COMcheck Software Version 4.1.4.3 „��4 SW �211d Q.
N(1 Mechanical Compliance Certificate
RECEIVED
Project Information
Energy Code: 90.1 (2016)Standard NOV 0 2 2020
Project Title: 72ND AVENUE APARTMENTS-SUITE 120 T.I. CITY OF TIGARD
Location: Portland,Oregon BUILDING DIVISION
Climate Zone: 4c
Project Type: New Construction
Construction Site: Owner/Agent: Designer/Contractor:
11740 SW 72nd Ave. Jacobs Heating Mark Denyer
Tigard, OR 97223 (503) 234-7331 MFIA CONSULTING ENGINEERS
2007 ASH ST.
PORTLAND, OR 97214
503 234 0548
Mechanical Systems List
Quantity Svsfam Tvna R. naerrinfinn
1 HP-1 (Single Zone):
Split System Heat Pump
Heating Mode:Capacity=24 kBtu/h,
Proposed Efficiency=10.00 HSPF,Required Efficiency=8.20 HSPF
Cooling Mode:Capacity=24 kBtu/h,
Proposed Efficiency=20.00 SEER,Required Efficiency: 14.00 SEER
Fan System: FAN SYSTEM 1 I FC-1 --Compliance(Motor nameplate HP method): Passes
Fans:
FAN 1 Supply,Constant Volume,870 CFM,0.3 motor nameplate hp,0.0 fan efficiency grade
Mechanical Compliance Statement
Compliance Statement: The proposed mechanical design represented in this document is consistent with the building plans,
specifications, and other calculations submitted with this permit application.The proposed mechanical systems have been
designed to meet the 90.1 (2016)Standard requirements in COMcheck Version 4.1.4.3 and to comply with any applicable
mandatory requirements listed in the Inspection Checklist.
Mark Denyer
Name-Title Signature Date
Project Title: 72ND AVENUE APARTMENTS-SUITE 120 T.I. Report date: 10/12/20
Data filename: G:'1Jacobs Heating &Air Conditioning\10107_72 St Hair Salon\Energy Forms\72nd Ave Apts TI H Page 1 of 10
Salon COMcheck.cck
COMcheck Software Version 4.1.4.3
Inspection Checklist
Energy Code: 90.1 (2016) Standard
Requirements: 2.0% were addressed directly in the COMcheck software
Text in the "Comments/Assumptions" column is provided by the user in the COMcheck Requirements screen. For each
requirement, the user certifies that a code requirement will be met and how that is documented, or that an exception
is being claimed. Where compliance is itemized in a separate table, a reference to that table is provided.
Section
# Plan Review Complies? Comments/Assumptions
& Req.ID
4.2.2, Plans, specifications, and/or ❑Complies
6.4.4.2.1, calculations provide all information ❑Does Not
6.7.2 with which compliance can be
[PR2]1 determined for the mechanical ❑Not Observable
systems and equipment and ❑Not Applicable
document where exceptions to the
standard are claimed. Load
calculations per acceptable
engineering standards and
handbooks.
6.7.2.4 Detailed instructions for HVAC ❑Complies
[PR5]1 systems commissioning included on ❑Does Not
the plans or specifications for projects
>=50,000 ft2. ❑Not Observable
:Not Applicable
- Additional Comments/Assumptions:
1 High Impact(Tier 1) 2 Medium Impact (Tier 2) 3 Low Impact (Tier 3)
Project Title: 72ND AVENUE APARTMENTS-SUITE 120 T.I. Report date: 10/12/20
Data filename: G:\Jacobs Heating &Air Conditioning\10107_72 St Hair Salon\Energy Forms\72nd Ave Apts TI H Page 2 of 10
Salon COMcheck.cck
Section
Footing f Foundation inspection Complies? Comments/Assumptions
Si• Req.10
6.4.3.7 Freeze protection and snow/ice ❑Complies
[FO9]3 melting system sensors for future ❑Does Not
connection to controls.
❑Not Observable
❑Not Applicable
Additional Comments/Assumptions:
1 High Impact(Tier 1) 2 Medium Impact(Tier 2) 3 Low Impact(Tier 3)
Project Title: 72ND AVENUE APARTMENTS-SUITE 120 T.I. Report date: 10/12/20
Data filename: G:\Jacobs Heating &Air Conditioning\10107_72 St Hair Salon\Energy Forms\72nd Ave Apts TI H Page 3 of 10
Salon COMcheck.cck
Section Mechanical Rough-In Plans Verified Field Verified
# Inspection Value Value Complies? Comments/Assumptions
' &Req.ID
6.4.1.4, HVAC equipment efficiency Efficiency: Efficiency: ❑Complies See the Mechanical Systems list
6.4.1.5 verified. Non-NAECA HVAC ❑Does Not for values.
• [ME1]2 equipment labeled as meeting
90.1. ❑Not Observable
❑Not Applicable
6.4.3.4.1 Stair and elevator shaft vents ❑Complies
[ME3]3 have motorized dampers that ❑Does Not
automatically close. ❑Not Observable
❑Not Applicable
6.4.3.4.2, Outdoor air and exhaust systems ❑Complies
6.4.3.4.3 have motorized dampers that ❑Does Not
[ME4]3 automatically shut when not in
use and meet maximum leakage ['Not Observable
rates. Check gravity dampers ❑Not Applicable
where allowed.
6.4.3.4.5 Enclosed parking garage ❑Complies
(ME39]3 ventilation has automatic ❑Does Not
contaminant detection and ❑Not Observable
capacity to stage or modulate
fans to 50%or less of design ❑Not Applicable
capacity.
6.4.3.4.4 Ventilation fans>0.75 hp have ❑Complies
(ME5]3 automatic controls to shut off fan ❑Does Not
• when not required. ❑Not Observable
❑Not Applicable
6.4.3.8 Demand control ventilation ❑Complies
[ME6]' provided for spaces>500 ft2 and ❑Does Not
>25 people/1000 ft2 occupant ['Not Observable
density and served by systems ❑Not Applicable
air side economizer,auto pplira ble
modulating outside air damper
control, or design airflow>3,000
cfm.
6.5.3.2.1 DX cooling systems>=75 kBtu/h ❑Complies See the Mechanical Systems list
[ME40]2 (>=65 kBtu/h effective 1/2016) ❑Does Not for values.
and chilled-water and
evaporative cooling fan motor hp ❑Not Observable
>= V4 designed to vary supply ❑Not Applicable
fan airflow as a function of load
and comply with operational
requirements.
6.4.4.1.1 Insulation exposed to weather ❑Complies
[ME7P protected from damage. ❑Does Not
Insulation outside of the
conditioned space and associated ['Not Observable
with cooling systems is vapor ❑Not Applicable
retardant.
6.4.4.1.2 HVAC ducts and plenums R- R-_ ❑Complies
[ME8]2 insulated per Table 6.8.2.Where ❑Does Not
ducts or plenums are installed in
or under a slab,verification may ❑Not Observable
need to occur during Foundation ❑Not Applicable
Inspection.
6.4.4.1.3 HVAC piping insulation thickness. in. in. ❑Complies
(ME9]2 Where piping is installed in or ❑Does Not
under a slab,verification may 1
need to occur during Foundation ❑Not Observable
Inspection. ❑Not Applicable
1 High Impact(Tier 1) 2 Medium Impact(Tier 2) 3 Low Impact(Tier 3)
Project Title: 72ND AVENUE APARTMENTS-SUITE 120 T.I. Report date: 10/12/20
Data filename: G:\Jacobs Heating &Air Conditioning\10107_72 St Hair Salon\Energy Forms\72nd Ave Apts TI H Page 4 of 10
Salon COMcheck.cck
•
Section Mechanical Rough-In Plans Verified Field Verified
Inspection Value Value Complies? Comments/Assumptions
& Req.ID
6.4.4.1.4 Thermally ineffective panel ❑Complies
[ME41]3 surfaces of sensible heating ❑Does Not
• panels have insulation >= R-3.5.
❑Not Observable
❑Not Applicable
6.4.4.2.1 Ducts and plenums having ❑Complies
[ME10]2 pressure class ratings are Seal ❑Does Not
Class A construction.
❑Not Observable
DNot Applicable
6.4.4.2.2 Ductwork operating >3 in.water ❑Complies Exception: Requirement
[ME11]3 column requires air leakage ❑Does Not does not apply.
testing.
❑Not Observable
❑Not Applicable
6.5.2.3 Dehumidification controls ❑Complies
[ME19]3 provided to prevent reheating, ❑Does Not
recooling, mixing of hot and cold
airstreams or concurrent heating ❑Not Observable
and cooling of the same • ❑Not Applicable
airstream.
6.5.2.4.1 Humidifiers with airstream ❑Complies
[ME68]3 mounted preheating jackets have ❑Does Not
preheat auto-shutoff value set to
activate when humidification is ❑Not Observable
not required. ❑Not Applicable
6.5.2.4.2 Humidification system dispersion ❑Complies
[ME69]3 tube hot surfaces in the ❑Does Not
airstreams of ducts or air-
handling units insulated >= R- ❑Not Observable
0.5. ElNot Applicable
6.5.2.5 Preheat coils controlled to stop ❑Complies
[ME7013 heat output whenever ❑Does Not
mechanical cooling, including
economizer operation, is active. ❑Not Observable
❑Not Applicable
6.5.2.6 Units that provide ventilation air ❑Complies
[ME106]3 to multiple zones and operate in ElDoes Not
conjunction with zone heating
and cooling systems are ['Not Observable
prevented from using heating or ❑Not Applicable
heat recovery to warm supply air
above 60°F when representative
building loads or outdoor air
temperature indicate that most
zones demand cooling.
6.5.3.6 Motors for fans >= 1/12 hp and ❑Complies
[ME72]2 < 1 hp are electronically- ❑Does Not
commutated motors or have a
minimum motor efficiency of ['Not Observable
70%.These motors are also ❑Not Applicable
speed adjustable for either
balancing or remote control.
1 High Impact(Tier 1) 2 Medium Impact(Tier 2) 3 Low Impact(Tier 3) I
Project Title: 72ND AVENUE APARTMENTS-SUITE 120 T.I. Report date: 10/12/20
Data filename: G:\Jacobs Heating&Air Conditioning\10107_72 St Hair Salon\Energy Forms\72nd Ave Apts TI H Page 5 of 10
Salon COMcheck.cck
Section Mechanical Rough-In Plans Verified Field Verified
Inspection Value Value Complies? Comments/Assumptions
&Req.ID
6.5.3.4 Parallel-flow fan-powered VAV air ❑Complies
[ME108]2 terminals have automatic ❑Does Not
controls to a)turn off the
terminal fan except when space ❑Not Observable
heating is required or if required ❑Not Applicable
for ventilation; b)turn on the
terminal fan as the first stage of
heating before the heating coil is
activated; and c)during heating
for warmup or setback
temperature control, either
operate the terminal fan and
heating coil without primary air
or reverse the terminal damper
logic and provide heating from
the central air handler through
primary air.
6.5.3.7 Required minimum outdoor air ❑Complies
(ME109]2 rate is the larger of minimum ❑Does Not
outdoor air rate or minimum
exhaust air rate required by ENot Observable
Standard 62.1,Standard 170, or ❑Not Applicable
applicable codes or accreditation
standards.Outdoor air ventilation
systems shall comply with one of
the following: a) design minimum
system outdoor air provided <
135%of the required minimum
outdoor air rate, b)dampers,
• ductwork, and controls allow the
system to supply<=the
required minimum outdoor air
rate with a single set-point
adjustment., or c)system
includes exhaust air energy
recovery complying with Section
6.5.6.1.
6.5.3.3 Multiple zone VAV systems with ❑Complies See the Mechanical Systems list
[ME42]3 DDC of individual zone boxes ❑Does Not for values.
have static pressure setpoint
reset controls. ['Not Observable
❑Not Applicable
6.5.4.2 HVAC pumping systems with >— ❑Complies
[ME25)3 3 control values designed for ❑Does Not
variable fluid flow(see section
details). ['Not Observable
ONot Applicable
6.5.6.1 Exhaust air energy recovery on ❑Complies
[ME56]1 systems meeting Tables 6.5.6.1- EDoes Not
1, and 6.5.6.1-2. ENot Observable
❑Not Applicable
6.5.7.1 Conditioned supply air to space ❑Complies
[ME100]2 with mechanical exhaust<=the ❑Does Not
greater of criteria of supply flow,
required ventilation rate, exhaust ENot Observable
flow minu the available transffer ❑Not Applicable
air(see section details).
6.5.7.2.1 Kitchen hoods>5,000 cfm have ❑Complies
[ME32]2 make up air>=50%of exhaust ❑Does Not
air volume.
['Not Observable
❑Not Applicable
[1 iHigh Impact(Tier 1) 2 Medium Impact(Tier 2) 3 Low Impact(Tier 3)
Project Title: 72ND AVENUE APARTMENTS-SUITE 120 T.I. Report date: 10/12/20
Data filename: G:'Jacobs Heating&Air Conditioning\10107_72 St Hair Salon\Energy Forms\72nd Ave Apts TI H Page 6 of 10
Salon COMcheck.cck
Section Mechanical Rough-In Plans Verified Field Verified
# Inspection Value Value Complies. Comments/Assumptions
& Req.ID
6.5.7.2.4 Approved field test used to ❑Complies
[ME49)3 evaluate design air flow rates Does Not
and demonstrate proper capture
and containment of kitchen DNot Observable
exhaust systems. DNot Applicable
6.5.8.1 Unenclosed spaces that are DComplies
[ME34]2 heated use only radiant heat. ❑Does Not
[Not Observable
❑Not Applicable
6.4.3.9 Heating for vestibules and air ❑Complies
[ME6312 curtains with integral heating ❑Does Not
include automatic controls that
shut off the heating system when [Not Observable
outdoor air temperatures>45F. DNot Applicable
Vestibule heating and cooling
systems controlled by a
thermostat in the vestibule with
heating setpoint<=60F and
cooling setpoint>= 80F.
6.5.10 Doors separating conditioned ❑Complies
[ME73]3 space from the outdoors have ❑Does Not
controls that disable/reset
heating and cooling system when DNot Observable
open. DNot Applicable
Additional Comments/Assumptions:
•
1 High Impact(Tier 1) 2 Medium Impact(Tier 2) 3 Low Impact(Tier 3)
Project Title: 72ND AVENUE APARTMENTS-SUITE 120 T.I. Report date: 10/12/20
Data filename: G:\Jacobs Heating&Air Conditioning\10107_72 St Hair Salon\Energy Forms172nd Ave Apts TI H Page 7 of 10
Salon COMcheck.cck
• Section
# Rough-In Electrical Inspection Complies? Comments/Assumptions
' & Req.ID
10.4.1 Electric motors meet requirements ❑Complies
(EL912 where applicable. ❑Does Not
• :Not Observable
❑Not Applicable
Additional Comments/Assumptions:
•
1 High Impact(Tier 1) 2 Medium Impact(Tier 2) 3 Low Impact(Tier 3)
Project Title: 72ND AVENUE APARTMENTS-SUITE 120 T.I. Report date: 10/12/20
Data filename: G:\Jacobs Heating&Air Conditioning\10107_72 St Hair Salon\Energy Forms\72nd Ave Apts TI H Page 8 of 10
Salon COMcheck.cck
I
Section
Final Inspection Complies? Comments/Assumptions
Sc• Req.ID
6.4.3.1.2 Thermostatic controls have a 5 °F ❑Complies
[FI3]3 deadband. ❑Does Not
❑Not Observable
❑Not Applicable
6.4.3.2 Temperature controls have setpoint ❑Complies
[F120]3 overlap restrictions. DDoes Not
❑Not Observable
ONot Applicable
6.4.3.3.1 HVAC systems equipped with at least ❑Complies
[F121]3 one automatic shutdown control. ❑Does Not
❑Not Observable
❑Not Applicable
6.4.3.3.2 Setback controls allow automatic ❑Complies
[F122]3 restart and temporary operation as ❑Does Not
required for maintenance.
❑Not Observable
❑Not Applicable
6.4.3.5 Heat pump controls prevent ❑Complies
[F15)3 supplemental electric resistance heat Oboes Not
from coming on when not needed.
DNot Observable
❑Not Applicable
• 6.4.3.6 When humidification and ❑Complies
[F16]3 dehumidification are provided to a Oboes Not
zone, simultaneous operation is
prohibited. Humidity control prohibits ❑Not Observable
• the use of fossil fuel or electricity to ❑Not Applicable
produce RH > 30%in the warmest
zone humidified and RH <60%in the
coldest zone dehumidified.
6.7.2.1 Furnished HVAC as-built drawings ❑Complies
[FI7]3 submitted within 90 days of system ❑Does Not
acceptance.
[Not Observable
❑Not Applicable
6.7.2.2 Furnished O&M manuals for HVAC ❑Complies
(FIB]3 systems within 90 days of system ❑Does Not
acceptance.
❑Not Observable
❑Not Applicable
6.7.2.3 An air and/or hydronic system ❑Complies
[F19]1 balancing report is provided for HVAC ❑Does Not
systems serving zones>5,000 ft2 of ❑Not Observable
conditioned area. ❑Not Applicable
6.7.2.4 HVAC control systems have been ❑Complies
[FI10]1 tested to ensure proper operation, ❑Does Not
calibration and adjustment of controls.
['Not Observable
❑Not Applicable
10.4.3 Elevators are designed with the ❑Complies
[F12412 proper lighting,ventilation power, and ❑Does Not
standby mode.
['Not Observable
❑Not Applicable
Additional Comments/Assumptions:
1 High Impact(Tier 1) 12 'Medium Impact(Tier 2) 3 Low Impact(Tier 3)
Project Title: 72ND AVENUE APARTMENTS-SUITE 120 T.I. Report date: 10/12/20
Data filename: G:\Jacobs Heating&Air Conditioning\10107_72 St Hair Salon\Energy Forms\72nd Ave Apts TI H Page 9 of 10
Salon COMcheck.cck