Plans (106) 6'667015= Uiifl • Dan Nelson /117947,7? A/., A9zrc.. From: Josh Cabot <joshc@serapdx.com> Sent: Monday, November 30, 2015 4:44 PM To: Dan Nelson Cc: Mark VanDomelen Subject: Burnham &Ash: Fire Rating of Exterior Shear Walls from Inside Only Attachments: 2015-11.30 Burnham &Ash - Shear Walls to be Fire-Rated from Inside_opt.pdf Dan, Hope you had a nice Thanksgiving. I'm finally getting a chance to e-mail you about the wall question I had asked you during our PreCon meeting a couple of weeks back. We have a number of exterior shear walls where we have plywood to handle the shear, but we also have Dens Glass (gypsum sheathing)to provide the fire rating. These two layers together create some constructability problems for us when this kind of shear wall is run next to another exterior wall with the same kind of cladding but no shear. Basically, the extra layer of plywood on the shear wall makes that piece of wall%z" thicker than the wall beside it,which means we have a bump in the wall or we have to conceal it with another layer of sheet rock on the inside. We have realized that per OSSC 705.5, when we have more than 10'-0" of fire separation distance, we only need to rate the wall from the inside. With this in mind, I want to let you know that we'd like remove the Dens Glass from any exterior shear wall that fits this criteria so that we can take care of this issue. Do you see an issue with this? I have attached a set of plans showing the walls I'm talking about, and I have explained our methodology below: For a 4-story building of Type V-A Construction: • Exterior walls are required to be 1-hour rated. • 705.5 Fire-resistance ratings. Exterior walls shall be fire-resistance rated in accordance with Tables 601 and 602 and this section.The required fire-resistance rating of exterior walls with a fire separation distance of greater than 10 feet (3048 mm) shall be rated for exposure to fire from the inside.The required fire-resistance rating of exterior walls with a fire separation distance of less than or equal to 10 feet(3048 mm) shall be rated for exposure to fire from both sides. • The wall still needs to be 1-hr rated, but we can use the component method for materials on fire exposed side of wall in order to calculate a 60—min rating. • Table 721.6.2(1) lists 5/8"Type X drywall as 40-min, and Table 721.6.2(2) lists wood studs @ 16"oc is equal to 20-min. 40+20=60=1hr from interior side. Here is how it would affect the wall assemblies: 1 of L5 I tu 2" 4-4- Y ' ; 1:. > >-‹ ; .0r99/ 1° 04 20 01-MASONRY VENEER 04 20 01-VENEER TIE,SEE STRUCTURAL ... . I 07 25 00-WEATHER BARRIER,ALL •.- s v4/ SEAMS SEALED 06 16 53-5/T TYPE X EXTERIOR . • • 4‘,, SHEATHING BOARD • / 06 10 00-WOOD SHEATHING,SEE ; i.. / STRUCTURAL t f- 0 / 07 21 00-THERMAL INSULATION,MIN , 4:71// / R21 i 09 21 16-5/&TYPE X GYPSUM . - ..----\v. 'ry i BOARD --->-<- ., /\r-l/ i _ .. On- i 09 21 16-VAPOR RETARDING PRIMER , REMOVE THIS EXTRA LAYER OF GYPSUM NOTES: i SHEATHING OUT IN FRONT Of THE 1)1 HR FIRE RATED(BASED ON GA FILE NO.WP 8105)is_ --PLYWOOD WHEN EXTERIOR WALL HAS GREATER THAN 10-0- EIRE SEPARATION DISTANCE PER OSSC 705 5 EXT - BRICK - SHEAR / 72 REFER TO CODE COMPLIANCE SUMMARY AND PLANS FOR RATED WALL LOCATIONS ' "- 2 REMOVE THIS EXTRA LAYER OF GYPSUM SHEATHING OUT IN FRONT OF THE PLYWOOD WHEN EXTERIOR WALL HAS GREATER THAN 1O'-O"FIRE SEPARATION DISTANCE PER OSSC 705 5 cn ' -t 07 4646-FIBER CEMENT SIDING .1>-->_< '; 0610 00-112"WOOD FURRING, FIRE/PRESSURE TREATED ',. 07 2500-WEATHER BARRIER,AU. • �` N SEAMS SEALED 1- ,0 "'0616 53-518'TYPE X EXTERIOR I sh_ SHEATHING BOARD P• _f06 10 00-WOOD SHEATHING,SEE STRUCTURAL 1 a1. ` 07 2100•THERMAL INSULATION,MIN IN:t R21 09 21 16-518`TYPE X GYPSUM 7 r BOARD 09 21 16-VAPOR RETARDING PRIMER 1� ., 09 21 16-RESILIANT CHANNEL AT `i■r► t ALTERNATE TYPE ONLY NOTES: 1)1 HR FIRE RATED(BASED ON GA FILE NO.WP 8103) EXT - FIBER CEMENT PANEL - SHEAR cm] ALTERNATE TYPE - RESILIENT CHANNEL REFER TO CODE COMPLIANCE SUMMARY AND PLANS FOR RATED WALL LOCATIONS If this all sounds good to you, we can reissue you the pertinent sheets that will show updated wall types for these shear walls with plywood only and no Dens Glass. Thanks, Josh Cabot. LEED AP r,+u-c d: 5031105 7898 o: 503 4,15 78.72 SERA sustainable design for the built environment sera pdx.com DISCLAIMER This mencane and any nitachrnonis are intendcrt for the sole race crt the indrviauat or entity In whom it is addressed I; ma:'contain rnforn aline that rs pix rt qcd.confidential,and/ci e..cmpl from disc 1c1:7Liln under app'irahIs law It you are not the intended recipient you arc her rho notified that you n 1e!y not u<e copy dieclose or 0 aler,ute the,Irre.o,oage Cr ouy infornrrtron curt erred v;itltir ,.rrr.ludrno errry atlachnierito to rr yor;t If you hale received; thdc rnesarge r„error fyleace Immediately rdvra.e the-o€,•rder a rid penrr<rnent'y, 3 delete the message and any attachments and destroy any printouts made. Although we have taken steps to ensure that our e-mail and attachments are . free from viruses,the recipients should also ensure that they are virus free 4