Report (2) . _ MS72o22 -ec2.22
8)26)6-cm/ 4le/zi--o c,1 !-1c/
VECTOR
)11
Er) G I n E E R s AIL 13 2'320
CITY OF Tlt a 9
VSE Project Number:U3054.0209.201
Ujl ®III ul�Ibi��
June 19,2020 �j
1 Solar
ATTENTION:Ty Church
2391 South 1560 West
Woods Cross,UT 84087
REFERENCE: Joe Harper Residence: 8205 Southwest Norfolk Lane,Tigard,OR 97224
Solar Array Installation
To Whom It May Concern:
Per your request, we have reviewed the existing structure at the above referenced site. The purpose of our review was to
determine the adequacy of the existing structure to support the proposed installation of solar panels on the roof as shown on
the panel layout plan.
Based upon our review,we conclude that the existing structure is adequate to support the proposed solar panel installation.
Design Parameters
Code:Oregon Structural Specialty Code,2019 Edition(2018 IBC)
Risk Category: II
Design wind speed: 120 mph (3-sec gust)per ASCE 7-16
Wind exposure category:B
Design snow load on roof:20 psf
Seismic design category:D
Existing Roof Structure
Roof structure:2x4 manufactured trusses G 24"O.C.
Roofing material:composite shingles
Roof slope:22.6°
Connection to Roof
Mounting connection: (1)5/16" lag screw w/min.2.5"embedment into framing at max.48"o.c. along rails
(2)rails per row of panels,evenly spaced;panel length perpendicular to the rails not to exceed 67 in
Conclusions
Based upon our review,we conclude that the existing structure is adequate to support the proposed solar panel installation.
The gravity loads, and thus the stresses of the structural elements, in the area of the solar array are either decreased or
increased by no more than 5%. Therefore, the requirements of Section 806.2 of the 2018 IEBC as amended by Section
3408.6 of the 2019 OSSC are met and the structure is permitted to remain unaltered.
6S1 W.Galena Park Blvd.,Ste. 101/Draper,UT 84020/T(801)990-1775/F(801)990-1776/www.vectorse.com
VSE Project Number: U3054.0209.201
O Joe Harper Residence
6/18/2020
E n G I fl E E R S
The solar array will be flush-mounted (no more than 6" above the roof surface) and parallel to the roof surface. Thus, we
conclude that any additional wind loading on the structure related to the addition of the proposed solar array is negligible.
The attached calculations verify the capacity of the connections of the solar array to the existing roof against wind (uplift),
the governing load case. Regarding seismic loads, we conclude that any additional forces will be small. Conservatively
neglecting the weight of existing wall materials, the installation of the solar panels represents an increase in the total weight
(and resulting seismic load) of 7.3%. Because the increase in lateral forces is less than 10%, this addition meets the
requirements of the exception in Section 806.3 of the 2018 IEBC.Thus the existing lateral force resisting system is permitted
to remain unaltered.
Limitations
Installation of the solar panels must be performed in accordance with manufacturer recommendations. All work performed
must be in accordance with accepted industry-wide methods and applicable safety standards. The contractor must notify
Vector Structural Engineering, LLC should any damage,deterioration or discrepancies between the as-built condition of the
structure and the condition described in this letter be found. Connections to existing roof framing must be staggered, except
at array ends, so as not to overload any existing structural member. The use of solar panel support span tables provided by
others is allowed only where the building type, site conditions, site-specific design parameters, and solar panel configuration
match the description of the span tables. The design of the solar panel racking(mounts,rails, etc.)and electrical engineering
is the responsibility of others. Waterproofing around the roof penetrations is the responsibility of others. Vector Structural
Engineering assumes no responsibility for improper installation of the solar array.
VECTOR STRUCTURAL ENGINEERING,LLC
Wells ,° Poi-
\ IN FRs/
9
Holmes r 93806PE
Digitally signed by Digitally Signed
OREGON
Wells Holmes
Date: 2020.06.19 �`4e ��2Y 10, 2°���
13:28:27 -06'00' 1 l ND ��
EXPIRES: 6/30/2021
06/19/2020
Wells Holmes,S.E.
Project Engineer
Enclosures
WLH/ych
651 W.Galena Park Blvd.,Ste. 101/Draper, UT 84020/T(801)990-1775/F(801)990-1776/www.vectorse.com
U305
JOB NO.: WIND 0RESS 1
SUBJECT: WIND PRESSURE
E n G I n E E R S
PROJECT: Joe Harper Residence
Components and Cladding Wind Calculations
Label: Solar Panel Array Note: Calculations per ASCE 7-16
SITE-SPECIFIC WIND PARAMETERS:
Basic Wind Speed [mph]; 120 Notes:
Exposure Category: B
Risk Category: II
ADDITIONAL INPUT & CALCULATIONS:
Height of Roof, h [ft]: 15 (Approximate)
Comp/Cladding Location: Gable Roofs 20°<0 5 27°
Enclosure Classification: Enclosed Buildings
Zone 1, 2e GCp: 1.5 Figure 30.3-2C (enter negative pressure coefficients)
Zone 2n, 2r, 3e GCp: 2.5
Zone 3r GCp: 3.6
a: 7 Table 26.11-1
zg [ft]: 1200 Table 26.11-1
Kn: 0.57 Table 26.10-1
Ke: 0.99 Table 26.9-1
Kzr 1 Equation 26.8-1
Kd: 0.85 Table 26.6-1
Velocity Pressure, qt, [psf]: 17.9 Equation 26.10-1
PRESSURES: p = qh (GCp)(yE)(ya) Equation 29.4-5
Zone 1, 2e, p [psf]: 32.2 psf(1.0 W)
Zone 2n, 2r, 3e, p [psf]: 53.6 psf(1.0 W)
Zone 3r, p [psf]: 77.2 psf(1.0 W)
(a = 4.5 ft)
V ECr 0 R E rl G I n E E R S JOB NO.: U3054.0209.201
SUBJECT: CONNECTION
PROJECT: Joe Harper Residence
Calculate Uplift Forces on Connection
Pressure Max Connection Max Trib. Max Uplift
(0.6 Wind) Spacing Area2 Force
(psf) (ft) (ft2) (Ibs)
Zone 1, 2e 19.3 4.0 11.2 216
Zone 2n, 2r, 3e 32.2 4.0 11.2 359
Zone 3r 46.3 4.0 11.2 430
Calculate Connection Capacity
Lag Screw Size [in]: 5/16
Cd: 1.6 NDS Table 2.3.2
Embedment3 [in]: 2.5
Grade: SPF (G = 0.42)
Nominal Capacity [Ibs/in]: 205 NDS Table 12.2A
Number of Screws: 1
Prying Coefficient: 1.4
Total Capacity [Ibs]: 586
Determine Result
Maximum Demand [Ibs]: 430
Lag Screw Capacity [Ibs]: 586
Result: Capacity> Demand, Connection is adequate.
Notes
1. 'Max Connection Spacing' is the spacing between connections along the rails.
2. 'Max Trib Area' is the product of the 'Max Connection Spacing'and 1/2 the panel width/height perpendicular
to the rails. (2) rails per row of panels. Length or panels perpindicular to the rails shall not exceed 67".
3. Embedment is measured from the top of the framing member to the beginning of the tapered tip of the lag
screw. Embedment in sheathing or other material is not effective.The length of the tapered tip is not part of the
embedment length.
U3054.
VECTOR
JOB NO.: GRAVITY
LOADS
1
SUBJECT: GRAVITY LOADS
E n G i n E E R 9
PROJECT: Joe Harper Residence
CALCULATE ESTIMATED GRAVITY LOADS Roof Pitch: 5.0 :12
Design material Increase due to Material weight
ROOF DEAD LOAD (D) weight [psf] pitch [psf]
Composite Shingles 2.2 1.08 2.0
1/2" Plywood 1.1 1.08 1.0
Framing 3.0 3.0
Insulation 0.5 0.5
1/2" Gypsum Clg. 2.2 1.08 2.0
M, E & Misc 1.5 1.5
Total Original Roof DL 10.4
PV Array DL 3.3 1.08 3
ROOF LIVE LOAD (Lr)
Existing Design Roof Live Load [psf] 20 ASCE 7-16, Table 4-1
Roof Live Load With PV Array [psf] 0 2019 OSSC, Section 1607.13.5
SNOW LOAD (S): Existing w/ Solar Array
Roof Slope [x:12]: 5.0 5.0
Roof Slope [°]: 23 23
Snow Ground Load, pg [psf]: 10 10 ASCE 7-16, Section 7.2
Terrain Category: B B ASCE 7-16, Table 7-2
Exposure of Roof: Fully Exposed Fully Exposed ASCE 7-16, Table 7-2
Exposure Factor, Ce: 0.9 0.9 ASCE 7-16, Table 7-2
Thermal Factor, CI: 1.1 1.1 ASCE 7-16, Table 7-3
Risk Category: II II ASCE 7-16, Table 1-1
Importance Factor, Is: 1.0 1.0 ASCE 7-16,Table 7-4
Flat Roof Snow Load, pf[psf]: 7 7 ASCE 7-16, Equation 7-1
Minimum Roof Snow Load, pm [psf]: 20 20 ASCE 7-16, Section 7.3.4
Unobstructed Slippery Surface? No No ASCE 7-16, Section 7.4
Slope Factor Figure: Figure 7-2b Figure 7-2b ASCE 7-16, Section 7.4
Roof Slope Factor, Cs: 1.00 1.00 ASCE 7-16, Figure 7-2
Sloped Roof Snow Load, ps [psf]: 7 7 ASCE 7-16, Equation 7-2
Design Snow Load, S [psf]: 20 20
NIECTOR JOB NO.: U3054.0209.201
SUBJECT: MEMBER FORCES
E 11 G I 11 E E R S
PROJECT: Joe Harper Residence
DESIGN LOADS FPSFI: Load Types: Snow Live Dead (D+S)/Cd (D+Lr)/Cd Max Load
Existing Roof 20 20 10 26 24 26
Proposed PV Array 20 0 13 29 15 29
(Cd=Load Duration Factor=0.9 for D, 1.15 for S,and 1.25 for Lr)
Label manufactured trusses
Length 44.75 Existing Proposed Check
M (ft-lb) 13242 13557 102% OK
Existing Proposed Check
V(lb) 1184 1241 105% OK
The gravity loads,and thus the stresses of the structural elements,in the area of the solar array are either decreased
or increased by no more than 5%.Therefore,the requirements of Section 806.2 of the 2018 IEBC as amended by
Section 3408.6 of the 2019 OSSC are met and the structure is permitted to remain unaltered.
Existing Loads (Distributed) LOAD(LB)
Add'I Add'I 80 - —EXISTING —PROPOSED
Live Dead
Roof Load Load Bm wt 60 - I I
Cond Trib(ft) (plf) (plf) (pif) wu(plf) woL(pIf) 40 -
1 2.00 0 0 0 34.8 18.1
20 -
Proposed Loads(Distributed) 0 . —
0 10 20 30 40 50
Dist to Length
Load 'a' of Load A wLL SHEAR(LB)
Cond (ft) 'b' (ft) (plf) A wog(plf) 2000 1
2 0.0 11.0 0.0 5.2 —EXISTING PROPOSED
3 33.8 11.0 0.0 5.2 1000
4 .#,.,
0
5 0 10 20 40 50
6 -1000
Proposed Loads as Point Loads -2000
Point Point MOMENT(FT-LB)
Live Dead 15000
Dist'a' Load Load ---EXI —PROPOSED
Cond (It) 'PLC'(lb) 'PDL' (lb)
7 10000
8 5000
9
10 0
11 0 10 20 30 40 50