NAC EOL VOLTAGE CALCULATION '2`
RECEIVED
CAPITOL ELECTRIC CO., INC. JAN 26 2021
(503) 255-9488 Office OFFICE COPY
(503) 255-1966 Fax CITY OF TIGARD
BUILDING DIVISION
Job Name: EMBASSY CENTER
Job Address: 9020 SW WASHINGTON SQUARE ROAD TIGARD, OR 97223
Job Number: Conductor Wire Gauge 14
Prepared By: ShaneTercek Ohms Per 1000 Ft @ 75 Deg C ( 167 Deg F ) 3.07
Date: 1/20/2021
Cable Length In Feet (source to end of line) 404
Total Circuit Current 1.227
Nominal System Voltage 20.4
Panel Description: SILENT KNIGHT 5495 Minimum Device Voltage 16
Panel No.: 5.1
Output No.: 4 Point To Point Method EOLv 18.55
Circuit Within Limits ? YES
NAC Devices Mfg By: System Sensor
Load Centering Method EOLv 18.88
Circuit Within Limits ? YES
Dev Device Location Device Model No. & Description Candella Alarm Distance From Voltage At
No. Rating Current Previous Device Device
( Feet)
1 SUITE 501, LITHIA SCWL 15cd Strobe, Ceil, Wht, Hi 15 0.060 68 19.89
2 SUITE 501, LITHIA SCWL 15cd Strobe, Ceil, Wht, Hi 15 0.060 19 19.75
3 SUITE 501, LITHIA PC2WL 15cd H/S, Ceil, Wht, Hi 15 0.107 56 19.37
4 SUITE 501, LITHIA PC2WL 177cd H/S, Ceil, Wht, Hi 177 0.286 34 19.16
5 SUITE 501, LITHIA PC2WL 15cd H/S, Ceil, Wht, Hi 15 0.107 48 18.95
6 SUITE 501, LITHIA PC2WL 15cd H/S, Ceil, Wht, Hi 15 0.107 22 18.87
7 SUITE 501, LITHIA PC2WL 75cd H/S, Ceil, Wht, Hi 75 0.179 53 18.71
8 SUITE 501, LITHIA PC2WL 15cd H/S, Ceil, Wht, Hi 15 0.107 55 18.60
9 SUITE 501, LITHIA PC2WL 15cd H/S, Ceil, Wht, Hi 15 0.107 25 18.57
10 SUITE 501, LITHIA PC2WL 15cd H/S, Ceil, Wht, Hi 15 0.107 24 18.55
11 18.55
12 18.55
13 18.55
14 18.55
15 18.55
16 18.55
17 18.55
18 18.55
19 18.55
20 18.55
NAC 5.1 EOLv Calc NAC, 4 CKT (20.4V Nominal) OUTPUT 4
•
NAC EXTENDER BATTERY CALCULATIONS
CAPITOL ELECTRIC CO., INC.
(503)255-9488 Office, (503) 255-1966 Fax
JOB NAME: EMBASSY CENTER
ADDRESS: 9020 SW WASHINGTON SQUARE ROAD TIGARD,OR 97223 DATE: 1/20/21
PANEL DESCRIPTION: SK 5495-7 PREPARED BY:Shane Tercek
DEVICE TOTAL DEVICE TOTAL
STANDBY STANDBY ALARM ALARM
DEVICE QUANTITY CURRENT CURRENT CURRENT CURRENT
NAC EXTENDER
Silent Knight 5495 NAC Panel 1 0.075 0.075 0.175 0.175
CIRCUIT#1 :114 ,7:1155BERESNEMESIMaSSOMENRESSZE
IFEMINEEREAKIN 0.000
ESTIMATED LOAD 1 rigningtaingar 1.200 1.200
tfflEMPONitian0.000
_: 0.000
0.000
RESPERNESSEM0.000
FAMERE liver ice. U 0.000
0.000
1 0.000
TOTAL 1.200
CIRCUIT#2 SlanitnierMIKEMZEZ
MEi '
ESTIMATED LOAD 1119111=MilBORANC 1.200 1.200
0.000
-. r w ,- 0.000
a .. ... ,..,,r G 0.000
riESSMIRMEragil 0.000
NEEREMELMES
0.000
11188103111EASSM 0.000
- M a 0.000
riggiaffEntlinaliSiniarliAamAIENNITERKLiZESERMISERE TOTAL 1.200
CIRCUIT#3 RISINEMERWLIMIARAILNOWEIMAINEINIESH
NAMMEIERREO 0.000
ESTIMATED LOAD 1 Ingisitamszlii 1.200 1.200
. 0.000
0.000
EREMENBEVON 0.000
ILSgignentartfli 0.000
0.000
- ,. .. �1 0.000
IMEINERNEASIVISERMaiKettatilaiSkinigiEREERREISSI TOTAL 1.200
CIRCUIT#4 SUITE 501 'ZIEREZMERIEMEMNETERREPREMSBW-
HaMainMilef=1 0.000
PC2WL 177cd HIS,Ceiling,Wht,Hi 1 0.286 0.286
iii
PC2WL 75cd HIS,Ceiling,Wht,Hi initattaiLVEES. 0.179 0.179
PC2WL 15cd HIS,Ceiling,Wht,Hi 6 0.107 0.642
SCWL 15cd Strobe,Ceiling,Wht,Hi 2 IVERIDEIRMIESE 0.060 0.120
USINEMSUNita 0.000
traMinalMARESr's- 0.000
0.000
0.000
LaiSMIRMEMBESSEVISIMENNLIEMERMENSERBEEREIN TOTAL 1.227
NAC 5.1 Batt Calc SK 5495 NAC Panel (20.4V Nominal)- Page 1 of 2
NAC EXTEN
DER BATTERY CALCULATIONS
CAPITOL ELECTRIC CO., INC.
(503) 255-9488 Office, (503) 255-1966 Fax
JOB NAME: EMBASSY CENTER
ADDRESS: 9020 SW WASHINGTON SQUARE ROAD TIGAR[ DATE: 1/20/21
PANEL DESCRIPTION: SK 5495-7 PREPARED BY: Shane Tercek
DEVICE TOTAL DEVICE TOTAL
STANDBY STANDBY ALARM ALARM
DEVICE QUANTITY CURRENT CURRENT CURRENT CURRENT
AUXILIARY DEVICES
0.000 0.000
0.000 0.000
0.000 0.000
TOTAL 0.000
STANDBY TOTAL CURRENT: 0.075
STANDBY HOURS: 24
STANDBY AMP HOURS: 1.800 NAC DEVICE CURRENT 4.827
ALARM TOTAL CURRENT: 5.002
ALARM MINUTES: 5
ALARM AMP HOURS: 0.417
TOTAL CALCULATED AMP HOURS 2.217
APPLIED SAFETY FACTOR 1.20
MINIMUM AMP HOURS REQURED 2.660
SELECTED BATTERY SIZE 12 EACH 12 VOLT, 7 AMP HOUR BATTERIES
NAC 5.1 Batt Calc SK 5495 NAC Panel (20.4V Nominal)- Page 2 of 2
r �
•
Indoor Selectable, '
Output Strobes and
Horn Strobes for 7cfct WI.
Ceiling Applications f �`; � � '
SpectrAlerfo Advance audible visible notification products
-4813
are rich with features guaranteed to cut installation times SPECTFIelrt
and maximize profits. ,
Features The SpectrAlert Advance series offers the most versatile and
easy-to-use line of horns, strobes,and horn strobes in the industry
• Plug-in design with minimal intrusion into the back box
With white and red plastic housings,wall and ceiling mounting
• Tamper-resistant construction options,and plain and FIRE-printed devices, SpectrAlert Advance
• Automatic selection of 12-or 24-volt operation at 15 and can meet virtually any application requirement.
15/75 candela
Field-selectable candela settings on ceiling units: 15, 15/75, 30, Like the entire SpectrAlert Advance product line,ceiling-mount
• strobes and horn strobes include a variety of features that increase
75,95, 110, 115, 135, 150, 177,and 185
their application versatility while simplifying installation.All devices
• Horn rated at 88+dBA at 16 volts feature a plug-in design with minimal intrusion into the back box,
• Rotary switch for horn tone and three volume selections making installations fast and foolproof while virtually eliminating
• Universal mounting plate for ceiling units costly and time-consuming ground faults.
• Mounting plate shorting spring feature checks wiring continuity To further simplify installation,SpectrAlert Advance utilizes a
before device installation universal mounting plate so you can mount them to a wide array
• Electrically Compatible with legacy SpectrAlert devices of back boxes.With an onboard shorting spring,installers can test
wiring continuity before the device is installed.
• Compatible with MDL3 sync module
• Listed for ceiling or wall mounting Installers can also easily adapt devices to a suit a wide range of
application requirements using field-selectable candela settings,
automatic selection of 12-or 24-volt operation,and a rotary switch
for horn tones with three volume selections.
Agency Listings
SIGNALING
44/;0. MEA I". I
LISTED APPROVED approved 7125:653:01ee(hmnstrorbess)
84011(chmes,horn strobes,horns) 3023572 MEA452-O5-E chime strobes)
85512(strobes) 7135-1653:0189(horns,chimes)
SpectrAlert Advance Specifications
Architect/Engineer Specifications
General
SpectrAlert Advance strobes and horn strobes shall mount to a standard 4 x 4 x 11/2-inch back box,4-inch octagon back box,or double-
gang back box.Two-wire products shall also mount to a single-gang 2 x 4 x 17/8-inch back box.A universal mounting plate shall be used for
mounting ceiling and wall products.The notification appliance circuit wiring shall terminate at the universal mounting plate.Also,SpectrAlert
Advance products,when used with the Sync•Circuit'°Module accessory,shall be powered from a non-coded notification appliance circuit
output and shall operate on a nominal 12 or 24 volts.When used with the Sync•Circuit Module, 12-volt-rated notification appliance circuit
outputs shall operate between 8.5 and 17.5 volts;24-volt-rated notification appliance circuit outputs shall operate between 16.5 and 33
volts. Indoor SpectrAlert Advance products shall operate between 32 and 120 degrees Fahrenheit from a regulated DC or full-wave rectified
unfiltered power supply.Strobes and horn strobes shall have field-selectable candela settings including 15, 15/75,30,75,95, 110, 115, 135,
150, 177,and 185.
Strobe
The strobe shall be a System Sensor SpectrAlert Advance Model listed to UL 1971 and shall be approved for fire protective service.
The strobe shall be wired as a primary-signaling notification appliance and comply with the Americans with Disabilities Act requirements for
visible signaling appliances,flashing at 1 Hz over the strobes entire operating voltage range.The strobe light shall consist of a xenon flash
tube and associated lens/reflector system.
Horn Strobe Combination
The horn strobe shall be a System Sensor SpectrAlert Advance Model listed to UL 1971 and UL 464 and shall be approved for
fire protective service.The horn strobe shall be wired as a primary-signaling notification appliance and comply with the Americans with
Disabilities Act requirements for visible signaling appliances,flashing at 1 Hz over the strobe's entire operating voltage range.The strobe light
shall consist of a xenon flash tube and associated lens/reflector system.The horn shall have three audibility options and an option to switch
between a temporal three pattern and a non-temporal(continuous)pattern.These options are set by a multiple position switch.On four-wire
products,the strobe shall be powered independently of the sounder.The horn on horn strobe models shall operate on a coded or non-coded
power supply.
Synchronization Module
The module shall be a System Sensor Sync•Circuit model MDL3 listed to UL 464 and shall be approved for fire protective service.The module
shall synchronize SpectrAlert strobes at 1 Hz and horns at temporal three.Also,while operating the strobes,the module shall silence the horns
on horn strobe models over a single pair of wires.The module shall mount to a 4 11/16 x 4 11/16 x 2 1/8-inch back box.The module shall also
control two Style Y(class B)circuits or one Style Z(class A)circuit.The module shall synchronize multiple zones.Daisy chaining two or more
synchronization modules together will synchronize all the zones they control.The module shall not operate on a coded power supply.
Physical/Electrical Specifications
Standard Operating Temperature 32°F to 120°F(0°C to 49°C)
Humidity Range 10 to 93%non-condensing
Strobe Flash Rate 1 flash per second
Nominal Voltage Regulated 12 DC/FWR or regulated 24 DC/FWR'
Operating Voltage Range2 8 to 17.5 V(12 V nominal)or 16 to 33 V(24 V nominal)
Operating Voltage Range(MDL3) 8.5 to 17.5V(12 V nominal)or 16.5 to 33 V(24V nominal)
Input Terminal Wire Gauge 12 to 18 AWG
Ceiling-Mount Dimensions(including lens) 6.8"diameter x 2.5"high(173 mm diameter x 64 mm high)
Ceiling-Mount Surface Mount Back Box Skirt Dimensions 6.9"diameter x 3.4"high(175 mm diameter x 86 mm high)
(SBBCR,SBBCW)
Notes:
1.Full Wave Rectified(FWR)voltage is a non-regulated,time-varying power source that is used on some power supply and panel outputs.
2. P,S,PC,and SC products will operate at 12 V nominal only for 15 and 15/75 cd.
AVDS10101
r Draw UL Current a Data
UL Max.Strobe Current Draw(mA RMS)
8-17.5 Volts 16-33 Volts
Candela DC FWR DC FWR
Standard Candela Range 15 123 128 66 71
15/75 142 148 77 81
30 NA NA 94 96
75 NA NA 158 153
95 NA NA 181 176
110 NA NA 202 195
115 NA NA 210 205
High 135 NA NA 228 207
Candela Range 150 NA NA 246 220
177 NA NA 281 251
185 NA NA 286 258
UL Max.Current Draw(mA RMS),2-Wire Horn Strobe,Standard Candela Range(15-115 cd)
8-17.5 Volts 16-33 Volts 4
DC Input 15 15/75 15 15/75 30 75 95 110 115
Temporal High 137 147 79 90 107 176 194 212 218
Temporal Medium 132 144 69 80 97 157 182 201 210
Temporal Low 132 143 66 77 93 154 179 198 207
Non-Temporal High 141 152 91 100 116 176 201 221 229
Non-Temporal Medium 133 145 75 85 102 163 187 207 216
Non-Temporal Low 131 144 68 79 96 156 182 201 210
FWR Input
Temporal High 136 155 88 97 112 168 190 210 218
Temporal Medium 129 152 78 88 103 160 184 202 206
Temporal Low 129 151 76 86 101 160 184 194 201
Non-Temporal High 142 161 103 112 126 181 203 221 229
Non-Temporal Medium 134 155 85 95 110 166 189 208 216
Non-Temporal Low 132 154 80 90 105 161 184 202 211
UL Max.Current Draw(mA RMS),2-Wire Horn Strobe,High Candela Range(135-185 cd)
16-33 Volts 16-33 Volts
DC Input 135 150 177 185 FWR Input 135 150 177 185
Temporal High 245 259 290 297 Temporal High 215 231 258 265
Temporal Medium 235 253 288 297 Temporal Medium 209 224 250 258
Temporal Low 232 251 282 292 Temporal Low 207 221 248 256
Non-Temporal High 255 270 303 309 Non-Temporal High 233 248 275 281
Non-Temporal Medium 242 259 293 299 Non-Temporal Medium 219 232 262 267
Non-Temporal Low 238 254 291 295 Non-Temporal Low 214 229 256 262
Horn Strobe Tones and Sound Output Data
Horn Strobe Output(dBA) _T ' era r��r2xi arr
8-17.5 16-33 24-Volt Nominal
Switch Volts Volts Reverberant Anechoic
Position Sound Pattern dB DC FWR DC FWR DC FWR DC FWR _
1 Temporal High 78 78 84 84 88 88 99 98
2 Temporal Medium 74 74 80 80 86 86 96 96
3 Temporal Low 71 73 76 76 83 80 94 89
4 Non-Temporal High 82 82 88 88 93 92 100 100
5 Non-Temporal Medium 78 78 85 85 90 90 98 98
6 Non-Temporal Low 75 75 81 81 88 84 96 92
7t Coded High 82 82 88 88 93 92 101 101
8t Coded Medium 78 78 85 85 90 90 97 98
9t Coded Low 75 75 81 81 88 85 96 92
tSettings 7, 8,and 9 are not available on 2-wire horn strobes.
AVDS IC101
SpectrAlert Advance Dimensions
6.8" 6.922" I— 2.5" 1
ill
Dla. dia.
Ell
\t �� 1 i i
t,t 2.5"
�� 1 J 0
•
Ceiling-mount horn strobes Ceiling back box surface mount back box
SpectrAlert Advance Ordering Information
Model Description Model Description
Ceiling Horn Strobes Ceiling Strobes
PC2R 2-Wire Horn Strobe,Standard cd, Red SCR Strobe,Standard cd,Red
PC2R-P 2-Wire Horn Strobe,Standard cd, Red,Plain SCRH Strobe,High cd,Red
(no"FIRE")marking SCW Strobe,Standard cd,White
PC2RH 2-Wire Horn Strobe,High cd,Red SCW-P Strobe,Standard cd,White,Plain(no"Fire")marking
--l• PC2W 2-Wire Horn Strobe,Standard cd,White SCWH Strobe,High cd,White
PC2W-P 2-Wire Horn Strobe,Standard cd,White, Plain Accessories
(no"FIRE")marking SBBCR Surface Mount Back Box,Ceiling,Red
PC2W-SP 2-Wire Horn Strobe,Standard Cd,White, "Fuego" SBBCW Surface Mount Back Box,Ceiling,White
marking
PC2WH 2-Wire Horn Strobe,High cd,White
PC2WH-P 2-Wire Horn Strobe,High cd,White, Plain
(no"FIRE")marking
PC2WH-SP 2-Wire Horn Strobe,High cd,White, "Fuego"
PC4R 4-Wire Horn Strobe,Standard cd,Red
PC4RH 4-Wire Horn Strobe,High cd,Red
PC4W 4-Wire Horn Strobe,Standard cd,White
Notes:
All-P models have a plain housing(no"FIRE"marking on cover)
All-SP models have"FUEGO"marking on cover
"Standard cd"refers to strobes that include 15,15/75,30,75,95,110,and 115 candela settings."High cd"refers to strobes that include 135,150,177,and 185
candela settings.
SYSTEM 02015 System Sensor.
SENSOR' 3825 Ohio Avenue•St.Charles, IL 60174 Product specifications subject to change without notice.Visit systemsensorcren
Phone:800-SENSOR2•Fax:630-377-6495 tot cunent product inhnation,including the latest version of this data sheet
AVDS10102•03/15