Report ME2ozn c07109 RECEIVED
7875svV .j-U/Q 2-1< A U G 2 4 2020
CITY yr fIGABD
BUILDING DIVISION
® ® ..r 'w mir■ �■ mir■
Equipment Package
For
Artistic EV Satellite Shop
Structural Calculations
Northwest Collision Equipment
Nat
Intertek AUTHORIZATION TO MARK
This authorizes the application of the Certification Mark(s) shown below to the models described in the Product(s)
Covered section when made in accordance with the conditions set forth in the Certification Agreement and Listing
Report. This authorization also applies to multiple listee model(s) identified on the correlation page of the Listing
Report.
This document is the property of Intertek Testing Services and is not transferable. The certification mark(s) may be
applied only at the location of the Party Authorized To Apply Mark.
Applicant: Nova Verta, USA Manufacturer: Nova Verta, USA
Address: 8207 E. Trent Avenue Address: 8207 E. Trent Avenue
Spokane Valley, WA 99212 Spokane Valley, WA 99212
Country: USA Country: USA
Contact: Mr. Brad Kennison Contact: Mr. Brad Kennison
Phone: 509-444-7910 800-668-2921 Phone: 509-444-7910 800-668-2921
FAX: 509-444-3699 FAX: 509-444-3699
Email: brad@novavertausa.com Email: brad@novavertausa.com
Party Authorized To Apply Mark: Same as Manufacturer
Report Issuing Office: Portland
Control Number: 104197 Authorized by: • �,� 'W../Lid"William arr, Certification Manager
ETL CLASSIFIE"I
C US
4 CO
Intertek
This document supersedes all previous Authorizations to Mark for the noted Report Number.
This Authorization to Mark is for the exclusive use of Intertek's Client and is provided pursuant to the Certification agreement between Intertek and its Client.Intertek's responsibility and liability are
limited to the terms and conditions of the agreement Intertek assumes no liability to any party,other than to the Client in accordance with the agreement,for any loss,expense or damage occasioned
by the use of this Authorization to Mark.Only the Client is authorized to permit copying or distribution of this Authorization to Mark and then only in its entirety.Use of Intertek's Certification mark is
restricted to the conditions laid out in the agreement and in this Authorization to Mark.Any further use of the Intertek name for the sale or advertisement of the tested material,product or service must
first be approved in writing by Intertek.Initial Factory Assessments and Follow up Services are for the purpose of assuring appropriate usage of the Certification mark in accordance with the
agreement,they are not for the purposes of production quality control and do not relieve the Client of their obligations in this respect.
Intertek Testing Services NA Inc.
165 Main Street, Cortland, NY 13045
Telephone 800-345-3851 or 607-753-6711 Fax 607-756-6699
Standard(s): Standard for Spray Application Using Flammable or Combustible Materials,ANSI/NFPA 33-2011; ERTA
2007/04/12; CGA CR 90-003, Issued: 1992/02/13 Ed:4 Paint Spraybooths and Drying Ovens
Product: Paint Spray Booth
Brand Name: N/A
Models: K40: Super Prestige, Prestige, Super Conquer, Conquer, Raptor, Empress, Excel and Maxi- range 30-60.
ATM for Report 3194129PRT-001 Page 1 of 1 ATM Issued: 30-Aug-2012
ED 16.3.15(8-Jan-10)Mandatory
CLASSIFICATION REPORT
INTERTEK TESTING SERVICES NA INC.
,,. 3933 US RT 11, CORTLAND,NY 13045
607-753-6711 FAX 607-756-9891
Job No.98250-208 Page 1 of 4 Date:June 15, 1998
Revised:January 8,2007
CLASSIFICATION REPORT NO.550000
INSPECTION,TESTS,AND EVALUATION
OF A SPRAY BOOTH
RENDERED TO
Nova Verta, USA
Spokane,WA
GENERAL:
This report gives the results of the evaluation of spray booth for conformance with the requirements of the Standard for Spray
Application Using Flammable and Combustible Materials,ANSI/NFPA 33,2003 Edition and Certification Requirements for Paint
Spraybooths and Drying Ovens,CGA CR90-003.Compliance was determined with UFC 4502.5.2 on May 15,1997. These products
*VOW were also evaluated with considerations for UL 795(Commercial Heating Equipment)and CGA-3.2(Industrial and Commercial Gas-
Fired Package Furnaces),however,no listing is being carried for these standards.
The sample was provided by the client and tested in the field. The evaluation commenced on April 12,1995 and concluded on July 11,
1995. An additional specimen for CTOF and a Double booth was evaluated on February 5,2002 in Lubbock, TX. Testing for
additional heaters was performed in August 2004. An additional investigation to the report into compliance with NFPA33-2003 was
performed on January 8,2007.
CLASSIFICATION REPORT
Spray Application Using Flammable and Combustible Materials
ANSI/NFPA 33,2003 Edition
Certification Requirements for Paint Spraybooths and Drying Ovens
CGA CR90-003
Participant:
Nova Verta,USA
16311 East Euclid Avenue,Suite H
Spokane,WA 99216-1670
.111110
Cort/Safe/Eng/LstngRprt/12Dec97 An independent organization testing for safety,performance,and certification
All services undertaken subject to the following general policy Reports are submitted for exclusive use of the clients to whom they are addressed.Their significance is subject to the
adequacy and representative character of the samples and to the comprehensiveness of the tests,examinations or surveys made.No quotations from reports or use of ITS's name is
permitted except as expressly authorized by ITS in writing.
Intertek Testing Services NA Inc.
Nova Verta,USA
Report Number:550000 Page 2 of 4 Issued:06/15/98
411111, Revised:3/25/05
CONSTRUCTION
PRODUCT COVERED:
Spray Booth,Model K40: Super Prestige,Prestige,Super Conquer,Conquer,Raptor,Empress,Excel and Maxi-range 30-60. Model
3000 and 4000 Series.
PRODUCT DESCRIPTION:
The product covered by this report is fully automated spray booth with forced air filtration system and a paint cure cycle. It is erected
on site,ground supported and permanently connected to the supply sources.An indirect-fired make-up air heater pre-conditions the air
used for ventilation and curing,where supplied,and is connected to the booth through permanently installed ducts and dampers. Listed
direct fired burners are also approved with airflow consistency maintained per model design. Direct fired capability is not permitted in
any instance where any recirculated air is present in CTOF booths for curing(high heat).
MODEL SIMILARITY:
Super Prestige contains 80-100 ea.4'florescent light tubes with external dimensions of 26',28',or 30'8"long x 14'8"wide x 11'2"
high.Prestige contains 80 ea.4'fluorescent light tubes,with external dimensions of 24'or 26'long x13'5"wide x10'2"high. Super
Conquer contains 56 ea.4'florescent light tubes,with external dimensions of 24'4"or 26'4"long x13'5"wide x10'2"high. Conquer
contains 40 ea.4'florescent light tubes,with external dimensions of 24'4"or 26'4"long x13'5"wide x10'2"high. Raptor contains 40
ea.4'florescent light tubes,with external dimensions of 24'4",26'4" 30'8"long x13'5"wide x10'2"high. Excel contains 40 ea.4'
florescent light tubes,with external dimensions of 24'or 26'long x14'5"wide x10'2"high. Empress construction is identical to the
Excel,except for the installation of one or more double-insulated sidewalls. Super Prestige models are same construction as Prestige
other than the larger make up air of the M1.5 on 26',28'and 30'dry exhaust models. M2 with 2 WW are used on the 28'and 30'wet
exhaust models. Maxi Range models 30'-80'in length and vary in height outside of 16'-20'and 16.5'-20'in width. The Maxi Range
models have the ability to sub divide into 2 separate booths to be operated independently or simultaneously and may have 1 to 3
electric roll up doors. Door motor has been tested to comply for its location to be located within the 3'rule.
4410 3000 and 4000 Series CTOF(Closed Top Open Front)and Double Booths are alike in all aspects other than lights in hip run front-to-
back in 3000 Series,and side-to-side in 4000 Series. Booth volumes for these two series shall be limited to 7500 cubic feet,with no
areas that permit dead air space. CTOF booths have no fixed doors, and rely on curtains classified as noncombustible or limited
combustible as defined in NFPA 220 or Method 2 of NFPA 701. Double booths have door frontals and exits complying with NFPA
101. The booth ventilation system cannot be isolated for operation of a single side.
RATINGS:
ELECTRICAL:
PRODUCT VOLTAGE AMPERAGE FREQUENCY
Model K40 208/240/480 V,3 phase or single phase 125 A fuse max. 60 Hz
208/240/480 V,3 phase or single phase 60 A fuse max. 60 Hz
120 V,single phase 60 A fuse max. 60 Hz
Maxi Range Models,3000
And 4000 Series 208/240/480 V,3 phase 400 A fuse max. 60 Hz
208/240/480 V,3 phase 200 A fuse max. 60 Hz
**Due to the nature of the electrical service available,some units require a separate disconnect for the booth lighting circuits.
BURNER:
Fuel Type Capacity
Natural Gas,Liquid Propane M1,M1R-800,000 Btu/hr max.
or Oil M1.5,M1.5R- 1,500,000 Btu/hr max
M2,M2R- 1,500,000 Btu/hr max.
Natural Gas LMU1 —1,000,000 Btu/hr max.
LMU1.5—1,200,000 Btu/hr max.
Cort/Safe/Eng/LstngRprt/12Dec97
Intertek Testing Services NA Inc.
Nova Verta,USA
Report Number:550000 Page 3 of 4 Issued:06/15/98
e Revised:3/25/05
TEST PERFORMANCE
A representative sample of the product was tested in accordance with the Standard for Spray Application Using Flammable and
Combustible Materials,ANSI/NFPA 33,2000 Edition. Results of these tests also indicate compliance with CSA CR90-003.
The following tests were performed:
Tests
Airflow
Door Closing Force
Combustion Test
Temperature Test
Combustible Mixture Test
Proximity of Electric Roll Up Door Motor at Top of Door
The following testing was performed for CTOF/Double Booth:
Tests
Airflow
Overspray Capture—Panel Spray
Overspray Capture—Direct Spray
Results of the tests indicate the specimens conform to applicable test criteria.
low
%O
Cort/Safe/Eng/LstngRprt/12Dec97
Intertek Testing Services NA Inc.
Nova Verta,USA
Report Number: 550000 Page 4 of 4 Issued:06/15/98
Revised:iortf
CONCLUSION
A representative sample of the product covered by this report has been evaluated and found to comply with the applicable requirements
of the Standard for Spray Application Using Flammable and Combustible Materials,ANSI/NFPA 33,2000 Edition,and Certification
Requirements for Paint Spraybooths and Drying Ovens,CGA CR90-003.
Reported by: Report Reviewed by:
[signature on file]
iowr' Brian Berlin Dale W.Soos
Project Engineer Sr.Project Engineer
Cort/Safe/Eng/LstngRprt/12Dec97
CLASSIFICATION REPORT
INTERTEK TESTING SERVICES NA INC.
3933 US ROUTE 11 CORTLAND,NY 13045
Job No. 3008277 Issued: September 11,2001
REPORT NO. 3008277-001
INSPECTION,TESTS AND EVALUATION
OF A
PAINT MIXING ROOM
RENDERED TO
NOVA VERTA USA
SPOKANE,WASHINGTON
GENERAL: This Report gives the results of the inspection,tests and evaluation of a Paint Mix Room for compliance with applicable
requirements of the Standard for Spray Application Using Flammable or Combustible Materials, ANSI/NFPA 33-2000. A
representative drawing of the Mix Room was provided by the client on and evaluated at ITS'Cortland,NY facility.
CLASSIFICATION
ANSIJNFPA 33
Participant: Manufacturer:
NOVA VERTA USA Same as Participant
16311 E.Euclid Ave,Suite H
Spokane,WA 99216-1670
Contact:Mr.Brad Kennison Contact:
Phone: 509 444 7910 800 668 2921 Phone:
Fax: 509 444 3699 Fax:
*OW An independent organization testing for safety,performance,and certification.
All services undertaken are subject to the following general policy: Reports are submitted for exclusive use of the clients to whom they are addressed. Their
significance is subject to the adequacy and representative character of the samples and to the comprehensiveness of the tests,examinations or surveys made.
This document may not be reproduced except in its entirety without written permission from ITS.
Cortland\Form\ListingReport\24FebW
Intertek Testing Services NA Inc.
Report No. 3008277-001 Page 1 Issued:09/11/01
Nova Verta USA
PRODUCT DESCRIPTION
PRODUCT COVERED
Paint Mix Room,Model MR-(Followed by dimension size,for example,MR-916 is a 9'x16'room).
PRODUCT DESCRIPTION
The product covered by this report is a paint mixing room for use in conjunction with a Classified Paint Spray Booth. The booth may
or may not be attached to the mixing room. A door is provided for personnel access. A continuously operating spark-proof blower
is provided for evacuation of volatiles. The mixing room is a freestanding structure and is provided with a fire rated air damper,
lighting fixtures,and is permanently connected to the electrical supply
MODEL SIMILARITY
All models are identical except for dimensions. Some may incorporate an external electrical control panel with switching capability
for lighting and mixing banks.
CLASSIFICATION LIMITATIONS
Maximum mixing room footprint to be 150 square feet.
Fire suppression systems to be installed per applicable NFPA Standards,by others.
Door opening force must be less than 301bf.
All electrical wiring and components must be installed per the applicable clauses of NFPA 70,and NFPA 33,for Hazardous areas.
Installation must be completed per NFPA 33,all joints shall be caulked or otherwise made air tight.
Ventilation fan must be non-sparking and maintained in continuous operation.
Portable fire extinguishers must be located per NFPA 10,by others.
r All flammable and combustible liquids shall be stored,handled,and mixed per the applicable requirements of NFPA 30.
Aluminum shall not be used to complete any enclosure,or for ducting.
ELECTRICAL RATINGS
Product Voltage Amperage Frequency
MR-(Followed by dimension size) 120 40 60
Co tland'FormlLisungReportVAFeboo
Intertek Testing Services NA Inc.
Report No. 3008277-001 Page 2 Issued:09/11/01
Nova Verta USA Revised:04/16/02
TEST PERFORMANCE
A representative sample of the product was tested in accordance with the Standard for Spray Application Using Flammable or
Combustible Materials,NFPA 33.
The following tests were performed:
Test Description
None
Results of the tests indicate the specimens conform to applicable test criteria.
*60
Cortland\Form\ListingReport\24Feb00
Intertek Testing Services NA Inc.
Report No. 3008277-001 Page 3 Issued:09/11/01
Nova Verta USA
'slaw CONCLUSION
A representative sample of the product covered by this report has been evaluated and found to comply with the applicable
requirements of the Standard for Spray Application for Flammable and Combustible Materials,NFPA 33.
Rep rt prepared j�}: Report approved by:
44 �f iV( 4,r
r
Dale W.Soos Kevin J.Wolf
Sr.Project Engineer Engineering Manager-HVAC
rh>Mw
CortlandWonn\l.istingReportl24Feb00
Intertek Testing Services NA Inc.
Report No. 3008277-001 Page 4 Issued:09/11/01
Nova Verta USA
'woo GENERAL INFORMATION
The Applicant and Manufacturer have agreed to produce,test and label ETL Listed products in accordance with the requirements of
this Report. The Manufacturer has also agreed to notify ITS and to request authorization prior to using alternate parts,components
or materials.
COMPONENTS
Components used shall be those listed in the ITS report covering the products specified in the index including any amendments and/or
revisions.
LISTING MARK
The ETL listing mark applied to the products shall either be separable in form,such as labels purchased from ITS,or on a product
nameplate or other media only as specifically authorized by ITS. Use of the listing mark is subject to the control of ITS.
MANUFACTURING AND PRODUCTION TESTS
Manufacturing and Production Tests shall be performed as required in this Report.
FOLLOW-UP SERVICE
Periodic unannounced audits of the manufacturing facility shall be scheduled by ITS. An audit report shall be issued after each visit.
In addition to the audit of the manufacturing facility,one annual audit of the listed apparatus at a field installation will be conducted
as described below under"FIELD INSTALLATION AUDIT".Special attention will be given to the following:
1. Conformance of the manufactured product to the descriptions in this Report.
2. Conformance of the use of the ETL mark with the requirements of this Report and the Listing,Labeling,and Follow-up Service
Agreement.
3. In-plant quality control procedures and personnel.
4. Manufacturing changes.
5. Performance of specified Manufacturing and Production Tests.
In the event that the ITS representative identifies non-conformance(s)to any provision of this Report,the Applicant shall take one
or more of the following actions:
1. Correct the non-conformance.
2. Remove the ETL Listing Mark from non-conforming product.
3. Contact the issuing product-safety-evaluation center-for-instructions.
____..._
FIELD INSTALLATION AUDIT(For Spray Booths Only)
1. During the manufacturing facility audit,the Estee must produce records of recent installations which indicate what was installed
and when and where each installation took place.
2. The ETL representative will make this list available to Follow Up Services in Cortland where the Certification Manager will select
several potential sites for the field audit.
3. Based on the site information submitted to the listee by the Certification Manager, the listee will identify, in a letter to the
Certification Manager,one or more sites where the annual field installation audit may take place.
4. The Certification Manager will advise the listee of the final selection and a scheduled date for the audit.
5. The areas for examination for the field installation include:
Nameplate/Markings
Lighting
Explosion Relief Venting
Cortland\rortn\ListingReport\24Feb00
NOVA VERTA USA
SPRAY BOOTH OWNERS MANUAL
NOVA VERTA USA
8207 E. TRENT AVE. • SPOKANE, WA 99212
(509) 444-7910 • (800) 668-2921 • Fax: (509) 444-3699
NOVAVERTAUSA.COM
ABLE OF CONTENTS
INTRODUCTION 1
Energy Efficiency 2
Terms & Definitions 3
General Cautions 4
Safety Precautions 5
CHAPTER 1 -- Installation
Notice To Installation Personnel 6
Booth Cabin Installation 7-12
Prep Cabin Installation 13-14
Mechanical Installation 15-19
Wiring Lights 20-22
Pit Installation 23
,HAPTER 2 -- Operating
Guidelines for high quality finish 23
Booth Maintenance 24
Dust Control 25-26
Basics of Operation 27
Panel View 300 Instructions 28-29
Panel View 550 Instructions 30-31
Panel View 600/1000 Inst. 32-33
Factory Settings 34-35
CHAPTER 3 — Start Up
Installers Check List 36
Before powering up Disconnect 37
Powering up Disconnect 38-39
CHAPTER 4 — Word Documents
Notice To Consignees 40
Customer Comment Card 41
Warranty 42-43
INTRODUCTION
ova Verta USA is the leading supplier of top performance automotive and industrial paint booths, prep
stations and closed top open face paint booths.
The last ten years has brought tremendous change and improvement in Nova Verta's spray booth technology
and performance. Nova Verta's products have been designed to be user friendly for the technicians and owners
who purchase and operate the equipment while maintaining the ability to adjust to continued paint product
changes.
Nova Verta leads the industry incorporating Total Control Technology. This technology features self-
diagnostics, automated pressure control using variable frequency drive (VFD standard on all models);
eliminating pressure control dampers. The Total Control System incorporates better control of booth pressure
and airflow, and it provides maintenance reminders, ensuring longevity of the equipment. Additionally, a
complete maintenance log can be viewed from the convenience of the operator station.
The Total Control Technology conserves energy, lowering consumption by as much as 40% over typical booth
control systems. Equipment updates are also made easier, through the use of an e-prom chip and/or PCMI card.
The majority of Nova Verta products are ETL listed in entirety not just in components assuring code
compliance, safety and performance.
;<: ep into a Nova Verta spray paint booth and you'll see what makes us the industry leader in the production and
cistribution of downdraft paint booths, mix rooms, and prep stations. With over thirty years of experience,
we've pioneered solutions to create the highest quality spray paint booth available. Only Nova Verta products
package features and benefits like these:
• Three distinct operating modes trim energy costs for the complete paint process—typically 30-40% over
competitive systems
• Allen-Bradley controls simplify paint booth operations and assure quality and parts availability
• Self-diagnostic control system provides maintenance and troubleshooting tips to maximize production
time
• Superior, shadow-free lighting optimizes visibility
• Verifiable air-flow supports water-based paints ensuring conformance to future legislative mandates
• Durable, quality construction provides built-to-last solution
• Touch safe control wiring safeguards operators
• Pre-wired controls minimize installation time and expense and ensure proper wiring
• Indirect heating recirculates warm air during final masking and paint prep providing a safe, comfortable
working environment for operators
With a nationwide network of factory-trained distributors,Nova Verta USA offers complete assistance in shop
planning, commissioning, and collaboration with your paint suppliers—all to create a turnkey solution
optimized for your production needs.
It's not by chance that Nova Verta products are the choice of Formula One racing teams,NASCAR teams,
lucational and training facilities, independent and dealer collision repair facilities, truck collision centers,
Manufacturers and many others.
1
2
TERMS AND DEFINITIONS
Definitions of some of the terms used in the manual are given below in order to facilitate the consultation and use of the manual.
BOOTH-OVEN A closed,heat-ventilated environment where painting and drying of vehicles or vehicle
parts is carried out.Equipped with vertical hot air flow from top to bottom
BASE Base of booth-oven. It may be in stone or metalwork. Designed for holding the gratings
that make up the floor of the booth-oven.
OVER-SPRAY Paint product mix not deposited on the vehicle which is drawn out by the internal air flow
GRATING Floor grating that allows the expulsion of air
FILTERS BENEATH GRATING Dry filters inserted immediately under the gratings. Their function is to catch most of the
paint product not deposited on the vehicle or part to be painted
FRONT DOOR Access door to booth-oven
SERVICE DOOR Door for operator(may be provided with anti-panic bars)
CONTROL PANEL Panel with all the controls and programmes necessary for the booth-oven to function
TEMPERATURE Device for setting and controlling temperature values
THERMOREGULATOR
TEMPERATURE CONTROL Temperature digital display
DIGITAL DISPLAY
SPRAYING PHASE Spraying/Painting operation
FLASH-OFF PHASE Phase following the spraying/painting operation indispensable for complete exhalation of
solvents from the applied paint
&KING PHASE Phase for drying applied paint
AIR RECIRCULATION Recirculation of air from inside booth
N,, PLENUM FOR AIR Chamber for expansion of air flow from generator set
DISTRIBUTION
PLENUM FILTERS Filters for intake of air into booth
GENERATOR SET Apparatus for the production of ventilated and heated air
HEAT EXCHANGER Stainless steel apparatus for the exchange of heat between the combustion products and the
air drawn in from outside and then input into booth
FLUE STACK Expulsion vent for combustion products
INTAKE DUCT Metal connecting duct between generator set and air distribution plenum
AIR RECYCLE DUCT Lower metal connecting duct between base and generator set
DIFFUSORS Punched metal located under grates and filter media.
PIT FILTERS Filters for overspray collection under grates
INTAKE FILTERS Pre filters for the burner system
(PRE FI LT ERS)
POST FILTERS Secondary filters for overspray collection for additional exhaust fan protection
ACTIVATED CARBON Solvent blasting end filters
CARTRIDGES(OPTIONAL)
VFD(VARIABLR Device utilized to control motor speed for optimum performance and pressure control of
FREQUENCY DRIVE) the paint booth
EXHAUST DUCT Round ducting for the expulsion of air from the extraction set into the atmosphere
INTAKE DUCT Round section ducting for makeup of air from atmosphere for input by the generator into
the booth
BY-PASS
PIECE TO BE PAINTED Vehicle or vehicle part which is placed in booth ready for painting
3
GENERAL CAUTIONS
• PRESERVE THIS USE AND MAINTENANCE MANUAL CAREFULLY IN A SAFE PLACE. IT
SHOULD ACCOMPANY THE EQUIPMENT IN EVERY PHASE OF ITS LIFE-CYCLE,
INCLUDING IF IT SHOULD BE LATER SOLD ON, UNTIL ITS EVENTUAL DISMANTLING.
• READ THIS USE AND MAINTENANCE MANUAL CAREFULLY BEFORE USING THE
EQUIPMENT
• USE THE EQUIPMENT ONLY FOR THE PURPOSES EXPRESSLY STATED IN THIS
MANUAL. ANY OTHER USE IS INCORRECT AND POTENTIALLY DANGEROUS
• FOLLOW THE INSTRUCTIONS IN THIS MANUAL SCRUPULOUSLY IN REGARD TO ALL
PHASES OF THE LIFE-CYCLE OF THE EQUIPMENT
• IN THE CASE OF ANY PROBLEM CONTACT ONLY SPECIALISED PERSONNEL
AUTHORISED BY THE MANUFACTURER.
• THE MANUFACTURER RESERVES THE RIGHT TO MAKE ANY MODIFICATIONS TO THE
MODEL AT ANY TIME WITHOUT ADVANCE NOTICE.
‘1601• THE MANUFACTURER DECLINES ANY RESPONSIBILITY FOR DAMAGE TO THE
EQUIPMENT, OR TO PERSONS, ANIMALS OR THINGS DERIVING FROM FAILURE OR
PARTIAL FAILURE TO OBSERVE THE REGULATIONS SET DOWN IN THIS MANUAL, OR
FROM USE OF THE EQUIPMENT BY AN INADEQUATELY TRAINED OPERATOR, OR
FROM UNAUTHORISED MODIFICATIONS, FROM DISASTERS OR NATURAL EVENTS
WITH EXCEPTIONAL CHARACTERISTICS.
• THE MANUFACTURER DECLINES ANY RESPONSIBILITY FOR COMPONENTS DESIGNED
AND REALISED BY THE CUSTOMER.
THE EQUIPMENT REMAINS THE PROPERTY OF THE MANUFACTURER UNTIL IT HAS BEEN
COMPLETELY PAID FOR.
WARNING! READ INSTRUCTION MANUAL BEFORE OPERATING BOOTH
4
WARNING SAFETY PRECAUTIONS
Maintenance or operating procedures, All users of this equipment should read,
techniques, etc..., necessary to prevent understand, and follow these safety instructions to
injury or loss of life. ensure safe and efficient operation of equipment.
AREA: HAZARD: SAFEGUARDS:
Indicates where a hazard Indicates what can happen if Indicates how to avoid the
can occur. precautions are not observed. hazard and what special
protective clothing, equipment,
and precautions will be used.
Moving Parts: Loose items, or parts of the Keep hands and all items away
body may get caught and cause from the fan blades. A guard is
injury or damage. not placed over the fan. A mesh
type guard will act as an
accumulation point for
combustible residues and
become a fire hazard.
Hot Parts: Motors get hot when running. Never touch the motor during,
Serious bums may result if or immediately after, operation
touched. of the fan.
Electrical Hazard: Electrical currents can cause Always turn electricity OFF
serious injuries. before attempting to repair or
maintenance the fan or motor.
5
Notice to all installation personnel involved in the installation of Nova
Verta Spray Booth Products.
The following procedures need to be followed upon installation of Nova Verta ETL listed Booth Products. If questions
regarding particular installation call (800) 668-2921 for proper verification. If there are any known guidelines that cannot
be adhered to,the ETL label must be removed and non-compliance check sheet sent back to Spokane main office
attention Chris Gumm. This does not mean the booth is not a safe install only that it cannot adhere to all of the
requirements.
All warning labels must be placed in the proper location as described in the warning placement guide.
Booths must be installed in accordance with NFPA33,NFPA70 and NFPA101 2011 edition.
All booth fire suppression must meet standards of supplying manufacturers requirements. All booths must have dry
hemical or wet fire suppression.
1'Vater based systems must meet NFPA13
All other systems must meet NFPA17,NFPAI2 and NFPA2001
Explosion Venting
Ceiling panels must not be adhered to or obstructed from their relief operation. Minimum clearance 15"(Nova Verta
models only).
Must be installed with restraint cables.
High Limit Switch not to exceed 200 degrees F.
Must have 2 means of egress (emergency exits). Clearance must be proper for these exits. Cannot exit through a mix
room.
Proper booth location.
Must be 3' from all other operations.
Must have clearance on all sides of 3' except in the following:
May be located less than 3' from a partition with 1 hour fire rating
May be located less than 3' from an exterior wall that is non-combustible these exceptions are provisions provided booth
can be adequately cleaned and maintained.
All field wiring must meet current editions of NEC.
Clearance of all electrical from 3' of any opening is the most common rule broken please maintain this clearance unless
properly wired for hazardous location by licensed electrician.
Ducting must meet NFPA standards and local mechanical codes for proper maintenance, penetrations and air quality
a stndards.
6
r•-•
I I 7 0 5 iir 4 i 3 i 2 40 -_-_.1„,
. ,
- ; •
I- -
rIltukiii t II ,D 0
1 '
—
" '\ dliki
'/' 1
,•' . I
-41 4110
I ,•."'"
i .00"
1 ."."..
..e
, ,••
I
8
...,"
41PF
I ,
.../.""" •
EA
11144114111111111111114116s14%,Irt....." .
..."
. ..`,A, .4. .'. : A
I 27 BASE ASSEMBLY
L_ II/WOO T
a I 7 I 6 1 5 ---16-- 4 i 3 2 1
I „
)
00
8 I 7 I 8 I-_ 5 4 3 2 1
NOTE: FOUR SECTIONS OF WALL PER BOOTH M.TRIAL LIST: WALL ASSEMBLY
o®mom
, 1111111=INIE:21
CM 16111111=1111
0 Ell fa IMMIM1111111150.7=11=111111INIM
D ...- 4 I" lanillilini== D
ice/ ro,..... 1 . ii
�
I
°1•11'...... ......' ?.(011./..... -0 i
' t.'s}- 001! 0
0011! '
rill./. : '
leo
1
1
11111,
A I IIIIVIAMMI ; A
M Y NOYAVE
" RTALUCOF
27'WALL ASSEMBLY
71 w to .«..., I
8 I 7 I 6 T 5 ? 4� 3 F--T 2 1 kW . ,Y.
0,
8 7 1 6 L__-___- 5_.. j 4 I 3 1 2 I 1
MATERIAL LIST:BACK WAL_ASSY
•l, arc iw-r
200 uaiu
L i i I 'Y Lti16V1
a
`. 7 �]ppee��, UAW
f flAa wiZS
D
D
1
C
C
V
•
•
•
•
4.
11
—
P
ei e
1
—yI
f,
A E k t A
i 27' SACK WALL ASSEMBLY
1
f, b rM
8 --I 7 --V 6 F 5 4 3 2 1
=
8 1 7 I 8 1 5 lir 4 I 3 2 1
MATERIAL LIST. PLENUM , MBLY
EN 111111 itralf# 11461
0 MN!IIZEME111111111111411
0 0 1!*""MIMIIIIBM*110
ire 11111U4 M'Ilirlr,7771111. IN
l. 0 11011111.1111112101411
D OM 01=1001111111111111111• D
..i. ICI 11•111111111111 ...117'11111, MIE
MI 111101111111MMINNIS
WA MI ,111111Irmr**11101,_ 111 ,177.17111111141
MN IIIM111•11111 .
"--t 0- —
4 ..i
4
** ...
*C
C
1
ii.
1 , *
41
.----
11#1 111 400
,0000110/111111°'''' '/ t 4/0 6111# C.
.,."' ,.........."-
, a
B .,
11111110111iihe e a 1
L 1 1 13
,
6 ..., -.4111r11111111111r* 411111011111' 6 i '
el°1
1
:0•00"...°/..°1/*(411r- 0 _
4
6
1 111011514111111111129t WM NO AVERTALISAC01^ A
A
27'P_ENUM ASSEMBLY
71
PM Na Wm El MORE Pm —1—..., .1
ralIAMIMER i
a —1 7 I 6 I 5 ----+- 4 1. 3 I 2 I 1
-,--
; i
• —s• 8 i 7 I 8 I 5 4 4 I 3 2 1
1..1 ERIAL LIST. FRONIT. AS Y
warm ifErifIllINIIIIIIIIIIIIIME:71
. .
117.1. 1111111M121EINIIMEEI
. .
Wil III ,=11111117M MI .. ....11M
VI 1111111111MI!ir.a rammesumumorrr
MilliffIr
Cl
D wawa •Nommramos rwzrammemmo D
. MI 51111111111111111111111111M . — =
..-
49 111111111111111111111111111OMI
=•1111111111111111=1111111
' 11111111111111111MINIM=IIMMI
MI 111111111M111•1111111111=
MB MIIIIIIMIIIIIMMIIIIIIIIIIIMIN=1N
II NM 111111=11111111111•11=1111111111=11111M11111111•1
,
li 1
C C
il .1
. I f
lif i I
4 4-
, `...1
B 11 i B
. • 4.
Sig**** (11:1
, 1 I •
. •...
- ..
1 I" -
0' •
1 I
.-• ,
A 1 A
. 11M- 1 VAVICNVIEFITPICOPI
27 FRONTAL ASSEMBLY
,w.....
1 . relididiei I
ma MI 11,3,7,0 p..1.1.5ft. IIIIP pa
8 I 7 I 8 I 5 I` 4 I 3 I 2 I 1
)
)
)
r 1
8 1 1 B J . 5 li' 4 I 3 2 ( 1
MATERIAL LIST: 27' DRIVE THRU I
• OPT PART 9 0 SCA,ON
I 1 03140025 CENTER SUPER STRICTURE 1
�\ 49 t 4 046001 I'BASE SIDE TRACK
3 4 1003 P BASE CORNER6
4 2 1000660 1'IRQ7 BASE TRAOS
D 5 BO CAGE NUi CAGE NUT D
\\\ 6 It 33.'. .P°412 VIAL.PANEL
1 9 334
-ISOI WALL PANG hSERT
B &. 390440N _i6l1i FlC?URC
•, 9 It 3353 ,P°di WALE.A.PLL
.�` 10 It 333E -312ER WA`.°NEL INSERT
\ F B 3357 T BAR
`\ It 2 4007 ROOF PUS END CAPS
\` IS 60 450E ORANGE FILTER TIE RODS -
14 2 4022 CEILING BRACES
IS 20 4092 tto.31UM BpACPS
16 4 4320 W,II It FILTER SUPPORT BARS
17 4 43YI ONANGG U FILTER TIE R05 cirk
IS 4 436066 CRAPES 1 milli ARROWS
19 i 04416002 UPPER LIGHT RICH:E
20 4 04496003 y01MER LI6n71161014E
21 4 04426004 PLENUM �+
12 6 NF122013190 CEILING PANE ALL
LL C
t3 I NET60X319 CEILING PANEL r.ALF
24 2 20476E RONTAL HEADER
\ F 23' 4 20466E ANT PANE:.
`. 26 4 P04966 ANT INSULATED PANEO
27 2 20P1 RN 0�BOOR
25 2 20P2 NM Al DOOR
20 2 POPS INN OS 0005
30 2 2064 WN 04 DOOR
II .FF 31 2 70011 NAiDW► K'..T
t Ns.01,
I
6 ;� 4U U
B
I
A A
tl UWW.,0vAv:RTNAACON
27' DRIVE THR
RUU
01 NA pawn WS'LW I
8 C 7 I 8 I 5 ♦ 4 1 3 I 2 1
b
M
1 I 2 I 3 I 4 I 5 1 6
PREP ARE A DOPPR
A - A
:,--''''',1100.'''''
B ` B
FF, % l
� k c ``.
k �r�ti1i J� - C
Lk
t H t , ,-:
� '
,,,N407-- _
1-141410i
L. ...
,,
D ,,,,,,,.."
r
a� Y� D
r
J
•.tl
1 I 2 I 3 I a I 5 I 6
i
0 I 0 I CO I
/ , i c AT
,; , , rik, Itni.......A inn
I
,,
.,
/ A aa "
-
1'" ' " jt /
3 ,1 / r/, / f DJ
/ , /
/ a,..=.*g : ,- \\YO° * X> i\-
-9 ki 1 • ,i
g Xf/ vs,.. 1171/4 1 / /41 S %
CD
� �7 * API "V
--' / r 8171—;771 .ie
r // ill
/ / r
..,elp/ f 7" N
%. ii:,- ,,,
s �
yi
r
\ 1==== . ...-. _.7t
! I MIMI
11111L=Ak \\1 \ik_\ 1,1)1 v nu
!V�1 i i // 5
! r7 ////I/// i
4000,
\ i
/
i '� :w/ / I
r a 1 t
1
.41
lks
I 1 / �� e
1 / , "'�i
— __ —
/ /
"� / i / '"�
,,, . x,"
,ff !5'. A '' L_,..2.}... ...,, ,7
,/jic
A/7,. .,
.
g- / . ....1_37., _
L
I / IS
J
1y.}n. p
2104
41,
14
0 I 0 I
1-- 1700 500
r i I M
., Q
1111 it
in ---1'6
gni„....2 1,1
t.) I ea 1 K1
3250
— ....
984 580
I440 i 462
(A w
ig illiga g dah..,- --i
amemern MO WIN I
111
?3
1111111111111I4i _ 1
_
4:.
1 1564 J I 480 j
— —
L
at r i_ , .
f
E ,.,
.
1 .---§
--
. ..,.., •,,,,
C —1 cn
. •
.., 1 traL ! so° 1
0 I 0 I CO I >
..,. 1 5
1 I 2 I 3 I 4 I 5 I 6
.,,
:;,...
.: A
,,,-(1891
*A
„..-0787
0733 fri 0740 illIllPlt.
arse161'..i."
0777-,„
- 0 07601 1 -
lOrl
-Of& -70792 ,
0777 i
107361 .
B iiiiiii <000 r ...-, ,i t:0754 B
0789
0755 ':'L'--1'- .
1.-0793 .
41°.$1111.1:: 0780--,, .----.... t
I
_
. _
it 0744
0751- Illitillib' \-0747 -0792
,.. .scii
..„. ,
. \ A 11,0744 ale Iiiii)0123 07601732
II '10A 0745 C
I 0792 , 0741 0765
,N I
. 1
I
.........,,,IN• /-07 ::1 It) -•••4,
: ...-
-0X t
'4 s. .7: •.„.
I-07.g _,.ob all L1.100 . -
• • /
0751-/ • 1 ., \ :It • 9rri
. .....
1
D
, • ,.,/0.3 ' L,:lit....,..,/ ip.,.r D
L .... .0 .../
1 I 2 I 3 I 4 I 5 I 6
, .••••
. ,..
0 I 0 I Ca I >
r66.9" 23.6' E=
i I 1 E
_.
,,,i 0 c _.
.
4.4
..
.11.11 4 V.
gi]
4 111111113" 11111111 '''l
1 III _
~a omonomm.us.MM.
10 18.9" ro
1 127.9'
Mir 22.86 _
I I 18.2 I
I 127.9'
...ie..
, 11,....
mi. at am'mil
, --- i
11111 UIlk it 1111111. 11
MM
allill
-8 -I, if....i - 4T. .111111
i
4.
1 W =Mill 4..
t__.
L
i 61.6" J 1 mg.
_
L
127.9*
of I 1/1.9' I (A
----1
. ,.....
Th
....
VP.
‘n•
cr) • o)
_I
„ 0 I C) I co I >
17
oo
1 I 2 I 3 1 4 I 5 I 6
Y-0892
,r-0788
A 07601 A
0733
4714.11
0739i iii
0, II 1 0759
rIi
J773 . _
0792
ki 0 :2'. 4
e
Fil 0081 ''076403 1 Iii ° -...'‘'t ;3;)'11::1
err0751 "+ 54
B ?602� 076s " 07321-v,. B
O0715 ,`.0793
07au'_
I 0781-,�
— i 0725 —
0715
i 0751 0744 1` ♦ r
rt 1 "5C11 0762 /,,,' [ . /0123
r
C
+i 0792 �� `0744 -r/ �' �/ C
i 011+ 074 -0786
b r
�: Di :
0743 0762-_ -
1704 07131
767 , ,,,,.o � ,. t —
0. �
757_." *�c� �
0770 i -,. NO Ill I PI
11
0751 0702 131 ^�
07131
0720= L
I 1 2 I 3 I 4 I 5 1 6
0.,
...
r I
4
U It ....
J I 1111 I
....
---,--- - .
_ .
,:.--'.. ".:.`.. ' ..:_-.-',:,'.-Y•!•-• :-.. • : ,41 ;
os-;• ....
...J
_ ........,S . €)
CIL '
' -...... ....... ............
..
Z
, ... all
67709 .....
1 t70 I I 1504 I
F u
1 D D
...
,1
. _
w
"RAPTOR BOOTH"
x SIDE WALL
0
m
—)
I—
M F M F M F M F M F
• F HIP FIXTI. I HIP FILLER PANEL i HIP FIXTURE f HIP FILLER PANEL L.. _ _ HIP FIXTURE 1 M
P/N 37804 - P/N 3780 1 P/N 3780-8 �
�t > I P/N 3760 P/N 3780-B P/N 3780
-
-END WITH
M MALE PLUG
. 1:
F M F M F M F M F M
t M(L)) SIDE WALL FILLER PANEL SIDE WALL FIXTURE , SIDE WALL FILLER PANEL I SIDE WALL FIXTURE - c SIDE WALL FILLER PANEL F
C4I1ram, a r ,
P/N 3780 J P/N 37B0 8 S - P/N 3780 P/N 3780-8 P/N 3780 1 P/N 3780 8 P/N 3780{
4 ) ______
-START WITH
FEMALE PLUG
LEGEND:
M(L)-MALE (LOOP)
M - MALE PLUG
F - FEMALE PLUG
CABLE DESCRIPTION:
- PLUG P/N 3780-J
- FIXTURE CABLE P/N 3780
- FIXTURE TO FIXTURE CABLE P/N 3780-8 SIZE TITLE:
- SIDE WALL TO HIP PATCH CABLE P/N 3780-C
A RAPTOR CABLE LAYOUT
- FIXTURE TO J-BOX CABLE P/N 3780-A SCALE j"_I" SHEET NA
cv
"PRESTIGE BOOTH"
x SIDE WALL
0
m
0
M F M F M F M F M F
4 ( F ' _ - _ _ - - -
HIP FIXTLRE HIP FIXTURE HIP FIXTURE I HIP FIXT RE I HIP FIXTURE I M
P/N 3780-A . P/N 3780 I P/N 3780 P/N 37$0 I PIN 3780 1 PMI 37� I
_ - - - — - - - -10
- Y
—END WITH
MALE PLUG
1,
ss
F M F M F M F M F M
14
M(L)' SIDE WALL FIXTURE I 1 SIDE WALL FIXTURE - I 1 - SIDE WALL FIXTURE - I I - SIDE WALL FIXTURE '. I SIDE WALL FIXTURE - I F
PIN 3780-J 7 P/N 3780 I I P/N 3780 _ I I _ P/N 3780 I I P/N 3700 I I P/N 3780 I P/N 3760-C
( ) - -
—START WITH
FEMALE PLUG
LEGEND:
M(L) -MALE (LOOP)
M - MALE PLUG
F - FEMALE PLUG
CABLE DESCRIPTION:
- PLUG -P/N 3780 J
- FIXTURE CABLE P/N 3780 SIZE TITLE:
- SIDEWALL TO HIP PATCH CABLE P/N 3780-C A PRESTIGE CABLE LAYOUT
- FIXTURE TO J-BOX CABLE 3780-A
S CALF 1 _) SHEET
NA
N
cV
Illii”
RANGE (LOOP).—
ine. IW
/WI
11111.1 O RANGE (LOOP)—
MALE PLUG
--ORANGE
WHITE
GREEN
n / f
FEMALE PLUG MALE PLUG
BLACK
/ +
PURPLE
ORANGE
WHITE
GREEN
n /
/ TO JBOX—T
r /
U ,r
r
FEMALE PLUG
BLACK
CANNILY,.;.mUu'aCM RM4"M RYle1 COMM MO f11
PURPLE
SIZE DWG NO.
A DESCRIPTION-010603
SCALE I"=I" SHEET S-1
r�
Cl
8 1 7 $ -- 5 ' 4 ( 3 ( 2 I 1
• AMTI VAMO710=W10m DESCRIPTION (®
Mu.AT taa 9adA] �a
/ N
a _■- �WORM
p4 lio, + is .... aur �a.as 0
AIL IN°TES:
c tinS'''.3c1
A �''�,,
A c
1 i .r
HoiST EP I -RUNNER a LEG ASSEMBLY] STEP 2 -CENTER A ANCHOR RUNNER ASSY. "4—
EMI ".m. sar nmarE arrvae11,010. ( Z
X4i.'
6 -�i ` I B
AI II 10 41 HO. .
--.......Lilit.I iii ''''',.._ ..-
• ''''SN' ... 1%111
A A
- LV[I Vat.hOVAVENTALMC01!
'7!
2-ROW ASSEMBLY
EP AN�H4RrEbGE RUNN IERS STEP 3 -PLACE FILTER TRAY'S a GRATE$( ""
$
B I 7 1 6 5 All' I 3 ( r Hr� 1 1
1
INSTALLATION OF DOORS
When building the booth cabin it is essential the booth door opening is square and
plumb as possible. Failure to heed this warning will make the installation of the doors
difficult. Do not just hang doors and try to adjust after hanging as this creates problems.
Once the opening is square and plumb begin by hanging the outer doors only. There
should be a 3mm gap between the anterior panel and the door leaf. The top and bottom gap
should be equal. Shims should be utilized to keep door positioned while tightening hinge
bolts. The hinge pin should be centered on 3mm gap or slightly toward the anterior panel.
Tighten outside leaf hinges with the 3mm gap and split top and bottom dimension.
Repeat above steps with inside door leafs maintaining a 3mm gap between the inner
and outer door leaf and equal gap at top and bottom. The door gap in the center will be much
larger than 3mm and is designed accordingly. Make final adjustment after installing
remaining hardware.
Install latching hardware positioning latches as instructions detail. Note after
positioning has been determined the remaining screws to secure location must be installed.
We have found the kit includes 2 small black pan head screws with a length of 3/8". Also
41100 included is a bag of self tapping tapered head screws (nickel color)that can also be used and
is preferred to avoid having to pilot drill for black pan heads. Note it is very important that
these screws be installed. The latching mechanisms will become damaged in a short period of
operation voiding warranty (this can easily be determined upon inspection of the latch).
Attach the release hardware as supplied directions indicate noting to cut square pin between
inside and outside latch to avoid any binding. Note that exterior handles can be reversed by
dissembling the handle for proper placement (right or left horizontally when door is closed).
Take care in threading aluminum rods that secure to latches top and bottom so that free and
correct movement is achieved before installing plastic covers. If latches bind do not apply
lubrication adjust latch mechanism housing, as lubrication is temporary fix.
Make final adjustment to door latching of exit door from the 2 inside leafs. Before
installing latching mechanism covers at top and bottom of door check to be sure latches move
freely as we have found that they can hang up. Slight widening of the sides of the latch will
allow free movement should they be tight causing binding of the latch.
22
2111
GUIDELINES TO OBTAINING HIGH GUALITY FINISH RESULTS
Following the maintenance schedule religiously is the most essential part of achieving a quality finish.
The booth is designed to be automated to control proper booth pressures, air flow and temperature
settings within normally desired settings but may need minor adjustment should any issues arise.
Proper cleaning and preparation to the vehicle or parts is essential along with the use of quality
materials such as masking paper and tape. Most if not all preparation should be completed prior to
entering the booth cabin. The booth should be in preparation mode while doors are open and moving
vehicles or parts in and out. This mode of operation will maintain positive pressure keeping
contaminates from entering the booth. The vehicle or parts should be grounded to limit any static
capabilities.
All airlines should be of quality, designed for the extreme temperatures and should be kept cleaned
from contamination. The compressed air should be filtered and free of any oil residues and humidity
commonly produced by compressors. The paint material should be properly filtered. The material
should also be of quality and properly stored and kept from being dated. The supplier should work
closely with technicians to achieve the proper reducers and catalyst for air speeds and temperatures
within the environment being sprayed. Quality HVLP spray guns with the properly set up tips and air
caps should also be addressed by the paint supplier as new technologies are constantly available.
Technicians should be wearing properly suited safety clothing and complete protection from
overspray including fresh air systems to eliminate any possible means of contamination while
spraying. The booth doors should be kept closed and traffic minimized while painting is in operation.
The technician should verify that all booth settings for temperature and air speed are correct and that
proper booth pressure is achieved prior to spraying.
If there are any questions or concerns contact Nova Verta USA (800) 668-2921for further information
or technical support.
23
Dry Filter Maintenance Schedule Booths
(Systems with Variable Frequency Drive)
Daily
iwapirow 1. Sweep booth floor with booth operating.
2. Check booth-operating pressure.
3. Open Face Models check pressure by curtain positioning or leakage at edge of curtain. The CTOF or prep station
should operate with slight negative pressure. The curtain will appear to be slightly drawn inward at proper adjusted
level.
Every 100 operation hours
1. Remove the intake prefilters from the air-heating unit and wash with pressure and replace.
2. Replace floor filter media or primary media.
Every 500 operation hours
1. Lightly use compressed air to blow out heat sinks behind VFD (variable frequency drive).
2. Replace post filtration media.
3. Replace floor media or primary media.
4. Remove and wash pre-filters in air make-up unit.
5. Inspect Damper Fluid Level. If low check for leaks at fittings.
6. Wash down booth walls and reapply new application of booth guard.
7. Inspect belts and damper in makeup air unit for proper operation.
Every 1000 operation hours
1. Check intake fan belt tension.
2. Inspect floor grating and clean with pressure hose as needed.
3. Lightly use compressed air to blow out heat sinks behind VFD(variable frequency drive).
4. Replace post filtration media.
5. Replace pre filters.
6. Replace floor media or primary media.
7. Inspect recirculation damper and lubricate hinges and pivot pins with a light grease as necessary.
8. Inspect Damper Fluid Level. If low check for leaks at fittings.
Every 2000 operation hours
1. Have trained personnel inspect burner,clean and adjust if necessary(this will insure long heat exchanger life and
lower fuel operating cost).
2. Remove pit grates, filter supports, scrape and clean pit complete. Dispose all materials in properly labeled
containers.
3. Remove intake prefilters. Blow out intake chamber with compressed air. Remove booth ceiling filters and
vacuum ceiling as needed. Replace ceiling filters (always replace prefilters at time of ceiling filters to insure
proper booth pressure). Restart booth and check pressure and adjust if necessary.
4. Inspect all door gaskets and caulked joints. Clean and repair as necessary.
5. Inspect lighting. Clean and replace any unlit light tubes as needed. Replace all light tubes every 6000 hours.
6. Check incoming airline filter at control panel service as necessary. Check airline filter regulator in booth and
service as necessary. Inspect air hose for deterioration and replace as necessary.
7. Repeat 1000-hour service information.
Disconnect and lock out power when removing any access panels for service in makeup air and
exhaust post filtration system.
The prefilters are located in service access door below burner assembly.
The exhaust post filtration is located behind access doors to exhaust fan box.
It is always best to purchase filtration from the manufacturer for best performance results and warranty.
Pre Filter— NV0123
Exhaust Post Filter— NV0125
Primary Pit Media — NV27x300-22
ceiling Diffusion Media — NV665HT
record all regular service on touch screen and provided maintenance sheet.
24
DUST CONTROL IN AUTOMOTIVE REFINISHING SPRAY BOOTHS
The control of dust in a spray booth is as critical to the refinisher as the control of bacterial
infections to a surgeon and takes just about the same degree of preventative measures. The
complete spray booth paint shop is the refinisher's closest means of measuring up to the
painstaking protective standards set by the manufacturer. By use of a spray booth, with all its
fine protective features whether by the manufacturer or the refinisher, does not assure an
uncontaminated paint job. No paint shop in the world, regardless of its careful segregation,
filtered replacements and balanced exhaust, will guarantee a spotless finish if certain seemingly
insignificant paint shop practices are ignored.
Remember that the air in a spray booth is in constant motion and that minor
malpractice in dust control will be greatly magnified.
There are a few malpractices, any of which is capable of nullifying the splendid advantage a
complete spray booth paint shop gives to the refinisher.
MALPRACTICE Allowing the operator or spectator with linty,uncovered clothing into
OF: spray booth.
RESULTS IN: The lint off the operator's clothing can contaminate a whole day's work.
CORRECTED BY: (a)Operator should,always wear starched coveralls in spray booth.
(b)Spectators should be kept out or allowed to inspect job through glass
panel.
(c) ...show room paint shop features this inspection facility.
MALPRACTICE Opening the spray booth doors on wet paint job with fan running.
OF:
RESULTS IN: A moment's exposure puts outside dust into the booth and onto the paint
job. Even drafts existing in normal shop areas can carry heavy dust
particles to the booth interior when doors are opened.
CORRECTED BY: (a)Never open doors once a job is started.
(b)Take enough material along to finish the job.
(c)An access door near fan permits entrance with minimum danger of
dust entering spray area.
(d)Remote fan control switch,which permits stopping and starting fan
from inside or outside of booth,should be installed.
(e)Do not even tack rag the job with the doors open.
MALPRACTICE Failing to clean dirt from the underbody,underside of finders and from
OF: underneath molding and seams.
RESULTS IN: Dust and dirt is blown off the underbody or from underneath fenders or
from beneath molding or out of seams.
CORRECTED BY: (a)Steam clean the underbody thoroughly. It may cost several dollars,
but it goes a long way to perfecting the finish.
(b)Use a duster to blow dirt from underneath molding and out of seams.
(c)Seal in all underneath surfaces, seams and moldings with scrap
lacquer or enamel to insure laying down all dirt. Use sandpaper to scuff
oil exterior coated surfaces after sealing. NOTE: A& B should be done
outside of spray booth.
MALPRACTICE Straining the material through a cheesecloth filter before spraying.
OF:
RESULTS IN: As much as a tablespoon of dirt and lint may come off such a filter and
contaminate the material.
' ,,,,r CORRECTED BY: Always strain material but do not use a cheesecloth strainer. Use a
metal mesh filter.
25
DUST CONTROL CONTINUED
MALPRACTICE OF: Ignoring or merely estimating proper viscosity or thinness of material for
spraying.
RESULTS IN: Overspray from an over heavy material will spot surface and give it a dirty
appearance.
CORRECTED BY: Get material manufacturer's recommendation off the container or from the
material salesman. Viscosity of synthetics is generally about 17 to 19 seconds.
MALPRACTICE OF: Allowing dust to settle on walls or floors of spray booths,on distributor plates
and in ducts
RESULTS IN: Dust accumulations anywhere in a spray booth will get on the job,eventually.
CORRECTED BY: (a)Periodic cleaning of ceiling,walls,and floor of spray booth reduces
possibility of circulating dust particles.
(b)Wetting the floor down before spraying is a wise precaution to anchor present
dust and catch new dust which may touch it.
(c)An oil saturated sweeping compound in outside of shop as well as spray
booth helps pick up or anchor dust.
(d)Install an automatic damper in exhaust stack to prevent down currents from
carrying dirt into booth. It also prevents cold air from getting in.
MALPRACTICE OF: Failing to seal seams,doors,and light openings of spray booth.
RESULTS IN: Dust particles may pull through seams and crevices to fall upon paint job.
CORRECTED BY: (a)Seal spray booth seams with caulking compound.
(b)Gaskets should be placed around doorframes,for a snug airtight fitting.
(c)Seal space between bottom edges of booth and floor.
MALPRACTICE OF: Allowing filter to become clogged with excess dirt.
/460 RESULTS IN: Increased velocity of air increases the possibility of dirt getting through the
filters.
CORRECTED BY: Filters should be cleaned or replaced when dirt begins to go through them.
MALPRACTICE OF: Using excess exhaust velocity in the fan draft.
RESULTS IN: Using more draft than enough to exhaust fumes may unduly agitate air into dust
raising currents. Excess velocity may even draw dirt through filters.
CORRECTED BY: Follow manufacturer's recommendations for the minimum velocity needed to
exhaust spray vapors properly.
MALPRACTICE OF: Neglecting to track rag surface after spraying doorjambs and truck door edges.
RESULTS IN: Spraying door jambs sets up of air within the car sends dust into and out of the
open door and into the job
CORRECTED BY: Spraying door jambs and trunk compartments first,then shutting openings and
giving the exterior its final tack ragging with a clean,new factory prepared tack
rag.
MALPRACTICE OF: Neglecting to keep spray equipment in booth clean.
RESULTS IN: Dust accumulations on transformer, cup, and on exterior of hose are loosened
and deposited on job.
CORRECTED BY: Keep equipment wiped clean.
26
Basics of Operation
The paint booth provides 5 unique operating cycles:
1st Cycle: Prep Mode, 2nd Cycle: Spray Mode, 3rd Cycle: Flash Mode, 4th Cycle: Flash Cure Mode,
h Cycle Cure Mode.
Prep Mode:
The Prep Mode is utilized for the period of loading or unloading of vehicles or parts to be painted.
Utilizing this mode conserves energy by recirculating 90% air rather than replacing 100% air 4 times a
minute that needs to be heated. This mode is also used to acclimate and finish tape off and final prep
before actual painting. This mode greatly reduces energy usage as the exhaust fans are running at
only 10% and you are only heating 10% of the outside air. This mode can only be utilized with an
indirect fired heat system as supplied with this model. In this mode the recirculation damper is in the
up position in the makeup air units. The spray gun air is shut off in this mode to prevent paint
application. The booth pressure is maintained automatically in this cycle as in all cycles from the use
of VFD's. There are no timers for this event.
Spray Mode:
The Spray Mode is used upon the readiness to apply paint. In this mode the recirculation damper is
in the closed position allowing 100% fresh air and exhausting 100% air. The spray gun solenoid is
then opened allowing air to the spray gun upon booth maintaining proper positive pressure via the
VFD's. The air is heated to the desired temperature or maintained at ambient condition if higher than
set point. There are no timers for this event.
lash Mode:
the flash mode is utilized to speed the required time between applications of coatings by speeding up
the air velocity utilizing VFD's on both the makeup air unit(s) and the exhaust unit(s). The time,
temperature and air speed are adjustable within factory parameters but usually remain preset upon
initial start up. Upon touching the flash mode button the booth air speed will increase to set point
(usually maximum) for the desired preset time and temperature and automatically cycle back to spray
mode upon completion. During this time booth pressure will also be maintained. Note Speed
increases are only available with Velocity Cure models.
Flash Cure Mode:
The flash mode is utilized to speed the required time between applications of coatings by speeding up
the air velocity utilizing VFD's on both the makeup air unit(s) and the exhaust unit(s). The damper
shifts to recirculation mode to conserve energy and aid in the removal of humidity. The time,
temperature and air speed are adjustable within factory parameters but usually remain preset upon
initial start up. Upon touching the flash mode button the booth air speed will increase to set point
(usually maximum) for the desired preset time and temperature and automatically cycle back to spray
mode upon completion. During this time booth pressure will also be maintained. Note Speed
increases are only available with Velocity Cure models.
Cure Mode:
NO ONE SHOULD ENTER THE BOOTH DURING CURE MODE.
he cure mode is utilized upon completing the final coat of paint. Upon touching this mode button the
booth will shut off the spray gun solenoid and lights and continue to exhaust 100% for minimum of 3
minutes as required per ANSI and NFPA 33 Standards (referred to as purge). During this time the
temperature will begin to rise up to 100 degrees (adjustable setting if lower temps are desired). Upon
reaching the set point of 3 minutes (adjustable up to 15 minutes) the recirculation damper will open
recirculating 90% air while adjusting motor speeds to maintain pressure and increase air speed at the
came time while also increasing temperature to desired set point (120-180 degrees). Upon reaching
are mode time set point the booth will automatically turn on the lights and shift damper to full 100%
air change to begin automated cool down cycle. Upon reaching desired cool down temperature set
point (or default time if ambient air temps are higher than temp set point) the booth will completely
shut off including lights.
All modes of operation can be interrupted by touching the System Off button.
All modes of operation incorporate safety controls and limits as determined by ANSI and NFPA Standards
current to the date at time of manufacturing.
27
law
31
Panel View Plus Operator Instructions for Standard and Velocity Cure Models
Upon initial power up (after completing startup procedures) the initial screen will display Nova
Verta contact info. Touch the NEXT button. The Daily Maintenance screen will be displayed
touch NEXT button. You are now at the main operating screen displaying the mechanics of the
booth and daily operating touch buttons (LIGHTS ON/OFF, PREP ON/OFF, SPRAY
ON/OFF,FLASH ON/OFF, CURE ON/OFF, SYSTEM ON/OFF).
1. From the Main screen touch Menu button.
2. From the MENU screen scroll down to Setup Screen-Times & Temps touch the return button
(Enter).
3. Adjust any of the preset times and temps by touching the desired button from the preset settings.
A keypad will appear that will also display range of settings top of keypad. Enter desired
settings by touching the keypad and complete by touching the Enter button. Note that this
screen has a Summer On/Off touch key. This is utilized in summer months to turn the burner
and pilot completely off for prep and spray cycles.
4. (Velocity Cure models only) In normally desired settings Flash Temp is set to same as spray
temp. Flash Time is normally set to 5 minutes but can be changed on preference. This mode is
primarily designed for water borne materials but can also be utilized for solvent based materials.
5. Note that the Cooling Temp if not able to be reached will default to Cooling Time after 5
minutes and shut down booth and lights to complete cycle. Touch Menu to return to Menu
screen.
6. (Velocity Cure models only) Scroll to Velocity Speed Settings . Note the 5 - buttons; Velocity
Cure Fan Speed (start speed of cure) and Spray Fan Speed are preset at 70%. This means that
you will run at 70%of full air speed capacity normally relating to 80-100 FPM over vehicle. If
changing speed both should be changed to the same percentage for optimal performance and
eliminate speed change over between modes of operation. Touch buttons for keypad to change
460 settings. Velocity Flash Speed is set to maximum but can be set to lower speed if necessary.
Max Cure Speed is also set to maximum and can also be lowered if desired. The maximum
speeds of flash and cure allow for air speeds to transfer heat and remove solvents or moisture at a
faster rate for maximum production and energy efficiency. These two settings should also be set
the same. Flash Ramp Offset is adjustable to balance the slow down of the intake fan with the
exhaust fan to minimize pressure differential between modes of operation when recirc- damper
shifts. Note standard models operate at 100% in all modes.
7. Touch Menu button to return to Menu Screen. Scroll down to Recirculation Damper Settings
and touch Enter. Damper delay settings are preset to .5 seconds and may need slight adjustment
to the delay after checking booth pressure when switching modes of operation from Prep to
Spray or Spray to Prep from the Main-operating screen. Note minimizing pressure changes is
the purpose of the delay settings. It is not possible to have perfect pressure while damper
changes and exhaust motor speeds are achieved. These settings are used to minimize the
pressure changes. Pressure of the booth cabin should stabilize within 30-45 seconds of the mode
change. You will have to check manually by changing modes from the Main screen while
having the entry door slightly (less than %2 inch) open. Return to Menu.
8. Note if application is for a prep station with curtain walls and no auto pressurization capability
cabin pressure is adjusted from the Menu screen by scrolling to Setup Prep Deck and touching
the Enter key. The Prep Deck Fan Speed screen will display 2 buttons Spray Fan Speed and
Prep & Bake Fan Speed each showing the percentage of the current adjustment. To adjust
pressure touch the button corresponding to the mode of operation and change percentage until
desired pressure is reached (watching curtains move in or out displaying negative or positive
pressure). Note that desired setup should be slightly negative to keep contaminates from
entering unprotected shop areas. 32
9. Note that the Menu screen features other abilities such as showing Maintenance schedules (that
also pop up as they are due), Alarm History (showing date and time of failures and also the
ability to view any current alarms), Booth Hours (shows break down of total hours into mode
hours), PLC Input—PLC Outputs (utilized for diagnostics if needed) Maintenance Entry
Screen (this screen allows entry of maintenance by simply touching the recommended
maintenance button which will log the date and hours of that maintenance automatically and
store for future reference), Maintenance PG1-Maintenance PG5 (these pages display your
logged maintenance for future reference.
10. There is also a Help & Info page from the Menu that can assist in diagnostics and maintenance.
11. Upon completion of setup test through all cycles to be sure operation is set as desired. Call Nova
Verta Tech Support for any questions or problems.
12. Note that from the Menu screen you can scroll to Debug Screen to demonstrate Alarm Test to
show how the system troubleshoots. Touch Alarm Test then touch and hold any of the 3 buttons
until pop up of alarm appears showing the alarm displaying pertinent information. Touch Reset
button and pop up of photo will appear showing actual reset action. Touch Main to return to
normal operation. From the Debug screen the Enable Manual Operations button when
touched will ask for a password, which will allow for technicians to make adjustments. Note this
is password protected to keep unwanted persons from being able to get to areas not serviceable
by other than factory authorized technicians or from over the phone technical support. Within
the debug screen is also located a software release code that limits booth operation to 80 hours
until final payment has been received which covers the software for booth operation beyond 80
hours.
Please note that Nova Verta continues to improve existing product and that future upgrades may
change these instructions slightly as new operations or screens become available.
Dated 10-1-07
33
Allen Bradley Power Flex Drive 208-480
Analog Input 0-10 Volts
FACTORY SET UP:
Upon first power up you must pick a language, English should be highlighted.
Push enter
Push escape
Push up or down arrow until ABORT is highlighted
Push enter
Parameter should be highlighted
Push ALT key
Push PAR+/-
Push 196
Push enter
Push enter
Push 1
Push enter
This gives you access to parameters you otherwise wouldn't be able to change.
SETTING PARAMETERS:
To set the following parameters put in the parameter # you wish to set and push enter.
That will take you to that parameter and it should be highlighted. To change the setting
push enter (setting should be highlighted) put in the value you want it to be and push
enter.
SET THESE PARAMETERS:
#202 - set at #2 for 208 volts
#42 - set at 32 for 208V, 16 for 480V = Overload protection
#48 - set at 1.25
#53 - set at 2
#72 - set at 10
#91 - set at 60 = High set speed
#92 - set at 5 = Low set speed
#140 - set at 20 = Acceleration ramp time
#142 - set at 20 = Deceleration ramp time
#148 - set at 50.6 for 208 Volt (default for 230 volt and 480 volt)
#150 - set at 1
#151 - Adjust for frequency noise .2 at a time (Do not exceed 8.6)
#163 - set at 2 (none) = Resistor internal or external not used
#169 - set at 1 (enabled) = Auto catch on the fly enabled
#190- set at 2 (disabled) = Reverse disabled
#320- set at 00
#325- set at 10
#326- set at 0
#361- set at 7 (run) = Input 1 logic
#362- set at 2 (clear faults) = Input 2 logic
#363- set at 0 (not used)
#364- set at 0 (not used)
#365- set at 0 (not used)
#366- set at 0 (not used)
#151-Adjust for frequency noise .2 at a time (Do not exceed 8.6)
#82 —Adjust hertz capability to higher than 60 when needed, not to exceed 68 35
INSTALLERS CHECK LIST
(Must be completed & returned to the Spokane office make copy and leave original in panel)
YES NO
1. Proper booth clearance as described in NFPA33-2011.
2. Proper fire suppression.
3. Full load amps checked not to exceed rating on nameplate.
4. Proper Egress per NFPA (exit doors).
5. Ducting requirements per NFPA and local authorities.
6. Intake motor amp draw(please record reading).
7. Exhaust motor amp draw (please record reading).
kiwpoe
8. Manuals and instructions for installation given to customer.
41410,
9. Maintenance and operation explained to operators.
10. Air velocity check sheet attached.
11. Booth cleaned and inspected for damage.
Signature of installer as to compliance of above and installation directions.
Name of Nova Verta Authorized Distributor
Signature of Owner that he has been notified of the following compliance or non-compliance issues above.
Serial # of Product: Burner Invoice #
Installation Name:
\ddress:
l hone: Fax:
Contact Name: 36
JOB NAME:
BOOTH: PREP:
SERIAL #:
TECHNICIAN: DATE:
DISTRIBUTOR:
-BERORE POWERING UP DISCONNECT-
CHECK OFF WHEN DONE
YES NO RECORD
1. Check wiring for intake motor.
2. Check wiring for exhaust motor.
3. Check wiring for drive (in& out).
4. Check wiring for burner(including airflow& high limit).
5. Check wiring for lights (including magnetic switches).
6. Check J-Boxes for ground & secure wire nuts.
7. Check all sealtite ends for tightness.
8. Check doors for alignment.
9. Check EU1DD inspection doors for proper fit.
, ,, 10. Check EU1DD for proper filters.
11. Check ceiling filters.
12. Check that the ceiling panels are secured properly.
13. Check voltage into disconnect across all three legs.
14. Check auxiliary 120-volt service.
15. If wild leg; make sure it is in the center.
16. Check touch screen wiring.
17. Pull fuses (FU 11).
18. Check for any loose wires in panel.
19. Check for wire lead damage (from shipping)
37
- POWERING UP DISCONNECT-
CHECK OFF WHEN DONE
„� YES NO RECORD
*ow1. Verify voltage in control panel.
2. Replace fuses (power off).
3. Program drive.
4. Check motor rotation.
5. Set time and date.
6. Program touch screen (damper delays, pressure, etc...).
7. Run booth in spray mode.
8. Run booth in bake mode.
9. Run booth in prep mode.
10. Check spray valve operation.
11. Check magnetic gauges on EU 1 DD and booth (also set).
12. Go through burner start up.
13. Note gas pressures and orifice size.
14. Check function of alarms, high limit, air flow, honey well.
15. HZ, of VFD in spray.
immy
16. HZ, of VFD in bake.
17. Recirculation damper in bake.
18. Recirculation damper in spray.
19. Check intake pre-filters for debris.
20. Run booth through complete cycle.
21. Check for proper sign locations.
22. Trouble shoot any operation problems.
23. Go through instructions with painters on how to use booth.
38
- CONTINUED-
CHECK OFF WHEN DONE
YES NO RECORD
1. Proper booth clearance as described in NFPA33-2011.
2. Proper fire suppression.
3. Full load amps checked not to exceed rating on name plate.
4. Proper egress per NFPA (exit doors).
5. Ducting requirements per NFPA and local authorities.
6. Intake motor amp draw in spray cycle (please record reading).
7. Intake motor amp draw in bake cycle (please record reading).
8. Exhaust motor amp draw in spray cycle (please record reading).
9. Exhaust motor amp draw in bake cycle (please record reading).
10. Check amp draw in full velocity (only with velocity cure models).
11. Manuals and instructions for installation given to customer.
12. Maintenance and operation explained to operators.
13. Air velocity check sheet attached.
14. Booth cleaned & inspected for any damage & damage noted below.
15. Go through instructions
NOTE COLUMN:
Nome
39
♦ -; I
Al
NOTICE TO CONSIGNEES
SHORTAGES:
If all the goods covered by or Bill of Lading and Packing Slip are not received by you. The
transportation company is responsible to you for your loss. You should have the number of
pieces short noted on your Freight Receipt and signed by the agent of the transportation
company.
DAMAGED GOODS:
If any goods are received damaged insure that the representative of the transportation
company makes a notation on your freight bill and signs before you accept the shipment.
If the damage to the goods is not discovered until being unpacked, cease unpacking and
immediately contact the representative of the transportation company and have him inspect
the goods and note any damage on your freight bill and sign it.
410
CLAIMS:
Claims for loss or damage should be instituted by the Consignee and supported with the
following documents:
Original Freight Bill
Original Bill of Lading
Copy of Invoice or other evidence of value
Correspondence regarding loss or damage (if any)
Canceled loss damage forms where necessary
Under contract of Carriage of Goods, notice of loss, damage or delay must be made in
writing to the carrier at point of delivery or the carrier at point of origin within sixty (60) days
after delivery of the goods or in the case of failure to make delivery, within nine (9)months
from the date of shipment together with a copy of the paid freight bill.
A notation of damage on Freight Bill at time of delivery by carrier's representative
constitutes notification of claim. If the above instructions are followed. There should be little
trouble in collecting your claims.
40
CUSTOMER COMMENT CARD
`7e would like to thank you for choosing Nova Verta. If we can be of any assistance please contact us at any
Below is a comment card we urge all of our customers to take part in filling out. The response that we receive
helps us to provide better service and support of our products.
Date: Customer Name:
City: State:
1) After your first contact with Nova Verta, did we respond in a timely manner?
❑ Excellent ❑ Good ❑ Fair ❑ Poor
2) Was your sales person professional and courteous?
❑ Excellent ❑ Good ❑ Fair ❑ Poor
3) Was your sales person helpful in explaining our product lines?
❑ Excellent ❑ Good ❑ Fair ❑ Poor
4) Was our drawing/planning department helpful?
❑ Excellent ❑ Good ❑ Fair ❑ Poor
5) Did your equipment arrive on time?
❑ Excellent ❑ Good ❑ Fair ❑ Poor
6) Was the installation completed on time?
❑ Excellent ❑ Good ❑ Fair ❑ Poor
Akkiar
7) Was the installation crew professional and courteous?
❑ Excellent ❑ Good ❑ Fair ❑ Poor
8) Did your sales person provide adequate training of the operations and maintenance procedures?
❑ Excellent ❑ Good ❑ Fair ❑ Poor
9) Did the equipment meet your expectations in quality and performance?
❑ Excellent ❑ Good ❑ Fair ❑ Poor
10) Would you purchase again from Nova Verta? ❑ Yes ❑No
11) Comments or suggestions:
ioato
41
Warranty (6-2002)
Nova Verta USA warrants Spray Booths, Prep Stations and Mix Rooms from the date they are
installed new on the premise of the original buyer, against mechanical defects in material or
rr+y workmanship for a period of I year. Electrical components are warranted against defects in
material and workmanship for a period of 1 year except those covered further by the
manufacturer (Lincoln motors, ballast etc.). This warranty is given to the original purchaser
and is non-transferable. Nova Verta USA will replace defective parts and make necessary
repairs upon its discretion under this warranty if examination reveals evidence of defective parts
or faulty workmanship. This warranty does not cover damage caused by overpowering the
electrical circuits or motors, misuse of product, accidents, neglect, or failure to maintain the
product in accordance with the maintenance schedules and training by installation personnel.
The heat exchanger unit carries a five-year pro rated warranty provided purchaser has had
qualified personnel complete burner startup procedures and completes annual service
inspection. Record of burner performance must be supplied should defect occur. The Power
Flame Burner carries a one-year warranty and with proof of above maintenance is extended by
Nova Verta USA to two years exclusive of normal maintenance as required by the manufacturer.
These warranties specifically exclude maintenance components such as filters, belts,fuses,
broken glass or any other related maintenance or wear items not properly maintained or
lubricated.
This warranty shall be in lieu of all other warranties, including the warranty of fitness and the
warranty of merchantability and the remedies set forth in this warranty shall be the only
remedies available against Nova Verta USA. Nova Verta USA shall not be liable for incidental,
consequential damage or commercial loss from damage except as set forth in this warranty.
This warranty is only for Nova Verta USA product sold and ordered by distribution through
Nova Verta USA located in Spokane, Washington.
Nova Verta USA retains the exclusive right to make any and all determinations that are
necessary in regard to the warranty of any and all components covered under this warranty.
Such determination will be made upon inspection of the possible defective component upon its
return to Nova Verta USA national distribution center.
Water related components are not warranted against rust or corrosion, as water quality and
proper maintenance are not a controllable condition by Nova Verta. This includes any
components that may come in contact with water related systems (ducting,fan base of system
etc.).
Labor and shipping charges are not included under this warranty. Warranty items must be
freight prepaid or COD. This warranty is only valid after installation test and certification
documents have been returned to Nova Verta USA.
441110,
42
WARRANTY REGESTRATION COVER SHEET
Please return the attached forms for warranty registration along with this cover sheet.
This cover sheet needs to be signed by customer that he has seen the installation and operators
manual and been instructed for operation and maintenance. He has also seen the warranty
requiring specific maintenance to maintain warranty. Warranty information must be on file
within 90 days of delivery.
Distributor or installers signature Date
Customer or authorized receiver Date
k
43
VERTA
TABLE OF CONTENTS:
1) GENERAL INSTRUCTIONS pg. 3
2) TECHNICAL SPECIFICATIONS pg. 4
3) DRAWING OF PAINT ROOM pg. 5/6
4) SAFETY RECOMMENDATIONS pg. 7
5) DESCRIPTION OF THE PAINT ROOM pg. 8
6) OPERATION pg. 9
7) USER INSTRUCTIONS pg. 10
8) DANGER WARNINGS pg. 11
10) PHOTOS pg. 12/15
NOVA VERTA USA
8207 East Trent Avenue
Spokane Valley, WA 99212
(800) 668-2921
NOVA VERTA USA Page 2
villERTA
1) GENERAL INSTRUCTIONS
Mixing rooms shall be installed to ETL Listing requirements for NFPA33 and meet the following requirements:
(1) The mixing room shall meet the construction requirements of Section 3.1.
(2) The mixing room shall not exceed 150 ft2(14 m2).
(3) The mixing room shall be designed to contain a spill of the contents of the room.
(4) The mixing room or a spray area used for mixing and dispensing operations shall be provided with continuous
mechanical ventilation capable of providing not less than 1 cfm of air movement per ft2(0.3 m3/m•m2)of floor area or 150 cfm
(4 m3/min),whichever is greater.The ventilation system shall be in operation at all times.
(5) Dispensing and mixing rooms shall be classified,for purposes of electrical area classification,the same as enclosed
spray booths,in accordance with 4.3.4.
(6) The mixing room shall be provided with an approved automatic fire protection system that meets all applicable
requirements of Chapter 7.
(7) Where a separate mixing room is provided and the mixing room is located within 6 ft(1830 mm)of an adjacent spray
area or areas,the combined quantities of liquids located in the spray areas and the mixing room shall not exceed 120 gal(454
L).
FOREWORD
This guide has been written for staff in charge of using the paint mixing booth PAINT ROOM
model.
Staff in charge of its use refers to anyone with the skills and technical knowledge able to operate
the paint mixing booth.
kirmw
This guide illustrates the various mechanical and electrical parts of the PAINT ROOM and sets out
the correct and compliant use of the paint mixing booth.
CAUTION: THE PAINT ROOM CAN ONLY BE USED FOR THE
41
40111,1 SPECIFIC USE SET OUT IN THIS GUIDE
This guide must be read by staff before the PAINT ROOM is commissioned.
CAUTION: ALL SAFETY INSTRUCTIONS
, a CONTAINED IN THIS GUIDE MUST BE
COMPLIED WITH!
This user guide should be kept close to the control power panel of the paint mixing booth, in a
place which is appropriately sheltered but at the same time easy to access, so it may always be
within easy reach.
A PAINT ROOM can also be provided with a bench to prepare the paints BENCH model; this guide
is valid irrespective of the presence of the BENCH as the information set out here is of a general
nature.
If the PAINT ROOM is provided with a paint preparation bench, BENCH model, refer to the
relevant user and maintenance guides for information.
NOVA VERTA USA Page 3
VERTA
2) TECHNICAL SPECIFICATIONS
DIMENSIONS
The PAINT ROOM has a modular structure; the table below shows the dimensions which can be
achieved by combining the various modules: (not to exceed 150 square feet)
WIDTH mm LENGTH mm
4.8'
6.4'
6.8' 10.5' 12.4' 14.3' 16.3' 17.6' 19.6' 20.2' 22.2' 24.2'
8.5'
10.5'
The height is the same for all models: 9' externally
8.8' internally
Custom Dimensions can be achieved upon special order.
The exhaust fan protrudes by 20" beyond the external height jndicated above.
Exhaust Fan
Air-exhaust fan to be applied on-site on one of the roof panels of the Paint Room (if a paint
preparation bench is not present), or to position at the end of the 0250 vertical pipe of the
bench, if this is present.
Air flow extracted : 1000 CFM
Single Phase Motor 1/6th HP
Power supply : 120/220 Volt single phase
POWER PANEL
Type of operation : On/Off fan (with Red Light On Indication) - On/Off Lights
tir..r» NOVA VERTA USA Page 4
eVERTA
3) DRAWING OF PAINT ROOM
The drawing of the paint mixing booth is shown below in its standard configuration which
measures 2580x3180x2740 h mm.
The drawing is supplied with identification codes of the various parts. These codes are essential
to Nova Verta for identifying the component.
The following pages show the elements of the various pieces of the PAINT ROOM with some
instructions for assembly.
3PLAS
3540 3537 \ /4011
3560 - \ 3039
3009 `` 35E0
3P1 4S \ 1. J ,I `\
3537 \ ". \ ` 35�6 3009
3566 Milk
���
3008 i I -� 3547
4414boo,
3546 ,, \ 4// /
\ / / \3021
3009 r �- ,I 4,011.
.�' 3009 1V ,-.IS '''�
iii
OROOM 40 4740 ___....Lc--- , 4 ., t 3009
1,
5063 �� I I t 3562
2E50 2651 I 3542
3553 . 1 3553
3543___406,..
3551
3543
3009
2090\ 2550 D 3540
0 1552 \ 3C21
60 4..7 1 3542
p ,2550 1 \354166
AIL8000.8'0 3551
..,.41
3PS 1'J86 2550 D/ i4,1
2060 �{ •
T �.• iP
y
,../ Mit .N.,.."0
# v ?
Cod. 3100#2 Cod. 4021 #50 Cod. 1004#50 Cod. 1009#60 Cod. 1008 #100
NOVA VERTA USA Page 5
t!../VERTA
PCS 118 PCS PCS ft30
A `° Lr
c."..--' ...,"..7 V ---.. `-. Josie _ -'1.44': ,,- /.., A \42Se
f
n-N,{9 .--__79;-_ ,.<- ,, ,, ,,,,,,,--..- 0
lil Cl ' ,./../../."7:-";;"
Cod.3542#2 Cod.3543#4 Cod. 3552#2 Cod.3553#4
I a o g
.D tp
5721 N N
1 i / --
Cod.3021#4 Cod.3009#7 Cod. 3540#2 Cod.354166#1
I
Waw 9r PCS#4° is ##1u
1
4E11 „A./..,9,? o 1 t \*.*:,..-`.,...t/5.0
N toQ 0 0 \� X{",A7s."-_, \4'0
�/ a% ��o \ \ss
Cod.2550 D#1 Cod.3546#2 Cod. 3547#2 Cod.3560#5
PCS 08 PCS _.
lea 'l-1 Ts.-ss
6C ssp I
101
I� / ][jill
\ *y I Cod.2060#2 cod.5000.751*1
0
).. '. ..-'...'
Cod.3637#4 Cod.3PLAS 4 2 Cod. 3PS 1V66#1 I
i ccd.dooas7d:, QM.n5o,#,
NOVA VERTA USA Page 6
o`'!i!ERTA
4) SAFETY RECOMMENDATIONS
The installations manufactured by Nova Verta U S A are designed and built in compliance
with NFPA33 to meet listing requirements provided by ETL/Intertek.
The indication of the ETL Listing is located on the wall panel near the door entry.
Knowledge and observance of the safety recommendations set out below are
essential for a correct and compliant use of the paint room.
- install the PAINT ROOM on flat concrete slab.
- ensure that the floor in the zone of the paint mixing booth is
in good condition
- do not position machinery inside the paint mixing booth which can
generate sparks or use open flames
- connect the structure of the booth to the ground line in power supply panel
- store the paint inside the PAINT ROOM using only the containers provided by the
manufacturing company, ensuring that they are always in good condition and securely
closed after use
- Ground all containers and dispensers and gun washers etc. to prevent static
combustion.
- handle the containers appropriately, to prevent them falling with the
result of uncontrolled leakage of paint and/or solvents inside the PAINT ROOM
- avoid the accumulation of dangerous substances by quickly removing the
pools of paint and/or solvents which could accidently form inside the PAINT ROOM
- do not obstruct the inlet air filter(s) in ceiling replace semi annually.
- NO SMOKING
- use adequate PPE (gloves, goggles, mask, shoes, overalls, etc.) to avoid contact
with solvents, paints or other chemicals.
err&
NOVA VERTA USA Page 7
- ensure there is a fire extinguisher close to the PAINT ROOM
��"��VERTA
1
414,0
IMPORTANT !!! The PAINT ROOM is not equipped with an internal electrical
system. If this is required the customer must use a qualified electrician to
provide Class 1 Div 1 connections for any required electrical inside the mix
room for accessory equipment.
Nova Verta USA shall not be held liable for any damage which can be
attributed to the electrical system and/or to the additional equipment
(not provided by Nova Verta) such as PC, weighing scales, gun washer
etc. which the PAINT ROOM could be equipped with.
5) DESCRIPTION OF INSTALLATION
The paint mixing room is designed to create the most suitable working environment to
perform standard paint preparation and mixing per NFPA33 requirements.
Equipped with a suitable forced air-exhaust and an air-intake filter(s), it keeps the air of
the work environment clean, without solvents, dust or other dirt.
In this way it prevents the paint being contaminated by particles of dirt during the
mixing operations, which would compromise the good result of the painting. It also
prevents the formation of accumulations of solvents, protecting the health of the worker
and the safety of the work place.
The essential parts of a PAINT ROOM are:
- basement 1" high, made from galvanized sheet-metal with 4"containment at door
opening and sealed to floor with butlyl caulking to contain any spillage. Optional base
heights are optional to match booth placement height.
- wall panels are made from 2 -20 guage precoated panels made from galvanized sheet-
metal and pre-painted white inside and blue exterior, with insulating material
interposed; the panels are nut and bolted for secure grounding and strength and then
caulked upon completion of assembly.
- roof, made from same panels of galvanized metal.
- access door measuring 31.5" width x 78.75" height with anti-panic opening and
tempered glass viewing window measuring 23.6"x 47.2"
- inlet air filter, positioned in ceiling with fire damper.
- Class 1 Div 2 ceiling lights each fitted with 4 T8 tubes or optional LED fixtures
- exhaust fan
- power panel
NOVA VERTA USA Page 8
N'MERTA
6) OPERATION
The MIX ROOM is a paint mixing room where the preparation and mixing of paint can be
correctly performed.
The running and stop controls of the exhaust fan and lights are situated near the entrance (3'
clearance from door opening), which should be positioned close to the entry of the mix room.
The power panel includes circuit protection for fan motor and lights and additional accessories
provided by others if needed.
The photo shows the three main components of the power panel of a standard PAINT ROOM.
To turn on the exhaust fan using provided switch with red on indication. This
should remain on at all times to prevent any fume accumulation inside the
room.
To switch on the ceiling lights inside the PAINT ROOM turn on white light switch.
7) USER INSTRUCTIONS
Make sure the ventilation is on before entering the MIX ROOM (Red Light Switch Illuminated) in
the meantime do not open the access door to the paint room.
Turn on the ceiling lights of the MIX ROOM before entering. From this moment on it is possible
to enter the paint room and perform normal preparation and/or paint mixing operations.
For correct operation the access door of the paint room must always be closed and is supplied with
auto door closer.
0 These instructions are of a general nature and are subordinate to any other
restrictive behavioural rules in force within the area in which the MIX
ROOM will be installed.
8) DANGER WARNINGS
The correct and compliant use of the PAINT ROOM does not cause particular risks.
NOVA VERTA USA Page 9
t'4UERTA
It is strictly forbidden to remove, tamper with, or evade safety systems, which must be
periodically checked to verify their efficiency.
UMW
It is forbidden to change the electrical parts; these operations must only be
A\ performed by a Nova Verta technician.
+sww
NOVA VERTA USA Page 10
'*VERTA
9) STARTING-UP
The ROOM is turned on from the main switch on the power panel which is provided with an ON-
OFF remotely mounted switches for exhaust fan and lights that turns on the fan and the ceiling
lights in the paint-room.
To prevent the solvents which can accumulate inside the paint room the exhaust fan is intended
to run 24/7 and is indicated on by the red provided switch.
The operations to be performed to start-up the MIX ROOM are:
1- check that the access door is closed
2- make sure fan is on
3- turn on the lights
4- check to be sure there is no strong fume smell or spillage.
Nova Verta Staff will start-up the MIX ROOM for the first time during testing.
t ifto'
NOVA VERTA USA Page 11
‘,VVERTA
NOVA VERTA USA Page 13
N..!../VERTA
NOVA VERTA USA Page 14
wVERTA
NOVA VERTA USA Page 15