Plans • PROJECT NOTES d. 303.2-PV SYSTEMS AND SUPPORTING STRUCTURE SHALL COMPLY WITH REQUIREMENTS OF OSSC CHAPTER 6 OR.THE UI 1110. ORSC AS APPLICABLE 2. 303.3-ALL PV MODULES TO BE UL 1703 LISTED ■ 3. 303.5-PV SYSTEM SHALL HAVE A FIRE CLASSIFICATION THAT IS EQUAL TO OR GREATER THAN THE ROOF ASSEMBLY REQUIRED BY OSSC SECTION 1501.1 4. 303.6-ALL COMPONENTS OF THE PV SYSTEM SHALL BE RATED FOR THEIR USE. 5. 303.4-303.8-PV LAYOUT SHALL NOT RESTRICT EGRESS, INSIDE: LIGHT,VENTILATION,OR ROOF DRAINAGE :°14AAUCCITDNCSIOI:CMCCEySOP; D 6. 304.9.1 GERNERAL PATHWAYS REQUIREMENTS EXEMPTION 1: ON STRUCTURE WITH A PV ARRAY AREA OF 1,000 SF OR LESS INSTALLED ONA ROOF WITH A SLOPE THAT EXCEEDS 2:12NNECTAND WITH AN INTERSECTING ADJACENT ROOF WHERE NO27INER6. ...CONTINUED...SECTION IS LARGER THAN 150 FEET MEASURED UTILIT METER IN LENGTH OR WIDTH.EXEMPTION IA:WHERE PV ARRAY DOES NOT EXCEED 25%AS MEASURED IN PLAN VIEW OF TOTAL ROOF AREA OF THE STRUCTURE,A MINIMUM OF 12"UNOBSTRUCTED PATHWAY SHALL BE MAINTAINED ALONG EACH SIDE OF ANY HORIZONTAL RIDGE. 7. ROOF STRUCTURE IS CONVENTIONAL LIGHT FRAMED WOOD CONSTRUCTION WITH 2X4 TRUSSES AT 24"ON CENTER MAX - - EXEMPT FROM ALLOWABLE SPAN REQUIREMENTS IN TABLE 38y'� , ; 'k] P 1 305.4.1 , ; ' , 1 I T✓ I I 'I , I I I I ' 8. 304.9.5-DISCONNECTS,J-BOXES,COMBINER BOXES OR s �-j I, p s 0 1 11 1 1 1 1 I ' , ' GUTTERS SHALL NOT BE PLACED IN ANY REQUIRED PATHWAYS 4'1 11 ' 1 1 OR CUTOUTS 1 s _._,._._..__...- s, , 9. ROOF MATERIAL IS COMPOSITION ROOF,IF METAL,FOLLOWS . ..._-_..._._ PRECRIPTIVE PATH IN 2010 OREGON SOLAR CODE , __..._ -_.._._...- s s 10. PER 305.4 ITEM 3-TOTAL SYSTEM WEIGHT SHOULD NOT 11. __ _._.__--- s EXCEED 4.5 PSF.PV MODULES AND RACKING SHALL BE i -' - _ _ DIRECTLY ATTACHED TO ROOF FRAMING.ATTACHEMENTS 1 _ .' - 1 SPACING WILL BE 48"ON CENTER MAX,WHEN ATTACHMENT IS 1 '1 1 I , 27' LOCATED WITHIN 3'OF ROOF HIP,EDGE,EAVE,AND RIDGE SHALL BE 24"ON CNETER MAX s - -- ---"" 11. MAX MODULE HEIGHT WILL NOT EXCEED 12"OFF ROOF s 1 ._._._.....__..------ , 1 °-• LlaI SURFACE 1 I`pyltE5�7 1 12. SECTION 304.7-MECHANICAL EQUIPMENT CLEARANCES OF 30" �1 I s '1 j s '1 { 1, 1 s s, s s ,s 1 MINIMUM ON ROOF. s s 1 s 1 1 s s s 1 s 11, s s 1 'I i s 1 s s ; 1 ; 1 ; s s 1 ATTACHMENTS EVERY 24"ON CENTER 21' WHEN UNDER 36"FROM ANY HIP,EAVE, RIDGE,OR VALLEY.ATTACHMENTS ARE 7' EVERY 48"WHEN OVER 36" 17' ENERGY SOLUTIONS,LLC EDINA NA—SONGKHLA N PO BOX 887 15492 SW SUMMERVIEW DR. BEAVERCREEK, OR 97004 PORTLAND OR 97224 A ENERGY 503.680.3718 425.772.4460 W ` ll` E CCB#202002 9.18 KW SOLAR ARRAY—RESIDENTIAL SolutionsPr ENLARGED ROOF PLAN S 11 k INSIDE: MAIN OCPD OUTSIDE: AC DISCONNECT 27' AC COMBINER UTILITY METER 38' 4't 27' LOWEST READING 5o 1 1 I 1 1 1 1 1 1 ll I i 21' 7' 17' MODULE END CLAMP RAFTER or PRE-ENGINEERED TRUSSES 11 I II i I . . j I I , 11 I I I I 0II:: �n:r. u1. I es: I� M00 CLAMP .ter x- nlMaaerx"+ COMPO5RI�, R. i1i.moo m v I wow FOOT /.. PV MODULE TYP. j�� ��' OOT MODULE MID CLAMP11 " _'y' 4�'�� i r SHING I RACKING RAIL i'" � � 6. S. II v r-'1-r �^ i I I 11 ;I' m a: m [VM� C%'SC�[,1 ''Llai: 1 1 �. �i� I I ,�" 1,±4' 1 I 11 I I I I Y 11 11 11 11 11 II II 11 II II II 11 ► M,BETWEEN ATTACHMENTS MOUNTING RTRAIT) ®MOUNTING DETAIL SCALE: 1'= SCALE: 1"=2'-0" 5.25" OCi CoMP�1��'�� =�® RAFTER OR TRUSS 24"ON CENTER �pR��08/09/2020_,..iii.,.. ...;:is.. .„.0 � y aGINEF S 0' 85997 41 OR $.MARK5‹ EXPIRES "'w'2U2U O MOUNTING METHOD STRUCTURALASP SCALE: 1"=2'-0" ECTS ONLY System Information Labels PV Module Ratings Inverter Ratings Photovoltaic AC Disconnect Module Make Hanwha Q.Cells Inverter Make Enphase AC Output Current = 32.7 A ENERGY Module Model Q.Peak Duo BIk-G6+ 340 Inverter Model IQ7PLUS-72-2-US Nominal AC Voltage = 240 V Max Power = 340 W Max. Output Power = 290 W Solutions Open Circuit Voltage = 40.66 V Max. DC Voltage = 60 V Max Power Point Voltage = 33.94 V Norminal AC Voltage = 240 V P.O. Box 887 Short Circuit Current = 10.52 A Max. AC Current = 1.21 A Beavercreek, Oregon 97004 Max Power Point Current = 10.02 A CEC In erter Efficiency = 97.0 % Phone: 503-680-3718 < ,14, Q Meter Base 9 Modules w/ J-Box ©O �TILITas\Y\ I`"1 Micro-inverters (at array) ISERVIC 9 a Branch#1 __. — I AC Main Solar "-. / Combiner AC n 9 Modules w/ Panel Disconnect 3:' U Micro-inverters I' wl(3)20A ' it — / • ..' !I Branch#2 I Circuit - 45A Fusing ——14-———1 I /I Breakers / (@ Utility / I I / / / .. ,w Aq 1 a 9 Modules w/ t,, I / Meter) / I Main 1 Micro-inverters / / ;' / OCPD 200A / 3 1.2 Branch#3 _ '_ ___(i) 8 (i) / C) a BUILDING 1 G Main Service GROUNDING = Panel PV System meets requirements for Rapid Shutdown as defined in 690.12 ELECTRODE 200A Bus EQUIPMENT SCHEDULE REF DESCRIP11ON PN NOTES 1 SOLAR IN MODULE Q.PEAK DUO BLK-G6+340 HANWHA Q.CELLS 340W MONOCRYSTALLINE MODULE Notes: 2 ACDCMCRO-INVERTER IQ7PLUS-72-2-US B'JPHASE290W MICROINVERTER a Equipment, conductors and conduit 3 ARRAY HARDWARE TBD FLUSH ROOF RACKING SYSTEM as listed or equivalent. 4 JUNCTION BOX _MD FOR TRANSITION FROM TRUNK CABLETO CONDUCTORS IN CONDUIT a DC side of the Micro-Inverter is 5 AC COMBINER PANEL X-IQ-AM1-240-2 ENF'HASE IQ COMBINER+PANEL W/IQ ENVOY,125A BUS BAR isolated. A DC CEG is not required. 6 BRANCH CIRCUIT OCPD BRK-20A-2-240 EATON BR220,20A.2-POLE,240V CIRCUIT BREAKER(BACK-FED) 7 MAIN SOLAR AC DISCONNECT D222NRB SQUARED,SAFETY SWITCH,60A,240V.2-POL45AFUSING ONE-LINESTANDAImELECTRICALgAGRAM L PROJECT REF: Edina Na-Songkhla 8 MAIN SERVICE PAN WA 240V(EXISTING) SITE ADDRESS: 15492 SW Surmierview Dr, CONDUIT&CONDUCTOR SCHEDULE Portland,OR 97224 REF DESCRIP./CONDUCTOR TYPE CONDUCTOR GAUGE NUMBER OF CONDUCTORS CONDUIT TYPE CONDUIT SIZE SYSTEM SIZE 9.18 kW A ENPHASE Q-12-10-240 CABLE #12 2(Per Cable) IN FREE AIR 3 Branches of 9 Modules/Inverters (Hanw ha B BARECU #6ir 1 IN FREE AIR Q.Cells 340W/Enphase IQ7-Plus) C NM orNMC(Romex) #12/#10 2/1 (x3) IN FREE AIR r Sheet 1 of3 D THWN-2 #6/#6 3/1 EMT 1" Date: September 25, 2020 NOT TO SCALE PORTLAND/HILLSBORO Elev. High Temp Distance above roof Extreme ENERGY 0.4% 2%Avg. 0.5" 3.5" 12" Min Solutions 62 m 37 °C 32°C 54°C 49 °C 46 °C -8 °C Correction Temperatures Voltage Drop calculations: ATcmd=-8°C-25°C=-33°C MTh°,_(37°C+ 35°C)-25°C=47°C DC voltage drop is insignificant because of micro-inverters mounted at P.O.Box 887 Flush Roof mount PV modules. Beavercreek,Oregon 97004 Phone: 503-680-3718 Module Voltage Calculations Per Enphase Technical Brief on Calculating AC Line Voltage Rise for Hanwha Q.Cells 340W Mono(Q.Peak Duo Blk-G6+340) IQ-Series Micros with Q Cable for center termination of IQ7+,240V, Voc=40.66V Vmp=33.94V Voc Temp Coefficient=-027%1°C portrait trunk cable, Branch Circuit AC voltage drop for 9 or 10 micro- Isc= 10.66A Imp= 10.02A Pmax Temp Coefficient=-0.36%/°C inverters center-tapped is given as 0.13%. Cold Voc=40.66V+(40.66V x-0.27%/°C x-33°C)=40.66V+3.62V=44.3V Worst case branch circuit drop on branch of 9(for distance). Hot Vmp=33.94V+ (33.94V x-0.36%/°C x 47°C)=33.94V-5.74V=28.2V AC conductor run from junction box to ac combiner is 70 ft(estimated) Micro-inverter output voltage is 240V, 1.21A x 9= 10.9A Enphase IQ7PLUS-72-2-US (2 x 70ft x 10.9A x 1.980./kft x 100)/(1000ft/kft x 240V)=1.26%. Max DC Input Voltage: 60V Max DC!so: 15A AC conductor run from AC Combiner to Interconnection is 10 ft(est) DC Operating range: 16V-60V Peak Power Tracking Voltage:27V-45V Micro-inverter output voltage is 240V, 1.21A x 27=32.7A AC output voltage:240V AC output current: 1.21A (2 x 10ft x 32.7A x 0.77811/kft x 100)/(1000ft/kft x 240V)=0.21% Max Branch Circuit Size: 13 Max Branch Circuit OCPD: 20A 0.13%+ 1.26%+0.21%=1.60%total worst case voltage drop Conductor Amoacity.OCPD&Disconnects Branch Circuit: 1.21A x 9x 125%= 13.6A Conditions of use-3 branch circuits in nonmetallic sheathed cable(2 current carrying conductors per)not on the roof: 13.6A+1.0= 13.6A #12 AWG NM(rated for 20A into 60°terminals and required OCPD) 20A,240V,2-Pole Back-Fed Circuit Breaker in AC Combiner Panel AC Combiner Output Circuit: 1.21A x 27 x125%=40.8A #8 AWG(rated for 50A into 75°terminals and required OCPD) #6 AWG selected per AHJ requirements 45A fusing in a 60A,2-Pole,240V, Fused AC Disconnect adjacent to the utility meter. Table 1.10: Internal Q Cable VRise(Portrait Cable, Q-12-10-240) IQ 7+1240V I P I 10 7+Microinverters per branch ELECTRICAL CALCULATIONS PROJECT REF: Edina Na-Songkhla 1 2 3 4 5 6 7 8 9 10 11 12 13 SITE ADDRESS: 15492 SW Sumnerview Dr, Portland,OR 97224 Current(A) 1.2 2.4 3.6 4.8 6.0 7.3 8.5 9.7 10.9 12.1 13.3 14.5 15.7 SYSTEM SIZE 9.18 kw 3 Branches of 9 Modules/Inverters(Hanwha VRise(V) 0.02 0.06 0.12 0.20 0.31 0.43 0.57 0.73 0.92 1.12 1.35 1.59 1.86 Q.Cells 340W/Enphase IQ7-Pus) Sheet 2 of 3 VRise(%) 0.01 0.03 0.05 0.09 0.13 0.18 0.24 0.31 0.38 0.47 0.56 0.66 0.77 Date: September 25, 2020 Notes: • PV System compliant with requirements for Rapid Shutdown per 690.12. • Each microinverter is attached to the racking at the back of the corresponding PV module. ENERGY • Enphase Raw Q Cable(#12 AWG)is used to span from the Enphase Q Trunk cable of each branch to the penetration through the roof. Once below the roof, conductors are Solutions transitioned to Nonmetallic Sheathed Cable(Romex or equivalent). The Raw Q Cable is installed below the array and attached to racking frame members. • Branch circuits penetrate the roof where the transition from Enphase Raw Q Cable to P.O.Box 887 Nonmetallic Sheathed Cable is made. Beavercreek,Oregon 97004 • The Enphase AC Combiner Panel&Main Solar AC Disconnect are located on the outside Phone: 503-680-3718 wall of the garage,adjacent to the Utility Meter. • Nonmetallic Sheathed Cable will be run(per Code)in open space. No deratings for condition of use will be required. • Conductor sizing for the NMC is minimum required to meet ampacity calculations. Conductors may be upsized to achieve#10 AWG grounding conductor requirement. • Circuit breakers in the AC Aggregate Panel serve as disconnecting means for each branch of microinverters. • The Q Cable will be connected in a"Center-Fed"configuration to minimize AC voltage drop. • The Main Solar AC Disconnect will be connected with the line-side of the disconnect towards the utility and the load-side towards the PV System. • Enphase recommends maintaining a total voltage drop for 2%or less from the array to the point of interconnection,and a less than 1%for the Q Cable. • Conductor run lengths and voltage drop to be confirmed. Conductors will be upsized as required to maintain 2%or less total voltage drop. • Interconnection via a line-side tap to the supply conductors in the Meter Base. Complies with 705.12. • If 45A fusing can not be readily sourced for the Main Solar AC Disconnect,50A fusing may be substituted. Conductors will still be protected. • The CEG will be relocated from the MSP to the Meter Base. A new#6 AWG CU ECG will be established between the MSP and the Meter Base. • Conductor sizing listed is minimum required based on NEC ampacity calculations for CU conductors or voltage drop calculations. • Conduit sizing based on listed conductors and NABCEP recommended maximum fill of 25%. Conduit sizing may need to be recalculated for conductors of a different type. Conduit may be sized to comply with NEC,Annex C. • All electrical work must be made in accordance with the local and applicable National Electrical Code ANSI/NFPA 70. • PV System to be installed and labeled per National Electric Code. Specifically: -690.4(D) -690.31(B) -690.5(C) -690.35(C)and(F) -690.13(B) -690.5(C) -690.17(E) -705.12(D) DESIGN/BUILD NOTES • Inverters listed to UL-1741 for grid-interactive use and GFDI protection. PROJECT REF: Edina Na-Songkhla • Equipment,conductors and conduit as listed or equivalent. SITEADDRESS: 15492 SW Surmierview Dr, • All equipment used UL listed. Portland,OR 97224 SYSTEM SIZE 9.18 kW 3 Branches of 9 Modules/Inverters(Hanwha Q.Cells 340W/Enphase IQ7-Rus) Sheet 3 of 3 Date: September 25, 2020 Data Sheet • Enphase Microinverters Region:AMERICAS Enphase The high-powered smart grid-ready Enphase IQ 7 Micro" and Enphase IQ 7+ MicroT" IQ 7 and IQ 7+ dramatically simplify the installation process while achieving the highest system efficiency. IVI i croi nverters Part of the Enphase IQ System,the IQ 7 and IQ 7+ Microinverters integrate with the Enphase IQ Envoy", Enphase IQ Battery",and the Enphase Enlighten'' monitoring and analysis software. IQ Series Microinverters extend the reliability standards set forth by previous generations and undergo over a million hours of power-on testing, enabling Enphase to provide an industry-leading warranty of up to 25 years. Easy to Install • Lightweight and simple • Faster installation with improved,lighter two-wire cabling • Built-in rapid shutdown compliant(NEC 2014&2017) 1101 Productive and Reliable • Optimized for high powered 60-cell and 72-cell*modules • More than a million hours of testing - r • Class II double-insulated enclosure t.� - • UL listed e ENPHASE.i - 1Q7 E " Smart Grid Ready • Complies with advanced grid support,voltage and frequency ride-through requirements • Remotely updates to respond to changing grid requirements • Configurable for varying grid profiles • Meets CA Rule 21 (UL 1741-SA) *The IQ 7+Micro is required to support 72-cell modules. QGl a r" E341165 E141165 E N PHASE E. To learn more about Enphase offerings,visit enphase.com e Enphase IQ 7 and IQ 7+ Microinverters INPUT DATA(DC) IQ7-60-2-US/IQ7-60-B-US IQ7PLUS-72-2-US/IQ7PLUS-72-B-US Commonly used module pairings' 235 W-350 W+ 235 W-440 W+ Module compatibility 60-cell PV modules only 60-cell and 72-cell PV modules Maximum input DC voltage 48 V 60 V Peak power tracking voltage 27 V-37 V 27 V-45 V Operating range 16 V-48 V 16 V-60 V Min/Max start voltage 22 V/48 V 22 V/60 V Max DC short circuit current(module Ise) 15 A 15 A Overvoltage class DC port II II DC port backfeed current 0 A 0 A PV array configuration 1 x 1 ungrounded array;No additional DC side protection required; AC side protection requires max 20A per branch circuit OUTPUT DATA(AC) IQ 7 Microinverter IQ 7+Microinverter Peak output power 250 VA 295 VA Maximum continuous output power 240 VA 290 VA Nominal(L-L)voltage/range' 240 V/ 208 V/ 240 V/ 208 V/ 211-264 V 183-229 V 211-264V 183-229V Maximum continuous output current 1.D A(240 V) 1.15 A(208 V) 1.21 A(240 V) 1.39 A(208 V) Nominal frequency 60 Hz 60 Hz Extended frequency range 47-68 Hz 47-68 Hz AC short circuit fault current over 3 cycles 5.8 Arms 5.8 Arms Maximum units per 20 A(L-L)branch circuit' 16(240 VAC) 13(208 VAC) 13(240 VAC) 11 (208 VAC) Overvoltage class AC port III III AC port backfeed current 0 A 0 A Power factor setting 1.0 1.0 Power factor(adjustable) 0.7 leading...0.7 lagging 0.7 leading...0.7 lagging EFFICIENCY @240 V @208 V @240 V @208 V Peak CEC efficiency 97.6% 97.6% 97.5% 97.3% CEC weighted efficiency 97.0% 97.0% 97.0% 97.0% MECHANICAL DATA Ambient tem erature ran e -40°C to+65°C Relative humidity range 4%to 10D%(condensing) Connector type(IQ7-60-2-US&IQ7PLUS-72-2-US) MC4(or Amphenol H4 UTX with additional Q-DCC-5 adapter) Connector type(IQ7-60-B-US&IQ7PLUS-72-B-US) Friends PV2(MC4 intermateable). Adaptors for modules with MC4 or UTX connectors: -PV2 to MC4:order ECA-S20-S22 -PV2 to UTX:order ECA-S20-S25 Dimensions(WxHxD) 212 mm x 175 mm x 30.2 mm(without bracket) Weight 1.08 kg(2.38 Ibs) Cooling Natural convection-No fans Approved for wet locations Yes Pollution degree PD3 Enclosure Class II double-insulated,corrosion resistant polymeric enclosure Environmental category/UV exposure rating NEMA Type 6/outdoor FEATURES Communication Power Line Communication(PLC) Monitoring Enlighten Manager and MyEnlighten monitoring options. Both options require installation of an Enphase IQ Envoy. Disconnecting means The AC and DC connectors have been evaluated and approved by UL for use as the load-break disconnect required by NEC 690. Compliance CA Rule 21 (UL 1741-SA) UL 62109-1,UL1741/IEEE1547,FCC Part 15 Class B, ICES-0003 Class B, CAN/CSA-C22.2 NO.107.1-01 This product is UL Listed as PV Rapid Shut Down Equipment and conforms with NEC-2014 and NEC-2017 section 690.12 and C22.1-2015 Rule 64-218 Rapid Shutdown of PV Systems,for AC and DC conductors,when installed according manufacturer's instructions. 1.No enforced DC/AC ratio.See the compatibility calculator attittusi/wlphase com/en-us/sy000rt/module-compatibility. 2.Nominal voltage range can be extended beyond nominal if required by the utility. 3.Limits may vary.Refer to local requirements to define the number of microinverters per branch in your area. To learn more about Enphase offerings,visit enphase.com e EN P H A S E. ©2018 Enphase Energy.All rights reserved.All trademarks or brands used are the property of Enphase Energy,Inc. 2018-05-24 Data Sheet Enphase Networking Enphase The Enphase IQ Combiner+-" with Enphase IQ Envoy`" consolidates interconnection IQ Combiner+ equipment into a single enclosure and (X-IQ-AMI1-240-2) streamlines PV and storage installations by providing a consistent, pre-wired solution for residential applications. It offers up to four 2-pole input circuits and Eaton BR series busbar assembly. Smart • Includes IQ Envoy for communication and control — I • Flexible networking supports Wi-Fi, �� ��' Ethernet,or cellular • Provides production metering and optional r consumption monitoring st = • Supports installation of the • I Enphase Q Aggregator."' 1 Simple _ `` y;• ( • Eaton BR series panelboard interior asiniseari �---Q- • Up to four 2-pole branch circuits for 240 VAC r plug-in breakers(not included) • 80 A total PV or storage branch circuits Reliable • Durable NRTL-certified NEMA type 3R enclosure • Five-year warranty • UL listed LISTED ENPHASE To learn more about Enphase offerings,visit enphase.com �,/ Enphase IQ Combiner+ MODEL NUMBER IQ Combiner+X-IQ-AM1-240-2 IQ Combiner+with Enphase IQ Envoy"for integrated revenue grade PV production metering (ANSI C12.20+/-0.5%)and optional*consumption monitoring(+/-2.5%). ACCESSORIES(order separately) Enphase Mobile Connect" CELLMODEM-03(4G/12-year data plan) Plug and play industrial grade cellular modem with data plan for systems up to 60 CELLMODEM-01 (3G/5-year data plan) microinverters.(Available in the US,Canada,Mexico,Puerto Rico,and the US Virgin Islands, CELLMODEM-M1(40 LTE CAT-M1/5-year data plan) where there is adequate cellular service in the installation area.) Consumption Monitoring CT CT-200-SPLIT Split core current transformers enable whole home consumption metering*(+/-2.5%). Circuit Breakers BRK-15A-2-240 Breaker,2 pole,15A,Eaton BR215 BRK-20A-2-240 Breaker,2 pole,20A,Eaton BR220 ELECTRICAL SPECIFICATIONS Rating Continuous duty System voltage 240 VAC,60 HZ Eaton BR series busbar rating 125 A Max.continuous current rating(output to grid) 65 A Max.fuse/circuit rating(output) 90 A Branch circuits(solar and/or storage) Up to four 2-pole Eaton BR series Distributed Generation(DG)breakers only(not included) Max.continuous current rating(input from PV) 64 A Max.total branch circuit breaker rating(input) 80 A(any combination) Production Metering CT 200 A solid core pre-installed and wired to IQ Envoy MECHANICAL DATA Dimensions(WxHxD) 49.3 x 46.5 x 16.0 cm(19.4"x 18.3 x 6.3") Weight 7.5 kg(16.5 Ibs) Ambient temperature range -40°C to+46°C(-40°to 115°F) Cooling Natural convection,plus heat shield Enclosure environmental rating Outdoor,NRTL-certified,NEMA type 3R,polycarbonate construction Wire sizes • 20 A to 50 A breaker inputs: 14 to 4 AWG copper conductors • 60 A breaker branch input: 3 to 1/0 AWG copper conductors • Main lug combined output 10 to 2/0 AWG copper conductors • Neutral and ground: 14 to 1/0 copper conductors Always follow local code requirements for conductor sizing. Altitude To 2000 meters(6,560 feet) INTERNET CONNECTION OPTIONS Integrated Wi-Fi 802.11b/g/n Ethernet 802.3,Cat5E(or Cat 6)UTP Ethernet cable-not included Cellular Optional,CELLMODEM-01 (3G)or CELLMODEM-03(4G)(not included) COMPLIANCE Compliance,Combiner UL 1741 CAN/CSA C22.2 No.107.1 47 CFR,Part 15,Class B,ICES 003 Production metering:ANSI C12.20 accuracy class 0.5(PV production) Compliance,IQ Envoy UL 916 CAN/CSA C22.2 No.61010-1 *Consumption monitoring is required for Enphase Storage Systems. To learn more about Enphase offerings,visit enphase.com ©2018 Enphase Energy.All rights reserved.All trademarks or brands in this document are registered by their respective owner. A 1 P I- /4 S E 2018-05-02 `� E/ 1"�fl NA .�1 G