Report ELe_2D.20-024/c
t/60c, 7244) .ftr/c�
Switchboard General Information
Pow-R-Line C-Specifications
Quantity:1 E r
Alignment:Front Access/Front and Rear Align E�,/
Service:208Y/120V 3-Phase 4-Wire Minimum Interrupt Rating:42 kA Y 1�
Bus Specifications MAY 12 2020
Bus Amps:2000 Bus Bracing Rating:65kA
Neutral Amps:2000 CITY OF TIGA D
Bus Material:Aluminum Heat Test BUILDING MOON
1N
Ground Bus Material: Aluminum .25 X 2.0 Ground Bus Bolted To t„ ;,.e v r�,r v'^`
Frame,(1)#6-350 kcmil Ground Lug
Incoming Information
Terminals,Mechanical,Bottom,See Utility Specifications
Incoming Entry: Bottom Incoming Location: Right
Incoming Qty & Size: Terminals, Mechanical, Bottom, See Utility
Specifications
Structure Specifications
Service Entrance
Enclosure Type:Type 1
Seismic Label(IBC/CBC Seismic Qualified)-Freestanding
Refer to seismic installation data sheet TD01508002E
and drawing 1A32496 for details.
Nameplates: None-
Special Notes
Qty Description Catalog Number
1 BREAKERS IN SECTION 3 TO BE MINIMUM OF 24" FROM CN92535
FLOOR
Utility Specfications
Struct#4
2000 Amps Util.Mtr.Compt.-PORTLAND GENERAL ELECTRIC
Utility Service Requirements Page References:
UGPS Per Dwg.345
LUGS
(7)EUSERC Press Bolts
Utility Specfications
Struct#2
1200 Amps Util.Mtr.Compt.-PORTLAND GENERAL ELECTRIC
Utility Service Requirements Page References:
Lug Drillings Per Dwg.:347
CT Compartment Per Dwg.322/330
Meter Door per Dwg.332
13J Meter Socket(s)
LUGS
Doors-(2)-15"with Meter at the Bottom
None
Enclosure properties
Struct# Description/Modifications
1 50x chassis mounted feeders(Feeder Structure)
2 Utility Structures(Utility Structure)
Vertical isolating barrier
Horizontal isolating barrier
The information on this document is PREPARED BY DATE
created by Eaton Corporation.It is MARK WHITE 5/5/2020 Eaton SumterSC
disclosed in confidence and it is only to
be used for the purpose in which it is APPROVED BY DATE JOB NAME La Londe-Tigard Triangle-E7580503X0K1
supplied. DESIGNATION MDS1
VERSION TYPE DRAWING TYPE
9.0.24.5 Switchboards CustAppr
NEG-ALT Number REVISION DWG SIZE G,O. ITEM SHEET
E7560503X0K1-0002 0 DwgA 001 1 of 5
3 50x chassis mounted feeders(Feeder Structure)
4 Incoming Utility Structures(Incoming Utility Section)
Vertical isolating barrier
Horizontal isolating barrier
The information on this document is PREPARED BY DATE
created by Eaton Corporation.It is MARK WHITE 5/5/2020 Eaton SumterSC
disclosed in confidence and it is only to
be used for the purpose in which it is APPROVED BY DATE JOB NAME La Londe-Tigard Triangle-E7580503X0K1
supplied. DESIGNATION MDS1
VERSION TYPE DRAWING TYPE
9.0.24.5 Switchboards CustAppr
NEO-ALT Number REVISION DWG SIZE G.O. ITEM SHEET
E7580503X0K1-0002 0 DwgA 001 2 of 5
13J
UTIL I
I Blank Doorl
_ _ PI II I
' a a 2 I 0 11 ®SPD I SECT I
3 ° ° 4
4
° ° s 214GSl CI l
Iffi 3uos I o j
I I
NGS
Front View
Struct 1 2 3 4
Depth 30 30 1 30 1 30
Width 36 38 36 45
Power Flow n (Ti
1 I
I
See 1A32043 For See 1A32043 For
Floor Plan Detail Floor Plan Detail
Floor Plan Top/Bottom Top/Bottom
Rear Cable Exit Cable Exit
A
A 24 00
r 12.00 s,s�o zoo z�so ` �y
30 T s a 3u _T i 35 T >
300 .4. F 300 ... .4..3.00
Total of 4 Structures.Total Weight of 2512 Weight-Lbs.
Total of 4 Structures,Total Width of 155 Inches
Structure 1 2 3 4
Ship-Inches 36.00 38.00 36.00 45.00
Ship-MM 914 965 914 1143
Wdth-Inches 36.00 38.00 36.00 45.00
Wdth-MM 914 965 914 1143
Depth(Inner)-In. 30.00 30.00 30.00 30.00
Depth(Inner)-MM 762 762 762 762
Depth(Outer)-In. 30.00 30.00 30.00 30.00
Depth(Outer)-MM 762 762 762 762
Height-Inches 90.00 90.00 90.00 90.00
Height-MM 2286 2286 2286 2286
Weight-Lbs.(Est.) 520 725 617 650
Weight-Kq.(Est.) 235 328 279 294
The information on this document is PREPARED BY DATE
created by Eaton Corporation.It is MARK WHITE 5/5/2020 Eaton SumterSC
disclosed in confidence and it is only to
be used for the purpose in which it is APPROVED BY DATE JOB NAME La Londe-Tigard Triangle-E7580503X0 K1
supplied. DESIGNATION MDS1
VERSION TYPE DRAWING TYPE
9.0.24.5 Switchboards CustAppr
NEG-AIT Number REVISION DWG SIZE G.O, ITEM SHEET
E7580503XOK1-0002 0 DwgA 001 3 of 5
Switchboard Units Information
Str# Unit Description/Modifications Nameplate
1
1 Feeder Breaker-Chassis Mtd-150A 3P[EDS 225A Frame],Trip 150A.,Thermal Mag PANEL L1/L2
Terminals,Mechanical,(1)#4-4/0
PANEL L1 /L2
Neutral Terminal,(1)#6-350 kcmil
2 Feeder Breaker-Chassis Mtd-200A 3P[FDE 225A Frame],Trip 200A.,225A 310+, LSI ATS-1
Terminals,Mechanical,(1)#6-300 kcmil
Neutral Terminal,(1)#6-350 kcmil
3 Feeder Breaker-Chassis Mtd-200A 3P[EDS 225A Frame],Trip 200A.,Thermal Mag PANEL M1
Terminals,Mechanical,(1)#6-300 kcmil 2 SECTIONS
PANEL M1 2 SECTIONS
Neutral Terminal,(1)#6-350 kcmil
4 Feeder Breaker-Chassis Mtd-100A 3P[EDS 225A Frame],Trip 100A.,Thermal Mag FUTURE SOLAR
Terminals,Mechanical,(1)#14-1/0
Neutral Terminal,(1)#14-1/0
5 Feeder Breaker-Chassis Mtd-200A 3P[EDS 225A Frame],Trip 200A.,Thermal Mag PANEL M3
Terminals,Mechanical,(1)#6-300 kcmil 2 SECTIONS
PANEL M3 2 SECTIONS
Neutral Terminal,(1)#6-350 kcmil
6 Feeder Breaker-Chassis Mtd-200A 3P[EDS 225A Frame],Trip 200A.,Thermal Mag PANEL M5
Terminals,Mechanical,(1)#6-300 kcmil 2 SECTIONS
Neutral Terminal, (1)#6-350 kcmil
2
Main Breaker-Ind Mtd-1200AAdj,3P[NGS 1200A Frame],Trip 1200A.,310+w/ARMS,ALSI MAIN BREAKER
ARMS Operation-Local using breaker interface and remote wired to terminal block-Customer HOUSE POWER
to supply 24VDC for remote activation
Lockoff devices:Padlockable Hasp
1200A Utility Metering-PORTLAND GENERAL ELECTRIC
3
1 Surge Protective Device-SPD Series 200kA SPD,Basic(Disconnect Included)
2 Feeder Breaker-Chassis Mtd-1000A Adj,3P[NGS 1200A Frame],Trip 1000A.,310+w/ARMS, METER CENTER
ALSI MC-1
Terminals,Mechanical,(4)4/0-500 kcmil
Lockoff devices:Padlockable Hasp
The information on this document is PREPARED BY DATE
created by Eaton Corporation.It is MARK WHITE 5/5/2020 Eaton SumterSC
disclosede sed inconfidence and ith c it only to APPROVED BY DATE JOB NAME La Londe-Tigard Trian le-E7580503X0K1
be used for the purpose in which it is 9 9
supplied. DESIGNATION MDS1
VERSION TYPE DRAWING TYPE
9.0.24.5 Switchboards CustAppr
NEG-ALT Number REVISION DWG SIZE G.O. ITEM SHEET
E7580503X0K1-0002 0 DwgA 001 4 of 5
Neutral Terminal,(4)#4-500 kcmil
3 Feeder Breaker-Chassis Mtd-1000A Adj, 3P[NGS 1200A Frame],Trip 1000A., 310+w/ARMS, METER CENTER
ALSI MC-2
Terminals, Mechanical,(4)4/0-500 kcmil
Lockoff devices:Padlockable Hasp
Neutral Terminal,(4)#4-500 kcmil
4
2000A Pull Section-PORTLAND GENERAL ELECTRIC
The information on this document is PREPARED BY DATE
created by Eaton Corporation.It is MARK WHITE 5/5/2020 Eaton SumterSC
disclosed in confidence and it is only to
be used for the purpose in which it is APPROVED BY DATE JOB NAME La Londe-Tigard Triangle-E7580503X0K1
supplied. DESIGNATION MDS1
VERSION TYPE DRAWING TYPE
9.0.24.5 Switchboards CustAppr
NEG-ALT Number REVISION DWG SIZE G.D. ITEM SHEET
E7580503X0K1-0002 0 DwgA 001 5 of 5
Portland General Electric Company
11/21/19 (GE
CONTACT: Sabrina La Londe
PHONE: 503-308-4777
CUSTOMER NAME: Scott Edwards Architecture
ADDRESS: sw Baylor st and sw 72nd ave
SDPM/ENGR: Wayne Brabham WR: M2771856
PHONE: 503-672-5440
3-PHASE SECONDARY LINE-LINE FAULT CURRENT (RMS)
TRANSFORMER DATA PAD MOUNT? YES
XFMR Impedance (%): 5.32 % 3-PH SUBMERSI YES
TRANSFORMER SIZE: 750 KVA XFMR? NO
Secondary VOLTAGE (L to L): 208 v WYE OH BANK? NO
VAULT--> VAULT ( or Pole --> Pole) SECONDARY
Secondary Wire LENGTH: 1 Feet WIRE SIZE
Number of SECONDARY RUNS: 1 Run(s) of:
Secondary WIRE Resistance R: 0.0180 Ohms/1000'
Secondary WIRE Reactance X: 0.0258 Ohms/1000'
VAULT ( or Pole) --> PANEL SECONDARY (or Svc Drop)
Service Wire LENGTH: 15 Feet WIRE SIZE
Number of Service RUNS: 6 Run(s) of: 750 QX UG M
Service WIRE Resistance R: 0.0286 Ohms/1000'
Service WIRE Reactance X: 0.0264 Ohms/1000'
MAXIMUM FAULT CURRENT*: 37,562 Amps
*Maximum fault current based upon transformers/conductors sized for 100% of electrical panel rating.
Based on a panel size of: 2000 Amps
To Print This Page: "Ctrl M"and choose "Print 3-Phase Data"
Generated by COM check-Web Software
(11:\rirfil Interior Lighting Compliance
Certificate
Section 1: Project Information
Energy Code:2014 Oregon Energy Efficiency Specialty Code
Project Title:Tigard Triangle(72nd&Baylor)
Project Type: New Construction
Construction Site: 11600 SW 72nd Ave., Tigard, OR 97223 Designer/Contractor:
Owner/Agent: Community Development Partners
Section 2: Interior Lighting and Power Calculation
B C D
A Floor Area Allowed Allowed Watts
Watts/ft2
Multifamily 87180 0.58 50564
Total Allowed Watts= 50564
Section 3: Interior Lighting Fixture Schedule
A B C D E
Fixture ID : Description/Lamp/Wattage Per Lamp/Ballast Lamps/ #of Fixture (C X D)
Fixture Fixtures Watt.
Multifamily(87180 sq.ft.)
LED:Li:Flush Lights:LED PAR 16W: 1 520 16 8320
LED:L2:Hallway Lighting:LED Linear 22W: 1 115 22 2530
LED:L4:Wall Wash Light:LED Linear 17W: 1 2 18 36
LED:L5:Designer Common Area:LED A Lamp 7W: 4 2 28 56
LED:L6:Vanity Light:LED PAR 8W: 2 91 16 1456
LED:L7.1:Service Spaces:LED Linear 33W: 1 10 33 330
LED:L8:Wall Sconce:LED Other Fixture Unit 16W: 1 5 18 90
LED:L10:Bedroom Lights:LED Other Fixture Unit 16W: 1 224 20 4480
LED:L12:Common Suspended Lights:LED Other Fixture Unit 60W: 1 4 74 296
LED:L14:Bathroom Can Lights:LED PAR 16W: 1 92 16 1472
LED:L15:Community RM Pendant Lights:LED Other Fixture Unit 13W: 1 7 13 91
LED:L16:Community Room Lights:LED Other Fixture Unit 13W: 1 23 14 322
LED:L20:Community Room Lights:LED Other Fixture Unit 13W: 1 4 13 52
LED:L21:Common Space Wall Sconce: LED Other Fixture Unit 13W: 1 4 11 44
LED:L22:Elevator Lobbies:LED Other Fixture Unit 60W: 1 5 60 300
LED:L23:Lobby-Small Pendant:LED Other Fixture Unit 103W: 1 3 100 300
LED:L24:Elevator Lobby:LED Other Fixture Unit 16W: 1 6 16 96
LED:Exit Lights:Exit Lights:Other: 1 24 5 120
Total Proposed Watts= 20391
Section 4: Requirements Checklist
In the following requirements,blank checkboxes identify requirements that the applicant has not acknowledged as being met.Checkmarks
identify requirements that the applicant acknowledges are met or excepted from compliance. 'Plans reference page/section'identifies where in
the plans/specs the requirement can be verified as being satisfied.
Lighting Wattage:
® 1. Total proposed watts must be less than or equal to total allowed watts.
Allowed Wattage:50564 Proposed Wattage:20391
Complies:YES
Mandatory Requirements:
a 2. Exit signs.Internally illuminated exit signs shall not exceed 5 watts per side.
Project Title:Tigard Triangle Copy 2 Copy 2 Report date: 05/11/20
Data filename: Page 1 of 6
Plans reference page/section:
21 3. Daylight zone control.All daylight zones are provided with individual controls that control the lights independent of general area lighting
in the non-daylight zone.In all individual daylight zones larger than 350 sq.ft.,automatic daylight controls is provided.Automatic
daylight sensing controls reduce the light output of the controlled luminaires at least 50 percent,and provide an automatic OFF control,
while maintaining a uniform level of illumination.Contiguous daylight zones adjacent to vertical fenestration may be controlled by a
single controlling device provided that they do not include zones facing more than two adjacent cardinal orientations(i.e.,north,east,
south,west).Daylight zones under skylights shall be controlled separately from daylight zones adjacent to vertical fenestration.
Exception(s):
• Retail spaces adjacent to vertical glazing(retail spaces under overhead glazing are not exempt).
• Display,exhibition and specialty lighting
O HID lamps 150 watts or less.
[?� Spaces required to have occupancy sensors.
Plans reference page/section: E1.1 through E1.6
a 4. Interior lighting controls.At least one local shutoff lighting control has been provided for every 2,000 square feet of lit floor area and
each area enclosed by walls or floor-to-ceiling partitions.The required controls are located within the area served by the controls or are
a remote switch that identifies the lights served and indicates their status.
Exception(s):
® Lighting systems serving areas designated as security or emergency areas that must be continuously lighted.
j Lighting in public areas such as concourses,stairways or corridors that are elements of the means of egress with switches that
are accessible only to authorized personnel.
▪ Lighting for warehouses,parking garages or spaces using less than 0.5 watts per square foot.
❑ Lighting for contiguous,single-tenant retail spaces.
Plans reference page/section: E1.1 through E1.6
® 5. Sleeping unit controls.Master switch at entry to hotel/motel guest room.
Plans reference page/section: E2.1 &E2.3
a 6. Egress lighting.Egress illumination is controlled by a combination of listed emergency relay and occupancy sensors to shut off during
periods that the building space served by the means of egress is unoccupied.
Exception(s):
p Building exits as defined in Section 1002 of the Oregon Structural Specialty Code.
Plans reference page/section: E1.1 -E1.6
La 7. Additional controls. Each area that is required to have a manual control shall have additional controls that meet the requirements of
Sections 505.2.2.1 and 505.2.2.2.
Plans reference page/section: See all E-Sheets
® 8. Light reduction controls. Each space required to have a manual control also allows for reducing the connected lighting load by at least
50 percent by either 1)controlling(dimming or multi-level switching)all luminaires;or 2)dual switching of alternate rows of luminaires,
alternate luminaires,or alternate lamps;or 3)switching the middle lamp luminaires independently of other lamps;or 4)switching each
luminaire or each lamp.
Exception(s):
❑ Only one luminaire in space.
[g An occupant-sensing device controls the area.
• The area is a corridor,storeroom,restroom,public lobby or sleeping unit.
• Electrical and mechanical room.
LI Areas that use less than 0.6 Watts/sq.ft.
Plans reference page/section: See all E-sheets
xj 9. Buildings larger than 2,000 square feet are equipped with an automatic control device to shut off lighting in those areas.This automatic
control device shall function on either:1)a scheduled basis,using time-of-day,with an independent program schedule that controls the
interior lighting in areas that do not exceed 10,000 square feet and are not more than one floor;or 2)an occupant sensor that shall turn
lighting off within 30 minutes of an occupant leaving a space;or 3)a signal from another control or alarm system that indicates the area
is unoccupied.
Exception(s):
D Sleeping units,patient care areas;and spaces where automatic shutoff would endanger safety or security.
Project Title:Tigard Triangle Copy 2 Copy 2 Report date: 05/11/20
Data filename: Page 2 of 6
Plans reference page/section: E1.1 -E1.6
3 10.Occupancy sensors in rooms that include daylight zones are required to have Manual ON activation.
Plans reference page/section: E1.1-E1.6
® 11.An occupant sensor control device is installed that automatically turns lighting off within 30 minutes of all occupants leaving a space.
Exception(s):
• Classrooms and lecture halls.
O Conference,meeting and training rooms.
• Employee lunch and break rooms.
• Rooms used for document copying and printing.
• Office spaces up to 300 square feet.
Restrooms.
O Dressing,fitting and locker rooms.
Plans reference page/section: E1.1 -E1.6
12.Additional controls.An occupant sensor control device that automatically turns lighting off within 30 minutes of all occupants leaving a
space or a locally activated switch that automatically turns lighting off within 30 minutes of being activated is installed in all storage and
supply rooms up to 1000 square feet.
Plans reference page/section: E1.1-E1.6
• 13.Occupant override.Automatic lighting shutoff operating on a time-of-day scheduled basis incorporates an override switching device
that: 1)is readily accessible,2)is located so that a person using the device can see the lights or the area controlled by that switch,or
so that the area being lit is annunciated,3)is manually operated,4)allows the lighting to remain on for no more than 2 hours when an
override is initiated,and 5)controls an area not exceeding 2,000 square feet.
Exception(s):
❑ In malls and arcades,auditoriums,single-tenant retail spaces,industrial facilities and arenas,where captive-key override is
utilized,override time is permitted to exceed 2 hours.
❑ In malls and arcades,auditoriums,single-tenant retail spaces,industrial facilities and arenas,the area controlled shall not exceed
20,000 square feet.
Plans reference page/section: E1.1 -E1.6
j 14.Holiday scheduling.Automatic lighting shutoff operating on a time-of-day scheduled basis has an automatic holiday scheduling feature
that turns off all loads for at least 24 hours,then resumes the normally scheduled operation.
Exception(s):
❑ Retail stores and associated malls,restaurants,grocery stores,places of religious worship,theaters and exterior lighting zones.
p Single zone electronic time control devices and self-contained wall box preset lighting controls.
Plans reference page/section:
® 15.Exterior lighting controls. Lighting not designated for dusk-to-dawn operation shall be controlled by either a combination of a
photosensor and a time switch,or an astronomical time switch.Lighting designated for dusk-to-dawn operation shall be controlled by
an astronomical time switch or photosensor.
Plans reference page/section: E1.1 -E1.6
• 16.Tandem wiring.The following luminaires located within the same area shall be tandem wired:1.Fluorescent luminaires equipped with
one,three or odd-numbered lamp configurations,that are recess-mounted within 10 feet center-to-center of each other.2.Fluorescent
luminaires equipped with one,three or any odd-numbered lamp configuration,that are pendant-or surface-mounted within 1 foot edge-
to-edge of each other.
Exception(s):
• Where electronic high-frequency ballasts are used.
[g Luminaires on emergency circuits.
❑ Luminaires with no available pair in the same area.
Plans reference page/section: E1.1 -E1.6
• 17.Medical task lighting or art/history display lighting claimed to be exempt from compliance has a control device independent of the control
of the nonexempt lighting.
Plans reference page/section: Not Applicable
• 18.Each dwelling unit in a building is metered separately.
Project Title:Tigard Triangle Copy 2 Copy 2 Report date: 05/11/20
Data filename: Page 3 of 6
Plans reference page/section: E0.2
Interior Lighting PASSES:Design 60%better than code.
Section 5: Compliance Statement
Compliance Statement: The proposed lighting design represented in this document is consistent with the building plans,specifications and
other calculations submitted with this permit application.The proposed lighting system has been designed to meet the 2014 Oregon Energy
Efficiency Specialty Code requirements in COMcheck-Web and to comply with the mandatory requirements in the Requirements Checklist.
Bruce La Londe,Vice President i774 _ _ r 5/1112020
Name-Title Signature Date
Project Notes:
Tigard Triangle(72nd&Baylor)11600 SW 72nd AvenueTigard,OR 97223
Project Title:Tigard Triangle Copy 2 Copy 2 Report date: 05/11/20
Data filename: Page 4 of 6
GExteriorenerated by COMcheckLighting-Web Software
Compliance
Certificate
Section 1: Project Information
Energy Code: 2014 Oregon Energy Efficiency Specialty Code
Project Title:Tigard Triangle Copy 2 Copy 2
Project Type: New Construction
Exterior Lighting Zone: 2 (Residentially zoned area)
Construction Site: Owner/Agent: Designer/Contractor:
Section 2: Exterior Lighting Area/Surface Power Calculation
A B C D E F
Exterior Area/Surface Quantity Allowed Tradable Allowed Proposed
Watts/ Wattage Watts Watts
Unit (B x C)
Front Entry(Entry canopy) 100 ft2 0.25 Yes 25 32
32 Space Parking Area(Parking area) 9883 ft2 0.06 Yes 593 800
Deck in Front(Illuminated length of facade wall/surface 25 ft 2.5 No 62 64
or roof path)
Outside Area(Parking area) 8800 ft2 0.06 Yes 528 650
Total Tradable Watts*= 1146 1482
Total Allowed Watts= 1208
Total Allowed Supplemental Watts**= 600
*Wattage tradeoffs are only allowed between tradable areas/surfaces.
**A supplemental allowance equal to 600 watts may be applied toward compliance of both non-tradable and tradable areas/surfaces.
Section 3: Exterior Lighting Fixture Schedule
A B C D E
Fixture ID: Description/Lamp/Wattage Per Lamp/Ballast Lamps/ #of Fixture (C X D)
Fixture Fixtures Watt.
Front Entry(Entry canopy,100 ft2):Tradable Wattage
LED:LED PAR 16W: 1 2 16 32
32 Space Parking Area(Parking area,9883 ft2):Tradable Wattage
LED:LED Other Fixture Unit 40W: 1 20 40 800
Deck in Front(Illuminated length of facade wall/surface or roof path,25 ft):Non-tradable Wattage
LED:LED PAR 16W: 1 4 16 64
Outside Area(Parking area,8800 ft2):Tradable Wattage
LED:LED Roadway-Parking Unit 130W: 1 5 130 650
Total Tradable Proposed Watts= 1482
Section 4: Requirements Checklist
In the following requirements, blank checkboxes identify requirements that the applicant has not acknowledged as being met. Checkmarks
identify requirements that the applicant acknowledges are met or excepted from compliance. 'Plans reference page/section'identifies where in
the plans/specs the requirement can be verified as being satisfied.
Controls, Switching, and Wiring:
® 1. Lighting designated to operate more than 2000 hours per year for Uncovered Parking Areas shall be equipped with motion sensors that
will reduce the luminaire power by thirty-three percent or turn off one-third the luminaires when no activity is detected.
Plans reference page/section: El 0
Exterior Lighting Restrictions and Exceptions:
Project Title:Tigard Triangle Report date: 05/11/20
Page 5 of 6
2. Mercury vapor and incandescent lighting is not permitted for use as exterior lighting.
Exception(s):
❑ Incandescent lighting controlled by motion sensors and having total power less than 150 watts.
Incandescent lighting used in or around swimming pools,water features,or other locations subject to the requirements of Article
680 of the National Electric Code.
JD 3. Exempt lighting fixtures are equipped with a control device independent of the control of the nonexempt lighting and are identified in
Section 3 table above.
Plans reference page/section: All are non-exempt.
Exterior Lighting PASSES: Design 15%better than code.
Section 5: Compliance Statement
Compliance Statement: The proposed exterior lighting design represented in this document is consistent with the building plans,specifications
and other calculations submitted with this permit application.The proposed lighting system has been designed to meet the 2014 Oregon
Energy Efficiency Specialty Code requirements in COMcheck-Web and to comply with the mandatory requirements in the Requirements
Checklist.
Bruce La Londe, Vice President � �i. 5/11/2020
Name-Title Signature Date
Project Title:Tigard Triangle Copy 2 Copy 2 Report date: 05/11/20
Data filename: Page 6 of 6