Specifications -avoSs-c at4y
r c\q Su:►20AcL5(. ��
i
STRUCTURAL CALCULATIONS
FOR RECEIVED
MAY 8 2018
ARBOR HEIGHTS CITY OF TIGARD
BUILDING DIVISION
15 025 SW ROYALTY PARK
TIGARD, OR 97224
-- COVERED DECK --
0 PROF8f�o
444 12,187 .0
ORE ON fin
✓O ✓G�r
��
1 5. 19 �G
6',1/ E.
NOFLO�`
EXPIRES:12/31/18
OFFICE COPY
Contents
Gravity Calculations G1 -G7
Lateral Calculations L1 -L3
Contact Person: John E Nordling,PE Foundation Calculations Fl -F5
NORDLING Proj. No.: 18-132
STRUCTURAL ARBOR HEIGHTS POOL SHELTER
ENGINEERS, LLC HARRISON ROYCE ARCHITECTURE
6775 SW 111th,Suite 200•Beaverton OR,97008 Date:APR 2018 By:JEN Sheet No.: COVER
.
r
16A'
JrQ
O
Ics,L 0,
0,
N L T J
8 2' 0 S
0 .
il mi
im
CD
® =
gm a
imi 0
w
r 1 1 ;;I:
til
01® 6► N
iil=
. W •0
--_-__--__ - I IN .... 0
r — \ 1 I \\\
— \ \,
il \ i''s \Al ) 0
WIND: 20 If
E3: 70 �If
_ 1111 I IIII IIIIIIIIIIIIIII IIi 1 1111 WIWI 111111111 I IIII IIIII1_;
,1.3%, 27.7' 13'
303'
NORDLING Proj. No.: 18-132
STRUCTURAL ARBOR HEIGHTS POOL SHEL1'hR
„,,,.„ .6.. ,
ENGINEERS, LLC HARRISON ROYCE ARCHITECTURE
6775 SW 111th,Suite 200•Beaverton OR,97008 Date:APR 2018 By:JEN Sheet No.: PI
E.
11 r i
® // -- /7� \\ ,-- \\ 230
1 ,/ \ r \�
_ / •'' /k/ 1\S1[.
•
�/
/ \�:, /h,\ \\
(/ �'�� // v-•\ 1 \
• _ 390
I r- // ft ii
,� 6,10
1 1 I
1 1 I
1 I I
L_- _
4 --T
L__., I I r-
® '� 4
T[ ® 650 c2
`--1-1— __L;---A 300
460
0 o 0o
14
cl
WIND
-
SEISMIC
NORDLING Proj. No.: 18-132
4
STRUCTURAL ARBOR HEIGHTS POOL SHELTER r,pl
\> ENGINEERS, LLC HARRISON ROYCE ARCHITECTURE
6775 SW 111th,Suite 200•Beaverton OR,97008 Date:APR 2018 By:JEN Sheet No.: P2
41 2x T4G DECKING
42 TRUSS
PSP PSF
W DL 15 per DL LL TW
15 25
7°2' o/c
LL 25 par
W DL 110 pir
LL 1/5 ph" e,
9 ,�Y'
I - ,- row
s o,`ry�
; : 3423,fd)
W
(NI R DI-. 312'
ib80 be.LLLLf LL 2,800 lbs
ti
LI
11-6" 1 ah :,,,, : r( b"x<i,r'•'i5
z ,,4.31:"rc,,_^.
kJa 'ii ti„ •irs%t:f ?ivyr{ t "fy ' nn��:gl .:•
i'4:xFrp�6,<y'' 7
1.
i`
.`!`» O�:SX ' -: 1t't , yeL '''''a -ii VJ?s ,:4,-4•�'fi .,V . ,—fYFy',i„ :s ,1 { !ir1.=y :r;, 4 �, � � 1"rrGf ?xa rt s'; ^',-? �,dc/-Ff, e`i
` o:t i�X, , ,, � =q ,*- a' j ' Iexxa� .2X6 DF-i,No.2 �., ii .j Jnrr,�`� 4 {„RS R2 RDL 33 33I
LL 43 43
I 11 76 76
brg I, 0.08” 0.08"
I V MAX 76 lbs
Self Wt
M MAX 143 ft-lbs 11 96 p f
I V (co 67 lbs 1
fv 12 <
tb 226 < 207 psi I
1,346 psi
Si
I ADL -0,02
I ALL -0.02
LL/+999
ok
A n• -0.04
L/+999
'CR 1.001
Co 1,15i I C 1.00
Cf 1.30
___ NORDLING
STRIICTITRAL
Proj, No.: 18-132
-,/ ENGINEERS, LLC ARBOR HEIGHTS POOL SHELTER
HARRISON ROYCE ARCHITECTURE
6775 SW I I lth,Suite 200•Beaverton OR,97008
Date:APR 2018 By:JEN Sheet No.:G1
Geometry data 42
Nodes
Node X Y Z Rigid Floor
[in] [in] [in]
1 0.00 0.00 0.00 0
2 103.50 51.70 0.00 0
3 171.20 85.60 0.00 0
4 238.80 51.70 0.00 0
5 342.30 0.00 0.00 0
6 171.20 37.10 0.00 0
Restraints
- Node TX TY TZ RX RY RZ
1 1 1 1 0 0 0
5 0 1 1 0 0 0
Members
Member NJ NK Description Section Material dO dL Ig factor
(in) [in]
1 1 2 Chord S4S 8x12 DFir-L_No1_beam 0.00 0.00 0.00
2 2 3 Chord S4S 8x12 DFir-L_No1_beam 0.00 0.00 0.00
3 5 4 Chord S4S 8x12 DFir-L_No1_beam 0.00 0.00 0.00
4 4 3 Chord S4S 8x12 DFir-L_No1_beam 0.00 0.00 0.00
5 2 6 Web S4S 8x8 DFir-L_No1_beam 0.00 0.00 0.00
6 6 5 Web S4S 8x8 DFir-L_No1_beam 0.00 0.00 0.00
7 1 6 Web S4S 8x8 DFir-L_No1_beam 0.00 0.00 0.00
8 6 4 Web S4S 8x8 DFir-L_No1_beam 0.00 0.00 0.00
Hinges
Node-J Node-K
Member M33 M22 V3 V2 M33 M22 V3 V2 TOR AXL Axial rigidity
2 0 0 0 0 1 1 0 0 0 0 Full
5 1 1 0 0 1 1 0 0 0 0 Full
6 1 1 0 0 1 1 0 0 0 0 Full
7 1 1 0 0 0 0 0 0 0 0 Full
8 1 1 0 0 1 1 0 0 0 0 Full
Load data
Load conditions
Condition Description Comb. Category
DL Dead Load No DL
LL Live Load No SNOW
LC1 DL+LL Yes
Distributed force on members
Condition Member Dirt Vail Va12 Dist1 % Dist2 %
[Lb/ft] [Lb/ft] [in] [in]
DL 1 Y -110.00 -110.00 0.00 No 100.00 Yes
2 Y -110.00 -110.00 0.00 No 100.00 Yes
3 Y -110.00 -110.00 0.00 No 100.00 Yes
4 Y -110.00 -110.00 0.00 No 100.00 Yes
LL 1 Y -175.00 -175.00 0.00 No 100.00 Yes
2 Y -175.00 -175.00 0.00 No 100.00 Yes
3 Y -175.00 -175.00 0.00 No 100.00 Yes
4 Y -175.00 -175.00 0.00 No 100.00 Yes
NORDLING Proj. No.: 18-132
STRUCTURAL ARBOR HEIGHTS POOL SHELTER
ilI ENGINEERS, LLC HARRISON ROYCE ARCHITECTURE
6775 SW 111th,Suite 200•Beaverton OR,97008 Date:APR 2018 By: JEN Sheet No.: G2
Wood Design A2
Design code: AF&PA NDS-ASD-2005
Report: Summary-For all selected load conditions
Load conditions to be included in design:
LC1=DL+LL
Description Section Member Ctrl Eq. Ratio Status Reference
Chord S4S 8x12 1 LC1 at 100.00% 0.95 OK (Eq.3.9-3)
2 LC1 at 0.00% 0.96 OK (Eq.3.9-3)
3 LC1 at 100.00% 0.95 OK (Eq.3.9-3)
4 LC1 at 0.00% 0.96 OK (Eq.3.9-3)
Web S4S 8x8 5 LC1 at 0.00% 0.10 OK (Eq.3.9-1)
6 LC1 at 0.00% 0.10 OK (Eq.3.9-1)
7 LC1 at 0.00% 0.10 OK (Eq.3.9-1)
8 LC1 at 0.00% 0.10 OK (Sec.3.8)
4Ailli ,„
i"
4.4 k / 1,894 lbs = 2.3 bolts (3) bolts -ok- 4
3.1 k / 1,894 lbs = 1.9 bolts (2) bolts -ok-
2.5 k / 1,894 lbs = 1.3 bolts (2) bolts -ok-
2.5 k / 1,519 lbs = 1.6 bolts (2) bolts -ok-
CONNECT W/ 543'0 M. BOLTS
NORDLING Proj. No,: 18-132
STRUCTURAL ARBOR HEIGHTS POOL SHELTER
J J ENGINEERS, LLC HARRISON ROYCE ARCHITECTURE
6775 SW 111th,Suite 200•Beaverton OR,97008 Date:APR 2018 By:JEN Sheet No.: G3
,
DOUBLE SHEAR BOLT CAPACITIES (PER 2005 NDS)
0
Bolt Main Member Side Member-Steel
Size 5/8" 0 Member 8x12 Member 1/4" Steel Plate
Root Diameter 0.526 Species DF-L#1 VGDL Species Steel A36
Fyb 45,000 Load Angle 0° Load Angle 0°
#in Row (2) Thickness 7.25 Thickness 0.25
Spacing in Row 12" Width 11.25 Width 12
Row Spacing 2" E 1,700,000 E 29,000,000
Re 0.10 Fejt 5,600 Feil 58,000
Rt 29.00 Fe_l_ 3,100 Fe_1_ N.A.
4 1.000 Fe4,m 5,600 Fe.s 58,000
ki 1.13 k2 0.49 k3 7.51
Snacine Distance Edge Distance End Distance
minimum 2.50" 1/D 0.40 minimum i I 4.38"
minimum 0.94" minimum__ 2.50"
Row Snacine
minimum j 0.94"
minimum j_ 0.94"
1 T'= 7,052 lbs
Z'= 1,894 lbs Adjustment Factors
YeildMode CD 1.15 Snow
Mode lin (113-7) Z= 5,338 lbs Cm 1,00 Dry
Mode Is (11.3-8) Z= 3,813 lbs Ct 1.00 T<=100°
Mode Ills 01.3-9) Z= 1,648 lbs Cg 1.00 Group Action
Mode IV (113-10) Z= 2,140 lbs Co 1,00 Distance&Spacing
639°
{ T'= 7,052 lbs
Z'= 1,519 lbs Adjustment Factors
Yelld Mode CD 1.15 Snow
Mode Im (113-7) Z= 3,650 lbs CM 1.00 Thy
Mode 15 (11.3-8) Z= 3,440 lbs Ct 1.00 T<=100°
Mode III, (11.3-9) Z= 1,321 lbs Cg 1.00 Group Action
Mode IV (11.3-1o) Z= 1,699 lbs CA 1.00 Distance&Spacing
NORDLING Proj. No,: 18-132
5S,hRUC,rUR�L ARBOR HEIGHTS POOL SHELTER
III ENGINEERS, LLC HARRISON ROYCE ARCHITECTURE
6775 SW 111th,Suite 200•Beaverton OR,97008 Date: APR 2018 By: JEN Sheet No,: G4
43 2x T4G DECKING 44 TRUSS
PSP PSF PSP PSF
DL LL TW DL LL 1W
15 25 0' - 26' 15 25 1.5' / 2
1.2' •coe(45')/2 = 2.6' W DL 56 plf
LL 100 plf
PDL 130 lbe BEAM A3 WN),
LL 202 lbe �01,
zo
c9 ryry, 1),
019;',.;.4m �L A3
211 II/ IIB
(0,18b) II (18 ,18.6)
0 Kl s
1'
(145 0):: e1 4 (1145,0)
W
1 1 1 1 1 1 will
RIX. 580 lbs
LL 950 lbe
16.0'
93I ,,
MAX AXIAL LOAD = 2000 lbs
USE (2) 2x FASCIA
2.0 k / 1,844 lbs = 1.05 bolts (2) bolts -ok-
2x6 DF-L No.2
R1 R2
RDL 70 130 CONNECT W/ Sia' M. BOLTS
LL 101 202
rl. 170 332
brgL 0.18" 0.35"
✓ MAX 332 lbs Self Wt
M MAX 598 fl-lbs 1.96 plf
✓ (d) 284 lbs 1
fv 52 < 180 psi 1
fb 948 < 1,170 psi
Si
ADL -0.11
1 A LL -0.16
L/678
ok
•n. -0.27
L/408
CR 1.001 I Ci, 1.001
CD 1.001 1 Cf 1.301
NORDLING Proj. No.: 18-132
STRUCTURAL ARBOR HEIGHTS POOL SHEL 1'hR
J` ENGINEERS, LLC HARRISON ROYCE ARCHITECTURE
6775 SW 111th,Suite 200•Beaverton OR,97008 Date: APR 2018 By: JEN Sheet No.: G5
Geometry data
Nodes
Node X Y Z Rigid Floor
[in] [in] [in)
1 14.50 135.00 0.00 0
2 0.00 153.60 0.00 0
3 14.50 160.80 0.00 0
4 26.80 167.00 0.00 0
5 94.50 200.80 0.00 0
6 162.20 167.00 0.00 0
7 174.50 160.80 0.00 0
8 189.00 153.60 0.00 0
9 174.50 135.00 0.00 0
10 94.50 152.30 0.00 0
11 14.50 0.00 0.00 0
12 174.50 0.00 0.00 0
- Restraints
Node TX TY TZ RX RY RZ
11 1 1 1 0 0 1
12 1 1 1 0 0 1
Members
Member NJ NK Description Section Material dO dL Ig factor
[in] [in]
1 2 3 Chord S4S 8x12 DFir-L_No1_beam 0.00 0.00 0.00
2 3 4 Chord S4S 8x12 DFir-L_No1_beam 0.00 0.00 0.00
3 4 5 Chord S4S 8x12 DFir-L_No1_beam 0.00 0.00 0.00
4 8 7 Chord S4S 8x12 DFir-L_No1_beam 0.00 0.00 0.00
5 7 6 Chord S4S 8x12 DFir-L_No1_beam 0.00 0.00 0.00
6 6 5 Chord S4S 8x12 DFir-L_No1_beam 0.00 0.00 0.00
7 1 10 Web S4S 8x8 DFir-L_No1_beam 0.00 0.00 0.00
8 10 6 Web S4S 8x8 DFir-L_No1 beam 0.00 0.00 0.00
9 9 10 Web S4S 8x8 DFir-L_No1_beam 0.00 0.00 0.00
10 10 4 Web S4S 8x8 DFir-L_No1_beam 0.00 0.00 0.00
11 1 3 Col S4S 8x8 DFir-L_No1_beam 0.00 0.00 0.00
12 9 7 Col S4S 8x8 DFir-L_No1_beam 0.00 0.00 0.00
13 1 11 Col S4S 8x8 DFir-L_No1_beam 0.00 0.00 0.00
14 9 12 Col S4S 8x8 DFir-L_No1_beam 0.00 0.00 0.00
Hinges
Node-J Node-K
Member M33 M22 V3 V2 M33 M22 V3 V2 TOR AXL Axial rigidity
3 0 0 0 0 1 1 0 0 0 0 Full
8 1 1 0 0 1 1 0 0 0 0 Full
9 0 0 0 0 1 1 0 0 0 0 Full
10 1 1 0 0 1 1 0 0 0 0 Full
11 1 1 0 0 1 1 0 0 0 0 Full
12 1 1 0 0 1 1 0 0 0 0 Full
NORDLING Proj. No.: 18-132
STRUCTURAL ARBOR HEIGHTS POOL SHELTER
ENGINEERS, LLC HARRISON ROYCE ARCHITECTURE
6775 SW 111th,Suite 200•Beaverton OR,97008 Date:APR 2018 By:JEN Sheet No.: G6
Load data
Load conditions
Condition Description Comb. Category
DL Dead Load No DL
LL Live Load No SNOW
LC1 DL+LL Yes
Load on nodes
Condition Node FX FY FZ MX MY MZ
[Lb] [Lb] [Lb] [Lb*ft] [Lb*ft] [Lb*ft]
DL 2 0.00 -130.00 0.00 0.00 0.00 0.00
8 0.00 -130.00 0.00 0.00 0.00 0.00
LL 2 0.00 -202.00 0.00 0.00 0.00 0.00
8 0.00 -202.00 0.00 0.00 0.00 0.00
Distributed force on members
Condition Member Dirt Vail Va12 Dist1 % Dist2 %
[Lb/ft] [Lb/ft] [in] [in]
DL 1 Y -56.00 -56.00 0.00 No 100.00 Yes
2 Y -56.00 -56.00 0.00 No 100.00 Yes
3 Y -56.00 -56.00 0.00 No 100.00 Yes
4 Y -56.00 -56.00 0.00 No 100.00 Yes
5 Y -56.00 -56.00 0.00 No 100.00 Yes
6 Y -56.00 -56.00 0.00 No 100.00 Yes
LL 1 Y -100.00 -100.00 0.00 No 100.00 Yes
2 Y -100.00 -100.00 0.00 No 100.00 Yes
3 Y -100.00 -100.00 0.00 No 100.00 Yes
4 Y -100.00 -100.00 0.00 No 100.00 Yes
5 Y -100.00 -100.00 0.00 No 100.00 Yes
6 Y -100.00 -100.00 0.00 No 100.00 Yes
Wood Design
Design code: AF&PA NDS-ASD-2005
Description Section Member Ctrl Eq. Ratio Status Reference
Chord S4S 8x12 1 LC1 at 100.00% 0.04 OK (Sec.3.4)
2 LC1 at 0.00% 0.11 OK (Sec.3.4)
3 LC1 at 37.50% 0.05 OK (Eq.3.9-3)
4 LC1 at 100.00% 0.04 OK (Sec.3.4)
5 LC1 at 0.00% 0.11 OK (Sec.3.4)
1
6 LC1 at 37.50% 0.05 OK (Eq.3.9-3)
Col S4S 8x8 11 LC1 at 0.00% 0.03 OK (Sec.3.6.3)
12 LC1 at 0.00% 0.03 OK (Sec.3.6.3)
13 LC1 at 0.00% 0.16 OK (Eq.3.9-3)
14 LC1 at 0.00% 0.16 OK (Eq.3.9-3)
Web 7 LC1 at 0.00% 0.16 OK (Eq.3.9-1)
8 LC1 at 0.00% 0.03 OK (Eq.3.9-1)
9 LC1 at 0.00% 0.16 OK (Eq.3.9-1)
10 LC1 at 0.00% 0.03 OK (Eq.3.9-1)
NORDLING Proj. No.: 18-132
r, ,
STRUCTURAL ARBOR HEIGHTS POOL SHELTER
ii, If ENGINEERS, LLC HARRISON ROYCE ARCHITECTURE
6775 SW 111th,Suite 200•Beaverton OR,97008 Date:APR 2018 By: JEN Sheet No.: G7
ASCE 7.10 Wind Force Standard
Wind Speed: 120 mph Exposure: B
Mean Height(h): 18'-0"
Width(x): 30'-0" Topographic Feature: Homogeneous
Length(y): 30'-0" Height of Hill(h) 0 ft
Crest Length(Lb) 0 ft
qh : 18.97 psf-LRFD Crest to Structure Dist(x) 0 ft
--• 1
1 1 X IIY Ka: 0.85 Ki : 0.00
Cp: 0.80 0.80 windward K,,t : 1.00 K2 : 0.00
Cp: -0.50 -0.50 leeward Ks : 0.00
- Gust: 0.87 0.87
'Wal Loads -► 11x I IIY 4
I ASD
Leeward qh * Cp * Gust = -4.9 psf I qh * Cp * Gust = -4.9 psf
Windward la qz* Cp * Gust Total I qz* Cp * Gust Total
20'-0" 0.624 8.1 psf 13.1 psf I 8.1 psf 13.1 psf
15'-0" 0.575 7.5 psf 12.4 psf I 7.5 psf 12.4 psf
'Roof Loads I --► I I X I IIY l
Wind Force Perpendicular to Ridge Pitch 6/12 Angle of Pitch 26.6 qz: 11.4 psf ASD
h/Ly 0.600 h/Lx 0.600
Wind Pressures windward leeward windward leeward
Normal to Roof Cp 0.17 -0.60 Cp 0.17 -0.60
Slope q: 1.7psf -5.9psf q: 1.7psf -5.9psf
Horizontal Force applied at cave line Horizontal Force applied at cave line
Horiz outward inward total outward inward total
Dist (plf) (plf) (plf) (plf) (p10 (plf)
15'-6" I 13.2 -45.8 591 I 13.2 -45.8 591
NORDLING Proj. No.: 18-132
STRUCTURAL ARBOR HEIGHTS POOL SHELTER
ENGINEERS, LLC HARRISON ROYCE ARCHITECTURE
6775 SW 111th,Suite 200•Beaverton OR,97008 Date:APR 2018 By:JEN Sheet No.:LI
SGS
arthquake Hazards Program
ASCE 7-10 Standard
Lat: 45°24'35.7"N Ss and Si=Mapped Spectral Acceleration Values
Long: 122°47 29.29" W 15099 SW Royalty Pkwy,Tigard,OR 97224
Ground Motion Ss 0.956 Si 0.420
Occupancy Category II Cantilevered Column Systems
Site Class D R 2.5 ‘,(),,
Importance Factor 1.00
Height of Structure 20.0 ft
Structural Period T 0.189
Site Coefficients Ct 0.020
Fa 1.12 x 0.75
Fv 1.58
Cs SDs I/R 0.285
SMs Fa* Ss 1.068 Cs Max SDs I/T R 0.936
SMI F, * Si 0.664 Cs MIN 0.044 SDs I 0.031
SDS (2/3)SMS 0.712 I V Cs* WP 0.285 WP
SD! (2/3)SMi 0.442
IASD =V* 0.7 0.199 WP I
Seismic Design Category
SDC D
El Roof 0.199 * 15 psf * 30.3 ft = 91 plf
E2 Roof 0.199 * 15 psf * 16.4 ft = 49 p1f
E3 Roof 0.199 * 15 psf * 23.4 ft = 70 plf
NORDLING Proj. No.: 18-132
STRUCTURAL ARBOR HEIGHTS POOL SHELTER
ENGINEERS, LLC HARRISON ROYCE ARCHIFECTtTRE
6775 SW 111th,Suite 200•Beaverton OR,97008 Date:APR 2018 By: JEN Sheet No.:L2
•
® COLUMNS m COLUMNS 0 COLUMNS
•
P A2 DL l,680 lbs P A2 DL 1b80 Iba P A4 DL 580 lbs
LL 2,800 lbs LL 2,800 lbs 1 LL 950 lbs
,.,._____ i
V 355 ibs V 325 lbs V 15$ lbs
1060 lbs /3 columns 650 lbs /2 columns230 lbs/2 columns
Q Q 0-)
di 61 N
. 8x8 DF-L No.1 8x8 DF-L No.1 8x8 DF-L No.1
R1 R2 R1 R2 R1 R2
RDL 0 0 I RDL 0 0 RDL 0 0
LL 355 0 I LL 325 0 LL 115 0
I, 355 0 m 325 0 TL 115 0
✓ MAX 355 lbs V MAX 325 lbs I V MAX 115 lbs
M MAX 3,195 ft-lbs M MAX 2,925 ft-lbs M MAX 1,466 ft-lbs
✓ (d) 355 lbs ( V (d) 325 lbs 1 I V (d) 115 lbs 1
fv 9 < 226 psi Ifv 9 < 226 psi I fv 3 < 226 psi 1
fb 545 < 1,596 psi fb 499 < 1,596 psi fb 250 < 1,596 psi
Eq.3.9-3 0.42 < 1.0 Eq.3.9-3 0.39 < 1.0 Eq.3.9-3 0.18 < 1.0
S1 S1 S1
A DL 0.00 A DL 0.00 ' A DL 0.00
ALL -035 ALL -0.32 ALL -033
L/306 ( L/334 L/470
ok I ok I ok
A it, -0.35 I A iL -0.32 f A rL -0.33
CR 1.00E Cv --- CR 1.001 1 Cv ---1 CR 1.00 I Cv
CD 1.331 CF 1.00 CD 1.331 I CF 1.001 I CD 1.33 I Cr 1.001
CL 1.001 I I CL 1.001 I I CL 1.001 I
Axial Dead Load 1,680 lbs I Axial Dead Load 1,680 lbs I Axial Dead Load 580 lbs
Live IAad 2,800 lbs Live Load 2,800 lbs Live Load 950 lbs
Total Load 4,480 lbs 1 I Total IAad 4,480 lbs I Total Load 1,530 lbs
H(ft) K H(ft) K H(ft) K
b 7.50 9.00 2.0 b 7.50 9.00 2.0 I I b 7.50 12.75 2.0
d 7.50 9.00 2.0 d 7.50 9.00 2.0 d 7.50 12.75 2.0
fc 80 < 487 psi I fc 80 < 487 psi 1 1 fc 27 < 269 psi
"Fell 1,000 psi Cr 0.49 Fc 11 1,000 psi Cr 0.49 Fe II 1,000 psi Cr 0.27
E 1,600 ksi CD 1.00 E 1,600 ksi CD 1.00 E 1,600 ksi CD 1.00
Cm 1.00 Cm 1.00 Cm 1.00
CF 1.00 CF 1.00 CF 1.00
n .' ii &-Colli re I.of _
I�enlltn�&�.�gw�rC`ssjori' . " g" Compre , =Y . ,�„-ar ,Be'II° l , ,I ,I'' " to;
FbE 25,558,252 psi 0.00 FbE 25,558,252 psi 0.00 FbE 25,558,252 psi 0.00
FcEl 579 psi 0.14 FcEl 579 psi 0.14 FcEl 289 psi 0.09
FcE2 579 psi 0.14 FcE2 579 psi 0.14 FcE2 289 psi 0.09
NORDLING Proj. No.: 18-132
STRUCTURAL ARBOR HEIGHTS POOL SHELTER
J ENGINEERS, LLC HARRISON ROYCE ARCHITECTURE
6775 SW 111th,Suite 200•Beaverton OR,97006 Date:APR 2018 By:JEN Sheet No.: L3
0 RETAINING WALL 6'-6' EXPOSED I-IEIGHT
;.irlt.""""il-4 v't:t.•,....k Si-1„O'r,i÷j,:rt:,,i:,::..
:110°'
00
X0oo
:: Cf'oo ,o 5,,o oor•,,
i.
•,••�3e
r. i::::::::.. SOIL SEARING PRESSURE: 1500 per
EQ. ACTIVE FLUID: 35 per
.:'.;::;::::..;1'..;k: PASSIVE PRESSURE: 150 per
WEIGI-IT OF SOIL: 110 p.r
' '' WE IGNT OF CONCRETE: 145 per
.. ::, COEFFICIENT OF FRICTION: 0.35
_ it
ts
•
_ ,',s:
r.��� ji.
: 1•
I5J..1;.
r~ ` i�i`��,' `:{':''` : 3.3'
:- iN
ig
0 • .
1 ':
0.8' 3.3' [
01..i.E.:A IL
421
NORDLING Proj. No.: 18-132
t • STRUCTURAL ARBOR HEIGHTS POOL SHELTER
\> J ENGINEERS, LLC HARRISON ROYCE ARCHITECTURE
6775 SW 111th,Suite 200•Beaverton OR,97008 Date: APR 2018 By: JEN Sheet No.:Fl
0 RETAINING WALL. 61-6' EXPOSED HEIGHT
11664:1erm qwiffilvioapArrillio, ,*,,,,, ,pv1,-; rvoiviwveg,,,:i.,; iO4-Togy.. .pvii:1
ilait-061Z-Ftxrcl4Fe:e1,14.:!!:471,y ,.0 1,,,AR1/4.,. ..W4Yri,ets:;g1-. 5%- ,.4 :i•"t,,,'evi:1442 -i..,„,,i-m-r.4-4.Pia$,.--4'-',. *A4'.4=. tVi...A.1,,i*,.. .,,.
Wall Height 6-8" 6.67' Allowable S.B.P. 1,500 psf Resulant 3,174 lbs
Retained Height 6-8" 6.67' Active Lateral 35 pcf result eccentricity 4.74 in
Base Wall Width 8" 0.67' Passive Lateral 150 pcf Pres sure @Toe 1,264 psf
Weight of Soil 110 pcf Pressure @Heel 323 psf
Toe Width 9" 0.75' Friction Coefficient 0.35 0.84
Heel Width 39" 3.25' Backfill Slope 0 :1-Level Pressure @Toe Face 1,087 psf
Width 4'-0" 4.00' Soil To Neglect 0.00' Pressure AHeel Face 931 psf
Eq ALP 35.0 pcf
Footing Depth 10" 0.83Internal Friction Ang 311' [,,(NtootINA
Height 0.00' 3,33' 6.67'
Key Width 8" 0.67'
Key Depth 12" 1.00' Bar #4 #4 #4
Key Location 40" 3.33' Spacing 12" o/c 12" o/c 12" o/c
Key Loc+Key Width 4'-0" dev len 6.00' req'd d 9.00"
Soil Cover over Toe 8 0.67' A,,Utin2\
0.196 0.196 0.196
fc 3,000 psi Bar Depth 5.75" 5.75" 5.75"
''',a4niViilifiaitilP.;:tAPNIAIMMIA
4•V Z _ ->•',---4-;;IA- ,,-, !,,:i.;e-•,:', 40-i'Z.:A.1,--.Ah!`,ITh4,- Fy 60,000 psi Cover 200" 2.00" 200
Vertical Dead Load plf Min.As Percent 0.0014
Vertical Live Load plf Unit Weight 145 pcf Force(lbs) 1,266 331 0
Surchage Load Rebar Cover @ Toe 3.00 in Mu(ft-lbs) 2,926 367 0
Seismic Load Rebar Cover A lIeel 3.00 in Earth Earth Inside
epMn(ft-lbs) 4,902 4,902 4,902
0.60 0.07 0.00
Vertical Force Dist Vu(psi) 18.3 4.8 0.0
lbs feet 4Vn(psi) 93.1 93.1 93.1
Wall 644 1.08 0.20 0.05 0.00
Footing 483 2.00
.z1.,_.., , _,:iei---,Ai:kw ,,, ,,. ,,owft,14,,yq:„,..191.,.„74.7-$.A
Key 97 3.67
111)110-V t901-0-',0j014!V'',. "-L74, 471,:r.i,tt,,,t''',-t,' .:-:."''.L
Soil over Heel 1894 2.71 Toe Heel
Sloped Soil over Heel 0 0.00 Reinforcing #4 #4
Soil over Toe 55 0.38 Spacing 24" o/c 18" ole in o/c
Vertical Component 0 0.00 Area 0.098 0.131
Total 3,174 lbs Depth d 6.75 6.75
Horizontal(base-top) lbs lbs M<S Fr: Toe Reinf Not Reg'd
Active Pressure 984 0
Passive Pressure 469 -x- Longit. I (4) #4 I
As 0.784 > 0.672 in 2
,,t V`s-,1
040Y4WWNIV;POCVN,
Active Soil Pressure 984 lbs Factored Pres sures 1,769 453 psf
Passive Soil Pressure 469 lbs at Face of 1,522 1,303 psf
Resisting Force 1,111 lbs Mu:Upward 474 2,456 ft-lbs
Factor of Safety 1.60 Mu:Downward 257 3,990 ft-lbs
Mu :Design 217 1,534 ft-lbs
'1,044116 - 704FP.e *VA
-,-,-------i,., -*': e,' ,`,"fit-t`,- A,'':,,,kttION:"- :/ ',0 (IpMn : 2,934 3,894 ft-lbs
Resisting Moment 7,639 ft-lbs
Overturning Moment 2,545 ft-lbs Actual Vu 8.6 6.8 psi
Factor of Safety 3.00 AllowalbeiWn 93.1 93.1 psi
NORDLING Proj. No.: 18-132
STRUCTURAL ARBOR HEIGHTS POOL SHELLER
\> Ay ENGINEERS, LLC
HARRISON ROYCE ARCHITECTURE
6775 SW 111th,Suite 200•Beaverton OR,97008 Date:APR 2018 By:JEN Sheet No.: F2
® RETAINING WALL
riaii":"... 41,4.+.flit• omi
I:::.. 000oto CoTOcPne 1° °
0 op (r
_. ., SOIL BEARING PRESSURE: 1500 per
EQ. ACTIVE FLUID: 35 per
::::::;:::;::1:,::
PASSIVE PRESSURE: 150 per
_ ';; ,.
I--. WEIGHT OF SOIL: 110 per
" WEIGHT OF CONCRETE: 145 per
_ ".s: `;I COEFFICIENT OF FRICTION: 0.35
S 11 .:
;1::
..::.1.
.✓' ''`''`''`''`''�''`''`''`''`' 1 \�; .
'TOE' 1.
'WIDTH'
4 DETAIL
63 )'a1'-0.
NORDLING Proj. No.: 18-132
STRUCTURAL ARBOR HEIGHTS POOL SHELTER/l .t ...
ENGINEERS, LLC HARRISON ROYCE ARCHITECTURE
6775 SW 111th,Suite 200•Beaverton OR,97008 Date:APR 2018 By: JEN Sheet No.: F3
0 RETAINING WALL 5'-6' EXPOSED HEIGHT
...s=.,, ..,;;,";a: 5 .�;,•, -ax.. sq'. r.s '.;?. _ -*:, - .�sem: - +'.t..:�•�c': - _
yL, ,�..;L:�„ �'-"�° •�:�'�' irc=:f .. %gas",. .�.�,"'. s�'"�` -�' ...a*+�,.'''
k l�Cl( - t� .,d..tA '� ,es 's`' sg.` wdd; �y0'd .'v '" f-YY t^. ,', -it '•�,•�.-'y=^. ^'# ,9 :'�7�.'' ;';'pW ai`3;.�„ :olt,
7:6.< S-f{ lu ,4>.s,,o...� �t,�a sk. '.sit3i:�S.�.s�ret7!+1tr.gR �.<^sOMO. ":Y .. .. .:.,..Az,x,,..,�,,,4,z,^,'" a 9 ¢ d � E" ly�a#•`* ,.., °d.
Wall height 5'-8" 5.67' Allowable S.B.P. 1,500 psf Resulant 2,696 lbs
Retained Height 5-8" 5.67' Active Lateral 35 pcf result eccentricity 4.31 in
Base Wall Width 8" 0.67' Passive Lateral 150 pcf Pressure @Toe 1,037 psf
Weight of Soil 110 pcf Pressure @Heel 311 psf
Toe Width 9" 0.75' Friction Coefficient 0.35 0.69
Heel Width 39" 3.25' Backfill Slope 0 :1-Level Pressure @Toe Face 901 psf
Width 4'-0" 4,00' Soil To Neglect 0.00' Pres sure @Heel Face 780 psf
Eq ALP 35.0 pcf
Footing Depth 10" 0.83' Internal Friction Ang 31.1° f2 3 I I .; VM 3= a 'Pi A
Height 0.00' 2.83' 5.67'
Key Width 0.00'
Key Depth 0.00' Bar #4 #4 #4
Key Location 0.00' Spacing 12" o/c 12" o/c 12" o/c
Key Loc+Key Width 0'-0" dev len 6.00" req'd d 9.00"
Soil Cover over Toe h ' . . . .. a �. 1^ x.0,100 , 2
8 0,67 : if_0 9.,,Alq,s ; i,.. .", ,1 :..; Area(in) 0.196 0.196 0.196
fc 3,000 psi Bar Depth 5.75" 5.75" 5.75"
.�I fil,T3-, : t`•: t?t'` ;€-u, u;fi' , 1" .`;,`. Fy 60,000 psi Cover 2.00" 2.00" 2.00
Vertical Dead Load plf Min.As Percent 0.0014
Vertical Live Load plf Unit Weight 145 pcf Force(Ibs) 899 239 0
Surchage Load Rebar Cover @ Toe 3.00 in Mu(ft-lbs) 1,792 226 0
Seismic Load Rebar Cover A Heel 3.00 in Earth Earth Earth
_ OMn(ft-lbs) 4,902 4,902 4,902
1 � :< '� dfib i'1.7.1C 01 `;t: 0.37 0.05 0.00
Vertical Force Dist Vu(psi) 13.0 3.5 0.0
lbs feet OVn(psi) 93.1 93.1 93.1
Wall 548 1.08 0.14 0.04 0.00
Footing 483 2.00
Key 0 0.00 "1:�4At>:r x ^ `, . t' r.- �07"` ^.v;..) { " ,
Soil over Heel 1610 2.71 Toe Heel
Sloped Soil over Heel 0 0.00 Reinforcing #4 #4
Soil over Toe 55 0.38 Spacing 24" o/c 18" o/c in o/c
Vertical Component 0 0.00 Area 0.098 0.131
Total 2,696 lbs Depth d 6.75 6.75
Horizontal(base-top) lbs lbs M<S Fr: Toe Reinf Not Req'd
Active Pressure 739 0
Passive Pressure 169 -x- Longit. I (4) #4 I
As 0.784 > 0.672 in'
j'!.000.1;• ,MA$_';..'�:r:r„t {`',z C;'d ft,t,{k a.p
Active Soil Pressure 739 lbs Factored Pressures 1,452 435 psf
Passive Soil Pressure 169 lbs at Face of 1,262 1,092 psf
Resisting Force 944 lbs Mu:Upward 391 2,183 ft-lbs
Factor of Safety 1.50 Mu:Downward 257 3,476 ft-lbs
Mu :Design 133 1,293 ft-lbs
--'yr;.�,'w.}'r,`4; `;:'• .=a ;..=, �,:•:,- ..,.':.-`en.:,.� * --;�,. :iv{a;,kr ro
V(�t$f;'C�.Il16T11',��s:4anF� W.,''t,i ate'x k .'�'s art?' avg�
(fNln: 2,934 3,894 ft-lbs
Resisting Moment 6,111 ft-lbs
Overturning Moment 1,686 ft-lbs Actual Vu 6.8 6.0 psi
Factor of Safety 3.62 Allowalbe 4Vn 93.1 93.1 psi
NORDLING Proj, No.: 18-132
ARBOR HEIGHTS POOL SHELLER
STRUCTURAL
ENGINEERS, LLC HARRISON ROYCE ARCHITECTURE
6775 SW 111th,Suite 200•Beaverton OR,97008 Date:APR 2018 By:JEN Sheet No.: F4
® RETAINING WALL
WIO�'si�-,� .',a��n`��,�.a' i'3;,« 4A,�'����� ..�'eV.
�t', ,�,. .. :- .� .. �,�'r ....���.�� k'�.��.. Nuc. ` rta4 ,�..�p�,� N�r�,,��-�1���',� ;lr".,:.�';. .�- '�r�+�is �.3V"
Wall Height 4'-8" 4.67' Allowable S.B.P. 1,500 psf Resulant 1,791 lbs
Retained Height 4'-8" 4.67' Active Lateral 35 pcf result eccentricity 4.58 in
Base Wall Width 8" 0.67' Passive Lateral 150 pcf Pressure @Toe 1,053 psf
Weight of Soil 110 pcf Pressure @Heel 141 psf
Toe Width 6" 0.50' Friction Coefficient 0.35 0.70
IIeel Width 30" 2.50' Backfill Slope 0 :1-Level Pressure @Toe Face 901 psf
Width 3'-0" 3.00' Soil To Neglect 0.00' Pressure a,Heel Face 698 psf
Eq ALP 35.0 pcf
Footing Depth ]0 0.83' Internal Friction Ang 31.1° , -u le _ -„.j3 MV-Vi- 4q4 , v
Height 0.00' 2.33' 4.67'
Key Width 0.00'
Key Depth 0.00' Bar #4 #4 #4
Key Location 0.00' Spacing 12" o/c 12" o/c 12" o/c
Key Loc+Key Width 0'-0" dev len 6.00" req'd d 9.00"
.?t. ,-4. u.4,. o.va 4 ; ii&W. t.Y;.: .: Area z 0.196
Soil Cover over Toe 8" 0.67' fSfffIc ,K Riti,i , $,4, 4,„-i rc>°, '{ (in ) 0.196 0.196
fc 3,000 psi Bar Depth 5.75" 5.75" 5.75"
,910. ,r' ' a, r @ . l t Fy 60,000 psi Cover 2.00" 2.00" 2.00"
Vertical Dead Load plf Min.As Percent 0.0014
Vertical Live Load plf Unit Weight 145 pcf Force(lbs) 591 162 0
Surchage Load Rebar Cover @ Toe 3.00 in Mu(ft-lbs) 995 126 0
Seismic Load Rebar Cover @ Heel 3.00 in Earth Earth Earth
0/In(ft-lbs) 4,902 4,902 4,902
rampftglityroo44-'4=44, .*,:f4-4'4
0.20 0.03 0.00
Vertical Force Dist Vu(psi) 8.6 2.3 0.0
lbs feet cVn(psi) 93.1 93.1 93.1
Wall 451 0.83 0.09 0.03 0.00
Footing 363 1.50
Key 0 0.00 gAPJ 1, f 9 tl me It:�, .��`ts�.� '' - . ::,.,'2"
Soil over Heel 941 2.08 Toe Heel
Sloped Soil over Heel 0 0.00 Reinforcing) #4 #4
Soil over Toe 37 0.25 Spacing 24" o/c 18" o/c in ole
Vertical Component 0 0.00 Area 0.098 0.131
Total 1,791 lbs Depth d 6.75 6.75
Horizontal(base-top) lbs lbs M<S Fr: Toe Rein!Not Req'd
Active Pressure 529 0
Passive Pressure 169 -x- Longit. I (3) #4 I
As 0.588 > 0.504 in2
Active Soil Pressure 529 lbs Factored Pressures 1,474 198 psf
Passive Soil Pressure 169 Ibs at Face of 1,261 978 psf
Resisting Force 627 lbs Mu :Upward 175 769 ft-lbs
Factor of Safety 1.50 Mu:Downward 89 1,492 ft-lbs
Mu :Design 86 723 ft-lbs
044 t^±f " 2 A. WO"` tliMn: 2;934 3,894 ft-lbs
Resisting Moment 3,058 ft-lbs
Overturning Moment 1,055 ft-lbs Actual Vu 4.6 4.6 psi
Factor of Safety 2.90 Allowalbe 4Vn 93.1 93.1 psi
NORDLING Proj, No.: 18-132
11 STRUCTURAL ARBOR HEIGHTS POOL SHELTER
JJ
A in)
ENGINEERS, LLC HARRISON ROYCE ARCHITECTURE
6775 SW 111th,Suite 200•Beaverton OR,97008 Date:APR 2018 By:JEN Sheet No.: F5
•
tc),,--_st_1/4 cs, ,, .
. ,,„••••-
PREVAIL ttt
MULTIFAMILY SIDING PRODUCTS Lap Siding ILIJLIVCL , I
INSTALLATION REQUIREMENTS-PRIMED AND FACTORY BUILT COLOR T AIE,D� PRODUCTS EFFECTIVE FEBRUARY 2010
SMOOTH ° TEXTUREi3�'�
IMPORTANT:FAILURE TO INSTALL AND FINISH THIS PROD II�AdCAIRthAdtt1 H APPLICABLE BUILDING CODES AND
• THE MANUFACTURER'S WRITTEN APPLICATION INSTR IMMO I , %:'►ONAL INJURY,AFFECT SYSTEM
• PERFORMANCE,VIOLATE LOCAL BUILDING CODES,AND VOID T -• UCT ONLY WARRANTY.
• STORAGE& HANDLING: CUTTING INSTRUCTIONS
Store flat and keep dry and
covered prior to installation, 1.P�Rp�g station so that wind will blow dust away from user 1.CINDOORS using score and snap,or shears(manual,electric or pneumatic).
Installing siding wet or saturated and others in working area. 2.Position cutting staton in well-ventilated area
may result in shrinkage at butt 2.Use one of the following methods:
joints,Ca tanks on a.Best i.Score and snap
j � edge.p g a.Shears(manual,electric or pneumatic) -NEVER use a power saw indoors
Protect edges and corners from b.Better: I Dust reducing circular saw equippedwith a -NEVER use a dreular saw blade that does not cony the Haniiebiade saw blade trademark
e.
breaks The manufacturer is not Hardiebadeulsaw blade and NE Avacuumextraction -NEVER drysweep—Use wet suppression orHEPA Vacuum
g c.Good: i.Dust reducing circular saw with a Hardieblade saw blade
responsible for damage caused by (only use for low to moderate cutting)
improper f ye�-�, Important Note:For maximum protection(lowest respirable dust production),the manufacturer recommends always using'Bed-level sitting methods where feasible.
storage and ��.�'
handlingof the �`�" NIOSH-approved respirators can be used in conjunction with above outdo practices to further reduce dust exposures.Additional exposure information is available
at wuw.prevarlsiding.com to help you determine the most appropriate cuthng method for your job requirements.If concern ptg exists about exposure levels or you
product. \,1 --" do not comply with the above practices,you should always consult a qualified industrial hygienist or contact the manufacturer for further information. SD063105
GENERAL REQUIREMENTS: (For elevations of 4000 ft and aboveplease refer to page 4 for specific requirements)
• Prevail lap siding can be installed over braced wood or steel studs spaced a maximum of 24 o.c.sheathing*.Irregularities in framing and sheathing can mirror
through the finished application.
•Prevail."'lap siding can also be installed over foam insulation/sheathing up to 1'thick.When using foam insulation/sheathing,avoid over-driving nails
(fasteners),which can result in dimpling of the siding due to the compressible nature of the foam insulation/sheathing.Extra caution is necessary if
power-driven nails(fasteners)are used for attaching siding over foam insulation/sheathing,
• A water-resistive barrier is required in accordance with local building code requirements, The water-resistive barrier must be appropriately installed with
penetration and junction flashing in accordance with local building code requirements.The manufacturer will assume no responsibility for water infiltration. •
Install Prevailui products with a minimum 6"clearance to the finished grade on the exterior of the building or in accordance with local building codes
if greater than 6"is required(fig.3).
• Maintain a 1"-2"clearance between PrevaiP products and roofs,decks,paths, steps and driveways(figs.4,5&6).
• Maintain a 1/4"clearance between Prevailw products and horizontal flashing(fig.7).
• Ensure gutters have end caps.Maintain a minimum 1"gap between end caps and siding FI �� Double Wall Single Wall
I &trim(fig.8). 9 Construction Construction
• Install kickout flashing at roof-wall junctions(fig.9). water-resistive barrier let-in bracing
• Adjacent finished grade must slope away from the building in accordance with local or 24"o.c.max.
building codes-typically a minimum of 6"in the first 10'. OSB sheathing
• Do not install Prevail'!"products,such that they may remain in contact with -
standing water. ;_:
• PrevailTM lap siding must be installed on vertical wall applications only. ,`•• ;
• DO NOT use stain on Prevail'products. . .
• For larger projects,including commercial and multi-family projects,where the span of the wall is ;. x
significant in length,the designer and/or architect should take into consideration the coefficient of Als ,
thermal expansion and moisture movement of the product in their design.These values can be rr 6
found in the Technical Bulletin Characteristics of James Hardie®Siding
Products"at www.JamesHardie.com. `.
• INSTALLATION: JOINT TREATMENT3
I (Required for Factory Built Color Finish,Recommended for Primed product)
It is not recommended to use caulk at field butt Joints.
Figure 2 water-resistive st d
barrier
01" t ,r
/ A
//yi/� � from
041
plank..p a' ''0Joint flashing'" Ii 8"fromo• Xr °/'plankedgestive
oo /44.,: i..
;oj, • w�IBbarrier
install planks in 1 0 o x ry
moderate contact j o o Xe" • fastener
'0000 i oo0 Install a 11/4"starter strip to
I ,0• .,6o ensure a consistent plank angle
I o •
Install factory finished edges together at butt joints, leave appropriate gap between
planks and trim,then caulk""
"As required by local building code "'Apply caulk in accordance with caulk manufacturers written application instructions.
WARNING:AVOID BREATHING SILICA DUST
Prevailn products contain respirable crystalline slica,which is known to the State of California to cause cancer and is considered by IARC and NIOSH to be a cause of cancer from some occupational
sources. Breathing excessive amounts of respirable silica dust can also cause a disabling and potentially fatal lung disease called silicosis,and has been linked with other diseases.Some studies suggest
smoking may increase these risks. During installation or handling:(1)work in outdoor areas with ample ventilation;(2)use fiber cement shears for cutting or,where not feasible,use a Hardiebladew saw
blade and dust-reducing circular saw attached to a HEPA vacuum;(3)warn others In the Immediate area;(4)wear a properly-fitted,NIOSH-approved dust mask or respirator(e.g.N-95)in accordance with
applicable government regulations and manufacturer Instructions to further limit respirable silica exposures. During clean-up,use HEPA vacuums or wet cleanup methods-never dry sweep. For further
information,refer to our Installation instructions and Material Safety Data Sheet available at www.prevailsiding.com or by calling 1-877-238-7526. FAILURE TO ADHERE TO OUR WARNINGS,MSDS,
AND INSTALLATION INSTRUCTIONS MAY LEAD TO SERIOUS PERSONAL INJURY OR DEATH. saaam
PR1008-P1/4 7/10
RECEIVED ' ','-':'':':;*vi4.''fl,e':,4'.,
, ,,,, ",,.,,,,,,.,.,,,,,,,,,:tt,.:‘,i,,,i,-,,,,..,.44:,.:*,, ,,:,,,,:
.-4,A,-:, .1 ,....,'1 _ iiklimilliv--- --dling.imm- ,,.. -,t ,...,7.--"'"'---ii,-FRii•-, ;'. -. , tri,, „.,„_ .
,....: „,. .,._._,..,..,,,,,,-;--7,..„.._, _,,, „., _. .. 1,:, ..._._
� 1 4.-. .11 Ill _..it , BUILDING DIVISION , z:v.."W'=''X',
•
Ng
0.. !wqrtunteloot
i:";..)',...,,, ;,17::'',kii'tfio~“I I:.:'"V:t.
' ''.., -: ''''' lt;ii$:.•--,.''. ,‘,.24
•
• ...\,‘,,,,,,,.:,•===,-,...•t
---":=,...',t ••. -'? '24 CP ---;'- : • -,------------ :-. B ti till'i$1614.,...-.211,143113 41„g0411.,V,7 11 !.,.---'------,403', - 111111, I:' -..;;;''''''''.7.;1:1':-;.::1'!.:''' . t:.."'""`. : .----t-.,11.s.*w.,....,..
0: BEiteletakettgi
.;„.,,....*, .„. 1 it_..-„,„___arn=. :yr -1 AM —1 A.-..I 1-------=,
_-_______., a 1,_,,E.„......_ , , _...,_ •,....•,
'‘ ,.4w.-,L,,:,tr.4, ..,..: :=-_,-_,.g.•_-_ :--..-::_---- _----.2.---0. _.-_-_-:-_—"------7-,.rr-rte.--:-.,TI- --mini ff--.E.-.-__ID a--•=7-1 it-- i b-1 .
7._
iii5.,...::::::_____,____,_,,,...: ..._:. ..,....._ , ,,_,1!,...: ,,:,,,,It,,,,,,:,„z;,41t,....,,, ,,„ 44E,,
....7.,__ =......_..„_____ ::„.„.... . .„,.... „....„,.,4,004,
VP likurstiEk
` . ~ias
. . ~ . .
.
• RECEIVED ,,;„,,4„,n� J,,
PREVAIL MAY 14 2018 , ` '
MULTIFAMILY SIDING PRODUCTS Lap Siding 'r' • `'
i INSTALLATION REQUIREMENTS-PRIMED AND FACTORY BUILT BuILmrpTypEmotoDucTs EFFECTIVE FEBRUARY 2010
SMOOTPUI*pktaj} .5:11-.f1V
IMPORTANT:FAILURE TO INSTALL AND FINISH THIS PRODUCT IN ACCORDANCE WITH APPLICABLE BUILDING CODES AND
, THE MANUFACTURER'S WRITTEN APPLICATION INSTRUCTIONS MAY LEAD TO PERSONAL INJURY,AFFECT SYSTEM
• PERFORMANCE,VIOLATE LOCAL BUILDING CODES,AND VOID THE PRODUCT ONLY WARRANTY.
•• STORAGE& HANDLING: I Q CUTTING INSTRUCTIONS
, Store flat and keep dry and
covered prior to installation, 1.OUTDOORS�sin so that wind will blow dust away h om user 1.Cut using score and snap,or shears(manual,electric or pneumatic),
Installing siding wet or saturated and others in working area. 2.Position aitth9 station in well-ventilated area
may result in shrinkage at butt 2.Use one of the following methods:
oints.Ca tanks on edge. a.Best I Score and snap
j Carry p g ii.Shears(manual,electric or pneumatic) -NEVER use a power saw indoors
Protect edges and corners from b.Better. i.Dust reducing circular saw equipped with a -NEVER use a circular saw blade that does not cany the Hardieblade saw blade trademark
breakage.The manufacturer is not Hardlebladem'saw blade and HPAvacuum extraction -NEVER dry sweep—Use wet suppression orNEPA Vacuum
for damage caused byc.Good: I.Dust reducing circular saw with a Hardieblade saw blade
responsible
g (only use for low to moderate tutting)
improper 1., -.--0/0-....„. Important Note:For maximum protection(lowest respirable dust production},the manufacturer recommends always using'Besr-level cutting methods where feasible.
storage and % .10 `�.
handling of the ` .. "' NIOSH-approved respirators can be used in conjunction with above cutting practices to further reduce dust exposures.Additional exposure information is available
product. `I at www.prevailsiding.com to help you determine the most appropriate cutting method for your job requirements.If concern still exists about exposure levels or
do not comply with the above practices,you should always consult a qualified industrial hygienist or contact the manufacturer for further information.
GENERAL REQUIREMENTS: (For elevations of 4000 ft.and above please refer to page 4 for specific requirements)
• Prevail"'lap siding can be installed over braced wood or steel studs spaced a maximum of 24 o.c.sheathing*.Irregulanties in framing and sheathing can mirror
through the finished application.
•Prevail.""lap siding can also be installed over foam insulation/sheathing up to 1"thick.When using foam insulation/sheathing,avoid over-driving nails
(fasteners),which can result in dimpling of the siding due to the compressible nature of the foam insulation/sheathing.Extra caution is necessary if
power-driven nails(fasteners)are used for attaching siding over foam insulation/sheathing.
• A water-resistive barrier is required in accordance with local building code requirements. The water-resistive barrier must be appropriately installed with
penetration and junction flashing in accordance with local building code requirements.The manufacturer will assume no responsibility for water infiltration. •
Install Prevail"'products with a minimum 6"clearance to the finished grade on the exterior of the building or in accordance with local building codes
if greater than 6"is required(fig.3).
• Maintain a 1'-2"clearance between Prevail"'products and roofs,decks,paths, steps and driveways(figs.4,5&6).
• Maintain a 1/4"clearance between Prevail"'products and horizontal flashing(fig.7).
• Ensure gutters have end caps.Maintain a minimum 1"gap between end caps and siding Figure 1 Double Wall Single Wall
&trim(fg.8). g Construction Construction
• Install lockout flashing at roof-wall junctions(fig.9). water-gyve barrier let-in bracing
• Adjacent finished grade must slope away from the building in accordance with localIsheathior 24•o.c.max.
building codes-ttypicallya minimum of 6"in the first 10'. O&e ng
• Do not install Prevail"'products,such that they may remain in contact with ,�` i
standing water. �!
• Prevail"'lap siding must be installed on vertical wall applications only. ;44.'"4"41.414- I* ----',/ ,. it
• DO NOT use stain on Prevail"''products. s
• For larger projects,including commercial and multi-family projects,where the span of the wall is
significant in length,the designer and/or architect should take into consideration the coefficient of
thermal expansion and moisture movement of the product in their design.These values can be ,
found in the Technical Bulletin'Expansion Characteristics of James Hardie®Siding 1'1" I /
• Products"at www.JamesHardie.com. 4 '; l':,II.'.
• INSTALLATION: JOINT TREATMENT ���
(Required for Factory Built Color Finnish,Recommended for Primed product) '
Itis not recommended to use caulk at field butt joints. , ,. / ` ' •4)
I .i
Y y
Figure 2 water-resistive
barrier p,Ai a
°hili a 1 ffkG ';.. ' fr,;:".:.,...":;,- . . ',
joint flashing** I1 ° o
�/g{ o water-ress
1'plank edge- oo o° • barrier
Install planks In 1 o° 4tive'
moderate contact • ° ° fastener
° Install a 1 1/4"starter strip to
°° ° o ° ensure a consistent plank angle
0
Install factory finished edges together at butt joints. leave appropriate gap between
planks and trim,then caulk*"
"As required by local building code *"Apply caulk in accordance with caulk manufacturers written application instructions.
WARNING:AVOID BREATHING SILICA DUST
Prevail'products contain respirable crystalline silica,which is known to the State of California to cause cancer and is considered by IARC and NIOSH to be a cause of cancer from some occupational
sources. Breathing excessive amounts of respirable sicca dust can also cause a disabling and potentially fatal lung disease called silicosis,and has been linked with other disrwi•s.Some studies suggest
smoking may increase these risks, During installation or handling:(1)work In outdoor areas with ample ventilation;(2)use fiber cement shears for cutting or,where not feasible,use a HardiebladeTM saw
blade and dust-reducing circular saw attached to a HEPA vacuum;(3)warn others In the Immediate area;(4)wear a properly-fitted,NIOSH-approved dust mask or respirator(e.g.N-95)in accordance with
applicable government regulations and manufacturer instructions to further limit respirable silica exposures. During clean-up,use HEPA vacuums or wet cleanup methods-never dry sweep. For further
information,refer to our installation Instructions and Material Safety Data Sheet available at www.prevailsiding.com or by calling 1-877-236-7526. FAILURE TO ADHERE TO OUR WARNINGS,MSDS,
AND INSTALLATION INSTRUCTIONS MAY LEAD TO SERIOUS PERSONAL INIURY OR DEATH. 90050°°6
PR1008-P1/4 7/10