Correspondence (5) a
City of Tigard, Oregon • 13125 SW Hall Blvd. • Tigard, OR 97223
•
January 26 2007 •
'FILE CCIPY C' �� " .,,
11
Coral Commons,LLC
Dean Greay
1905 SW 257th Ave
Troutdale, OR 97060
RE: CORAL COMMONS SINGLE FAMILY DWELLINGS- REVIEW#2
Project Information
Building Permit: 4 Building types Construction Type: 5B
Tenant Name: Coral Commons Occupancy Type: R3/U1
Address: Coral St. Stories: 2 / 1
Building type "A" Building type "B" Building type"C" 4 Garages/2 Breezeways
9352 SW Coral St. 9340 SW Coral St 9396 SW Coral St. 9304 SW Coral St.
MST2006-00261 MST2006-00262 MST2006-00259 BUP2006-00542
9360 SW Coral St. 9310 SW Coral St 9368 SW Coral St. 9322 SW Coral St
MST2006-00270 MST2006-00264 MST2006-00260 BUP2006-00541
9414 SW Coral St. 9316 SW Coral St 9328 SW Coral St. 9384 SW Coral St
MST2006-00258 MST2006-00265 MST2006-00263 BUP2006-00540
9420 SW Coral St 9346 SW Coral St. 9334 SW Coral St. 9408 SW Coral St
MST2006-00273 MST2006-00269 MST2006-00268 BUP2006-00539
9376 SW Coral St 9402 SW Coral St
MST2006-00271 MST2006-00272
The plan review is performed under the State of Oregon Residential Specialty Code (ORSC) 2005 edition
and the 2003 International Fire Code as amended by TVF&R. The following information is required in
order to complete the review. (ORSC 106.1.1)
1. Provide truss design information at location of furnace in attic on each building types with attic
furnaces.
RESPONSE NOT ACCEPTED 1/26/07—Truss pack submitted is the same pack as original
submittal. Please provide truss design as noted.
2. Provide foundation footing/stem wall construction details for each building type.
RESPONSE NOT ACCEPTED 1/26/07—The foundation stem and footing is missing the #4 at
48" oc vertical placements as required per ORSC section R403.1.4. Please provide foundation
footing/stem wall details as noted.
Phone: 503.639.4171 • Fax: 503.684.7297 • www.tigard-or.gov • TTY Relay: 503.684.2772
I
.a
3. Provide water heater closet construction details showing combustion air design for each building type.
RESPONSE NOT ACCEPTED 1/26/07—sheet Dl still notes gas water heater detail.
4. Provide stair construction details for each building type.
RESPONSE NOT ACCEPTED 1/26/07- Stair detail on sheet D1 still dose not meet code section
R312. Please provide detail as noted.
5. Provide smoke detectors in locations required per R313 missing in hall out side of bedrooms on each
building type.
RESPONSE ACCEPTED 1/26/07—Thank you for the revision
6. Provide 2 sets of plans for each building type with information noted above to established complete
sets. On the garage plans please include the breezeway construction.Also please provide 2 total
complete set of plans with all the revisions as noted above to be used as our city copy and fire
department copy. I believe you have had this conversation with Mark VanDomelen on this submittal
requirement.
RESPONSE ACCEPTED 1/26/07—Thank you for the revision
Please provide an item by item response.
When submitting revised drawings or additional information,please attach a copy of the enclosed City of
Tigard, Letter of Transmittal.The letter of transmittal assists the City of Tigard in tracking and
processing the documents.
Respec ,
ValI l; /3
Senior Plans Examiner