Loading...
Report 11.1(p50 SvJ crITtA Sanderson Fire Protection Inc. `\ 1-800-452-9955 www.sandersonfire.com S4RSCW The Northwest's Premier Choice for Fire Protection Systems, Service,&Equipment FIRE PROTECTION INC. SYSTEM INFORMATION JOB NAME: Twality Middle School RECEIVED 1460 SW 97th Ave Tigard, OR 97224 DEC 7 1.020 CITY OF rIGARD DATE: December 4, 2020 BOLDING DIVISION Design Manual: Ansul R-102 Restaurant Fire Suppression System Manual (Standard UL 300 Listed) SEP 01, 2014 SYSTEM INSTALLED PER NFPA 17, 17A, & 96 INCLUDING ALL APPLICABLE LOCAL CODE REQUIREMENTS. 3 GALLON- FIRE SYSTEM: • Total maximum flow for 3 gallon system is: 11 . Total flows used: 6 . • Total number of nozzles used: o Appliance 1 o Plenum 2 o Duct 2 • Total number of detectors used: 3 • Total number of fusible links & temperature rating: 3ea 0360 dea; 0ea @450 dea; 0ea 0500 deg. NOTE: Detectors placed above each appliance. Appliances underneath duct share same detector. 3 Gal Tank 1.5 Gal Tank • Supply pipe size: 3/8" 3/8" o Maximum supply line: 40' 32' o Maximum duct branch line: 8' 8' o Maximum plenum branch line: 4' 4' o Maximum appliance branch line: 12' 12' NOTE: Pipe length does not exceed maximums allowed per Ansul R-102 Manual • Power shutdown: Micro-switches (manual reset) • Fuel shutdown: Mechanical Gas Valve • System tied to building fire alarms: Y / NA (if applicable) • Remote pull location: 10-20'from hood on path of egress • K-class extinguisher: Yes, Located within 30ft of hood Tukwila,WA Portland, OR Eugene, OR 774 Industry Dr. 98188 1101 SE Third Ave. 97214 645 Wilson St. 97402 Corporate Headquarters