Loading...
Report . 21-000 - 1 07,20 Sry 6 12c1 Toilet Rooms 5L 2nd Floor RECEIVED APR 8 2U2 CITY OF TIGARD Material Data Report BUILDING DIVISION MC %niStry For Fire Protection Systems For ih Ile Of Your Building v.z.3, 11 { Y aG .., k .a Y $ Oti re e ' C � _te {•¢6 e �' 1 x b ' b.., k t, 44;4- to,1;,,:::,:.,,,,, RI fill }Yµ •Iv Fn 0.1 rlate,& E $ _ i , . 401442144: 3 FIRE SPRINKLERS Worldwide wwwtyco-fire.com ti1t1 c Contacts Series RFII - 5.6 K-factor "Royal Flush II" Concealed Pendent Sprinklers Quick & Standard Response, Standard Coverage General The Series RFII Sprinklers are shipped with a Disposable Protective Cap.The Description Protective Cap is temporarily removed p during installation and replaced to help The TYCO Series RFII 5.6 K-factor, protect the sprinkler during ceiling "Royal Flush II" Concealed Pendent installation or finish.The tip of the Pro- Sprinklers Quick Response (3-mm tective Cap can be used to mark the mom_ 'N bulb) and Standard Response (5-mm center of the ceiling hole into plaster ;1140- bulb), are decorative sprinklers fea- board or ceiling tiles by gently pushing turing a flat cover plate designed to the ceiling product against the Pro- conceal the sprinkler.These sprinklers tective Cap. When ceiling installa are optimal for architecturally sensi- tion is complete,the Protective Cap is five areas such as hotel lobbies, office removed and the Cover Plate/Retainer buildings,churches,and restaurants. Assembly is installed. �'m� f'''" Each sprinkler includes a Cover Plate/ As an option,the Series RFII Standard Retainer Assembly and a Sprinkler! Response(5-mm bulb)"Royal Flush II" Support Cup Assembly. The separa Concealed Pendent Sprinklers can be ble, two-piece assembly design pro- fitted with a silicone Air and Dust Seal. Technical vides the following benefits: See Figure 5. The Air and Dust Seal is intended for sensitive areas where Data • Allows installation of the sprinklers it is desirable to prevent air and dust and pressure testing of the fire pro- from the area above the ceiling to pass Sprinkler Approvals tection system prior to installation of through the cover plate. Approvals apply only to the service a suspended ceiling or application of conditions indicated in the Design Criteria the finish coating to a fixed ceiling. NOTICE section. • Permits the removal of suspended The Series RFII Concealed Pendent • TY3531 (3 mm Bulb)is UL Listed, ceiling panels for access to building Sprinklers described herein must be C-UL Listed and NYC Approved service equipment without having installed and maintained in compliance (MEA 353-01-E)as Quick Response. to first shut down the fire protection with this document and with the appy- • TY3531 (3 mm Bulb)is VdS Approved system and remove sprinklers. cable standards of the NATIONAL FIRE (Certificate No.G4090007). • Provides for 1/2 in.(12,7 mm)of ver- PROTECTION ASSOCIATION (NFPA), in addition to the standards of any • TY3531 (3 mm Bulb)is FM and tical adjustment to allow a measure LPCB Approved(Ref. No.094a/10)as of flexibility in determining the length authorities having jurisdiction. Failure Standard Response. of fixed piping to cut for the sprinkler to do so may impair the performance drops. of these devices. Note:FM and LPCB do not approve The owner is responsible for maintain- concealed sprinklers for quick response. ing their fire protection system and devices in proper operating condition. • TY3551 (5 mm Bulb)is UL Listed,C-UL The installing contractor or sprinkler Listed,FM Approved, LPCB Approved manufacturer should be contacted with (Ref.No.094a/9),and NYC Approved any questions. (MEA 353-01-E)as Standard Response. IMPORTANT Approvals for Air and Dust Seal Refer to Technical Data Sheet Sprinkler UL and C-UL Listed for use with the RFII TFP2300 for warnings pertaining to Standard Response Concealed Sprinkler regulatory and health information. Identification (TY3551) Always refer to Technical Data Maximum Working Pressure Sheet TFP700 for the "INSTALLER Number (SIN) Maximum 250 psi(17,3 bar)by UL, WARNING" that provides cautions C-UL,and NYC with respect to handling and instal- TY3531 - 3 mm bulb Maximum 175 psi(12,1 bar)by FM,VdS, lation of sprinkler systems and corn- TY3551 - 5 mm bulb and LPCB ponents. Improper handling and Temperature Rating installation can permanently damage 155°F(68°C)Sprinkler with a sprinkler system or its compo- 139°F(59°C)Cover Plate nents and cause the sprinkler to fail to operate in a fire situation or cause 200°F(93°C)Sprinkler with it to operate prematurely. 165°F(74°C)Cover Plate Page 1 of 4 MARCH 2O19 TFP181 TFP181 Page 2 of 4 , Discharge Coefficient 2 NPT SEALING K=5.6 GPM/psit12(80,6 LPM/bar""2) --- j__________________________ ASSEMBLY Adjustment 1/2 in.(12,7 mm) Finishes FRAME See the Ordering Procedure section. ' . CAP Physical Characteristics i Frame Bronze Support Cup Plated Steel SUPPORT Guide Pins Stainless Steel CUP WITH I IiIiiBULB Deflector Bronze ROLL FORMED Compression Screw Brass THREADS Bulb Glass R Cap Bronze or Copper I I Sealing Assembly..Beryllium Nickel w/TEFLON I I COMPRESSION Cover Plate Brass SCREW Retainer Brass GUIDE Ejection Spring Stainless Steel PINS(2) (I $ I I Design DEFLECTOR (DROPPED Criteria DEFLECTOR i I I / POSITION) tJ The TYCO Series RFII 5.6 K-factor, "Royal Flush II" Concealed Pendent I SPRINKLER/SUPPORT CUP Sprinklers are intended for fire protec- ASSEMBLY tion systems designed in accordance I with the standard installation rules THREAD INTO I RETAINER recognized by the applicable Listing SUPPORT ) I WITH THREAD or Approval agency; for example, UL CUP UNTIL tN CI O DIMPLES Listing is based on NFPA 13 and VdS MOUNTING Approval is based on the CEA 4001. SURFACE IS EJECTION FLUSH WITH SPRING For more information on LPCB and VdS CEILING Approvals, contact Johnson Controls at the following office: Enschede, Netherlands r� a Telephone:31-53-428-4444 / Fax:31-53-428-3377 SOLDER J COVER The Series RFII Concealed Pendent TABS(3) COVER PLATE/RETAINER PLATE Sprinklers are only listed and approved ASSEMBLY with the Series RFII Concealed Cover FIGURE 1 Plates having a factory applied finish. MODEL RFII CONCEALED SPRINKLER ASSEMBLY NOTICE Do not use the Series RFII in applica- Installation Do not attempt to compensate for tions where the air pressure above the insufficient adjustment in the Sprinkler ceiling is greater than that below.Down The TYCO Series RFII 5.6 K-factor, by under-or over-tightening the Sprin- drafts through the Sprinkler/Support "Royal Flush II" Concealed Pendent kler/Support Cup Assembly. Re-adjust Cup Assembly can delay sprinkler Sprinklers must be installed in accor- the position of the sprinkler fitting to operation in a fire situation. dance with this section. suit. General Instructions Step 1. Install the sprinkler only in the Operation Do not install any bulb-type sprin- pendent position with the center-line kler if the bulb is cracked or there is of the sprinkler perpendicular to the When exposed to heat from a fire,the mounting surface. Cover Plate, normally soldered to the a loss of liquid from the bulb.With the Step 2. Remove the Protective Cap. Retainer at three points, falls awayto sprinkler held horizontally, a small air expose the Sprinkler/Support Cup bubble should be present. The diam- Step 3. With pipe thread sealant Assembly. eter of the air bubble is approximately applied to the pipe threads, hand- 1/16 in. (1,6 mm) for the 155°F (68°C) tighten the sprinkler into the sprinkler The Deflector — supported by the and 3/32 in. (2,4 mm) for the 200°F fitting. Guide Pins — then drops down to its (93°C)temperature ratings. Step 4. Wrench-tighten the sprinkler operational position. A leak-tight 1/2 in. NPT sprinkler joint using only the RFII Sprinkler Wrench. The glass bulb contains a fluid that should be obtained by applying a See Figure 3. Apply the RFII Sprinkler expands when exposed to heat.When minimum to maximum torque of 7 to Wrench to the Sprinkler as shown in the rated temperature is reached, the 14 lb-ft(9,5 to 19,0 N•m).Higher levels Figure 3. fluid expands sufficiently to shatter the of torque can distort the sprinkler Inlet glass bulb,activating the sprinkler and with consequent leakage or impairment allowing water to flow. of the sprinkler. TFP181 Page 3 of 4 FACE OF CLEARANCE HOLE CLEARANCE _ SPRINKLER DIAMETER HOLE FITTING I DIMENSION C l \ J 1�� SPRINKLER SUPPORT CUP ll ASSEMBLY � lii l'''''' V THREADED �1 I!W D ADJUSTMENT— cI FACE j El OF CEILING, I o w----.--i RETAINING RING MOUNTING FIGURE 4 SURFACE �.� r I , DISPOSABLE PROTECTIVE CAP Step 5. Replace the Protective Cap by --------- —Ii II pushing it upwards until it bottoms out against the Support Cup. See Figure =z r_ -_ 4. The Protective Cap helps prevent T ~I k\-, - ' ' damage to the Deflector and Arms 3/16"to 11/16" MANUFACTURER DEFLECTOR COVER PLATE during ceiling installation and/or finish. (4,8 to 17,5 mm) PRESET GAP IN DROPPED RETAINER You can also use the Protective Cap to REFERENCE 3/32"(2,4 mm) POSITION ASSEMBLY locate the center of the clearance hole by gently pushing the ceiling material COVER PLATE COVER PLATE up against the center point of the Pro- -PROFILE DEPTH - DIAMETER - - tective Cap. DIMENSION B DIMENSION A A:3-1/4 in.(82,6 mm) C:2-3/8 to 2-5/8 in.(60,3 to 66,7 mm) NOTICE As long as the Protective Cap remains B:3/16 in.(4,8 mm) D:1-3/4 to 2-1/4 in.(44,5 to 57,2 mm) in place,the system is considered "Out of Service". FIGURE 2 Step 6. After the ceiling has been SERIES CONCEALED SPRINKLER INSTALLATION DIMENSIONS completed with the 2-1/2 in.(63,5 mm) diameter clearance hole and in prep- aration for installing the Cover Plate/ Retainer Assembly,remove and discard _ the Protective Cap. Verify that the ` • FRAME t,=i, Deflector moves up and down freely. i � If the Sprinkler is damaged and the �I:,,;,, Deflector does not move up and down SUPPORT _ � freely, replace the entire Sprinkler. - ' Do not attempt to modify or repair a _ _ �_ I damaged sprinkler. ����� ����� Step 7.When installing an Air and Dust ^��� Seal,see Figure 5;otherwise, proceed I■I ` to Step 8. To attach the Air and Dust - — Seal, verify the angle of the outside 7/8"(23 mm) edge of the seal is oriented accord- SQUARE ing to Figure 5. Start the edge of the Retainer in the grooved slot of the Air is- _ and Dust Seal and continue around the ALIGN �� �. retainer until the entire Air and Dust ARROWS WITH / I I \\ Seal is engaged. FRAME ARMS Step 8. Screw on the Cover Plate/ 1 l prl Retainer Assembly until the Retainer, ACCEPTS �( i7 shown in Figure 2, or the Air and Dust 0 1/2"SOCKET \ \�_�� Seal, shown in Figure 5, contacts the DRIVE \ ceiling.Do not continue to screw on the Cover Plate/Retainer Assembly so that FIGURE 3 it lifts a ceiling panel out of its normal RFII SPRINKLER WRENCH position. If you cannot engage the Cover Plate/Retainer Assembly with the Support Cup or you cannot engage the Cover Plate/Retainer Assembly suf- ficiently to contact the ceiling,you must reposition the Sprinkler Fitting. TFP181 Page 4 of 4 • e SUPPORT �_ SPRINKLER FACE OF ORIENT Limited CUP CEILING '---SEAL / SHOWN Warranty l=L ___ 'T SHOWN POLATE For warranty terms and conditions,visit iir ` + 11 RETAINER — www.tyco-fire.com. � �i, ASSEMBLY ' tk Ordering ICI AProcedure „■" ;i%> � AIR �/ AND DUST Contact your local distributor for --r -ujij_-- LIP OF COVER SEAL availability. When placing an order, RETAINER PLATE indicate the full product name. FIGURE 5 Sprinkler/Support Cup Assembly OPTIONAL AIR AND DUST SEAL FOR SERIES RFII(TY3551) Specify: Series RFII (specify SIN), K=5.6, "Royal Flush IIf1 Pendent Sprin- Care and if they cannot be completely cleaned klers(specify)temperature rating, P/N* by wiping the sprinkler with a cloth or (specify): Maintenance by brushing it with a soft bristle brush. 155°F(66°C) 200°F 193°Cl Care must be exercised to avoid TY3531 51-792-1-155 51-792-1-200 The TYCO Series RFII 5.6 K-factor, damage to the sprinklers - before, TY3551 51-790-1-155 51-790-1-200 "Royal Flush II" Concealed Pendent during, and after installation. Sprin- Use Suffix"I"forlso7-1Donne«lon;lore=ample, Sprinklers must be maintained and klers damaged by dropping, striking, 51-792-1-155-I serviced in accordance with this wrench twist/slippage,or the like,must Separately Ordered Cover Plate/ section. be replaced.Also,replace any sprinkler Before closinga fireprotection system that has a cracked bulb or that has lost Retainer Assembly: y liquid from its bulb.See the Installation Specify: (temperature rating from main control valve for maintenance Section. below) Series RFII Concealed Cover work on the fire protection system Plate with(finish), P/N(specify). that it controls, obtain permission to Exercise care to avoid damage to sprin- 139°F(59°C)(a) 165°F(74°c)(b) shut down the affected fire protection klers before, during, and after instal- Grey White system from the proper authorities lation. Replace sprinklers damaged (RAL9002) 56-792-0-135 56-792-0-165 and notify all personnel who may be by dropping, striking, wrench twist- Brass 56-792-1-135 56-792-1-165 affected by this action. ing, wrench slipping, or the like. Also, Pure White(c) Absence of the Cover Plate/Retainer replace any sprinkler that has a cracked (RAL9010) 56-792-3-135 56-792-3-165 Assembly can delay sprinkler opera- bulb or that has lost liquid from its bulb. signal White See the Installation section. (RAL9003) 56-792-4-135 56-792-4-165 tion in a fire situation. Ifyou must remove a sprinkler, do not Jet Black p (RAL9005) 56-792-6-135 59-792-6-165 When properly installed, there is a nominal 3/32 in. (2,4 mm) air gap reinstall i the a replacement men/ Retainer Br shed reinstalling Cover Plate/Retainer Chrome 56-792-8-135 56-792-8-165 between the lip of the Cover Plate and Assembly. If a Cover Plate/Retainer Chrome 56-792-9-135 56-792-9-165 the ceiling, as shown in Figure 2. Assembly becomes dislodged during Custom 56-792-X-135 56-792-X-165 This air gap is necessary for proper service, replace it immediately. operation of the sprinkler. If the ceiling (a) For use with 155°F(68°C)sprinklers. P The owner is responsible for the (b) For use with 200°F(93°C)sprinklers. requires repainting after sprinkler inspection,testing,and maintenance of installation, ensure that the new paint their fire protection system and devices (c) Eastern Hemisphere sales only. does not seal off any of the air gap. in compliance with this document, as Sprinkler Wrench Do not pull the Cover Plate relative to well as with the applicable standards Specify: RFII Sprinkler Wrench, the Enclosure.Separation may result. of the NATIONAL FIRE PROTECTION P/N 56-000-1-075 ASSOCIATION,for example, NFPA 25, Air and Dust Seal Sprinklers which are found to be in addition to the standards of any other leaking or exhibiting visible signs of authorities having jurisdiction.Contact Specify:Air and Dust Seal, corrosion must be replaced. the installing contractor or sprinkler P/N 56-908-1-001 Automatic sprinklers must never be manufacturer regarding any questions. painted, plated, coated, or other- Automatic sprinkler systems should be wise altered after leaving the factory. inspected,tested,and maintained by a Modified sprinklers must be replaced. qualified Inspection Service in accor- Sprinklers that have been exposed to dance with local requirements and/or corrosive products of combustion, but national code. have not operated,should be replaced 1400 Pennbrook Parkway,Lansdale,PA 194461 Telephone+1-215-362-0700 /J / e1019 Johnson Controls.All rights reserved All specifications and other Information shown were current es of document revision date and are subject to change without notice. Johnson )��' NATIONAL FIRE PROTECTION ASSOCIATION and NFPA are registered trademarks of National Fire Protection Association; Controls s TEFLON is a registered trademark of DuPont Availability:Americas Bulletin 213 July 2019 Rel RASCOFLEXTM Sprinkler Connections iabit cULus Listed, FM Approved Product Description RASCOFLEXTM Sprinkler Connections are intended to connect a branch line to a sprinkler using a flexible stainless steel hose assembly. RASCOFLEXTM Sprinkler Connections are suitable for use in suspended and hard ceiling applications such as T-Bar ceiling grids, wood, metal stud, or hat furring channel hard lid ceilings. Every package contains one (1) fully assem- bled stainless steel flexible sprinkler system complete with hose, branch line connection,and sprinkler connection,as well as the pre-assembled bracket assembly to attach to the ceiling. RASCOFLEXTM Sprinkler Connections are designed for use in hydraulically calculated wet, preaction, or dry sprinkler sys- tems per NFPA 13, 13R, 13D, and FM Global Loss Prevention Data Sheets. Technical Data Table A RASCOFLEXTA9 Sprinkler Connections Maximum Working Pressure FM: 200 psi(13.79 bar) UL: 175 psi(12.07 bar) Maximum Working Temperature 300°F(149°C) Ordering Information Inlet/Branch Line 1" NPT Specify: Connections Outlet/Reducer 1/2"or 3/4" NPT Nominal Hose Length • 24"(610 mm) Minimum Bending Radius UL: 3"(76 mm) • 31"(790 mm) FM: 7" (178 mm) • 40"(1015 mm) Maximum Number of Bends See Friction Loss Chart • 48"(1220 mm) • 60" 1525 mm) 1/2" Outlet 5.6 (80 metric) • 72"(1830 mm) Maximum K-Factor UL: 14.0(200 metric) 3/4"Outlet Reducer Outlet: 1/2" NPT or 3/4" NPT FM: 8.0(115 metric) Reducer Type Maintenance Standard: • 6-1/8"(155 mm)straight RASCOFLEXTM Sprinkler Connections should be inspected Optional: and the sprinkler system maintained in accordance with NFPA • 4-1/4"(110 mm)straight 25, as well as the requirements of any Authorities Having • 5-1/4"(135 mm)straight Jurisdiction. • 11-3/4"(300 mm)straight • 5-5/8"(143 mm)elbow Patents • 7-3/8"(187 mm)elbow RASCOFLEXTM Sprinkler Connections may be covered by Bracket Length one or more of the following US Patent Nos. 10,173,088 and • 24"(610 mm)standard 10,328,296. • 48" (1220 mm)optional Listings and Approvals FM Approved Class No. 1637(FM) UL Listed and UL Certified for Canada to ANSI/UL 2443 (cULus) www.reliablesprinkler.com Bracket Dimensions Figure 1 I 28"[711] Standard or 52"[1320] Optional 1 * _ . P _ � � c Ill rCV r Ceiling grid shown for reference only. 7-Verify actual ceiling grid dimensions and ceiling tile reveal prior to ordering. Co d- M Reducer Dimensions Figure 2 iggig mem ii! .11PA PDI _ _ —_-_- 1— r0 =c c0 M =__ in- r T Lc) OLI co = ET !-E co O =__ __= V __= M . X. it " M 11r 7 _IV _ r M _III IliHMV `�MVV HMV M HMV ��M77 6-1/8'(155 mm) 4-5/16'(110 mm) 5-5/16'(135 mm) 11-13/16'(300 mm) 5-5/8'(143 mm) 7-3/8'(187 mm) Straight Straight Straight Straight Elbow Elbow Standard Bulletin 213 Reliable Page 2 of 6 July 2019 www.reliablesprinkler.com Installation DimensionNNs�� Figure 3 EMI Ali EEE._ 111 112 -\ ===_ ! === IIPl i Ceiling grid ov- I1'� 1 V shown for m reference only. Ili v Verify actual ceiling grid .CO dimensions and ceiling tile reveal prior to ordering. Minimum and Maximum Face of Fitting to Bottom of Ceiling Grid for Each Reducer Table B 6-1/8° 4-5/6" 5-5/16" 11-13/16" 5-5/8" 7-3/8" (155mm) (110mm) (135mm) (300mm) (143mm) (187mm) Straight Straight Straight Straight Elbow Elbow Standard Fig.3 Dimension A Max. Face of Fitting 3" (77mm) 3" (7mm) 3" (7mm) 3" (7mm) 3" (7mm) 3" (7mm) Distance above Bottom of Ceiling Grid Fig.3 Dimension B Max. Face of Fitting 1/8" (3mm) 1-5/8"(42mm) 11/16" (17mm) 6-3/8"(148mm) 1-7/16"(36mm) 5/16" (60mm) Distance from Bottom below above above below above below of Ceiling Grid Note:Based on 1-11/16"(43mm)tall ceiling grid. Fig.3 Dimension C-Clearance Above Ceiling Required at Max.Sprinkler Recess Table C Recessed Escutcheon or Reducer Concealed/Flush Sprinkler 5-5/8"(143mm) Elbow 7-3/8"(187mm)Elbow F1 recessed escutcheon NC 5-5/8" (144mm) F2 recessed escutcheon NC 5-3/8" (138mm) FP recessed escutcheon NC 6-1/4"(160mm) CCP conical concealed cover plate NC 6-1/4"(160mm) G4 series concealed sprinklers 5-5/8"(144mm) 7-3/8" (188mm) G5 series concealed sprinklers 5-1/4"(134mm) 7"(179mm) RFC series concealed sprinklers 5-1/4" (134mm) 7"(179mm) XL commercial flush sprinkler with flat escutcheon 4-7/8" (125mm) 6-5/8" (169mm) XL commercial flush sprinkler with conical escutcheon 4-3/8"(112mm) 6-1/8"(157mm) Note:NC-Reducer not compatible with sprinkler adjustment range. Based on 1-11/16"(43mm)tall ceiling grid and flush ceiling tile. Bulletin 213 Reliable Page 3 of 6 July 2019 www.reliablesprinkler.com Materials Figure 4 Number Item Description Material ���,�,.. i lil`I�I,i'III': %f% 1 Flexible Hose/Bellow AISI Type 304 Stainless Steel 2 Isolation Ring Nylon 66 0 0 6 ,� 3 Gasket EPDM V 8 4 Nut Zinc Plated Carbon Steel ►�V� 5 Branch Line Nipple(1") Zinc Plated Carbon Steel 4:0_+.= 6 Reducer Zinc Plated Carbon Steel 3 7 Braid AISI Type 304 Stainless Steel 4 8 Welded Collar Fitting AISI Type 304 Stainless Steel - Bar Stock Zinc Plated SGCC Steel 6 - Brackets: Center and Side Zinc Plated SPCC Steel Flexible Hose Number of Bends Figure 5 One Bend Two Bends Three Bends Minimum bend radius 2x 2x Min Min bend bend radius radius OR OR Minimum 1 bend radius 1 \ 1 Minimum Minimum I� bend radius Minimum Minimum bend radius bend radius bend radius \ _ Minimum bend radius Bulletin 213 Reliable Page 4 of 6 July 2019 www.reliablesprinkler.com C ® US cULus Friction Loss Data Table D Maximum Maximum Nominal Reducer Sprinkler Number of Equivalent Length Length of Flexible o of 1" (33.7mm) Hose K-Factor 90 Bends at 3" in(mm) NPT Threads Type gpm/psi112 (76mm) Sch. 40 Pipe (Ipm/bar1'2) Bend Radius (C=120),ft(m) 24 1/2 Straight 5.6(80) 2 10(3) (610) 3/4 Straight 14.0(200) 2 13(4) 31 1/2 Straight 5.6(80) 3 14(4.3) (790) 3/4 Straight 14.0(200) 3 16(4.9) 40 1/2 Straight 5.6(80) 4 21 (6.4) (1015) 3/4 Straight 14.0 (200) 4 23(7) 48 1/2 Straight 5.6(80) 4 24(7.3) (1220) 3/4 Straight 14.0(200) 4 26(7.9) 60 1/2 Straight 5.6(80) 4 25(7.6) (1525) 3/4 Straight 14.0(200) 4 30(9.1) 72 1/2 Straight 5.6(80) 5 36(11) (1830) 3/4 Straight 14.0(200) 5 33(10.1) UL Notes: 1.Available data for use with 6.1"straight reducers. 2.Sprinkler K-Factor:5.6(80 metric)for 1/2-inch reducer and 14.0(200 metric)for 3/4-inch reducer. 3.RASCOFLEXT"'Sprinkler Connections have been tested and approved by Underwriter's Laboratories,Inc.for use in wet,preaction, and dry sprinkler systems per NFPA 13, 13D, 13R and UL2443. Bulletin 213 Reliable Page 5 of 6 July 2019 www.reliablesprinkler.com APPROVED FM Friction Loss Data Table E Nominal Reducer Maximum Maximum Equivalent Length Length of Flexible Sprinkler Number of of 1" (33.7mm) Hose K-Factor 90 Bends at 3" Sch.40 Pipe in(mm) NPT Threads Type gpm/psi12 (76mm) (C=120),ft(m) (Ipm/bar1°) Bend Radius 1/2 Straight 5.6(80) 1 9.7(2.9) 24 1/2 90° Elbow 5.6(80) 0 11.5(3.5) (610) 3/4 Straight 8.0(115) 1 9.9(3) 3/4 90°Elbow 8.0(115) 0 10.2(3.1) 1/2 Straight 5.6(80) 2 12.4(3.8) 31 1/2 90°Elbow 5.6(80) 2 15.8(4.8) (790) 3/4 Straight 8.0(115) 2 13.7(4.1) 3/4 90°Elbow 8.0(115) 2 14.5(4.4) 1/2 Straight 5.6(80) 2 15.9(4.8) 40 1/2 90°Elbow 5.6(80) 2 21.6(6.6) (1015) 3/4 Straight 8.0(115) 2 18.5(5.6) 3/4 90° Elbow 8.0(115) 2 20(6) 1/2 Straight 5.6(80) 3 19.0(5.8) 48 1/2 90° Elbow 5.6(80) 3 25.9(7.9) (1220) 3/4 Straight 8.0(115) 3 22.7(6.9) 3/4 90°Elbow 8.0(115) 3 24.8(7.5) 1/2 Straight 5.6(80) 4 23.7(7.2) 60 1/2 90° Elbow 5.6(80) 4 33.1 (10) (1525) 3/4 Straight 8.0(115) 4 29.1 (8.8) 3/4 90°Elbow 8.0(115) 4 32.2(9.8) 1/2 Straight 5.6(80) 4 28.4(8.6) 72 1/2 90° Elbow 5.6(80) 4 40.4(12.3) (1830) 3/4 Straight 8.0(115) 4 35.5(10.8) 3/4 90° Elbow 8.0(115) 4 39.5(12) FM Notes: 1.RASCOFLEXTm Sprinkler Connections have been tested and approved by FM Approvals for use in wet, preaction,and dry sprinkler systems per FM data sheets 2-0,2-5,and 2-8 per FM1637. 2.Maximum sprinkler K-Factor:5.6(80 metric)for 1/2-inch reducer and 8.0(115 metric)for 3/4-inch reducer. 3.Differences in equivalent lengths are due to varying test methods,per FM 1637 standards. 4.Above data of friction loss for use with 6.1"straight reducers. Bulletin 213 Reliable Page 6 of 6 July 2019 www.reliablesprinkler.com PIPE _ _ at - i - - . ..: - _ - - OM�" 4 �.. _ '�L....-- — _ - - s i -- _ _ - - NM IMM — Yr _ a - _ rt - - M c - r - -- ,. n t ,li .`mi - -- - _ - me ii _ _ _ - NM - MI rf — — .. _ ____=-- _- . ----- _ NM MN SPRINKLER PIPE Trust Bull Moose when it comes to protecting your most valuable assets. As the leading manufacturer of steel sprinkler pipe, we understand that there are no second chances in fire suppression. You need products of enduring quality and exceptional strength—plus reliable service. You need Bull Moose. OTHER BFREFITS/SERVICEF • UL listed(US&Canada)and FM approved • We have the most stocking locations in industry,for best delivery and availability • ASTM A135 and A795 Type E, Grade A Certified • Plain end or roll groove • Complies with NFPA-13,13R and 14 • Eddy Guard lP'bacterial-resistant internal coating • Industry-leading hydraulic characteristics. • Custom length options • CRR of 1.0 and greater • Hot dipped galvanization • All pipe N DT weld tested • Reddi-Pipe®red pipe to eliminate field painting Exclusive maker of Reddi-Pipe ' • Compatible for use in wet,dry, preaction red painted pipe. and deluge sprinkler systems A c ut us LISTED rM APPROVED MO API. NFPA` `"""`°"r7 BprMklee A.sec lut un `- 1LJ2/, ' 800.325.4461 - . sales@bullmooseindustries.com -' n BULL NECIOSE. i T oosetube.com - Bull Moose Fire Sprinkler Pipe Product Information •I Pipe Size(1n1C ,`r`'' 1" 1-1/4" 1-1/2" 2" 2-1/2" 3" 4" 6° 8" 00.(in) 1.660 1.900 2.375 2.875 3.500 4.500 ID.(in) 1.530 1.728 2.203 2.705 3.334 4.310 Empty Weight(Ib/ft) 1.222 1.844 2.330 2.809 3.361 4.968 CD J Water Filled Weight(lb/ft) 2.019 2.860 3.982 5.299 7.144 11.290 LJ }, cR.R. j 1.98 3.44 2.78 1.66 1.00 1.00 0 PiecesperLift I 61 61 37 30 19 19 W Lift Weight(Ibs)21'lengths 1,565 2,362 1,810 1,770 1,341 1,982 Lift Weight(Ibs)24'lengths 1,789 2,700 2,069 2,022 1,533 2,265 I Lift Weight(Ibs)25'lengths ' 1,864 2,812 2,155 2,107 1,596 2,360 O.D.(in) 1.315 1.660 1.900 2.375 2.875 3.500 4.500 6.625 8.625 . i 1.0.(in) 1.097 1.442 1.682 2.157 2.635 3.260 4.260 6.357 8.249 i CD IL— Empty Weight OWN 1.410 1.810 2.090 2.640 3.530 4.340 5.620 9.290 16.940 1 Lu Water Filled Weight(Ib/ft) 1.820 2.518 3.053 4.223 5.893 7.957 11.796 23.038 40.086 1 G C R.R. 15.27 9.91 7.76 6.27 4.92 3.54 2.50 1.158 1.805 W = Pieces per Lift 91 61 61 37 30 19 19 10 7 u V1 Lift Weight Rs)21'lengths 2,695 2,319 2,677 2,051 2,224 1,732 2,242 1,951 2,490 Lift Weight(Ibs)24'lengths 3,079 2,650 3,060 2,344 2,542 1,979 2,563 2,230 2,848 Lift Weight(Ibs)25'lengths 3,208 2,760 3,187 2,442 2,648 2,062 2,670 0.0.(in) 1.295 1.650 1.900 2.375 p 1.0.(in) I 1.083 1.418 1.645 2.123 Empty Weight(Ib/ft) 1.461 2.070 2.547 3308 CD Q Water Filled Weight(lb/ft) 1.860 2.754 3.468 4.842 W CY C.R.R. 1.00 1.00 1.00 1.00 I-- ›— Pieces per Lift 70 51 44 30 i0 Lift Weight(Ibs)2l'lengths 2,148 2,217 2,353 2,084 W lift Weight(Ibs)24'lengths 2,454 2,534 2,690 2,382 Lift Weight(Ibs)25'lengths 2,557 2,639 2,802 2,481 O D.(in) 1.315 1.660 1.900 2.375 2.875 3.500 4.500 I.D.(in) 1.049 1380 1.610 2.067 2.469 3.068 4.026 C EmptyWeight(Ib/ft) 1.680 2.270 2.720 3.660 5.800 7.580 10.800 d . J Water Filled Weight(Ib/ft) ( 2.055 2.918 3.602 5.114 7.875 10.783 16.316 = G _CR4 1.00 1.00 1.00 1.00 1.00 1.00 1.00 W - Pieces per Lift 70 51 44 30 30 19 19 N Lift Weight(Ibs)21'lengths 2,470 2,431 2,513 2,306 3,654 3,024 4,309 Lift Weight(Ibs)24'lengths 2,822 2,718 2,872 2,635 4,176 3,456 4,925 1 Lift Weight(lbs)25'lengths 2,940 2,894 2,992 2,745 4,350 3,601 5,130 104 . .,, 800.325.4467 1 BULL sales®builmooseindustries.com ]y[OOSE� Ha ; f r ooseTube.com -- - FireLock® Rigid Coupling Style 005H jctaultc" with Vic-Plus" Gasket System 10.02 Material Specifications: Housing: Ductile iron conforming to ASTM A-536, grade 111111 �1� 65-45-12. Ductile iron conforming to ASTM A-395, grade 65-45-15, is available upon special request. Patented Exaggerated for clanty Housing Coating: (specify choice) tOMIS Standard: Orange enamel (North America); red et System enamel (Europe) ❑ Optional: Hot dipped galvanized Approvals/Listings: LPCB; Coupling Gasket: (specify choice) CO" ® Vd5 LIST® NOTE:Additional gasket styles are available.Contact Victaulic for details. 104-1a/02 See Vctaubc Publication 10.01 for more details. ❑ Grade "E" EPDM Type A Vic-Plus- Gasket System' LPC and VdS Approved,see notes on page 3 EPDM (Violet color code). FireLock products have been Listed by Underwriters Laboratories Inc.and Approved by Factory Mutual Research for wet and dry(oil free air) Product Description: sprinkler services up to the rated working pressure using the Grade"E"Type A Vic-Plus'Gasket System, requiring no field FireLock Style 005H rigid coupling has a unique, lubrication for most installation conditions. patented angle-pad design which allows the housings ❑ Grade "L" silicone to offset while clamping the grooves. By permitting the housings to slide on the angled bolt pads, rigidity is Recommended for dry heat,air without hydrocarbons to obtained. +350°F and certain chemical services. Support and hanging requirements correspond to For dry services, Victaulic continues to recommend the NFPA 13 Sprinkler Systems. Angle-pad design permits use of Grade "E" Type A FlushSeal®Gasket. assembly by removing one nut/bolt and swinging the Contact Victaulic for details. housing over the gasket. This reduces components to handle during assembly. Bolts/Nuts: Heat-treated plated carbon steel, trackhead Style 005H FireLock coupling are designed and meeting the physical and chemical requirements of recommended for use ONLY on fire protection systems. ASTM A-449 and physical requirements of ASTM A-183. ' Standard gasket and FlushSeal gasket approved for dry pipe systems to Vic-Plus'Gasket System: —40°F/-40°C.Based on"typical"pipe surface conditions,supplemental lubricant is recommended for services installed below 0°F/-18°C and Victaulic offers a gasket system which requires no field for all dry pipe systems or systems to be subjected to air tests prior to lubrication on wet pipe systems that are hydrostatically being filled with water.Supplemental lubrication may also be required on tested. The Vic-Plus System (patented) is dry, clean, pipe with raised or undercut weld seams or pipe that has voids and/or cracks at the weld seams.Victaulic continues to recommend the use of and non-toxic. It reduces assembly time substantially FlushSeal gaskets for dry services. and eliminates the mess and chance of over-lubrication. Please refer to the latest copy of the Victaulic Field Installation Handbook (1-100)for supplemental lubrication requirements and dry pipe fire protection system notes. Job/Owner Engineer System No. Spec Section • Location Paragraph Contractor Approved • Submitted By Date Date victaulic.com 1 Couplings I Rigid I Style 005H I Publication 10.02 10.02 1538 Rev M Updated 10/2014 e 2014 Victaulic Company.All rights reserved. 1 tctaulrc' victaulic.com I Couplings I Rigid I Style 005H I Publication 10.02 Dimensions: Y z-�I Rated for wet and dry sprinkler systems at 350 psi/2413 kPa ._� for 1 ya-4"/32-100 mm sizes and 300 psi/2068 kPa for liL��►AL Ierin�l M��� -� .I Sc4 hedule e'4 08-or 0r mm sizes;Steeepule 10 roll 05H is or �� `�" Schedule 40 cut or roll grooved steel pipe.Style 005H is rigid �� �,�,� and does not accommodate expansion,contraction or angular deflection. 1 Actual Maximum Maximum Allow. Approx. Nominal Outside Working End Pipe End Dimensions Weight Size Diameter Pressure'+ Load' Separation' Bolt/Nuta X Y Z Each inches inches psi lbs. inches No.-size inches inches inches lbs. mm mm kPa N mm inches mm mm mm kg 13/4 1.660 350 755 0.05 2.75 4.50 1.88 12 32 42.4 2413 3370 1.2 2-a/e x 214 70 114 48 05 11: 1.900 350 990 0.05 3.00 4.75 1.88 1.2 40 48.3 2413 4415 1.2 2-3/ex23/4 76 121 48 0.5 2 2.375 350 1550 0.07 3.50 5.25 1.88 1.6 50 603 2413 6900 1.7 2-'/a x 21/2 89 133 48 0.7 21/2 2.875 350 2270 0.07 4.00 5.75 1.88 1.9 65 73.0 2413 10110 1.7 2-3/ex21/2 102 146 48 .09 3.000 350 2475 0.07 4.13 5.75 1.88 1.9 76.1 mm 76.1 2413 11010 1.7 2-'/s x 2'/z 105 146 48 0.9 3 3.500 350 3365 0.07 4.63 6.13 1.88 2.1 80 88.9 2413 14985 1.7 2-3/4 x 21/2 118 156 48 1.0 4 4.500 350 5565 0.16 5.75 7.25 2.13 3.1 100 114.3 2413 24770 4.1 2-3/4 x 21/2 146 184 54 1.4 4.250 300 4255 0.16 5.63 7.25 2.13 3.1 108.0mm 108.0 2068 18940 4.1 2-a/a x 2'h 143 184 54 1.4 5 5.563 300 7290 0.16 6.88 9.00 2.13 4.5 125 141.3 2068 32445 4.1 2-112 x 3 175 229 54 2.0 5.250 300 6495 0.16 6.63 9.00 2.13 4.5 133.0mm 133.0 2068 28900 4.1 2-'hx23/` 168 229 54 2.0 5.500 300 7125 0.16 6.88 9.00 2.13 4.8 139.7mm 139.7 2068 31715 4.1 2-%:x2'/a 175 229 54 2.2 6 6.625 300 10340 0.16 8.00 10.00 2.13 5.0 150 168.3 2068 46020 4.1 2-1/2 x 3 203 254 53 2.3 6.250 300 9200 0.16 7.63 10.00 2.13 5.5 159.0mm 159.0 2068 40955 4.1 2-''/:x2ah • 194 254 54 2.5 6.500 300 9955 0.16 8.15 10.00 2.13 5.5 165.1 mm 165.1 2068 44295 4.1 2-'/z x 3 207 254 54 2.5 8 8.625 300 17525 0.19 10.50 13.14 2.63 11.3 200 219.1 2068 78000 4.8 2-s/e x 4'A 267 334 67 5.1 1 Working Pressure and End Load are total,from all internal and external loads,based on standard weight(ANSI)steel pipe,standard roll or cut grooved in accordance with Victaulic specifications.Contact Victaulic for performance on other pipe.WARNING:FOR ONE TIME FIELD TEST ONLY,the Maximum Joint Working Pressure may be increased to 11/2 times the figures shown. 2 The allowable pipe separation dimension shown is for system layout purposes only.Style 005H couplings are considered rigid connections and will not accommodate expansion or contraction of the piping system. 3 Number of bolts required equals number of housing segments.Metric thread size bolts are available(color coded gold)for all coupling sizes upon request. Contact Victaulic for details. 4 Style 005H couplings are VdS and LPC Approved to 16 Bar/235 psi. 10.02 1538 Rev M Updated 10/2014 02014 Victaulic Company.All rights reserved. victaulic.com 2 rctaul,c' victaulic.com I Couplings I Rigid I Style 005H I Publication 10.02 Listings/Approvals; The information provided below is based on the latest listing and approval data at the time of publication. Listings/Approvals are subject to change and/or additions by the approvals agencies. Contact Victaulic for performance on other pipe and the latest listings and approvals. Related Working Pressure Related Working Pressure Related Working Pressure psi psi psi Pipe Size Pipe Size Pipe Size Sch. inches UL ULC FM Sch. inches UL ULC FM Sch. inches UL ULC FM 5 11-3 175 175 175 EL l/a-2 300 N/A N/A MT 1%4-2 300 N/A N/A 11/4-3 350 350 350 ET 11/4-2 300 N/A N/A STF 1/-4 N/A N/A 300 10,40 5-8 300 300 300 EZ 4-6 3006 N/A 300 Steady 11/4-2 N/A N/A 300 Thd. BLT 11/4-2 300 300 N/A FF 11/4-4 N/A N/A 300 TF 3-8 N/A N/A 300 DF 11/4-4 300 300 300 GAL-7 1Y-2 300 N/A N/A WL5 1'/4-2 300 300 N/A DT 1'/4-2 300 300 N/A MLT 11/4-2 300 N/A N/A XL 114-3 300 300 300 EF 11/4-4 175' N/A 175 MF 11/4-4 300 N/A 300s 5 FM approved for service in 1 1/2—4'pipe. 6. UL Listed for service up to 4'pipe only. 7 UL Listed for service up to 3'only. Installation Nate Reference should always be made to the I-100 Victaof.c Meld Installation Handbook for This product shall be manufactured by Victaulic or to Victaulic specifications.All products the product you are metalling.Handbooks are included with each shipment of Victaulic to he installed in accordance with current Victaulic installation/assembly instructions. products for complete installation and assembly data,and are available in PDF format Victaulic reserves the right to change product specifications,designs and standard on our website at www.victaulic.com. equipment without notice and without incurring obligations. Warranty Trademarks Refer to the Warranty section of the current Price List or contact Victaulic for details. Victaulic®is a registered trademark of Victaulic Company. 10.02 1538 Rev M Updated 10/2014 e 2014 Victaulic Company.All rights reserved. victaulic.com 3 rctaultc' CARBON STEEL PIPE-GROOVED FITTINGS 0 I Grooved End Fittings 040. ® SAC B SEE VICTAULIC PUBLICATION lO.OFOR DETAILS .............. . Victaulic offers a broad line of fittings in sizes through 48"/1200mm in a variety of straight and reducing styles.Most standard fittings are cast of durable ductile iron to precise tolerances. 4,0Alw- Victaulic standard fittings pressure ratings conform to the ratings of Victaulic Style 77 couplings. All fittings are supplied with grooves or shoulders to permit fast installation without field preparation. The grooved design permits flexibility for easy alignment. These fittings are not intended for use with Victaulic couplings for plain end pipe(refer to Section 14.04 for fittings available for plain end applications). Fittings are provided in various materials including ductile iron,steel or segmentally welded steel NO.20 TEE depending on styles and size.Fittings are painted orange enamel with a galvanized finish available as an option,contact Victaulic for details. Victaulic fittings are designed specifically for use in grooved piping systems. Fittings are provided 4y4 , grooved or with shoulders conforming to standard steel pipe outside diameters.When connecting wafer or lug-type butterfly valves directly to Victaulic fittings with 741 or 743 Vic-Flange®adapters, check disc clearance dimensions with I.D.dimension of fitting. Note:The following Victaulic fittings are VdS approved:NO.10 90"Elbow,NO.11 45"Elbow,NO.20 Tee and NO.60 Cap. Note:The following Victaulic fittings are LPCB approved:NO.10 90"Elbow,NO.11 45"Elbow, No.10 ELBOW NO.12 221/2"Elbow,NO.13 1114"Elbow,NO.30 45"Lateral,NO.30-R Reducing Lateral,NO.100 Long Radius Elbow,NO.110 Long Radius Elbow,NO.20 Tee,NO.35 Cross,NO.60 Cap,NO.25 Reducing Tee,NO.33 True Wye,NO.50 Concentric Reducer,NO.51 Eccentric Reducer,NO.29M Tee with Threaded Branch,NO.27 Standpipe Tee,and NO.32 Tee Wye. Advanced Groove System-For 14-24'/350-600mm piping systems,Victaulic now offers the Advanced Groove System(AGS).Refer to Section 20.05 for AGS fitting details. Stainless Steel-Grooved end fittings are available in Schedule 10 Type 316 stainless steel(Schedule 5,40 and Type 304 available as an option)in various sizes.Fitting center-to-end dimensions will vary 0 depending upon type and schedule.Refer to Section 17.04 and 17.16 for details. Aluminum-Grooved end fittings are available in aluminum alloy 356 T6,in sizes from 1-8"/25-200mm.Refer to Section 21.03 or contact Victaulic for details. AGS-ADVANCED GROOVE SYSTEM ALTERNATE STYLES Extra Heavy EndSeal®"ES"Fittings-EndSeal fittings are available in 2-12"/50-300mm for use with"ES"grooved pipe and HP-70ES EndSeal couplings."ES"fittings are painted black for easy identification.EndSeal(and standard)fittings may be easily internally coated(by others)for severe service requirements.Always specify"ES EndSeal fittings"when ordering.See Section 07.03 for information on EndSeal fittings. Fittings Machined for Rubber or Urethane Lining(MRL)-For severe abrasive services,Victaulic fittings may be rubber or urethane lined(by others).Lining may be inside diameter/end(abrasion resistance)or wrap-around(corrosion and/or abrasion)machined.Refer to Section 25.03 or contact Victaulic for specific details. Note:Fittings are available with a variety of coatings upon request such as hot dip galvanized,epoxy, glass lined and others. JOB/OWNER CONTRACTOR ENGINEER System No. Submitted By Spec Sect Para Location Date Approved Date www.victaulic.com jotaulic' VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY 0 2010 VICTAULIC COMPANY.ALL RIGHTS RESERVED. REY_N 07.01_1 CARBON STEEL PIPE-GROOVED FITTINGS 07.01 Grooved End Fittings MATERIAL SPECIFICATIONS Fitting: Ductile iron conforming to ASTM A-536,grade 65.45.12. Ductile iron conforming to ASTM A-395,grade 65-45-15, is available upon special request. • Or:Segmentally welded steel as shown under nipples Nipples:(adapter,swaged&hose) • 3/4—4720—100mm:Carbon steel, Schedule 40,conforming to ASTM A-53,Type F • 5—67125— 150mm: Carbon steel, Schedule 40,conforming to ASTM A-53,Type E or S, Gr. B • 8—127200—300mm: Carbon steel, Schedule 30 or 40,conforming to ASTM A-53,Type E or S,Gr. B Flanged Adapter Nipples: (Nipple—see above) • Class 125 Flange:Cast iron conforming to ANSI B-16.1 • Class 150 Flange:Carbon steel conforming to ANSI B-16.5, raised or flat face • Class 300 Flange:Carbon steel conforming to ANSI B-16.5, raised or flat face Fitting Coatings:Orange enamel • Optional: Hot dip galvanized and others.Some fittings supplied electroplated as standard—see product specifications. Flanged Adapter Nipple Coating: None(Unfinished) • Optional:Orange enamel, hot dip galvanized and others. www.victaulic.com VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY®2010 VICTAULIC COMPANY ALL RIGHTS RESERVED. ul.'ita Vlld 07.01_2 REV._N CARBON STEEL PIPE-GROOVED FITTINGS 07.01 Grooved End Fittings FLOW DATA The chart expresses the frictional resistance of various Victaulic fittings as equivalent feet of straight (Frictional Resistance) pipe.Fittings not listed can be estimated from the data given,for example,a 221/°elbow is approximately one-half the resistance of a 45°elbow.Values of mid-sizes can be interpolated. Size Dimension-Feetimeters d: Elbows Tees 90`Elbows 45'Elbows Actual No.100 No.110 0 Nominal Outside No.10 1 ii 0 No.11 1 k D 'l'! Size Dia. Std. Long Std. Long In.lmm In./mm Radius Radius Radius Radius Branch Run 1 1.315 1.7 0.8 4.2 17 25 33.7 0.5 0.2 1.3 1 0.5 2 2.375 3.5 2.5 1.8 1.1 8.5 3.5 50 60.3 j 1.1 l 0.8 05 0.3 2.6 1.1 76.1 mm 3.000 4.3 _ 2.1 - 10.8 4.3 76.1 1.3 0.7 3.3 1.3 3 3.500 5.0 38 26 1.6 13.0 5.0 80 899 I 1.5 1.2 0.8 0.5 4.0 15 108.0 mm 4.250 6.4 - 3.2 15.3 6.4 108.0 2.0 09 4.7 2.0 4 4.500 6.8 50 34 2.1 160 68 100 114.3 2.1 1.5 10 0.6 4.9 2.1 133.0 mm 5.250 8.1 _ 4.1 20.0" 8.1 133.0 2.5 1.2 6.2 2.5 139.7 mm 5.500 • 8.5 _ 4.2 21.0 8.5 139.7 2.6 1.3 04 26 5 5 563 i 8.5 4.2 21.0 8.5 125 141.3 26 1.3 64 2.6 159.0 mm 6250 94 _ 4.9 _ 25.0 9.6 159.0 2.9 1.5 7.6 2.9 165.1 mm 6.500 9.6 - 50 - 25.0 10.0 165.1 2.9 1,5 7.6 3.0 6 6.625 10.0 7.5 5.0 3.0 25.0 10.0 150 168.3 ,4, 3.0 2.3 15 0.9 7.6 3.0 _ 8 8625 13.0 9.8 6.5 4.0 33.0 13.0 200. 2191 j, • 4.0 3.0 2.0 1.2 10.1 4.0 10 ' 10.750 17.0 120 8.3 5.0 41.0 17.0 250 273.0 5.2 3.7 2.5 1.5 125 5.2 12 12.750 20.0 14.5 100 6.0 500 20.0 300 323.9 6.1 44 3 0 1.8 15.2 6.1 14 14.000 24.5 4 158 18.5 4 11.0 70.0 23.0 350 355.6 7' 4.8 5.6 34 21.3 7.0 16 16000 2804 18.0 2104 130 800 27.0 400 406.4 fly 5.5 64 4.0 244 8.2 18 18.000 31.04 20.0 23.5 4 143 90.0 30.0 450 4570 9.5 61 72 4.3 27.4 9.1 20 20.000 34 0§ 22.5 25.5 4 16.0 100.0 33.0 800 508.0 10. 6.9 78 4.9 30.5 10.1 24 24.000 42.0 4 27.0 295 4 '9.0 120.0 400 600 610.0 °° 8.2 9.0 5.8 366 12.2 26 26.000 28.0 20.5 130.0 43.0 650 660.4 8.5 # 5.3 39,6 13,1 30 30.000 34.0 240 150.0 50.0 750 762.0 # 104 # 73 45.7 15.2 36 i 36.000 40.5 78.5 180.0 60.0 900 914.0 # 12.3 # 8 7 54.9 18.3 42 42000 470 330 2100 70.0 1050 10670 # 14.3 # 10.1 64.0 213 #Contact Victaulic for details. #For use on cut grooved systems only.For roll grooved systems,Victaulic offers the Advanced Groove System(AGS).For pricing and availability of cut groove fittings in this size,contact your nearest Victaulic sales office. §Fitting flow data for 14-247350-600 mm size NO.10 and NO.11 Elbows is based on fittings for Style 07 and 77 couplings.For flow data on AGS fittings(NO.W10 and NO.W11 Elbows),refer to submittal 20.05. Note.All fittings are ductile iron unless otherwise noted with an"sw"or"s".SW=Segmentally Welded. S=Carbon Steel www.victaulic.com VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY.0 2010 VICTAULIC COMPANY.ALL RIGHTS RESERVED. ictauIl�. REV,_N 07.01__3