Report OFFICE Copy REGE VE Ultt APR 6 2021 `RY R 3UILDHVGiOF DNTIGAisoD i Ci I ljpiiiiitd 1111°I IH°I I 1111 I I FIRE PROTECTION CENTURION FIRE PROTECTION LLC PO BOX 1705 OREGON CITY, OR 97045 503-894-0563 Job Name : HIGHKEY LAB-PLAZA WEST BUILDING-4TH FLOOR Drawing : SP-100.00 Location : 9600 SW OAK STREET, TIGARD, OR 97232 Remote Area : 1 Contract Data File : 032111-HIGHKEY LAB-PLAZA WEST BUILDING-4TH FLOOR-SP PLANS (C Date/Time : 03/26/2021 - 12:23 AM Computer Programs by Hydratec Inc. Revision: 50.54.2 CENTURION FIRE PROTECTION LLC Page 1 HIGHKEY LAB-PLAZA WEST BUILDING-4TH FLOOR Date 03-26-21 HYDRAULIC CALCULATIONS for Project name: HIGHKEY LAB-PLAZA WEST BUILDING-4TH FLOOR Location: 9600 SW OAK STREET, TIGARD, OR 97232 Drawing no: SP-100.00 Date: 03-26-21 Design Remote area number: 1 Remote area location: 4TH FLOOR Occupancy classification: LIGHT HAZARD Density: .10 - Gpm/SqFt Area of application: 900 - SqFt Coverage per sprinkler: 196- SqFt Type of sprinklers calculated: 1/2", 5.6 K-FACTOR No. of sprinklers calculated: 9 In-rack demand: N/A- GPM Hose streams: 100-GPM Total water required(including hose streams): 323.55-GPM • @ 70.62- Psi Type of system: WET Volume of dry or preaction system: N/A- Gal Water supply information Date: Location: Source: Name of contractor: CENTURION FIRE PROTECTION LLC Address: PO BOX 1705/OREGON CITY, OR 97045 Phone number: 503-894-0563 Name of designer: FM Authority having jurisdiction: Notes: (Include peaking information or gridded systems here.) PROFF ¢ 5433OPE OREGON 134::13 N94V C. S Expires: 7/1/22 Computer Programs by Hydratec Inc. Revision: 50.54.2 Water Supply Curve C CENTURION FIRE PROTECTION LLC Page 2 HIGHKEY LAB-PLAZA WEST BUILDING-4TH FLOOR Date 03-26-21 City Water Supply: Demand: C1 -Static Pressure : 95 D1 - Elevation : 22.954 C2- Residual Pressure: 90 D2-System Flow : 223.556 C2- Residual Flow : 2293 D2- System Pressure : 79.825 Hose ( Demand ) : 100 D3- System Demand : 323.556 Safety Margin : 15.041 150 140 130 p 120 R 110 E 100 C1 C2 S 90 D2 S 80 .. U 70 I.' R 60 E 50 40 30 20 D1 10 . 300 600 900 1200 1500 1800 2100 2400 2700 FLOW( N ^ 1.85 ) Computer Programs by Hydratec Inc. Revision: 50.54.2 Fittings Used Summary CENTURION FIRE PROTECTION LLC Page 3 HIGHKEY LAB-PLAZA WEST BUILDING-4TH FLOOR Date 03-26-21 Fitting Legend Abbrev. Name V: ° 1 1% 114 2 2% 3 3% 4 5 6 8 10 12 14 16 18 20 24 E NFPA 13 90'Standard Elbow 1 2 2 3 4 5 6 7 8 10 12 14 18 22 27 35 40 45 50 61 G NFPA 13 Gate Valve 0 0 0 0 0 1 1 1 1 2 2 3 4 5 6 7 8 10 11 13 T NFPA 13 90'Flow thru Tee 3 4 5 6 8 10 12 15 17 20 25 30 35 50 60 71 81 91 101 121 Zwd Watts 709DCDA Fitting generates a Fixed Loss Based on Flow Units Summary Diameter Units Inches Length Units Feet Flow Units US Gallons per Minute Pressure Units Pounds per Square Inch Note: Fitting Legend provides equivalent pipe lengths for fittings types of various diameters. Equivalent lengths shown are standard for actual diameters of Sched 40 pipe and CFactors of 120 except as noted with *. The fittings marked with a*show equivalent lengths values supplied by manufacturers based on specific pipe diameters and CFactors and they require no adjustment. All values for fittings not marked with a*will be adjusted in the calculation for CFactors of other than 120 and diameters other than Sched 40 per NFPA. Computer Programs by Hydratec Inc. Revision: 50.54.2 Flow Summary - NFPA CENTURION FIRE PROTECTION LLC Page 4 HIGHKEY LAB-PLAZA WEST BUILDING-4TH FLOOR Date 03-26-21 SUPPLY ANALYSIS Node at Static Residual Available Source Pressure Pressure Flow Pressure Total Demand Required Pressure TEST 95.0 90 2293.0 94.866 323.56 79.825 NODE ANALYSIS Pressure Discharge Node Tag Elevation Node Type at Node at Node Notes DP02 49.0 5.6 12.25 19.6 1 EQ02 50.0 12.19 DP05 49.0 5.6 7.0 14.82 EQ05 50.0 6.79 DP01 49.0 5.6 7.0 14.82 EQ01 50.0 6.79 DP04 49.0 5.6 7.0 14.82 EQ04 50.0 6.79 DP03 49.0 5.6 7.0 14.82 EQ03 50.0 6.79 S2 50.0 5.61 12.19 19.6 K=K @ EQ02 1 50.0 12.34 2 50.0 20.8 3 50.0 21.0 4 50.0 27.0 1M 50.0 36.07 2M 50.0 36.61 3M 50.0 40.59 8T 50.0 46.23 9B 14.0 62.43 TOR 14.0 64.83 FAF 1.0 70.62 UG -3.0 72.39 BO -3.0 72.55 BI -3.0 79.57 TEST -3.0 79.83 100.0 S1 50.0 5.69 11.51 19.29 K=K @ EQ01 S3 50.0 5.69 18.29 24.31 K=K @ EQ01 S4 50.0 5.61 19.6 24.85 K=K @ EQ02 S5 50.0 5.69 25.05 28.45 K=K @ EQ03 S6 50.0 5.61 18.09 23.87 K=K @ EQ02 5 50.0 21.19 6 50.0 28.01 7 50.0 28.85 S7 50.0 5.61 19.97 25.08 K=K @ EQ02 S8 50.0 5.69 26.39 29.21 K=K @ EQ04 S9 50.0 5.69 25.81 28.89 K=K @ EQ05 Computer Programs by Hydratec Inc. Revision: 50.54.2 Final Calculations : Hazen-Williams CENTURION FIRE PROTECTION LLC Page 5 HIGHKEY LAB-PLAZA WEST BUILDING-4TH FLOOR Date 03-26-21 Node1 Elev1 K Qa Nom Fitting Pipe CFact Pt to or Ftngs Pe Node2 Elev2 Fact Qt Act Eqiv Len Total Pf/Ft Pf DP02 49 5.60 19.60 1 E 2.0 1.000 120 12.250 to 0.0 2.000 -0.433 EQ02 50 19.6 1.049 0.0 3.000 0.1253 0.376 Vet= 7.28 0.0 EQ02 19.60 12.193 K Factor= 5.61 DP05 49 5.60 14.82 1 E 2.0 1.000 120 7.000 to 0.0 2.000 -0.433 EQ05 50 14.82 1.049 0.0 3.000 0.0747 0.224 Vel = 5.50 0.0 EQ05 14.82 6.791 K Factor= 5.69 DP01 49 5.60 14.82 1 E 2.0 1.000 120 7.000 to 0.0 2.000 -0.433 EQ01 50 14.82 1.049 0.0 3.000 0.0747 0.224 Vel = 5.50 0.0 EQ01 14.82 6.791 K Factor= 5.69 DP04 49 5.60 14.82 1 E 2.0 1.000 120 7.000 to 0.0 2.000 -0.433 EQ04 50 14.82 1.049 0.0 3.000 0.0747 0.224 Vel = 5.50 0.0 EQ04 14.82 6.791 K Factor= 5.69 DP03 49 5.60 14.82 1 E 2.0 1.000 120 7.000 to 0.0 2.000 -0.433 EQ03 50 14.82 1.049 0.0 3.000 0.0747 0.224 Vel = 5.50 0.0 EQ03 14.82 6.791 K Factor= 5.69 S2 50 5.61 19.60 1 0.0 1.170 120 12.193 K= K© EQ02 to 0.0 0.0 0.0 1 50 19.6 1.049 0.0 1.170 0.1256 0.147 Vel = 7.28 1 50 19.29 1 T 5.0 14.000 120 12.340 to 0.0 5.000 0.0 2 50 38.89 1.049 0.0 19.000 0.4453 8.460 Vel= 14.44 2 50 24.85 1.25 0.0 0.670 120 20.800 to 0.0 0.0 0.0 3 50 63.74 1.38 0.0 0.670 0.2925 0.196 Vel = 13.67 3 50 24.31 1.25 0.0 11.310 120 20.996 to 0.0 0.0 0.0 4 50 88.05 1.38 0.0 11.310 0.5311 6.007 Vel= 18.89 4 50 28.45 1.25 T 6.0 4.170 120 27.003 to 0.0 6.000 0.0 1M 50 116.5 1.38 0.0 10.170 0.8915 9.067 Vel= 24.99 1M 50 0.0 2.5 0.0 14.000 120 36.070 to 0.0 0.0 0.0 2M 50 116.5 2.635 0.0 14.000 0.0383 0.536 Vel= 6.85 2M 50 107.06 2.5 0.0 31.240 120 36.606 to 0.0 0.0 0.0 3M 50 223.56 2.635 0.0 31.240 0.1276 3.985 Vel= 13.15 3M 50 0.0 2.5 T 16.474 19.480 120 40.591 to E 8.237 24.711 0.0 8T 50 223.56 2.635 0.0 44.191 0.1276 5.639 Vel = 13.15 Computer Programs by Hydratec Inc. Revision: 50.54.2 Final Calculations : Hazen-Williams CENTURION FIRE PROTECTION LLC Page 6 HIGHKEY LAB-PLAZA WEST BUILDING-4TH FLOOR Date 03-26-21 Node1 Elev1 K Qa Nom Fitting Pipe CFact Pt to or Ftngs Pe Node2 Elev2 Fact Qt Act Eqiv Len Total Pf/Ft Pf 8T 50 0.0 4 E 13.167 36.000 120 46.230 to 0.0 13.167 15.592 9B 14 223.56 4.26 0.0 49.167 0.0123 0.604 Vel = 5.03 9B 14 0.0 4 3E 39.501 130.000 120 62.426 to T 26.334 65.835 0.0 TOR 14 223.56 4.26 0.0 195.835 0.0123 2.408 Vel = 5.03 TOR 14 0.0 4 0.0 13.000 120 64.834 to 0.0 0.0 5.630 FAF 1 223.56 4.26 0.0 13.000 0.0123 0.160 Vel = 5.03 FAF 1 0.0 6 E 20.084 4.000 140 70.624 to 0.0 20.084 1.732 UG -3 223.56 6.16 0.0 24.084 0.0016 0.038 Vel = 2.41 UG -3 0.0 6 0.0 100.000 140 72.394 to 0.0 0.0 0.0 BO -3 223.56 6.16 0.0 100.000 0.0015 0.153 Vel= 2.41 BO -3 0.0 6 Zwd 0.0 4.000 140 72.547 to 0.0 0.0 7.015 ** Fixed Loss =7.015 BI -3 223.56 6.16 0.0 4.000 0.0015 0.006 Vel = 2.41 BI -3 0.0 6 E 20.084 100.000 140 79.568 to T 43.037 67.425 0.0 TEST -3 223.56 6.16 G 4.304 167.425 0.0015 0.257 Vel = 2.41 100.00 Qa= 100.00 TEST 323.56 79.825 K Factor= 36.21 S1 50 5.69 19.29 1 0.0 6.830 120 11.508 K= K @ EQ01 to 0.0 0.0 0.0 1 50 19.29 1.049 0.0 6.830 0.1218 0.832 Vel= 7.16 0.0 1 19.29 12.340 K Factor= 5.49 S3 50 5.69 24.31 1 E 2.0 7.500 120 18.288 K= K @ EQ01 to T 5.0 7.000 0.0 3 50 24.31 1.049 0.0 14.500 0.1868 2.708 Vel = 9.02 0.0 3 24.31 20.996 K Factor= 5.31 S4 50 5.61 24.85 1 T 5.0 1.170 120 19.600 K= K @ EQ02 to 0.0 5.000 0.0 2 50 24.85 1.049 0.0 6.170 0.1945 1.200 Vel = 9.22 0.0 2 24.85 20.800 K Factor= 5.45 S5 50 5.69 28.45 1 T 5.0 2.830 120 25.047 K= K @ EQ03 to 0.0 5.000 0.0 4 50 28.45 1.049 0.0 7.830 0.2498 1.956 Vel = 10.56 0.0 4 28.45 27.003 K Factor= 5.47 S6 50 5.61 23.87 1 E 2.0 15.170 120 18.090 K= K @ EQ02 to 0.0 2.000 0.0 5 50 23.87 1.049 0.0 17.170 0.1805 3.100 Vel = 8.86 5 50 25.09 1 0.0 10.000 120 21.190 to 0.0 0.0 0.0 6 50 48.96 1.049 0.0 10.000 0.6818 6.818 Vel = 18.18 Computer Programs by Hydratec Inc. Revision: 50.54.2 Final Calculations : Hazen-Williams CENTURION FIRE PROTECTION LLC Page 7 HIGHKEY LAB-PLAZA WEST BUILDING-4TH FLOOR Date 03-26-21 Node1 Elev1 K Qa Nom Fitting Pipe CFact Pt to or Ftngs Pe ******* Notes ****** Node2 Elev2 Fact Qt Act Eqiv Len Total Pf/Ft Pf 6 50 29.20 1.25 0.0 1.980 120 28.008 to 0.0 0.0 0.0 7 50 78.16 1.38 0.0 1.980 0.4263 0.844 Vel = 16.77 7 50 28.89 1.25 T 6.0 4.170 120 28.852 to 0.0 6.000 0.0 2M 50 107.05 1.38 0.0 10.170 0.7624 7.754 Vel= 22.96 0.0 2M 107.05 36.606 K Factor= 17.69 S7 50 5.61 25.08 1 T 5.0 1.170 120 19.970 K= K @ EQ02 to 0.0 5.000 0.0 5 50 25.08 1.049 0.0 6.170 0.1977 1.220 Vel= 9.31 0.0 5 25.08 21.190 K Factor= 5.45 S8 50 5.69 29.21 1 T 5.0 1.170 120 26.390 K= K @ EQ04 to 0.0 5.000 0.0 6 50 29.21 1.049 0.0 6.170 0.2622 1.618 Vel = 10.84 0.0 6 29.21 28.008 K Factor= 5.52 S9 50 5.69 28.89 1 T 5.0 6.830 120 25.813 K= K @ EQ05 to 0.0 5.000 0.0 7 50 28.89 1.049 0.0 11.830 0.2569 3.039 Vel = 10.72 0.0 7 28.89 28.852 K Factor= 5.38 Computer Programs by Hydratec Inc. Revision: 50.54.2