal Capacity Obi)Per Installation 1,2,3 Size 1"124mm)Brace Pipe ' 11/4"(32mm)Brace Pipe 30%44° 45°-59° 60°-74° 75°-90° in. (mm) Lbs. (kg) Lbs. (kg) Lbs. (kN) Lbs. IkN) Lbs. (kN) Lbs. (kN) 1" 125) 1001-1 X 1 100.0 (45.3) 1001-1 X 11/4 118.0 (53.51 1800 18.00) 2550 (11.34) 3120 (13.88) 3490 (25.521 1 I/4"1321 1001-11/4 X 1 100.0 (45.3) 1001-11/4 X 11/4 114.0 (51.71 1230 (5.47) 1740 (7.74) 2140 (9.52) 2380 (10.581 11/2"1401 1001-11/2 X 1 100.0 (45.3) 1001-11/2 X 11/4 115.0 152.11 1230 (5.47) 1740 (7.741 2140 (9.52) 2380 (10.581 2" (501 1001-2 X 1 108.0 (49.0) 1001-2 X 11/4 121.0 (54.9) 1230 (5.47) 1740 (7.741 2140 (9.52) 2380 (10.581 21/2"(65) 1001-21/2 X 1 138.6 (62.8) 1001-21/2 X 11/4 160.4 (72.7) 800 (3.56) 1130 (5.02) 1380 (6.14) 1540 (6.85) 3" 180) 1001-3 X 1 147.2 (66.7) 1001-3 X 11/4 168.7 176,5) 850 (3.78) 1200 (5.34) 1470 (6.541 1640 (7.29) 4" 1100) 1001-4 X 1 160.9 (73.0) 1001-4 X 11/4 182.4 182.7) 850 (3.78) 1200 (5.34) 1470 (6.54) 1640 (7.29) 6" 1150) 1001-6 X 1 190.0 (86.2) 1001-6 X 11/4 211.4 (95.9) 510 12.27) 730 (3.25) 890 (3.961 990 (4.40) 8" (200) 1001-8 X 1 217.4 (98.6) 1001-8 X 11/4 238.8 (108.3) 510 12.27) 730 (3.25) 890 (3.96) 990 (4.40) 1 FM Approved when used with 1 or 1 Va inch NPS Schedule 40 GB/T 3091,EN 10255H,or JIS G3451 steel pipe as the brace member. 2 Load rating for LW above refers to FM Approved Lightwall Pipe commonly referred to as"Schedule 7".These ratings may also be applied when EN 10220 and GIVE 8163 steel pipe. 3 Load rating for Schedule 10 above may be applied to GB/T 3092,EN 10255M and H,or JIS G3454,FM Approved Thinwall, or Schedule 40 steel pipes. Note: See UL load ratings in UL Listed Design Load chart shown under drawing. Note: Metric sizes are available,contact factory. rep e 0 I I I fill. ii 11111 . 4 Fig.1001 All dimensions in charts and on drawings are in inches.Dimensions shown in parentheses are in millimeters unless otherwise specified. B-Line series Fire Protection Solutions 67 Eaton Seismic Bracing TOLCO'' Fig. 4L- Longitudinal In-Line Sway Brace Attachment (UL Listed) Size Range: 2" (50mm)through 8'(200mm)IPS. OPM C us Material: Steel LISTED ci) Function: For bracing pipe against sway and seismic disturbance. Set Bolt&Hardware Included Approvals: Underwriters Laboratories Listed in the USA(UL)and Canada(cUL) 21/2"(65mm)through 8"(200mm)pipe. :d For FM Approval information refer to FM Approved page 75. , �. Included in our Seismic Engineering Guidelines approved by the State of ("494".,a,to California Office of Statewide Health Planning and Development(OSHPD). For additional load, spacing and placement information relating to OSHPD A projects, please refer to our Seismic Engineering Guidelines, OPM-0052-1 3. Installation Instructions: Fig.4L is the "braced pipe"attachment component of a longitudinal sway brace assembly. It is intended to be combined with the"bracing pipe"and TOLCO structural attachment o component to form a complete bracing assembly. NFPA 13 guidelines should be followed. ILI .11 To Install: Place the Fig.4L over the pipe to be braced and tighten bolts.Then engage"bracing pipe"into jaw opening and tighten set bolt 0.1 until head snaps off. Jaw attachment can pivot for adjustment to proper t brace angle. Finish: Plain. Contact customer service for alternative finishes and materials. Order By: Figure number, pipe size and finish. Brace Fig.980 t 4 Fig.4L Longitudinal Brace Pipe Max.Rec.Load Approx. Part Size A C D Bolt Size (cULus) Wt/100 No. in. (mm) in. (mm) in. Imml in. (mm) Ns. (kN) 16s. (kg) 41-2 2" (50) 53/e" (136.5) 21/16" (52.4) 21/16" (52.4) 1/2"-13 2015 (8.96) 243 (110.2) 4L-21/2 21/2" (65) 67/16" (163.5) 21/2" (63.5) 23/4" (69.8) 1/2'-13 2015 18.96) 253 (114.7) 9L-3 3" (80) 7" (177.8) 23/4" (69.8) 31/16" (77.8) 1/2"-13 2015 (8.961 268 (121.5) 41-4 4" (100) 81/2 (215.9) 33/8" (85.7) 311/16" (93.7) 1/2"-13 2015 (8.981 348 (157.8) 41-5 5" (125) 93/4' (247.6) 37/8" (98.4) 43/8" (111.1) 1/2"-13 2015 (8.96) 360 (172.3) 41-6 6" (150) 111/2" (292.1) 5" (127.0) 51/8" (130.2) 1/2"-13 2015 (8.96) 640 1290.3) 41-8 8" (200) 131/4" (336.5) 55/9" (142.8) 55/8" (142.9) 1/2"-13 2015 (8.96) 728 1330.2) Eaton's B-Line series seismic bracing components are designed to be compatible only with other B-Line series bracing components, resulting in a listed seismic bracing assembly. Eaton B-Line Division warranty for seismic bracing components will be the warranty provided in Eaton B-Line Division standard terms and conditions of sale made available by Eaton,except that, in addition to the other exclusions from Eaton B-Line Division warranty, Eaton makes no warranty relating to B-Line series seismic bracing components that are combined with products not provided by Eaton. All dimensions in charts and on drawings are in inches.Dimensions shown in parentheses are in millimeters unless otherwise specified. Eaton 74 B-Line series Fire Protection Solutions • Seismic Bracing TOLCO'Fig.4L- Longitudinal In-Line Sway Brace Attachment (FM Approved) Size Range: 21/2"(65mm)through 8"(200mm) IPS. OPM Material: Steel APPROVED Function: For bracing pipe against sway and seismic disturbance. Set Bolt&Hardware Included c Approvals: Approved by Factory Mutual Engineering(FM), 21/2"(65mm) ke through 8" (200mm)pipe. '�% For UL Listed information refer to UL Listed page 74. �„ E Included in our Seismic Engineering Guidelines approved by the State of ' I arty California Office of Statewide Health Planning and Development(OSHPD). A For additional load,spacing and placement information relating to OSHPD projects, please refer to our Seismic Engineering Guidelines, OPM-0052-13. Installation Instructions: Fig.4L is the"braced pipe"attachment component of a longitudinal sway brace assembly. It is intended to be combined with a"bracing pipe"e and TOLCO structural attachment3and or component to form a complete bracing assembly. NFPA 13 and/or FM guidelines should be followed. Ilk Nib. To Install: Place the Fig.4L over the pipe to be braced and tighten bolts.Then engage"bracing pipe"into jaw opening and tighten set bolt c until head snaps off.Jaw attachment can pivot for adjustment to proper brace angle. Finish: Plain.Contact customer service for alternative finishes and materials. Order By: Figure number, pipe size and finish. Designed to meet or exceed requirements of FM DS 2-8. Brace w 3 Fig.= Fig.4L Longitudinal Brace Pipe Max.Rec.Load(FM) Approx. Part Size A C D Bolt Size 30°-44° 45°-59° 60°-74° 75°-90° Wt./100 No. in. (mm) in. (mm) in. (mm) in. (mm) lbs. (kN( lbs. (kN) lbs. 114 lbs. (kN) lbs. (kg) 4L-21/2 21/2" (65) 67/16" (163.5) 21/2" (63.5) 23/4" (69.8) 1/2"-13 1030 (4.58) 1180 15.24) 1420 16.31) 1590 (7.07) 253 (114.71 4L-3 3" (80) 7" 1177.8) 23/4" (69.8) 31/18' (77.8) 1/2"-13 1030 14.581 1180 15.24) 1420 (6.31) 1590 (7.071 268 1121.5) 4L-4 4" (100) 81/2' 1215.8) 33/8" (85.7) 311/le(93.7) 1/2"-13 530 (2.36) 730 (3.25) 890 13.96) 990 (4.40) 348 1157.8) 41.-5 5" (125) 93/4' 1247.6) 37/8" (98.4) 43/8" (111.1) 1/2"-13 530 (2.36) 730 (3.25) 890 13.96) 990 (4.40) 380 (172.3) 4L-6 6" 11501 111/2' 1292.1) 5" (127.0) 51/8' (130,2) 1/2'-13 530 (2.36) 730 (3.25) 890 13.96) 990 (4.40) 640 (290.3) 4L-B 8" 1200) 131/4" (336.5) 55/8"(142.8) 55/8" (142.91 1/2"-13 490 (2.181 680 (3.02) 830 13.69) 930 (4.13) 728 (330.2) FM Approved when used with 1", 11/4', 11/2"or 2"Sch.40 brace pipe. FM Approved design loads are based on ASD design method. * UL Listed not FM Approved. Eaton's B-Line series seismic bracing components are designed to be compatible only with other B-Line series bracing components, resulting in a listed seismic bracing assembly.Eaton B-Line Division warranty for seismic bracing components will be the warranty provided in Eaton B-Line Division standard terms and conditions of sale made available by Eaton,except that, in addition to the other exclusions from Eaton B-Line Division warranty, Eaton makes no warranty relating to B-Line series seismic bracing components that are combined with products not provided by Eaton. All dimensions in charts and on drawings are in inches.Dimensions shown in parentheses are in millimeters unless otherwise specified. B-Line series Fire Protection Solutions 75 Eaton • 2-pc Recessed Sprinkler Escutcheon tit „ FPPI® Description The recessed canopy has been widely accepted as the preferred method of finished sprinkler head installation.This type of canopy is one of the most aesthetically pleasing by making the sprinkler less obtrusive. FPPI's recessed canopies are4aC..77D° available in three standard finishes and two standard thread sizes. The threadable portion or retainer features 15 tines for maximum friction to the skirt or outer ring. Both the white and black finishes are polyester powder coated for maximum durability - as well as consistent color. Non-finished canopies are available for special color match requirements. Also available in a short skirt version for residential sprinklers. Installation Specifications Proper installation of the recessed sprinkler escutcheon can be accomplished with tools ordinarily found on the job site. The installer must make sure that the Type: Adj. recessed face of the reducing coupling must extend to within 3/4" of the finished ceiling material but no farther than flush with the finished ceiling.Thread the cup Standard threads: (retainer)by hand all the way on to the sprinkler head threads.Then install the /2"or 3/4" IPS sprinkler into the reducing coupling at the end of the drop nipple according to Material: the sprinkler head manufacturers specifications.The skirt can be installed after .020" cold rolled steel the finished ceiling has been completed. Firmly push the skirt over the retainer until the skirt is firmly seated against the finished ceiling. Installation is now Standard finishes: Chrome complete. Brass White Black Adjustment range: 0_g/4„ Coverage: 2%/e The information contained herein is produced in good faith and is believed to be reliable but is provided for guidance and information purposes only.FPPI and its agents cannot assume liability or responsibility for results obtained in the use or misuse of its product by persons whose methods and qualifications are outside and beyond our control.It is the user's responsibility to determine the suitability of,methods of use,preparation prior to use,and appropriate installation for all products purchased from FPPI.It is the user's sole responsibility to observe and adapt such precautions as may be advisable or necessary for the protection of personnel and property in the handling and use of any of our products. 3198 LIONSHEAD AVE +1 -1 92010 (7 0)5991168 +1 (800)344-1822 a +1 (800)344.3775 FAX 0 2016 Fire Protection Products,Inc.