Loading...
Report 'mac 202o- o oioZ COMcheck Software Version 4.1.4.3 „��4 SW �211d Q. N(1 Mechanical Compliance Certificate RECEIVED Project Information Energy Code: 90.1 (2016)Standard NOV 0 2 2020 Project Title: 72ND AVENUE APARTMENTS-SUITE 120 T.I. CITY OF TIGARD Location: Portland,Oregon BUILDING DIVISION Climate Zone: 4c Project Type: New Construction Construction Site: Owner/Agent: Designer/Contractor: 11740 SW 72nd Ave. Jacobs Heating Mark Denyer Tigard, OR 97223 (503) 234-7331 MFIA CONSULTING ENGINEERS 2007 ASH ST. PORTLAND, OR 97214 503 234 0548 Mechanical Systems List Quantity Svsfam Tvna R. naerrinfinn 1 HP-1 (Single Zone): Split System Heat Pump Heating Mode:Capacity=24 kBtu/h, Proposed Efficiency=10.00 HSPF,Required Efficiency=8.20 HSPF Cooling Mode:Capacity=24 kBtu/h, Proposed Efficiency=20.00 SEER,Required Efficiency: 14.00 SEER Fan System: FAN SYSTEM 1 I FC-1 --Compliance(Motor nameplate HP method): Passes Fans: FAN 1 Supply,Constant Volume,870 CFM,0.3 motor nameplate hp,0.0 fan efficiency grade Mechanical Compliance Statement Compliance Statement: The proposed mechanical design represented in this document is consistent with the building plans, specifications, and other calculations submitted with this permit application.The proposed mechanical systems have been designed to meet the 90.1 (2016)Standard requirements in COMcheck Version 4.1.4.3 and to comply with any applicable mandatory requirements listed in the Inspection Checklist. Mark Denyer Name-Title Signature Date Project Title: 72ND AVENUE APARTMENTS-SUITE 120 T.I. Report date: 10/12/20 Data filename: G:'1Jacobs Heating &Air Conditioning\10107_72 St Hair Salon\Energy Forms\72nd Ave Apts TI H Page 1 of 10 Salon COMcheck.cck COMcheck Software Version 4.1.4.3 Inspection Checklist Energy Code: 90.1 (2016) Standard Requirements: 2.0% were addressed directly in the COMcheck software Text in the "Comments/Assumptions" column is provided by the user in the COMcheck Requirements screen. For each requirement, the user certifies that a code requirement will be met and how that is documented, or that an exception is being claimed. Where compliance is itemized in a separate table, a reference to that table is provided. Section # Plan Review Complies? Comments/Assumptions & Req.ID 4.2.2, Plans, specifications, and/or ❑Complies 6.4.4.2.1, calculations provide all information ❑Does Not 6.7.2 with which compliance can be [PR2]1 determined for the mechanical ❑Not Observable systems and equipment and ❑Not Applicable document where exceptions to the standard are claimed. Load calculations per acceptable engineering standards and handbooks. 6.7.2.4 Detailed instructions for HVAC ❑Complies [PR5]1 systems commissioning included on ❑Does Not the plans or specifications for projects >=50,000 ft2. ❑Not Observable :Not Applicable - Additional Comments/Assumptions: 1 High Impact(Tier 1) 2 Medium Impact (Tier 2) 3 Low Impact (Tier 3) Project Title: 72ND AVENUE APARTMENTS-SUITE 120 T.I. Report date: 10/12/20 Data filename: G:\Jacobs Heating &Air Conditioning\10107_72 St Hair Salon\Energy Forms\72nd Ave Apts TI H Page 2 of 10 Salon COMcheck.cck Section Footing f Foundation inspection Complies? Comments/Assumptions Si• Req.10 6.4.3.7 Freeze protection and snow/ice ❑Complies [FO9]3 melting system sensors for future ❑Does Not connection to controls. ❑Not Observable ❑Not Applicable Additional Comments/Assumptions: 1 High Impact(Tier 1) 2 Medium Impact(Tier 2) 3 Low Impact(Tier 3) Project Title: 72ND AVENUE APARTMENTS-SUITE 120 T.I. Report date: 10/12/20 Data filename: G:\Jacobs Heating &Air Conditioning\10107_72 St Hair Salon\Energy Forms\72nd Ave Apts TI H Page 3 of 10 Salon COMcheck.cck Section Mechanical Rough-In Plans Verified Field Verified # Inspection Value Value Complies? Comments/Assumptions ' &Req.ID 6.4.1.4, HVAC equipment efficiency Efficiency: Efficiency: ❑Complies See the Mechanical Systems list 6.4.1.5 verified. Non-NAECA HVAC ❑Does Not for values. • [ME1]2 equipment labeled as meeting 90.1. ❑Not Observable ❑Not Applicable 6.4.3.4.1 Stair and elevator shaft vents ❑Complies [ME3]3 have motorized dampers that ❑Does Not automatically close. ❑Not Observable ❑Not Applicable 6.4.3.4.2, Outdoor air and exhaust systems ❑Complies 6.4.3.4.3 have motorized dampers that ❑Does Not [ME4]3 automatically shut when not in use and meet maximum leakage ['Not Observable rates. Check gravity dampers ❑Not Applicable where allowed. 6.4.3.4.5 Enclosed parking garage ❑Complies (ME39]3 ventilation has automatic ❑Does Not contaminant detection and ❑Not Observable capacity to stage or modulate fans to 50%or less of design ❑Not Applicable capacity. 6.4.3.4.4 Ventilation fans>0.75 hp have ❑Complies (ME5]3 automatic controls to shut off fan ❑Does Not • when not required. ❑Not Observable ❑Not Applicable 6.4.3.8 Demand control ventilation ❑Complies [ME6]' provided for spaces>500 ft2 and ❑Does Not >25 people/1000 ft2 occupant ['Not Observable density and served by systems ❑Not Applicable air side economizer,auto pplira ble modulating outside air damper control, or design airflow>3,000 cfm. 6.5.3.2.1 DX cooling systems>=75 kBtu/h ❑Complies See the Mechanical Systems list [ME40]2 (>=65 kBtu/h effective 1/2016) ❑Does Not for values. and chilled-water and evaporative cooling fan motor hp ❑Not Observable >= V4 designed to vary supply ❑Not Applicable fan airflow as a function of load and comply with operational requirements. 6.4.4.1.1 Insulation exposed to weather ❑Complies [ME7P protected from damage. ❑Does Not Insulation outside of the conditioned space and associated ['Not Observable with cooling systems is vapor ❑Not Applicable retardant. 6.4.4.1.2 HVAC ducts and plenums R- R-_ ❑Complies [ME8]2 insulated per Table 6.8.2.Where ❑Does Not ducts or plenums are installed in or under a slab,verification may ❑Not Observable need to occur during Foundation ❑Not Applicable Inspection. 6.4.4.1.3 HVAC piping insulation thickness. in. in. ❑Complies (ME9]2 Where piping is installed in or ❑Does Not under a slab,verification may 1 need to occur during Foundation ❑Not Observable Inspection. ❑Not Applicable 1 High Impact(Tier 1) 2 Medium Impact(Tier 2) 3 Low Impact(Tier 3) Project Title: 72ND AVENUE APARTMENTS-SUITE 120 T.I. Report date: 10/12/20 Data filename: G:\Jacobs Heating &Air Conditioning\10107_72 St Hair Salon\Energy Forms\72nd Ave Apts TI H Page 4 of 10 Salon COMcheck.cck • Section Mechanical Rough-In Plans Verified Field Verified Inspection Value Value Complies? Comments/Assumptions & Req.ID 6.4.4.1.4 Thermally ineffective panel ❑Complies [ME41]3 surfaces of sensible heating ❑Does Not • panels have insulation >= R-3.5. ❑Not Observable ❑Not Applicable 6.4.4.2.1 Ducts and plenums having ❑Complies [ME10]2 pressure class ratings are Seal ❑Does Not Class A construction. ❑Not Observable DNot Applicable 6.4.4.2.2 Ductwork operating >3 in.water ❑Complies Exception: Requirement [ME11]3 column requires air leakage ❑Does Not does not apply. testing. ❑Not Observable ❑Not Applicable 6.5.2.3 Dehumidification controls ❑Complies [ME19]3 provided to prevent reheating, ❑Does Not recooling, mixing of hot and cold airstreams or concurrent heating ❑Not Observable and cooling of the same • ❑Not Applicable airstream. 6.5.2.4.1 Humidifiers with airstream ❑Complies [ME68]3 mounted preheating jackets have ❑Does Not preheat auto-shutoff value set to activate when humidification is ❑Not Observable not required. ❑Not Applicable 6.5.2.4.2 Humidification system dispersion ❑Complies [ME69]3 tube hot surfaces in the ❑Does Not airstreams of ducts or air- handling units insulated >= R- ❑Not Observable 0.5. ElNot Applicable 6.5.2.5 Preheat coils controlled to stop ❑Complies [ME7013 heat output whenever ❑Does Not mechanical cooling, including economizer operation, is active. ❑Not Observable ❑Not Applicable 6.5.2.6 Units that provide ventilation air ❑Complies [ME106]3 to multiple zones and operate in ElDoes Not conjunction with zone heating and cooling systems are ['Not Observable prevented from using heating or ❑Not Applicable heat recovery to warm supply air above 60°F when representative building loads or outdoor air temperature indicate that most zones demand cooling. 6.5.3.6 Motors for fans >= 1/12 hp and ❑Complies [ME72]2 < 1 hp are electronically- ❑Does Not commutated motors or have a minimum motor efficiency of ['Not Observable 70%.These motors are also ❑Not Applicable speed adjustable for either balancing or remote control. 1 High Impact(Tier 1) 2 Medium Impact(Tier 2) 3 Low Impact(Tier 3) I Project Title: 72ND AVENUE APARTMENTS-SUITE 120 T.I. Report date: 10/12/20 Data filename: G:\Jacobs Heating&Air Conditioning\10107_72 St Hair Salon\Energy Forms\72nd Ave Apts TI H Page 5 of 10 Salon COMcheck.cck Section Mechanical Rough-In Plans Verified Field Verified Inspection Value Value Complies? Comments/Assumptions &Req.ID 6.5.3.4 Parallel-flow fan-powered VAV air ❑Complies [ME108]2 terminals have automatic ❑Does Not controls to a)turn off the terminal fan except when space ❑Not Observable heating is required or if required ❑Not Applicable for ventilation; b)turn on the terminal fan as the first stage of heating before the heating coil is activated; and c)during heating for warmup or setback temperature control, either operate the terminal fan and heating coil without primary air or reverse the terminal damper logic and provide heating from the central air handler through primary air. 6.5.3.7 Required minimum outdoor air ❑Complies (ME109]2 rate is the larger of minimum ❑Does Not outdoor air rate or minimum exhaust air rate required by ENot Observable Standard 62.1,Standard 170, or ❑Not Applicable applicable codes or accreditation standards.Outdoor air ventilation systems shall comply with one of the following: a) design minimum system outdoor air provided < 135%of the required minimum outdoor air rate, b)dampers, • ductwork, and controls allow the system to supply<=the required minimum outdoor air rate with a single set-point adjustment., or c)system includes exhaust air energy recovery complying with Section 6.5.6.1. 6.5.3.3 Multiple zone VAV systems with ❑Complies See the Mechanical Systems list [ME42]3 DDC of individual zone boxes ❑Does Not for values. have static pressure setpoint reset controls. ['Not Observable ❑Not Applicable 6.5.4.2 HVAC pumping systems with >— ❑Complies [ME25)3 3 control values designed for ❑Does Not variable fluid flow(see section details). ['Not Observable ONot Applicable 6.5.6.1 Exhaust air energy recovery on ❑Complies [ME56]1 systems meeting Tables 6.5.6.1- EDoes Not 1, and 6.5.6.1-2. ENot Observable ❑Not Applicable 6.5.7.1 Conditioned supply air to space ❑Complies [ME100]2 with mechanical exhaust<=the ❑Does Not greater of criteria of supply flow, required ventilation rate, exhaust ENot Observable flow minu the available transffer ❑Not Applicable air(see section details). 6.5.7.2.1 Kitchen hoods>5,000 cfm have ❑Complies [ME32]2 make up air>=50%of exhaust ❑Does Not air volume. ['Not Observable ❑Not Applicable [1 iHigh Impact(Tier 1) 2 Medium Impact(Tier 2) 3 Low Impact(Tier 3) Project Title: 72ND AVENUE APARTMENTS-SUITE 120 T.I. Report date: 10/12/20 Data filename: G:'Jacobs Heating&Air Conditioning\10107_72 St Hair Salon\Energy Forms\72nd Ave Apts TI H Page 6 of 10 Salon COMcheck.cck Section Mechanical Rough-In Plans Verified Field Verified # Inspection Value Value Complies. Comments/Assumptions & Req.ID 6.5.7.2.4 Approved field test used to ❑Complies [ME49)3 evaluate design air flow rates Does Not and demonstrate proper capture and containment of kitchen DNot Observable exhaust systems. DNot Applicable 6.5.8.1 Unenclosed spaces that are DComplies [ME34]2 heated use only radiant heat. ❑Does Not [Not Observable ❑Not Applicable 6.4.3.9 Heating for vestibules and air ❑Complies [ME6312 curtains with integral heating ❑Does Not include automatic controls that shut off the heating system when [Not Observable outdoor air temperatures>45F. DNot Applicable Vestibule heating and cooling systems controlled by a thermostat in the vestibule with heating setpoint<=60F and cooling setpoint>= 80F. 6.5.10 Doors separating conditioned ❑Complies [ME73]3 space from the outdoors have ❑Does Not controls that disable/reset heating and cooling system when DNot Observable open. DNot Applicable Additional Comments/Assumptions: • 1 High Impact(Tier 1) 2 Medium Impact(Tier 2) 3 Low Impact(Tier 3) Project Title: 72ND AVENUE APARTMENTS-SUITE 120 T.I. Report date: 10/12/20 Data filename: G:\Jacobs Heating&Air Conditioning\10107_72 St Hair Salon\Energy Forms172nd Ave Apts TI H Page 7 of 10 Salon COMcheck.cck • Section # Rough-In Electrical Inspection Complies? Comments/Assumptions ' & Req.ID 10.4.1 Electric motors meet requirements ❑Complies (EL912 where applicable. ❑Does Not • :Not Observable ❑Not Applicable Additional Comments/Assumptions: • 1 High Impact(Tier 1) 2 Medium Impact(Tier 2) 3 Low Impact(Tier 3) Project Title: 72ND AVENUE APARTMENTS-SUITE 120 T.I. Report date: 10/12/20 Data filename: G:\Jacobs Heating&Air Conditioning\10107_72 St Hair Salon\Energy Forms\72nd Ave Apts TI H Page 8 of 10 Salon COMcheck.cck I Section Final Inspection Complies? Comments/Assumptions Sc• Req.ID 6.4.3.1.2 Thermostatic controls have a 5 °F ❑Complies [FI3]3 deadband. ❑Does Not ❑Not Observable ❑Not Applicable 6.4.3.2 Temperature controls have setpoint ❑Complies [F120]3 overlap restrictions. DDoes Not ❑Not Observable ONot Applicable 6.4.3.3.1 HVAC systems equipped with at least ❑Complies [F121]3 one automatic shutdown control. ❑Does Not ❑Not Observable ❑Not Applicable 6.4.3.3.2 Setback controls allow automatic ❑Complies [F122]3 restart and temporary operation as ❑Does Not required for maintenance. ❑Not Observable ❑Not Applicable 6.4.3.5 Heat pump controls prevent ❑Complies [F15)3 supplemental electric resistance heat Oboes Not from coming on when not needed. DNot Observable ❑Not Applicable • 6.4.3.6 When humidification and ❑Complies [F16]3 dehumidification are provided to a Oboes Not zone, simultaneous operation is prohibited. Humidity control prohibits ❑Not Observable • the use of fossil fuel or electricity to ❑Not Applicable produce RH > 30%in the warmest zone humidified and RH <60%in the coldest zone dehumidified. 6.7.2.1 Furnished HVAC as-built drawings ❑Complies [FI7]3 submitted within 90 days of system ❑Does Not acceptance. [Not Observable ❑Not Applicable 6.7.2.2 Furnished O&M manuals for HVAC ❑Complies (FIB]3 systems within 90 days of system ❑Does Not acceptance. ❑Not Observable ❑Not Applicable 6.7.2.3 An air and/or hydronic system ❑Complies [F19]1 balancing report is provided for HVAC ❑Does Not systems serving zones>5,000 ft2 of ❑Not Observable conditioned area. ❑Not Applicable 6.7.2.4 HVAC control systems have been ❑Complies [FI10]1 tested to ensure proper operation, ❑Does Not calibration and adjustment of controls. ['Not Observable ❑Not Applicable 10.4.3 Elevators are designed with the ❑Complies [F12412 proper lighting,ventilation power, and ❑Does Not standby mode. ['Not Observable ❑Not Applicable Additional Comments/Assumptions: 1 High Impact(Tier 1) 12 'Medium Impact(Tier 2) 3 Low Impact(Tier 3) Project Title: 72ND AVENUE APARTMENTS-SUITE 120 T.I. Report date: 10/12/20 Data filename: G:\Jacobs Heating&Air Conditioning\10107_72 St Hair Salon\Energy Forms\72nd Ave Apts TI H Page 9 of 10 Salon COMcheck.cck