Report OFFICE COPY 2ozi- )
RECEIVED 's,t 'si .-4 l
tyro FEB 2021
Worldwide ����tyco-fire.com
Fire Protection CITY OF TIGARD Contacts
Products BUILDING DIVISION
Series TY-FRB — 2.8, 4.2, 5.6, and 8.0 K-Factor
Upright, Pendent, and Recessed Pendent Sprinklers
Quick Response, Standard Coverage
General when exposed to corrosive atmo-
spheres. Although corrosion-resistant
Description coated sprinklers have passed the •y,
standard corrosion tests of the appli-
The TYCO Series TY-FRB, 2.8, 4.2, cable approval agencies,the testing is a i _
5.6,and 8.0 K-factor,Upright,Pendent, not representative of all possible cor- ,
rosive atmospheres. Consequently,
and Recessed Pendent Sprinklers iy,
described in this data sheet are quick it is recommended that the end user •be consulted with respect to the suit- I•
response, standard coverage, deco- fi
ability of these coatings for any given
rative 3 mm glass bulb type spray corrosive environment. The effects of
sprinklers designed for use in light or ambient temperature,concentration of
ordinary hazard,commercial occupan- chemicals, and gas/chemical velocity, �
1:. . -
des such as banks, hotels, and shop- should be considered, as a minimum, . '-
ping malls. along with the corrosive nature of the
The recessed version of the Series chemical to which the sprinklers will be
TY-FRB Pendent Sprinkler, where exposed.
applicable,is intended for use in areas An intermediate level of the Series
with a finished ceiling. This recessed TY-FRB Pendent Sprinklers is detailed
pendent sprinkler uses one of the in Technical Data Sheet TFP356, and
following: Sprinkler Guards are detailed in Tech-
• A two-piece Style 10(1/2 inch NPT) nical Data Sheet TFP780.
or Style 40(3/4 inch NPT) Recessed
Escutcheon with 1/2 inch (12,7 mm) NOTICE '
of recessed adjustment or up to 3/4 The Series TY-FRB, 2.8, 4.2, 5.6, 4'It,'
inch (19,1 mm) of total adjustment and 8.0 K-factor, Upright, Pendent,
from the flush pendent position,or a and Recessed Pendent Sprinklers
• A two-piece Style 20(1/2 inch NPT) described herein must be installed ',
or Style 30(3/4 inch NPT)Recessed and maintained in compliance with
Escutcheon with 1/4 inch (6,4 mm) this document and with the applica-
of recessed adjustment or up to 1/2 ble standards of the National Fire Pro-
inch (12,7 mm) of total adjustment tection Association, in addition to the
from the flush pendent position. standards of any authorities having
The adjustment provided by the jurisdiction.Failure to do so may impair Recessed Escutcheon reduces the the performance of these devices. Sprinkler
accuracy to which the fixed pipe drops The owner is responsible for maintain- Identification
to the sprinklers must be cut. ing their fire protection system and
Corrosion-resistant coatings, where devices in proper operating condition. Number (SIN)
applicable,are utilized to extend the life The installing contractor or sprinkler
of copper alloy sprinklers beyond that manufacturer should be contacted with TY1131 -Upright 2.8K,1/2"NPT
which would otherwise be obtained any questions. TY1231 -Pendent 2.8K,1/2"NPT
TY2131 - Upright 4.2K,1/2"NPT
TY2231 - Pendent 4.2K,1/2"NPT
IMPORTANT TY3131 - Upright 5.6K,1/2"NPT
Always refer to Technical Data TY3231 -Pendent 5.6K,1/2"NPT
Sheet TFP700 for the "INSTALLER TY4131 -Upright 8.0K,3/4"NPT
WARNING"that provides cautions TY4231 -Pendent 8.0K,3/4"NPT
with respect to handling and instal- TY4831 -Upright 8.0K, 1/2"NPT
lation of sprinkler systems and corn- TY4931 -Pendent 8.0K, 1/2"NPT
ponents. Improper handling and
installation can permanently damage
a sprinkler system or its compo-
nents and cause the sprinkler to fail
to operate in a fire situation or cause
it to operate prematurely.
Page 1 of 10 NOVEMBER 2015 TFP171
TFP771
Page 2 of 10
*Temperature rating ** Pipe thread connections per 1 - Frame 3 - Sealing 5 - Compression
is indicated on ISO 7-1 can be provided on ESCUTCHEON 2 - Button Assembly Screw
Deflector. special request. PLATE SEATING 4 - Bulb 6 - Deflector*
SURFACE 7 - Bushing
7
------ IM:=--- ---i- Ir.
,1� (11,1 mm) • �A� .
NOMINAL 2-1/4" ��� r r 2
MAKE-IN (57,2 mm) I
I I 2-3/16" 4
j (55,6 mm)/II
ii 1-9/16" 41�
._ ____.
(39,7 mm) . c 5
\ I .z
1/2 NPT** f WRENCH STYLE 10 or 20 2-7/8"(73,0 mm)DIA. -
FLATS RECESSED
UPRIGHT PENDENT ESCUTCHEON RECESSED PENDENT CROSS SECTION
FIGURE 1
QUICK RESPONSE SERIES TY-FRB UPRIGHT(TY1131)AND PENDENT(TY1231)SPRINKLERS
2.8 K-FACTOR, 1/2 INCH NPT
*Temperature rating ** Pipe thread connections per 1 - Frame 3 - Sealing 5 - Compression
is indicated on ISO 7-1 can be provided on ESCUTCHEON 2 - Button Assembly Screw
Deflector. special request. PLATE SEATING 4 - Bulb 6 - Deflector*
SURFACE
1 / 1
dil7/16" ■Ih 3
1111 N10MINAL 0 , 2-3/16" lciMIE - 2MAKE-IN (556mm) 4
t�r 2-3/16" �� 1-1/2"j (55,6mm) (38,1mm) 10 5
j a +
\ -- - .. 6*
1/2"NPT** WRENCH STYLE 10 or 20 2 7/8"(73,0 mm)DIA.---,-
FLATS RECESSED
UPRIGHT PENDENT ESCUTCHEON RECESSED PENDENT CROSS SECTION
FIGURE 2
QUICK RESPONSE SERIES TY-FRB UPRIGHT(TY2131)AND PENDENT(TY2231)SPRINKLERS
4.2 K-FACTOR, 1/2 INCH NPT
*Temperature rating ** Pipe thread connections per 1 - Frame 3 - Sealing 5 - Compression
is indicated on ISO 7-1 can be provided on ESCUTCHEON 2 - Button Assembly Screw
Deflector. special request. PLATE SEATING 4 - Bulb 6 - Deflector
SURFACE
1
-----. I / =---- ----•------"-
Mg . 3
gill Ls
iil
NOMINAL I- 2-3/16" ���`�� 2
MAKE-IN (55,6 mm) 4
(55,6 mm) I 1� 1-1/2" 4l1,
(38,1 mm) ,---5
1/2"NPT** t WRENCH STYLE 10 or 20 2-7/8'(73,0 mm)DIA. -
FLATS RECESSED
UPRIGHT PENDENT ESCUTCHEON RECESSED PENDENT CROSS SECTION
FIGURE 3
QUICK RESPONSE SERIES TY-FRB UPRIGHT(TY3131)AND PENDENT(TY3231)SPRINKLERS
5.6 K-FACTOR, 1/2 INCH NPT
TFP171
Page 3 of 10
*Temperature rating ** Pipe thread connections per 1 - Frame 3 - Sealing 5 - Compression
is indicated on ISO 7-1 can be provided on ESCUTCHEON 2 - Button Assembly Screw
Deflector. special request. PLATE SEATING 4 - Bulb 6 - Deflector*
SURFACE
1
fi
1/2"(12,7 mm) I / - __
j�NOMINAL IIjj
2-5/16" =�� ,I :
MAKE IN (58,7 mm) ` A l
(57,2/mm) I 1-9/16" II
I 4
(39,7 mm). i� 5
6*
3/4"NPT** } WRENCH STYLE 30 or 40 —J`
FLATS RECESSED /8"(73,0 mm)DIA.
UPRIGHT PENDENT ESCUTCHEON RECESSED PENDENT CROSS SECTION
FIGURE 4
QUICK RESPONSE SERIES TY-FRB UPRIGHT(TY4131)AND PENDENT(TY4231)SPRINKLERS
8.0 K-FACTOR,3/4 INCH NPT
CEILING PLATE 1 - Frame 5 - Compression
SEATING SURFACE 2 - Button Screw
1 3 - Sealing 6 - Deflector
rr----- IZt Assembly
Y 1 3 4 - Bulb
A
2-1/4"
(11,1 mm) f (57,2 mm) :A 4 2
NOMINAL
MAKE-IN I *Temperature rating is
t�r 2-3/16" 1-9/16" 4 indicated on Deflector.
(55,6 mm) i i (39,7 mm)
\ --_---- — y!s��5 ** Pipe thread connections
Nei J`\` per ISO 7-1 can be
1 6 * provided on special
1/2"NPT** I WRENCH request.
FLATS
UPRIGHT PENDENT CROSS SECTION
FIGURE 5
QUICK RESPONSE SERIES TY-FRB UPRIGHT(TY4831)AND PENDENT(TY4931)SPRINKLERS
8.0 K-FACTOR, 1/2 INCH NPT
4e„„ WRENCH
/
RECESS
WRENCH RECESS �
,.../1-'.°
(END"A"USED FOR i/'�yl
1/2"NPT MODELS)
d
WRENCH RECESS
(END"B"USED FOR
fir,
3/4"NPT MODELS) PUSH WRENCH
IN TO ENSURE
ENGAGEMENT
WITH SPRINKLER
WRENCHING AREA
FIGURE 6 FIGURE 7
W-TYPE 6 SPRINKLER W-TYPE 7 RECESSED
WRENCH SPRINKLER WRENCH
TFP171
Page 4 of 10
Technical Design Do not attempt to compensate for
insufficient adjustment in the Escutch-
Data Criteria eon Plate by under- or over-tightening
the sprinkler. Re-adjust the position of
Approvals The TYCO Series TY-FRB, 2.8, 4.2, the sprinkler fitting to suit.
UL and C-UL Listed 5.6,and 8.0 K-factor,Upright, Pendent, Series TY-FRB Upright and Pendent
FM,LPCB,and NYC Approved and Recessed Pendent Sprinklers are Sprinklers
Refer to Table A and B for complete intended for fire protection systems The Series TY-FRB Pendent and
approval information including corrosion- designed in accordance with the stan- Upright Sprinklers must be installed
resistant status. dard installation rules recognized by in accordance with the following
Maximum Working Pressure the applicable Listing or Approval instructions.
Refer to Table C. agency (such as, UL Listing is based Step 1.Install Pendent sprinklers in the
on the requirements of NFPA 13, and
Discharge Coefficient FM Approval is based on the require- pendent position. Install upright sprin-
K=2.8 gpm/psi'/'(40,3 Ipm/bares) ments of FM's Loss Prevention Data klers in the upright position.
K=4.2 gpm/psi' (60,5 Ipm/bar'/) Sheets). Only the Style 10, 20, 30, or Step 2. With pipe-thread sealant
K=5.6 gpm/psi' (80,6 1pm/bar- ) 40 Recessed Escutcheon, as applica- applied to the pipe threads, hand-
K=8.0 gpm/psi%(115,2 Ipm/bard) ble,is to be used for recessed pendent tighten the sprinkler into the sprinkler
Temperature Rating installations. fitting.
Refer to Table A and B. Step 3. Tighten the sprinkler into the
Finishes Installation sprinkler fitting using only the W-Type
Sprinkler:Refer to Table D. The TYCO Series TY-FRB,2.8,4.2,5.6, 6 Sprinkler Wrench(Figure 6).With ref-
and 8.0 K-factor,Upright,Pendent,and erence to Figures 1 through 5, apply
Recessed Escutcheon:Signal or Pure the W-Type 6 Sprinkler Wrench to the
White,Jet Black,Chrome Plated,or Recessed Pendent Sprinklers must sprinkler wrench flats.
Natural Brass be installed in accordance with this p
section. Series TY-FRB Recessed Pendent
Physical Characteristics Sprinklers
Frame Bronze General Instructions
Button Brass/Copper Do not install any bulb-type sprinkler The Series TY-FRB Recessed Pendent
Sealing Assembly..Beryllium Nickel w/TEFLON if the bulb is cracked or there is a loss Sprinklers must be installed in accor-
Bulb Glass of liquid from the bulb. With the sprin- dance with the following instructions.
Compression Screw Bronze kler held horizontally,a small air bubble StepA.After installingthe Style 10,20,
Deflector Copper/Bronze Y
Bushing(K=2.8) Bronze should be present.The diameter of the 30, or 40 Mounting Plate, as applica-
air bubble is approximately 1/16 inch ble,over the sprinkler threads and with
Operation (1,6 mm)for the 135°F(57°C)and 3/32 pipe-thread sealant applied to the pipe
inch(2,4 mm)for the 286°F(141°C)tern- threads, hand-tighten the sprinkler into
The glass bulb contains a fluid that perature ratings. the sprinkler fitting.
expands when exposed to heat.When A leak-tight 1/2 inch NPT sprinkler
the rated temperature is reached, the Step B. Tighten the sprinkler into the
fluid expands sufficiently to shatter the joint should be obtained by applying a sprinkler fitting using only the W-Type
glass bulb, allowing the sprinkler to minimum to maximum torque of 7 to 7 Recessed Sprinkler Wrench (Figure
activate and water to flow. 14 ft.-lbs. (9,5 to 19,0 Nm).A leak tight 7). With reference to Figures 1 to 4,
3/4 inch NPT sprinkler joint should be apply the W-Type 7 Recessed Sprinkler
obtained with a torque of 10 to 20 ft.- Wrench to the sprinkler wrench flats.
lbs. (13,4 to 26,8 Nm). Higher levels of Step C. After ceiling installation and
torque can distort the sprinkler Inlet finishing, slide on the Style 10, 20, 30,
with consequent leakage or impairment or 40 Closure over the Series TY-FRB
of the sprinkler. Sprinkler and push the Closure over the
Mounting Plate until its flange comes in
contact with the ceiling.
TFP171
Page 5 of 10
SPRINKLER FINISH(See Note 5) •
K TYPE TEMPERATURE BULB LIQUID NATURAL CHROME POLYESTER*** •
FACTOR COLOR BRASS PLATED
135°F(57°C) Orange
PENDENT 155°F(68°C) Red
(TY1231)
and 175°F(79°C) Yellow 1,2,3,4
UPRIGHT(TY1131) 200°F(93°C) Green
286°F(141°C) Blue
135°F(57°C) Orange
2.8 RECESSED 155°F(68°C) Red
1/2"NPT PENDENT
(TY1231)* 175°F(79°C) Yellow
Figure 8
200°F(93°C) Green
1,2,4
135°F(57°C) Orange
RECESSED PENDENT 155°F(68°C) Red
(TY1231)** 175`F(79°C) Yellow
Figure 9
200°F(93°C) Green
135°F(57°C) Orange
PENDENT 155°F(68°C) Red
(TY2231)
and 175°F(79°C) Yellow
UPRIGHT(TY2131) 200°F(93°C) Green
286°F(141°C) Blue
135°F(57°C) Orange
4.2 RECESSED 1/2"NPT PENDENT 155°F(68°C) Red 1,2
(TY2231)* 175°F(79°C) Yellow
Figure 10
200°F(93°C) Green
135°F(57°C) Orange
RECESSED PENDENT 155°F(68°C) Red
(TY2231)** 175°F(79°C) Yellow
Figure 11
200°F(93°C) Green
NOTES:
1. Listed by Underwriters Laboratories,Inc.,(UL)as Quick Response Sprinklers.
2. Listed by Underwriters Laboratories,Inc.,for use in Canada(C-UL)as Quick Response Sprinklers.
3. Approved by Factory Mutual Research Corporation(FM)as Quick Response Sprinklers.
4. Approved by the City of New York under MEA 354-01-E.
5. Where Polyester Coated Sprinklers are noted to be UL and C-UL Listed,the sprinklers are UL and C-UL Listed as Corrosion-Resistant Sprinklers.
'Installed with Style 10(1/2'NPT)or Style 40(3/4"NPT)3/4"Total Adjustment Recessed Escutcheon,as applicable.
"Installed with Style 20(1/2"NPT)or Style 30(3/4"NPT)1/2"Total Adjustment Recessed Escutcheon,as applicable.
Frame arc Deflector only.
N/A:Not Available
TABLE A
LABORATORY LISTINGS AND APPROVALS FOR
2,8 AND 4.2 K-FACTOR SPRINKLERS
TFP171
Page 6 of 10
SPRINKLER FINISH(See Note 8)
K TYPE TEMPERATURE BULB LIQUID NATURAL CHROME POLYESTER*** LEAD
FACTOR COLOR BRASS PLATED COATED
135°F(57°C) Orange
PENDENT(TY3231) 155°F(68°C) Red
and 175°F(79°C) Yellow 1,2,3,4.5,6,7 1,2,3,5
UPRIGHT 200°F(93°C) Green
(TY3131) 286°F(141°C) Blue
135`F(57°C) Orange
RECESSED 155°F(68°C) Red
5.6 PENDENT 175°F(79°C) Yellow 1,2,4,5 N/A
1/2"NPT (TY3231)*
Figure 12 200°F(93°C) Green
286°F(141°C) Blue
135°F(57°C) Orange
RECESSED 155'F(68°C) Red
PENDENT 175°F(79°C) Yellow 1,2,3,4,5 N/A
(TY3231)
Figure 13 200°F(93°C) Green
286°F(141°C) Blue
135°F(57°C) Orange
PENDENT 155°F(68`C) Red
(TY4231)
and 175°F(79°C) Yellow 1,2;3,4,5,6,7 1,2,5
UPRIGHT 200°F(93°C) Green
(TY4131) 286°F(141°C) Blue
135°F(57°C) Orange
RECESSED 155°F(68°C) Red
8.0 PENDENT 175`F(79°C) Yellow 1,2,5 N/A
3/4"NPT (TY4231)*
Figure 14 200°F(93°C) Green
286°F(141°C) Blue
135°F(57°C) Orange
RECESSED 155°F(68°C) Red
PENDENT 175°F(79°C) Yellow 1,2,3,5 N/A
(TY4231)**
Figure 15 200°F(93°C) Green
286°F(141°C) Blue
135`F(57°C) Orange
PENDENT 155°F(68°C) Red
8.0 (TY4931)
1/2"NPT and 175°F(79°C) Yellow 1,2,4,5,6 1,2,5
UPRIGHT 200°F(93°C) Green
(TY4831) 286°F(141°C) Blue
NOTES:
1. Listed by Underwriters Laboratories,Inc.,(UL)as Quick Response Sprinklers.
2. Listed by Underwriters Laboratories,Inc.,for use in Canada(C-UL)as Quick Response Sprinklers.
3. Approved by Factory Mutual Research Corporation(FM)as Quick Response Sprinklers.
4. Approved by the Loss Prevention Certification Board(_PCB Ref.No.007k/04)as Quick Response Sprinklers.However.LPCB does not rate the thermal sensitivity of
recessed sprinklers.
5_ Approved by the City of New York under MEA 354-01-E.
6. VdS Approved(For details,contact Tyco Fire Suppression&Building Products,Enschede,Netherlands,Tel.31-53-428-4444/Fax 31-53-428-3377.)
7. Approved by the Loss Prevention Certification Board(LPCB Ref.No.094a/06)as Quick Response Sprinklers.
B. Where Polyester Coated and Lead-Coated Sprinklers are noted to be UL and C-UL Listed,the sprinklers are UL and C-UL Listed as Corrosion-Resistant Sprinklers.
Where Lead-Coated Sprinklers are noted to be FM Approved,the sprinklers are FM Approved as a Corrosion-Resistant Sprinklers.
'Installed with Style 10(1/2"NPT)or Style 40(3/4'NPT)3/4"Total Adjustment Recessed Escutcheon,as applicable.
"Installed with Style 20(1/2"NPT)or Style 30(3/4'NPT)1/2"Total Adjustment Recessed Escutcheon,as applicable.
-Frame and Deflector only.
N/A:Not Available
TABLE B
LABORATORY LISTINGS AND APPROVALS FOR
5.6 AND 8.0 K-FACTOR SPRINKLERS
TFP171
Page 7of10
SPRINKLER FINISH
K TYPE NATURAL CHROME POLYESTER LEAD
FACTOR BRASS PLATED COATED
PENDENT(TY1231)
and
2.8 UPRIGHT(TY1131) 175 PSI(12,1 BAR) N/A
1/2"NPT
RECESSED
PENDENT(TY1231)
PENDENT(TY2231)
and
4.2 UPRIGHT(TY2131) 175 PSI(12,1 BAR) N/A
1/2"NPT
RECESSED
PENDENT(TY2231)
PENDENT(TY3231)
and
UPRIGHT(TY3131) 250 PSI(17,2 BAR)
5.6 OR 175 PSI(12,1 BAR)
1/2"NPT RECESSED (SEE NOTE 1)
PENDENT(TY3231)
PENDENT(TY4231) 175 PSI
and (12,1 BAR)
8.0 UPRIGHT(TY4131) 175 PSI(12,1 BAR)
3/4"NPT
RECESSED N/A
PENDENT(TY4231)
8 0 PENDENT(TY4931) 175 PSI
1/2"NPT and 175 PSI(12,1 BAR) (12,1 BAR)
UPRIGHT(TY4831)
NOTES:
1. The maximum working pressure of 250 psi(17,2 bar)only applies to the Listing by Underwriters Laboratories Inc.(UL);the Listing by Under-
writers Laboratories,Inc.for use in Canada(C-UL);and,the Approval by the City of New York.
TABLE C
MAXIMUM WORKING PRESSURE
Care and have not operated,should be replaced Care must be exercised to avoid
if they cannot be completely cleaned damage to the sprinklers -before,
Maintenance by wiping the sprinkler with a cloth or during, and after installation. Sprin-
by brushing it with a soft bristle brush. klers damaged by dropping, striking,
The TYCO Series TY-FRB must be Care must be exercised to avoid wrench twist/slippage,or the like,must
maintained and serviced in accordance damage to the sprinklers before, be replaced. Also, replace any sprin-
with this section. during, and after installation. Sprin- kler that has a cracked bulb or that has
Before closin afire rotection s stem klers damaged by dropping, striking, lost liquid from its bulb. (Ref. Installa-
g p y wrench twist/slippage,or the like,must lion Section).
main control valve for maintenance be replaced. Also, replace s rin-
work on the fire protection system pany p Initial and frequent visual inspections of
that it controls, obtain permission to kler that has a cracked bulb or that has random samples are recommended for
shut down the affected fire protection lost liquid from its bulb. (Ref. Installa- corrosion-resistant sprinklers to verify
tion Section.) the integrity of the corrosion-resistant
systems from the proper authorities g y
and notify all personnel who may be The owner is responsible for the material of construction. Thereafter,
affected by this action. inspection,testing,and maintenance of annual inspections per NFPA 25 should
Absence of the outer piece of an their fire protection system and devices suffice.
escutcheon, which is used to cover in compliance with this document, as Inspections of corrosion-resistant
a clearance hole, can delay sprinkler well as with the applicable standards sprinklers are recommended at close
operation in a fire situation. of the National Fire Protection Asso- range, instead of from the floor level
ciation (e.g., NFPA 25), in addition to per NFPA. Inspection at close range
Sprinklers which are found to be the standards of any other authorities can better determine the exact sprin-
leaking or exhibiting visible signs of having jurisdiction.Contact the install- kler condition and the long-term integ-
corrosion must be replaced. ing contractor or sprinkler manufac- rity of the corrosion-resistant material,
Automatic sprinklers must never be turer regarding any questions. which can be affected by the corrosive
painted, plated, coated, or other- Automatic sprinkler systems are rec- conditions present.
wise altered after leaving the factory. ommended to be inspected, tested,
Modified sprinklers must be replaced. and maintained by a qualified Inspec-
Sprinklers that have been exposed to tion Service in accordance with local
corrosive products of combustion, but requirements and/or national codes.
TFP171
Page 8 of 10
2-7/8" DIA. 2-7/8" DIA.
5/St1/4" (73,0 mm) 3/4"(19,1 mm) (73,0 mm)
(15,9±6,4 mm) 1/4"(6,4 mm) 1/2t1/8" 1/2"((6,4 mm)
2-1/4"DIA. (12,7t3,2 mm) 2-1/4"DIA. 1/4"(6,4 mm)
(57,2/ FACE mm) 1
SPRINKLER MOUNTING / FACE OF (57,2 mm) MOUNTING
FITTING PLATE SPRINKLERFI PLATE
/ 2 m 1/8'
(3,2 mm) / (3,2 mm)
Ai .-7- -----=11 I
��.
\ a .L gi F'77 7;_
MOUNTING
��� SURFACE
II�
SURFACE 4iy1' - iye-rr��
CLOSURE SERIES 1-5/16"(33,3 mm) CLOSURE SERIES 1-5/16"(33,3 mm)
TY-FRB 13/16"(20,6 mm) TY-FRB 1-1/16"(27,0 mm)
FIGURE 8 FIGURE 9
SERIES TY-FRB RECESSED PENDENT SERIES TY-FRB RECESSED PENDENT
WITH TWO-PIECE 3/4 INCH TOTAL ADJUSTMENT WITH TWO-PIECE 1/2 INCH TOTAL ADJUSTMENT
STYLE 10 RECESSED ESCUTCHEON STYLE 20 RECESSED ESCUTCHEON
2.8 K-FACTOR, 1/2 INCH NPT 2.8 K-FACTOR, 1/2 INCH NPT
2-7/8"DIA. 2-7/8" DIA.
5/8±1/4" -
(73,0 mm) 3/4"(19,1 mm) 1/2±1/8" (73,0 mm) 1/2"(12,7 mm)
(15,9±6,4 mm) 2-1/4'DIA. 1/4"(6,4 mm) (12,7*3,2 mm) 2-1/4"DIA. 1/4"(6,4 mm)
/ FACE OF (57,2 mm) / FACE OF (57,2 mm)
MOUNTING MOUNTING
SPRINKLER PLATE SPRINKLER PLATE
FITTING FITTING
1/8"
1/8'
(3,2 mm) 7/ I (3,2 mm)
zlai M-'1_ C
laG
MOUNTING
,ll, .il-pr,
SURFACE 1I'
SURFACE �• ! ..
CLOSURE SERIES 1-1/4"(31,8 mm) CLOSURE SERIES 1-1/4°(31,8 mm)
TY-FRB 3/4"(19,1 mm) TY-FRB 1"(25,4 mm)
FIGURE 10 FIGURE 11
SERIES TY-FRB RECESSED PENDENT SERIES TY-FRB RECESSED PENDENT
WITH TWO-PIECE 3/4 INCH TOTAL ADJUSTMENT WITH TWO-PIECE 1/2 INCH TOTAL ADJUSTMENT
STYLE 10 RECESSED ESCUTCHEON STYLE 20 RECESSED ESCUTCHEON
4.2 K-FACTOR, 1/2 INCH NPT 4.2 K-FACTOR, 1/2 INCH NPT
TFP171
Page 9 of 10
_ 2-7/8"DIA. _ _ 2-7/8"DIA. -
5/8±1/4" (73,0 mm) 3/4"(19,1 mm) 1/2±1/8 (73,0 mm) 1/2"(12,7 mm)
(15,9±6,4 mm) 1/4"(6,4 mm) (12,7±3,2 mm) 1/4"(6,4 mm) '
2-1/4"DIA. y 2-1/4"DIA.
/ FACE OF (57,2 mm) MOUNTING / FACE OF (57,2 mm) 1 MOUNTING
SPRINKLER PLATE SPRINKLER PLATE
FITTING FITTING
/ 2 m / 1/8"
(3,2 mm) (3,2 mm)
al II 1 M �T/, r
1,01 I- Fr T% i / -,
1 \
'I, -J II,
SURFACE \ ._ SURFACE
{fII
CLOSURE SERIES 1-1/4"(31,8 mm) CLOSURE SERIES 1-1/4"(31,8 mm)
TY-FRB 3/4"(19,1 mm) TY-FRB 1"(25,4 mm)
FIGURE 12 FIGURE 13
SERIES TY-FRB RECESSED PENDENT SERIES TY-FRB RECESSED PENDENT
WITH TWO-PIECE 3/4 INCH TOTAL ADJUSTMENT WITH TWO-PIECE 1/2 INCH TOTAL ADJUSTMENT
STYLE 10 RECESSED ESCUTCHEON STYLE 20 RECESSED ESCUTCHEON
5.6 K-FACTOR, 1/2 INCH NPT 5.6 K-FACTOR, 1/2 INCH NPT
2-7/8"DIA. _ 2-7/8"DIA.
5/8±1/4" (73,0 mm) 3/4"(19,1 mm) 1/2±1/8" (73,0 mm) 1/2"(12,7 mm)
(15,9±6,4 mm) 2-1/4"DIA. 1/4"(6,4 mm) (12,7±3,2 mm) 2-1/4"DIA. 1/4"(6,4 mm)
/ FACE OF (57,2 mm) MOUNTING / FACE OF (57,2 mm) MOUNTING
SPRINKLER PLATE SPRINKLER PLATE
FITTING FITTING
/ 1/8"
(3,2 mm) /
1/8"
(3,2 mm)m)
I \ = P7Zr/
��_/
\ f MOUNTING
MOUNTING SURFACE II ,
CLOSURE SERIES 1-5/16"(33,3 mm) CLOSURE SERIES 1-5/16"(33,3 mm)
TY-FRB 13/16"(20,6 mm) TY-FRB 1-1/16"(27,0 mm)
FIGURE 14 FIGURE 15
SERIES TY-FRB RECESSED PENDENT SERIES TY-FRB RECESSED PENDENT
WITH TWO-PIECE 3/4 INCH TOTAL ADJUSTMENT WITH TWO-PIECE 1/2 INCH TOTAL ADJUSTMENT
STYLE 40 RECESSED ESCUTCHEON STYLE 30 RECESSED ESCUTCHEON
8.0 K-FACTOR,3/4 INCH NPT 8.0 K-FACTOR, 3/4 INCH NPT
TFP171
Page 10 of 10
P/N 57 - XXX - X - XXX
SIN SPRINKLER TEMPERATURE
FINISH RATINGS
330 2.8K UPRIGHT(1/2"NPT) TY1131 1 NATURAL BRASS 135 135°F(57°C)
331 2.8K PENDENT(1/2"NPT) TY1231 3 PURE WHITE
POLYESTER(RAL9010)1 155 155°F(68°C)
340 4.2K UPRIGHT(1/2"NPT) TY2131 4 SIGNAL WHITE
POLYESTER(RAL9003) 175 175°F(79°C)
341 4.2K PENDENT(1/2"NPT) TY2231 5 JET BLACK
POLYESTER(RAL9005)2 200 200°F(93°C)
370 5.6K UPRIGHT(1/2"NPT) TY3131 7 LEAD COATED 286 286°F(141°C)
371 5.6K PENDENT(1/2"NPT) TY3231 9 CHROME PLATED
390 8.0K UPRIGHT(3/4"NPT) TY4131
NOTES:
1. Eastern Hemisphere sales only.
391 8.0K PEN DENT(3/4"NPT) TY4231 2. Available in only 2.8K,4.2K,and 8.0K,155°F(68°C)
and 200°F(93°C);requires lead time to manufacture.
360 8.0K UPRIGHT(1/2"NPT) TY4831°
361 8.0K PENDENT(1/2"NPT) TY4931°
TABLE D
SERIES TY-FRB PENDENT AND UPRIGHT SPRINKLERS
PART NUMBER SELECTION
Limited Ordering
Warranty Procedure
For warranty terms and conditions,visit Contact your local distributor for
www.tyco-fire.com. availability. When placing an order,
indicate the full product name and Part
Number(P/N).
Sprinkler Assemblies with NPT
Thread Connections
Specify: Series TY-FRB (Specify SIN),
(specify K-factor), (specify Pendent or
Upright)Sprinkler(specify)temperature
rating, (specify) finish or coating, P/N
(specify from Table D)
Recessed Escutcheon
Specify: Style (10, 20, 30, or 40)
Recessed Escutcheon with (specify`)
finish, P/N(specify')
Sprinkler Wrench
Specify: W-Type 6 Sprinkler Wrench,
P/N 56-000-6-387
Specify: W-Type 7 Sprinkler Wrench,
P/N 56-850-4-001
Refer to Technical Data Sheet TFP770
GLOBAL HEADQUARTERS 1 1400 Pennbrook Parkway,Lansdale,PA 19446 I Telephone+1-215-362-0700
Copyright CO 2015 Tyco Fire Products,LP. All rights reserved. *"CD
TEFLON is trademark of The DuPont Corporation. 'f Fire Protection Products