Report F2c O -cxa110 OFFIE COP le Northwest Fire Suppression, Inc. RECEIVED EQUIPMENT SUBMITTAL OCT 27 202U BIDING DMSION FOR TIGARD TRIANGLE 72ND & BAYLOR APARTMENTS FIRE ALARM SYSTEM 11600 SW 72N1D Avenue Tigard, OR 97223 10/7/20 SYSTEM Fire Alarm System CONTENTS Manufacturer's Data Sheet 1800 NW 169th Place, Suite C600 • Beaverton, Oregon 97006 • 503-644-7720 • Fax 503-644-8289 www.nwfire.com CCB#88629 Licensed • Bonded • Insured Northwest Fire Suppression,. ( r Inc.. - '__7 EQUIPMENT LIST Model Number Description 1 NFW-100X Addressable Fire Alarm Control Panel 2 HWF2V-COM LTE/IP Single or Dual Path Commercial Communicator 3 N-ANN-80 Fire Alarm Annunciator NFC-50/100 Voice Evac Control Panel NFC-BDA-70V Backup Amplifier for Voice Control Panel 4 NFC-CE6 Speaker Circuit Expansion Card NFC-RM Remote Microphone NFC-50/100DA Distributed Amplifier 5 NFC-BDA-BU Backup Amplifier for Distributed Amplifier 6 PSN-106 10A, 6 Circuit Notification Power Supply w/Sync 7 ISO-X Isolator Module FMM-1 Addressable Monitor Module 8 FDM-1 Addressable Dual Monitor Module FCM-1 Addressable Control Module 9 FRM-1 Addressable Relay Module 10 NBG-12LX Addressable Manual Pull Station • 1800 NW 169th Place, Suite C600 • Beaverton, Oregon 97006 • 503-644-7720 • Fax 503-644-8289 www.nwfire.com CCB# 88629 Licensed • Bonded • Insured Northwest Fire Suppression, Inc. FSP-951 Addressable Photoelectric Smoke Detector 11 FSP-951R Addressable Duct Smoke Detector • B300-6 Low Profile, 6" Dia. Detector Base 12 FST-951 Addressable 135 Deg. Heat Detector DNR Duct Detector Housing 13 DNRW Duct Detector Housing, Outdoor DST-?? Duct Detector Sampling Tube(Field Verify Length) 14 R-20E DPDT, Multi-Voltage AUX Relay w/Enclosure 15 SWL Multi-CD Strobe, Wall, White 16 SCWL Multi-CD Strobe, Ceiling, White 17 SPSWL Multi-CD Speaker/Strobe,Wall, White SPSCWL Multi-CD Speaker/Strobe, Ceiling, White 18 SPCWL Multi-CD Speaker, Ceiling, White SPSWK Multi-CD Speaker/Strobe, Wall, White, Outdoor 19 SPSCWHK 135CD-185CD Speaker/Strobe, Ceiling, White, Outdoor 1800 NW 169th Place, Suite C600 • Beaverton, Oregon 97006 • 503-644-7720 • Fax 503-644-8289 www.nwfire.com CCB#88629 Licensed • Bonded • Insured ® NOTIFIERA by Honeywell NFW-100X Intelligent Addressable FACP with Communicator ' General The FireWarden-100X(NFW-100X) is the latest intelligent address- able Fire Alarm Control Panel(FACP)within the FireWarden Series and is a direct replacement for the FireWarden-100(NFW-100).The NFW-100X comes with a pre-installed communicator and supports up to 198 addressable devices(99 detectors and 99 modules).With nFw ioox an extensive list of powerful features, the NFW-100X programs just like FireWarden-100 products, yet fits into applications previously 1 , served only by conventional panels. The pre-installed IPOTS-COM is a dual technology (POTS and IP) communicator.The POTS transmits system status(alarms,troubles, J-t:.}J AC loss,etc.)to a Central Station via the public switched telephone 1� network.The IP communicator's internet monitoring capability sends alarm signals over the Internet saving the monthly cost of two dedi- catedm�.o.,.,• business telephone lines.Although not required, the second- ary telephone line may be retained providing backup communication over the public switched telephone line.Optional cellular reporting is available using the CELL-MOD or CELL-CAB-N. Remote and local programming of the control panel is possible using the FS-Tools Upload/Download utility. Programming databases can be uploaded/downloaded via the panel's USB port(and USB cable) or via an ethernet connection using the IPOTS-COM communicator. The USB port also allows for the download or upload of the entire program, history file,walk-test data, current status and system volt- ages by means of a USB flash drive. • Maintenance alert warns when smoke detector dust accumula- ' The power supply and all electronics are contained on a circuit tion is excessive board supported on a new quick install chassis and housed in a • One-person audible or silent walk test with walk-test log and metal cabinet. Available accessories include local and remote printout upload/download software, remote annunciators,and reverse polar- • System alarm verification selection per detector point ity/city box transmitter(4XTM). • PAS (Positive Alarm Sequence) and Pre-signal per point (NFPA Features 72 compliant) • Up to 16 ANN-BUS annunciators-8 per each ANN-Bus • Listed to UL Standard 864, 10th edition • Remote Acknowledge, Alarm Silence, Reset and Drill via • Pre-installed IPOTS-COM Ethernet IP and POTS(Plain Old Tele- addressable modules or remote annunciator phone Service)Central Station Communicator over AlarmNet • Upload/Download of program and data via USB with optional FS- • Optional CELL-MOD or CELL-CAB-N GSM Central Station Corn- Tools Programming Utility municator over AlarmNet® • Automated activation of the NFC-50/100 Emergency Command SLC COMMUNICATION LOOP Center • Supports FlashScan®and CLIP protocols • NFC-FFT Firefighter Telephone option • SLC operates up to 10,000 ft.(3,000 m)in FlashScan mode with • Compatible with SWIFT®wireless devices twisted,unshielded wire • Auto-programming (learn mode) reduces installation time. • Single addressable SLC loop which meets NFPA Class B and Reports two devices set to the same address Class A requirements • Four built-in, independently programmable Style Z (Class A) or Style Y(Class B)NAC circuits • 198 addressable device capacity(99 addressable detectors and • Selectable strobe synchronization for System Sensor, Wheelock, 99 modules) and Centex devices • Compatible with NOTIFIER FireWarden and ONYX Series • Notification Appliance Circuit End of Line resistor matching addressable devices (refer to the FireWarden SLC Wiring Man- • Four programmable function keys for ease of maintenance ual) • Two programmable relays and one fixed trouble relay NOTIFICATION APPLIANCE CIRCUITS(NACS) • Built-in Programmer • Integral 80-character LCD display with backlighting • Four independently programmable output circuits.Circuits can be • Real-time clock/calendar with automatic daylight savings control configured for the following outputs: • History file with 1,000 event capacity —Style Y(Class B) • Addressable sounder base compatibility —Style Z(Class A) • Control module delay timer • Silence Inhibit and Autosilence timer options • Automatic detector sensitivity testing(NFPA 72 compliant) • Continuous, March Time, Temporal, or California code for main • Automatic device type code verification circuit board NACs with two-stage capability • Point trouble identification • Waterflow selection per module point • Selectable strobe synchronization per NAC • Alarm verification selection per detector point • 2.5 A special application,250mA regulated,total power for NACs • NOTE:Maximum or total 24VDC system power shared between all NAC circuits and the ANN-BUS is 2.7 A DN-60959:C•7/16/2018—Page 1 of 4 PROGRAMMING AND SOFTWARE vised output for local energy municipal box transmitter, alarm and • Autoprogramming(learn mode)reduces installation time trouble. Includes a disable switch and disable trouble LED. • Custom English labels (per point) may be manually entered or PWRMOD24 Power Expander Module: Optional power module. selected from an internal library file Increases alarm power output to 6 amps. • Two programmable Form-C relay outputs COMPATIBLE ANNUNCIATORS • 99 software zones N-ANN-80: Remote LCD annunciator mimics the information dis- • Continuous fire protection during online programming played on the FACP LCD display. Recommended wire type is un- • Program Check automatically catches common errors not linked shielded.(Basic model is black;order-W for white; see DN-7114.) to any zone or input point N-ANN-100R: Remote LCD annunciator mimics the information dis- • OFFLINE PROGRAMMING: Create the entire program in your played on the FACP LCD display. Recommended wire type is un- _ office using FS-Tools,a Windows®-based software package,and shielded. For use in FM applications only. (Basic model is black; upload/download system programming locally. Offline program- order R for red.) ming requires an ethernet connection. FS-Tools is available on N-ANN-IlO: LED Driver Module provides connections to a user sup- www.notifier.com. plied graphic annunciator.(See DN-7105.) N-ANN-LED: Annunciator Module provides three LEDs for each 1 User interface zone: Alarm, Trouble, and Supervisory. Ships with red enclosure. LED INDICATORS (See DN-60242.) N-ANN-RLED: Provides alarm (red) indicators for up to 30 input • Fire Alarm(red) • CO Alarm(red) zones or addressable points. (See DN-60242.) • AC Power(green) • Supervisory(yellow) N-ANN-RLY: Relay Module provides 10 programmable Form-C • Trouble(yellow) • Ground fault(yellow) relays.Can be mounted inside the cabinet.(See DN-7107.) • Battery fault(yellow) • Disabled (yellow) N-ANNS/PG: Serial/Parallel Printer Gateway module provides a • Maintenance(yellow) Communication(yellow) connection for a serial or parallel printer.(See DN-7103.) • Alarm Silenced(yellow) • F1-F4 Programmable Function ADDRESSABLE DEVICES Keys(yellow) FSP-951: Addressable low-profile photoelectric smoke detector. FlashScan only. KEYPAD FSP-951-IV:Addressable low-profile photoelectric smoke detector. • 16 key alpha-numeric pad • Acknowledge Ivory. FlashScan and CLIP mode. • Alarm Silence • Drill(Manual Evacuate) NP-200: Addressable low-profile photoelectric smoke detector. • Four(4)programmable function keys • Reset(lamp test) B300-6 base included, FlashScan only. NP-200-IV: Addressable low-profile photoelectric smoke detector. PRODUCT LINE INFORMATION Ivory,B300-6-IV base included.FlashScan and CLIP mode. NFW-100X: Addressable Fire Alarm Control Panel with one SLC FSP-951T: Addressable low-profile photoelectric smoke detector • loop. Includes main circuit board with display chassis with trans- with thermal sensor.FlashScan only. former, backbox with door, plastic bag containing screws, cables, FSP-951T-IV:Addressable low-profile photoelectric smoke detector key,etc. with thermal sensor. Ivory. FlashScan and CLIP mode. FS-Tools: Programming software for Windows®-based PC com- NP-200T:Addressable low-profile photoelectric smoke detector with outer.Available for download at www.notifier.com. thermal sensor.B300-6 base included.FlashScan only. CELL CAB-N/CELL-MOD:Optional GSM communicators. NP-200T-IV: Addressable low-profile photoelectric smoke detector IPOTS-COM: Dual technology (POTS and IP) communicator. with thermal sensor. Ivory, B300-6-IV base included. FlashScan and (replacement board) CLIP mode. DP-ES-R:Optional dress panel for the NFW-100X(red). FSP-951R: Remote test capable addressable photoelectric smoke DP-ES-B:Optional dress panel for NFW-100X(black). detector for use with DNR(W) duct detector housing. FlashScan TR-CE-B: Optional trim ring for semi-flush mounting. (Black. For only. red,order TR-CE.) FSP-951R-IV: Remote test capable addressable photoelectric BB-XP:Optional cabinet for one or two modules. smoke detector for use with DNR(W) duct detector housing. Ivory. BB-25: Optional cabinet for up to six modules mounted on CHS-6 FlashScan and CLIP mode. chassis. NP-200R: Remote test capable addressable photoelectric smoke BB-26: Battery backbox, holds up to two 25 AH batteries and CHG- detector for use with DNR(W) duct detector housing. FlashScan 75. only. NFS-LBB:Battery box,houses two 55 AH batteries NP-200R-IV: Remote test capable addressable photoelectric smoke CHS-6:Chassis,mounts up to six multi-modules in a BB-25 cabinet. detector for use with DNR(W)duct detector housing. Ivory, FlashS- CHG-75: Battery charger for lead-acid batteries with a rating of 25 to can and CLIP mode. 75 AH. FST-951: Low-profile 135°F fixed thermal sensor.FlashScan only. CHG-120: Remote battery charging system for lead-acid batteries FST-951-IV: Low-profile 135°F fixed thermal sensor. Ivory. FlashS- with a rating of 55 to 120 AH. Requires additional NFS-LBB for can and CLIP mode. mounting. NH-200: Low-profile 135°F fixed thermal sensor. B300-6 base NOTE:CHG-120 or CHG-75 required for batteries larger than IBAH. included, FlashScan only. - BAT Series: Batteries,see data sheet DN-6933. NH-200-IV: Low-profile 135°F fixed thermal sensor.Ivory.B300-6-IV PRN Series: UL listed compatible event printer. Uses tractor-fed base included, FlashScan and CLIP mode. paper. FST-951R: Low-profile, intelligent, rate-of-rise thermal sensor. • OPTIONAL MODULES FlashScan only. FST-951R-IV: Low-profile, intelligent, rate-of-rise thermal sensor. 4XTM Reverse Polarity Transmitter Module: Provides a super- Ivory. FlashScan and CLIP mode. Page 2 of 4—DN-60959:C•7/16/2018 - NH-200R: Low-profile 135°F fixed thermal sensor. B300-6 base zone of conventional two-wire detectors. Requires resettable 24 included, FlashScan only. VDC power. Refer to the Device Compatibility Document for listed NH-200R-IV: Low-profile 135°F fixed thermal sensor. Ivory. B300-6- compatible devices and quantity limitation. IV base included, FlashScan and CLIP mode. NZM-100:Similar to NMM-100.Addressable Monitor Module for one FST-951H: Low-profile intelligent 190°F/88°C fixed thermal sensor. zone of conventional two-wire detectors. Requires resettable 24 FlashScan only. VDC power. Refer to the Device Compatibility Document for listed FST-951 H-IV: Low-profile intelligent 190°F/88°C fixed thermal sen- compatible devices and quantity limitation. sor.Ivory. FlashScan and CLIP mode. FCM-1:Addressable Control Module for one Style Y/Z (Class B/A) NH-200H: Low-profile intelligent 190°F/88°C fixed thermal sensor. zone of supervised polarized Notification Appliances. Mounts B300-6 base included, FlashScan only. directly to a 4.0" (10.16 cm.) electrical box. NAC option requires external 24 VDC to power notification appliances. NH-200H-IV: Low-profile intelligent 190°F/88°C fixed thermal sen- NC-100:Addressable Control Module for one Style Y/Z(Class B/A) sor.Ivory.6300-6-IV base included, FlashScan and CLIP mode. zone of supervised polarized Notification Appliances. Mounts Legacy Devices directly to a 4.0" (10.16 cm.) electrical box. NAC option requires FSI-851:Addressable low-profile ionization smoke detector, external 24 VDC to power notification appliances. NI-100:Addressable low-profile ionization smoke detector. FRM-1: Addressable relay module containing two isolated sets of FSP-851:Addressable low-profile photoelectric smoke detector. Form-C contacts,which operate as a DPDT switch. Mounts directly NP-100:Addressable low-profile photoelectric smoke detector. to a 4.0"(10.16 cm.)box,surface mount using the SMB500. FSP 851T: Addressable low-profile photoelectric smoke detector NC-100R:Addressable relay module containing two isolated sets of with thermal sensor. Form-C contacts,which operate as a DPDT switch. Mounts directly to a 4.0"(10.16 cm.)box,surface mount using the SMB500. NP-100T:Addressable low-profile photoelectric smoke detector with NBG-12LX: Addressable manual pull station with interface module thermal sensor. mounted inside. FSP-851R: Remote test capable addressable photoelectric smoke NOT-BG12LX:Addressable manual pull station with interface mod- detector for use with DNR(W)duct detector housing. ule mounted inside. NP-100R: Remote test capable addressable photoelectric smoke ISO-X: Fault Isolator Module. detector for use with DNR(W)duct detector housing. FST-851: Fast-response,low-profile heat detector. N700•ISO: Fault Isolator Module. NH-100: Fast-response, low-profile heat detector. ISO-6:Six-fault isolator module.Mount one or two modules in a BB- XP cabinet(optional). Mount up to six modules on a CHS-6 chassis FST-851 R: Fast-response, low-profile heat detector with rate-of-rise in a CAB-3/CAB-4 series cabinet. option. SMB500: Used to mount all modules except the FMM-101/NMM- • NH-100R: Fast-response, low-profile heat detector with rate-of-rise 100P. option. NMM-100-10:Ten-input monitor module.Mount one or two modules FST-851 H: Fast-response, low-profile heat detector that activates at in a BB-2F cabinet(optional). Mount up to six modules on a CHS-6 • 190°F/88°C. chassis in a BB-6F cabinet. NH-100H: Fast-response, low-profile heat detector that activates at NZM-100-6: Six-zone interface module. Mount one or two modules 190°F/88°C. in a BB-XP cabinet(optional). Mount up to six modules on a CHS-6 FAPT-851:Addressable low-profile multi-sensor detector. chassis in a CAB-3/CAB-4 series cabinet. NP-A100:Addressable low-profile multi-sensor detector. SWIFT Wireless Devices B200S: Programmable,addressable sounder base. FWSG:Wireless Gateway B200SR:Addressable sounder base. FWD-200P: intelligent,wireless photo detector. DNR: InnovairFlex low-flow non-relay duct-detector housing. (Order FWH-200R0R135: LiteSpeed intelligent wireless rate of rise (135°) FSP-851 R, FSP-951 R, or NP-100R separately.) heat detector. DNRW: InnovairFlex low-flow non-relay duct-detector housing, with FWD-200ACCLIMATE:Wireless Acclimate Detector NEMA-4 rating. Watertight. (Order FSP-851R, FSP-951R, or FWH-200FIX135: intelligent wireless fixed-temperature (135°) heat NP-100R separately.) detector. Addressable Modules FW-MM: Intelligent wireless monitor module. FMM-1:Addressable Monitor Module for one zone of normally-open FW-RM: Intelligent wireless relay module. dry-contact initiating devices. Mounts in standard 4.0" (10.16 cm.) NBG-12LW: Intelligent wireless pull station. box. Includes plastic cover plate and end-of-line resistor. Module WAV-RL,WAV-WL,WAV-CRL,WAV-CWL: Intelligent AV bases. may be configured for either a Style B(Class B)or Style D(Class A) W-USB: Wireless USB radio/antenna dongle that plugs into the IDC. USB port of a PC running SWIFT Tools. NMM-100:Addressable Monitor Module for one zone of normally- SWIFT Tools: Programming and diagnostic utility for the Wireless open dry-contact initiating devices. Mounts in standard 4.0" (10.16 Gateway and devices.Available for download from firelite.com. cm.) box. Includes plastic cover plate and end-of-line resistor. Mod- NOTE: For more information on Compatible Addressable Devices for ule may be configured for either a Style B(Class B)or Style D(Class use with the Fire Warden-100X,see the following data sheets(document A)IDC. numbers): NP-200 Series (DN-60979), NH-200 Series (DN-60980), FDM-1: Dual Monitor Module.Same as NMM-100 except it provides FSP-851 Series (DN-6935), FSP-951 Series (DN-60977), FST-851 two Style B(Class B)only IDCs. Series (DN-6936), FST-951 Series (DN-60975), FAPT-851 (DN-6937), NDM-100: Dual Monitor Module. Same as NMM-100 except it pro- N100-ISO(DN-6994),NP-100 series(DN-6995),NH-100/NH-100R(DN- vides two Style B(Class B)only IDCs. 6997), DNR/InnovairFlex(DN-60424, DN-60429), NP-A100 (0N-6998), NMM-100/NMM-100P/NDM-100/NZM-100 (DN-6999), NC-100 (ON- FMM-101: Miniature version of NMM-100. Excludes LED and Style 7000), NC-100R (DN-60383), NMM-100-10 (DN-6990), MM-1/FDM-1/ • D option.Connects with wire pigtails. May mount in device backbox. FZM-1/FMM-101 (DN-6720), FCM-1/FRM-1 (DN-6724), NOT-BG12LX NMM-100P: Miniature version of NMM-100. Excludes LED and Style (DN-7001), NBG-12LX (DN-6726), and FireWarden SLC Manual D option.Connects with wire pigtails. May mount in device backbox. (52304). • FZM-1: Similar to NMM-100.Addressable Monitor Module for one DN-60959:C•7/16/2018—Page 3 of 4 SPECIFICATIONS System Capacity Addressable Device Accessories • Intelligent Signaling Line Circuits 1 End-of-Line Resistor Assembly (R-47K and R-3.9K): The • Addressable device capacity 198 47k ohm assembly supervises the NMM-100-10, NDM-100, NMM- • Programmable software zones 99 100P, and NC-100 module circuits. The 3.9k ohm assembly super- vises the NZM-100-6 module circuit. These resistors are included • Annunciators 16 with each module. Power Supervision Relay: Supervises the power to 4-wire smoke Electrical Specifications detectors and notification appliances. AC Power: Operates in either 120 or 240 VAC, 50/60 Hz, 3.25 A, Wiring Requirements auto-sensing- no switch required. Wire size: minimum 14 AWG (2.00 mm2) with 600 V insulation. Nonpower-limited, supervised. While shielded wire is not required, it is recommended that all SLC Battery: Two 12 V 18 AH lead-acid batteries. Battery Charger wiring be twisted-pair to minimize the effects of electrical interfer- Capacity: 7-18 AH (FireWarden-100X cabinet holds maximum of ence.Refer to the panel manual for wiring details. two 18 AH batteries.) NFPA Standards Communication Loop: Supervised and power-limited. The FireWarden-100X complies with the following NFPA 72 Fire Notification Appliance Circuits: Terminal Block provides connec- Alarm Systems requirements: tions for four NACs, Style Y(Class B)or Style Z(Class A). Special —LOCAL (Automatic, Manual, Waterflow and Sprinkler Supervi- Application power. Power-limited, supervised circuitry. Maximum signaling current per circuit: 2.5 amps special application, 250mA SOry)' regulated. End-of-Line Resistor: 4.7k ohm, 1,4 watt (P/N 71252 UL —AUXILIARY (Automatic, Manual and Waterfiow) (requires listed)for Style Y(Class B)NAC;system capable of 1.9 IQ-22 K2 4XTM). ELR range. Refer to the NOTIFIER Device Compatibility Document -REMOTE STATION (Automatic, Manual and Waterflow) for listed compatible devices. (Where a DACT is not accepted,the alarm,trouble and supervi- Two Programmable Relays and One Fixed Trouble Relay: Con- sory relays may be connected to UL 864 listed transmitters.For tact rating: 2.0 A @ 30 VDC (resistive), 0.5 A @ 30 VAC(resistive). reverse polarity signaling of alarm and trouble, 4XTM is Form-C relays,non-power-limited, non-supervised. required.) —PROPRIETARY(Automatic,Manual and Waterfiow). • Cabinet Specifications -CENTRAL STATION (Automatic, Manual and Waterflow, and . Door: 19.26" (48.92 cm.) high x 16.82" (42.73 cm.) wide x 0.72" Sprinkler Supervised). (1.82 cm.)deep. Backbox: 19.00"(48.26 cm.)high x 16.65"(42.29 —OT, PSDN (Other Technologies, Packet-switched Data Net- - cm.)wide x 5.25" (13.34 cm.)deep. Trim Ring (TR-CE/B): 22.00" work) (55.88 cm.)high x 19.65"(49.91 cm.)wide. —IBC 2012,IBC 2009,IBC 2006,IBC 2003,IBC 2000(Seismic). —CBC 2007(Seismic) Shipping Specifications Weight: 26.9 lbs. (12.20 kg.)Dimensions: 20.00"(50.80 cm.)high Agency Listings and Approvals x 22.5"(57.15 cm.)wide x 8.5"(21.59 cm.)deep. The listings and approvals below apply to the basic FireWarden- 100X control panel. In some cases, certain modules may not be Temperature and Humidity Ranges listed by certain approval agencies, or listing may be in process. This system meets NFPA requirements for operation at 0—49°C/32 Consult factory for latest listing status. —120°F and at a relative humidity 93%±2% RH(noncondensing)at • UL: S635 32°C ± 2°C (90°F ± 3°F). However, the useful life of the system's • CSFM:7165-0028:0505 standby batteries and the electronic components may be adversely • FDNY:COA#6268 affected by extreme temperature ranges and humidity.Therefore, it is recommended that this system and its peripherals be installed in an environment with a normal room temperature of 15—27°C/60— 80°F. IS® etgamms I rpersnrls QUAb1Th SYSTEMS This document is not intended to be used for installation purposes. We try to keep our product information up-to-date and accurate. We cannot cover all specific applications or anticipate all requirements. NI specifications are cabled to change without notice. NOTIFIER AamiNet®,NOTIFIER®,FireWarden®,SWIFT®,and System Sens® are registered trademarks of Honeywell Intemaflaal inc Microsoft®and 12 Clintonville Road Windows®are registered trademarks of the Microsoft Corporation. Northford,CT 06472 C2018 by Honeywell International Inc.All rights reserved.Unauthorized NOT 1 F 1 ER 203.484.7161 use of Sits document is slncUy prohibited. www.notifier.com Country of Origin:USA by Honeywell - HWF2J,OM SERIES LTE / IP Single or Dual Path Commercial Fire Communicators The HWF2-COM Series LTE / IP fire communicators are single or dual path commercial fire alarm communicators that offer Contact ID reporting with any FACP (fire HWF2A-COM alarm control panel) with a built-in dialer. • Models include: HWF2A-COM(AT&T LTE&IP) HWF2V-COM(Verizon LTE&IP) Both models connect directly to the primary or secondary communication ports of a fire panel's digital alarm communicator transmitter COACT). • Three selectable reporting paths include:LTE cellular only,IP only,or IP primary with LTE cellular backup.AU signals from the HWF2-COM Series are delivered to the AlarmNet° network control center which routes highly encrypted,cybersecured Ethernet data packets via a customer-provided Internet connection or LTE cellular network to the appropriate • central station.The AlarmNet°network control center is fully redundant and monitored 24/7.Installation and programming are easy using the handheld 7720P Programming tool. HWF2V-COM FEATURES AND BENEFITS • LTE and IP connection tested every clay connection(LAN or WAN),DSL model or • Diagnostic LEDs indicate signal strength • Three selectable reporting paths:LTE cable modem and status cellular only,IP only,or IP Primary with LTE • Data transmits over standard Contact ID • cellular backup protocol but is secured with the industry's Choice of LTE provider services • QOS:Quality of Service diagnostics via • Requires no change to the existing FACP advanced encryption standard(AES 256 AlarmNet conveys vital communicator configuration bit) information including signal strength, • Connects directly to the primary and • Supports both dynamic(DHCP)or public message path used,and when the message secondary telephone ports of a DACT and private Static IP addressing was received • Plan choices range from 5 minute,60 • Reliable connection:IP and cellular • 7720P Handheld programmer for easy minute,6 hour,and 24 hour supervision connection tested every day setup intervals • Built-in,standalone power supply module. • Operates over the following communication Onboard charging circuit design protocols:LTE,HSPA+(4G)HSPA(3G) accommodates battery backup.Includes • • Works over any type of customer provided primary power and battery supervision Ethernet 10/100 based network Honeywell The HWF2-COM LIE/IP fire communicators operate over the most • Primary Subscriber ID(four digits),obtained from your monitoring modern and common cellular networks including LTE,4G and3G. station • Communication Module MAC ID,and MAC CRC number located on - They connect to any customer provided Ethernet 10/100 base the outside of the box and inside of the module network connection(LAN or WAN),DSL or cable modem.Selectable All parameters are assigned by the monitoring station. reporting path feature allows the radios to be configured for a single pr dual path,while providing appropriate supervision intervals ALARMNET based on NFPA 72 requirements.Selectable paths and supervision AlarmNet communications technology provides a highly reliable timing intervals include: alternative for the transmission of alarm signals.The network Ft.4i,, provides extensive coverage in the United States and Canada.The Alarm Net Network Control Center processes signals from powerful servers in multiple locations equipped with 24/7 infrastructure 2010 Cell .Single path,cellular 5 Minutes support.Redundant hardware servers,real-time backup databases, 2010 IP Single path,IP 5 Minutes and generators with battery backup at all locations ensure 2010 IP&Cell Dual path,IP and cellular 24 Hours continuity of service.Signals from AlarmNet are transmitted to 2013 Cell Single path,cellular 60 Minutes central station receivers using multiple communication paths consisting of the Internet,LTE radio network,or toll free plain old 2013 IP Single path,IP 60 Minutes telephone service(POTS).Visit AlarmNet.com to learn more. 2013 IP&Cell Dual path,IP and cellular 6 Hours INSTALLATION REQUIREMENTS,UL COMPLIANCE OPERATION To meet UL864/NFPA requirements,ensure the following: When an event occurs,the FACP goes off-hook to dial the central station.The HWF2-COM Series dialer capture module detects the • HWF2-COM Series must be installed in accordance with the National . off-hook condition and provides the fire panelwith a dialtone.When Fire Protection Association(NFPA)standards 70 and 72 the fire panel detects the dial tone,it begins dialing the central • HWF2-COM Series must be mounted in the same room and within • station. 20 feet of the fire panel. • HWF2-COM Series and all equipment used for the IP connection After the dialing is completed,the dialer capture module returns a (e.g.,router,hub,modem,etc)must be UL-listed,powered from an signal to the fire panel.The fire panel then sends the Contact ID unswitched branch circuit,and be provided with appropriate standby reports to the dialer capture module,which in turn sends a signal power. after the report is successfully received from the fire panel.The • HWF2-COM Series must use the 7AH battery(not included)to dialer capture nodule sends the Contact ID reports to the HWF2- provide 24 hour backup capability COM Series communications module.When allthe reports are sent, the fire panel goes on-hook.The HWF2-COM Series communications module then transmits the messages to the central station either over the LTE network or the Internet (depending on configuration). FIRE COMMUNICATOR/PANEL CAPABILITY The HWF2-COM Series is compatible with fire alarm control panels that use the Contact ID communications format as described in the SIA DC-05 standard. EASY TO PROGRAM The HWF2-COM communicator can be pre-programmed using the 7720P programmer to enter all central station information.This is saved to the HWF2-COM communicator panel memory.When the HWF2-COM is installed at the site and connected to the Internet/ Intranet,it registers with the AlarmNet Receiver. For most installations,the only required parameters are: • Primary City ID(two digits),obtained from your monitoring station • Primary Central Station ID(two digits),obtained from your • monitoring station Page 2 of 3—DH-62010:C•6/10/2020 HWF2-Cak SERIES TECHNICAL SPECIFICATIONS ELECTRICAL Both models include: Transformer: • Red cabinet with key and lock AlarmNet"is a registered trademark • Primary:120VAC,60Hz,0.5A • Wall outlet box of Honeywell International Inc. • Secondary:18VDC,50VA • Dialer capture module ©2019 by Honeywell International Battery: • LTE communications module Inc.All rights reserved. • One 12 V 7.0 AH lead-acid battery:(not • Antenna and mounting adapter Unauthorized use of this document supplied) • PowerBoostl power supply is strictly prohibited. • •• Battery charging current:1 Amp maximum LED display board • Battery discharge current:Standby 210mA, • Transformer This document is not intended to be Active 290mA • Manual and required screws used for installation purposes.We • Cables,etc. try to keep our product information CABINET SPECIFICATIONS up-to-date and accurate.We cannot • Dimensions:14.875"H x 12.75"W x 3.0"D ANTENNA AND EXTERNAL cover all specific applications or HARDWARE anticipate all requirements.All (37.8cm H x 32.4cm W x 7.6cm D) • Color:Red CELL-ANT3DB:3dBA gain antenna specifications are subject to change WA7626-CA:SMA to N adapter cable without notice. SHIPPING DIMENSIONS 7626-50HC:50 ft.antenna cable,low loss Country of origin:USA • Weight:5.3 lbs(6.94kg) Note:The WA7626-CA adapter cable and • Dimensions:15.625°H x 13.79"Wx 9.25'D (39.7cm H x 34.9cm W x 23.9cm D) 7626-50HC antenna cable are only required when installing the CELL-ANT3DB TEMPERATURE AND HUMIDITY antenna remotely. . RANGES OTHER ACCESSORIES This system meets NFPA requirements for operation at 0-49°C/32-120°F and at a 7720P:HWF2V-COM,HWF2A-COM and ' relative humidity 930/0+-20/0 RH(non- IPGSM-4G handheld programmer - condensing at 32°C+-2°C(90°F+-3°F). HPTCOVER:Plug-in transformer box for However the useful life of the system's HWF2V-COM,HWF2A-COM,and IPGSM- standby batteries and the electronic 4G communicators components may be adversely affected by BAT-1270: Battery 12 Volts,7AH,sealed extreme temperature ranges and humidity. AGENCY LISTINGS AND Therefore,it is recommended that this APPROVALS system and its peripherals be installed in an environment with a normal room The listings and approvals below apply to temperature of 15-27°C/60-80°F. the HWF2-COM Series communicators.In some cases,certain modules may not be PRODUCT LINE INFORMATION listed by certain approvalagencies,or listing HWF2V-COM:LTE Digital Cellular Fire may be in process.Consult the factory for Alarm Communicator and Internet Panel, latest listings. Verizon LTE/IP UL Listed:S789 HWF2A-COM:LTE Digital Cellular Fire CSFM:7300-1645:0511 Alarm Communicator and Internet Panel, FD NY:Approved AT&T LTE/IP THE FUTURE IS 'Honeywell Power Products WHAT 12 Clintonville Road WE MAKE IT Northford,CT 06472-1610• 203.484,7161 DH-62010 I C 106/20 www.honeywettpower.com ©2020 Honeywell International Inc. Honeywell NOTIFIER by Honeywell N-ANN-80 80-Character Serial LCD Annunciator - General �.. The N-ANN-80 annunciator is a compact, backlit, 80-character LCD g fire annunciator that mimics the Fire Alarm Control Panel (FACP) display. It provides system status indicators for AC Power, Alarm, Trouble, Supervisory, and Alarm Silenced conditions. The N-ANN- 80 and the FACP communicate over a two-wire serial interface I A r employing the ANN-Bus communication format. Connected devices are powered, via two additional wires, by either the host FACP or a remote UL-listed, filtered power supply. The N-ANN-80 is black; for — -- white order N-ANN-80-W. a • The N-ANN-80 displays English-language text of system point infor- mation including device type,zone, independent point alarm,trouble QNOTIFIER' or supervisory status, as well as any custom alpha labels pro- y°' I q'a°^eroeii grammed into the control panel. It includes control switches for remote control of critical system functions. (A keyswitch prevents l m� unauthorized operation of the control switches.) Up to eight N-ANN-80s may be connected to the ANN-Bus of each FACP. Minimal programming is required, which saves time during system commissioning. The N-ANN-80 is compatible with NOTI- FIER FACPs with an ANN-Bus,such as the NFW-50X. - Features • Trouble • Listed to UL Standard 864, 9th Edition • Supervisory • Backlit 80-character LCD display(20 characters x 4 lines) • Alarm Silenced • Mimics all display information from the host panel • Control switches for System Acknowledge, Signal Silence, Drill, Specifications and Reset • Operating voltage range: 18 VDC to 28 VDC • Control switches can be independently enabled or disabled at the • Current consumption @ 24 VDC nominal (filtered and non- FACP resettable):40 mA maximum • Keyswitch enables/disables control switches and mechanically • Ambient temperature:32°F to 120°F(0°C to 49°C) locks annunciator enclosure • Relative humidity: 93% ± 2% RH (non-condensing) at 32°C ± • Keyswitch can be enabled or disabled at the FACP 2°C(90°F±3°F) • Enclosure supervised for tamper • 5.375" (13.65 cm.) high x 6.875"(17.46 cm.)wide x 1.375" (3.49 • System status LEDs for AC Power,Alarm, Trouble, Supervisory, cm.)deep and Alarm Silence • For use indoors in a dry location • Local sounder can be enabled or disabled at the FACP • All connections are power-limited and supervised • N-ANN-80 connects to the ANN-Bus terminal on the FACP and requires minimal panel programming The ANN-Bus • Displays device type identifiers, individual point alarm, trouble, supervisory,zone, and custom alpha labels POWERING THE DEVICES ON THE ANN-BUS FROMAUXIL- • Time-and date display field !ARV POWER SUPPLY • Surface mount directly to wall or to single, double, or 4" square The ANN-Bus can be powered by an auxiliary power supply when electrical box the maximum number of ANN-Bus devices exceeds the ANN-Bus • Semi-flush mount to single, double, or 4" square electrical box. power requirements.See the FACP manual for more information. Use ANN-SB8OKIT for angled view mounting ANN-BUS DEVICE ADDRESSING • Can be remotely located up to 6,000 feet (1,800 m) from the Each ANN-Bus device requires a unique address (ID Number) in panel order to communicate with the FACP.A maximum of 8 devices can • Backlight turns off during AC loss to conserve battery power but be connected to the FACP ANN-Bus communication circuit. See the will turn back on if an alarm condition occurs FACP manual for more information. • May be powered by 24 VDC from the host FACP or by remote WIRE REQUIREMENTS: COMMUNICATIONS CIRCUIT power supply(requires 24 VDC) • Up to eight N-ANN-80s can be connected on the ANN-Bus The N-ANN 80 connects to the FACP ANN-Bus communications cir- cuit.To determine the type of wire and the maximum wiring distance • Controls and Indicators that can be used with FACP ANN-Bus accessory modules, it is nec- essary to calculate the total worst case current draw for all modules • AC Power on a single 4-conductor bus. The total worst case current draw is • Alarm calculated by adding the individual worst case currents for each module. DN-7114:D•3/15/2018—Page 1 of 2 NOTE:For total worst case current draw on a single ANN-Bus refer to Agency Listings and Approvals appropriate FACP manual. The listings and approvals below apply to the N-ANN-80. In some WIRE REQUIREMENTS:POWER CIRCUIT cases, certain modules may not be listed by certain approval agen- • 14 to 18 AWG (0.75-2.08 mm2)wire for 24 VDC power circuit is cies, or listing may be in process. Consult factory for latest listing acceptable. status. • All connections are power-limited and supervised. • Ill:S635 • A maximum of eight N-ANN-80 modules may be connected to • FM approved this circuit. • CSFM: 7120-0028:0240 • MEA:442-06-E Vol.2 Ordering Options: N-ANN-80:Black 80 character LCD Annunciator. N-ANN-80-W:White,80 character LCD Annunciator. ANN-SB8OKIT-B:Black surface mount backbox with angled wedge. ANN-SB8OKIT-W: White surface mount backbox with angled wedge. • IS® MIMING E N&W I= QUALITY SYSTEMS This document is not intended to be used for installation purposes. We by to keep our product informationup-to-date and accurate. We cannot cover all specific applications or anticipate all requirements. • NOTIFIER All specifications are subject to change without notice. 12 Clintonville Road NOTIFIER® a registered trademark at l-teoemIl International Inc. Northford,CT 06472 e2018 by Honeywell International inc.AU rights reserved.Unauthorized N OT I F I E R - 203.484.7161 use of this document is suictiy prohibited. www.rwtlfier.com Country of Origin:USA by Honeywell NOTIFIER by Honeywell NFC-50/100(E) First Command Emergency Communication System -General µ<; Notifier's First Command NFC-50/100 and NFC-50/100E are multi- purpose emergency voice evacuation panels for fire applications, mass notification applications,or both.The First Command delivers 50 or 100 watts of audio power for distribution to up to eight speaker Olt I circuits(i.e.zones).The NFC-50/100(E)comes standard with a sin- • j gle speaker circuit and a built-in 50 watt,25V amplifier.A secondary 50 watt amplifier (NFC-BDA-25/70V) can be added for single speaker circuit backup or to increase system capacity to two -: speaker circuits and an additional 50 watts of audio power. An iMik, optional NFC-CE6 module added to the NFC-50/100(E)will upgrade the system to a maximum of eight speaker circuit outputs. All speaker output circuits can be wired in either Style Y (Class B) or Style Z (Class A) configuration. The NFC-50/100(E) has fourteen field programmable messages(up to 60 seconds each), built-in field configurable pre- and post-announce tone generators and a fully supervised Notification Appliance Circuit (NAC) with 2.0 amps of synchronized NAC power. The NFC-50/100(E) includes three built- in Form-C relay contacts, (AC power, trouble and MNS active) a "'F`60 "pO NAC follower and 500mA special application power.A built-in power supply delivers operational power and an onboard battery charger FIRST CO..' supports charging up to 26AH batteries (NFC cabinet holds up to - 18AH batteries). For fire protection applications, the NFC-50/100(E) is an adjunct (slave)to any UL listed FACP, providing reverse polarity or contact closure; can be used as a stand-alone unit for non-fire applications. For seamless integration between fire and mass notification, the Features - NFC-50/100(E) can be directly activated via serial communication UL 2 72 Communication(Control Units Mass Notifi- between the NFW-100X, NFW2-100, NFS-320, or NFS2-640.Acti- UL Listed to 5 vation of the NFC-50/100(E) via other FACPs uses the eight on cation Systems) and UL 864 (emergency voice evacuation for 9 fire) board Command Input Circuits (CMDs). Two of the eight CMD cuits (CMD 1 8 CMD 2) can be individually field programmed for • Modular design for system flexibility and easy expansion activation by an FACP Notification Appliance Circuit reverse polarity • Removable terminal blocks and all eight can be activated by a contact closure. In addition, the • 50 watts of 25V audio power(expandable to 100 watts)RMS NFC-50/100(E) can be activated from a building's Private Branch • 2 amp Notification Appliance Circuit (NAC) output, sync genera- Exchange(PBX)with the integral night ring feature. tor,or follower for System Sensor,Wheelock or Gentex protocols All NFC-50/100(E) programming is done by using a simple, built-in • Optional 70Vtransformer available for the primary amplifier.(Note programming utility accessed from any laptop. For added flexibility, that speaker wiring continues to be supervised in standby, alarm the NFC-50/100(E) supports both 25V and 70V speaker output and when background music is playing with this optional trans- operation. By adding a 70V transformer conversion module (NFC- former installed) XRM-70V)or an additional 70 volt secondary amplifier(NFC-BDA- 25l70V)the system supports 70 volt speaker devices. • Eight Command Input Circuits to activate messages 1 to 8: The NFC-50/100(E)can expand in order to accommodate larger or —CMD1 and CMD2 are field selectable to be activated from 12 or 24 VDC Notification Appliance Circuits(reverse polarity)or con- more complex installations. To add more control and increase sys- tact closures tem capacity, any combination of up to eight external remote con- soles (including the NFC-LOC, NFC-RPU, and NFC-RM)and up to —CMD3-CMD8 are activated by contact closures eight distributed audio amplifiers(including the NFC-50DA(E), NFC- • Speaker Circuits 100DA(E) and NFC-125-DA(E) can be connected on the external —Single Style Y(Class B)or Style Z(Class A)speaker Circuit data bus and audio riser data bus to create a fully integrated corn- _Two Style Y(Class B)or Style Z(Class A)speaker circuits(with mand center.A fully loaded system supports up to 1100 watts of total optional NFC-BDA-25/70V Audio Amplifier installed) audio power and up to 24 speaker circuit outputs. —Eight Style Y (Class B) or Style Z (Class A) speaker circuits TYPICAL APPLICATIONS (with optional NFC-BDA-25/70V and NFC-CE6 installed) Schools Nursing Homes Factories • 520Hz square wave tones available, which can be uploaded to • the NFC-50/100 to meet NFPA Low Frequency requirements • Theaters • Military facilities • Restaurants (Refer to the Device Compatibility Document 15378 for listed • Auditoriums • Places of Worship • Office Buildings compatible speakers.) • • NFC-50/100(E) can be controlled by an FACP via the ANN/ACS (EIA-485)link of the NFW-100X and NFW2-100,and via the ACS (EIA-485) link of the NFS-320 or NFS2-640. The NFS-320 or NFS2-640 must be firmware version 20.0 or higher. DN-60772:A7.1/22/2018—Page 1 of 6 - • Certified for seismic applications when used with the appropriate seismic mounting kit , r • Integral supervised microphone E MM, LmRs a • • Microphone time-out feature which reverts back to prerecordedMMIll c o message if emergency page exceeds the programmed time 1° / 8iWiR 4130D/ IVi; 117. • 14 recorded messages z° ► SPENCER (t4"}/ ; R it • Field-selectable message and custom message recording capa- 3° ► SPEAKER (�1 , T Z0rE3 � ON TO PAGE • bility using the local microphone,a USB port,or an external audio LEANER R t-r' MOBPLREO Input 46 ► Z0NE4 ( iI0 za+E oe p • External Audio Input can be used for background music s° / �z°rR a (�I► zONE R / "•s • Up to 60 second message duration for all messages s° ► sZ"°P EDI► ZONES / =�� • Integral tone generators field selectable for multiple tone types MI► SZONEER tap Mr: CD/ sue..,(� • Powered by integral AC power supply or batteries during AC fail �I-�► SZONEAR Eat o ZO,E2e C/ ME s''M,P4 / MESSAGES=I • Programmable delay of immediate, 2 hours or 6 hours reporting ®► Z ONEPR (r/ war V of AC Loss ISM ► zoo N =► ZPOENAEa C3/ WE"J'sB • Piezo sounder for local trouble IlrEllI 0 ort Y in J► Tea MI, / MESSAGE 7 • 100 event history log (lam / io E lMO► 'PO�-N"E , p�I, RUC-AGE a • Three Form-C relays: I I I I I I I -AC Power Loss Relay-TB1 0= DUGr° D TROUBLE MENU ® °°"'°"-"^ REMOTE AMPS -System Trouble Relay-TB2 --____ .-> AC POWER o Is. MAN CONSOLE -MNS Active-TB3 D DI�ST.AMP I Ea> GROtM°EARLT °► LOC 1 ra DIET.AMP: ar? CNAR6ER°AMT °► LOCK • 500mA (0.5A) Special Application (auxiliary power) output for a GIST.AMP ca.> LATTEA,PA10.T °► RPDI addressable modules when interfaced with compatible address- fl °° AMP =a•r> OUP MD MOLT o III. RPuz able FACPs and End-of-Line power supervision relays D. Dist AMP n `°°T °► RP°' • System Status LEDs (Refer to "Controls and Indicators"in prod- D. DIST AMP 7 a SYSTEM TW°pLE o► Rm T uct manual LS10001-001NF-E.) D MST.AMP A D ALMHOOUMAi o► RR _ • Integral Dress Panel • Optional TR-CE-B semi-flush trim ring • • Any combination of up to eight(8)external remote consoles: Control and Indicators -Optional NFC-RM Remote Microphone (includes cabinet) See PUSH BUTTON CONTROLS DN-60778. ' -Optional NFC-RPU Remote Page Unit (includes cabinet) See •All Call -Message Select 1-14 DN-60775. •MNS Control •Diagnostic Select -Optional NFC-LOC Local operator console (includes cabinet) See DN-60777. •System Control •Trouble Silence • Any combination of up to eight(8)distributed audio amplifiers: •Speaker Select 1-24 •Console Lamp Test • Optional NFC-5ODA(E) distributed amplifier, 50 watts. See DN- 60776. LED Status Indicators (visible with door • Optional NFC-125DA(E)distributed amplifier, 125 watts.See DN- closed) 60776. • Optional NFC-50/100 distributed amplifier with backup capability, -Fire System Active(green) •LOC/RPU/RM 1-8 Active(green) 50/100 watts. See DN-60776. •MNS Control(green) •Main Console Fault(yellow) Optional Internal Expansion Modules •System Control(green) •AC Power(green) NFC-CE6: Circuit Expander Module provides connections for up to •System in Use(green) Ground Fault(yellow) six Style Z (Class A) or Style Y (Class B) speaker circuits. Circuits •Speaker Zone 1-24 Active(green) •Charger Fault(yellow) are configured through the web-based programming utility. •Speaker Zone 1-24 Fault(yellow) •Battery Fault(yellow) NFC-BDA-25V: 25V, 50 watt audio amplifier module.Adding a seo- .OK to Page(green) •Data Bus Fault(yellow) and speaker circuit increases the total NFC-50/100 power output to 100 watts or can also be used as a backup amplifier. •Microphone Trouble(yellow) •NAC Fault(yellow) NFC-BDA-70V: 70V, 50 watt audio amplifier module.Adding a sec- •Message 1-8 Active(red) •NAC Active(green) and speaker circuit increases the total NFC-50/100 power output to .Message 1-8 Fault(yellow) •System Trouble(yellow) 100 watts or can also be used as a backup amplifier. NFC-XRM-70V: 70V Transformer Conversion Module. Converts the •Remote Amplifier 1-8 Fault(yellow) •Audio Riser Fault(yellow) NFC-50/100(E) primary amplifier to a 70V output. This transformer •LOC/RPU/RM 1-8 Fault(yellow) - mounts directly to the NFC-50/100(E) main control board by two metal brackets. LED Indicators (visible with door and dress panel open) • Speaker Volume Control Fault(yellow) • Option Card Fault(yellow) • Amplifier Over Current Fault(yellow) • Page 2 of 6—DN-80772:A7•1/22/2018 horns/strobes a M i• f inE L?_n o w . irate / ( IA �/ NFC-BDA25/70V Internal options optional amplifier NAC Circuit Speaker Circuits ®® °°'° / p tZQ4c7C O NFC-CE6 circuit expander TB19 TB20&TB21 a . t}�4OSOg,O. o i—�i—..aj!I r ` Z ---- • I l� t ) - _ _111 -. • NFC-FFT firefighter telephone .: I era _ o a a ''' ' �� 1 a,a I�1>' remote NFC-LOC NFC-RPU NFC-RM consoles local operator console remote paging unit remote microphone 1 -I ili I1: .0 1,11.1e • r. TB4 III;IFORMilr nOtlini LIC i A * MO q ,• • TB12 1 l_ w external battery distributed audio TB22 ` charger`-J7 �� � V ` t4gb Ill* =101'' • • V ---- I .�.. .. minemm miiimm NFC-SODA 50W NFC-125DA 125W NFC-50/100DA CHG-120 charger remote amplifier remote amplifier 50/100W remote amplifier •.®oo...o aaaNI •!JL fixx.'-Cti; ' CHG-75 charger tr_----- NFC-50/100(E) First Command (Possible Configurations) DN-60772:A7-1/22/2018—Page 3 of 6 - Product Line Information THUMBLTCH:Optional Thumb Latch.(Non UL-Listed). NFC-50/100: (Primary Operating Console) 50 Watt, 25V single CHG-75:25 to 75 ampere-hours(AH)External Battery Charger. speaker zone emergency voice evacuation system, integral micro- CHG-120:25-120 ampere-hours(AH)External Battery Charger. phone, built in tone generator and 14 recordable messages. ECC-MICROPHONE: Replacement Microphone only. NFC-50/100E: Export version(Primary Operating Console)50 Watt, 25V single speaker zone emergency voice evacuation system, inte- BAT-1270: Battery,12 volt,7.0 AH (Two required). gral microphone, built in tone generator and 14 recordable mes- BAT-12120: Battery,12 volt,12.0 AH(Two required). -sages.(240 VAC,50Hz). BAT-12180: Battery,12 volt, 18.0 AH(Two required). NFC-CE6:Speaker Circuit/Zone Expander Module. BAT-12260: Battery, 12 volt,26.0 AH(Two required). NFC-BDA-25V: 25V, 50 watt audio amplifier module.Adding a sec- BB-26: Battery cabinet mounts up to two 26 AH batteries. 'ond speaker circuit increases the total NFC-50/100 power output to 100 watts or can also be used as a backup amplifier. Wiring Requirements NFC-BDA-70V: 70V, 50 watt audio amplifier module.Adding a sec- ond speaker circuit increases the total NFC-50/100 power output to See product manual, part number LS10001-001 NF-E for detailed 100 watts or can also be used as a backup amplifier. wiring requirements. NFC-XRM-70V: 70V Transformer Conversion Module. Converts the NFC-50/100(E) primary amplifier to a 70V output. This transformer Total System Capacity: (NFC-50/100(E) mounts directly to the NFC-50/100(E) main control board by two only) metal brackets. • Total Built-in Audio Power:50 Watts. NFC-LOC: Local Operator Console (Complete user interface), • Total Expandable Audio Power: 100 Watts. Please refer to the data sheet DN-60777 for more information. • Total Built-in Speaker Circuits:2. NFC-RPU: Remote Page Unit Hand held microphone, 14 message • Total Expandable Speaker Circuits:8. buttons. Please refer to the data sheet DN-60775 for more informa- • Audio Message Max lime Duration:60 seconds. Lion. • NFC-RM: Remote Microphone only. Please refer to the data sheet External Audio Input: 1. DN-60778 for more information. Total System Capacity: (Fully Loaded Sys- NFC-50DA: Distributed (Remote)Audio Amplifier, 50 watts. Please tern) refer to the data sheet DN-60776 for more information. NFC-50DAE: Export version. Distributed (Remote)Audio Amplifier, • Total Distributed Audio Power: 1100 Watts. 50 watts.(240 VAC,50Hz).Please refer to the data sheet DN-60776 • Total Speaker Circuits Per System:24. • for more information. • Total Remote Consoles Supported: 8. NFC-125DA: Distributed (Remote) Audio Amplifier, 125 watts. • Total Distributed Audio Amplifiers Supported:8. Please refer to the data sheet DN-60776 for more information. NFC-125DAE: Export version.Distributed(Remote)Audio Amplifier, Electrical Specifications 125 watts. (240 VAC, 50Hz). Please refer to the data sheet DN- 60776 PRIMARY(AC)POWER(TB15) for more information. NFC-50N00DA: Distributed (Remote)Audio Amplifier with back up,50 NFC-50/100: 120 VAC,60 Hz,3.5 amps. watts/100 watts at 25Vrms or 70Vrms. Please refer to the data sheet NFC-50/100E: 240 VAC,50 Hz,2.0 amps. DN-60776 for more information. Wire size:minimum#14 AWG(2.00mm2)with 600 V insulation. NFC-501100DAE: Export version. Distributed (Remote)Audio Amplifier SECONDARY POWER BATTER CHARGING CIRCUIT J7 with back up,50 watts/100 watts(240 VAC,50Hz).Please refer to the ( ( ) data sheet DN-60776 for more information. • Supports lead-acid batteries only. NFC-BDA-BU:Expander card for ECC-50BDA remote amplifier for 100 • Float charge voltage at 27.3V watt primary/50 watt back up operation.P/ease refer to the data sheet • Maximum charge current: 1.0 Amp DN-60776 for more information. • Maximum battery charge capability: 2.8 Amps, 26AH (NFC cabi- NFC-CE4: Distributed Audio Speaker Circuit/Zone expander mod- net holds max. 18AH battery). ule. • Minimum Battery size:12 Amp Hour. NFC-FFT: Fire Fighter Telephone System. Please refer to the data AC LOSS RELAY CONTACT RATING(TB3) sheet DN-60779 for more information. • NFC-RTZM: Remote Telephone Zone Module. Allows for secure 2.0 amps @ 30 VDC(resistive),0.5 amps @ 30 VAC(resistive). access to the NFC via cell phone or remote telephone means; not FORM C- TROUBLE RELAY CONTACT RATING(TB2) UL listed.P/ease refer to the data sheet DN-60818 for more informa- • 2.0 amps @ 30 VDC(resistive),0.5 amp @ 30 VAC(resistive). tion. SEISKIT-COMMENC: Seismic kit for the NFC-50/100. Includes bat- MNS ACTIVE RELAY CONTACT RATING(TB7) tery bracket for two 12 AH or 18 AH batteries. • 2.0 amps @ 30 VDC(resistive),0.5 amps @ 30 VAC(resistive). N-FPJ: Remote Phone Jack. NOTIFICATION APPLIANCE CIRCUIT (NAC) OUTPUT RAT- FHS-F:Fire Fighters Remote Handset. ING(TB19) FHSC-R: Fire Fighters Handset Cabinet Recessed. • One(1)Style Y(Class B)or Style Z(Class A)circuit. FHSC-S: Fire Fighters Handset Cabinet Surface Mount - Power-limited circuitry, (Class 2)supervised. TR-CE-B:Optional Trim Ring. • Nominal operating voltage:24 VDC. Page 4 of 6—DN-60772:A7.1/22/2018 - • Maximum signaling current for special application power:2.0A. CMD6-TB7 Terminals 3(+)&4(-)are input terminals for contact clo- • Maximum signaling current for regulated power:200mA. sure only. • Maximum wiring impedance: la. CMD7-TB8 Terminals 1(+)&2(-)are input terminals for contact do- - • Current limit:fuse-less,electronic,power-limited. sure only. • End-Of-Line Resistor: 4.7 KS2, 'A watt, (P/N 71252) required for CMD8-TB8 Terminals 3(+)&4(-)are input terminals for contact do- Style Y(Class B)operation. sure only. Refer to the Device Compatibility Document 15378 for listed corn- • Power-limited and supervised circuitry. patible devices. • Normal Operating Voltage Range: 10.5 VDC - 29 VDC; (Maxi- mum Voltage:29 VDC). NAC FOLLOWER OUTPUT REMOTE SYNC(TB18) • NAC Reverse Polarity Current (requires End-of-Line Resistor • Connections for FACP NAC synchronization trigger signal. from NAC): 1.6 mA maximum. • Output terminals: pass-through to other system components. • Contact Closure Operation Current(requires 4.7Kf2,'A watt End- • Trigger input voltage:9 to 32 VDC,24 VDC rated. of-Line Resistor P/N 27072):6.6 mA maximum. • Input current draw in Alarm condition: 10 mA at rated voltage. • Maximum Wiring Impedance CMD1 - CMD8 (Contact Closure Operation):20052. SPECIAL APPLICATION POWER(AUX.POWER)(T61T) NOTE: When the system is programmed for Mass Notification, • 500 mA @ 24 VDC. CMD1 and CMD2 will be programmed for Reverse Polarity only. See • Used for powering addressable modules and associated End-of- manual P/N LS10001-001NF-E for more details. Line power supervision relays. MAXIMUM INPUT IMPEDANCE: Power-limited circuitry. Refer to the Device Compatibility Document • CMD1 &CMD2(Reverse Polarity Operation):20K52. 15378 for a list of compatible devices. • CMD1 -CMD8(Contact Closure Operation):4.75KS2. SPEAKER VOLUME CONTROL OVERRIDE(TB23) NIGHT RING INPUT-T816, TERMINALS 1 (+) & 2(-) • Style Y(Class B)or Style Z(Class A)circuit. closure input. Contact • • Special application power. • o non-supervised. • Power-limited circuitry,supervised. • Nominal operating voltage:24 VDC. • Operation current:3.8 mA,maximum. • Maximum wiring impedance:30KQ. _ • Maximum signaling current:0.25 amps. • Current limit:fuse-less,electronic, power-limited. • Minimum isolation withstand voltage: 1500 VRMS. • • End-Of-Line Resistor: 4.7 KO, 'A watt, (PIN 71252) required for EXTERNAL OPERATOR INTERFACE POWER OUTPUT Style Y(Class B)operation. (TB24) SPEAKER CIRCUITS • Non-resettable power for external operator interface components. • Primary Speaker Circuit(TB20) • Power-limited circuitry,non-supervised. • Secondary Speaker Circuit(TB21)(with optional amplifier only). • Nominal operating voltage:24 VDC. —Circuit can be wired Style Y(Class B)or Style Z(Class A). • Maximum output current:0.80 amps. —Power-limited circuitry. • Current limit:fuse-less,electronic,power-limited circuit. —Normal Operating Voltage:25 VRMS @ 2 amps max and maxi- EXTERNAL DATA BUS(EIA-485)(TB12) mum Load Impedance of 12.5f2 (70V @ 700 mA max. with •maximum load Impedance of 1000 operation possible by plug- Data connections for external operator interface components. ging optional NFC-XRM-70V conversion transformer into J12 of • Redundant transceiver circuitry for Class A operability. the main control board). • Power-limited circuitry,supervised. —Output Power: 50 watts (10 watts when background music is • Maximum wiring impedance: 13.212 employed). FACP DATA BUS(EIA-485)(TB13) —Frequency Range:400Hz-4,000Hz. • Dedicated connection to FACP serial bus. —Maximum total capacitancereq for eachr Y circuit:1K50O, 1 • Output terminals:pass-through to other system components. —End-of-Line Resistor required for Style Y circuit: 15 KO, 1 watt • • Isolated,supervised. (P/N:ELR-15K). COMMAND INPUT CIRCUITS(ALARM POLARITIES SHOWN) • Minimum isolation withstand voltage: 1500 VRMS. • Maximum wiring impedance:4052(ANN-BUS),26i2 (ACS-BUS). CMD1 -TB4 Terminals 3(+)&4(-)are input terminals and Terminals External Audio Riser(TB22). • 1(-)and 2(+)are output terminals which provide feed through of thele audio connections to exter- nal circuits to NAC devices down stream. StyleY(ClassudiB)or Style Z(Class A) nal operator interface components. CMD2-TB5 Terminals 3(+)&4(-)are input terminals and Terminals Power-limited circuitry,supervised. 1(-)and 2(+)are output terminals which provide feed through of the •NAC circuits to NAC devices downstream. • Audio signal level:3.85 V, maximum. CMD3-TB6 Terminals 1(+)&2(-)are input terminals for contact do- • Frequency range:400 Hz-4 KHz RMS. - sure only. • Frequency range(NFC-50/125DA):800Hz-2KHz RMS. CMD4-TB6 Terminals 3(+)&4(-)are input terminals for contact clo- sure only. - CMDS-TB7 Terminals 1(+)&2(-)are input terminals for contact clo- sure only. DN-60772:A7•1/22/2018—Page 5 of 6 Electrical Specifications Display Board Cabinet Specifications EXTERNAL.AUDIO INPUT(TB5) • Backbox: 19.0"(48.26 cm) high x 16.65"(42.29 cm) wide x 5.20"(13.23 cm)deep. _ • Input Impedance:8.5KS2 nominal @1 KHz • Door: 19.26" (46.92 cm) high x 16.82"(42.73 cm) wide x • Input Voltage:700 mV rms maximum 0.12"(0.30 cm)deep. • Input Current:0.1 mA maximum @ 700 mV • Trim Ring(TR-CE-B):22.00"(55.88 cm)high x 19.65"(49.91 cm) NOTE: Some laptops/personal computers only provide an audio output wide. - for headphones. It may be necessary to adjust the headphone output level for proper recording of voice messages. Shipping Specifications NFC-CE6 Circuit Expander Module Specifi- Base Unit Weight:27.85 lbs(12.63 kg). cations Temperature and Humidity ranges • Power-limited circuitry. • Up to six (6) circuits on the NFC-CE6 can be wired as Style Y This system meets NFPA requirements for operation at 0—49°C/32 (Class B)or Style Z(Class A). —120°F and at a relative humidity 93%±2%RH(noncondensing)at 32°C t 2°C (90°F t 3°F). However, the useful life of the system's • Normal Operating Voltage for Speaker Circuits:25 V@ 2.0 amps standby batteries and the electronic components may be adversely max.(Maximum Load Impedance of 12.50). affected by extreme temperature ranges and humidity.Therefore, it • 70.0 V @ 700 mA max.with maximum Load Impedance of 1000 is recommended that this system and its peripherals be installed in operation possible for the primary circuit by plugging in an an environment with a normal room temperature of 15—27°C/60— optional NFC-XRM-70V conversion transformer into J12 of the 80°F. main control board. The same operation is possible for the optional 50W amplifier by selecting the NFC-BDA-70V model. Agency Listings and Approvals • Speaker circuit wiring is supervised during standby, background The listings and approvals below apply to the basic NFC-50/100(E) music,and alarm. control panel. In some cases, certain modules may not be listed by • Output Power: 50 watts total; Frequency Range: 400Hz - certain approval agencies or listing may be in process. Consult fac- 4,000Hz. tory for latest listing status. • Maximum total capacitance: 250 pF. (Note that the total capaci- • UL/ULC Listed:S635 tance for the speaker outputs must not exceed the maximum of • CSFM:6911-0028:0265 ' 250 pF.) • NYC Fire Dept.Certificate of Approval:#6163 • End-of-Line Resistor required for Style Y (Class B) speaker cir- cuit: 15 KO, 1 watt (P/N: ELR-15K) TB13 on the main control Standards and Codes board:ACS/ANN (EIA-485)electrically isolated link to FACP pro- vides programmed speaker control. The NFC-50/100(E) complies with the following UL Standards, NFPA 72, International Building Codes, and California Building Codes. • UL 864 • UL 2572 • UFC 4-021-01 • IBC 2012, IBC 2009, IBC 2006,IBC 2003, IBC 2000(Seismic) • CBC 2007(Seismic) IS® RInMfl1lan I IWlIl IIMS QUALITY AYATLMA This document is not intended to be used for installation purposes. We try to keep our product information up-to-date and accurate. We cannot cover all specific applications or anticipate all requirenments. All specifications are subject to change without notice. NOTIFIER First Common*and ldotitier@ are registered trademarks of Honeywell 12 Clintonville Road International Inc. NOTIFIER Northford,CT 06472 C2018 by Honeywell International Inc.All rights reserved.Unauthorized • 203.484.7161 use of this document sstrlcdyprohibited. by Honeywell www.notifier.com Country of Origin:USA NFC-50 DA(E) DN-60776:C NFC-125DA(E) ( N OT I F I E R® NFC-50/1 OODA by Honeywell Distributed Audio Amplifiers 1.11111 General Notifier's FirstCommand NFC-50DA(E), NFC-50/100DA and NFC-125DA(E) are intelligent 50 watt, 100 watt, and 125 watt amplifiers that are used with the NFC-50/100(E) Emergency Command Center. These distributed audio amplifiers amplify an audio message for distribution throughout a facility when additional audio power is required.They are designed as self- contained units and can be conveniently installed near an area of protection to reduce wiring demands for speaker circuit out- puts. Each NFC-50DA(E) is capable of producing 50 watts of total power and includes four built-in, fully supervised speaker cir- cuits/zones. The NFC125DA(E) is capable of producing 125 watts of total power with four built-in,fully supervised speaker circuits/zones.Both amplifiers are expandable to include eight speaker circuits when an optional NFC-CE4 module is installed. For installations that require survivability, the NFC-50/100DA can be configured for 50 watts of primary power and 50 watts of backup power, or 100 watts primary with 50 watts back up and comes standard with eight built-in, fully supervised speaker circuits/zones. Any combination of up to eight, NFC-50DA(E)s, NFC-50/ • 106DAs,or NFC-125DA(E)s can be connected to the NFC-50/ 100(E) to provide a total output of 1100 watts of audio power and up to 24 speaker circuit outputs. These distributed audio amplifiers are wired to the data bus and the Audio-Riser bus of • UL2572 (Communication and Control Units Mass Notifica- the NFC-50/100(E)primary operating console.They have their tion Systems). UL 864 (Emergency Voice Evacuation for own power supplies with built-in battery charger and are both Fire). fully supervised by the NFC-50/100(E) for any trouble condi- • Built-in power supply and battery charger that supports up tions. to 35AH.(For batteries larger than 18 AH,use the BB-26 or NFS-LBB Battery Box.) Features • NFC-50DA(E) and NFC-50/100DA are field selectable for 25Vrms or 70Vrms of operation.NFC-125DA(E)operates at • The NFC-50DA(E) and NFC-125DA(E) units come stan- 25 volts. dard with four onboard fully supervised speaker circuit Sturdy,scratch resistant cabinet. zones, and are expandable to eight circuits when an optional NFC-CE4 module is added. SOME SUITABLE APPLICATIONS • The NFC-50/100DA includes eight onboard fully supervised speaker circuits/zones. • Schools • Nursing Homes • Factories • Any combination of up to eight NFC-50DA(E)s, NFC-50/ • Theaters • Military Facilities • Restaurants 100DAs, or NFC-125DA(E)s per system can be used with • Auditoriums • Places of Worship • Office Buildings the NFC-50/100(E)for a total of 1100 watts of audio power and 24 speaker circuit outputs. Installation • The NFC-50/100DA can be used in the following configura- tions: The NFC-50DA(E), NFC-50/100DA, and NFC-125DA(E) can — 50 Watts primary/50 Watts back up be surface or flush mounted. — 100 watts primary/No back up - 100 watts primary / 50 Watts backup (Optional NFC- Compatibility BDA-BU required) The NFC-50DA(E), NFC-50/100DA, and NFC-125DA(E) are • The NFC-50/100DA supports the use of low frequency only compatible with the NFC-50/100(E)FirstCommand evac- sounders per UL 464. Refer to the Device Compatibility uation panel. Document#15378 for compatible devices. • Supports both Class A(Style Z)and Class B (Style Y)wir- Electrical Specifications ing. PRIMARY AC POWER: - • Easy setup and configuration by using a simple, built-in • NFC-SODA: 120VAC,60Hz web based programming utility on the NFC-50/100(E). • NFC-SODAE:24OVAC,50Hz • NFC-50/100DA: 120VAC,60Hz DN-60776:C•6/30/2015—Page 1 of 4 • NFC-125DA: 120VAC,60Hz Optional Modules • NFC-125DAE:240VAC,50Hz NFC-CE4: Circuit Expander Module provides connections for SPEAKER POWER: up to four Style Z(Class A) or four Style Y(Class B)speaker circuits. Circuits are configured through the web-based pro- • NFC50DA(E): 50 watts primary only (25Vrms or gramming utility on the NFC-50/100(E). 70.7Vrms). • NFC 50/100DA: 50 watts primary & 50 watts back up NFC-BDA-BU Expander card for NFC-50/100DA remote ampli- (25Vrms or 70.7Vrms); 100 watts primary only (25Vrms or fier for 100 watt primary/50 watt back up operation. 70.7Vrms); 100 watts primary&50 watts back up (25Vrms or 70.7Vrms)(NFC-BDA-BU installed). Wiring Requirements • NFC-125DA(E): 125 watts primary only(25Vrms). See Product manual part number: LS10027-001NF-E for SPEAKER OUTPUTS detailed wiring requirements. • NFC-50DA(E): Four (4) supervised Class B (Style Y) or Cabinet Specifications Class A(Style Z). outputs. (Expandable to eight with NFC- CE4). 16" W x 26.25" H x 4.125" D (40.64cm W x 66.68cm H x • NFC50/100DA: (8) supervised Class B (Style Y) or Class 10.48cm D). A(Style Z).outputs. • NFC-125DA(E): Four (4) supervised Class B (Style Y) or Shipping Specifications Class A(Style Z). outputs. (Expandable to eight with NFC- NFC-SODA Weight:25.8 lbs(11.7kg) CE4). NFC-50DA(E)Weight:25.8 lbs(11.7kg) SECONDARY POWER(BATTERY)CHARGING CIRCUIT NFC-125DA Weight:24.3 lbs(11.02kg) • Supports lead acid batteries only. NFC-125DA(E)Weight:24.3 lbs(11.02kg) • Battery charge capability: 7AH to 35AH. NFC-50/100DA Weight:28 lbs(12 kg) (The NFC-50DA(E), NFC-50/100DA and the NFC-125DA(E) NFC-BDA-BU Weight:3 lbs(1 kg) cabinet only support up to 18AH. For batteries larger than 18AH, use the BB-26 or the NFS-LBB battery box. • Other Accessories BB-26: Battery cabinet used to mount up to two 26AH Batter- ies(BAT-12260). NFS-LBB: Battery cabinet used to mount up to two 55AH Bat- teries(BAT-12250). • Product Line Information (Ordering Information) NFC-SODA: Distributed(Remote)Audio Amplifier,50 watts. NFC-50/100DA: Distributed (Remote)Audio Amplifier with back up,50 watts/100 watts at 25Vrms or 70Vrms. NFC-125DA: Distributed(Remote)Audio Amplifier. NFC-50DAE: Export version, Distributed (Remote) Audio Amplifier,50 watts,240 VAC,50 Hz. NFC-125DAE: Export version, Distributed (Remote) Audio Amplifier, 125 watts,240 VAC,50 Hz. NFC-50/100: (Primary operating Console) 50 Watt, 25VRMS single speaker zone emergency voice evacuation system, Integral microphone, built in tone generator and 14 recordable messages. Please refer to the data sheet DN-60772 for more information. NFC50/100E: Export version (Primary operating Console)50 Watt,25VRMS single speaker zone emergency voice evacua- tion system, Integral microphone, built in tone generator and 14 recordable messages.240 VAC,50 Hz. Please refer to the data sheet DN-60772 for more information. CHG-75:25 to 75 ampere-hours(AH)external battery charger. BAT-1270: Battery, 12volt,7.0AH(Two required). BAT-12120: Battery,l2volt,12.0AH(Two required). BAT-12180: Battery,l2voit, 18.0AH(Two required). BAT-1260: Battery, 12volt,26.0AH(Two required). Page 2 of 4—DN-60776:C•6/30/2015 lui .., horns/strobesf ! ii I s 10 a _ _ L i NFC-BDA25/70V NFC-CE6 circuit Internal options optional amplifier expander NAC Circuit Speaker Circuits �o aa TB19 TB20&TB21 0.<0 3 QQi Lo o a F J !I (I I 1 Y r =1 � ' I NFC-FFT firefighter telephone C iF 1f ) T • — `._ 1 C 111 remote consoles NFC-LOC local NFC-RPU remote NFC-RM remote 1011 operator console paging unit microphone rr1 TB4 ���' IlL — ...... TB12 "-" U 1 1 VIP external battery distributed audio TB22 charger-J7 �� mamil i am- ..._ ...._ ..... _.... r-WRY 131111 NFC-SODA SOW NFC-125DA125W NFC-50/100DA remote amplifier remote amplifier 50/100W remote amplifier mpg dpooaa••w poop lb m r 1. _i a®y e.tz.-a it,Om r 1 CHG-120 charger CHG-75 charger NFC-50/100(E) FirstCommand (Possible Configurations) .M.. .u. DN-60776.0•6/30/2015—Page 3 of 4 Temperature and Humidity ranges This system meets NFPA requirements for operation at 0-49° C/32-120° F and at a relative humidity 93% ± 2% RH (non- ' condensing) at 32°C ±2°C (90°F±3°F). However, the useful life of the system's standby batteries and the electronic com- ponents may be adversely affected by extreme temperature ranges and humidity. Therefore, it is recommended that this system and its peripherals be installed in an environment with a normal room temperature of 15-27°C/60-80°F. Agency Listings and Approvals The listings and approvals below apply to the NFC-50/ 125DA(E)Remote Amplifiers. In some cases,certain modules may not be listed by certain approval agencies or listing may be in process.Consult factory for latest listing status. • UL Listed S635 • CSFM:7300-0028:0266 Standards and Codes The NFC-50/100 system complies with the following UL Stan- dards and with NFPA 72 Fire Alarm system requirements. UL 864 UL 2572 FirstCommand® and Notifier® are registered trademarks of Honeywell International Inc. ©2015 by Honeywell International Inc.All rights reserved.Unauthorized use of this document is strictly prohibited. ISO 9001 This document is not intended to be used for installation purposes. We try to keep our product information up-to-date and accurate. c E w r rr F o We cannot cover all specific applications or anticipate all requirements. ENCIM1EERINC SWUM—MINE All specifications are subject to change without notice. DUALITY SYSTEMS Assembled in the USA For more information,contact Notifier.Phone:(203)484-7161,FAX:(203)484-7118. www.notifier.com 111111 Page 4 of 4—DN-60776:C•6/30/2015 P POTTER PSN SERIES The Symbol of Protection POWER SUPPLY UL,cUL,CSFM Listed • PSN-64 has 6 amps regulated with 4 Outputs • PSN-106 has 10 amps regulated with 6 Outputs • Outputs Rated at 3 amps maximum each • May be configured as up to three class"A"Style"Z"notification circuits • 3 amp,24 VDC programmable output power • Supervised Battery Charger:27.3 @ 1A(supports 7-55 AH batteries) • Easy to install cabinet with leveling mounts and key lock • Wiring knockouts provided on sides and top of cabinet • Two Trouble Relays(5A at 30VDC) General System Trouble(programmable for AC delay) • Low AC Trouble with optional delay settings • Diagnostic LED's pant pending Status LED's for Active NAC and NAC trouble conditions Status LED's for Earth Fault(Amber),AC(Green),Battery Fault(Amber) • Trouble Memory feature captures troubles which have previously restored TIP 11 • Synchronized notification appliance circuits C 05 (Q•,± Potter/AMSECW,Wheelock°,Gentex',System Sensor' LISTED lil S2930 ra 15-0328:0189 • Configurable output circuits(DIP switch sets options for each circuit) • 15 mA at 8-33 VDC input trigger Product includes a 5 year warranty • Reference EOL allows 2K—27K EOL value to be used • • Quadrasync provides panel wide synchronization of same or multiple brands Dimenions: 16 1/8"W x 16 3/4"H x 3 1/2"D • PassThru mode allows the Outputs to match the Input Signal Electrical Specs: Stock Number:3006436 PSN-64 Red Enclosure • 120/240 VAC 50-60 Hz input 3006437 PSN-106 Red Enclosure • 5.1 Amps @ 120 VAC or 2.5 Amps @ 240 VAC 3006446 PSN-106 Black Enclosure • Battery Standby Current 75 mA • Alarm Standby Current 75 mA(no external load) • Terminals support 12- 18 AWG wire. Description The PSN series of notification power supplies offers reliable notification Sensor1°strobe devices. Each output can be configured the same sync power with unprecedented versatility.The power supplies offer either protocol or set independently. 6 or 10 amps of continuous power through 4 or 6 outputs respectively. In addition,the panel has an input PassThru mode allows the outputs Each output is rated at 3 amps and it maybe used continuously without to follow the input signal and sync up the input flash. The panel will any derating. recognize the type of input being supplied and pass this through to the The power supply operates on either 120 VAC or 220 VAC power input outputs with the same pattern.This input pass through can be selected and has a regulated 24 VDC output.In addition,the panel can charge on each output independently. up to 55 AH batteries and leads the industry in housing up to 18 AH The power supply contains simple dipswitch programming and LED batteries.The cabinet is constructed out of 18 gauge cold rolled steel and indications providing the installer indications of the operation and the has a durable red powder coat finish.In addition,a key lock is provided ability to correct any faults.A Trouble Memory is provided to allow an for securing the door.Ample electrical knockouts are provided on the installer to review past troubles and make the necessary repairs.Each sides and the top, allowing the installer options for running wires and output has an LED to pin point the exact circuit where a problem may maintaining the correct separations. have occurred.Relays are provided for monitoring the general system The power supply offers an industry leading Quadrasync function that and AC failure. allows for multiple strobe circuits ofdifferentbrands lobe synchronized Each output and be independently configured for various applications to flash at the same time.The panel can have four different brands each and installations.Each output can be independently configured for Class connected to its own circuit and all of the strobes flash together. A or Class B operation,constant power,ANSI Temporal Code 3,Single, Each output can independently be configured to provide one of Multiple or Combo Inputs or Door Holder Power. four synchronizations or steady power. This provides unequivocal flexibility in new and retrofit installations.The panel can be configured to synchronize Potter/AMSECO®, Gentex®, Wheelock® and System Potter Electric Signal Co., LLC • St. Louis,MO•Cust Service: 866-240-1870 •Tech Support: 866-956-1211 •Canada 888-882-1833•www.pottersignal.com PRINTED IN USA MKT.#8910013-REV D PAGE 1 OF 2 1/18 P POTTER PSN SERIES ® The Symbol of Protection POWER SUPPLY PSN-106 Wiring Diagram A T. 120/240 VAC GND FAULT F, ;•; Jumper Position DETECT ENABLE ~ ON 0=0I OFF 120VAC 50Hz-60Hz 240VAC 50Hz-60Hz Black Connect to separate White unswitched AC circuit Ground -- status LEDs -- --- �-{ tract NAC2 NAC1 NAcA NAGS NAC6 DC MR • • • [YBYAGffiYl[BEEIBBYO] 0 ___ ail tit kii— e N IXMM• Fuse ll= o%906f1f s% /o / o111 01'[Till .1 Factory Installed Interconnect. o AC Power I I 11 El =[now Low Battery C God Fault 0 000� S6 • Comm O YW O Bulk Options • .� 7-4lv'17 i0 1rr�y�y!'yy - I i.,I 'I u u u►Y u u.'�IJ u 0 O NIACI. NAC'_ \ACI NAca . C C rWR ReF tN, 1`1= O l V I IOW, ... ___� + + + + rn +Rrll +PDl . Nr CUM NO NC CUMNU Battery+ O Common relays are ei Battery �(_ u. II n.r.. non-power limited. }=l! R t ot. F OI_ �t DC Power Truer Battery connection(non-power umired) Note:PSN-64 and PSN-106 draw 15 mA when polarity reverses and the power Use two(2)12V batteries connected in sates. supply is triggered.There is no current draw in Standby Mode. Engineering Specification The contractor shall supply and install the Potter PSN power supply.The assemblies.The LEDs shall have distinct flash patterns to provide further power supply shall operate on either 120 or 240 VAC input.The panel indication of the troubles present.The panel shall have selectable Trouble shall be capable of continuous load power without any degradation to Memory to provide the installer an indication that a past trouble existed the main supply or the distribution board.The cabinet shall be capable of on a circuit for diagnostic purposes. housing up to 18 AH batteries and the panel shall be capable of charging Each output ofthe power supply shall be capable of3 amps ofcontinuous up to 55 AH batteries in an external cabinet. power without degradation over time.The power supply shall provide for The panel shall have dip switches for simplistic configuration of the multiple circuitsofstrobeappliances.Thepowersupplyshallsynchronize system and LEDs to provide visual indication to the installer of the status the flashes of any of the above listed strobe appliances on a per circuit of the system.The dip switches shall allow forAC power delay selection, basis.Up to four different strobe circuits may be connected and all of Class A/B operation per output,Door Holder Power options,constant the strobes shall flash in unison as required by UL 864.In addition to -auxiliary power,trigger input type,ANSI Code 3 Temporal Code,Pass this Quadrasync feature, the panel shall allow any of the four above Thtu(input tracking), Potter/AMSECO®sync,Gentex®Sync, System mentioned sync patterns as an input and pass this signal through and Sensor®Sync or Wheelock®sync. The LEDs shall provide indication synchronize the outputs to match the input flash pattern. -of communication between the power supply and distribution circuit PRINTED IN USA MKT.#8910013-REV D PAGE 2 OF 2 1/18 DN-2243:B•H-300 ISO-X(A) ( ) N OT I F I E R° Fault Isolator Module by Honeywell Intelligent/Addressable Devices General The Notifier ISO-X(A) Fault Isolator Module is used with Noti- fier Onyx and CLIP series Fire Alarm Control Panels(FACPs) to protect the system against wire-to-wire short circuits on the SLC loops. Features its • Powered by SLC loop directly,no external power required. • Base mounts on standard junction boxes (4.0"/10.16 cm square by 2.125•/5.398 cm deep). • Integral LED blinks to indicate normal condition. Illuminates steady when short circuit condition is detected. • High noise (EMF/RFI) immunity. • Wide viewing angle of LED. • SEMS screws with clamping plates for ease of wiring. • Opens SLC loop automatically on detection of short, pre- venting the short from causing failure of the entire loop. • Automatically resets on correction of short. • Supports Style 4,6,or 7 wiring. d N Applications ISO-x(A) The Fault Isolator Modules should be spaced between groups of sensors in a loop to protect the rest of the loop. Use to iso- late short circuit problems within a section of a loop so that Construction other sections can continue to operate normally.The ISO-X(A) supports a maximum of 25 devices in-between isolators, The face plate is made of off-white plastic. Includes yellow except when using relay bases or legacy IPX multisensors. LED indicator that pulses when normal and illuminates steady NOTE: ON LOADS PER RELAY BASE AND LEGACY MULTI- when a short is detected. SENSOR DETECTORS/ISOLATORS/ISOLATOR BASES: the maximum number of addressable devices between isolators (or Operation B22461 isolator bases)is 25 devices. Automatically opens circuit when the line voltage drops below 25 DEVICES I four volts. Fault Isolator Modules should be spaced between groups of addressable devices (maximum 25, see notes on isolator isolator page 1) in a loop to protect the rest of the loop. If a short module module occurs between any two isolators,then both isolators immedi- or base or base ately switch to an open circuit state and isolate the groups of 2243demcee.wmr detector module sensors between them. The remaining units on the loop con- tinue to fully operate. B224RB relay bases and legacy IPX-751 multisensor detec- In Style 4 loops,the ISO-X(A) is generally used at each T-tap tors draw more current than all other intelligent devices.When branch, to limit the effect of short circuits on a branch to the calculating the 25 device maximum:B224RB. devices on that branch. The LED indicator is on continuously during a short circuit condition. • B224RB represents 2.5 devices. The ISO-X(A) Fault Isolator Module automatically restores the • IPX-751 in a standard base represents 12 devices. shorted portion of the communications loop to normal condi- • IPX-751 in a relay base represents 14.5 devices. tion when the short circuit condition is removed. • All other addressable devices represent 1 device. See examples on page 2. Installation NOTE: ON MAXIMUM NUMBER OF DEVICES: See the SLC • Mount on a standard junction box (4.0"/10.16 cm square) Manual (PN 51253) for information on loss of addresses due to which is at least 2.125"/5.398 cm deep. current limitatiOns. Each module or base added reduces the • Terminal screws are provided for"in and out"wiring. capacity of address positions in an SLC.All SLC field devices must have been purchased after February 1995 to meet the aforemen- • Installation instructions are provided with each module. tioned requirements.If the SLC field devices were purchased prior • Surface-mount box is available as an option. to February 1995,each ISO-X(A)used reduces the capacity of an SLC by two address positions. Requirements differ as applied to relay bases(see note above). DN-2243:B•01/05/2012—Page 1 of 2 Specifications Architectual/Engineering Normal operating voltage: 15—32 VDC(peak). Specifications Standby current:450 pA(not isolating). Fault Isolator Modules shall be provided to automatically iso- late current draw: 17 mA (device in isolation, LED wire-to-wire short circuits on an SLC loop.The Fault Isola- Maximumtched in alarm). tor Module shall limit the number of modules or detectors that lamay be rendered inoperative by a short circuit fault on the SLC Temperature range: 32°F to 120°F(0°C to 49°C). Loop. If a wire-to-wire short occurs, the Fault Isolator Module Relative humidity: 10%to 93%(non condensing). shall automatically open-circuit (disconnect) the SLC loop. When the short circuit condition is corrected,the Fault Isolator Weight:5 oz. (150 grams). Module shall automatically reconnect the isolated section of Dimensions: 4.5"H x 4.5"W x 0.25" D (11.43 cm H x the SLC loop.The Fault Isolator Module shall not require any 11.43 cm W x 0.635 cm D). address-setting,and its operations shall be totally automatic.It shall not be necessary to replace or reset an Fault Isolator Agency Listings and Approvals Module after its normal operation. The Fault Isolator Module shall mount in a standard 4.0" (10.16 cm) deep electrical box, In some cases, certain modules may not be listed by certain in a surface-mounted backbox, or in the Fire Alarm Control approval agencies, or listing may be in process. Consult fac- Panel. It shall provide a single LED which shall flash to indi- tory for latest listing status. cate that the Isolator is operational and shall illuminate steadily • UL:S635(UOXX);BP6480(AMCX,APOU). to indicate that a short circuit condition has been detected and isolated. • ULC: S635(OUOXXC, ISO-XA). • FM Approved. Product Line Information • CSFM: 7165-0028:0214; 7165-0028:0224; 7165- 0028:0243. NOTE:"A"suffix indicates ULC Listed model. • MEA: 17-96-E; 104-93-E Vol. VI; 290-91-E Vol. V; 317-01- ISO-X: Isolator Module. E;447-99-E. ISO-XA: Isolator Module.Canadian(ULC)version. • U.S. Coast Guard: 161.002/42/1 (NFS-640); 161.002/50/0 SMB500:Surface Mount Backbox (NFS2-640/NFS-320/NFS-320C,excluding B210LP(A)). • Lloyd's Register: 1 1/60001 3 (NFS2-640/NFS-320/NFS- 320C,excluding B210LP(A)). • BSA:578-81-SA. Examples of Device Counts (see notes under Applications) Starts Next Count isolator �� isolator a � module module or base detector with detector with • or base 3 standard base relay base module Counts as... 1 + 3.5 + 1 = 5.5 Q (2.5+1) (less than 25 total) Notifiert is a registered trademark of Honeywell international Inc. ©2012 by Honeywell International Inc.All rights reserved.Unauthorized use of this document is strictly prohibited. ISO 9001 This document is not intended to be used for installation purposes. We try to keep our product information up-to-date and accurate. c a r r F r E o We cannot cover all specific applications or anticipate all requirements. moffin ENilMERIN6 d MANUFACTURING All specifications are subject to change without notice. QUALITY SYSTEMS Made in the U.S.A. For more information,contact Notifier.Phone:(203)484-7161,FAX:(203)484-7118. www.notifier.com Page 2 of 2—DN-2243:B•01/05/2012 DN-6720:E FMM-1 (A), FMM-101 (A), N QT I F I E R® FZM-1 (A) & FDM-1 (A) Monitor Modules with FlashScan® by Honeywell Intelligent/Addressable Devices V,, General Four different monitor modules are available for Notifier's intelligent control panels for a variety of applications. Monitor :a , . modules supervise a circuit of dry-contact input devices, such as conventional heat detectors and pull stations, or _ monitor and power a circuit of two-wire smoke detectors .MD � ,« (FZM-1(A)). •..°,.,..� ... FMM-1(A) is a standard-sized module (typically mounts to a 4" [10.16 cm] square box) that supervises either a Style D (Class A) or Style B (Class B) circuit of dry-contact input •" n • FMM-101(A) is a miniature monitor module a mere 1.3•' (3.302 cm)H x 2.75"(6.985 cm)W x 0.65"(1.651 cm)D that supervises a Style B (Class B) circuit of dry-contact input devices. Its compact design allows the FMM-101(A) to be mounted in a single-gang box behind the device it monitors. 41160 1111 • FZM-1(A) is a standard-sized module that monitors and supervises compatible two-wire, 24 volt, smoke detectors on a Style D(Class A)or Style B(Class B)circuit. FMM-1(A)(Type H) FDM-1(A)is a standard-sized dual monitor module that mon- itors and supervises two independent two-wire Style B(Class open dry-contact alarm activation devices. May also be used B)dry-contact initiating device circuits(IDCs)at two separate, to monitor normally-open supervisory devices with special consecutive addresses in intelligent,two-wire systems. supervisory indication at the control panel. Monitored circuit FlashScan® (U.S. Patent 5,539,389) is a communication may be wired as an NFPA Style B (Class B)or Style D(Class protocol developed by NOTIFIER that greatly increases the A) Initiating Device Circuit.A 47K Ohm End-of-Line Resistor speed of communication between analog intelligent devices. (Provided) terminates the Style B circuit. No resistor is Intelligent devices communicate in a grouped fashion. If one required for supervision of the Style D circuit. of the devices within the group has new information, the FMM-1(A) OPERATION panel CPU stops the group poll and concentrates on single points. The net effect is response speed greater than five Each FMM-1(A)uses one of the available module addresses times that of other communication protocols. on an SLC loop. It responds to regular polls from the control panel and reports its type and the status(open/normal/short) FMM-1(A) Monitor Module of its Initiating Device Circuit(IDC).A flashing LED indicates that the module is in communication with the control panel. • Built-in type identification automatically identifies this The LED latches steady on alarm (subject to current limita- device as a monitor module to the control panel. tions on the loop). • Powered directly by two-wire SLC loop. No additional FMM-1(A)SPECIFICATIONS power required. • High noise(EMFJRFI)immunity. Nominal operating voltage: 15 to 32 VDC. • SEMS screws with clamping plates for ease of wiring. Maximum current draw: 5.0 mA(LED on). • Direct-dial entry of address:01 —159 on FlashScan loops; Average operating current: 375 pA(LED flashing), 1 corn- 01 —99 on CLIP loops. munication every 5 seconds,47k EOL. • LED flashes green during normal operation (programma- Maximum IDC wiring resistance: 1500 Ohms. ble option)and latches on steady red to indicate alarm. Maximum IDC Voltage: 11 Volts. The FMM-1(A) Monitor Module is intended for use in intelli- gent,two-wire systems,where the individual address of each EOL resistance:47K Ohms. module is selected using the built-in rotary switches. It pro- Temperature range: 32°F to 120°F(0°C to 49°C). vides either a two-wire or four-wire fault-tolerant Initiating Device Circuit(IDC)for normally-open-contact fire alarm and Humidity range: 10%to 93% noncondensing. supervisory devices.The module has a panel-controlled LED Dimensions: 4.5" (11.43 cm) high x 4" (10.16 cm) wide x indicator. The FMM-1(A) can be used to replace MMX-1(A) 1.25" (3.175 cm) deep. Mounts to a 4" (10.16 cm) square x modules in existing systems. 2.125"(5.398 cm)deep box. FMM-1(A)APPLICATIONS Use to monitor a zone of four-wire smoke detectors, manual fire alarm pull stations,waterflow devices, or other normally- DN-6720:E•07/30/2015—Page 1 of 4 FMM-101(A) Mini Monitor Module Temperature range:32°F to 120°F(0°C to 49°C). • Built-in type identification automatically identifies this Humidity range: 10%to 93%noncondensing. device as a monitor module to the panel. Dimensions: 1.3"(3.302 cm)high x 2.75" (6.985 cm)wide x • Powered directly by two-wire SLC loop. No additional 0.65"(1.651 cm)deep. power required. Wire length:6"(15.24 cm)minimum. • High noise(EMF/RFI)immunity. . • Tinned,stripped leads for ease of wiring. FZM-1(A) Interface Module • Direct-dial entry of address:01 —159 on FlashScan loops; . Supports compatible two-wire smoke detectors. 01 —99 on CLIP loops. • Supervises IDC wiring and connection of external power source. zi 3 1415 0 1 ADDRESS 0 1 • High noise(EMF/RFI)immunity. 3 113 2 1 3 1 2 • SEMS screws with clamping plates for ease of wiring. 11 4 LOOP 4 • Direct-dial entry entry of address: 01 — 159 on FlashScan 10 5 III 5 loops,01 —99 on CLIP loops. 9 8 7 6 g 8 7 6 • LED flashes during normal operation; this is a program- TENS ONES mable option. I • LED latches steady to indicate alarm on command from control panel. The FZM-1(A) Interface Module is intended for use in intelli- Otu Q gent, addressable systems, where the individual address of O z Lu geach module is selected using built-in rotary switches. This > co module allows intelligent panels to interface and monitor two- ,: wire conventional smoke detectors. It transmits the status (normal, open, or alarm) of one full zone of conventional detectors back to the control panel. All two-wire detectors I I I I being monitored must be UL compatible with the module. The FMM-101(A) Mini Monitor Module can be installed in a The FZM-1(A)can be used to replace MMX-2(A) modules in single-gang junction directly behind the monitored unit. Its existing systems. small size and light weight allow it to be installed without rigid FZM-1(A) APPLICATIONS mounting.The FMM-101(A)is intended for use in intelligent, two-wire systems where the individual address of each mod- Use the FZM-1(A) to monitor a zone of two-wire smoke • ule is selected using rotary switches. It provides a two-wire detectors. The monitored circuit may be wired as an NFPA initiating device circuit for normally-open-contact fire alarm Style B (Class B) or Style D (Class A) Initiating Device Cir- and security devices. The FMM-101(A) can be used to cuit.A 3.9 K Ohm End-of-Line Resistor(provided)terminates replace MMX-101(A)modules in existing systems. the end of the Style B or D (class B or A) circuit (maximum IDC loop resistance is 25 Ohms). Install ELR across termi- FMM-101(A)APPLICATIONS nals 8 and 9 for Style D application. Use to monitor a single device or a zone of four-wire smoke FZM-1(A) OPERATION detectors, manual fire alarm pull stations,waterflow devices, or other normally-open dry-contact devices. May also be Each FZM-1(A) uses one of the available module addresses used to monitor normally-open supervisory devices with spe- on an SLC loop. It responds to regular polls from the control cial supervisory indication at the control panel. Monitored cir- panel and reports its type and the status(open/normal/short) cuit/device is wired as an NFPA Style B (Class B) Initiating of its Initiating Device Circuit(IDC).A flashing LED indicates Device Circuit. A 47K Ohm End-of-Line Resistor (provided) that the module is in communication with the control panel. terminates the circuit. The LED latches steady on alarm (subject to current limita- tions on the loop). FMM-101(A) OPERATION Each FMM-101(A) uses one of the available module FZM-1(A)SPECIFICATIONS addresses on an SLC loop. It responds to regular polls from Nominal operating voltage: 15 to 32 VDC. the control panel and reports its type and the status (open/ Maximum current draw: 5.1 mA(LED on). normal/short)of its Initiating Device Circuit(IDC). Maximum IDC wiring resistance:25 Ohms. FMM-101(A)SPECIFICATIONS Average operating current: 270 pA, 1 communication and Nominal operating voltage: 15 to 32 VDC. 1 LED flash every 5 seconds,3.9k eol. Average operating current: 350 pA, 1 communication EOL resistance:3.9K Ohms. every 5 seconds, 47k EOL; 600 pA Max. (Communicating, IDC Shorted). External supply voltage (between Terminals T10 and T11): - Maximum IDC wiring resistance: 1500 Ohms. • DC voltage:24 volts power limited. Maximum IDC Voltage: 11 Volts. • Ripple voltage:0.1 Vrms maximum. Maximum IDC Current:450 pA. • Current: 90 mA per module maximum. EOL resistance:47K Ohms. Temperature range:32°F to 120°F(0°C to 49°C). Page 2 of 4—DN-6720:E•07/30/2015 Humidity range: 10%to 93%noncondensing. Agency Listings and Approvals Dimensions: 4.5" (11.43 cm) high x 4" (10.16 cm) wide x In some cases, certain modules may not be listed by certain 1.25" (3.175 cm) deep. Mounts to a 4" (10.16 cm) square x approval agencies,or listing may be in process. Consult fac- 2.125"(5.398 cm)deep box. tory for latest listing status. FDM-1(A) Dual Monitor Module • UL:S635. • ULC:S635. The FDM-1(A)Dual Monitor Module is intended for use in intelli- ▪ FM Approved. gent, two-wire systems. It provides two independent two-wire initiating device circuits (IDCs) at two separate, consecutive • CSFM:7300-0028:0219, 7165-0028:0224, addresses.It is capable of monitoring normally open contact fire 7165-0028:0243. alarm and supervisory devices; or either normally open or nor- • MEA:457-99-E. mally closed security devices. The module has a single panel- controlled LED. • U.S. Coast Guard: 161.002/50/0 (NFS2-640, NFS2-320, NOTE: The FDM-1(A)provides two Style B(Class B) IDC circuits NFS2-3030). ONLY. Style D (Class A) IDC circuits are NOT supported in any • Lloyd's Register: 11/600013 (NFS2-640, NFS2-320, application. NFS2-3030). FDM-1(A)SPECIFICATIONS • Fire Dept. of New York: COA #6121 (NFS2-640, NFS- 320), COA#6114(NFS2-3030). Normal operating voltage range: 15 to 32 VDC. Maximum current draw: 6.4 mA(LED on). Product Line Information Average operating current:750 pA(LED flashing). NOTE:"A"suffix indicates ULC-listed model. Maximum IDC wiring resistance: 1,500 Ohms. FMM-1(A): Monitor module. Maximum IDC Voltage: 11 Volts. FMM-101(A): Monitor module, miniature. Maximum IDC Current: 240 pA FZM-1(A): Monitor module,two-wire detectors. EOL resistance:47K Ohms. FDM-1(A): Monitor module, dual, two independent Class B circuits. Temperature range:32°to 120°F(0°to 49°C). SMB500:Optional surface-mount backbox. Humidity range: 10%to 93%(non-condensing). NOTE: See installation instructions and refer to the SLC Wiring Dimensions: 4.5" (11.43 cm) high x 4" (10.16 cm) wide x Manual,PN 51253. 1.25" (3.175 cm) deep. Mounts to a 4" (10.16 cm) square x 2.125"(5.398 cm)deep box. FDM-1(A)AUTOMATIC ADDRESSING The FDM-1(A) automatically assigns itself to two address- able points,starting with the original address. For example, if the FDM-1(A)is set to address"26",then it will automatically assign itself to addresses"26"and"27". NOTE:"Ones"addresses on the FDM-1(A)are 0,2,4,6,or 8 only. Terminals 6 and 7 use the first address,and terminals 8 and 9 use 1 the second address. ACAUTION: Avoid duplicating addresses on the system. Installation FMM-1(A), FZM-1(A), and FDM-1(A)modules mount directly to a standard 4"(10.16 cm)square,2.125" (5.398 cm)deep, electrical box. They may also be mounted to the SMB500 surface-mount box. Mounting hardware and installation instructions are provided with each module. All wiring must conform to applicable local codes, ordinances, and regula- tions. These modules are intended for power-limited wiring only. The FMM-101(A) module is intended to be wired and mounted without rigid connections inside a standard electri- - cal box. All wiring must conform to applicable local codes, ordinances, and regulations. DN-6720:E•07/30/2015—Page 3 of 4 FlashScan®and NOTIFIER®are registered trademarks and FireWatch"'is a trademark of Honeywell International Inc. ©2015 by Honeywell International Inc.All rights reserved.Unauthorized use of this document is strictly prohibited. Iso 9001 This document is not intended to be used for installation purposes. We try to keep our product information up-to-date and accurate. C E R T F 1 E U We cannot cover all specific applications or anticipate all requirements. UUII EIN6 8 MNYOFRCTERIN6 All specifications are subject to change without notice. QUALITY SYSTEMS For more information,contact Notifier.Phone:(203)484-7161,FAX:(203)484-7118. www.notifier.com Page 4 of 4—DN-6720:E•07/30/2015 ON-6724:63 FCM-1 (A) & FRM-1 (A) * NOT 1 F 1 E R® Series Control and Relay Modules by Honeywell Intelligent / Addressable Devices General FCM-1(A) Control Module: The FCM-1(A)Addressable Con- trol Module provides Notifier intelligent fire alarm control pan- els a circuit for Notification Appliances (horns, strobes, speakers, etc.).Addressability allows the FCM-1(A)to be acti- vated, either manually or through panel programming, on a t` . select(zone or area of coverage)basis. FRM-1(A)Relay Module: The FRM-1(A) Addressable Relay ""'" •''' ot ,....- Module provides the system with a dry-contact output for acti- •rr of„p,„R,., vating a variety of auxiliary devices, such as fans, dampers, u r, control equipment, etc.Addressability allows the dry contact to be activated, either manually or through panel programming, on a select basis. `t x FlashScan®(U.S. Patent 5,539,389) is a communication pro- tocol developed by NOTIFIER Engineering that greatly enhances the speed of communication between analog intelli- „ gent devices. Intelligent devices communicate in a grouped , , fashion. If one of the devices within the group has new infor- mation,the panel CPU stops the group poll and concentrates on single points.The net effect is response speed greater than five times that of other designs. FCM-1(A) Features • • Built-in type identification automatically identifies these • The FCM-1(A)is configured for a single Class B(Style Y)or devices to the control panel. Class A(Style Z) Notification Appliance Circuit. • Internal circuitry and relay powered directly by two-wire • The FRM-1(A) provides two Form-C dry contacts that • SLC loop.The FCM-1(A)module requires power(for horns, switch together. strobes,etc.),or audio(for speakers). • Integral LED "blinks" green each time a communication is Operation received from the control panel and turns on in steady red Each FCM-1(A)or FRM-1(A)uses one of 159 possible module when activated. addresses on a SLC loop (99 on CLIP loops). It responds to 1 • LED blink may be deselected globally(affects all devices). regular polls from the control panel and reports its type and • High noise immunity(EMF/RFI). status, including the open/normal/short status of its Notifica- tionThe FCM-1(A) may be used to switch 24-volt NAC power, Appliance Circuit (NAC). The LED blinks with each poll • received. On command, it activates its internal relay. The audio(up to 70.7 Vrms). FCM-1(A) supervises Class B (Style Y) or Class A (Style Z) • Wide viewing angle of LED. notification or control circuits. • SEMS screws with clamping plates for wiring ease. Upon code command from the panel, the FCM-1(A) will dis- • Direct-dial entry of address 01— 159 for FlashScan loops, connect the supervision and connect the external power sup- 01 —99 for CLIP mode loops. ply in the proper polarity across the load device. The • Speaker, and audible/visual applications may be wired for disconnection of the supervision provides a positive indication Class B or A(Style Y or Z). to the panel that the control relay actually turned ON. The external power supply is always relay isolated from the corn- Applications munication loop so that a trouble condition on the external pP power supply will never interfere with the rest of the system. The FCM-1(A) is used to switch 24 VDC audible/visual power, Rotary switches set a unique address for each module. The high-level audio (speakers). The FRM-1(A) may be pro- address may be set before or after mounting. The built-in grammed to operate dry contacts for applications such as door TYPE CODE(not settable)will identify the module to the con- holders or Air Handling Unit shutdown, and to reset four-wire trol panel, so as to differentiate between a module and a sen- smoke detector power. sor address. NOTE:Refer to the SLC Manual(PN 51253)for details regarding releasing applications with the FCM-1(A). Refer to the FCM-f-REL Specifications for FCM-1(A) datasheet(DN-60390)for new FlashScan®releasing applications. Normal operating voltage: 15 to 32 VDC. Construction Maximum current draw: 6.5 mA(LED on). • The face plate is made of off-white heat-resistant plastic. Average operating current: 350 pA direct poll,375 pA group • Controls include two rotary switches for direct-dial entry of poll with LED flashing, 485 pA Max. (LED flashing, NAC address(01-159). shorted.) DN-6724:B3.2/17/2011—Page 1 of 2 - Maximum NAC Line Loss: 4 VDC. Contact Ratings for FRM•1(A) External supply voltage(between Terminals T10 and Maximum Load T11): Maximum (NAC): Regulated 24 VDC; Maximum Currente Voltage Description Application • (Speakers):70.7 V RMS, 50W. Drain on external supply: 1.7 mA maximum using 24 VDC 3 A 30 VDC Resistive Non-Coded supply;2.2 mA Maximum using 80 VRMS supply. 2 A 30 VDC Resistive Coded Max NAC Current Ratings: For class B wiring system, the 9 A 110 VDC Resistive Non-Coded current rating is 3A; For class A wiring system, the current rat- ing is 2A. .9 A 125 VDC Resistive Non-Coded Temperature range: 32°F to 120°F(0°C to 49°C). .5 A 30 VDC Inductive Coded (L/R=5ms) Humidity range: 10%to 93%non-condensing. 1 A 30 VDC Inductive Coded Dimensions: 4.5" (114.3 mm) high x 4" (101.6 mm) wide x (L/R=2ms) 1.25" (31.75 mm) deep. Mounts to a 4" (101.6 mm) square x 2.125"(53.975 mm)deep box. .3 A 125 VAC Inductive Non-Coded (PF=0.35) Accessories: SMB500 Electrical Box;CB500 Barrier Inductive Specifications for FRM•1(A) 1.5 A 25 VAC (PF=0.35) Non-Coded Normal operating voltage: 15 to 32 VDC. Inductive Maximum current draw: 6.5 mA(LED on). .7 A 70.7 VAC (PF=0.35) Non-Coded Average operating current: 230 pA direct poll;255 pA group poll. Inductive 2 A 25 VAC (PF=0.35) Non-Coded EOL resistance: not used. Temperature range: 32°F to 120°F(0°C to 49°C). NOTE:Maximum(Speakers):70.7 V RMS,50 W Humidity range: 10%to 93%non-condensing. Dimensions: 4.5° (114.3 mm) high x 4" (101.6 mm) wide x Product Line Information - 1.25" (31.75 mm) deep. Mounts to a 4" (101.6 mm) square x NOTE: A"suffix indicates ULC Listed model. 2.125"(53.975 mm)deep box. FCM-1(A): Intelligent Addressable Control Module. Accessories: SMB500 Electrical Box;CB500 Barrier FRM-1(A): Intelligent Addressable Relay Module. Agency Listings and Approvals A2143-20: Capacitor, required for Class A(Style Z)operation - of speakers. In some cases, certain modules may not be listed by certain SMB500: Optional Surface-Mount Backbox. approval agencies, or listing may be in process. Consult fac- SMB500: Optional Surface-Mount Backbox. tory for latest listing status. CB500: Control Module Barrier-required by UL for separat- • UL:S635 ing power-limited and non-power limited wiring in the same • ULC:S3705(A version only) junction box as FCM-1(A). • FM Approved NOTE:For installation instructions,see the following documents: • CSFM:7300-0028:0219 • FCM-1(A)Installation document 156-1169. • MEA: 14-00-E • FRM-1(A)Installation document 156-3502. • FDNY:COA#6067,#6065 • Notifier SW Wiring Manual,document 51253. Notifier® and FlashScan® are registered trademarks of Honeywell International Inc. C2011 by Honeywell International Inc.All rights reserved.Unauthorized use of this document is strictly prohibited. ISO 9001 This document is not intended to be used for installation purposes. We try to keep our product information up-to-date and accurate. gi C E FUT F E We cannot cover all specific applications or anticipate all requirements. ItlMHIN6 8 MANMACTLAIN6 All specifications are subject to change without notice. QUALITY SYSTEMS Made in the U.S.A. For more information,contact Notifier.Phone:(203)484-7161,FAX:(203)484-7118. www.notifier.com Page 2 of 2-DN-6724:B3.2/17/2011 DN-6726:D•H-240 NBG-12LX ® NOTIFIER® Addressable Manual Pull Station by Honeywell i, Intelligent/Addressable Devices `General The Notifier NBG-12LX is a state-of-the-art, dual-action (i.e., FIRE requires two motions to activate the station) pull station that includes an addressable interface for any Notifier intelligent control panel except FireWarden series panels, and the NSP- 25 panel. Because the NBG-12LX is addressable, the control panel can display the exact location of the activated manual PUSH tt4 station.This leads fire personnel quickly to the location of the 1 PULL DOWN' `. alarm. 1. i Features • Maintenance personnel can open station for inspection and address setting without causing an alarm condition. • Built-in bicolor LED, which is visible through the handle of L the station,flashes in normal operation and latches steady CJ 1.40T{FIER . % red when in alarm. 1 0 S • Handle latches in down position and the word"ACTIVATED" appears to clearly indicate the station has been operated. • Captive screw terminals wire-ready for easy connection to The NBG-12LX SLC loop(accepts up to 12 AWG/3.25 mmz wire). • Can be surface mounted (with SB-10 or SB-I/O) or semi- Addressable Manual Pull Station flush mounted. Semi-flush mount to a standard single- Installation gang,double-gang,or 4" (10.16 cm)square electrical box. • Smooth dual-action design. The NBG-12LX will mount semi-flush into a single-gang, dou- • Meets ADAAG controls and operating mechanisms guide- ble-gang, or standard 4" (10.16 cm) square electrical outlet lines (Section 4.1.3[13]); meets ADA requirement for 5 lb. box, or will surface mount to the model SB-10 or SB-I/O sur- maximum activation force. face backbox. If the NBG-12LX is being semi-flush mounted, then the optional trim ring (BG12TR) may be used. The • Highly visible. BG12TR is usually needed for semi-flush mounting with 4" • Attractive shape and textured finish. (10.16 cm)or double-gang boxes(not with single-gang boxes). • Key reset. • Includes Braille text on station handle. Operation • Optional trim ring(BG12TR). Pushing in, then pulling down on the handle causes it to latch • Meets UL 38, Standard for Manually Actuated Signaling in the down/activated position.Once latched, the word "ACTI- Boxes. VATED" (in bright yellow) appears at the top of the handle, • Up to 99 NBG-12LX stations per loop on CLIP protocol while a portion of the handle protrudes from the bottom of the loops. station.To reset the station, simply unlock the station with the key and pull the door open.This action resets the handle;clos- • Up to 159 NBG-12LX stations per loop on FlashScan®pro- ing the door automatically resets the switch. tocol loops. • Dual-color LED blinks green to indicate normal on Each manual station, on command from the control panel, FlashScan®systems. sends data to the panel representing the state of the manual switch.Two rotary decimal switches allow address settings (1 —159 on FlashScan®systems, 1 —99 on CLIP systems). Construction Shell, door, and handle are molded of durable polycarbonate Architectural/Engineering material with a textured finish. Specifications ec S ifications Manual Fire Alarm Stations shall be non-coded, with a p key- operated reset lock in order that they may be tested, and so • Shipping Weight:9.6 oz. (272.15 g) designed that after actual Emergency Operation, they cannot • Normal operating voltage:24 VDC. be restored to normal except by use of a key.An operated sta- Maximum SLC loop voltage:28.0 VDC. tion shall automatically condition itself so as to be visually • detected as activated. Manual stations shall be constructed of • Maximum SLC standby current:375 pA. red-colored polycarbonate material with clearly visible operat- • Maximum SLC alarm current:5 mA. ing instructions provided on the cover. The word FIRE shall • . • Temperature Range:32°F to 120°F(0°C to 49°C) appear on the front of the stations in white letters, 1.00 inches • Relative Humidity: 10%to 93%(noncondensing) (2.54 cm) or larger. Stations shall be suitable for surface mounting on matching backbox SB-10 or SB-I/O;or semi-flush • For use indoors in a dry location mounting on a standard single-gang, double-gang, or DN-6726:D•4/13/2012—Page 1 of 2 4"(10.16 cm) square electrical box, and shall be installed within the limits defined by the Americans with Disabilities Act (ADA) or per nationaVlocal requirements. Manual Stations shall be Underwriters Laboratories listed. Manual stations shall connect with two wires to one of the con- trol panel SLC loops. The manual station shall, on command from the control panel,send data to the panel representing the state of the manual switch. Manual stations shall provide address setting by use of rotary decimal switches. The loop poll LED shall be clearly visible through the front of the station.The LED shall flash while in the normal condition, • and stay steadily illuminated when in alarm. Product Line Information NBG-12LX: Dual-action addressable pull station. Includes key locking feature. (Listed for Canadian and non-Canadian appli- cations.) NBG-12LXSP:Spanish/English labelled version. NBG-12LXP:Portuguese labelled version. SB-10:Surface backbox;metal. SB-I/O:Surface backbox;plastic. BG12TR:Optional trim ring. 17021:Keys,set of two. NY-Plate: New York City trim plate. Agency Listings and Approvals In some cases, certain modules or applications may not be listed by certain approval agencies, or listing may be in pro- • cess.Consult factory for latest listing status. • UUULC Listed: S692 (listed for Canadian and non-Cana- dian applications). • MEA:67-02-E. • CSFM:7150-0028:0199. • FDNY:COA#6085(NFS2-640),COA#6098(NFS2-3030). • BSMI:CI313066760047. • U.S.Coast Guard. • Lloyd's Register. • FM Approved. Patented: U.S. Patent No. D428,351; 6,380,846; 6,314,772; 6,632,108. NOTIFIER® and FlashScan® are registered trademarks of Honeywell International Inc. ®2012 by Honeywell International Inc.All rights reserved.Unauthorized use of this document is strictly prohibited. 1 S O 9001 This document is not intended to be used for installation purposes. We try to keep our product information up-to-date and accurate. _ G E R T•F 1 E O We cannot cover all specific applications or anticipate all requirements. �r @ICINEMIN6&MANIFACTIMN6 All specifications are subject to change without notice. QUALITY SYSTEMS Made in the U.S.A. For more information,contact Notifier.Phone:(203)484-7161,FAX:(203)484-7118. www.notifler.com • Page 2 of 2—DN-6726:D•4/13/2012 ® NOTIFIER� by Honeywell FSP-951 Series Addressable Photoelectric Smoke Detectors The NOTIFIER®FSP-951 Series intelligent plug-in smoke detectors are designed for both performance and aesthetics, and are direct replacements for the FSP-851 Series. A new modern, sleek, con- -temporary design and enhanced optical sensing chamber is engi- neered to sense smoke produced by a wide range of combustion sources in accordance with more stringent code standards. The FSP-951 Series detector sensitivity can be programmed in the control panel software. Sensitivity is continuously monitored and reported to the panel. Point ID capability allows each detector's address to be set with rotary, decimal address switches, providing exact detector location for selective maintenance when chamber contamination reaches an unacceptable level. Dual electronic 44,100 thermistors add 135°F(57°C)fixed temperature thermal sensing on the FSP-951T.The FSP-951R is a remote test capable detector for ,. use with DNR Series duct detector housings. FSP-951 series detec- tors are available for both FlashScan® and CLIP applications as designated. Features SLC LOOP: • Separate base allows interchange of photoelectric,ionization and thermal sensors • Two-wire SLC loop connection • Unit uses base for wiring OPTIONS: • Compatible with FlashScan®and CLIP protocol systems • Optional relay, isolator,and sounder bases • Stable communication technique with noise immunity• Installation ADDRESSING: FSP-951 Series plug-in intelligent smoke detectors use a detach- • Addressable by device able base to simplify installation, service and maintenance. Installa- • Rotary,decimal addressing tion instructions are shipped with each detector. (Refer to the NOTIFIER panel manuals for device capacity.) Mount detector base(all base types)on an electrical backbox which ARCHITECTURE: is at least 1.5" (3.81 cm) deep. For a chart of compatible junction • Sleek, low-profile,stylish design boxes,see DN-60054. • Unique single-source design to respond quickly and dependably NOTE:Because of the inherent supervision provided by the SLC loop, to a broad range of fires end-of-line resistors are not required. Wiring "T-taps"or branches are 9 permitted for Style 4(Class B)wiring only. • Integral communications and built-in device-type identification When using relay or sounder bases, consult the ISO-X(A) installation • Built-in tamper resistant feature sheet 156-1380 for device limitations between isolator modules and iso- • Remote test feature from the panel /ator bases. • Walk test with address display (an address on 121 will blink the Construction detector LED: 12-[pause]-1(FlashScan systems only) • Built-in functional test switch activated by external magnet These detectors are constructed of fire-resistant plastic.The FSP- 951 Series plug-in intelligent smoke detectors are designed to com- • Removable cover and insect-resistant screen for simple field mercial standards and offer an attractive appearance. cleaning • Expanded color options Operation OPERATION: Each FSP-951 Series detector uses one of the panel's addresses • Designed to meet UL 268 7th Edition (total limit is panel dependent)on the NOTIFIER Signaling Line Cir- • Factory preset at 1.5%nominal sensitivity for panel alarm thresh- cuit (SLC). It responds to regular polls from the control panel and old level reports its type and the status.If it receives a test command from the • LED"blinks"when the unit is polled (communicating with the fire panel (or a local magnet test), it stimulates its electronics and panel)and "when alarm. reports an alarm. It blinks its LEDs when polled and turns the LEDs P ) on when commanded by the panel. The FSP-951 Series offers fea- • Low standby current tures and performance that represent the latest in smoke detector MECHANICALS: technology. • Sealed against back pressure • SEMS screws for wiring of the separate base • Designed for direct-surface or electrical-box mounting . • Plugs into separate base for ease of installation and maintenance DN-60977:B•7/1/2019—Page 1 of 3 - Product Line Information B200SA-IV:Same as B200S-IV,ULC listing NOTE:"-IV"suffix indicates CLIP and FlashScan device. B200SCOA-WH: White, Intelligent, programmable sounder base in FSP-951:White,low-profile intelligent photoelectric sensor, FlashS- English/Frenchedto (requiredppliatiin Canada for ULC applications with CO - can only Series detector applications B200SCOA-IV: Ivory Intelligent, programmable sounder base in FSP-951A:Same as FSP-951 but with ULC listing English/French (required in Canada for ULC applications with CO FSP-951-IV: Ivory, low-profile intelligent photoelectric sensor Series detector applications,ULC listing FSP-951A-IV:Same as FSP-951-IV but with ULC listing B200S-LF-WH: White, Low Frequency Intelligent, programmable sounder base. Produces a fundamental frequency of 520 Hz +/- FSP-951T: White, same as FSP-951 but includes a built-in 135°F 10% with a square wave or its equivalent; designed to meet the (57°C)fixed-temperature thermal device,FlashScan only NFPA 72 sleeping space requirement.(CSFM:7300-1653:0238) FSP-951TA:Same as FSP-951T but with ULC listing B200S-LF-IV: Ivory, Low Frequency Intelligent, programmable FSP-951T-IV: Ivory,same as FSP-951T but includes a built-in 135°F sounder base. Produces a fundamental frequency of 520 Hz +/- (57°C)fixed-temperature thermal device 10% with a square wave or its equivalent; designed to meet the NFPA 72 sleeping space requirement.(CSFM:7300-1653:0238) FSP-951TA-IV:Same as FSP-951T-IV but with ULC listing B200SR-WH:White, Intelligent sounder base capable of producing FSP-951R: White, low-profile intelligent photoelectric sensor, sound output with ANSI Temporal 3 or continuous tone. Intended for remote test capable,for use with DNR/DNRW, FlashScan only retrofit applications. (CSFM:7300-1653:0213) FSP-951RA: Same as FSP-951R but with ULC listing, for use with B200SR-IV: Ivory, Intelligent sounder base capable of producing DNRA sound output with ANSI Temporal 3 or continuous tone. Intended for retrofit applications. (CSFM: 7300-1653:0213) FSP-951R-IV: Ivory, low-profile intelligent photoelectric sensor, remote test capable,for use with DNR/DNRW B200SRA-WH: Same as B200SR-WH with, ULC listing FSP-951RA-IV: Same as FSP-951 R-IV but with ULC listing,for use B200SRA IV: Same as B200SR-IV in Ivory color,ULC listing with DNRA B200SR-LF-WH: White, Low Frequency Intelligent, programmable sounder base. Produces a fundamental frequency of 520 Hz +/- INTELLIGENT BASES 10% with a square wave or its equivalent; designed to meet the NOTE:For details on intelligent bases,see DN-60981. NFPA 72 sleeping space requirement. Intended for retrofit applica- B300-6:White,6"base,standard flanged low-profile mounting base tions. (CSFM:7300-1653:0238) (CSFM:7300-1653:0109) B200SR-LF-IV: Ivory, Low Frequency Intelligent, programmable - B300-6-IV: Ivory,6" base, standard flanged low-profile mounting sounder base. Produces a fundamental frequency of 520 Hz +/- base (CSFM:7300-1653:0109) 10% with a square wave or its equivalent; designed to meet the NFPA 72 sleeping space requirement. Intended for retrofit applica- B300A-6:Same as B300-6, ULC listed tions.(CSFM: 7300-1653:0238) B300A-6-IV: Ivory, 6" standard flanged low-profile mounting base, MOUNTING KITS AND ACCESSORIES ULC listed B300-6-BP: Bulk pack of B300-6,package contains 10 TR300:White, replacement flange for 6210LP(A)base TR3004V: Ivory, replacement flange for B210LP(A)base B501 WHITE: White, 4" standard European flangeless mounting base.UUULC listed(CSFM:7300-1653:0109) RA100Z(A): Remote LED annunciator.3-32 VDC. Mounts to a U.S. B501-BL: Black, 4" standard European flangeless mounting base. single-gang electrical box. For use with B501(A)and B300-6(A). UUULC listed(CSFM:7300-1653:0109) M02-04-00:Test magnet B501-IV: Ivory color, 4" standard European flangeless mounting M02-09-00:Test magnet with telescoping handle base.UUULC listed(CSFM:7300-1653:0109) CK300:Color Kit(includes cover and trim ring),white, 10-pack B501-WHITE-BP:Bulk pack of B501-WHITE contains 10 CK300-IV:Color Kit(includes cover and trim ring),ivory, 10-pack B224RB-WH:White,relay base(CSFM:7300-1653:0216) CK300-BL:Color Kit(includes cover and trim ring),black, 10-pack B224RB-IV: Ivory, relay base(CSFM: 7300-1653:0216) B224RBA-WH:White, relay base, ULC listing B224RBA-IV: Ivory,relay base, ULC listing B224BI-WH:White,isolator detector base(CSFM:7300-1653:0216) B224B1-IV: Ivory isolator detector base(CSFM:7300-1653:0216) B224BIA-WH:White,isolator detector base, ULC listing B224BIA-IV: Ivory isolator detector base,ULC listing B200S-WH:White, Intelligent addressable sounder base capable of producing sound output in high or low volume with ANSI Temporal 3, ANSI Temporal 4,continuous tone,marching tone,and custom tone. Uses FlashScan protocol.(CSFM:7300-1653:0213) B200S-IV: Ivory, Intelligent addressable sounder base capable of producing sound output in high or low volume with ANSI Temporal 3, ANSI Temporal 4,continuous tone,marching tone,and custom tone. Uses FlashScan protocol.(CSFM:7300-1653:0213) B200SA-WH:Same as B200S-WH,ULC listing Page 2 of 3—DN-60977:8•7/1/2019 SPECIFICATIONS Sensitivity: Listings and Approvals • UL Applications:0.5%to 4.0%per foot obscuration. Listings and approvals below apply to the FSP-951 Series detectors. • ULC Applications:0.5%to 3.5%per foot obscuration In some cases, certain modules may not be listed by certain Size:2.0"(5.3 cm)high;base determines diameter approval agencies, or listing may be in process. Consult factory for latest listing status. —B300-6:6.1"(15.6 cm)diameter • UL/ULC Listing:51115 - —B501:4"(10.2 cm)diameter • FM Approved For a complete list of detector bases see DN-60981 • CSFM:7272-0028:0503 Shipping weight:3.4 oz.(95 g) Operating temperature range: • FSP-951:32°F to 122°F(0°C to 50°C) • FSP-951T Series: 32°F to 100°F(0°C to 38°C) • FSP-951 R Series installed in a DNRIDNRW,-4°F to 158°F(-20°C to 70°C) UUULC Listed Velocity Range: 0-4000 f lmin. (1219.2 mlmin.), suitable for installation in ducts Relative humidity: 10%—93%non-condensing Thermal ratings:fixed-temperature set point 135°F(57°C),rate-of- rise detection 15°F(8.3°C)per minute, high temperature heat 190°F (88°C) ELECTRICAL SPECIFICATIONS Voltage range: 15-32 volts DC peak Standby current(max.avg.): 200pA @ 24 VDC(one communica- tion every 5 seconds with LED enabled) . Max current:4.5 mA @ 24 VDC("ON") DETECTOR SPACING AND APPLICATIONS NOTIFIER recommends spacing detectors in compliance with NFPA - 72. In low airflow applications with smooth ceiling, space detectors 30 feet(9.1 m). For specific information regarding detector spacing, placement, and special applications refer to NFPA 72. A System Smoke Detector Application Guide, document A05-1003, is avail- able at www.systemsensor.com. ISO nurataIA6 B MAkvrA aWS QUAIITY SYSTEMS This documents not Intended to be used for Installation puposes. We try to keep our product inlamaton up-to-date and accurate. We cannot cover all specific applications or anticipate all requirements. NI specifications are subject to change without notice. NOTIFIER Fasnbcana NOTV- _:stered trademar, 12 Clintonville Road et Honeywell lnternaOona Inc ® NOTIFIER Northford,CT 06472 M2019 by Honeywell International Inc M rgnts reserved.Ureuthodzed 203.484.7161 use ofidrs document is smcly probbded. �`/t Honeywell www.notifier.com Country of Origin:Mexico � f t NOTIFIER,. by Honeywell FST-951 Series Intelligent Addressable Heat Detectors The NOTIFIER® FST-951 Series intelligent thermal detectors are designed for both performance and aesthetics, and are direct replacements for the FST-851 Series. A new modern, sleek, con- .temporary design and advanced thermal technologies make the FST-951 Series ideal for both system operation and building design. The point ID address, set using rotary decimal switches, provide specific detector locations. The series includes a 135°F/57°C fixed-temperature, rate-of-rise, and a 190°F/88°C fixed high-temperature detectors.These thermal detectors provide effective,intelligent property protection in a variety of applications. Detectors are available for both FlashScan® and CLIP applications as designated. Features SLC LOOP: • • Two-wire SLC loop connection • Unit uses base for wiring ADDRESSING: Installation • Addressable by device FST-951 Series plug-in intelligent thermal detectors use a detach- _ • Rotary,decimal addressing able base to simplify installation, service and maintenance. Installa- (Refer to the NOTIFIER panel manuals for device capacity.) tion instructions are shipped with each detector. • ARCHITECTURE: Mount detector base(all base types)on an electrical backbox which • Designed to meet UL 268 7th Edition is at least 1.5" (3.81 cm) deep. For a chart of compatible junction boxes, see DN-60054. • Sleek, low-profile,stylish design NOTE:Because of the inherent supervision provided by the SLC loop, • State-of-the-art thermistor technology for fast response end-of-line resistors are not required. Wiring °T taps"or branches are • Integral communications and built-in device-type identification permitted for Style 4(Class°B)wiring only. • Built-in tamper resistant feature When using relay or sounder bases, consult the ISO-X(A) installation sheet 156-1380 for device limitations between isolator modules and iso- • Built-in functional test switch activated by external magnet /atorbases. OPERATION: • Fixed temperature model (FST-951) factory preset to 135°F Applications (57°C) Use thermal detectors for protection of property.For further informa- • Rate-of-rise model(FST-951 R),15°F(8.3°C)per minute tion, refer to 156-6522, Applications Manual for System Smoke • High-temperature model FST-951 H) factory preset to 190°F Detectors,which provides detailed information on detector spacing, (88°C) placement,zoning,wiring,and special applications. • 360°-field viewing angle of the two visual alarm indicators, LEDs Construction blink red in Normal condition and turn on steady red in Alarm • LEDs blink every time the unit is polled These detectors are constructed of fire-resistant plastic. The FST- 951 Series plug-in intelligent thermal detectors are designed to corn- MECHANICALS: mercial standards and offer an attractive appearance. • Sealed against back pressure • SEMS screws for wiring of the separate base Operation • Designed for direct-surface or electrical-box mounting Each FST-951 Series detector uses one of the panel's addresses • Plugs into separate base for ease of installation and maintenance (total limit is panel dependent)on the NOTIFIER Signaling Line Cir- • Separate base allows interchange of photoelectric,ionization and cuit (SLC). It responds to regular polls from the control panel and thermal sensors reports its type and the status.If it receives a test command from the panel (or a local magnet test), it stimulates its electronics and OTHER SYSTEM FEATURES: reports an alarm. It blinks its LEDs when polled and turns the LEDs • Remote test feature from the panel on when commanded by the panel.The FST-951 Series offers fea- tures and performance that represent the latest in thermal detector • Walk test with address display technology. • Low standby current ' OPTIONS: • Remote LED output connection to optional RA100Z remote LED annunciator DN-60975:B•6/26/2019—Page 1 of 3 Product Line Information B200SCOA-WH: White, Intelligent, programmable sounder base in English/French (required in Canada for ULC applications with CO NOTE:"-IV"suffix indicates CLIP and FlashScandevice. Series detector applications FST-951: White, low-profile intelligent 135°F fixed thermal sensor, B200SCOA-IV: Ivory Intelligent, programmable sounder base in FlashScan only English/French (required in Canada for ULC applications with CO FST-951A:Same as FST-951 but with ULC listing Series detector applications,ULC listing FST-951-IV: Ivory, low-profile intelligent 135°F fixed thermal sensor, B200S-LF-WH: White, Low Frequency Intelligent, programmable - FlashScan and CLIP sounder base. Produces a fundamental frequency of 520 Hz +/- FST-951A-IV: Same as FST-951-IV but with ULC listing 10% with a square wave or its equivalent; designed to meet the NFPA 72 sleeping space requirement.(CSFM:7300-1653:0238) FST-951R: White, low-profile intelligent rate-of-rise thermal sensor, B200S-LF-IV: Ivory, Low Frequency Intelligent, programmable FlashScan only sounder base. Produces a fundamental frequency of 520 Hz +/- FST-951RA: Same as FST-951 but with ULC listing 10% with a square wave or its equivalent; designed to meet the FST-951R-IV: Ivory, low-profile intelligent rate-of-rise fixed thermal NFPA72 sleeping space requirement.(CSFM: 7300-1653:0238) sensor,FlashScan and CLIP B200SR-WH: White, Intelligent sounder base capable of producing FST-951RA-IV:Same as FST-951R-IV but with ULC listing sound output with ANSI Temporal 3 or continuous tone. Intended for retrofit applications. (CSFM:7300-1653:0213) FST-951H:White, low-profile intelligent 190°F fixed thermal sensor, FlashScan only B200SR-IV: Ivory, Intelligent sounder base capable of producing sound output with ANSI Temporal 3 or continuous tone. Intended for FST-951HA:Same as FST-951H but with ULC listing retrofit applications. (CSFM:7300-1653:0213) FST-951H-IV: Ivory, low-profile intelligent 190°F thermal sensor, B200SRA-WH:Same as B200SR-WH with, ULC listing FlashScan and CLIP B200SRA-IV:Same as B200SR-IV in Ivory color, ULC listing FST-951HA-N Same as FST-951 but with ULC listing B200SR-LF-WH: White, Low Frequency Intelligent, programmable INTELLIGENT BASES sounder base. Produces a fundamental frequency of 520 Hz +/- NOTE:For details on intelligent bases,see DN-60981. 10% with a square wave or its equivalent; designed to meet the 8300 6:White,6"base,standard flanged low-profile mounting base NFPA 72 sleeping space requirement. Intended for retrofit applica- lions.(CSFM:7300-1653:0238) (CSFM: 7300-1653:0109) B300-6-IV: Ivory,6" base, standard flanged low-profile mounting B200SR-LF-IV: Ivory, Low Frequency Intelligent, programmable sounder base. Produces a fundamental frequency of 520 Hz +/- base(CSFM:7300-1653:0109) 10% with a square wave or its equivalent; designed to meet the B300A-6: Same as B300-6, ULC listed NFPA 72 sleeping space requirement. Intended for retrofit applica- B300A-6-IV: Ivory, 6" standard flanged low-profile mounting base, lions.(CSFM:7300-1653:0238) • ULC listed MOUNTING KITS AND ACCESSORIES B300-6-BP: Bulk pack of B300-6, package contains 10 TR300:White,replacement flange for B210LP(A)base B501-WHITE: White, 4" standard European flangeless mounting TR300-V: Ivory, replacement flange for B210LP(A)base base. UUULC listed(CSFM:7300-1653:0109) RA100Z(A): Remote LED annunciator.3-32 VDC. Mounts to a U.S. B501-BL: Black, 4" standard European flangeless mounting base. single-gang electrical box.For use with B501(A)and B300-6(A). UUULC listed(CSFM:7300-1653:0109) M02-04-00:Test magnet B501-IV: Ivory color, 4" standard European flangeless mounting base.UUULC listed (CSFM:7300-1653:0109) M02-09-00:Test magnet with telescoping handle B501-WHITE-BP:Bulk pack of B501-WHITE contains 10 CK300:Color Kit(includes cover and trim ring),white, 10-pack B224RB-WH:White,relay base(CSFM:7300-1653:0216) CK300-IV:Color Kit(includes cover and trim ring),ivory, 10-pack B224RB-IV: Ivory,relay base(CSFM: 7300-1653:0216) CK300-BL:Color Kit(includes cover and trim ring),black, 10-pack B224RBA-WH:White,relay base,ULC listing B224RBA-IV: Ivory,relay base, ULC listing B224BI-WH:White,isolator detector base(CSFM:7300-1653:0216) B224BI-IV: Ivory isolator detector base(CSFM:7300-1653:0216) B224BIA-WH:White, isolator detector base, ULC listing B224BIA-IV: Ivory isolator detector base, ULC listing B200S-WH:White, Intelligent addressable sounder base capable of producing sound output in high or low volume with ANSI Temporal 3, ANSI Temporal 4,continuous tone,marching tone,and custom tone. Uses FlashScan protocol.(CSFM:7300-1653:0213) B200S4V: Ivory, Intelligent addressable sounder base capable of ' producing sound output in high or low volume with ANSI Temporal 3, ANSI Temporal 4,continuous tone,marching tone,and custom tone. Uses FlashScan protocol. (CSFM:7300-1653:0213) • B200SA-WH: Same as B200S-WH, ULC listing B200SA-IV: Same as B200S-IV, ULC listing Page 2 of 3—DN-60975:B-6/26/2019 SPECIFICATIONS Sensitivity: UL Applications: 0.5% to 4.0% per foot obscuration. ULC is 0.5%to 3.5% ' Size:2.0"(5.3 cm)high;base determines diameter —B300-6:6.1"(15.6 cm)diameter —B501:4"(10.2 cm)diameter For a complete list of detector bases see DN-60981 Shipping weight:3.4 oz.(95 g) Operating temperature range: • FST-951, FST-951 R Series:—4°F to 100°F(-20°C to 38°C) • FST-951H Series:—4°F to 150°F(-20°C to 66°C) Detector spacing: UL approved for 50 ft. (15.24 m)center-to-cen- ter, FM approved for 25 x 25 ft.(7.62 x 7.62 m)spacing Relative humidity: 10%—93%non-condensing Thermal ratings:fixed-temperature set point 135°F(57°C), rate-of- rise detection 15°F(8.3°C)per minute,high temperature heat 190°F (88°C) Mounting: B300-6(A)flanged base, included See"Product Line Information: Intelligent Bases," if using a dif- ferent base. ELECTRICAL SPECIFICATIONS Voltage range: 15-32 volts DC peak Standby current(max. avg.): 200pA @ 24 VDC (one communica- tion every 5 seconds with LED enabled) Max current:4.5 mA @ 24 VDC("ON") - Listings and Approvals Listings and approvals below apply to the FST-951 Series detectors. In some cases, certain modules may not be listed by certain ' approval agencies, or listing may be in process. Consult factory for latest listing status. • ULIULC Listing:S747 • FM Approved • CSFM:7270-0028:0502 ISO ta61MalM a NANeA I= QUALITY SYSTEMS This document is not intended to be used for installation purposes. We by to keep our product information up-to-date and accurate. We cannot cover all speck applications or anticipate all requirements. WI specifications are subject to change Without mice. NOTIFIER r as scar and NUnFIERo are 'larks of Honeyee /�� 12 Clintonville Road Iniematiosal,Inc V N OT I F I ER ' NOrthford,CT 06472 v2C19 Dy Honeywell Inlemationa Inc Al Wits resery o.Unauthori eo 203.484.7161 use oftels document is strictly prnhibted. �y Honeywell www.notifier.com Country of origin:Mexico ® NOTIFIER k by Honeywell DNR(A) and DNRW Intelligent Photoelectric Duct Detectors The Notifier DNR(A) intelligent non-relay photoelectric duct smoke ---- detector and DNRW watertight non-relay photoelectric duct smoke ; . .N$ I.> - _ _� detector feature a pivoting housing that fits both square and rectan- «jd gular footprints capable of mounting to a round or rectangular duct. I_ ; The DNRW duct smoke detector,with its NEMA-4 rating, is listed as t` I 41 a watertight,UV resistant enclosure providing protection against fall- \ e'er. /'• )1'—.; ing dirt, rain, and windblown dust, splashing and hose directed ;" I.4`�/ water, allowing operators to use the detector in the most extreme s environments. `\ J These units sense smoke in the most challenging conditions, oper- ating in airflow speeds of 100 to 4,000 feet per minute(0.5—20.32 Accessories m/s), temperatures of-4°F— 158°F (-20°C—70°C), and a humidity Notifier provides system flexibility with a variety of accessories, range of 0—95 percent(non condensing.) including two remote test stations and different means of visible and An improved cover design isolates the sensor head,which allows for audible system annunciation.As with our duct smoke detectors, all ease of maintenance.A cover tamper feature indicates a trouble sig- duct smoke detectors accessories are UL listed. nal for a removed or improperly installed sensor cover.The housing DNR(W)housings with a date code of 0013 or higher do not require provides a 3/4-inch conduit knockout and ample space to facilitate external 24VDC for remote test applications when used with a easy wiring and mounting of a relay module. remote-test-capable detector. The Notifier DNR(A) duct smoke detectors can be customized to meet local codes and specifications without additional wiring and are ACCESSORY CURRENT LOADS AT 24 VDC compatible with all previous models, including remote test accesso- Device Standby Alarm ries. RA100Z OmA 12mA Max ' Features RTS1511RTS151KEY OmA 12mAMax - • Photoelectric, integrated low-flow technology • • Air velocity rating from 100 ft/min—4,000 ft/min (0.5 m/s—20.32 Agency Listings and Approvals m/s) • Versatile mounting options:square or rectangular configuration Consult product manual for lists of compatible UL-Listed devices. In some cases,certain modules may not be listed by certain approval • Broad ranges for operating temperature (-4°F — 158°F, -20°C — agencies,or listing may be in process.Consult factory for latest list- 70°C)and humidity(0%—95%non-condensing) ing status. • Patented sampling tube installs from front or back of the detector • UL:5635,S3705 with no tools required • ULC:S635 • Cover tamper signal • • Increased wiring space with a newly added 3/4"conduit knockout CSFM:3240-1653:0209 • • Available space within housing to accommodate mounting of a FM approved relay module Product Line Information • Easily accessible code wheels on sensor head(sold separately) • Clear cover for convenient visual inspection NOTE:A suffix indicates ULC listed model. • Remote testing capability DNR(A): Intelligent non-relay photoelectric low flow smoke detector • Requires corn line power only housing. Requires photoelectric smoke detector(sold separately). • Accommodates an addressable relay module, sold separately, DNRW: Watertight intelligent non-relay photoelectric low flow duct (FRM-1)for applications requiring a Form-C relay smoke detector housing. Requires photoelectric smoke detector (sold separately).NEMA-4 rated. Specifications FSP-951R(A)-IV: Remote test capable addressable low-profile pho- toelectric smoke detector; ivory; supports CLIP and FlashScan® Size:(Rectangle)14.38 in(37 cm)Length;5 in(12.7 cm)Width,2.5 protocols in(6.6 cm)Depth FSP-951R(A): Remote test capable addressable low-profile photo- Size:(Square)7.75 in(19.7 cm)Length;9 in(22.9 cm)Width;2.5 in electric smoke detector;white;supports FlashScan protocol only (6.35 cm)Depth FSP-951(A)-IV:Addressable low-profile photoelectric smoke detec- Weight: 1.6 lb(0.73 kg) tor; ivory;supports CLIP and FlashScan protocols Operating Temperature Range:-4°F—158°F(-20°C—70°C) FSP-951R(A): Addressable low-profile photoelectric smoke detec- Storage Temperature Range: -22°F—158°F(-30°C—70°C) tor;white;supports FlashScan protocol only ' Operating Humidity Range: 0%—95% relative humidity(non-con- DCOIL: Remote test coil. Required for older DNR(W)duct detector densing) housing Air Duct Velocity: 100—4,000 ft/min (0.5—20.32 m/s) DUCTCOV: Retrofit DNR cover for manufactured prior to April 2014 DN-60429:C2•11/7/2019—Page 1 of 2 - DUCTCOVW: Retrofit DNRW cover for manufactured prior to April Important Notes 2014 • DNR(W) duct detector housings with a date code of 0013 or DST1(A): Metal sampling tube duct width up to 1 ft(0.3m) higher do not require a DCOIL or auxiliary 24 VDC for remote test DST1.5(A): Metal sampling tube duct widths up to 1 ft—2 ft (0.3— applications when used with a remote test capable detector. 0.6 m) • DNR(W)duct detector housings with a date code of 0012 or ear- DST3(A): Metal sampling tube duct widths up to 2 ft—4 ft(0.6—1.2 tier require a DCOIL and auxiliary 24 VDC power for remote test m) applications. DST5(A): Metal sampling tube duct widths up to 4 ft-8 ft(1.2—2.4 m) DST10(A): Metal sampling tube duct widths up to 8 ft— 12 ft(2.4- -3.7 m) DH4000E-1:Weatherproof enclosure ETX: Metal exhaust tube duct,width 1 ft(0.3 m) M02-04-00:Test magnet P48-21-00: End cap for metal sampling tubes RA100Z(A): Remote annunciator alarm LED RTS151(A): Remote test station RTS151KEY(A): Remote test station with key lock ISO• • MIMINGEwwracn.c QUALITY SYSTEMS This document is not intended to he used for installation purposes. We try to keep our product information up-to-date and accurate. We cannot cover all specific applicavons or anticipate htl requirements. MI specifications are subject to change without notice • _ NOTIFIER 12 Clintonville Road No avis ft asn r a Fug.sieFd trademark of Honeywell linter- national Inc. NOT 1 F 1 E Northford,CT 06472 FQ019 by Honeywell Intemaronal Inc All rights renamed Ureafnuneec • 203.484.7161 use of this document is stncoy prohibited. Honeywellwww.notifier.com counts of origin:Mexico by DN-7015:A2•k-155 Multi-Voltage N OT I F I E R� Conventional Relays CiD by Honeywell Miscellaneous General '` s Notifier's multi-voltage conventional relays are used for high- current switching applications such as fan and damper aysem- ° bly control, door control, air handling unit controls, and other •- '. Lf types of system interfacing. :• ' err, The R-10T(A)/20T(A) and R-14T(A)/R-24T(A) models are multi-voltage relays with terminal strip field wiring connections, + _ mounting track and hardware. The R-10T(A) is a single FORM-C (SPDT) relay with a red activation LED, and the ---'' R-14T(A)is a 4-gang 1 FORM-C(SPDT) relay with 4 red acti- vation LEDs. The R-20T(A) is a single 2 FORM-C (DPDT) relay with red activation LED, and the R-24T(A) is a 4-gang 2 Multi-Voltage Conventional Relays FORM-C(DPDT)relay with 4 red activation LEDs. The R-10E(A)/R-20E(A)and R-14E(A)/R-24E(A)are similar to R-10E(A)/R-14E(A)/R-20E(A)/R-24E(A) the T series track mount relays, but they are mounted into a Operating Voltage Range: 18-35 VDC,. 18-35 VAC, 115 steel enclosure. The enclosure has a removable front cover VAC,230 VAC. that provides easy access and a LED viewing hole on the top of the cover. Operating Current: 23 mA DC max. © 24 V,59 mA PR-1(A)/PR-2(A)/PR-3(A) are epoxy encapsulated multi-volt- @ 24 VAC,150mA @ 120 VAC, age relays.They are single pole double throw relays that use a 180 mA 240 VAC[R-10E(A)/ red LED as a visible indication of relay coil energization. PR-3 R-14E(A)]. is identical to PR-2 except it has an extra pair of wires for -40 mA DC max. @ 24 VDC, redundant power input. 24 VAC, 115 VAC,230 VAC(R- Model EOLR-1(A) is an epoxy encapsulated single pole single 20E/R-24E). throw, normally open relay that can be used as an end of line Humidity Range: 10%to 93%(non-condensing). device in fire alarm systems,e.g.to supervise power supplies. Dimensions: R-10E(A)/R-20E(A): 5.1"L x Specifications 3.75°w x 2.5"H. R-14E(A)/R-24E(A): 11"L x R-10T(A)✓R-14T(A)/R-20T(A)/R-24(A)T 5.3"W x 2.5"H. Operating Voltage Range: 18-35 VDC, 18-35 VAC, 115 Operating Temperature: -40° F to 158° F(-40° C to 70° VAC,230 VAC. C). Operating Current: 23 mA @ 24 VDC , 59 mA © Contact Ratings: 24 VDC:7 A with UR=5mS. 24 VAC,150 mA @ 120 VAC, 120 VAC: 10 A. 180 mA @ 240 VAC[R-10T(A)/ R-14T(A)]. 120 VAC: 1/6 HP. 40 mA DC max. @ 24 VDC,24 230 VAC:7 A. VAC, 92 mA @ 24 VAC, 220 mA © 120 VAC, 260 mA @ PR-1(A) 240 VAC[R-20T(A)/R-24T(A)] Operating Voltage Range: 18-35 VDC, 18-35 VAC, 120 Humidity Range: 10%to 93%(non-condensing). VAC. Dimensions: R-10T(A)/ R-20T(A): 2.5"L x Operating Current: 15 mA DC max. 24 VDC,24 3.35"W x 1.2"H. VAC,12OVAC. R-14T(A)/R-24T(A): 10"L x Humidity Range: 10%to 93%RH. 3.35"W x 1.2"H. Dimensions: 0.87"H x 2.01"W x 1.42"D. Operating Temperature: 40° F to 158° F (-40°C to Operating Temperature: -40° F to 158° F (-40° C to 70° 70°C) C). Contact Ratings: 24 VDC:7A with UR=5 mS. Contact Ratings: 24 VDC:7 A with LR=5 mS. 120 VAC: 10 A. 120 VAC:7 A max.(0.35 PF). 120 VAC: 1/6 HP. 250 VAC: 10 A resistive. 230 VAC:7 A. 30 VDC: 10 A resistive. Wire Length: 8"minimum. DN-7015:A2•7/30/13—Page 1 of 4 PR-2(A)/PR-3(A) Agency Listings and Approvals Operating Voltage Range: 10 to 40 VDC. In some cases, certain modules may not be listed by certain Operating Current: 30 mA DC max. approval agencies, or listing may be in process. Consult fac- tory for latest listing status. Humidity Range: 10%to 93% RH. • UUULC Listed:S3705 Dimensions: 0.91"H x 1.65"W x 1.22"D. • ULC Listed:CS669 Operating Temperature: -40° F to 158° F (-40° C to 70° • MEA:419-04-E C). • CSFM:7300-1653:173 Contact Ratings: 120 VAC: 10 A(resistive load). 120 VAC:7 A max.(0.35 PF). PRODUCT LINE INFORMATION 250 VAC: 10 A max. (resistive NOTE:A"suffix indicates ULC listed model. load). PR-1(A): Epoxy encapsulated single pull double throw 30 VDC: 10 A max. (resistive (SPDT) relay. It also uses a red LED as a visible indication of load). relay coil energization with pigtails. Wire Length: 8"minimum. PR-2(A): Epoxy encapsulated single pull double throw (SPDT)activated by 10 to 40 VDC. It uses a red LED as a vis- EOLR-1(A) ible indication of relay coil energization with pigtails. Operating Voltage Range: 9 to 40 VDC. PR-3(A): Epxoy encapsulated single pull double throw (SPDT) activated by 10 to 40 VDC. It contains an additional Operating Current: 20 mA DC max. black and red wire for redundant power input with pigtails. Humidity Range: 10%to 93%RH. EOLR-1(A): Epoxy encapsulated single pull single throw Operating Temperature: -22° F to 140° F (-30°C to 60° (SPST) normally open relay that is activated by 9 to 40 VDC. C) This relay can be used as an end of line device in fire alarm systems,e.g.,to supervise power supplies. Contact Ratings: 120 VAC: 0.5 A max. (resistive R-10T(A): Single(SPDT) relay with a red activation LED. load). 30 VDC: 3 A max. (resistive R-14T(A): 4-gang(SPDT)relay with 4 red activation LEDs. load). R-20T(A): Single(DPDT)relay with a red activation LED. Wire Length: 8"minimum. R-24T(A): 4-gang(DPDT) relay with 4 red activation LEDs. The R-10E(A)/R-20E(A)and R-14E(A)/R-24E(A)are similar to the T series track mount relays, but they are mounted into a steel enclosure. The enclosure has a removable front cover that provides easy access and a LED viewing hole on the top of the cover. R-10E(A): Single (SPDT) relay mounted into a steel enclo- sure, 1 red activation LED. R-14E(A): 4-gang (SPDT) relay mounted into a steel enclo- sure,4 red activation LEDs. R-20E(A): Single (DPDT) relay mounted into a steel enclo- sure, 1 red activation LED. R-24E(A): 4-gang (DPDT) relay mounted into a steel enclo- sure,4 red activation LEDs. Page 2 of 4—DN-7015:A2•7/30/13 o s PR-1(A) -_. PR-2(A) PR-3(A) EOLR-1(A) • titk fit. R-10T(A) R-14T(A) aTT^.�.= O0 aroiZ^YRr R'i. 4 Qa R-20E(A) & R-24E(A) R-10E(A) & R-14E(A) Enclosures Enclosures DN-7015:A2•7/30/13—Page 3 of 4 ©2013 by Honeywell International Inc.All rights reserved.Unauthorized use of this document is strictly prohibited. ISO 9001 This document is not intended to be used for installation purposes. 1 We try to keep our product information up-to-date and accurate. G E R T F E We cannot cover all specific applications or anticipate all requirements. ENGINEERING 8 MANUFACTURING All specifications are subject to change without notice. QUALITY SYSTEMS For more information,contact Notifier.Phone:(203)4847161,FAX:(203)484-7118. www.notifier.com Page 4 of 4—ON-7015:A2.7/30/13 DN-60918:B Indoor Selectable-Output Horns, Strobes, and Horn @ N OT I F I E R Strobes for Wall Applications by Honeywell Audio/Visual Devices General The L-Series offers the most versatile and easy-to-use line of horns,strobes,and horn strobes in the industry with lower cur- ' rent draws and modern aesthetics. With white and red plastic F F housings, standard and small footprint devices, and plain, I I FIRE-printed devices, L-Series can meet virtually any applica- R 1 , e A R tion requirement. •` .; `-,. , E The L-Series product line of wall-mount horns, strobes, and ''a E' horn strobes include a variety of features that increase their application versatility while simplifying installation. All devices feature plug-in designs with minimal intrusion into the back P2RL box,making installations fast and foolproof while virtually elim- inating costly and time-consuming ground faults. To further simplify installation and protect devices from con- struction damage, L-Series utilizes a universal mounting plate i,i,.,y for all standard and compact models with an onboard shorting F F spring,so installers can test wiring continuity before the device is installed. I I Installers can also easily adapt devices to a suit a wide range R �; I R of application requirements using field-selectable candela set- E 1 i E tings, automatic selection of 12- or 24-volt operation, and a i - rotary switch for horn tones with two volume selections. - Features P2GWL SGWL - • Updated modern aesthetics. • Small profile devices for Horns and Horn Strobes. • Plug-in design with minimal intrusion into the back box. • Tamper-resistant construction. ,�0, • Automatic selection of 12-or 24-volt operation at 15 and 30 'i:i::' candela. • Field-selectable candela settings on wall units: 15, 30, 75, 95, 110, 135,and 185. • Horn rated at BB+dBA at 16 volts. • Rotary switch for horn tone and two volume selections. ' • Universal mounting plate for all standard and all compact HWL wall units. • Mounting plate shorting spring checks wiring continuity. before device installation. • Electrically Compatible with legacy SpectrAlert® and 12 or 24 volts.When used with the Sync•Circuit Module, 12- SpectrAlert Advance devices. volt-rated notification appliance circuit outputs shall operate Compatible with MDL3 sync module. between 8.5 and 17.5 volts; 24-volt-rated c appliance circuit ue. • outputs shall operate between 16.5 and 33 volts. Indoor • Listed for wall mounting only. L-Series products shall operate between 32 and 120 degrees Fahrenheit from a regulated DC or full-wave rectified unaltered Architectural/Engineering Specifications power supply.Strobes and horn strobes shall have field-select- able candela settings including 15, 30, 75, 95, 110, 135, and General: L-Series standard horns, strobes, and horn strobes 185. shall mount to a standard 2" x 4" x 17/8" back box, 4" x 4" x 11/2" back box,4"octagon back box,or double-gang back box. Strobe. The strobe shall be a L-Series Model listed to UL L-Series compact products shall mount to a single-gang 2" x 1971 and shall be approved for fire protective service. The 4" x 17/8" back box. A universal mounting plate shall be used strobe shall be wired as a primary-signaling notification appli- for mounting ceiling and wall products for all standard-size ance and comply with the Americans with Disabilities Act models and a separate universal mounting plate shall be used requirements for visible signaling appliances, flashing at 1 Hz for mounting compact wall models. The notification appliance over the strobe's entire operating voltage range. The strobe circuit wiring shall terminate at the universal mounting plate. light shall consist of a xenon flash tube and associated lens/ • • Also, L-Series products, when used with the Sync•CircuitTM reflector system. Module accessory, shall be powered from a non-coded notifi- cation appliance circuit output and shall operate on a nominal DN-60918:B•5/19/17—Page 1 of 4 - Horn Strobe Combination. The horn strobe shall be a L-Series Drawings L-Series Model listed to UL 1971 and UL 464 and shall be approved for fire protective service. The horn strobe shall be Compact Horn wired as a primary-signaling notification appliance and comply with the Americans with Disabilities Act requirements for visi- 3.as 125 ble signaling appliances, flashing at 1 Hz over the strobe's entire operating voltage range.The strobe light shall consist of _ a xenon flash tube and associated lens/reflector system.The �i - horn shall have two audibility options and an option to switch '" ,- ' "•�' between a temporal three pattern and a non-temporal(contin- I or;00000 uous) pattern. These options are set by a multiple position �oeo°000a0' switch• . The horn on horn strobe models shall operate on a 5.27 o0o0o0e0r0o coded or non-coded power supply. 18488 061•e" IN Synchronization Module.The module shall be a Sync•Circuit 00e0e000000 1 model MDL3 listed to UL 464 and shall be approved for fire ` . protective service. The module shall synchronize SpectrAlert , oJ strobes at 1 Hz and horns at temporal three.Also,while oper- ating the strobes, the module shall silence the horns on horn strobe models over a single pair of wires. The module shall mount to a 411/6" x 411/16" x 21/8" back box. The module shall Compact Combo also control two Style Y(class B)circuits or one Style Z(class 1.91 A)circuit.The module shall synchronize multiple zones. Daisy 3.46 —® chaining two or more synchronization modules together will - = 1.2E synchronize all the zones they control. The module shall not operate on a coded power supply. "'"11, 1 101 PHYSICAL/ELECTRICAL SPECIFICATIONS s • 49°CStan Operating Temperature: 32°F to 120°F (0°C to 5.27 ••,•,,• Il • Humidity Range: 10 to 93%non-condensing. i I _ 1 IIII • • Strobe Flash Rate: 1 flash per second. ek,IIIIIMI! all • Nominal Voltage: Regulated 12 DC or regulated 24 DC/ 1111 • FWR1 (full wave rectified). • Operating Voltage Range2: 8 to 17.5 V (12 V nominal) or 16 to 33 V(24 V nominal). • Operating Voltage Range:MDL3 Sync Module 8.5 to 17.5 V(12 V nominal)or 16.5 to 33 V(24 V nominal). Horn • Input Terminal Wire Gauge: 12 to 18 AWG. - 4.70 1.25 • Wall-Mount Dimensions(including lens):5.6"L x 4.7"W x 1.25"D(143 mm L x 119 mm W x 32 mm D). li (r 1: • Compact Wall-Mount Dimensions(including lens):5.26" ''L x 3.46"W x 1.93"D (133 mm L x 88 mm W x 49 mm D). ;- _ • Horn Dimensions:5.6" L x 4.7"W x 1.25" D(143 mm L x 5.67 '' ' - 119mmWx32mmD). 1•1 • Compact Horn Dimensions: 5.25" L x 3.45"W x 1.25" D �)ti;r, e (133mm L x 88mm W x 32mm D). ` ra_ 41, ( NOTE: 1. Full Wave Rectified(FWR)voltage is a non-regulated,time- varying power source that is used on some power supply and panel outputs. Combo 2. P,S, PC,and SC products will operate at 12 V nominal only = 4.70 1 for 15 cd and 30 cd. 1.91 1.25 5.67 tt_o_JP) Page 2 of 4—DN-60918:B•5/19/17 UL Current Draw Data UL MAX. HORN CURRENT DRAW(MA RMS) UL MAX.STROBE CURRENT DRAW(MA RMS) The 3.1 k thesound n the mini-son The (which stands for Electro-mechanical) is the souundd Sp of the SpectrAlert 8-17.5 Advance line which uses an algorithm that hops frequencies Volts 16-33 Volts between 2Hz and 4Hz. Candela DC DC FWR 8-17.5 15 88 43 60 Volts 16-33 Volts - 30 143 63 83 Sound Pattern dB DC DC FWR 75 N/A 107 136 Temporal High 39 44 54 95 NIA 121 155 Temporal Low 28 32 54 110 N/A 148 179 Non-Temporal High 43 47 54 135 N/A 172 209 Non-Temporal Low 29 32 54 185 N/A 222 257 3.1 KHz Temporal High 39 41 54 3.1 KHz Temporal Low 29 32 54 3.1 KHz Non-Temporal High 42 43 54 3.1 KHz Non-Temporal Low 28 29 54 Coded High 43 47 54 3.1 KHz Coded High 42 43 54 UL MAX. CURRENT DRAW(MA RMS),2-WIRE HORN STROBE, CANDELA RANGE(15-115 CD) The 3.1k is the sound of the mini-horns. The EM(which stands for Electro-mechanical)is the sound of the SpectrAlert Advance line which uses an algorithm that hops frequencies between 2Hz and 4Hz. DC Input: 8-17.5 DC Input: FWR Input: Volts 16-33 Volts 16 FWR - 15 30 15 30 75 95 110 135 185 15 30 75 95 110 135 185 cd cd cd cd cd cd cd cd cd cd cd cd cd cd cd cd Temporal High 98 158 54 74 121 142 162 196 245 83 107 156 177 198 234 287 Temporal Low 93 154 44 65 111 133 157 184 235 68 91 145 165 185 223 271 Non-Temporal High 106 166 73 94 139 160 182 211 262 111 135 185 207 230 264 316 Non-TemporalLow 93 156 51 71 119 139 162 190 239 79 104 157 175 197 235 283 3.1 K Temporal High 93 156 53 73 119 140 164 190 242 81 105 155 177 196 234 284 3.1K Temporal Low 91 154 45 66 112 133 160 185 235 68 90 145 166 186 222 276 3.1K Non-Temporal High 99 162 69 90 135 157 175 208 261 104 131 177 204 230 264 326 3.1 K Non-Temporal Low 93 156 52 72 119 138 162 192 242 77 102 156 177 199 234 291 DN-60918:B•5/19/17—Page 3 of 4 HORN TONES AND SOUND OUTPUT DATA: HORN Product Line Information AND HORN STROBE OUTPUT(DBA) WALL HORN STROBES The 3.1k is the sound of the mini-horns. The EM (which P2WL(A)(-E)(-F), P2RL(A)(-E)(-F). 2-Wire, Horn Strobe stands for Electro-mechanical) is the sound of the SpectrAlert (White, Red). Advance line which uses an algorithm that hops frequencies P2GWL(A)(-E)(-F), P2GRL(A)(-E)(-F).2-Wire, Compact Horn between 2Hz and 4Hz. Strobe(White, Red). In the coded positions, temporal coding must be provided by the NAC. If the NAC voltage is held constant,the horn output P2WL(A)-P, P2RL(A)-P. 2-Wire, Horn Strobe, Plain (White, will remain constantly on. Red). B 17 5 P2WL-SP, P2RL-SP. 2-Wire, Horn Strobe, FUEGO (White, • Volts 16-33 Volts Red). Pos. Sound Pattern dB DC DC FWR WALL STROBES 1 Temporal High 84 89 89 SWL(A)(-E)(-F),SRL(A)(-E)(-F).Strobe, Red(White, Red). 2 Temporal Low 75 83 83 SGWL(A)(-E)(-F), SGRL(A)(-E)(-F). Compact Strobe (White, Red). 3 Non-Temporal High 85 90 90 SWL(A)-P,SRL(A)-P.Strobe, Plain (White, Red). 4 Non-Temporal Low 76 84 84 SRL-SP.Strobe, FUEGO(Red). 5 3.1 KHz Temporal High 83 88 88 SWL-CLR-ALERT.Strobe, ALERT(White). 6 3.1 KHz Temporal Low 76 82 82 SWL-ALERT.Strobe,Wall,Amber Lens,ALERT(White). 7 3.1 KHz Non-Temporal High 84 89 89 8 3.1 KHz Non-Temporal Low 77 83 83 HORNS HWL(A),HRL(A).Horn(White, Red). 9t Coded High 85 90 90 HGWL(A),HGRL(A).Compact Horn (White, Red). 10t 3.1 KHz Coded High 84 89 89 ACCESSORIES tSettings 9 and 10 are not available on the 2-wire horn strobes. TR-2W,TR-2.Universal Wall Trim Ring(White, Red). Agency Listings and Approvals SBBWL,SBBRL.Wall Surface Mount Back Box(While, Red). The listings and approvals below apply to L-series devices. In SBBGWL, SBBGRL. Compact Wall Surface Mount Back Box some cases,certain modules or applications may not be listed (White, Red). by certain approval agencies, or listing may be in process. NOTE: A"suffix indicates ULC-Listed model. ULC-listed devices Consult factory for latest listing status. include required French labeling. See Agency Listings for listing details. • UUULC-Listed —S4011 Wall Horn Strobes NOTE: "A"suffix indicates ULC-listed models, ULC models have FIRE/FEU marking on cover. -S5512 Wall Strobes NOTE: ULC-listed models add"-E"suffix for English only"FIRE" -S5512 Wall Horns marking on cover. 1 -S5512 Strobe-only ALERT devices NOTE: ULC-listed models add "-F"suffix for French only "FEU" • FM Approved(All except ALERT models) marking on cover. • CSFM Listed:7135-1653:0503(Wall Horns and Wall Horn Strobes), 7125-1653:0504(Wall Strobes) NOTIFIER® and SpectrAlert® are registered trademarks and Sync•Circuitm is a trademark of Honeywell International Inc. ©2017 by Honeywell International Inc.All rights reserved.Unauthorized use of this document is strictly prohibited. This document is not intended to be used for installation purposes. ISO 9001 We try to keep our product information up-to-date and accurate. . G E RT F E O We cannot cover all specific applications or anticipate all requirements. MAKE IPA 1 MIMIR11UtA All specifications are subject to change without notice. QUALITY SYSTEMS For more information,contact Notifier.Phone:(203)484-7161,FAX:(203)484-7118. www.notifier.com Page 4 of 4—DN-60918:B•5/19/17 DN-60938:B Indoor Selectable-Output Strobes and Horn Strobes for ® NOT 1 F 1 E R` Ceiling Applications by Honeywell Audio/Visual Devices General System Sensor L-Series audible visible notification products are rich with features guaranteed to cut installation times and maximize profits with lower current draw and modern aesthet- aics. { . .. ti The System Sensor L-Series offers the most versatile 1 and easy-to-use line of horns,strobes,and horn strobes in the .� industry with lower current draws and modern aesthetics.With q „• white and red plastic housings, wall and ceiling mounting air options, System Sensor L-Series can meet virtually any appli- /A cation requirement. The entire L-Series product line of ceiling-mount strobes and SCRL PC2WL horn strobes include a variety of features that increase their application versatility while simplifying installation. All devices Architect/Engineer Specifications feature a plug-in design with minimal intrusion into the back box,making installations fast and foolproof while virtually elim- GENERAL inating costly and time-consuming ground faults. L-Series ceiling-mount strobes and horn strobes shall mount To further simplify installation,the L-Series utilizes a universal to a standard 4 x 4 x 1 Y2-inch back box, 4-inch octagon back mounting plate so installers can mount them to a wide array of box, or double-gang back box. Two-wire products shall also back boxes. With an onboard shorting spring, installers can mount to a single-gang 2 x 4 x 17/8 inch back box.A universal test wiring continuity before the device is installed. mounting plate shall be used for mounting ceiling and wall Installers can also easily adapt devices to a suit a wide range products. The notification appliance circuit wiring shall termi- of application requirements using field-selectable candela set- nate at the universal mounting plate. Also, L-Series products, tings, automatic selection of 12- or 24-volt operation, and a when used with the Sync•CircuitT Module accessory,shall be rotary switch for horn tones with two volume selections. powered from a non-coded notification appliance circuit output and shall operate on a nominal 12 or 24 volts.When used with Features the Sync•Circuit Module, 12-volt-rated notification appliance circuit outputs shall operate between 8.5 and 17.5 volts; 24- • Plug-in design with minimal intrusion into the back box volt-rated notification appliance circuit outputs shall operate • Tamper-resistant construction between 16.5 and 33 volts. Indoor L-Series products shall Automatic selection of 12-or 24-volt operation operate between 32 and 120 degrees Fahrenheit from a regu- • A At 15 and 30 candela lated DC or full-wave rectified unfiltered power supply. Ceiling strobes and horn strobes shall have field-selectable candela • Field-selectable candela settings on ceiling units: settings including 15, 30,75,95, 115, 150,and 177. 15,30,75,95, 115, 150,and 177 • Horn rated at 88+dBA at 16 volts STROBE • Rotary switch for horn tone and two volume selections The strobe shall be a System Sensor L-Series Model Universal mounting plate for ceiling units listed to UL 1971 and shall be approved for fire protective ser- • vice.The strobe shall be wired as a primary-signaling notifica- • Mounting plate shorting spring feature checks wiring conti- tion appliance and comply with the Americans with Disabilities nuity before device installation Act requirements for visible signaling appliances,flashing at 1 • Electrically compatible with legacy SpectrAlert and Hz over the strobe's entire operating voltage range.The strobe SpectrAlert Advance devices light shall consist of a xenon flash tube and associated lens/ • Compatible with MDL3 sync module reflector system. • Listed for ceiling mounting only HORN STROBE COMBINATION The horn strobe shall be a System Sensor L-Series Model listed to UL 1971 and UL 464 and shall be approved for fire protective service.The horn strobe shall be wired as a primary-signaling notification appliance and comply with the Americans with Disabilities Act requirements for visible signal- ing appliances,flashing at 1 Hz over the strobe's entire operat- ing voltage range. The strobe light shall consist of a xenon flash tube and associated lens/reflector system.The horn shall have two audibility options and an option to switch between a temporal three pattern and a non-temporal (continuous) pat- tern.These options are set by a multiple position switch.The horn on horn strobe models shall operate on a coded or non- coded power supply. DN-60938:B•5/15/17—Page 1 of 4 SYNCHRONIZATION MODULE The module shall be a System Sensor Sync•Circuit model MDL3 listed to UL 464 and shall be approved for fire protective service. The module shall synchronize L-Series strobes at 1 Hz and horns at temporal three. Also, while operating the strobes, the module shall silence the horns on horn strobe models over a single pair of wires.The module shall mount to a 411/16 x 411/16 x 21/8 inch back box.The module shall also con- ' trol two Style Y (class B) circuits or one Style Z(class A) cir- cuit. The module shall synchronize multiple zones. Daisy chaining two or more synchronization modules together will synchronize all the zones they control. The module shall not operate on a coded power supply. PHYSICAL/ELECTRICAL SPECIFICATIONS • Standard Operating Temperature: 32°F to 120°F (0°C to 49°C) • Humidity Range: 10 to 93%non-condensing • Strobe Flash Rate: 1 flash per second • Nominal Voltage: Regulated 12VDC or regulated 24DC/ FWR1 • Operating Voltage Range2: 8 to 17.5V (12V nominal) or 16 to 33V(24V nominal) • Operating Voltage Range with MLD3: 8.5 to 17.5V (12V nominal)or 16.5 to 33V(24V nominal) • Input terminal wire gauge: 12 to 18 AWG • Ceiling-Mount Dimensions(Including lens): 6.8" diame- ter 2.5"high(173 mm diameter 64 mm high) • Ceiling-Mount Surface Mount Back Box Skirt Dimen- sions (SBBCR, SBBCW): 6.9" diameter x 3.4" high (175 mm diameter x 86 mm high) Notes: 1. Full Wave Rectified(FWR)voltage is a non-filtered,time varying power source that is used on some power supply and panel outputs. 2. P, S, PC, and SC products will operate at 12 V nominal only for 15 and 30 cd. UL Current Draw Data UL MAX.STROBE CURRENT DRAW(MA RMS) 8-17.5 Volts 16-33 Volts Candela DC DC FWR 15 87 41 60 30 153 63 86 75 N/A 111 142 95 N/A 134 164 115 N/A 158 191 150 N/A 189 228 177 N/A 226 264 *This data represents coding at 3 chimes per second. Actual current draw will vary depending upon coding selected. Page 2 of 4—DN-60938:B•5/15/17 UL MAX. CHIME/STROBE CURRENT DRAW(MA RMS),2-WIRE HORN STROBE The 3.1k is the sound of the mini-horns. The EM(which stands for Electro-mechanical) is the sound of the SpectrAlert Advance line which uses an algorithm that hops frequencies between 2Hz and 4Hz. 8 VDC 16 VDC Candela 15 30 15 30 75 95 115 150 177 Temporal High 103 167 71 90 143 165 187 217 254 Temporal Low 96 165 54 71 137 161 185 211 249 Non-Temporal High 106 173 71 90 141 165 187 230 273 Non-Temporal Low 95 166 54 71 124 161 170 216 258 3.1K Temporal High 111 164 69 94 147 163 184 229 257 3.1K Temporal Low 103 163 54 88 143 155 185 212 252 3.1K Non-Temporal High 111 172 69 94 144 164 202 229 271 3.1K Non-Temporal Low 103 169 54 88 131 155 187 217 259 16VFWR Candela 15 30 75 95 115 150 177 Temporal High 107 135 179 198 223 254 286 Temporal Low 78 101 151 172 199 229 262 Non-Temporal High 107 135 179 198 223 254 286 Non-Temporal Low 78 101 151 172 199 229 262 3.1K Temporal High 108 135 179 200 225 255 289 3.1K Temporal Low 79 101 150 171 196 229 260 3.1K Non-Temporal High 108 135 179 200 225 255 289 3.1K Non-Temporal Low 79 101 150 171 196 229 260 Horn Strobe Tones and Sound Output Data HORN AND HORN STROBE OUTPUT(DBA) 8-17.5 16-33 Volts Volts Switch Position Sound Pattern dB DC DC FWR 1 Temporal High 84 89 89 2 Temporal Low 75 83 83 3 Non-Temporal High 85 90 90 4 Non-Temporal Low 76 84 84 5 3.1 KHz Temporal High 83 88 88 6 3.1 KHz Temporal Low 76 82 82 7 3.1 KHz Non-Temporal High 84 89 89 8 3.1 KHz Non-Temporal Low 77 83 83 DN-60938:B•5/15/17—Page 3 of 4 Product Drawings: L-Series Dimensions 2.47 1.37 _ �....._.-,N F 6.92 2.50 6.83 I I \ C 8 0 77/11/ ._--- Horn Strobes (Ceiling) Surface Mount Back Box (Ceiling) Agency Listings and Approvals The listings and approvals below apply to L-series devices. In some cases,certain modules or applications may not be listed by certain approval agencies, or listing may be in process. Consult factory for latest listing status. • UL1ULC-Listed —S4011 Ceiling horn strobes —S5512 Ceiling strobes —S5512 Strobe-only ALERT devices • FM Approved(All except ALERT models) • CSFM Listed: 7135-1653:0503 (Ceiling Horns and Ceiling Horn Strobes),7125-1653:0504(Ceiling Strobes) Product Line Information CEILING HORN STROBES PC2WL(A) (-E)(-F), PC2RL(A) (-E)(-F). 2-Wire, Horn Strobe (White, Red). CEILING STROBES SCWL(A)(-E)(-F),SCRL(A)(-E)(-F).Strobe(White, Red). SCWL-CLR-ALERT.Strobe,ALERT(White). ACCESSORIES TR-2W,TR-2.Universal Ceiling Trim Ring(White, Red). SBBCWL, SBBCRL.Ceiling Surface Mount Back Box(White, Red). NOTE: 'A"suffix indicates ULC-Listed model. ULC-listed devices include required French labeling. See Agency Listings for listing details. NOTE: "A"suffix indicates ULC-listed models, ULC models have FIRE/FEU marking on cover. NOTE: ULC-listed models add"-E"suffix for English only "FIRE' NOTIFIER® and SpectrAlert® are registered trademarks and marking on cover. Sync•Circuit*^'is a trademark of Honeywell International Inc. 02017 by Honeywell International Inc.All rights reserved.Unauthorized use NOTE: ULC-listed models add "-F"suffix for French only "FEU" of this document is strictly prohibited. marking on cover. ISO 9001 This document is not intended to be used for installation purposes. We try to keep our product information up-to-date and accurate. C E R T F r E O We cannot cover all specific applications or anticipate all requirements. BMIMHIM MNMIMS= All specifications are subject to change without notice. OULITY SYSTEMS For more information,contact Notifier.Phone:(203)484-7161,FAX:(203)484-7118. www.notifier.com Page 4 of 4—DN-60938:B•5/15/17 DN-60942:B Indoor Selectable-Output Speaker Strobes and Dual (0) N OT I F I E R Voltage Evacuation Speakers b Honeywell for Wall Applications yone y Audio/Visual Devices General System Sensor L-Series selectable output speaker strobes and dual-voltage evacuation speakers can reduce ground �,'�!+!�l+.'r'.�'•+!r!�!+! ,' faults and enable faster installation with lower current draw and modern aesthetics. �y' ',r,r,'; � � � fir � rrlir 1 The System Sensor L-Series of speakers and speaker strobes 1� reduce costly ground faults using a plug-in design and univer- sal mounting plate that allow the installer to pre-wire mounting � ;; plates, dress the wires, and confirm wiring continuity before ' ' " plugging in the speakers. In addition,a protective plastic cover prevents nicked wires by covering exposed speaker compo- _' nents. _ These devices also enable faster installations by providing instant feedback to ensure that wiring is properly connected, F j rotary switches to select voltage and power settings, and 7 field-selectable candela settings for wall speaker strobes. The low total harmonic distortion of the speaker offers high SPSWL fidelity sound output while still offering high volume sound out- put for use in high ambient noise applications. System Sensor L-Series makes installation easy. • Attach a universal mounting plate to a 4 x 4 x 2'/8 inch back box. Flush-mount applications do not require an extension ring. • Connect the notification appliance circuit or speaker wiring SPSRL to the terminals on the mounting plate. • Attach the speaker or speaker strobe to the mounting plate Architectural/Engineering Specifications by inserting the product tabs into the mounting plate grooves. Hinge the device into position to lock the product GENERAL pins into the mounting plate terminals.The device will tem- L-Series speaker and speaker strobes shall mount to a 4 x 4 x porarily hold in place with a catch until it is secured with a 21/3 inch back box.A universal mounting plate shall be used for captured mounting screw. mounting ceiling and wall products.The notification appliance circuit and amplifier wiring shall terminate at the universal Features mounting plate. Also, L-Series speaker strobes, when used with the Sync•CircuitTM Module accessory, shall be powered • Plug-in design and protective cover reduce ground faults. from a non-coded notification appliance circuit output and shall • Universal mounting plate with an onboard shorting spring operate on a nominal 12 or 24 volts. When used with the tests wiring continuity before installation. Sync•Circuit Module, 12-volt rated notification appliance circuit • No extension ring required. outputs shall operate between 8.5 and 17.5 volts;24-volt rated • Field selectable candela settings on wall units: notification appliance circuit outputs shall operate between 15,30,75,95, 110, 135, 185. 16.5 and 33 volts. Indoor L-Series products shall operate between 32°F and 120°F from a regulated DC, or full-wave • Automatic selection of 12-or 24-volt operation at 15 and 30 p rectified, unfiltered power supply.Wall-mount speaker strobes candela. shall have field-selectable candela settings including 15, 30, • Rotary switch simplifies field selection of speaker voltage 75,95, 110, 135, 185. (25 and 70.7 Vrms) and power settings CAI, 1/2, 1 and 2 watts). SPEAKER • Speakers offer high fidelity and high volume sound output. The speaker shall be a System Sensor L-Series model dual-voltage transformer speaker capable of operat- • UL 464(520 Hz) listed and complies with NFPA 72 require- ments for low frequency with compatible fire alarm control ing at 25.0 or 70.7 nominal Vrms. It should be listed to UL panel. 1480 and shall be approved for fire protective service. The Compatible with System Sensor synchronization protocol. speaker shall have a frequency range of 400 to 4,000 Hz and • shall have an operating temperature between 32°F and 120°F. • Electrical compatibility with existing SpectrAlert and The speaker shall have power taps and voltage that are SpectrAlert Advance products. selected by rotary switches. • Tamper-resistant construction. SPEAKER STROBE COMBINATION • Updated modern aesthetics. The speaker strobe shall be a System Sensor L-Series model listed to UL1480 and UL 1971 and be approved for fire protective signaling systems. The speaker shall be DN-60942:B•4/20/17—Page 1 of 4 capable of operating at 25.0 or 70.7 nominal Vrms selected via UL Current Draw Data rotary switch, and shall have a frequency range of 400 to 4,000 Hz.The speaker shall have power taps that are selected UL MAX.STROBE CURRENT DRAW(MA RMS) by rotary switch. The strobe shall comply with the NFPA 72 8-17.5 Volts 16-33 Volts requirements for visible signaling appliances, flashing at 1 Hz over the strobe's entire operating voltage range. The strobe Candela DC DC FWR light shall consist of a xenon flash tube and associated lens/ 15 88 43 60 reflector system. 30 143 63 83 SYNCHRONIZATION MODULE 75 N/A 107 136 The module shall be a System Sensor Sync•Circuit model 95 N/A 121 155 MDL3 listed to UL 464 and shall be approved for fire protective service.The module shall synchronize SpectrAlert strobes at 1 110 N/A 148 179 Hz.The module shall mount to a 411/16 x 411/16 x 21/8 inch back 135 N/A 172 209 box. The module shall also control two Style Y (class B) cir- cuits or one Style Z (class A) circuit. The module shall syn- 185 N/A 222 257 chronize multiple zones. Daisy chaining two or more synchronization modules together will synchronize all the SOUND OUTPUT SPEAKER STROBE zones they control.The module shall not operate on a coded power supply. 4 W 'h W 1 W 2 W PHYSICAL/ELECTRICAL SPECIFICATIONS UL Reverberant 77 80 83 86 • Standard Operating Temperature: 32°F to 120°F (0°C to (dBA @10 ft) 49°C) UL Anechoic 77 80 83 86 • Humidity Range: 10 to 93%non-condensing. (dBA @10 ft) DIMENSIONS, WALL-MOUNT SOUND OUTPUT SPEAKER • SP Speaker:6.5 in x 5 in x 2.3 in.(165 mm x 127 mm x 58 1/4y1f iyy 1W 2W mm) ernt • SP Speaker with Surface Mount Back Box:6.6 in x 5.1 in x ULdBA©100rft) ( 79 82 85 88 3.2in(168mmx130mmx82mm) • SPS Speaker/Strobe (including lens and speaker): 6.5 in x UL Anechoic 79 82 85 88 5.0 in x 2.3 in(165 mm x 127 mm x 58 mm) (dBA @10ft) • SPS Speaker/Strobe(including lens and speaker)with Sur- face Mount Back Box: 6.6 in x 5.1 in x 4.55 in. (168 mm x Agency Listings and Approvals 130 mm x 116 mm) The listings and approvals below apply to L-series devices. In ELECTRICAL/OPERATING SPECIFICATIONS: some cases,certain modules or applications may not be listed • Nominal Voltage(speakers):25 or 70.7(nominal) by certain approval agencies, or listing may be in process. • Maximum Supervisory Voltage(speakers):50 VDC Consult factory for latest listing status. • • Strobe Flash Rate: 1 flash per second UL-Listed: • Nominal Voltage (strobes): Regulated 12 VDC or regu- —S4048 Plain Speaker Strobes(Wall) lated 24 DC/FWR —S4048 Spanish-labeled Speaker Strobes(Wall) • Operating Voltage Range (includes fire alarm panels —S4048 Speaker Strobe ALERT devices. with built in sync):8 to 17.5 V(12 V nominal)or 16 to 33V • UL/ULC-Listed: (24 V nominal) —S4048 Speakers(Wall) • Operating Voltage with MDL3 Sync Module: 8.5 to 17.5 —S4048 Speaker Strobes(Wall) V(12 V nominal)or 16.5 to 33V(24 V nominal) • FM Approved(All except ALERT models) • Frequency Range:400 to 4000 Hz. 520Hz capable with compatible fire alarm control panel. • CSFM Listed:7320-1653:0505 • Power: 1/4, yz, 1,2 watts Product Line Information Note: A" suffix indicates ULC-listed models. ULC-listed devices include required French labeling. See Agency Listings for listing details. WALL MOUNT SPWL(A),SPRL(A).Speaker only(White, Red). SPSWL(A),SPSRL(A).Speaker Strobe(White, Red). SPSWL-P(A), SPSRL-P(A). Plain Speaker Strobe (White, • Red). SPSWL-ALERT.Speaker Strobe,Amber Lens,ALERT(White). - , SPSWL-CLR-ALERT. Speaker Strobe Clear Lens, ALERT (White). SPSRL-SP.Speaker Strobe, Fuego(White). Page 2 of 4—DN-60942:8.4/20/17 ACCESSORIES SBBSPW, SBBSPR. Surface Mount Back Box for Speakers RFPW,RFP.7 in x 9.5 in Retrofit Plate(White, Red). and Speaker Strobes(White, Red). TRW,TR.Wall Mount Trim Ring(White, Red). Product Drawings: Dimensions and Surface Mounting 5.00 = .97 1.63 5.00 = 2.30 = 1.63 1.39 _ r� J, x ,1 r —: , of 0 k. i HI 1111 �ill 6.50 __.1 6 50 r I i Mj ire lir E Wall-Mount Speaker Wall-Mount Speaker Strobe ®® i be _® _ AB0-11O ,e ics � a ° l ^ ao n,b g ales evili., rrl.,,ri,rfiirii ; Wall-Mount Speaker Strobe with SBBSPRL Surface Mount Back DN-60942:B•4/20/17—Page 3 of 4 MOWER® and SpectrAlert® are registered trademarks and Sync•Circuitm is a trademark of Honeywell International Inc. 02017 by Honeywell International Inc.All rights reserved.Unauthorized use of this document is strictly prohibited. ISO 9001 This document is not intended to be used for installation purposes. We try to keep our product information up-to-date and accurate. C E R T F E We cannot cover all specific applications or anticipate all requirements. • 8111NEMINS RMANRFACTRRINR All specifications are subject to change without notice. DUALITY SYSTEMS For more information,contact Notifier.Phone:(203)484-7161,FAX:(203)484-7118. www.notifier.com Page 4 of 4—ON-60942:B•4/20/17 D N-60924:B Indoor Selectable-Output Speaker Strobes and Dual ® N OT I F I E R'R. Voltage Evacuation Speakers for Ceiling Applications by Honeywell Audio/Visual Devices General The L-Series of speakers and speaker strobes reduce costly - ' ground faults using a plug-in design and universal mounting plate. The installer can pre-wire mounting plates, dress the wires, and confirm wiring continuity before plugging in the speakers. In addition, a protective plastic cover prevents nicked wires by covering exposed speaker components. ' # ". These devices also enable faster installations by providing instant feedback to ensure that wiring is properly connected, rotary switches to select voltage and power settings, and 7 .. +. field-selectable candela settings for both wall and ceiling .7! speaker strobes. The low total harmonic distortion of the SP speaker offers high fidelity sound output while still offering high volume sound out- put for use in high ambient noise applications. SPSCRL, SPSCWL L-SERIES MAKES INSTALLATION EASY Architectural/Engineering Specifications • Attach a universal mounting plate to a 4" x 4" x 21I8° back General.L-Series speaker and speaker strobes shall mount to box. Flush-mount applications do not require an extension a 4"x 4"x 2118 back box.A universal mounting plate shall be ring. used for mounting ceiling and wall products. The notification • Connect the notification appliance circuit or speaker wiring appliance circuit and amplifier wiring shall terminate at the uni- to the terminals on the mounting plate. versal mounting plate. Also, L-Series speaker strobes, when • Attach the speaker or speaker strobe to the mounting plate used with the Sync•CircuitTM Module accessory, shall be pow- by inserting the product tabs into the mounting plate ered from a non-coded notification appliance circuit output and grooves. Hinge the device into position to lock the product shall operate on a nominal 12 or 24 volts.When used with the pins into the mounting plate terminals.The device will tem- Sync•Circuit Module, 12-volt rated notification appliance circuit porarily hold in place with a catch until it is secured with a outputs shall operate between 8.5 and 17.5 volts;24-volt rated captured mounting screw. notification appliance circuit outputs shall operate between 16.5 and 33 volts. Indoor L-Series products shall operate Features between 32°F and 120°F from a regulated DC, or full-wave rectified, unfiltered power supply. Speaker strobes shall have • Plug-in design and protective cover reduce ground faults. field-selectable candela settings including 15, 30, 75,95, 115, • Universal mounting plate with an onboard shorting spring 150, 177. tests wiring continuity before installation. Speaker. The speaker shall be a System Sensor L-Series • No extension ring required. model dual-voltage transformer speaker capable of operating • Field selectable candela settings on ceiling units: 15, 30, at 25.0 or 70.7 nominal Vrms. It should be listed to UL 1480 75,95, 115, 150,and 177. and shall be approved for fire protective service.The speaker • Automatic selection of 12-or 24-volt operation at 15 and 30 shall have a frequency range of 400 to 4,000 Hz and shall candela. have an operating temperature between 32°F and 120°F.The Rotaryswitch simplifies field selection of speaker voltage speaker shall have power taps and voltage that are selected • P P g by rotary switches. (25 and 70.7 Vrms) and power settings (1/4, 1/z, 1 and 2 watts). Speaker Strobe Combination.The speaker strobe shall be a • Speakers offer high fidelity and high volume sound output. System Sensor L-Series model listed to UL1480 and UL 1971 and be approved for fire protective signaling systems. The • UL 464(520 Hz) listed and complies with NFPA 72 require- speaker shall be capable of operating at 25.0 or 70.7 nominal ments for low frequency with compatible fire alarm control Vrms selected via rotary switch, and shall have a frequency panel. range of 400 to 4,000 Hz. The speaker shall have power taps • Compatible with System Sensor synchronization protocol. that are selected by rotary switch.The strobe shall comply with • Electrical compatibility with existing SpectrAlert and the NFPA 72 requirements for visible signaling appliances, SpectrAlert Advance products. flashing at 1 Hz over the strobe's entire operating voltage Tamper-resistant construction. range.The strobe light shall consist of a xenon flash tube and • p associated lens/reflector system. • Updated modern aesthetics. Synchronization Module. The module shall be a System Sensor Sync•Circuit model MDL3 listed to UL 464 and shall be approved for fire protective service.The module shall synchro- nize SpectrAlert strobes at 1 Hz.The module shall mount to a 41V16"x 411/18"x 21/8° back box.The module shall also control two Style Y (class B) circuits or one Style Z (class A) circuit. The module shall synchronize multiple zones. Daisy chaining DN-60924:B•5/19/17—Page 1 of 4 two or more synchronization modules together will synchro- CEILING-MOUNT SPEAKER STROBE SOUND OUTPUT nize all the zones they control. The module shall not operate UL Reverberant UL Anechoic on a coded power supply. Setting (dBA @10 ft) (dBA @10 ft) Physical Specifications W 77 77 'iz w 80 80 • Standard Operating Temperature: 32°F to 120°F (0°C to 49°C) 1 W 83 83 • Humidity Range: 10 to 93%non-condensing. 2 W 86 86 • Dimensions,Ceiling-Mount: —SPC Speaker: Diameter 6.8 in, 173 mm. Depth: 1.0 in,25 Agency Listings and Approvals mm. —SPC Speaker with Surface Mount Back Box: Diameter: The listings and approvals below apply to L-series devices. In 6.9 in, 176 mm. Depth:3.5 in,89 mm. some cases,certain modules or applications may not be listed —SPSC Speaker Strobe: Diameter: 6.8 in, 173 mm. by certain approval agencies, or listing may be in process. Depth:2.8 in,73 Strobe: Consult factory for latest listing status. —SPSC Speaker Strobe with Surface Mount Back Box: UL-Listed: Diameter 6.9 in, 176 mm. Depth:5.37 in, 136 mm. —S4048 Plain Speaker Strobes(Ceiling) —S4048 Spanish-labeled Speaker Strobes (Ceiling) Electrical/Operating Specifications -S4048 Speaker Strobe ALERT devices • Nominal Voltage(speakers):25 Volts or 70.7 Volts (nomi- • UL/ULC-Listed: nal). —S4048 Speakers(Ceiling) • Maximum Supervisory Voltage(speakers):50 VDC. —S4048 Speaker Strobes(Ceiling) • Strobe Flash Rate: 1 flash per second. • FM Approved(All except ALERT models) • Nominal Voltage(strobes): Regulated 12 DC or regulated • CSFM Listed:7320-1653:0505 24 DC/FWR(full wave rectified). • Operating Voltage Range (includes fire alarm panels Product Line Information with built in sync):8 to 17.5 V(12 V nominal)or 16 to 33 V (24 V nominal). CEILING MOUNT SPEAKER STROBES • Operating Voltage with MDL3 Sync Module: 8.5 V to SPCWL(A),SPCRL(A).Speaker only(White, Red). 17.5 V(12 V nominal) or 16.5 V to 33 V(24 V nominal). SPSCWL(A)(-E)(-F), SPSCRL(A)(-E)(-F). Speaker strobe • Frequency Range:400 to 4,000 Hz. (White, Red). 520Hz capable with compatible fire alarm control panel. SPSCWL(A)-P.Plain speaker strobe(White). • Power: 1/4, Y, 1,2 watts. SPSCWL-SP. Spanish-labeled "Fuego" speaker strobe UL Current Draw Data (White) UUULC Listed. SPSCWL-TE. English with trim ring. UL MAX. STROBE CURRENT DRAW(MA RMS) SPSCWL-CLR-ALERT. Speaker Strobe, Ceiling, Clear Lens, 8-17.5 ALERT(White). Volts 16-33 Volts Candela DC DC FWR ACCESSORIES 15 87 41 60 SBBCWL, SBBCRL. Universal Ceiling Surface Mount Back Box(White, Red). 30 153 63 86 TRC-2W,TRC-2. Universal Ceiling Trim Ring(White, Red). 75 NA 111 142 NOTE: A"suffix indicates ULC-Listed model. ULC-listed devices 95 NA 134 164 include required French labeling. See Agency Listings for listing details. 115 NA 158 191 NOTE: "A"suffix indicates ULC-listed models, ULC models have 150 NA 189 228 FIRE/FEU marking on cover. 177 NA 226 264 NOTE: ULC-listed models add "-E"suffix for English only"FIRE" marking on cover. CEILING-MOUNT SPEAKER SOUND OUTPUT NOTE: ULC-listed models add "-F"suffix for French only "FEU" UL Reverberant UL Anechoic marking on cover. Setting (dBA @10 ft) (dBA @10 ft) W 79 79 Ys W 82 82 1 W 85 85 2 W 88 88 Page 2 of 4—DN-60924:B•5/19/17 Product Drawings 2.87" 6 80"diameter -8—(729 cm) .—1 63" (17 272 cm) i F(14.47 c 76"m)r (4.14 cm) iiiiii117.79/1:!7.— ... El) • :: , , ,, ..„,, 7 v„,..:,,,,,.„ ♦‘,,,,..,,,..„,.. _ --14:$::'Y > i y:ilt:::1**"34 �°11 /t„,,,,_, , _$>''��'i1 r �v- N in Q Speaker Strobe Dimensions Speaker Strobe with SBBCRLI SBBCWL Surface Mount Back Box 6.B0"diameter, 1.00" - 1.63" (17.272 cm) (2.54 cm) (4.14 cm) .:::-i) -VT-t- o .r 1 uf\ Lis IN Wef i :11:111 .0,,... J' . lI N Q Speaker with SBBCRLISBBCWL Speaker Dimensions Surface Mount Back Box DN-60924:B•5/19/I7—Page 3 of 4 NOTIFIER® and SpectrAlert® are registered trademarks and Sync•CIrcuit''is a trademark of Honeywell International Inc. 02017 by Honeywell International Inc.All rights reserved.Unauthorized use of this document is strictly prohibited. ISO 9001 This document is not intended to be used for installation purposes. We try to keep our product information up-to-date and accurate. G E R T r F r E U We cannot cover all specific applications or anticipate all requirements. einamm 8 MANOFAuRIN1 All specifications are subject to change without notice. QUALITY SYSTEMS For more information,contact Notifier.Phone:(203)484-7161,FAX:(203)484-7118. www.notifier.com Page 4 of 4—DN-60924:B•5/19/17 dn-60323:c1 SpectrAlert® Advance * NOTIFIEW Outdoor Selectable Output Speaker Strobes and Dual Voltage Evacuation Speakers by Honeywell Audio/Visual Devices t.a General The SpectrAlert Advance series offers the broadest line of out- � +-r door speakers and speaker strobes in the industry. From metal and plastic outdoor back boxes, to white and red plastic hous- ings, to wall and ceiling mounting options, virtually every appli- cation is covered. SpectrAlert Advance outdoor speakers and ( A speaker strobes offer reliable operation over the entire tempera- ture range of-40°F to 151°F.They may be used indoors or out- - doors in wet or dry applications. In addition, these speakers N` provide a broad frequency response range and low harmonic distortion to provide an accurate and intelligible broadcast of . ' t evacuation messages. High sound pressure level at all tap set- $ R tings ensures that messages are clearly heard. f= E The plug-in design allows the installer to pre-wire mounting plates and dress the wires before plugging in the speakers to help reduce ground faults.This design also allows faster instal- lations with instant feedback to ensure that wiring is properly connected,rotary switches to select voltage and power settings, and field selectable candela settings for wall and ceiling speaker strobes. The new weatherproof back boxes have plastic and metal ver- sions. They are now designed to accommodate in-and-out wir- ing for daisy chaining outdoor devices.The plastic weatherproof back boxes shipped with the product feature removable side flanges and improved resistance to salt water corrosion. The screw hole knockouts located on the back of the weatherproof Specifications back box eliminate the need to drill holes for screw-in mounting. • Both weatherproof back boxes are available with 3/4 inch top PHYSICAL SPECIFICATIONS and bottom conduit entries and 3/4 inch knock-outs at the back. Included with each back box is a screw-in NPT plug with an O- Operating Temperature: -40°F to 151°F(-40°C to 66°C) ring gasket for a watertight seal. Metal back boxes are available DIMENSIONS separately. Dimensions,Wall-Mount: Features • SPS Speaker Strobe:6.0"L x 5.0"W x 4.7"D Plug-in design (including lens and speaker) •• Electrical compatibility with existingSpectrAlert products • SP Speaker: 6.0"L x 5.0"W x 2.9"D P h+ P • Shorting spring on mounting plate tests continuity before Dimensions,Ceiling-Mount: installation • SPS Speaker Strobe:6.8"in Diameter x 4.7"D • Rotary switch simplifies field selection of speaker voltage and (including lens and speaker) power settings • SP Speaker:6.8"in Diameter x 2.9"D • Universal mounting plate for wall-and ceiling-mount units Dimensions,Wall-Mount Weatherproof Backbox • Weatherproof per NEMA 4x, IP56 • 6.5"L x 5.5"H x 2.9"D • Compatible with System Sensor synchronization protocol Dimensions,Ceiling-Mount Weatherproof Backbox • Automatic selection of 12 or 24-volt operation at 15 and 15/ • 7.2"Dia x 29"H 75 candela • Field selectable candela settings on wall and ceiling units ELECTRICAL/OPERATING SPECIFICATIONS • Ceiling and wall mount application Nominal Voltage(speakers):25 Volts or 70.7 Volts(nominal) Maximum Supervisory Voltage(speakers):50VDC Agency Listings and Approvals Strobe Flash Rate: 1 flash per second In some cases, certain modules may not be listed by certain Nominal Voltage (Strobes): Regulated 12VDC/FWR or approval agencies,or listing may be in progress.Consult factory 24VDC/FWR for latest listing status. Operating Voltage Range(includes fire panels with built-in • UL/ULC Listed:S4048 sync):8 to 17.5V(12V nominal)or 16 to 33V(24 nominal) • MEA: 10-08-E Operating Voltage with MDL Sync Module: • CSFM:7320-1653:201 9 to 17.5V(12V nominal)or 17 to 33V(24V nominal) Frequency Range:400 to 4000Hz Power: V4,Y2,1,2 watts dn-60323:c1•11/9/11—Page 1 of 2 Sound Output shall have an operating temperature from -40°F to 150.8°F. It P shall have power taps and wattage settings which are selected UL Reverberant 10ft(dBA 2W 1W Y:W y4W by rotary switches,The speaker must be installed with its weath- erproof backbox in order to remain outdoor approved per UU Outdoor Speaker 90 87 84 81 ULC listing S4048. The speaker shall be suitable for use in air handling spaces,as well as wet environments. Outdoor Speaker/Speaker Strobe 89 86 83 80 SPEAKER STROBE COMBINATION The Speaker Strobe shall be a System Sensor Model UL Maximum Strobe Current Draw(mA RMS) listed to ULJULC 1638 and UUULC 1480 and be approved for - fire protective signaling systems. It shall be capable of operating 8 to 17.5 Volts 16 to 33 Volts at 25.0 or 70.7 nominal Vrms,and shall have a frequency range Candela of 400 to 4000 Hz. It shall have power taps that are selected by DC FWR DC FWR rotary switch.The strobe shall consist of a xenon flash tube with " 15 123 128 66 71 associated lens/reflector system and operate on either 12V or 15/75 142 148 77 81 24V. The strobe shall also feature selectable candela output, providing options for 15 or 15/75 candela when operating on Standard 30 NA NA 94 96 12V and 15, 15/75,30,75,110, 115, 135, 150, 177 or 185 when . Candela 75 NA NA 158 153 operating on 24V. The strobe shall comply with the Americans Range 95 NA NA 181 176 with Disabilities Act requirement for visible signaling appliances, flashing at 1 Hz over the strobe's entire operating voltage range. 110 NA NA 202 195 The speaker strobe must be installed with its weatherproof back 115 NA NA 210 205 box in order to remain outdoor approved per UUULC. The 135 NA NA 228 207 speaker strobe shall be suitable for use in wet environments. High 150 NA NA 246 220 Candela 177 NA NA 281 251 Product Line Information Range 185 NA NA 286 258 NOTE:"A"suffix indicates ULC-Listed model. NOTE: All outdoor models ("K(A)"suffix), include weatherproof Candela Derating backbox. NOTE:Add"R"to outdoor models for weatherproof replacement NOTE:For K series products used at low temperatures,listed can- device(no backbox included). dela ratings must be reduced in accordance with this table. Strobe Output(cd) SPWK(A):Wall mount outdoor speaker;white. Listed Candela Candela Rating at-40°F SPRK(A): Wall mount outdoor speaker; red. 15 SPSWK: Wall mount outdoor speaker strobe, selectable can- 15/75 Do not use below 32°F dela(15, 15/75,30,75,95, 110,115);white. • 30 SPSRK: Wall mount outdoor speaker strobe, selectable can- 75 44 dela(15, 15/75,30,75,95, 110, 115);red. 95 70 SPCWK: Ceiling mount outdoor speaker;white. • 110 110 SPSCWK: Ceiling mount outdoor speaker strobe, selectable 115 115 candela(15, 15/75,30,50,75,95,110, 115);white. 135 135 150 150 SPSCWHK: Ceiling mount outdoor speaker strobe, selectable 177 177 candela, high cd(135, 150,177, 185);white. 185 185 ACCESSORIES Architectural/Engineering Specifications MWBB(A):Wall, metal weatherproof backbox;red. MWBBW(A):Wall,metal weatherproof backbox;white. GENERAL MWBBCW(A):Ceiling,metal weatherproof backbox;white. SpectrAlert Advance outdoor speaker and speaker strobes shall mount to a weatherproof back box. A universal mounting plate WTP-SP: Flush mount weatherproof plate for use with speak- shall be used for mounting ceiling and wall products.The notifi- ers/speaker strobes,red, cation appliance circuit and amplifier wiring shall terminate at WTP-SPW:Flush mount weatherproofplate for use with speak- strobes,universal mounting plate.Also,SpectrAlert Advance speakerP Pe strobes, when used with the Sync•CircuitTM Module accessory, ers/speaker strobes,white. shall be powered from a non-coded notification appliance circuit output and shall operate on a nominal 12 or 24 volts. When used with the Sync•Circuit Module, 12-volt rated notification appliance circuit outputs shall operate between 9 and 17.5 volts; 24-volt rated notification appliance circuit outputs shall operate between 17 and 33 volts. Outdoor SpectrAlert Advance prod- ucts shall operate between-40°F and 151°F from a regulated DC,or full-wave rectified,unfiltered power supply. SPEAKER The Speaker shall be a System Sensor SpectrAlert Advance Model dual voltage transformer speaker capable of operating at 25.0 or 70.7 nominal Vrms. It shall be listed to UU System Sensor®is a registered trademark of Honeywell International Inc. ULC Standard S4048 for outdoor fire protective signaling sys- tems. It shall have a frequency range f 400 to 4000 Hz and 02011 by Honeywell International Inc.All rights reserved.Unauthorized use of this document is strictly prohibited. 'SO9001 This document is not intended to be used for installation purposes. `V We try to keep our product information up-to-date and accurate. C E R T F E O We cannot cover all specific applications or anticipate all requirements. Own EfitirifBINt A MANUFACTURING All specifications are subject to change without notice. QUALITY SYSTEMS MadeintheU.S.A. For more information,contact Notifier.Phone:(203)484-7161,FAX:(203)484-7118. • www.notifier.com Page 2 of 2-dn-60323:c1•11/9/11 1