Loading...
Report F( ZO21 -o003S t o 7-.o yR 6.l + rzcl 12O3 )91,O 6 Simplex LifeAlarm Fire Alarm Controls UL,ULC,CSFM Listed;MEA(NYC) 4009 IDNet NAC Extender for Control with IDNet Communications or Conventional NACs Acceptance' Features Additional information.For additional operation detail and Provides additional notification appliance circuit(NAC)capacity application information,refer to Installation Instructions 574-181 and with flexible operation modes and power-limited design field wiring diagram 842-068. Four,Class B NACs are standard: Note:4100U requires revision 11 software or higher for compatibility. • Rated 2 A each for conventional reverse polarity 24 VDC notification 4010 requires revision 2 software or higher for compatibility. appliances and providing multiple operation modes. a Can be selected to provide synchronization for Simplex visible E 1 .b� notification strobe flashes. e • Capable of controlling TrueAlert non-addressable notification JUL iJ 2020 ��, appliances operating with SmartSync two-wire control mode. Input control options: ' -�-v OF"P A I Up to 8 NACs _ _ �4 a �IV S • IDNet addressable communications from a 4007E5,4010, ���� ���JI�yC1 Meg MP 4100U,or 4100ES Fire Alarm Control Panel.See note. 4� 4009 IDNet • Or from one or two conventional 24 VDC NACs with multiple output NAC Extender control options gg _ t`--),, IDNet communications control benefits: I =� � -0, r • Provides status monitoring and individual NAC control using a single address per 4009 IDNet NAC Extender .[ Optional IDNet • Supports IDNet"Device Level"earth fault location == Channel Repeater r WALKTEST operation is available with either input choicei Internal 8 A power supply/battery charger: 1 % • Charges internal batteries up to 12.7 Ah or up to 18 Ah batteries in / \ \% . external cabinet ' `\ . �. 2-Wire IDNet ` s • Provides status monitoring of battery,input power,and earth faults Communications a \ `', .`. • Rated 8 A for"Special Application"appliances;including 4901,4903, Fiber Optic IDNet .\ 4904,and 4906 Series horns,strobes,horn/strobes,and speaker/ Communications 91 \ strobes • Rated 6 A for"Regulated 24 DC"appliance power ® ,,,., , t t NAC Control - . r % Optional 4009 IDNet NAC Extender modules: • IDNet Communications Repeater provides Class B or Class A output IDNet Fiber • IDNet Communications Fiber Optic Receiver/Repeater,available as • Optic Transmitter • Class B or Class X • • Four additional Class B NACs,rated 1.5 A for Special Application 4007E5,4010(shown), • appliances;1 A for Regulated 24 DC appliance power 4010ES,4100ES,or 4100U L iiiii • Class A Two Circuit Adapter Module Fire Alarm Control Panel UL Listed to Standard 864 Fire Alarm Control Panel with Conventional NACs External Accessories Figure 1: 4009 IDNet NAC Extender IDNet communication fiber optic transmitters: connection reference drawing • For applications requiring the data integrity available with fiber optic communications •Available as Class B or Class X • Mounts in standard six-gang electrical box External battery cabinet for 18 Ah batteries Introduction ADA compliance.Complying with the notification requirements of ADA(Americans with Disabilities Act)may require more notification appliance power than is available within the fire alarm control panel. When additional power is required,a 4009 IDNet NAC Extender can provide up to 8 A of NAC power with up to eight,supervised reverse polarity NACs. Location flexibility.The 4009 IDNet NAC Extender can be mounted close to a compatible dedicated host panel or can be located remotely for convenient power distribution.Multiple operation modes and multiple connection options further increase location flexibility. uLC listed model is 4009-9202CA.This product has been approved by the California State Fire Marshal(CSFM)pursuant to Section 13144.1 of the California Health and Safety Code.See CSFM Listing 7300-0026214 for allowable values and/or conditions concerning material presented in this document.Accepted for use-City of New York Department of Buildings-MEA35-93E.Additional listings may be applicable;contact your local Simplex product supplier for the latest status.Listings and approvals under Simplex Time Recorder Co.are the property of Tyco Fire Protection Products_. 54009-0002 Rev. 15 9/2019 f35implEx 4009 IDNet NAC Extender for Control with IDNet Communications or Conventional NACs Application and operation information IDNet addressable communications compatible.Up to 10,4009 IDNet NAC Extenders can be controlled for each 4007ES,4010ES,4100U,or 4100ES IDNet communications channel;up to 5 can be controlled on the 4010 IDNet communications channel.Each output NAC can be individually controlled for general alarm or selective area notification requiring only one point address for each Extender.Individual Extender NACs can also be manually controlled from the host panel.IDNet controlled extenders will inform the host panel of troubles using IDNet communications.4007E5, 4010ES,4100ES,and 4100U control panels control using multi-point rules,refer to data sheet 54090-0011 for details. Optional IDNet repeaters.IDNet communications can be repeated with the optional IDNet Repeater Module or with the optional Fiber Optic Receiver Module.Up to 100 of the IDNet channel points can be repeated once(refer to Typical IDNet connection example and 4009 IDNet NAC Extender specifications for details).Repeated IDNet communications also support the"device level"earth fault location utility of the host panel. Hardwire control applications.For applications where an existing(or new)conventional NAC needs additional power,the 4009 IDNet NAC Extender can be controlled directly from the NAC.Either one or two NACs,from either the same,or from different host fire alarm control panels,can +r be connected to control the 4009 IDNet NAC Extender output NACs.Multiple control selections provide flexible operation.(See Hardwire Control Connection Information for more detail.)Alarms from the host panel will activate the four,4009 IDNet NAC Extender NACs(or optionally,8 NACs)to extend the alarm. The 4009 IDNet Extender monitors itself and each of its output NACs for trouble conditions,including earth faults.Extenders wired to conventional NACs will indicate a trouble by opening the path to the NAC's end-of-line resistor,but retaining the ability to respond to alarms.Individual troubles are also annunciated by LEDs located on the 4009 IDNet NAC Extender main circuit board.Refer to Service diagnostic features for more diagnostic information. Product selection Table 1:Standard models Model — ip Description 4009 9201** 20 VAC input 4009 IDNet NAC Extender with 4,Class B NACs 4009-9301 240 VAC input and 8 A power supply 4009-9202CA(ULC listed model) 120 VAC input - **4009-9201 has been seismic tested and is certified to IBC and CBC standards as well as to ASCE 7 categories A through F,requires battery brackets as detailed on data sheet 52081-0019 Table 2:Optional modules(for on-site installation) 'Model Description Comments —40.I4009-9807 Additional four point NAC module,rated 1.5 A Special Application 1 maximum appliances;1 A for Regulated 24 DC appliance power,Class B 4009-9808 Dual Class A adapter(for two NAC outputs) Select as required(4 maximum) 4009-9809 IDNet Repeater,output is Class A or Class B Select either an IDNet Repeater or a Fiber Optic 4009-9810 Class B Receiver as required;one transmitter can connect 4009-9811 Fiber Optic Receiver Class A(IDNet),Class X(fiber) to one receiver 4009-9805 Red Appliqué for door Select if required 2975-9801 Semi-Flush Trim Kit Beige trim 1 7/16 in.wide(78 mm),use if required for semi- 2975-9802 Red trim flush installations Table 3:Battery selection(select battery size using system requirements) ._....._____ Model Description - sit raw 2081-9272 6.2 Ah Battery,12 VDC 2081-9274 10 Ah Battery,12 VDC Two batteries are required,24 VDC operation 2081-9288 12.7 Ah Battery,12 VDC 2081-9275 18 Ah Battery,12 VDC Requires external battery cabinet,two batteries are required,24 VDC operation Table 4:External accessories(select using system requirements) Model Description Comments 4090-9105 Class B operation Mounts in six-gang electrical box,refer to 4090-9105/9107 IDNet fiber optic transmitter DNet Fiber Optic mounting information for mounting details 4090-9107 Transmitter Class X operation Note:Class B Fiber Transmitter Rev C or higher, IS NOT COMPATIBLE with Class B Fiber Receiver before RevJ. 4009-9801 External battery cabinet for up to 18 Ah batteries,beige 16-1/4 in.W x 13-1/2 in.H x 5-3/4 in.D(413 mm x 343mmx146mm) 4081 series End-of-Line resistor harnesses;see data sheet 54081-0003 for details Page 2 54009-0002 Rev. 15 9/2019 1:3Simplex 4009 IDNet NAC Extender for Control with IDNet Communications or Conventional NACs Typical IDNet connection example I Typical IDNet compatible devices (Refer to individual devices for actual wiring • requirements,some wiring is not shown.) IDNet addressable communications channel, �_,.../shown Class B(Style 4) Output NACs,four standard, Conventional NAC operation (horns) eight with expansion option Select conventional or SmartSync 4007ES,4010,4010ES, operation per NAC 4100ES (shown),or4100U Fire Alarm Control Panel • • • -` � .•, SmartSync operation(horns and strobes) ,C09 Net NAL EXTENDER 4009 IDNet NAG Extender with J Th—� optional internal IDNet Repeater �' Conventional NAG Ioperation (strobes) Repeated IDNet Channel: 1 r_i.. . up to 100 devices maximum on repeater output, 250 devices total on IDNet Channel IDNet devices and additional 4009 IDNet NAC Extender(s) Figure 2: Typical IDNet connection example Note:Up to 10 4009 IDNet NAC Extenders may be connected using 4007ES,4010E5,4100U,or 4100ES IDNet channel,up to 5 on the 4010 IDNet channel.IDNet communications can be repeated only once(can pass through only one series connected repeater or one fiber optic receiver). Page 3 S4009-0002 Rev. 15 9/2019 Simplex 4009 IDNet NAC Extender for Control with IDNet Communications or Conventional NACs Typical fiber optic system connections Two fiber cables,3000 ft Output NACs 4090-9105,Class B (914 m)maximum distance €€€€€€€__€€__ - (Style 4)Output Fiber r1� IIIIIIINIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIINIIIIIIINIIIIIIIII Optic Transmitter rr IDNet addressable communications channel Class B(Style 4)or Class A (Style 6),Class B shown Repeated IDNet Channel:up to 100 devices maximum �NNINIIIIIIIIIIIIIIIINIIIIIIIIIIIINIIIIIIIINIII on repeater output,250 devices total on IDNet Channel Four fiber cables,3000 ft 4007ES,4010(shown), (914 m)maximum distance 4010ES,4100ES,or41000 Fire Alarm Control Panel 24 VDC power for fiber optic transmitters � ��� 4090-9107,Class A(Style 7) r4 Output Fiber Optic Transmitter - i ' 4009 IDNet NAC Extenders with optional Output NACs internal IDNet Fiber Receivers Figure 3: Typical fiber optic system connections Note:Up to 10 4009 IDNet NAC Extenders may be connected per 4007ES,4100E5,or 4010ES.Up to 5 4009 IDNet NAC Extenders may be connected on the 4010 IDNet channel.IDNet communications can be repeated only once(can pass through only one series connected repeater or one fiber optic receiver).Fiber optic transmitters connect to only one receiver in a 4009 IDNet NAC Extender. Hardwire Control Connection Information NAC Input Selections.The 4009 IDNet NAC Extender can be selected to: • •Track input NAC operation or to provide a locally generated code,selectable using NAC input. • If selected for local coding,NAC outputs can be either Temporal Coded or 60 Beats/min March Time Coded,one code selection per extender (input NACs must be on continuous with Alarm). •Additionally,NAC outputs can be selected to provide the Simplex strobe synchronization signal.This signal will synchronize the flashes of synchronized strobes but will be ignored by free-run strobes and audible devices.(Strobes are for operation by noncoded NACs.) NAC input to NAC output control can be selected for standard and optional NACs per the following table: Table 5:Conventional NAC Output Operation Options Input A B C NAC 1 NACs 1 and 2,S and 6 NACs 1 -4 NACs 1 -8 NAC 2 NACs 3 and 47 And ft NACs 5-8 Table 6:SmartSync NAC Output Operation Input NAC Control Function NAC 1 Strobe Control All NAC outputs(1 -8) NAC 2 Horn Control • Page 4 54009-0002 Rev. 15 9/2019 f3SimplEx 4009 IDNet NAC Extender for Control with IDNet Communications or Conventional NACs SmartSync Notification Appliance Control The TrueAlert Notification Appliance product line includes addressable and non-addressable operation.Non-addressable models are available with 2-wire SmartSync operation or conventional 4-wire operation.The following details apply to use with the 4009 IDNet NAC Extender: •TrueAlert non-addressable models with SmartSync operation allow audible notification to be separately controlled over the same wire pair that controls visible notification. •4009 IDNet NAC Extenders can be selected to provide SmartSync operation whether controlled by IDNet communications or conventional NACs. • IDNet control allows output NACs to be individually selected for conventional or SmartSync operation. - • With NAC input control,all output NACs are selected for either conventional or SmartSync operation. Refer to data sheet 54009-0003 for TrueAlert Addressable operation details,contact your local Simplex product supplier for further information on specific TrueAlert notification appliances. Hardwire control NAC connection cne-line reference diagram Up to eight(8)output NACs total;hardwire control can be selected to map NAC inputs to different combinations of NAC outputs depending on system requirements NAC 1 input (see Note 1) 1 di / 121 Conventional NACs I .. UJ With hardwire control, NAC outputs are all I Output conventional or all avaa NACs SmartSync operation 4009 IDNet NAC nv C - f Extender .. r Fire Alarm Control Panel — r with Conventional NACs SmartSync operation Class A operation,either mode,requires --I NAC 2 input 4009-9808 Dual Class A Adapter (optional,see Note 1) To additional 4009 IDNet NAC Extenders(up to four(4), 4009 IDNet NAC Extenders per NAC);see Note 2 Figure 4: Hardwire control NAC connection one-line reference diagram Note: 1. For separate audible and visible output NAC control,or SmartSync NAC output operation,2 input NACs are required.NAC 1 is"on-until-reset"and NAC 2 is'on-until-silenced". 2. To synchronize strobe flash outputs for up to 44009 IDNet NAC Extenders,use the synchronized strobe output from a Synchronized Flash Module (4905-9914 for Class B operation,4905-9922 for Class A operation)or,if available,from a NAC selected to provide synchronized strobe flash output.NOTE:DO NOT USE a NAC selected for SmartSync operation for this function. Refer to Installation Instructions 574-181 for additional information and application guidance. Page 5 S4009-0002 Rev. 15 9/2019 • f3SimpIEx 4009 IDNet NAC Extender for Control with IDNet Communications or Conventional NACs 4009 IDNet NAC Extender specifications Table 7:Input ratings Specification Rating 120 VAC input(4009-9201) 3A @ 102 VAC-132 VAC,60 Hz 240 VAC input(4009-9301) 1.5A @ 204 VAC-264 VAC,50 Hz/60 Hz 'Hardwire control from external NACs,input requirements Conventional reverse polarity operation 5 mA maximum,16 VDC to 33 VDC Table 8:Output ratings ,Specification Rating Total rating 8 A,Special application appliances 6 A,regulated 24 DC appliance power Standard NACs 2 A each,special application or regulated 24 DC appliance power Optional NACs(requires 4009-9807) 1.5 A each,Special Application appliances 1 A each,Regulated 24 DC appliance power Special application appliances Simplex non-addressable horns,strobes,and combination horn/strobes and speaker/strobes (contact your Simplex product representative for compatible appliances) Regulated 24 DC appliances Power for other UL listed appliances;use associated external synchronization modules where required Strobe operation Up to 33 strobes for each NAC can be synchronized;output NACs configured for Simplex synchronized strobe operation are synchronized to each other ,Auxiliary output 500 mA @ 24 VDC nominal Table 9:Optional modules ratings Specification Input power 70 mA @ 24 VDC,system supplied IDNet input,one address Maximum distance from IDNet source is 2,500 ft(762 m) IDNet Repeater Repeated IDNet output for up to 100 devices(total IDNet devices not to exceed 250 for Module each channel) (4009-9809) IDNet output specifications Maximum distance to farthest device is 2,500 ft(762 m) Total distance including"T-taps"is 10,000 ft(3048 m) Class A loop maximum distance is 2,500 ft(762 m),no"T"taps Table 10:Fiber optic receiver modules Specification Rating 4009-9811 ,Class X,80 mA @ 24 VDC,system supplied Input current 4009-9810,Class B,65 mA @ 24 VDC,system supplied IDNet output specifications Same as those for repeater module Fiber optic transmission distance 3000 ft(914 m)maximum Table 11:General specifications Specification Rating Operating temperature 32°F to 120'F(0°C to 49°C) Operating humidity range 10%to 90%RH from 32°F to 104°F(0°C to 40°C) Wiring Connections* Terminal blocks for 18 AWG(stranded)to 12 AWG(solid) Note:*Metric wire equivalents:18 AWG=0.82 mm2;12 AWG=3.31 mm2 Page 6 S4009-0002 Rev. 15 9/2019 g Simplex 4009 IDNet NAC Extender for Control with IDNet Communications or Conventional NACs Fiber optic transmitter specifications Table 12:Fiber optic transmitter specifications IptalSatiOn Rating Input voltage 118.9 VDC-32 VDC from compatible listed fire alarm supply Input current 4090-9105,Class B,30 mA @ 24 VDC 4090-9107,Class X,35 mA @ 24 VDC Multimode,graded index,50/125pm,62.5/125 pm,100/40 pm,or 200 pm Fiber optic connections and cable requirements Type ST connectors 4090-9105,Class B operation,two fiber cables required 4090-9107,Class X operation,four fiber cables required Module size(with mounting bracket) 6-13/16 in.W x 3-3/4 in.H x 1-1/8 in.D(173 mm x 95 mm x 29 mm) Green LED flashing=transmit On-board status indicators Red LED flashing=receive Separate red LED on 4090-9107=Class X receive Communications Simplex IDNet Fiber optic transmission distance 3000 ft(914 m)maximum Wiring connections* Terminal blocks for 18 AWG(stranded)to 12 AWG(solid) Operating humidity 10%to 90%RH from 32°F to 104°F(0°C to 40°C) Operating temperature 32°F to 120°F(0°C to 49°C) *Metric wire equivalents:18 AWG=0.82 mm2;12 AWG=3.31 mm2 • Page 7 54009-0002 Rev. 15 9/2019 f3SimplEx 4009 IDNet NAC Extender for Control with IDNet Communications or Conventional NACs 4009 IDNet NAC Extender mounting and module placement information Additional four point module shown model 4009-9807. Cabinet depth 16-1/4"(413 mm) .Itr 1-4.1/4"(108 mm)-I 10-29/32"(277 mm) (1 Door,5/8" —0 O I o WWW a (16mm)thick �y O I J^I:I _Cr'i �' r o __:1 I •le 8 [ '9 Optional Class A 4009-9807 Additional Four 13.112" adapter modules point module(shown with �+,! (343 mm) 0 s Class A adapters) e ® Exposed cabinet I I dimension for— -.-- ri ( System Module ) o elJlfL semi-flush mount f"t m 1"(25.4 mm), Knockouts for screw IONet repeater or j 1-3I8"(35 mm)wflh or nail mounting holes :Met optic receiver semi-flush trim 0 a ei 96' 8 O Ie • Oa 12'(305 mm) .a 0 �---- Battery location,no conduit entry or wiring in this area(12.7 Ah battery outline shown) m O 0 Semi-flush trim option Non-power limited wring area(AC input) 1-33/9"/16"(9.5 (30 mm), 3/8"(9.5 mm)thick — Wall surface reference for semi-flush mount Figure 5: 4009 IDNet NAC Extender mounting and module placement information Note:Recommended conduit entrance varies with module selection.Refer to general installation instructions 574-181,specific module installation instructions,and to field wiring diagrams 842-068 before locating conduit entrance. 4009 IDNet NAC extender cabinet with door detail Optional red appliqué (4009-9805 ) 0 4009 IDNet' NAC EXTENDER Simplex Figure 6: 4009 IDNet NAC extender cabinet with door detail Page 8 S4009-0002 Rev. 15 9/2019 f3SimplEx 4009 IDNet NAC Extender for Control with IDNet Communications or Conventional NACs 4090-9105/9107 IDNet fiber optic transmitter mounting information Surface mount box: --I, 0 0 0 0 0 0 Simplex model 2975-9217 (ordered separately) n n n n r Flush mount masonry box: / ` ' ' ` ' ` ' '/ - use 6-gang box, RACO#960,2-1/2"deep - o o o 0 0 0 (64 mm),or RACO#965,3-1/2"(89 mm) U U V t 1 f 1 ( 1 ( 1 deep,or equal (supplied by others) �rJ �J �l �J J - Flush mount ganged boxes: . . O use 6-gang box, 1-1/2"(38 mm) 1 7 • minimum depth;six, RACO#400 or equal,(supplied by others) [1 O O C'1 0 0 0 0 0 0 IDNet fiber optic transmitter: 4090-9107,Shown,Class A(Style 7)output 4090-9105,Not shown,Class B(Style 4)output INSTALLATION NOTE: Fiber optic cable bend radius should be 2"(51 mm) minimum,or per Manufacturer's specification. 0 0 0 0 0 0� Six-gang blank cover plate Mulberry Metal Products 97156 or equal(by others) Service diagnostic features Power-up self-diagnostics.Upon power-up,the 4009 IDNet NAC Extender tests each module and performs earth fault diagnostics.Trouble conditions are communicated to the host control panel and are also displayed on diagnostic status LEDs in the 4009 IDNet NAC Extender.When connected via IDNet communications,detailed status information is available at the host.When controlled with conventional NAC inputs,common ' troubles are signaled by providing a polarized open circuit that disconnects the NAC wiring from its end-of-line resistor but still allows a reversed polarity alarm to be received. Door mounted reference label.The 4009 IDNet NAC Extender has a detailed programming and diagnostic label inside the front door that provides • • a quick reference for both installation and checkout. LED Status Indicators are provided for the following: • Each NAC(standard and optional)has a dedicated yellow LED that: - During supervision provides a slow flash to indicate a short circuit condition and a fast flash to indicate an open circuit. - During an alarm,the LED follows the NAC output(on steady or flashing with coded output). • Four,general status yellow LEDs provide nine separate indications listed in priority of urgency.As a trouble is eliminated,any remaining trouble will then be indicated until the 4009 IDNet NAC Extender is returned to normal operation. •AC power status is indicated by a green LED that is on when AC is normal.During low AC(brownout)conditions or with no AC,the LED is off. Additional power and battery status is indicated by the general status LEDs. • Page 9 54009-0002 Rev. 15 9/2019 6 SimpIEx 4009 IDNet NAC Extender for Control with IDNet Communications or Conventional NACs 4009 IDNet NAC extender current calculation chart Step 1.Calculate the basic extender battery requirements(minus NAC loads) Panel,NAC Options,and Auxiliary Power(underlined model numbers are optional modules). ModelSupervisory Actual Description current supervisory Alarm current Actual alarm 4009-9201 120 VAC input Basic Panel 85 mA 85 mA 185 mA 185 mA 4009-9301 240 VAC input 4009-9807 Additional four point NAC 40 mA + 40 mA + 4009-9808 Dual class A adapter(no additional current) - - - - Auxiliary power output (500 mA + (500 mA maximum) maximum) +[Al] Basic panel supervisory current =[51] Basic panel alarm current - _[A2] Step 2.Calculate IDNet output module and device current(if used) 4009-9809 IDNet Repeater 70 mA 70 mA 4009-9810* Fiber Optic Receiver,Class B Select one for 65 mA + 65 mA + 4009-9811 * Fiber Optic Receiver,Class X each extender 80 mA 80 mA IDNet devices(connected to repeater or receiver above),0.7 mA each, Total devices x 0.7 Total devices x 0.7 maximum of 100 mA each + mA each + Note:IDNet Fiber Optic Transmitter current IDNet module supervisory current [52]=_ is supplied from the host fire alarm control panel IDNet module alarm current =[A3] Maximum available current =8 A* c Po 2.Calculate available W 4,c current Subtract auxiliary power output -[Al] Subtract IDNet module current -[A3] *8 A for special application appliances;6 A for regulated 24 DC appliances Available NAC current =[A4] Step 3.Calculate actual NAC loading(Limited to available NAC current per Step 2.) NAC type NAC circuit# NAC alarm current Circuit 1 - Standard panel NACS,2 A maximum for each NAC Circuit 2 Circuit 3 + . Circuit 4 + Circuit 5 + Optional four point NAC module,1.5 A maximum special application rating,1 A maximum Circuit 6 + regulated 24 DC rating,per NAC Circuit 7 + Circuit 8 + Total actual NAC load alarm current =[AS] Step 4.Calculate total supervisory current Total supervisory current=Basic panel current[S1]+IDNet Module current[52]_ • Step 5.Calculate total alarm current Total alarm current=Basic panel current[A2]+IDNet module current[A3]+actual NAC Current(A5]_ O 2019Johnson Controls.All rights reserved.All specifications and other information shown were current as of document revision and are subject to change without notice.Additional listings may be applicable,contact your local Simplex®product supplier for the latest status.Listings and approvals under Simplex Time Recorder Co. Simplex,and the product names listed in this material are marks and/or registered marks.Unauthorized use is strictly prohibited.NFPA 72 and National Fire Alarm Code are registerec trademarks of the National Fire Protection Association(NFPA). 54009-0002 Rev.15 9/2019 • B Sim plEx TrueAlert Multi-Candela Notification Appliances UL,ULC,CSFM Listed;FM Visible Notification Appliances with Synchronized Flash;Non-Addressable,SmartSync Approved;MEA(NYC) Operation Compatible Acceptance` Features Description .. u„ Multi-Candela TrueAlert synchronized strobes provide convenient installation to standard electrical boxes.The enclosure designs are both impact and vandal resistant and provide a convenient strobe intensity selection.Since each model can be selected for intensity output,on- • site model inventory is minimized and changes encountered during ""w"`J11Mi • ,l �"'�""'swbNt""JMre-�-• construction can be easily accommodated. Wall mount strobe housings are a one-piece assembly(including lens) FIRE ( that mounts to a single or double gang,or 4"square standard electrical • box.The cover can be quickly removed(a tool is required)and covers are Figure 1: Wall Mount Strobes available separately for color conversion. Ceiling mount strobes install using standard single gang electrical FIRE F I R E boxes.Color choice is determined by model number. E-, Strobe Intensity Selection During installation,a selection plug at the back of the housing determines the desired strobe intensity.An attached flag with black Figure 2: Ceiling Mount Strobes letters on a highly visible yellow background allows the selected intensity Visible only(V/O)24 VDC notification appliances with high output to be seen at the side of the strobe lens. xenon strobe,available for wall or ceiling mount: • Intensity is selectable as 15,30,75,or 110 candela with visible Strobe Application Reference selection jumper secured behind strobe housing Proper selection of visible notification is dependent on occupancy, • Operation is compatible with ADA requirements(refer to Installation location,local codes,and proper applications of:the National Fire Alarm Reference,Surfaceom or Semi-FlushtADWall Mounting) Code(NFPA 72),ANSI A117.1;the appropriate model building code: BOCA,ICBO,or SBCCI;and the application guidelines of the Americans • Polarized input allows connection to compatible reverse polarity, with Disabilities Act(ADA). supervised notification appliance circuit(NAC) • Regulated circuit design ensures consistent flash output and provides Synchronized Strobes controlled inrush current Multiple Strobes.When multiple strobes and their reflections can be • Rugged,high impact,flame retardant thermoplastic housings are seen from one location,synchronized flashes reduce the probability available in red or white with clear lens of photo-sensitive reactions as well as the annoyance and possible • Listed to UL 1971 and ULC 5526 distraction of random flashing.These multi-candela strobes are • NEMA 1 rated.See Product Selection for more information synchronized over a two-wire circuit when connected to compatible NACs,to compatible Synchronized Flash Modules,or to SmartSync Strobes provide synchronized flash for use with: Control Modules. • Simplex fire alarm control panels with NACs selected to provide strobe synchronization or SmartSync two-wire control SmartSync Two-Wire Control • 4009 IDNet NAC Extenders Some applications desire the audible notification appliances to be • Separate strobe Synchronization Modules that are available for Class B capable of being silenced before the alarm condition is reset(on-until- or Class A operation silenced)while the visible notification appliances are kept activated until • Separate SmartSync Control Modules(SCMs)that provide Class B or the alarm condition is reset(on-until-reset).SmartSync operation mode Class A output from conventional NAC inputs provides this function using a single circuit(two-wire operation). Strobe housings provides flexible,easy,and convenient semi- SmartSync Control Sources flush or surface wall mounting: SmartSync two-wire control is available from: • Rear of housing does not extend into box 4006,4007ES Hybrid,4008,4010,4010ES,4100E5,and 41000 Fire •Wall mount strobes easily mount to single gang,double gang,or 4-inch Alarm Control Panels(refer to individual product data sheets for more square outlet box nformation) • Ceiling mount strobes mount to single gang boxes 4009 IDNet NAC Extenders(refer to data sheet S4009-0002) SmartSync Control Module(SCM)Model 4905-9938(refer to data sheet Wall mount strobe features: S4905-0003) • Wiring terminals are accessible from the front of the housing providing Additional SmartSync compatible notification appliances include easy access for installation,inspection,and testing separate horns and combination horn/strobe notification appliances. • Covers are available separately to convert housing color For more information refer to installation instructions,579-548. Optional adapters and wire guards: • Wall mount strobe adapters are available to cover surface mounted electrical boxes and to adapt to 2975-9145 boxes • UL listed red wire guards are available for wall or ceiling mount strobes* 54906-0001 Rev.6 01/2020 f3Simplex Visible Notification Appliances with Synchronized Flash;Non-Addressable,SmartSync Operation Compatible Product Selection Table 1:Multi-Candela Visible Notification Appliances(Strobes) SKU Mounting Housing Color LetteringDescription 4906--9101 * ,Wall Red FIRE(white) Ho.4906-9103* White FIRE(red) 4906-9102* Red FIRE(white) 4906-9104* White FIRE(red) Multi-candela strobe with intensity selectable as:15,30,75,or 110 4906-9114* Red ALERT(white) candela;synchronized flash rate;SmartSync two-wire control compatible 4906-9115* Gelling White ALERT(red) 4906-9116* Red Blank(white) • 4906-9117* (White Blank(red) *NEMA 1 rated when used with 4095-9931 adaptor plate and 2975-9145 back box. Table 2:Wall Mount Strobe Adapters SKU Description Dimensions 4905-9937 Red Surface Mount Adapter Skirt;use to cover 1-1/2"(38 mm)deep surface 5-3/8"H x 5-1/4"W x 1-5/8"D(136 mm x 133 mm 4905-9940 White mounted boxes x 41 mm)Total depth with strobe=4 3/8"(111 mm) 4905 9931 ** Red Adapter Plate for mounting to Simplex 2975-9145 box(typically for retrofit, 8-5/16"x 5-3/4"x 0.060"Thick(211 mm x 146 may be mounted vertical or horizontal) mm x 1.5 mm) 2975-9145** Red Mounting Box,requires Adapter Plate 4905-9931 7-718"x 5-1/8"x 2-3/4"D(200 mm x 130 mm x 70 mm) **NEMA 1 rated. Table 3:Ceiling Mount Strobe Adapter SKU Description Dimensions 4905-991 D Surface Mount Adapter Plate;zinc plated:required for mounting to handy box,not 4-7/8"x 3-1/8"x 0.060"D(124 mm x 79 mm x 1.5) needed when using 4905-9926 guard Table 4:Synchronization Modules(refer to data sheet 54905-0003 for additional information) SKU Description - Dimensions 4905-9914 Class B Synchronized Flash Module;epoxy encapsulated with in/out 18 AWG 1-3/8"x 2-7/16"x 13/16"(35 mm x 62 mm x 20 4905-9922 Class A (0.82 mm2)wire leads,rated for 2 A NAC,requires 5 mA for power mm) 4905-9938 SmartSync Control Module with Class B or Class A output;mounts in 4"(102 mm) 4"x 4-1/8"x 1-1/4"D(102 mm x 105 mm x 32 square box mm) Table 5:Replacement Covers and Guards SKU Description Dimensions 4905-9992 Red cover with white"FIRE"lettering 5-1/8"H x 5"W x 1-1/2"D(130 mm x 127 mm x 4905-9993 White cover with red"FIRE"lettering For Wall mount strobes 38 mm) 4905-9961* Wall mount 6-1/16"H x 6-1/16"W x 3-1/8"D(154 mm x 154 Red wire guard with mounting plate,compatible with semi- mm x 79 mm) 4905-9926* Ceiling mount flush or surface mounted boxes 6-1/8"x 4-3/8"x 2-7/8"deep(156 mm x 111 mm x73mm) *UL listed by Space Age Electronics Inc. Page 2 S4906-0001 Rev.6 01/2020 EiSimplEx Visible Notification Appliances with Synchronized Flash;Non-Addressable, SmartSync Operation Compatible Strobe Specifications Table 6:Wall Mount or Ceiling Mount,Common Specifications Specification _ Rating - Rated Voltage Range 'Regulated 24 VDC;see Note 1 below Flash Rate 1 Hz Synchronized NAC Loading Up to 35 synchronized strobes maximum per NAC Temperature Range 32°to 122°F(0°to 50°C) Humidity Range 10%to 93%,non-condensing at 100°F(38°C) Connections Terminal blocks for 18 AWG to 12 AWG(0.82 mm2 to 3.31 mm2);two wires per terminal for in/ out wiring • Housing Dimensions(with lens) 5-1/8"H x 5"W x 2-3/4"D(130 mm x 127 mm x 70 mm) Wall Maximum RMS Current Rating per Strobe 15 cd 30 cd 75 cd 110 cd Mount Setting(see Note 2 below) 60 mA 94 mA 186 mA 252 mA Reference RMS Currents at 18 VDC 53 mA 84 mA 165 mA 224 mA other voltages 24 VDC 40 mA 63 mA 124 mA 168 mA Housing Dimensions(with lens) 4-3/4"L x 2-5/16"W x 2-5/8"D(121 mm x 75 mm x 67 mm) Ceiling Maximum RMS Current Rating per Strobe 15 cd 30 cd 75 cd 110 cd Mount Setting(see Note 2 below) 75 mA 125 mA 233 mA 316 mA Reference RMS Currents at 18 VDC .67 mA 111 mA 207 mA 281 mA other voltages 24 VDC i50 mA 83 mA 155 mA 211 mA Note: 1. "Regulated 24 VDC"refers to the voltage range of 16 to 33 VDC per UL Standard 1971,Signaling Devices for the Hearing Impaired.This voltage range is the absolute operating range.Operation outside of this range may cause permanent damage to the strobe.Please note that 16 VDC is the lowest operating voltage that is allowed at the last appliance on the NAC under worst case conditions. 2. The maximum RMS current listed is the device nameplate rating.Strobe designs are constant wattage and the maximum RMS current rating occurs at the lowest allowable operating voltage.(RMS is root mean square and refers to the effective value of a varying current waveform.) Installation Reference, Surface or Semi-Flush Wall Mounting Mounting is compatible withfil / \ o / O single gang,double gang,and 1 / 1 4"(102 mm)square boxes, IMPORTANT!WALL MOUNT 1-1/2"(38 mm)deep,by others_ r1 I ,IIIMMINfiEW INSTALLATION HEIGHT REFERENCE I \ ) d ( �� 1 Bottom of lens is either even �r•V with,or slightly Electrical —' ' \�) above bottom box outline Wiring access hole VI.,140,,,,i •,�_I � ' of compatible pi" ® 0�4, Aill boxes Wiring terminals ,I•II`(r .Ii 0� I -I� Mounting Holes: �'� a"square(4) NFPA 72 requires 80"(2.03 m) v. that the entire lens minimum �fli v II�� Single gang(2) be not less than • �I�I'I Double gang(3) I 80"and not greater than 96"above the finished floor Transparent housing • and lens assembly Intensity selection >o plug,accessible only '15 from rear of housing;(� ll El E E factory setting is 15 cd al Removable cover Strobe intensity (tool required) viewing slot • Page 3 S4906-0001 Rev.6 01/2020 9SimplEx Visible Notification Appliances with Synchronized Flash;Non-Addressable, SmartSync Operation Compatible Ceiling Mount Strobe Installation Reference Handy box, 1-1/2" ( 38 mm) deep Single gang box (Wiremold (RACO 650 or equal) or single gang V5744S) 2-1/4" (57 mm) box, 2-1/2" (64 mm) deep (RACO 519 • deep, supplied by others or equal) supplied by others Also can be attached to boxes ,/ mounted to drop ceiling T-bar with clips (ERICO No. 512 or equal) 0 U U Adapter Plate, required for surface mount with handy box unless 0 o using the wire guard I I I -1 _ _ _ Ceiling mount strobe 1111111111 j R ii' ' Optional wire guard ® ■ I with mountingI / ra umni �� IPate `• i, Strobe intensity l 4 , e viewing slot iii �O i _ Intensity selection plug, l ' accessible only from rear of lens housing; factory setting is 15 cd l , Note: 1. Figure shows 4905-9910 Adaptor Plate. 2. **4905-9926 Wire guard shown Page 4 S4906-0001 Rev.6 01/2020 0Simplex Visible Notification Appliances with Synchronized Flash;Non-Addressable, SmartSync Operation Compatible Wall Mount Installation Reference;Adapter Plate,Guard,and Adapter Skirt Surface Mounting Reference Box• with Optional Adapter Skirt and Optional Wire Guard MIIMM 0 Surface mount conduit and box shown for reference �.■��� ���___ box profile, 1-1l2" i iiil■I■Irl11ll, (38 mm)deep um (�/�.1. ��I O O I Optional ��I■ I r I Wire Guard Strobe A� ri r I t o =1L!I— ,-�rrook_ Adapter Plate t Optional Surface Mount Adapter Skirt, O Optional Wire Guard 1-1/2"deep: Red; White (shown here for reference only, (conduit knockouts Adapter Plate can be used on other mounting options) are provided on all four sides) Figure 3: Wall Mount Installation Reference;Adapter Plate,Guard,and Adapter Skirt Note: Figure 3 shows: •4905-9931 Adapter Plate • 2975-9145 Box •4905-9961 Optional Wire Guard • Optional Surface Mount Adapter skirt: - Red:4905-9937 -White:4905-9940 Page 5 S4906-0001 Rev.6 01/2020 f35implEx Visible Notification Appliances with Synchronized Flash;Non-Addressable, SmartSync Operation Compatible 2019 Johnson Controls.All rights reserved.All specifications and other information shown were current as of document revision and are subject to change without notice. Additional listings may be applicable,contact your local Autocall product supplier for the latest status.Listings and approvals under Tyco Fire&Security GmbH,and the product names listed in this material are marks and/or registered marks.Unauthorized use is strictly prohibited.NFPA 72 and National Fire Alarm Code are registered trademarks of the National Fire Protection Association(NFPA). S4906-0001 Rev.6 01/2020 fi®SimpIEX TrueAlert Multi-Candela Notification Appliances UL, ULC, CSFM Listed; FM Approved; SmartSync Operation Audible/Visible Notification MEA (NYC)Acceptance* with Horn and Synchronized Flash, Non-Addressable Features r____--- „,,.., U41111,kx ............ �J-1 Ssmi�kx Audible/visible(AN) notification appliances with efficient electronic horn and high output xenon i strobe,available for wall or ceiling mount • Operation is compatible with ADA requirements(refer .-.� to important installation information on page 3) • Rugged,high impact,flame retardant thermoplastic housings are available in red or white with clear lens Operates over a two-wire SmartSync circuit to F E RE ' provide: • Horns that are controlled separately from strobes on the FIRE same two-wire circuit • "On-until-silenced"and"on-until-reset"operation on �; �' the same two-wire pair • SmartSync horn activation of Temporal pattern,March ��� Time pattern(at 60 BPM),or on continuously FIRE • Strobe appliances on the same circuit operating at a ®— ,3���" synchronized 1 Hz flash rate — i • Class B operation requires connection to a compatible SmartSync NAC or to SmartSync Control Module (SCM)4905-9938 Wall and Ceiling Mount ANs • Class A operation when connected to the 4905-9938 Descri•tion SCM or with 4100U series fire alarm control panel NACs Multi-Candela TrueAlert ANs with horn and Wall mount ANs features: synchronized strobe provide convenient installation • Wiring A/V terminals are accessible from the front of the to standard electrical boxes.The enclosure designs are both impact and vandal resistant and provide a convenient housing providing easy access for installation, strobe intensity selection.Since each model can be inspection,and testing selected for strobe intensity output,on-site model • Covers are available separately to convert housing color inventory is minimized and changes encountered during • Available UL listed sound damper for locations construction can be easily accommodated. requiring attenuation of 5 to 6(IBA(stairwells,small Wall mount A/V housings are aone-piece assembly rooms,highly reverberant areas,etc.) (including lens)that mounts to a single or double gang,or Optional adapters and wire guards: 4"square standard electrical box.The cover can be • Wall mount A/V adapters are available to cover surface quickly removed(a tool is required)and covers are mounted electrical boxes and to adapt to Simplex available separately for color conversion. 2975-9145 boxes • UL listed red wire guards are available for wall or Ceiling mount ANs install using standard 4"electrical ceiling mount ANs boxes.Color choice is determined by model number. Visible notification appliance(strobe): Strobe Intensity Selection • 24 VDC xenon strobe;intensity is selectable as 15,30, During installation,a selection plug at the back of the 75,or 110 candela with visible selection jumper secured housing determines the desired strobe intensity.An behind strobe housing attached flag with black letters on a highly visible yellow • UL listed to Standard 1971 background allows the selected intensity to be seen at the • Regulated circuit design ensures consistent flash output side of the strobe lens. and provides controlled inrush current ' This product has been approved by The California State Fire Marshal(CSFM)pursuant to Audible notification appliance Section 13144.1 of the California Health and Safety Code.See CSFM Listing Pp (horn): 71250026:317 or allowable values and/or conditions concerning material presented in this • Low current,24 VDC electronic horn with harmonically document.Accepted for use-City of New York Department of Buildings—MEA35-93E. Refer pagemay rich sound output suitable for either steady or coded contact your local Simplex product supplier or the latestt sltattus.gListingsband approvals operation(Temporal or 60 BPM March Time pattern) under Simplex Time Recorder Co.are the property of Tyco Fire Protection Products. • UL listed to Standard 464 S4906-0002-6 11/2014 Strobe Application Selection SmartSync Two-Wire Control Proper selection of visible notification is dependent on SmartSync operation mode allows a two-wire circuit to occupancy,location,local codes,and proper applications provide the ability to activate both the horn and strobe on of:the National Fire Alarm Code(NFPA 72),ANSI the same NAC and then allow the horn to be silenced A117.1;the appropriate model building code:BOCA, while the strobe remains flashing.The horn operates as ICBO,or SBCCI;and the application guidelines of the "on-until-silenced"while the strobe operation is Americans with Disabilities Act(ADA). "on-until-reset." Synchronized Strobes SmartSync Control Sources Multiple Strobes.When multiple strobes and their • 4006,4007ES Hybrid,4008,4010,4010ES,4100ES, reflections can be seen from one location,synchronized and 4100U Fire Alarm Control Panels(refer to • flashes reduce the probability of photo-sensitive reactions individual product data sheets for more information) as well as the annoyance and possible distraction of • 4009 IDNet NAC Extender(refer to data sheet random flashing.The multi-candela strobes of these A/Vs S4009-0002) are synchronized by the controlling SmartSync operation • SmartSync Control Module(SCM)4905-9938(refer to NAC. data sheet S4905-0003) Additional SmartSync compatible notification appliances include separate horns and combination Product Selection horn/strobe notification appliances. Multi-Candela ANs Model Mounting Housing Color "FIRE"Lettering Description 4906-9127 Wall Red White _♦ 4906-9129 White Red Horn with Multi-Candela Strobe;strobe intensity selectable as: 4906-9128 Red White 15,30,75,or 110 candela;operates with SmartSync two-wire Ceiling control 4906-9130 White Red Wall Mount AN Accessories Model Description Dimensions 4905-9937 Red Surface Mount Adapter Skirt;use to cover 1-1/2"(38 mm)deep 5-3/8"H x 5-1/4"W x 1-5/8"D 4905-9940 White surface mounted boxes (136 mm x 133 mm x 41 mm) depth with strobe=4-3/8"(111 mm) 4905-9931 Red Adapter Plate for mounting to Simplex 2975-9145 box(typically for 8-5/16"x 5-3/4"x 0.060"Thick retrofit,may be mounted vertical or horizontal) (211 mm x 146 mm x 1.5 mm) 2975-9145 Red Mounting Box, requires Adapter Plate 4905-9931 7-7l8"x 5-1l8"x 2-3/4"D (200 mm x 130 mm x 70 mm) Optional Sound Damper;package of 20;field installed adhesive backed 4905-9838 horn output attenuator;reduces output 5 to 6 dBA 1-3/4"Diameter(44.5 mm) NOTE:After Sound Damper installation,measure sound level to ensure with 0.31"(8 mm)sound opening compliance with applicable code requirements SmartSync Control Module Model Description Dimensions 4905-9938 SmartSync Control Module with Class B or Class A output;mounts in 4" 4"x 4-1/8"x 1-1/4"D (102 mm)square box;refer to data sheet S4905-0003 for details (102 mm x 105 mm x 32 mm) Replacement Covers for Wall Mount ANs Model Description Dimensions 4905-9994 Red cover with white"FIRE"lettering 5-1/8"H x 5"W x 1-1/2"D 4905-9995 White cover with red"FIRE"lettering (130 mm x 127 mm x 38 mm) Wire Guards and Ceiling Mount AN Adapter Model Description Dimensions 4905-9961* Wall mount red wire guard with mounting plate,compatible with semi-flush 6-1/16"H x 6-1/16"Wx 3-1/8"D or surface mounted boxes (154 mm x 154 mm x 79 mm) 4905-9927* Red Wire Guard for mounting to flush mounted electrical box 8-1/2"x 6-1/8"x 3" (216 mm x 156 mm x 76 mm) 4905-9928* Ceiling Red Adapter Plate,required to mount guard to surface 9"x 7" Mount mounted electrical box (229 mm x 178 mm) 4905-9915 White Surface Mount Adapter Box Extension,use to cover 4-3/4"x 6-7/8"x 1-1/2"deep, 4905-9916 Red 1-1/2"deep surface mounted boxes (121 mm x 175 mm x 38 mm) *UL listed by Space Age Electronics Inc. 2 S4906-0002-6 11/2014 A/V Specifications Wall Mount or Ceiling Mount,Common Specifications Rated Voltage Range UL Listed Rating Regulated 24 DC;see Note 1 below ULC Listed Rating 20 VDC to 30 VDC per ULC 5526-M878 Flash Rate and Synchronized NAC Loading 1 Hz;with up to 35 synchronized strobes maximum per NAC Environmental;Temperature and Humidity 32°to 122°F(0°to 50°C);10%to 93%,non-condensing at 100°F(38°C) Connections Terminal blocks for 18 AWG to 12 AWG(0.82 mm2 to 3.31 mm2);two wires per terminal for in/out wiring Horn Output Characteristics 2400 to 3700 Hz sweep,modulated at 120 Hz rate • Horn Output Voltage 16 VDC 24 VDC 33 VDC Ratings Sound Type(see Note 2) Steady Coded Steady Coded Steady Coded @ 10 ft(3 m) UL 464 Reverberant Chamber 86 dBA 82 dBA 88 dBA 84 dBA 90 dBA 86 dBA (see Note 2) Anechoic Chamber 92 dBA 91 dBA 94 dBA 95 dBA 96 dBA 96 dBA Housing Dimensions(with lens) 5-1/8"H x 5"W x 2-3/4"D(130 mm x 127 mm x 70 mm) Wall Maximum RMS Current Rating per 15 cd 30 cd 75 cd 110 cd Mount Strobe Setting(see Note 3 below) 75 mA 116 mA 221 mA 285 mA Reference RMS Currents 18 VDC 67 mA 103 mA 196 mA 253 mA at other voltages 24 VDC 50 mA 77 mA 147 mA 190 mA Housing Dimensions(with lens) 4-3/4 L"x 6-7/8"W x 2-5/8"D(121 mm x 175 mm x 67 mm) Ceilin Maximum RMS Current Rating per 15 cd 30 cd 75 cd 110 cd g Strobe Setting(see Note 3 below) 86 mA 132 mA 250 mA 320 mA Mount Reference RMS Currents 18 VDC 76 mA 117 mA 222 mA 284 mA at other voltages 24 VDC 57 mA 88 mA 167 mA 213 mA NOTES: 1. "Regulated 24 DC"refers to the voltage range of 16 to 33 VDC per UL Standard 1971, Signaling Devices for the Hearing Impaired.This voltage range is the absolute operating range.Operation outside of this range may cause permanent damage to the appliance.Please note that 16 VDC is the lowest operating voltage that is allowed at the last appliance on the NAC under worst case conditions. 2. Coded values are typical of the output measured with a Temporal coded or a March Time coded pulse and with a sound level meter reading on a"fast"setting.Under the same test conditions,coded horn output"peak"sound level readings are typically 4 dBA higher. Anechoic horn output ratings are typically more representative of actual installed sound output. ' 3. Currents are with horn on steady.The maximum RMS current listed is the device nameplate rating.Strobe designs are constant wattage and the maximum RMS current rating occurs at the lowest allowable operating voltage.(RMS is root mean square and refers to the effective value of a varying current waveform.) Installation Reference, Surface or Semi-Flush Mounting Mounting is compatible with single gang,double gang,and 4"(102 mm)square boxes, IMPORTANT! WALL MOUNT 1-1l2"(38 mm)deep,by others ����'`��� INSTALLATION HEIGHT REFERENCE Optional 4905-9638 - r�� - r ' Sound Damper,field attached , Bottom of lens to attenuate sound 5 to 6 dBA -- is either even ,_ i I with,or slightly Electrical _o �� "� O above bottom box outline Wiring access hole Q %L( :' _ - of compatible—I:� © boxes Wiring terminals for I II p i i� i�7 I SmaASync operation 6�7 .;l Mounting Holes: i�, 4"square(4) NFPA 72 requires 80"(2.03 m) �."� mom . i;11 ' Single gang(2) that the entire lens minimum w r l Double gang(3) be not less than :���111111 80"and not greater ris than 96"above the Transparent housing finished floor and lens assembly Intensity selection 10 plug,accessible only '5 1 from rear of housing; 1® - r I] IR LE factory setting is 15 cd all Removable cover Strobe intensity (tool required) viewing slot • 3 S4906-0002-6 11/2014 1 Ceiling Mount A/V and Guard Installation Reference Ceiling reference, 4"(102 mm)square box, Optional 4905-9928 Adapter Plate, surface mounted box 1-1/2"(38 mm)minimum depth required for surface mounted electrical box Four mounting clamps included,two each side e. Ceiling reference, ' ^o� I / • 9pp MLys- r flush mounted box, ' �„ Optional 4905.9915/-9916 Adapter, L recommended for surface mounted box -� Optional 4905-9927 j — r../ /Wiring terminals are Red Wire Guard / f located behind the housing 0--- 11 F n E End View i Strobe intensity viewing slot / Intensity selection plug, \ accessible only from rear of lens housing;factory setting is 15 cd Wall Mount Installation Reference; Adapter Plate, Guard, and Adapter Skirt Surface Mounting Reference 2975-9145 Box with Optional Adapter Skirt 0 and Optional Wire Guard ♦11.7 Surface mount conduit and 0 Ell box shown for reference mammmmi 4" 102 mm) I�Ee %�il���1�1�I�� ^""�• �" box profile, � II�'I■II I�I'I1 I (I (38un __ � O O 40 WI:ElR=�11 � oa � WI: El 4905-9931 Adapter Plate —i Optional Surface Mount Adapter Skirt, O 4905-9961 Optional Wire Guard 1-1/2"deep:4905-9937,Red; (shown here for reference only, 4905-9940,White(conduit knockouts 4905-9931 Adapter Plate can be used on other mounting options) are provided on all four sides) TYCO,SIMPLEX,and the product names listed in this material are marks and/or registered marks.Unauthorized use is strictly prohibited.NFPA 72 and National Fire Alarm and Signaling Code are registered trademarks of the National Fire Protection Association(NFPA). 1351 m p I Ex Tyco Fire Protection Products•Westminster,MA•01441-0001•USA S4906-0002-6 11/2014 www.simplex-fire.com • ©2014 Tyco Fire Protection Products.All rights reserved.All specifications and other information shown were current as of document revision date and are subject to change without notice. ®Simplex System Accessories UL Listed* 4081 Series End-of-Line Resistor Harnesses Features • For use as Class B end-of-line resistor: • Connect these resistor harnesses where • end-of-line resistors are required at remote locations to monitor wiring continuity • Refer to specific circuit specifications for end-of-line resistor requirements UL Listed to Standard 864 Product Selection 9-1/2° (241 mm) Model Reference Description"* Number 4081-9001 733-892 2.2 kS2, 1/2 W 4081-9002 733-893 3.3 kS2, 1 W 4081-9003 733-896 4.7 kft, 1/2 W 4081-9004 733-886 6.8 kS2, 1/2 W 4081-9005 733-984 1.8 kfl, 1/2 W 4081-9006 733-890 560 12, 1 W 4081-9007 733-891 1.2 ki2, 1 W -- 4081-9008 733-894 10 kS2, 1/2 W 4081-9009 733-912 20 S2, 1 W IF I. 4081-9010 733-973 1 kg), 1 W 4081-9011 733-974 100 S2, 1/2 W 4081-9012 733-985 22 kS2, 1/2 W Typical 4081 Series Resistor Harness Assembly 4081-9013 734-086 4.99 kit, 1/2 W, ± 1% (full size except for lead length) 4081-9014 734-092 2.4 kf2, 1/2 W 4081-9015 734-093 1.5 kc1, 1/2 W 4081-9016 734-149 150 kit, 1/2 W Specifications 4081-9017 734-171 3.9 kS2, 1 W 4081-9018 734-168 10 kS2, 1 W Overall Length Approximately 9-1/2"(241 mm) **±5%tolerance except as noted. Wire Length 7"(178 mm)±1"(25 mm) Wire Size 18 AWG(0.82 mm2) Insulation 600 V, black Leads Stripped 0.5"(13 mm);tinned Resistor Resistor leads are crimped to wires Attachment and covered with heat shrink tubing This product was not approved by ULC,FM,MEA(NYC),or CSFM as of document revision date.Additional listings may be applicable,contact your local Simplex®product supplier for the latest status.Listings and approvals under Simplex Time Recorder Co.are the property of Tyco Safety Products Westminster. S4081-0003 7/2004 • Tyco.Simplex,and the Simplex logo are trademarks of Tvco International Services AG or its titillates in the US.and/or other countries. ©Simplex Tyco Safety Products Westminster•Westminster MA•01441-0001•USA S4081-0003 7/2004 www.tycosafetyproducts-usa-wm.com C 2004 Tyco Safely Prothrols Westminster.All rights reserved All specifications and otter information shown were crania as ofdocument revision dale and are subject to change without notice.