Loading...
The URL can be used to link to this page
Your browser does not support the video tag.
Report (2)
/2080 5w U ►CFQ,s1 e . VT$I 201 a-oo iso Y RECEIVED tAlif OCT 2 2 2020 CITY OF TIGARD 10. nl\IIRI N Worldwide www.tyco-fire.com Fire Protection Contacts Products BLAZEMASTER CPVC Fire Sprinkler Pipe & Fittings Submittal Sheet General Technical Description Data TYCO CPVC Pipe and Fittings pro- Sizes duced by Tyco Fire Protection Prod- 3/4 Inch thru 3 Inch ucts (TFPP) are designed exclusively Maximum Working Pressure • for use in wet pipe automatic fire 175 psi sprinkler systems. The TYCO CPVC Approvals Pipe and Fittings are produced from UL and C-UL Listed BLAZEMASTER CPVC compound FM Approved ail that is a specially developed thermo- LPCB Approved VOW plastic compound composed of post NSF Certified chlorinated polyvinyl chloride (CPVC) MEA Approved resin and state of the art additives. City of Los Angeles TYCO CPVC Pipe and Fittings are (Refer to Installation Handbook IH-1900 "�' k easier to install than traditional steel dated June 2008 for exact listing/approval pipe systems, and at the same time, information.) provide superior heat resistance and Manufacture Source Installation strength as compared to traditional U.S A. TYCO CPVC Pipe and Fittings are to CPVC and PVC piping materials used Material be to be installed in accordance with in the plumbing trade. Various adapt- Pipe: Installation Handbook IH-1900 dated ers are available to connect CPVC ASTM F442,SDR 13.5 April 2016. pipe to metallic piping.All female pipe Fittings: thread adapters have brass inserts for ASTM F438(Sch.40) durability. Grooved adapters connect ASTM F439(Sch.80) directly to grooved end valves and ASTM F1970 metallic pipe,with flexible grooved end Color couplings. Orange NOTICE The CPVC Pipe and Fittings produced with BLAZEMASTER CPVC compound described herein must be installed and maintained in compliance with this document and with the applicable standards of the National Fire Protec- tion Association(NFPA), in addition to the standards of any authorities having jurisdiction.Failure to do so may impair the performance of these devices. The owner is responsible for main- taining their fire protection system and devices in proper operating con- dition. Contact the installing contrac- tor or product manufacturer with any questions. Page 1 of 2 APRIL 2016 TFP1915 TFP1915 Page 2 of 2 Care and Limited Maintenance Warranty TYCO CPVC Pipe and Fittings are to be For warranty terms and conditions,visit maintained and serviced in accordance www.tyco-fire.com with this section. Before closing a fire protection system control valve for inspection or main- tenance work on the fire protection system that it controls, permission to shut down the affected fire protection system must first be obtained from the proper authorities and all person- nel who may be affected by this action must be notified. After placing a fire protection system in service,notify the proper authorities and advise those responsible for moni- toring proprietary and/or central station alarms. The owner is responsible for the inspec- tion,testing, and maintenance of their fire protection system and de-vices in compliance with this document, as well as with the applicable standards of the National Fire Protection Associa- tion (e.g., NFPA 25), in addition to the standards of any authority having juris- diction.Contact the installing contrac- tor or product manufacturer with any questions. Automatic sprinkler systems should be inspected,tested,and maintained by a qualified Inspection Service in accor- dance with local requirements and/or national codes. GLOBAL HEADQUARTERS 11400 Pennbrook Parkway,Lansdale,PA 19446 I Telephone+1-215-362-0700 Copyright 02016 Tyco Fire Products,LP. All rights reserved. tyco BLAZEMASTER is a trademark of The Lubrizol Corporation. Firs Protection Products e OFFICE COPY RECEIVED BUILDING DIVISION em: yy � ja l : n Features • Includes flared edges to protect piping m • Rated for use with CPVC fire sprinkler pipe 73 vl t }'67 Ms e '' Specifications Material: Steel Finish: Pre-galvanized aOus ipe Si Part Number 1 Pze Outer Diameter I Hole Size I A I B c I Hanger spacing HS 1080075EG 3/4" 1.050" 7/32" 3 1/4" 2 1/4" 1 3/16" 6'Max 1080100EG 1 1.315" 7/32" 3 1/2" 2 1/2" 1 3/16" 6'Max 1080125E6 1 1/4" 1.660" 7/32" 4 1/4" 3 1/4" 1 3/16" 7' Max 1080150EG 1 1/2" 1.900' 7/32" 4 7/16" 37/16" 1 3/16 7'Max 1080200EG 2" 2 3/8" 7/32" 4 15/16" 3 15/16" 1 3/16" 8' Max I CADDY. 28 www.erico.com M p e E . Features • Includes flared edges to protect pipingLe • Rated for use with CPVC fire sprinkler pipe �a > e LJ: fill HIFT ! ....._1 Specifications Material:Steel Finish: Pre-galvanized cOus Part Number PipeOuter Diameter Hole Size Size I OD ... . HS A I B 111 t Hanger Spacing 1090075EG 3/4" 1,050" 7/32" 2 5/16" 1 11/16" 1 3/16" 6'Max 1090100EG 1" 1.315" 7/32" 2 5/8" 1 15/16" 1 3/16" 6'Max 1090125EG 1 1/4" 1.660" 7/32" 2 15/16" 2 5/16" 1 3/16" 7'Max 1090150EG 1 1/2" 1.900" 7/32" 3 3/16" 2 1/2" 1 3/16" 7' Max 1090200EG 2" 2 3/8" 7/32" 3 5/8" 3" 1 3/16" 8' Max . www.erico.com 29 R1 '■`++ . ''''.'616§:ittigmirritylifi22:1!firaP:'%2:::::5:::;5::::::5:6:10tifirti:,,le ' „may «FA a nt5,,pi.. a i '.: . .. . a " 9 r k as _ d I il�1 1 � - pp n Features z • Includes flared edges to protect piping m • Rated for use with CPVC fire sprinkler pipe N, ,v+ { -+ m Specifications Material: Steel Finish: Pre-galvanized CC as - Hok Size Han er Standard Park Number Pipe Size H5 A 0 C 5 ac9r Packaging Listings p 'r9 Quantity SOSR075 3/4" 0.2" 2 11/16" 3 5/8" 1" 6'Max 100 pc cUL, UL SOSR075810 3/4" 0.2" 2 1 1/16" 3 5/8" - 1" 6'Max 10 x 10 pc - SOSR100 1" 0.2" 2 15/16" 3 11/16" 1" 6' Max 100 pc cUL, UL SOSR100810 1" 0.2" 2 15/16" 3 11/16" 1" 6'Max 10 x 10 pc - SOSR125 1 1/4" 0.2" 3 5/16" 3 5/8" 1" 6' Max 100 pc cUL, UL SOSR1251310 1 1/4" 0.2" 35/16" 3 5/8" 1" 6'Max 10x 10 pc - SOSR150 1 1/2" 0.2" 3 7/8" 4 1/2" 1" 7'Max 100 pc cUL,UL S0SR150610 1 1/2" 0.2" 3 7/8" 4 1/2" 1" 7'Max 10 x 10 pc - SOSR200 2" 0.2" 4" 5 1/4" 1" 8' Max 100 pc cUL,UL SOSR200810 2" 0.2" 4" 5 1/4" 1" 8'Max 10 x 10 pc - (f:.� 1 4145 . 30 www.erico.com RECEIVED Y'Y .4 w.,u.. i.. -.-A. 4 OCT 2 2 2020 rtTY OF TIGARD Page : 1 of 8 i3U1LDING Dtti"�tON SENJU SPRINKLER CO.,LTD. 11 Residential Lead Free Flat Concealed Sprinkler, Pendent, I�I Model: RC-RES, K-Factor: 4.9, SIN: SS8464 GENERAL DESCRIPTION The Model RC-RES Residential Flat Concealed Sprinklers are automatic sprinklers of the compressed fusible solder type. These are decorative and fast response. The Cover Plate Assembly hides the Deflector, Heat Responsive Element etc.,which is in turn concealed above the ceiling. The cover plate has a flat profile, and its diameter is extremely small (2-5/8 inch, 68mm). The push-on and/or thread-on, thread-off design of the concealed cover plate assembly allows easy installation of the cover plate. Therefore, the Model RC-RES should be your first choice when aesthetics is the major consideration for ultimate appeal and unbeatable performance is desired. The Model RC-RES is designed for the residential occupancies and it is perfect for use in homes, hotels and other living quarters. The Model RC-RES is to be used in wet pipe residential sprinkler systems for One- and Two- Family Dwellings and Manufactured Homes per NFPA 13D; wet pipe residential sprinkler systems for Residential Occupancies up to and Including Four Stories in Height per NFPA 13R; or,wet pipe sprinkler systems for the residential portions of any occupancies per NFPA 13. The Model RC-RES has a 4.9 (70.6 LPM/bar12) K-factor that meets the required residential flow rates with minimal residual pressure,which allows for smaller pipe sizes and water supply requirements. For extended installation flexibility, the Model RC-RES provides 1/2 inch (12.8mm) vertical adjustment. This adjustment in installation decreases the need for precise cutting of the pipe that drops to the sprinkler and allows for a perfect fit with a range of pipe lengths. The heat sensitivity and water distribution design of Model RC-RES allows for an increased chance of residents' escape or evacuation in case of fire. However, residential fire sprinkler systems are not a substitute for fire safety awareness or fire safety construction required by building codes. "Lead Free" is defined in the Reduction of Lead in Drinking Water Act (S.3874) endorsed by AWWA's Water Utility Council, and California Assembly Bill #1953 as having less than or equal to a weighted average of 0.25% lead in wetted surface of pipes, plumbing fittings and fixtures. WARNINGS The Model RC-RES must be installed and maintained in accordance with the rules stated herein as well as in compliance with the applicable standards of the National Fire Protection Association regulations and the standards of any other authorities having jurisdiction. In the event of this condition, consult the authorities having jurisdiction for guidance and approval. Failure to do so may impair the integrity of these devices. It is the responsibility of the installing contractor to provide a copy of this document to the owner or his representative, and in turn, it is the obligation of the owner to provide a copy of this document to a succeeding owner. The owner is responsible for maintaining their fire protection system and devices in proper operating condition. The installing contractor or sprinkler manufacturer should be contacted with any related questions. Document No.U085160 Date : Feb/09/2015 ) TECHNICAL DATA Page : 2 of E. Approvals: cULas Listed, NSF-61-G Sprinkler Identification Number(SIN): SS8464 2-Y,fi"(0 52mm) Maximum Working Pressure: 175psi(12.1bar) NPT1 2 . kin. Discharge Coefficient(Nominal K-Factor): Lot No. Year of Manufacture K=4.9 GPM/psia"2(70.6 LPM/bar12) o I I 4 SIN:sse464 K—factor:K4.9 Temperature Rating: E - -- Temperature Rating:167F/72'C 162 F (72°C)Sprinkler with 140 F (60°C)Cover Plate ��l i UL Mark or ns•F/79'C Control No.:6P37 175T (79°C)Sprinkler with 162'F (72°C)Cover Plate g L (.^F NSF Mark:NSF-61—G 0 ' �r4' RES SPKR Color Code(Sprinkler) �'I 0 ail• 1 tard 162`F (72°C): Uncolored N 0 i m Body(Copper Alloy) 175'F (79°C):White I i ®Deflector(Phosphorus Bronze) Ala, - �— m Gasket(PTFE) Color Code(Cover Plate) a.1111 _ O Fusible Metal(Solder) 140'F (60°C): No Mark 2-a-(0 68mm) t Heat Collector(Copper) ®Cover Plate Assembly 162T (72°C):White-Colored Mark or 3-XI"(083mm) Vertical Adjustment: 1/2 inch(12.8 mm) or 2-%"square(❑68mm) Cover Plate Finishes: Standard Finishes- FIGURE 1. Model RC-RES K=4.9 White, Ivory, Beige, Brown, Black, Nickel, Wood Grain Color Cade ... Custom Finishes- � SIN:SSe464 eroactor:K4.9 Custom color and custom pattern cover plates are . • Temperature Rating available on special order. Contact a Senju ,M211 \`� eL6Mor 7C° US'F/79'C Sprinkler representative with any custom orders. '_= J '-/ Please see chart on Page 8 for more detail. . Physical Characteristics: Ref.Figure 1 ��-P" COVER PLATE SPRINKLER (Top view) (Bottom view) OPERATION FIGURE 1-1.Marking(Color Code) In case of fire, the solder component that holds together the Cover Plate and the Retainer melts. Then, the Cover Plate is released at once. As a result, the Deflector drops down to the intended position. Two Heat Collectors are exposed to fire, and when sufficient heat from the fire is recorded, internal components of the sprinkler to fall apart.This leads to allow the water flow to be distributed on the affected by fire area. (Ref. Figure 2) / / / xi, p,iff, ;,, , rl 715. " ;12:T1.7...,71 „,,, 0 .., Ii� 11 1 / IS, ,, . ,, -� .. . _17 ,,, r ! , , Normal Condition No, Cover Plate Operation .♦ Sprinkler Operation y Water Discharge FIGURE 2. OPERATION PROCESS (The figure is for illustrative purpose only) Document No.U085160 Date :Feb/09/2015 Page :3 of 8 DESIGN CRITERIA The herein stated rules for use and installation of Model RC-RES are provided by the manufacturer and must be strictly implemented for safe and full results. NOTES Residential Fire Sprinkler Systems should only be designed and installed by individuals who are completely familiar with automatic sprinkler system design,installation procedures,and techniques. Several criteria may apply to the installation and usage of each sprinkler. Consequently, it is recommended that the sprinkler system designer review and develop a working understanding of the complete list of criteria prior to initiating the design of the sprinkler system. Questions concerning sprinkler installation and usage criteria, which are not coverage by the following instructions, should be submitted to Contact Company. Include sketches and technical details as appropriate. In some instances, the requirements of this document may concern specifications which are more stringent and which - take precedence over those specified in NFPA 13, 13D, 13R, or by the authority having jurisdiction. The Model RC-RES must not be used in applications where the air pressure above the ceiling is greater than that below. Inspect all sprinklers after installation to ensure that both the gap between the cover plate,ceiling and the 6 slots in the cup are open and free from any air flow impediment. The spray from the sprinkler is distributed radically outward and downward from the sprinkler deflector. Consequently, the sprinklers must be located such that there will be no blind spaces shielded from spray by partitions, room dividers, overhangs or other parts of the dwelling structure. The number of sprinklers within each compartment (as defined by NFPA 13, 13D, or 13R) must be kept as small as possible.Do NOT use more sprinklers than necessary to cover a particular space. Use only the Cover Plate provided with the Model RC-RES. The sprinkler must be secured in place by firmly fastening the sprinkler system piping to the structure. If the sprinkler is not properly secured in position, reaction forces resulting from sprinkler operation could alter its orientation and its water distribution pattern. Obstruction to Water Distribution Locations of sprinklers must follow the obstruction rules of NFPA 13 for Residential Sprinklers. General Service Conditions The Model RC-RES must only be utilized in WET PIPE sprinkler systems. Heat Source Criteria Refer to NFPA 13D or 13R for the requirements relating to the prevention of possible activation of the Heat Responsive Element of Model RC-RES, due to exposure to a heat sources other than an actual fire. Precautionary Warnings for Corrosive Environments The Model RC-RES should not be installed where they may be subjected to a corrosive environment including the following: (1) Chlorine ion and Chloride environment. Stress corrosion cracking may be caused by exposure to environments with Chlorine ion and Chloride. Exposure to this environment may result in sprinklers operating under Non-Fire conditions or Not Operating when exposed to an actual fire. (2) Sprinkler system piping with Copper. Sprinkler systems should be constructed in compliance with the applicable standards and the requirements for the copper piping when copper piping is used in the sprinkler system. (Reference standards NFPA 13, ASTM B813, B828, and CDA (Copper Development Association)—Solder Joint) All residual flux must be removed from the interior and exterior of copper piping by thoroughly flushing before installation of the Sprinkler Heads. Otherwise, residues of flux may cause corrosion and leakage in the sprinkler system. Hydraulic Design Criteria The minimum required sprinkler flow rates for system designed to NFPA 13D or 13R are given in Table A as a function of temperature rating and the maximum allowable coverage areas. The sprinkler flow rate is the minimum required discharge from the most hydraulically demanding sprinkler from each of the total number of"design sprinklers"as specified in NFPA 13D or 13R. For systems designed to NFPA 13, the number of designed sprinklers is to be the four most hydraulically demanding sprinklers. The minimum required discharge from each of the four sprinklers is to be the greater of the followings; • The flow rates given in Table A for NFPA 13D and 13R as a function of temperature rating and maximum allowable coverage area. Document No.U085160 Date : Feb/09/2015 1 Page :4ofa. - • A minimum discharge 0.1GPM/sq.ft. [4.07LPM/sq.m] over the "design area" comprised of the four most hydraulically demanding sprinklers for the actual coverage areas being protected by the four sprinklers. TABLE A. NFPA 13D & 13R WET PIPE HYDRAULIC DESIGN CRITERIA for Model SS8464 Maximum Ordinary Intermediate Coverage Maximum Temperature Rating Temperature Rating Deflector Minimum Area(e) Spacing 162°F (72°C) 175`F (79°C) Installation Spacing Ft. Flow(b) Pressure(b) Flow(b) Pressure(b) to Type Ft. Ft. x Ft. (m) GPM PSI GPM PSI Ceiling (m) (m xm) (LPM )) (bar) (LPM) (bar) Smooth 12x12 12 13 7.0 13 7.0 Ceilings (3.7x3.7) (3.7) (49.2) (0.48) (49.2) (0.48) 3/8 to 7/8 Inches. 14x14 14 13 7.0 13 7.0 (4.3x4.3) (4.3) (49.2) (0.48) (49.2) (0.48) Beamed Ceilings • per NFPA 16x16 16 13 7.0 14 8.2 13D,13R 8 (4.9x4.9) (4.9) (49.2) (0.48) (53.0) (0.57) or 13 Concealed (2.4) Installed in beam 18x18 18 17 12.0 18 13.5 3/8 to (5.5x5.5) (5.5) (64.3) (0.83) (68.1) (0.93) 7/8 inches 20x20 20 21 18.4 below (6.1x6.1) (6.1) (79.5) (1.27) — — bottom of beam. (a) For coverage area dimensions less than the above mentioned, it needs to use the minimum required flow for the Next Higher Coverage Area listed. (b) Requirement is based on minimum flow in GPM/LPM from each sprinkler.The associated residual pressures are calculated using the nominal K-Factor. Refer to Hydraulic Design Criteria Section for details. (c) For systems with ceiling types smooth flat horizontal, or beamed, or sloped, in accordance with the 2013 Edition of NFPA 13D, 13R or 13 as applicable. Sprinkler Spacing Criteria The minimum spacing between sprinklers is 8 feet(2.4m). The maximum spacing between sprinklers cannot go beyond the coverage area calculated by using the specific hydraulic factors. (Ref. Table A) INSTALLATION The Model RC-RES must be installed in accordance with the following instructions. NOTES Do not use any sprinklers which have been subjected to potential mechanical damage.Do not use any sprinklers which show deformation or cracking in either the Sprinkler or the Protective Cap. Prior to installation, sprinklers should be maintained in the original cartons and packaging until used to minimize the potential for damage to sprinklers that would cause improper operation or non-operation. The Protective Cap must remain on the sprinkler during installation and until the ceiling installation is completed. The Protective Cap must be removed to place the sprinkler in service. Document No.U085160 Date :Feb/09/2015 f Page : 5 of 8 Use a torque of 7 to 14 ft.lbs(9.5 to 19.0Nm) to achieve a 1/2 inch NPT sprinkler joint. If you exceed the recommended maximum torque, this could result in damage to the sprinkler inlet, which may lead to leakage from the sprinkler. In case of insufficient adjustment in Cover Plate installation, do not try to overly tighten,screw the sprinkler too loosely or make any modification to the cover plate assembly. Readjust the sprinkler fitting for a better fit. Installing Procedure Step 1 The installation requirements for the sprinkler are as follows: to be installed only in the pendent position with the waterway perpendicular to the ceiling. Install the sprinkler fitting so that the distance from the face of the fitting to the mounting surface will be nominally 2 inch(50.8mm)as shown in Figure 3. Step 2 With pipe thread sealant applied to the threads, hand tighten the sprinkler into the sprinkler fitting. Then tighten it with the Sprinkler Socket or Wrench & Socket Combination (Ref. Figure 4). The grooves of the Socket must fit perfectly with the grooves on the Sprinkler for proper installation(Ref. Figure 4). Step 3 If desired the Protective Cap may also be used to locate the center of the clearance hole by gently pushing the ceiling material against the center point of the Protective Cap. Before the installation of the ceiling, the sprinkler installation can be started with the 2-3/8 inch (60mm) diameter clearance hole (Ref. Figure 3). Use the "Tolerance Limit of Ceiling Level" indicator on the Protective Cap to check for proper installation height(Ref. Figure 3). Make a Space Here Do NOT Ave.y"(6.4mm) Over—Tighten 1110 Groove on the S.rinkler Min.W.(3.2mm) L Tolerance Limit Protective Co. of Ceilin Level MI=1 riBl�ll19 Mountin Surface • ry Groove of h- Socket Mounting Surface (060mm) •cket Wrench Ceiling Hole Diameter CORRECT INCORRECT _ FIGURE 3. INSTALLATION FIGURE 4 Step 4 Use the Cap Remover RC to remove the Protective Cap(Ref. Figure 5), and then push or screw a Cover Plate Assembly on the Cup of the Sprinkler by hand until its flange just comes in contact with the ceiling (Ref. Figure 6 and Figure 7). Stop tightening the Cover Plate Assembly once the flange has come in contact with the ceiling. lithe ceiling has been lifted from its normal position in the process of tightening of the Cover Plate Assembly, readjust the cover plate assembly as necessary. If the flange of the Cover Plate Assembly cannot come in contact with the ceiling sufficiently, readjust the sprinkler fitting as necessary. When properly installed, there is a nominal 1/16 inch (1.6mm) air gap between the lip of the Cover Plate and the ceiling, as shown in Figure 6 Document No.U085160 Date : Feb/09/2015 1 Page : 6 of t? IN alb IMO ■o am. !Tool Sprinkler Head ' ' �' '�' ■ ■ Protective Ca. — II 11.111 lei :A: Mill �_—� Step 1Iiimmil Mii ■ Ca Remover RC Step 2 RI ■ Hook by turning III Step 3 I Pull down FIGURE 5. PROTECTIVE CAP REMOVAL In IN 1111 LO S NNW. c u. NSIU lmml mom lml Ma E ■ ■ ■l1�-�1 E r: ail r II :Ceiling ' Ceiling E y /II \ /Ceiling/ IllI + IllerCeiling, Mounting Surface i' Screw E 4 Deflector v « * u /Cover Plate Assembly e. ! ....-.-1 r 2-'4"(I5 68mm) or 3-y-(083mm) or 2-j"square(E68mm) FIGURE 6 WI E Ille !El _ WWII .--. MNnr .I.I. I1 ±:3_ i E •ICI o I N ■ l' Iri ,.. rJiiii_pm g a —_ ____- _—_-- ------ ----- ' / �/ NI /�. N /Ceiling • 1_'�Cei ling,l` aj ' J� INCORRECT CORRECT INCORRECT FIGURE 7. INSTALLATION(CORRECT OR INCORRECT) Document No.U085160 Date : Feb/09/2015 f Page : 7 of 8 CARE AND MAINTENANCE The following instructions must be implemented for the maintenance and service of the Model RC-RES. NOTES Wet pipe sprinkler systems must be maintained at a minimum temperature of 40T/4`C to prevent freezing and bursting of the pipe and/or sprinklers. Automatic sprinklers are not to be tested with a heat source. Operation of the heat responsive element can result. Absence of a Cover Plate Assembly may delay the response time of the sprinkler in case of fire. Install the cover plate assembly properly, as shown in Figure 6. Improper installation of the cover plate assembly may cause improper operation or non-operation. If the ceiling is to be repainted after the installation of the Sprinkler, care must be exercised to ensure that the new paint does not seal off any of the air gap. Factory painted Cover Plates must not be repainted. They should be replaced, if necessary, by factory painted cover plates.Non-factory applied paint may adversely delay or prevent sprinkler operation in case of a fire. Do not pull the Cover Plate. Separation may result. In preparation for maintenance of the fire protection system, permission to close the main control valve must be obtained from the proper authorities and all affected by this action parties must be informed before the maintenance session can commence. Do NOT enclose any sprinklers within drapes, curtains, or valances. Do NOT hang anything from the sprinklers. Do NOT clean the sprinklers with soap and water, detergents, ammonia, cleaning fluids, or other chemicals. Remove dust, lint, cobwebs, cocoons, insects, and larvae by gently brushing with a feather duster or gently vacuuming with a soft bristle(i.e., dusting)brush attachment. Exercise suitable safety precautions in the use and storage of highly flammable materials. The rapid rate of fire development and spread of these materials can reduce the ability of the sprinkler systems to aid in the control of a fire involving such hazards. Leaking or corroded sprinklers must be replaced Automatic Sprinklers must never be shipped or stored where the temperature exceeds 100`F/38°C. Automatic sprinkler must never be physically altered, such as painted, plated, or coated, once shipped from the factory. If the sprinklers have been in any way modified, they must be replaced. Great caution must be applied to prevent damage to the sprinklers at all stages- before, during, and after installation_ Damaged units, as a result of dropping, hitting, over-tightening, or wrench slippage, must be replaced. The Model RC-RES must only be replaced with pendent sprinklers which are listed for residential fire protection service and which have the same nominal K-Factor,the same coverage area, and the same or lower flow ratings(as indicated under Table A "Hydraulic Design Criteria"). When remodeling, such as by adding false beams or light fixtures or changing the location of compartment walls, first verity that the new construction will not violate the installation requirements of the applicable standards of NFPA.Alter the new construction and/or the sprinkler system to suit the requirements of this document and the applicable NFPA regulations. The owner is responsible for the maintenance of the sprinkler system, including inspection and testing, its compliance with this documents, as well as the standards of the National Fire Protection Association(e.g., NFPA 25), and the regulations of any other authorities having jurisdiction. The owner should direct any questions regarding the above rules and regulations to the installing contractors or the sprinkler manufacturer. It is recommended that automatic sprinkler systems be inspected, tested, and maintained by a qualified Inspection Service in accordance with NFPA 25. Document No.U085160 Date : Feb/09/2015 Page : 8of8. , ORDER PROCEDURE When placing an order, please contact a local distributor with the following information(Model Name, Specify,Temp. and Finish). Sprinkler: Model: RC-RES (SIN: SS8464, Residential Flat Concealed Sprinkler, Pendent, K4.9,Temperature: 162T (72°C)or 175°F (79°C)) Cover Plate Assembly: 2-5/8 inch(. 68mm)or 3-1/4 inch(083mm)or 2-5/8 inch square(068mm), Order Separately from Sprinkler Please refer to the chart below for available sizes, temperature, and finishes. Standard Finishes Custom Finishes White Ivory Beige Brown Black Nickel Wood grain Custom Color Custom Pattern 2-5/8"Round, 140°F 0 0 - - - 0 - 0 0 3-1/4"Round, 140°F 0 0 0 0 0 0 0 0 0 2-5/8"Square, 140°F 0 - - - - - - 0 0 2-5/8" Round, 162°F 0 - - - - - - 0 0 3-1/4" Round, 162°F 0 - - - - - - 0 0 Tools for Installation of Model: RC-RES • Socket for Model RC-RES • Wrench&Socket for Model RC-RES • Cap Remover RC Document No.U085160 Date :Feb/09/2015 , •liHydraulic Summary ' Job Number: 1 ®®®® Report Description:Residential Job Job Ncmbnr Demon Engineer Sye.nxy � 1 �h 1 . x lt.L1 i 'r m .« Jots Names Slab Certification/License Number Drawings OCT2 2 2G Address -- ?,, AHJ Address -- doe Hnedemloiny cm OF TK3AkD BUILDING UIVtSt0 Address 3 _ - Draw,ng Name — Razilov.cad ystem Remote Area(s) Most Demanding Spunkier Data Occupancy Job Suffix 4.9 K-Factor 12.96 at 7.000 Residential Hose Allowance Al Source Density Ares orApplication _. 0.00 0.100gpm/ft3 512.00ft'(Actual 213.43ft2) Additional Hose Supplies Number OtSprinklers Calculated Coverage Per Speirkler Node Flow(gom) 2 100.00f12 Aulopeak Results:Preasue For Remote Area(s)Aellecent To Meet Remote Area Left:45.423 Idol Hose Streams 0.00 System Flow Demand Total Water Required(Including Mose Allowance) 26.21 26.21 Maximum Pressure Unbalance In heaps 0.000 Maximum Velocity Above Ground 10.19 between nodes 3 and 2 Maximum Velocity Under Ground Volume capacity of Wet Pipes Volume capacity of Dry PIpes 47.81 gal Supplies 1 Hose Flow Static Residual @ Flow Available @ Total Demand Required Safety Margin Node Name , WIN/1) (psi) (psi) (gpm) (psi) (gpm) (psi) (psi) 3 Water Supply 60.000 50.000 50.00 56.973 26.21 46.545 10.428 Contractor Cori:actor Nd cher .,nrsc:Ner.c. cpnLFlc:nnc I Name of Contractor. _.— Phone E,lenelon Address I -- - — FAX Address 2 "-- Address 3 Web-Site k,©M.E.P.CAD,Inc. a AutoSPRINK®12 v12.0.61.0 9/17/2020 11:40:34AM Page 1. , Hydraulic Graph Job Number: 1 Report Description:Residential Water Supply at Node 3 100 • 90 80 70 60—Static Pressure 60.000 N d 50 '50.00 @ 50.000 1 .21 @ 46.545 a` 40 30 System demand curve 20 10 0 tl0tl011111111111111 111111111 1{111I111 I l l I l l 1 1 1 1 1 1 1 1 1 1 I 1 1 1 1 1 1 It ! I 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 010 20 3040 50 60 70 8090 100 Water flow,gpm Mydraulc Graph Water Supply at Node 3 Slatc:Pressure 60.000 Residual:Preeaura 50.000 @ 50.00 Avedetle Pressure at Time of Test 56.973 @ 26.21 System Demand 46.545 @ 26.21 System Demand(Mc4dnp Nose Morten.,al Source) 46.545 @ 26.21 [,©M.E.P.CAD, Inc. Vfi AutoSPRINK012 v12.0.61.0 9/17/2020 11:40:45AM Page 2 ij Summary Of Outflowng Devices 1 Job Number: 1 Report Description: Residential Actual Flow Minimum Flow K-Factor Pressure Device (gpm) (gpm) (K) (psi) c;? Sprinkler 101 12.96 12.96 4.9 7.000 Sprinkler 102 13.24 12.96 4.9 7.305 1 Most Demanding Sprinkler Data LM,©M.E.P.CAD, Inc. id AutoSPRINK®12 v12.0.61.0 9/17/2020 11:40:51AM Page 3 if 9 Node Analysis Job Number: 1 y, Report Description:Residential Node Elevation(Foot) Fittings Pressure(psi) Discharge(gpm) 3 -7'-314 S,T(2'-0) 46.545 26.21 101 20'-0 Spr(-7.000) 7.000 12.96 102 20'-0 Spr(-7.305) 7.305 , 13.24 1_ 0'-0 cplg(1'-0) 25.459 2 -3'-0 AngV(4'-0) 45.577 k,®M.E.P.CAD,Inc. 411AutoSPRINK®12 v12.0.61.0 9/17/2020 11:40:57AM Page 4 4119. Hydraulic Analysis Job Number: 1 1!� ��ff Report Description:Residential Pipe Type Diameter Flow Velocity HWC Friction Loss Length Pressure Downstream Elevation Discharge K-Factor Pt Pn Fittings Eq.Length Summary Upstream Total Length ea Route 1 BL 1.1010 12.96 4.37 150 0.030510 10'-0 Pf 0.305 101 20'-0 12.96 4.9 7.000 Sprinkler Pe 102 20'-0 7.305 10'-0 Pv BL 1.1010 26.21 8.83 150 0.112193 48'-6'/* Pf 9.483 102 20'-0 13.24 4.9 7.305 Sprinkler, 36'-0 Pe 8.671 1 0'-0 25.459 4E(5'-0),3T(5'-0),cplg(V-0) 84'-6'% Pv BL 1.2490 26.21 6.86 150 0.060703 302'-0 Pf 18.818 1 0'-0 25.459 8'-0 Pe 1.301 2 -3'-0 45.577 E(4'-0),AngV(4'-0) 310'-0 Pv BL 1.0250 26.21 10.19 150 0.158644 15'-0 Pf 2.702 2 -3'-0 45.577 2'-0 Pe -1.734 3 -7'-3'% 46.545 S,T(2'-0) 17'-0 Pv Equivalent Pipe Lengths of Valves and Fittings(C=120 only) II C Value Multiplier I Actual Inside Diameter 4'87 Value Of C 100 130 140 150 ( Schedule 40 Steel Pipe Inside Diameter ) =Factor Multiplying Factor 0.713 1.16 1 33 1.51 Pipe Type Legend Units Legend Fittings Legend AO Arm-Over Diameter Inch ALV Alarm Valve BL Branch Line Elevation Foot AngV Angle Valve CM Cross Main Flow gpm b Bushing DN Drain Discharge gpm BalV Ball Valve DR Drop Velocity fps BFP Backflow Preventer DY Dynamic Pressure psi BV Butterfly Valve FM Feed Main Length Foot C Cross Flow Turn 90° FR Feed Riser Friction Loss psi/Foot cplg Coupling MS Miscellaneous HWC Hazen-Williams Constant Cr Cross Run OR Outrigger Pt Total pressure at a point in a pipe CV Check Valve RN Riser Nipple Pn Normal pressure at a point in a pipe DelV Deluge Valve SP Sprig Pf Pressure loss due to friction between points DPV Dry Pipe Valve ST Stand Pipe Pe Pressure due to elevation difference between indicated points E 90°Elbow UG Underground Pv Velocity pressure at a point in a pipe EE 45°Elbow Eel 11%°Elbow Ee2 22%°Elbow f Flow Device fd Flex Drop FDC Fire Department Connection fE 90°FireLock(TM)Elbow fEE 45°FireLock(TM)Elbow fig Flange FN Floating Node fT FireLock(TM)Tee g Gauge GloV Globe Valve • GV Gate Valve Ho Hose Hose Hose HV Hose Valve Hyd Hydrant LtE Long Turn Elbow mecT Mechanical Tee Noz Nozzle P1 Pump In P2 Pump Out PIV Post Indicating Valve PO Pipe Outlet PRV Pressure Reducing Valve PrV Pressure Relief Valve red Reducer/Adapter S Supply sCV Swing Check Valve Spr Sprinkler St Strainer T Tee Flow Turn 90° Tr Tee Run U Union WirF Wirsbo WMV Water Meter Valve Z Cap L©M.E.P.CAD,Inc. dAutoSPRINKO 12 v12.0.61.0 9/17/2020 11:41:04AM Page 5