Specifications MEC.Z.o2o-ooG2--I 2400 SCk10 U g F'�'RRy t• !j OFFICE COPY 7650 S.W.Beveland St. RECEIVED 1M TM RIPPEY Tigard,Oregon 97223 Phone: (503)443-3900 'JUL. 2 $ 7'+ CONSULTING ENGINEERS Fax: (503)443-3700 CITY OF TIGARD BUILDING DIVISION STRUCTURAL CALCULATIONS PROJECT: HUNTER DAVISSON— 7-ELEVEN SCHOLLS FERRY LOCATION: 12100 SCROLLS FERRY RD. TIGARD,OR 97223 CLIENT: HUNTER DAVISSON DATE: JULY 16,2020 PROJECT NUMBER: 20003.19 TABLE OF CONTENTS: ITEM SHEET NUMBER GENERAL NOTES N1 SKETCHES SK1—SK2 CALCULATIONS Cl—05 DESCRIPTION: THIS DESIGN PACKAGE INCLUDES SKETCHES AND CALCULATIONS FOR INSTALLATION OF TWO(2)REPLACEMENT ROOFTOP UNITS AT THE ADDRESS NOTED ABOVE.CALCULATIONS TOOK INTO ACCOUNT THE WEIGHT OF THE UNIT AND CURB. NEW UNITS ARE REPLACING EXISTING HEAVEIER UNITS AT SAME LOCATIONS. SKETCHES INCLUDE THE CONNECTION OF THE UNIT TO THE CURB AND CURB TO THE EXISTING STRUCTURE. p� �!1 ASI:S\:GINE9-4,5)* L6.720 OREGON 9Gl- ao, TURNs9°� 9l oh, OPJ� EXP: 6/30/22 I. GENERAL STRUCTURAL NOTES CODE REOUIREMENTS: CONFORM TO THE 2018 INTERNATIONAL BUILDING CODE AS AMENDED BY THE 2019 OREGON STRUCTURAL SPECIALTY CODE,REFERENCED HEREAFTER AS IBC. • DESIGN CRITERIA: DESIGN WAS BASED ON THE STRENGTH AND DEFLECTION CRITERIA OF THE IBC. IN ADDITION TO THE DEAD LOADS,THE FOLLOWING LOADS WERE USED FOR DESIGN: ROOFTOP UNIT(5T)=656 LBS(UNIT+CURB)(48FC-5T-E-3PH) BASIC WIND SPEED(3-SEC GUST,ULTIMATE):97 MPH WIND EXPOSURE: B SEISMIC IMPORTANCE FACTOR le: 1.0 SITE CLASS:D(ASSUMED) SDS=0.685 EXISTING CONDITIONS: THE CONTRACTOR SHALL FIELD VERIFY ALL EXISTING CONDITIONS,DIMENSIONS AND ELEVATIONS. THE CONTRACTOR SHALL NOTIFY THE ARCHITECT/ENGINEER OF ANY DISCREPANCIES FROM CONDITIONS SHOWN ON THE DRAWINGS PRIOR TO THE START OF THE WORK. TEMPORARY CONDITIONS: THE CONTRACTOR SHALL BE RESPONSIBLE FOR STRUCTURAL STABILITY OF THE NEW AND EXISTING STRUCTURES AND WALLS DURING CONSTRUCTION. THE STRUCTURE SHOWN ON THE DRAWINGS HAS BEEN DESIGNED FOR STABILITY UNDER THE FINAL CONFIGURATION ONLY. MECHANICAL: THE CONTRACTOR SHALL COORDINATE SEISMIC RESTRAINTS OF ELECTRICAL EQUIPMENT,MECHANICAL,PLUMBING, FIRE SPRINKLER,MACHINERY,AND ASSOCIATED PIPING WITH THE STRUCTURE. ANY CONNECTIONS TO STRUCTURE NOT CONFORMING TO SHEET METAL AND AIR CONDITIONING CONTRACTORS NATIONAL ASSOCIATION(SMACNA),OR SPECIFICALLY DETAILED ON THE MECHANICAL ENGINEER'S DRAWINGS,SHALL BE DESIGNED IN ACCORDANCE OF THESE GENERAL NOTES,BY AN ENGINEER REGISTERED IN THE STATE OF OREGON,AND SHALL BE SUBMITTED TO THE ENGINEER PRIOR TO FABRICATION. FLASHING AND WATERPROOFING: ALL FLASHING AND WATERPROOFING SHALL BE BY OTHERS UNLESS NOTED OTHERWISE ON THE PLANS. 411NEE ���6,720� OREGON oa 9q � zo, gj JUG ...........") N ru100 EXP: 6/30/22 --f /1-p_ TM RIPPEY 1 Yl Consulting Engineers By: KMJ Date: 7650 SW Beveland Street HUNTER DAVISSON—7-ELEVEN SCHOLLS FERRY ChkBy: Date: Suite 100 Tigard,Oregon 97223 Job#: 20003.19 Phone:(503)443-3900 Sheet: NI Of � � (E) UNIT TO `I.tl6,g . R ir 3 BE REMOVED. ihi'°9 }' i? ®. `+'' 11 "ee , is �E`.�: �' ""R�, MODEL NO: 48FC-5T-E-3PH —_ II UNIT WGT= 565 LBS. ' ` �` Or-Tr7 '4 CURB WGT= 100 LBS. 1 — •'--- -- ATTACH CURB TO EACH (E) *°" +F�. --- '! TRUSS PER 1/SK2. ATTACH ,. "`�. (E) DOUBLE JOISTS AT TO MIN. OF (2)TRUSSES 0 ;, a HEAVY END OF UNITS BOTH SIDES. (4) TOTAL. gIL '`v +k (E) MANUFACTURED RTU-2 (5T) 1 : ) �` OPEN WEB WOOD MODEL NO: 48FC-5T-E-3PH `, , JOISTS @ 2'-8" O/C, TYP. UNIT WGT= 565 LBS. : t P. o CURB WGT= 100 LBS. * s: a ' 16 ATTACH CURB TO EACH (E) * . TRUSS PER 1/SK2. ATTACH w s r;: TO MIN. OF (2)TRUSSES - BOTH SIDES. (4)TOTAL. 1s a ` t Z tll.. G'S ADDRESS: , i".�' x "" 12100 SW SCHOLLS FERRY RD. Le ,+".^° , T GARD, OR 97223 At\�'J�< ��,1Ne0,„ 16,720 C1....) SITE PLAN oR--A115 GEGONc9sNOTES: 9p 2p, ♦- 0 9 I -ALL WATERPROOFING IS BY OTHERS <A PJ -EXACT LOCATION PER MECHANICAL PLANS N TURNe EXP: 6/30/22 TM RIPPEY BY KJ DATE CONSULTING ENGINEERS HUNTER DAVISSON -7-ELEVEN SCHOLLS FERRY CHK BY DATE 7650 SW Bcvcland,Suite 100 Tigard,Oregon 97223 JOB NO 20003.19 -Phone:(503)443-3900 Fax: (503)443-3700 SHEET SK1 OF 3'I}� EQ. SPACED .I BOTH WAYS TYP. �gIF{ 6,, 16 GA. CLIP MECHANICAL UNIT N.r.s. BY OTHERS 16 GA. CLIPS W/ (S) *10 TEK SCREWS PER CLIP, (4) CLIPS REQ'D. SEE DETAIL 'A' FOR Farah 1'-0", TYP. CLIP LOCATIONFA I I WOOD BLOCKING REQUIRED CLIP LOCATION FLASI-IING AND INSULATION MECH. UNIT NOT SI.4OWN FOR CLARITY A PLAN NTb. 1v f ...„„44., (E)TOP CHORD (1) #10 x 2" SCREW TO (E) TOP CHORD AT pp EACH TRUSS WHEN CURB RUNS PERPENDICULAR TO TRUSSES. (MIN. OF 4 TOTAL PER UNIT) 18,720 \� yG 0REG0N cro ti TUR03` CURB SECTION �s 1(2/ EXP: 6/30/22 TM RIPPEY BY KJ DATE CONSULTING ENGINEERS HUNTER DAVISSON - 7-ELEVEN SCHOLLS FERRY CHKRY DATE 7650 SW Beveland,Suite 100 Tigard,Oregon 97223 Joe No 20003.19 Phone:(503)443-3900 Fax:(503)443-3700 SHEET SK2 OF i y t I i I�1t ` 1 kar✓'c 'ra, ?, 1 6r16(na1 skis(.1 welkt 5ll 1b, ,tyLw u.nC-{-t. t{cgFG-s-c -E..-'-bPh' Jrt-§• wetoh- s 5SI4 N. N.Itiw uxwk'. wo6-4: 4. Old 1tvi-i- ',-> no 1fr:rco.Sg to -0cS41rtn) S-1-YvLe+Ls1,-c S1,-rc.acee o. eKts-hmb g-\-vu•-(r vA%C-O ... '--->.Ancn,6 Y0.I6L "To 4-r n,f- (k-t-rnnvi rv% e.)( stl n46 cwvb) —1'y,„,x — ' it-., lbc, / 2.AA ellarl, 139 .1tos(Ets' T-sAst, &114-scA .Q vmax - `-133 t`cl, / `I AM1chmr, .- lot, 1'a,', (P-.Sy`). ' mot?r -PPA1.k ect,C..S -e 40 X 1}4 \wVlau«b1A 1 co S lba iScre w ‘..j Vy wx , , 7 a�1 f• lb 11 - '- -1-at(w,ccHl,, z. e2.t i 11,6 (Scr2.W \l -'WIAX clv+ i L fro`n d 4 I o X 11/z' e 2.ffl. -IauSS 1 lkyl-k i- +P t,Lrrj 10 rcrE_u' 11A 11e h.(4'. 44)S 113c/Scxe.w > Th,iQy,, l/vKak L---> rovtd,t 4clak:,. CAIY wj (4) ItIl., sort_ws ea. C.,1Zp. , 4 styGiN ,,� ,Q 1-6,7-2^0 ' ,yG OEG6N 9q4 l� eb, ,�°Ja Ay TUFlNe1 EXP: ' 6/3'0/22 hANTMRIPPEY BY KY DATE__ CONSULTING ENGINEERS _... _ CHK BY _DATE 7650 S.W. Beveland St,Suite 100 pa NO "201.90.22.,19 Tigard, Oregon 97223 Phone(503) 443-3900 ___ SHEETC_k_ OF Wind and Seismic Loads on Mechanical Unit Worksheet Calculates the wind and seismic forces for a rooftop mounted mechanical unit based on the ASCE 7-16.Hold down forces are calculated based on 0.60+(0.6W or 0.7E) load cases. Wind and Seismic Loads on Mechanical Unit Windspeed:= 97mph Exposure:_ "B" Vasd "no" (Is wind speed ASD?) Seismic Parameters SDS:_ .685 ap 2.5 RP 6.0 lE:= 1.0 Building Dimensions Category:= "II" Roof Elevation:= 30ft Building_Width:= Il0ft Building_Depth 5011 Mechanical Unit Dimensions Displacement:_ "Fan Unit" RTU 5T Weight:= 5561b UnitHeight:= 33.5in Width:= 46.625in Length:= 74.5in Curb:= 14in Curb_Width:= 37.18in (Dimension for Calculating Overturning Uplift) SUMMARY(ALL VALUES ARE ASD) Method_Used= "ASCE 7-16-Section 29.5.1"D=556 lb W 3361b WindUpliflASD= Displacement="Fan Unit" (From ACSE 29.5-3) EASD= 1331b hseismic 2.563 ft WWindASD=433 lb (From ACSE 29.5-2) h 1.979ft X=3.098ft Wind= ,,. TWindTotalASD '278 th Notes: TseisnhiCASD=-57lb 1.Positive sign convenion shown.Negative values indicate opposite direcion 2.X equals the Wdth between attachmentprintsforoer.irnirg �M C2 Connection Calculator https://www.awc,org/calculators/connectiencaic.160106/ccstyle.as... Design Method I Allowable Stress Design(ASD) Connection Typell Lateral loading Fastener Type I Wood Screw Loading Scenario II Single Shear Main Member Type I Douglas Fir-Larch Main Member Thickness 1 1,75 in. Main Member:Angle of 190 Load to Grain I Side Member Type lI Steel Side Member Thickness 16 gage Side Member:Angle of Load to Grain �� Wood Screw Number 10(D=0.19 In,) Length 11.5 In. Load Duration Factor I Co= 1.6 Wet Service Factori I C_11 = 1.0 End Grain Factor I C_eg= 1.0 Temperature Factor I C_t= 1.0 Connection Yield Modes 1m 5451bs. Is 4101bs. II 223 lbs. Min 1263 lbs. Ills 185 lbs. IV I255lbs. Adjusted ASD Capacity 185 lbs. • Wood Screw bending yield strength of 80000 psi is assumed. • Dowel bearing strengths for wood screws with nominal diameter greater than 1/4 in. are calculated and rounded to the nearest 50 psi in accordance with NDS Table 11.3.2. • Length of tapered tip is assumed to be two times the nominal wood screw diameter for calculating dowel bearing length in the main member. • ASTM A36 Steel is assumed for steel side members 1/4 in.thick,and ASTM A653 I! Grade 33 Steel is assumed for steel side members less than 1/4 in.thick. While every effort has been made to insure the accuracy of the information presented,and special effort has been made to assure that the information reflects the state-of-the-art,neither the American Wood Council nor its members assume any responsibility for any particular design prepared from this on-line Connection Calculator.Those using this on-line Connection Calculator assume all liability from its use. • C� 1 of vnzrimn 1.SA nrn Connection Calculator https://www.awc.org/calculators/connectioncalc.160106/ccstyle.as... Design Method Ailowable Stress Design(ASD) Connection Type)Withdrawal loading LFastener Type I Wood Screw Loading Scenario I WA Main Member Type I Douglas Fir-Larch Main Member Thickness 1.75 In. Side Member Type I Steel ; Side Member Thickness 16 gage Wood Screw Number 110(D=0.19 in.) Length II 1.5 in. Load Duration Factor] C_D= 1.6 LWet Service Factor)I C_M =1.0 Temperature Factor I C t= 1,0 Adjusted ASD Capacity 217 lbs. • The Adjusted ASD Capacity does not apply for wood screws installed in the end grain of wood members. • The Adjusted ASD Capacity only applies to withdrawal of the fastener from the main member.It does not address head pull-through capacity of the fastener in the side member. While every effort has been made to insure the accuracy of the information presented,and special effort has been made to assure that the information reflects the state-of-the-art,neither the American Wood Council nor its members assume any responsibility for any particular design prepared from this on-line Connection Calculator.Those using this on-Iine Connection Calculator assume all liability from its use. The Connection Calculator was designed and created by Cameron Knudson,Michael Dodson and David Pollock at Washington State University.Support for development of the Connection Calculator was provided by American Wood Council. 1 of 1 7Itai-nmn z•cn pnn Search Information 4,11:od.,na-i21 Wat hmetton Square: 40 mud fla Address: 12100 SW Scholls Ferry Rd,Beaverton,OR 97008,USA 224 ft Rh w Coordinates: 45.44412369999999,-122.8007835 > R i Elevation: 224 ft Timestam p: 2020-07-10T22:51:15.974Z • Hazard Type: Seismic Goo'gle Reference ASCE7-16 I` Mapd<Repbd(8hiapertgte Document: Risk Category: II Site Class: D-default Basic Parameters Name Value Description Ss 0.856 MCER ground motion(period=0.2s) Si 0.397 MCER ground motion(period=1.0s) SMS 1.028 Site-modified spectral acceleration value SM1 *null Site-modified spectral acceleration value Sps 0.685 Numeric seismic design value at 0.2s SA SDI null Numeric seismic design value at 1.0s SA *See Section 11.4.13 Additional Information Name Value Description SDC *null Seismic design category Fa 1.2 Site amplification factor at 0.2s Fv *null Site amplification factor at 1.0s CRs 0.884 Coefficient of risk(0.2s) CRi 0.866 Coefficient of risk(1.0s) { PGA 0.391 MCEG peak ground acceleration FpGq 1.209 Site amplification factor at PGA • PGAM 0.473 Site modified peak ground acceleration TL 16 Long-period transition period(s) •