Loading...
Report Fire Alarm Control Panel 1 Battery Calculations Miain boards&PAD100 Devices model Qty standby total standby alarm total alarm fire alarm control panel IPA-4000 1 0.130000 0.130000 0.220000 0.220000 addressable loop expander SLCE-127 0 0.060000 0.000000 0.060000 0.000000 fire system annunciator 6500 1 0.020000 0.020000 0.050000 0.050000 manual alarm station PSSA 2 0.000200 0.000400 0.000200 0.000400 photoelectric smoke detector Po 47 0.000300 0.014100 0.000300 0.014100 heat detector HD 4 0.000300 0.001200 0.000300 0.001200 miniature monitor module MIM 0 0.000200 0.000000 0.000200 0.000000 monitor module SIM 0 0.000240 0.000000 0.000240 0.000000 dual input monitor module DIM 21 0.000240 0.005040 0.000240 0.005040 twin relay twin input module TRTI 4 0.000240 0.000960 0.000240 0.000960 duct smoke detector DUCTR 0 0.000500 0.000000 0.000500 0.000000 addressable relay module RM 12 0.000240 0.002880 0.000240 0.002880 I/O output 4 0.000000 0.000000 0.030000 0.120000 standby summary 0.174580 alarm sum 0.414580 standby time hours 24 panel total standby(All) 4.1899 N7 NB N9 N10 24VDC EVAC current device NAC model Qty Qty Qty Qty Qty Qty draw count strobe 15cd S 0 0 0 0 0 0 0.042 0 strobe 30cd S 0 0 0 0 0 0 0.058 0 strobe 75cd S 0 0 0 0 0 0 0.116 0 strobe 110cd S 0 0 2 1 0 0 0.161 3 WP speaker-strobe WSS 0 0 0 0 0 0 0.176 0 speaker/strobe 15cd SPKSTR 7 3 0 0 0 0 0.078 10 speaker/strobe 30cd SPKSTR 1 2 0 0 0 0 0.096 3 speaker/strobe 75cd SPKSTR 0 1 0 0 0 0 0.180 1 speaker/strobe 110cd SPKSTR 0 2 3 2 0 0 0.224 7 future 0 0 0 0 0 0 0.000 0 relay pam-1 0 0 0 0 1 0 0.030 1 0.642 1.054 0.994 0.609 0.030 0.000 3.3290 SLC&NAC Device Alarm 3.7436 Alarm Multiplied for 15 minutes alarm 0.2490 Total NAC Panel&Device Alarm(AH) 0.9322 Safety Factor Total System AH Total Standby Total Alarm Required AH Multiply by 1.2 Required Batteries Used 100. 4.1899 0.9322 5.1221 Times 1.2 6.1465 18AH Voltage-Drop Calculations(start voltage is 20.4 VDC,device operation range:16-33 VDC) total current draw 0.642 total current draw 1.054 N7 14 awg wire length in feet 485 NS 14 awg wire length in feet 560 voltage-drop 1.91181 voltage-drop 3.62407 voltage at last device 18.49 voltage at last device 16.78 total current draw 0.994 total current draw 0.609 N9 14 awg wire length in feet 130 N 10 14 awg wire length in feet 380 •7 voltage-drop 0.79341 voltage-drop 1.42092 voltage at last device 19.61 voltage at last device 18.98 total current draw 0.030 total current draw 0.000 24VDC 14 awg wire length in feet 375 EVAC Trip 14 awg wire length in feet 10 5th Floor voltage-drop 0.06908 voltage-drop 0 voltage at last device 20.33 voltage at last device 20.40 'moire Alarm Transmitter Battery Calculations total Device: Model Qty standby total standby transmitting transmitting fire alarm transponder 3G4010 1 0.200000 0.200000 0.400000 0.400000 standby summary 0.200000 standby time tours 24 total standby(AH) 4.800000 Total Transmitting 0.4000 Multiplied for fifteen minutes transmitting 0.2500 Total Alarm(AH) 0.1000 Safety Factor Total System AH Batteries Total Standby Total Transmitting Required AH Multiply by 1.2 Required Used 4.800000 0.1000 4.9000 Times 1.2 5.8800 7 AH P POTTER IPA-4000 The Symbol of Protection Fire Alarm Control Panel Features • 4,064 addresses available on this analog addressable system • Additional system capacity achieved via multi-point SLC modules • 1500 software zones • NFPA 72 Compliant Smoke Sensitivity Test Built-In `u•. • System Operates as Class A or Class B for SLC,P-Link and NACs _ rrrrn • I O Amp Power Supply,Expandable to 315 amps • 6 NACS,Regulated,Rated at 3 Amps each,expandable to 192 - • 4 Input/Output(I/O)Circuits for system flexibility rated at I Amp each, ideal for manual release and abort • Strobe Synchronization and System Wide Sync for Potter/AMSECO®, Gentex®,Cooper Wheelock®and System Sensor®strobes • Dedicated Alarm,Supervisory and Trouble Relays • 4,000 Event History Buffer • Cabinet will house up to 18 AH batteries • Optional two line DACT with UD-1000 that can report General,Zone or Point Information • Built in iP communicator LISTED • Ethernet Port for Programming and Network Connectivity • E-Mail System Status,Reports and Event Information • Product includes 5 year warranty Description Technical Specifications The IPA-4000 is an expandable analog/addressable releasing fire alarm Dimensions 18 x 27`/,'H x 47/ "D system with a total system capacity of 4,064 addresses. Additional capacity on the system is achieved using multi-point SLC modules AC Mains 5.0 Amps �t 120 VAC 50/60 HZ The control panel utilizes the exclusive Potter protocol that includes a 3.0 Amps a..240 VAC 50/60 HZ complete line of sensors and modules.The system is expandable with a 16 gauge cold rolled steel with removable total of thirty-one additional addressable Signaling Line Circuits(SLC) Enclosure locked door with Lexan viewing window each with a maximum of 127 devices.Each SLC may be comprised of any Standby Current-130 mA combination of smoke sensor,heat detectors or modules and allows for a Alarm Current-200 mA total of 50 ohms of impedance and may use any wire compliant with the • 10 Amps power for NACs,I/O,and P-Link National Electrical Code(NEC). • 3 Amps per NAC,regulated Battery The IPA-4000 has a 10 Amp power supply with six Notification • 1 Amp per I/O circuit,regulated Appliance Circuits (NACs) and four Input/Output (UO) circuits. The • Battery Charger range 8-55 Ah NACs are rated at 3 Amps each and the I/Os are rated at I Amp each. • Battery Charger voltage 27.3 VDC • Each output is regulated and power limited. In addition,each output is P-Link maximum current of 1 Amp uniquely programmable and may be configured for steady signal,strobe Temperature and 32°to 120°(0°C to 49°C)with a maximum synchronization, constant power, door holder power, or releasing. The Humidity Range humidity of 93%non-condensing. strobe synchronization includes Potter/AMSECO,Gentex,System Sensor • NFPA 12, 12A, 13, 15, 16, 17, 17A,70, and Cooper/Wheelock and with the exclusive Quadrasync each output may have a unique brand and all strobes will flash together.The I/Os are 72,750,and 2001 • designed for inputs such as manual release stations and abort switches that ANSI UL 864-Local(L),Remote Sta- tion(RS),Central Station(CS),Propriety will not require polling and react nearly instantaneously. (PPU),Auxiliary(AUX).Type of Service: The IPA-4000 is listed for releasing of fire suppression systems. The Automatic(A),Manual(M),Water flow Standards WF Sprinkler Supervisory(SS)Type of software allows cross zones,counting zones,and timers for suppression. (WF) P P ty YP The system is capable of multiple release outputs across multiple hazards. Signaling:Digital Alarm Communicator In addition,the PSN-1000 may be used to extend releasing capability. (DAC),March Time(March),Non Coded The NACs may be expanded using the PSN-1000 series intelligent power (NC),Reverse Polarity(Rev Pol),Other supplies.Each PSN-1000 adds another 10 Amps of power,2 additional Technologies(OT) input circuits and the IPA-4000 will support up to 31 power supplies.The • IBC 2000,2003.2006,2009,2012 system will synchronize the strobes system wide. In addition,the PSN- I000E has space to allow the installation of up to six PAD100-SLCE SLC loop expansion cards.The cards mount on a stacker bracket that allows access to all SLC circuit connections. Potter Electric Signal Company, LLC • St. Louis, MO • Phone: 800-325-3936 • www.pottersignal.com 8830102-REV A • 03/16 PAGE 1 OF'4 NP SERIES - NP18 -12 ` ' Data Sheet Reliability is your Security Utilizing the latest advance design Oxygen 1 Recombination Technology, Yuasa have applied their 80 years experience in the lead acid battery wi-',q field to produce the optimum design of Sealed t. '_"�'"� Lead Acid batteries. .�_; .6114° FEATURES R' • Superb recovery from deep discharge. g1:-4 • Electrolyte suspension system. . • Gas Recombination. t'cv. • Multipurpose: Float or Cyclic use. Terminals • Usable in any orientation. • Superior energy density. NP batteries are manufactured using a range of terminals which • Lead calcium grids for extended life. vary in size and type. Please refer to details as shown. • Manufactured World wide. an Operation in Orientation • Application specific designs. P Y The combination of sealed construction and Yuasa's unique Technical Features electrolyte suspension system allows operation in any orientation, with no loss of performance or fear of electrolyte Sealed Construction leakage. Yuasa's unique construction and sealing technique ensures no electrolyte leakage from case or terminals. Valve Regulated Design The batteries are equipped with a simple, safe, low pressure Electrolyte Suspension System venting system which releases excess gas and automatically All NP batteries utilize Yuasa's unique electrolyte suspension reseals should there be a build up of gas within the battery due system incorporating a microfine glass mat to retain the to severe overcharge. Note. On no account should the battery be maximum amount of electrolyte in the cells. The electrolyte is charged in a sealed container. retained in the separator material and there is no free General electrolyte to escape from the cells. No gels or other contaminants are added. Specifications Control of Gas Generation Nominal Capacity (Ah) NP18-12 The design of Yuasa's NP batteries incorporates the very latest 20hr to 1.75vpc 30°C 17.2 oxygen recombination technology to effectively control the generation of gas during normal use. lohrto 1.75vpc20°C 16 Low Maintenance Operation 5hrto1.70vpc20°C 14.5 Due to the perfectly sealed construction and the 1 hr to 1.60vpc 20°C 10.3 recombination of gasses within the cell,the battery is almost voltage 12 maintenance free. Energy Density(wh.L 20hr) 94 Specific Energy(wh.kg20hr) 38 Terminals Int.Resistance(m.Ohms) 11 Bolt fastened terminal E Maximum discharge(A) 112 Layout Short Circuit current(A) 500 1 4-12 : oR+ 2-. Dimensions (mm) ss INCH=MM 2 Length 180 III .472 12.00 - .453 11.50 Width 76 n, M "' .433 11.00 O O Height overall 167 NI • 1 .- 216 5.50 Weight(Kg) 6.2 079 2.00 — Terminal E �., Layout 2 Terminal Torque Nm www.yuasabatteries.com NP SERIES - NP18 -12 `e Data Sheet Lead Calcium Grids Long shelf Life The heavy duty lead calcium alloy grids provide an extra margin The extremely low self discharge rate allows the battery to be of performance and life in both cyclic and float applications and stored for extended periods up to one year at normal ambient give unparalleled recovery from deep discharge. temperatures with no permanent loss of capacity. Long Cycle Service Life Operating Temperature Range Depending upon the average depth of discharge, over a The batteries can be used over a broad temperature range thousand discharge/charge cycles can be expected. permitting considerable flexibility in system design and location. Float Service Life Charge —15°C to 50°C The expected service life is five years in float standby Discharge—20°C to 60°C applications. Storage —20°C to 50°C (fully charged battery) Separators The use of the special separator material provides a very efficient SELF DISCHARGE CHARACTERISTICS insulation between plates preventing inter-plate short circuits ,%,100 and prohibiting the shedding of active materials. ('C MT) CYCLIC RECHARGE REGIME _( SOM &lk Cnyga San40'/C/argp 0.3 - Ito♦ __ 1T 20 20.0 ) Z Tlm-.1 Gals.22 , 025 _ 1S5_ 10 D - NYC IfOA'1 ODO RO'FI 1 MANS Warne • L 25 y 0.2 -a100— �— u a W Cry-Vdupe .4 ¢0.14 - 15— IS 0 t¢i ' 1 6 9 1P 15 10 STOP AGE THE(MOMH5) 0 0.1 - SO— tamoTOp NM l.0.MC ANN 12 FLOAT CHARGE CHARACTERISTICS Mesa a aMma pp µ> 0 0 10 �`yB. i w,$ uyF RTe a d3ti§a. 025CA-2276VPC CONSTANT VOLTAGE CHARGING IIY NP DISCHARGE CHARACTERISTICS <%) ,.tA, M AT20'C(6S'F) CURVES AT 252C (772F) 100 130 'MVl lvI Nde:C.ONne-PsrM as MINI 4-d- NM ISO _CV4AD®VOWE____ ISO FOR ---- BATTERYBATTERY 10.0 03 SP AT NMITx'PH 100 0A0 -_ O 1_ CHARGE VOlTME NE 12.0- CO ---�'� u 0.15 SO W 0 1/ —AFTER I %0001UA6E ISO a 11.0- 5,5 ---AFTER 60%DISCHARGE Ilk10 0A0 i 1S• A 4ISA 60MI -,.7- -"3AlC. yo OM • .- �A euOA 0A0 I ____ CHAHGPuinMMCNi GA 0A- aA d 0 2 4 ev Am 0 0 w - - - a 10 16 IS CHARGING TIME(HOURS) 60- 4.0 0 I TYPICAL DISCHARGE CHARAC- 2 eo to IS 60 2 4 6 61'J 20 TERISTICS NP RANGE MONIES -1.%R10 DISCHARGE RUE CYCLE SERVICE LIFE IN RELATION FLOAT SERVICE LIFE NP RANGE TO DEPTH OF DISCHARGE TFSTNO OONgl10N5:DISCHARGE CURRENT: CAR IMMELL CHARGING CURRENT.O0OCAfro w CHARGING VOLUME:120%OP DISCHARGED CAPACITY COSOI (N'I%, TESING S, 2PC 10PF TOTYF)SMARM VOLTAGE:x215VPC FAM1(I E TEMPERATURE1 1MNN) AMSIENT TEMPERATURE:WPC TO xsr.l00'F TO Tx4) 120 AAlI '. 1N 1:7-"-- 800 go 3 ppA ` Fy�W yB . OOD 000 Of DISCHARGE QU 20 m yi 0 a 1 2 3 4 5 5.5 ° SOD 400 -o0 4o Hoe me RN LIFE(YEARS) NUMBER OP CYCLES 11F Yuasa Battery Inc. Distributed by 2901 Montrose Ave Laureldale, PA 19605 www.y u ass batte ri es.co m Y U ASA Registered number 1548820 Cat So. NP7-12 January 08 • P POTTER RA-65OOie The Symbol of Protection LCD Annunciator Features • Industry leading 4 line by 40 Character LCD • Common buttons for navigation • Common LEDs for status indication • 31 annunciator per panel • Maximum wire length of 6,500 feet • Available in 4 colors • Product includes a 5 year warranty MEI ( ' I•;.` LISTED Description Technical Spe • s The RA-6500 is a LCD remote annunciator for the PFC-6000 series Standby Current 20 mA fire control panels. The RA-6500 communicates using a RS-485 connection to the main panel providing common indication of Alarms, Alarm Current 25 mA Supervisory,Trouble and other system status and control functions. Operating Temperature ° -4 °C 2°F-120°F) The RA-6500 features a 4x40 LCD display with LED's for Power. 10%93%(u�30°C(86°F)non Alarm, Supervisory, Trouble, and Silenced conditions. It can be Operating Humidity Range condensing humidity mounted on a single gang electrical box or a four square electrical box. Maximum Wire Length 6500 ft. The annunciator is enclosed in a sheet metal enclosure and has a Potter lock securing the keypad. Maximum Annunciators 31 Size(WxHxD) I O"x 7-7/8"x 1-5/8" Wire Gauge 14 AWG-22 AWG Potter Electric Signal Company, LLC • St. Louis, MO • Phone, 800-325-3936 • www.pottersignal.com 8830113-REV A • 04/16 PAGE 1 OF 3 P POTTER RA-65001 The Symbol of Protection LCD Annunciator Dip Switch Settings Refer to the table below for dip switch settings per Annunciator Address. Annunciator Dip Switch Settings Annunciator Dip Switch Settings Address SW-1 SW-2 SW-3 SW-4 SW-5 Address SW-1 SW-2 SW-3 SW-4 SW-5 1 On Ott' Off Off Off 17 On Off Off Off On 2 Off On Off Off Off 18 Off On Off Off On 3 On On Off Off Off 19 On On Off Off On 4 Off Off On Off Off 20 Off Off On Off On 5 On Off On Off Off 21 On Off On Off On 6 Off On On Off Off 22 Off On On Off On 7 On On On Off Off 23 On On On Off On 8 Off Off Off On Off 24 Off Off Off On On 9 On Off Off On Off 25 On Off Off On On 10 Off On Off On Off 26 Off On Off On On 11 On On Off On Off 27 On On Off On On 12 Off Off On On Off 28 Off Off On On On 13 On Off On On Off 29 On Ott' On On On 14 Off On On On Off 30 Off On On On On 15 On On On On Off 31 On On On On On 16 Off Off Off Off On Ordering Information Model Description Stock No. RA-6500 LCD Annunciator-RED 3992660 RA-6500 LCD Annunciator-SLACK 3992744 RA-6500 LCD Annunciator-GRAY 3992745 RA-6500 LCD Annunciator-LIGHT GRAY 3992746 Potter Electric Signal Company, LLC • St. Louis, MO • Phone: 800-325-3936 • www.pottersignal.com 8830113-REV • 04/16 PAGE 3 OF 3 P POT TER 4 PAM0 The Symbol l of Protection MULTI-VOLTAGE RELAY MODULE • Single SPDT relay with LED • Double-sided adhesive tape ` _" •Mounting screw Sf• a- r ..x.,.. \ • 12" leads l 2 : i •6 wire nuts Power Requ lerr enls:Per position-0.015 Amps @ 24VDC,24VAC,115VAC Relay: UL recognized SPDT Contact Rating: 10 Amps @ 115 VAC 0 7Amps a 28VDC 250 Microamps @ 5VDC Stock number: 1000262 AmbientTempelature: 32°F to 120°F(0°C to 49°C) Approvals: UL Listed Dimensions: 1.5"(38.1 mm)H x 1"(25.44 mm)W x 0.875"(222MM)D 12"(304.8mm)18 ga.wire leads Product Description The PAM-1 Relay is an encapulated 24VDC multi-voltage device These devices are ideal for applications where remote relays are providing 10.0 Amp form C contacts. The relay may be energized by required for control or status feedback. They are suitable for use with one of three input voltages:24 VAC,24 VDC,or 115 VAC. HVAC,temperature control,fire alarm,security,energy management, A red LED is provided which,when illuminated,indicates the relay and lighting control systems. coil is energized. The PAM-SD may be mounted by using the double-sided adhesive tape,the self-drilling screw,or loosely placed in an electrical backbox. Installation Wiring RELAY ENERGIZED LED I'6 ©© _.WHT rV e BLUE i. 0 AMP/// ��© BLK • YEL N.C. CONTACTS MOE RED , i ORG N i 115 VAC g 0.015A --- 24 VAC-4-.0.015 A 24 VDC 0,0.015 A Potter Electric Signal Company•2081 Craig Road,St.Louis,MO,63146-4161 •Phone: 800-325-3936/Canada 888-882-1833•www.pottersignal.com PRINTED IN USA MFG.#5401102-REV C PAGE 1 OF I 9/07 - NPSERIES - NP7 -121 Data Sheet Reliability is your Security IIIIIIIIIIUtilizing the latest advance design Oxygen Recombination Technology, Yuasa have applied their Nam?" 80 years of experience in the lead acid battery field to , II�'t '"" " " produce the optimum design of Sealed Lead Acid VUASA ' ..ram, batteries. '� FEATURES • Superb recovery from deep discharge. • Electrolyte suspension system. Terminals • Gas Recombination. NP batteries are manufactured using a range of terminals • Multipurpose: Float or Cyclic use. which vary in size and type. Please refer to details as • Usable in any orientation • Superior energy density. shown. • Lead calcium grids for extended life. Operation in any Orientation • Manufactured World wide. The combination of sealed construction and Yuasa's • Application specific designs. unique electrolyte suspension system allows operation in Technical Features any orientation,with no loss of performance or fear of Sealed Construction electrolyte leakage. Yuasa's unique construction and sealing technique Valve Regulated Design ensures no electrolyte leakage from case or terminals. The batteries are equipped with a simple, safe low Electrolyte Suspension System pressure venting system which releases excess gas and All NP batteries utilize Yuasa's unique electrolyte suspension automatically reseals should there be a build up of gas system incorporating a microfine glass mat to retain the within the battery due to severe overcharge. Note. On no maximum amount of electrolyte in the cells.The electrolyte is account should the battery be charged in a sealed retained in the separator material and there is no free container. electrolyte to escape from the cells. No gels or other General Specifications contaminants are added. Control of Gas Generation Nominal Capacity (Ah) NP7-12 The design of Yuasa's NP batteries incorporates the very latest Layout 20hr to 1 .75vpc 30°C 7 oxygen recombination technology to effectively control the 1 Ohrto 1 .75vpc20°C 6.4 generation of gas during normal use. 4 O 5hr to 1.70vpc 20°C 5.9 Low Maintenance Operation 1 hr to 1 .60vpc 20°C 4.2 Due to the perfectly sealed construction and the 8 voltage 12 recombination of gasses within the cell,the battery is Energy Density min 1..sonr7 91 almost maintenance free. Specific Energy mn.kgsohp 32 Terminals Int.Resistance(m.Ohms) 25 Maximum discharge(A) 40/75 Faaton tab:187 A Faston tab:250 D Short Circuit current(A) 210 Dimensions (mm) .fay.o0 IMCN-=MM 2.50`031. °a' JNC'u=MM • .250 6.35 I- .310 7.9O Length 151 QS9 r .185 4.70 .250 6.35 Width 65 um --- .124 3.15 .16 4.0 .098 2.50 .0.31 0.8 Height overall 97.5 �� ,059 1.5D s ' .020 0.5 Weight(Kg) 2.65 .031 O.sa I I .020 0.50 --.I Terminal A/D -•II Ili .004 D.1D mii.ow Layout 4 03r Terminal Torque Nm - www.yuasabatteries.com NP P POTTER PVX-150 & PVX-200 The Symbol of Protection Voice Evacuation System 1 Features • Clean Dead-front Construction • Digitally Recorded Automatic Evacuation Message 11, (Up to 20 Minutes of Message Capacity) 4 • 50/100 Watt Bullet-Proof Amplifier 1 . �.:... • 25 or 70 VRMS Field Selectable • Class A/B Speaker Circuit • 120 VAC Power Supply and Battery Charger • Live Microphone Override of Message and Tone • • Analog Addressable Compatible • High Reliability,No Maintenance,Fully Supervised • Easy Installation and Operation • Studio Quality Voice Recordings • Built in Alarm and Alert Signals • Works with 12 VDC or 24 VDC Fire Alarm Panels • Works with Microprocessor based and Network Fire Alarm Systems • 3 Minute Message Restart on Microphone Key • 24 Hour Backup with 12V 7AH Batteries LISTED • Made in the USA S25376 6911-0328:0219 Description Technical Specifications The PVX-200/PVX-150 panels provide 200W and 150W of speaker Specifications are given per module: power respectively.Speaker zones can be configured for general alarm or alarm by zone operation as required. Digital message repeater, PVX-50-50 watt module microphone, 120 VAC power supply and battery charger are all built Primary Power 120VAC 40.8A in.The PVX Series voice evacuation can be configured for Churches, 0.15A Standby Restaurants.Movie Theaters,Auditoriums,and High Rise buildings. 24VDC Battery Power .80A Alarm Output 50 Watts`4 25/70 VRMS The paging microphone is an integral component removal of the microphone will cause a"Trouble"condition which will be reporting PVX-100- 100 watt module locally, as well as through the FACP. The PVX-150 / PVX-200 is Primary Power 120VAC 4P0.8A housed in a surface or semi-flush mounted backbox with a hinged and 0.16A Standby key locked door. 24VDC Battery Power I.1 A Alarm Output 100 Watts a 25/70 VRMS Backbox Dimensions(WxHxD) 14.5 x 27 x 4" Color Red(standard)Charcoal Grey (optional) Potter Electric Signal Company,LTC • St. Louis,MO • Tech Support: 866-956-1211 /Customer Service: 866-572-3005 • www.pottersignal.com 8830044-REV B • I2/14 PAGE I OF 2 • P POTTER PVX-1 50 & PVX-200 The Symbol of Protection Voice Evacuation System Typical Installation Fire 0 NAC j Alarm 0 Strobe _Li Circuits Control 0 NAC (Notification Appliance Circuit) I �II —1 EOLR Panel Q NAC ' Speaker Circuit EOLR Supervised-Power Limited 120 VAC _ III EOLR i I110111 Speaker Circuit EOLR Supervised-Power Limited • It ^CCTTCCIC rEEEE 11.1 Standard Message- 15 Seconds: 111- o -- ' "Attention Please,there has been a report 0 of an emergency. o 0 - Proceed calmly to the nearest exit and leave the building immediately. Do not use the elevators,use stairwells where necessary. All handicapped occupants shall use the [Emma asaers6: building evacuation plan." 12V -0 12V -D 12V -❑ 12V -❑ Battery+o Battery+O Battery+o Battery+o Ordering Information Optional Components Stock • PVX-ZM Zone Module 4-Class B/2-Class A Circuits Model Number Number Description • PVX-SL8 8 Switch/LED Card 150W Voice Evacuation System with: • PVX-1L8 8 Input/LED Card PVX-150/8Z 3500007 Power Supply/Battery Charger • PVX-OL8 8 Output/LED Card • Paging Microphone • PVX-RM/SC Remote MIC/Supervisory Card PVX-150/12Z 3500008 • Digital Message Repeater • 8 Speaker Zones(8Z) Engineering Specifications • 12 Speaker Zones(12Z) The voice evacuation system shall be Potter PVX 150/200 or approved PVX-150/16Z 35(10(109 PP • 16 Speaker Zones(16Z) equal. The voice evacuation system shall provide 150/200 Watts of 200W Voice Evacuation System with: signal and voice power,and shall be UL listed.All speaker circuits shall PVX-200/8Z 3500010 be field selectable for 25 or 70 VRMS operation and shall be power Power Supply/Battery Charger limited. The voice evacuation shall he micro-processor based, and • Paging Microphone shall contain an integral microphone, audio amplifer, tone generator Digital Messageand digital message repeater.A 120 VAC Power Supply and battery PVX-200/I2Z 3500011 g Repeater charger for standby shall be included. The voice evacuation message/ • 8 Speaker Zones(8Z) signal shall be broadcast until the FACP is reset,or until fire emergency • 12 Speaker Zones(12Z) personnel interrupt the broadcast with a manual page.Remote paging PVX-200/16Z 3500012 microphone(s)will be supported through a supervised circuit. • 16 Speaker Zones(16Z) Potter Electric Signal Company,LLC • St. Louis, MO • Tech Support: 866-956-1211 /Customer Service: 866-572-3005 • www.pottersignal.com um soot soos DESIGNING,MANUFACTURING, CERTIFIED I&DISTRIBUTING QUALITY SYSTEMS 8830044-REV B • 12114 PAGE 2 OF 2 P POTTER Pvx The Symbol of Protection Voice Evacuation Panels Accessory Cards PVX Accessory Cards • PVX-ZM-Supervised Zone Module • PVX-SLB-LED Switch Card • PVX-IL8-LED Input Card 6 • PVX-01,8-LED Output Card ;A P.• ,.• • • All cards connect and communicate over 10 pin ribbon cable n. - • Up to 16 total cards per panel in any combination PVX-Z:11 PVX-SI.8 PVX-11,8 PVX-OL8 LISTED S25376 PVX-ZM � '.� f� Stock Number:3510014 '• • +9R a og1 Supervised Zone Module ,- *E • Current draw(24VDC input):51mA(Standby), 130mA(All Call) •� „me • 4 Class B or 2 Class A speaker circuits(Field selectable) • 25/70 Vmts Field selectable n 8o • Compatible with PVX-SLB for zone selection E3.190.!, 3' TIII a t pas,. PI , M- M'f• q • Circuits rated up to 50W u'70V and 40W @ 25V * • Circuits rated up to 50W n 70V and 40W @ 25V ° i The Potter PVX-ZM Supervised Zone Module is used in conjunction Q an"-, '�� with the PVX Series Voice Evacuation Panels to provide separately - . supervised and protected circuits from a single speaker output. The p �1 EVX-ZM is default configured for 4 Class B circuits, but may be � ��,® at�• s converted to 2 Class A with the flip of a switch.The PVX-ZM can be ��t ro. ganged together to provide a maximum of 64 Class B circuits. _; , : . ; -.. The PVX-ZM in standard operating mode is strictly All Call. On P3 . '. ' .. :.• ' Rev Ele..:• any page,alarm,or message function all circuits activate. If separate zoning is required,the PVX-ZM has zone selection inputs which may © a4 be activated by a N.O.dry contact. Additionally.the PVX-SL.B(LED s s ' Switch Card) maybe employed to provide both Zone and Message pq �©'�©®� a,` selection by switch. 1^` t� re3 Each speaker circuit employs smart power metering to insure short circuit conditions are isolated from the other circuits. Each circuit is rated 50W(�70V and 40W r,25V. Potter Electric Signal Company,LLC • St. Louis,MO • Tech Support: 866-956-1211 /Customer Service: 866-572-3005 • www.pottersignal.com 8830072-REVA • 4/15 PAGE 1 OF 2 P POTTER PVX ® The Symbol of Protection Voice Evacuation Panels Accessory Cards PVX-SL8 Stock Number:3510015 • • LED Switch Module Current draw(On primary module battery back-up): 3mA(Standby), . 5.I6mA(All Call) II" ilin • 8 Momentary switches • 8 Tri-color LED's(green/red/amber) .. • Programmable for multiple functions - a The Potter PVX-SL8 LED Switch Module provides switch selection 3 for message activation,paging,and control functions. : al • When used in conjunction with the PVX-ZM zone module,the Sl.8 ,a can be programmed for page zone control.LEDs for switches assigned , . to page zones will indicate Red for page and flashing Red for alarm. PR 1, The LED will indicate Amber if the associated speaker circuit is in a fault condition. - Switches can be programmed to control corresponding points on the PVX-OL8. Switch LEDs will indicate steady Red on activation. PVX-IL8 - Stock Number:3510016 ■ . IL8 LED Input Module I - 0: - AID O O Current draw(On primary module battery back-up): 3mA(Standby): •i ! . •,Or:5.2mA(All Call) • .'�ftt . - 1i i • 8 Input points •: • 8RedLED's * ;' E12 I O *` • Programmable for multiple functions • . i a , , 11,,,, * The Potter PVX-IL8 LED Input Module can be used for page zone t 0 t+ O,t }G �, control, message selection, and control functions. The inputs monitor an external ND dry contact. PVX-IL8's are typically used Ea :: : : • for message/zone activation from an outside system such as Severe Weather Warnings. They can also be used to activate corresponding D ' outputs on the PVX-OL8. On activation,the corresponding LED will ■ O _4" * 0 �' indicate red. 0 ♦ SAS O PVX-OL8 v Stock Number: 35I0017 • ._ �• aa: LED Output Module 'is"'- : • - Q•Ot rt. :' Current draw(On primary module battery back-up): 3mA(Standby), clerkr ? • , 28mA(All Call) MIMI o,,, • 8 Input points I II Vi -[�@y 'I • ••• A/Ol yIMvtrIii I • • 8 Red LED's • N.O.Dry contacts rated at 30mA,fir 0-24VDC ,• •„ :. s'sud_ ^" r • The PVX-OL8 LED Output Module provides solid state N.O. dry 1 't • Y�� o I / • contacts. It can also be separately tied to a voltage(0-24VDC),with " "- t�t - !. + a s I I wwsir'E. a felleAs F'', •' that voltage used as a drive point or trigger. Outputs 1-4 and 5-8 may R ..•` .a= use different voltage references if desired. The PVX-OL8 outputs may aPu r.•a ► be programmed to follow message activation,page zones,or specific functions like PTT,alarm,or control. Potter Electric Signal Company, LLC • St. Louis, MO • Tech Support: 866-956-1211 /Customer Service: 866-572-3005 • www.pottersignal.com Iso 9001:2008 DESIGNING,MANUFACTURING, CERTIFIED I&DISTRIBUTING QUALITY SYSTEMS 8830072-REV A • 4/15 PAGE 2 OF 2 I P POTTER S-24 & HS-24 SELECTABLE CANDELA The Symbol of Protection STROBE & HORN/STROBES Features • 24VDC units have field selectable candela options of 15,30,60, 75,& 110 • Super-Slide®Bracket-Ease of Supervision Testing • Checkmate®-Instant Voltage Verification • Synchronize strobe and/or horn with AVSM Control Module • Prewire entire system,install mounting bracket,then install n,_ signals • Documented lower installation and operating costs IOW 1 Input terminals accept 12 to 18 AWG • Switch selection for high or low dBA Switch for chime,whoop,mechanical and 2400Hz tone R a p • Tamperproof re-entrant style grill ` — C I I I • Switch for continuous or temporal 3 tone(not available on whoop tone) • Surface mount with the AVBB(Surface Mount Back Box) • Silence audible while visual appliance will remain flashing(for use in accepted jurisdictions) • Faceplate available in red or off-white Operating Temperature • 32°F to 120°F(0°C to 49°C).The HS and S Series are not listed for outdoor use. Unit Dimensions • 5"(12.7 cm)high x 4.5"(11.43 cm)wide x 2.5"(6.35 cm)deep 1;131 LISTED S3247 Description The S-24/HS-24 Series is a low profile strobe and horn/strobe This Series is shipped with a standard 4" metal mounting combination that offers dependable audible and visual alarms and the plate which incorporates the popular Super-Slidee feature that allows absolute lowest current available. the installer to easily test for supervision.The product also features a locking mechanism which secures the product to the bracket without The S-24 & HS-24 Series 24VDC offers tamperproof field any screws showing. selectable candela options of 15,30,60,75,and 110 candela. The S-24/HS-24 also features the patented Checkmate® - The Strobe and Horn/Strobe offers a continuous or sync Instant Voltage Verification feature which allows the installer to check temporal three in 2400Hz and mechanical tone, a chime and whoop the voltage drop draw and match it to the blueprint. tone.All tones are easy for the professional to change in the field by the use of switches. The S-24& HS-24 Series appliances are ANSI/UL 464 and ANSI/UL 1971, listed for use with fire protective systems and are The S-24 & HS-24 Series has a minimal operating current warranted for three years from date of purchase. and has a minimum flash rate of 1Hz regardless of input voltage. Potter Electric Signal Company,LLC•St.Louis,M0 63042 USA.CustService:866-572-3005•Tech Support:866-956-0988-Canada888-882-1833•www.pottersignal corn PRINTED IN USA MFG.48830054-REV A PAGE I OF 4 06/13 I PPOTTER S-24 & HS-24 1' �,j� SELECTABLE CANDELA a The Symbol of Protection STROBE & HORN/STROBES Tone Switch Locations SWITCH POSITION TONE /■ 3 4 5 [ • •ub Mechanical Temporal 3 ON ON ON EE ,• MN p ,"r Mechanical-Continuous OFF ON ON �wM MN Tht S+—dal 1.11. 2400Hz-Temporal 3 ON OFF ON r• 2400Hz-Continuous OFF OFF ON ECAM IIIp S* —1 Chime-Temporal 3 ON ON OFF Er ■ ■■ H+ ••i Chime-Continuous OFF ON OFF [°'■ ■■ Thi H- Lr— Whoop ON OFF OFF ® Cr Whoop OFF OFF OFF NOTE: • Switch Positions I and 2 in the OFF position to select isolated horn and strobe power inputs • Switch Position 6 ON=HIGH dBA • Switch Position 6 OFF=LOW dBA Super Slides'Mounting Bracket / •li Checkmate®Instant Allows the installer to pre-wire , I I Voltage Verification the system,test for system Ilk t It is often necessary to confirm the voltage supervision,remove the signal r; drop along a line of devices.The access head until occupancy,switch J1 holes are provided in the back of the out signals without terminal block to allow the voltage to be changing mounting brackets III II. �'I measured directly without removing the and has locking edge connector I�11111 li •', 9 device.Typically,this would be done at the for snap-in-place installation. _-■ end of line to confirm design criteria.Most measurements will he taken using the S+ • _ _ and S-locations althouhg access is provided to other locations. NOTE:Care should be taken to not short the test probes. Candela selection slider switch. Depress center and slide switch to desire brightness level. •` pil, - \''''...,\ __+ r -r-- ' Break off pin and insert III �,`f t �. j,i i ill into hole at the bottom of •• 1 ' �'� 7 ,`1 I the selector to lock �_`� tkt. Ifcandela setting.Signal 111111 j II i` must be removed from'• ` I i 111,I10 bracket and pin pushed it I�I Il ` �� forward from backside out '�� J� 0. .�4.!� �� ;I I «• � ---/ of hole to change candela. ' � To remove bezel,grip both sides of bezel and pull in a download and outward motion. Potter ElectricSignal Company,LLC•St.Louis,M063042 USA.CustService 866-572-3005•TechSupport:866-956-0988•Canada 888-882-1833•www.pottersignal.corn PRINTED fN USA MFG.418830054-REV A PAGE 2 OF 4 0613 le P POTTER S-24 & HS-24 SELECTABLE CANDELA e The Symbol of Protection STROBE & HORN/STROBES S-24 24 VDC Selectable Candela,Low Profile Evacuation Strobe leiModel Part Nominal Candela Number Number Voltage (ANSI/UL 1971) S-24WR 4890010 24 VDC 15,30,60,75, 110 S-24W W 4890011 24 VDC 15,30,60,75, 110 • HS-24 24 VDC Selectable Candela,Low Profile Evacuation Horn/Strobe Model Part Nominal Candela Reverberant dBA at In Anechoic Room Number Number Voltage (ANSI/UL 1971) 10 ft.,per ANSI/UL 464 dBA at 10 ft. HS-24WR 4890030 24 VDC 15,30,60,75,110 62-82 100 HS-24WW 4890031 24 VDC 15,30,60,75, 110 62-82 100 S-24&HS-24 Product Strobe Current Ratings(mA) 24 VDC(16-33 Volts) Model Designations: W=Wall Mount Itle Candela 24 VDC UL Max' R=Red Faceplate W=White Faceplate 15cd 30mA 42mA 30 ed 35 mA 58 mA All units are available in plain(no lettering). Plain units are non-returnable. 60 cd 66 nt.1 97 mA 75 cd 80 mA 116 mA ALERT bezel available for order. 110 cd 103 mA 161 mA ALERT bezel available for order. S-24&HS-24 Product Horn Current Ratings Horn Decibel Levels Horn Current Ratings Minimum SPL Minimum SPL Regulated 24 VDC Horn Mode at 10 ft..per at 10 lt.,per Max.Operating(a; ANSI/UL 464 ANS1/UL464 High Setting(mA) (HIGH) (LOW) Temp 3 2400 Hz 78 dBA 71*dBA 28 mA Temp 3 Mechanical 76 dBA 70*dBA 25 mA Temp 3 Chime 70* dBA 66*dBA 15 mA Continuous 2400 Hz 81 dBA 74*dBA 28 mA Continuous Mechanical 80 dBA 72*dBA 25 mA Continuous Chime 70*dBA 66*dBA 15 mA Whoop 82 dBA 69*dBA 56 mA NOTES: • For nominal and peak current across ANSUUL regulated voltage range for filtered DC power and unfiltered(FWR[Full Wave Rectified]) power,see installation manual. • Potter does nto recommend usign a coded or pulsing signaling circuit with any or our strobe products. • The sound output for the temporal 3 tone is rated lower since the time the horn is off is averaged into the sound output rating.While the horn is producing a tone in the temporal 3 mode its sound pressure is the same as the continuous mode. * Operating the horn in this mode at this voltage will result in not meeting the minimum ANSI/UL 464 reverberant sound level required for public mode fire protection service.These settings are acceptable only for private mode fire alarm use.Use the high dBA setting for public mode application(not applicable when using the chime tone.The chime tone is always private mode). PotterElectric S ignal Company,LLC•St.Louis,MO 63042 USA-CustService:866-572-3005*Tech Support'866-956-0988•Canada 888-882-1833•www.pottersignai com PRINTED IN USA MFG.#8330054-REV A PAGE 3 OF 4 06/13 P P( S-24 & HS-24 ER SELECTABLE CANDELA The Symbol of Protection STROBE &HORN/STROBES Architect&Engineering Specifications The audible and/or visible signal shall be Potter S-24 strobe and Potter HS-24 hom/strobe Series or approved equal and shall be listed by Underwriters Laboratories,Inc.per ANSI/UL 1971 and/or ANSI/UL 464.The notification appliance shall also be listed with Factory Mutual Listing Service(FM)and the California State Fire Marshal(CSFM). The notification appliance(combination audible/visible)shall produce a peak sound output of 100dBA or greater at 24VDC as measured in an anechoic chamber.The signaling appliance shall also have the capability to silence the audible signal while leaving the visible signal energized with the use of a single pair of power wires.Additionally,the user shall he able to select either continuous or temporal tone output with the temporal signal having the ability to be synchronized. Unit shall be capable of being installed so that any unauthorized attempt to change the candela setting will result in a trouble signal at the fire alarm control panel. The audible/visible and visible signaling appliance shall also maintain a minimum flash rate of 1Hz or up to 2Hz regardless of power input voltage.The strobe appliance shall have an operating current of 42mA or less at 24VDC for the 15Cd strobe circuit. The appliance shall be polarized to allow for electrical supervision of the system wiring.The unit shall be provided with a mounting bracket with terminals and barriers for input/output wiring and be able to mount to a single gang or double gang box or double workbox without the use of an adapter plate.The unit shall have an input voltage range of 16-33 volts with either direct current or full wave rectified power for 24VDC models. The appliance shall be capable of testing supervision without disconnecting wires,verify voltage without removing unit and be capable of mounting to a surface back box. Conventional Wiring Diagrams for Emergency Notification Evacuation Series UL Listed UL Listed Control Control Signal Signal Signal Signal Panel S+ e+ S- H+ H. Panel S« S+ S H+ S* S+ S- H+ H• S+ S+ a- Ha H- Supervised �` o ;, 0+ a 4• p Supervised IS S SS 0� 'SS SG 0I SIg\Circuit � I"' I", ENPOEEwE Signal Circuit p 0 ENO OF OR RESISTOR RESISTOR \ Q �•i 11 O ENO(*LANE O RESISTOR NOTES: • All strobes are designed to flash as specified with continuous applied voltage.Strobes should not be used on coded or pulsing signaling circuits.However,use of the Potter AVSM control module or Gentex synchronization protocol is permitted to synchronize the strobe,horn,and/or mute the horn. • FOR SYNCHRONIZATION WIRING INFORMATION,REFERENCE AVSM CONTROL MODULE DATA SHEET(8830050) AND/OR AVSM CONTROL MODULE MANUAL FOR SYNCHRONIZATION MODULE WIRING DIAGRAMS.AVSM CONTROL MODULE DATA SHEET AND MANUAL CAN BE OBTAINED AT http://pottersignal.com OR CALL POTTER ELECTRIC AT 1-800-325-3936. Potter Electric Signal Company,LLC•St.Louis,M0 63042 USA.CustService:866-572-3005•Tech Support:866-956-0988•Canada888-882-1833•www.pottersignal.com PRINTED IN USA MFG.#8830054-REV A PAGE 4 OF 4 0613 • PPOTTER �I FASPKRASPKSTR-24CLP PO 1 1 ER Indoor Low Profile Speaker and Ceiling The Symbol of Protection Speaker/Strobe Series Features • 24VDC tamperproof selectable candela options of 15,30,60,75,and 110 • Speaker voltage 25 or 70.7 VRMs standard,field selectable • Field selectable power taps: 1/8W, 1/4W, 1/2W, 1 W,2W.4W • High quality dBA output(intelligible) ��//////,li1///!'I �l!, • Frequency range 400-4000 Hz �/ • Screw Terminals,separate in/out wiring(18-I 2 gauge) • Tamperproof grill ®' • Faceplate available in red or off-white ¢ • Product includes a 5 year warranty 0 411) LISTED S2657 7320-0328:0208 Application Product Listings The Potter SPKSTR-24CLP is a ceiling mount,low profile,field • ANSI/UL 1480,ANSI/UL1971 and ANSI/UL 2043 adjustable speaker/strobe and the FASPKR is a universal mount • CSFM 7320-0328:0208 speaker designed to meet code requirements for audio,visual,and voice communications.The SPKSTR-24CLP Series are quality speaker products offering dependable evacuation signaling,visual Product Compliance alarms,or a combination of both. p • Americans with Disabilities Act(ADA) Description • NFPA 72 The SPKSTR-24CLP has high output tamperproof candela selections • IBC/]FC iRC of 15,30,75,95,and 115.The SPKSTR-24CLP and FASPKR provide a 25 or 70.7 VRMs speaker with field selectable power taps of 1/8W Technical Specifications 1/4W, 1/2W, 1W,2W,or 4W.The SPKSTR-24CLP strobes can be p synchronized using the PotterAVSM Synchronization Control Module, Speaker Operating Voltage 25VRMs or 70.7VRMs FACP,or power supplies that produce a Gentex Synchronization Protocol. Strobe Operating Voltage I 6-33VDC Synchronization Module Potter AVSM The SPKSTR-24CLP and FASPKR can be mounted to a 4"X 2 1/8" deep back box without an extension ring or Potter SPKRBB surface Environmental Limitations 32°F to 120°F back box. Indoor Only Unit Dimensions 6.1"(15.494cm)square The SPKSTR-24CLP and FASPKR are constructed of high textured X 1.88"(4.7752cm)deep plastic. 4"X 2 1/8"deep box or Potter Back Box SPKRBB surface back box Shipping Weight 1.5 lbs. Potter Electric Signal Company,LLC • St. Louis,MO • Tech Support: 866-956-1211 /Customer Service: 866-572-3005 • www.pottersignal.com 8830060-REV B • 10/14 PAGE 1 OF 3 P P FASPKR/SPKSTR-24CLP POTTER Indoor Low Profile Speaker and Ceiling The Symbol of Protection Speaker/Strobe Series SPKSTR-24CLP Product Strobe Current Ratings Low Profile Evacuation Speakers Candela 15 cd 30 cd 75 cd 95 cd 115 cd Model Number Description Stock Number 24 VDC 72 mA 101 mA 167 mA 200 mA 214 mA FASPKR-R Speaker Red 4890200 III,Max 120 mA 120 mA 200 mA 220 mA 290 mA FASPKR-W Speaker White 4890201 Speaker 4RA C, 10 ft. Low Profile Evacuation Speakers Input Watts 25 Volts 70.7 Volts Model Number Description Stock Number 1/8 74.6 dBA 73.7 dBA SPKSTR-24CLPR Speaker/Strobe Red 4890220 1/4 77.7 dBA 76.7 dBA SPKSTR-24C1.PW Speaker/Strobe White 4890221 1/2 80.5 dBA 79.6 dBA SPKSTR-24CLPPR Speaker/Strobe Plain Red 4890222 I 83.1 dBA 82.5 dBA SPKSTR-24CLPPW Speaker/Strobe Plain White 4890223 2 85.6 dBA 85.4 dBA 4 87.9 dBA 87.9 dBA Model Designations NOTE: P=Plain(No Lettering) • Potter does not recommend using a coded or pulsing signaling W=Off-White Faceplate le circuit with any of our strobe products. R=Red Faceplate Plain units are non-returnable Architect and Engineering Specifications The fire alarm speaker shall be Potter FASPKR,SPKSTR-24CLP or equivalent.The speaker shall be capable of producing alarm tones or voice on all 25 or 70.7 VRMs audio systems.The speaker shall provide incremental tap settings of 1/8,1/4, 1/2, 1,2,or 4 watts.Minimum dBA ratings at 1/4 watt shall be 76.7 dBA and at 4 watts 87.9dBA.Tap settings shall be adjustable with field selectable jumper pins.The speaker shall also have an optional visual signal capability. The visual signal shall have a 1 Hz flash rate regardless of input voltage.All field wiring connections shall be made via separate in-out terminal connections and the speaker or speaker strobe shall be ANSI/UL,CSFM listed and comply with all local,state and federal fire alarm codes/standards. Potter Electric Signal Company, LLC • St. Louis, MO • Tech Support: 866-956-1211 /Customer Service: 866-572-3005 • www.pottersignal.com 8830060-REV B • 10/14 PAGE 20F3 • FASPKR/SPKSTR-24CLP P POTTER Indoor Low Profile Speaker and Ceiling The Symbol of Protection Speaker/Strobe Series SPKSTR-24CLP Candela Power Tap Selection Mounting Diagram Selection LINE VOLTS �� �A® ��a � _ =;8 llll0 �11IOOIII ��ll Oq� •��� �� va Adjust ,i>'� t o �'i 1, vz Power taps �= �E .r"�� �1re 1 using needle �l _ 4® ®® d� i Cr.77M.1 ,fif iI wa z nose pliers. i �I = ` d 11h �1n a ` .i o e a _ .. ..o N ...0....,-"1-4-ji; ..--, Mounts to a standard 4"square X 2 1/8" Adjust candela setting by turning dial back box or Potter SPKRBB surface back with screwdriver.Candela selection is box. displayed on front of unit. Wiring Diagram SPEAKER TO NEXT APPLINRCE FROM LAST APPLIANCE 25 OR 70V + 0■ EOLR NOTE:DO NOT USE SOURCE 0 44 LOOPED WIRE " UNDER TERMINALS. BREAK WIRE STROBE TO FEXTAPPLANE FROM LAST APPLIANCE RUN TO PROVIDE 24V POWER 0- ' �EOLR SUPERVISION OF III- 0 CONNECT►oN. I1 '1I La ] EX WIRE CONDUCTIVITY (OPTION gy SPE AKER 18 AWG 60 16AWG 95 14AWG 153 12AWG 244 • MAX WIRE DISTANCE- PANEL VOLTAGE-DEVICE MINIMUM VOLTAGE X WIRE CONDUCTIVITY TOTAL CURRENT DRAW • CAUTION:APPLIES ONLY TO REGULATED SUPPLIES. • NOTICE: POWER IS SUPPLIED TO DEVICES WHEN CONTROL PANEL IS LATCHED. Potter Electric Signal Company,LLC • St. Louis, MO • Tech Support: 866-956-1211 /Customer Service: 866-572-3005 • www.pottersignal.com 150 55o1:2ao5 DESIGNING,MANUFACTURING, CERTIFIED I&DISTRIBUTING DUALITY SYSTEMS SR30060-REV B • 10/14 PAGE 3 OF 3 SPKSTR-24WLP P POTTER Indoor Low Profil Wall Mount The Symbol of Protection Speaker/Strobe e Series Features • 24VDC tamperproof selectable candela options of 15,30,60,75,and 110 • Speaker voltage 25 or 70.7 VRMs standard,field selectable • Field selectable power taps: 1/8W, 1/4W,1/2W,1 W,2W,4W • Xenon strobe maintains constant flash rate(1Hz) /fir • • High quality dBA output(intelligible) N.,f,€ • Frequency range 400-4000 Hz • Screw Terminals,separate in/out wiring(18-12 gauge) 1 J _� • Tamperproof grill c -• •• • Faceplate available in red or off-white • Product includes a 5 year warranty �)=II1II'I,1IIIIII'I LISTED S2657 7320-0328:0207 Application Product Listings The Potter SPKSTR-24WLP is a wall mount,low profile,field • ANSI/UL 1638,ANSI/UL 1971 and ANSI/UL 1480 adjustable speaker/strobe designed to meet code requirements for • CSFM 7320-0328:0207 audio,visual,and voice communications.The SPKSTR-24WLP Series are quality speaker products offering dependable evacuation signaling, visual alarms,or a combination of both. Product Compliance Description ▪ Americans with Disabilities Act(ADA) • NFPA 72 The SPKSTR-24WLP has high output tamperproof candela selections of 15,30,75,95,and 115.The SPKSTR-24WLP provides a 25 or 70.7 • IBC/IFC/IRC VRMs speaker with field selectable power taps of 1/8 W, 1/4W, 1/2W. 1W,2W,or 4W.The SPKSTR-24WLP strobes can be synchronized using the PotterAVSM Synchronization Control Module,FACP,or Technical Specifications power supplies that produce a Gentex Synchronization Protocol. Speaker Operating Voltage 25VRMs or 70.7VRMs The SPKSTR-24WLP can be mounted to a 4"X 2 1/8"deep back box Strobe Operating Voltage 16-33VDC without an extension ring or Potter SPKRBB surface back box. Synchronization Module Potter AVSM The SPKSTR-24WLP is constructed of high textured plastic. Environmental Limitations 32°F to 120°F Indoor Only Unit Dimensions 6.1"(15.494cm)square X 1.88"(4.7752cm)deep Back Box 4"X 2 1/8"deep box or Potter SPKRBB surface back box Shipping Weight 1.5 lbs. Potter Electric Signal Company,LLC • St. Louis,MO • Tech Support 866-956-1211 /Customer Service: 866-572-3005 • www.pottersignal.com 8830061-REV B • 10/14 PAGE 1 OF 3 • In P PQTTEPOTTERSPKSTR-24WLP� Indoor Low Profil Wajl Mount e The Symbol of Protection Speaker1Strobe Serzes SPKSTR-24CLP Product Strobe Current Ratings Low Profile Evacuation Speakers Candela 15 cd 30 cd 60 cd 75 cd 110 cd Model Number iL, Description Stock Number 24 VDC 55 mA 63 mA 88 mA 112 mA 136 mA SPKSTR-24WLPR V Speaker/Strobe Red 4890210 UL Max 78 mA 96 mA 137 mA 180 mA 224 mA SPKSTR-24WLPW Speaker/Strobe White 4890211 SPKSTR-24WLPPR Speaker/Strobe Plain Red 4890212 Speaker dBA 10 ft. SPKSTR-24WLPPW Speaker/Strobe Plain White 4890213 Input Watts 25 Volts 70.7 Volts 1/8 74.6 dBA 73.7 dBA 1/4 77.7 dBA 76.7 dBA Model Designations 1/2 80.5 dBA 79.6 dBA P=Plain(No Lettering) 1 83.1 dBA 82.5 dBA W=OtT White Faceplate 2 85.6 dBA 85.4 dBA R=Red Faceplate 4 87.9 dBA 87.9 dBA NOTE: Plain units are non-returnable • Potter does not recommend using a coded or pulsing signaling circuit with any of our strobe products. Architect and Engineering Specifications The fire alarm speaker shall be Potter SPKSTR-24WLP or equivalent.The speaker shall be capable of producing alarm tones or voice on all 25 or 70.7 VRMs audio systems.The speaker shall provide incremental tap settings of 1/8,1/4, 1/2, 1,2,or 4 watts.Minimum dBA ratings at 1/4 watt shall be 76.7 dBA and at 4 watts 87.9dBA.Tap settings shall be adjustable with field selectable jumper pins.The speaker shall also have an optional visual signal capability. The visual signal shall have a 1 Hz flash rate regardless of input voltage.All field wiring connections shall be made via separate in-out terminal connections and the speaker or speaker strobe shall be ANSI/UL,CSFM listed and comply with all local,state and federal fire alarm codes/standards. Potter Electric Signal Company, LLC • St. Louis, MO • Tech Support: 866-956-1211 /Customer Service: 866-572-3005 • www.pottersignal.com 8830061-REV B • 10.14 PAGE 2 OF 3 P PO Indoor Low Profile Wall Mount The Symbol of Protection Speaker/Strobe Sertes SPKSTR-24WLP Power Tap Selection Mounting Diagram Candela Selection LINE P VOLTS —��` _.1 ' /„t ' ®�, ,,•' is...t•t �`� 25 70 API �I NON' '---. �-, a �I 118 0 1 x , va Adjust ,�,o � I �•.ru+l in Power taps ag..0 �t:e 1 using needle `o _ ® fi n®' 5� se 2 nose pliers.dl IIIm-ifir , I ,l .....1t2 4 ` 1.0ii — t:. -.-P z:i - .�_ N --.,ty-.„--/4477; \„,..„...........s, .7%.4 — .--- fl ei1‘\h ,;,.....-. , Mounts to a standard 4"square X 2 1/8" Adjust candela setting by turning dial back box or Potter SPKRBB surface back with screwdriver.Candela selection is box. displayed on front of unit. Wiring Diagram SPEAKER TO NETT APPLANCE FROM LAST APPLIANCE 25 OR 70V + 0 � EOLR NOTE:DO NOT USE SOURCE - I' J LOOPED WIRE CINDER TERMINALS. BREAK WIRE STROBE TO NEXT APPLLANCE FROM LAST APPL LANCE RUN TO PROVIDE 24V POWER + O I" —�EOLR SUPERVISION OF SOURCE I' "I J CONNECTION. + - + - WIRE CONDUCTIVITY STROBE SPEAKER 18 AWG 60 (OPTIONAL) 16AWG 95 14AWG 153 12AWG 244 MAX WIRE DISTANCE- PANEL VOLTAGE-DEVICE MINIMUM VOLTAGE -X WIRE CONDUCTIVITY • TOTAL CURRENT DRAW • CAUTION:APPLIES ONLY TO REGULATED SUPPLIES. • NOTICE: POWER IS SUPPLIED TO DEVICES WHEN CONTROL PANEL IS LATCHED. Potter Electric Signal Company,LLC • St Louis,MO • Tech Support: 866-956-1211 /Customer Service: 866-572-3005 • www.pottersignaLcom Iss sOo1:2oOB DESIGNING,MANUFACTURING, CERTIFIED I&DISTRIBUTING QUALITY SYSTEMS 8830061-REV A • 10/14 PAGE 3 OF 3 PPOTTER ©I WSSPK Outdoor Wall Mount Speaker and The Symbol of Protection Speaker Strobe Series Features • 24VDC fixed 15/75 candela • WSSPK series shipped with Gentex GBLP outdoor back box • Field selectable power taps_ I/8W, 1/4W, 1/2W, 1W,2W.4W • High quality dBA output(intelligible) r• • Frequency range 400-4000 Hz • Screw terminals,separate in/out wiring(18-12 gauge) tr- • Tamperproof grill �LI • Speaker voltage 25 or 70.7 VRMS standard,field selectable • Faceplate available in red or off-white • Strobe synchronization with Potter AVSM module • Product includes a 5 year warranty tk, LISTED Application Product Listings The Gentex WSSPK series is an outdoor listed, wall mount, field • ANSI/UL 1480,ANSI/ULI638 Listed adjustable speaker and speaker/strobe designed to meet code • CSFM 7320-0569:0141 requirements for audio, visual, and voice communications. The WSSPK Series are quality speaker products offering dependable evacuation signaling, visual alarms, or a combination of both. The Product Compliance WSSPK24-15/75 speaker/strobe offers a fixed 15/75 candela strobe. • Americans with Disabilities Act(ADA) Description • NFPA 72 The WSSPK Series provides a 25 or 70.7 VRMS speaker with field • IBC/IFC IRC selectable power taps of 1/8W, 1/4W, 1/2W', 1W, 2W, or 4W. The WSSPK24-15/75 provides a fixed 15/75 candela strobe output. The strobe can be synchronized using the Potter AVSM Synchronization Technical Specifications Control Module, FACP, or power supplies that produce a Gentex Speaker Operating Voltage 25VRMs or 70.7VRMs Synchronization Protocol. Strobe Operating Voltage I 6-33VDC The WSSPK Series grills are constructed of high impact textured Synchronization Module Potter AVSM plastic.Included with the WSSPK Series speaker and speaker/strobe is the GBLP outdoor listed back box.Using the GBLP back box with the Environmental Limitations -31°F to 150°F WSSPK Series provides protection from weather related conditions and allows the necessary full candela output. WSSPK-6.1"square X 3.19"deep Unit Dimensions WSSPK24-6.1"square X 4.0625° deep Back Box Includes GBLP outdoor back box Potter Electric Signal Company,LLC • St. Louis, MO • Tech Support: 866-956-1211 /Customer Service: 866-572-3005 • www.pottersignal.com 8830062-REV B • 08i I PAGE I OF 3 • WSSPK P POTTER Outdoor Wall Mount Speaker and The Symbol of Protection Speaker Strobe Series WSSPK24-15/75 Strobe Current Rating Outdoor Evacuation Speakers(Speaker Only) Candela 15/75 cd Model Number Description Stock Number 24 VDC 63 mA WSSPKR Speaker Red 4890204 UL Max 96 mA WSSPKW Speaker White 4890205 Speaker dBA @ 10 ft. Outdoor Evacuation Speaker/Strobes Fixed 15/75 candela Input Watts 25 Volts 70.7 Volts V Model Number Description Stock Number 1/8 74.6 dBA 73.7 dBA WSSPK24-15/75WR Speaker/Strobe Red 4890206 1/4 77.7 dBA 76.7 dBA WSSPK24-15/75 W W Speaker/Strobe White 4890207 1/2 80.5 dBA 79.6 dBA 1 83.1 dBA 82.5 dBA Model Designations 2 85.6 dBA 85.4 dBA W=Ott-White Faceplate 4 87.9 dBA 87.9 dBA R=Red Faceplate NOTE:Potter does not recommend using a coded or pulsing signaling circuit with any of our strobe products. Architect and Engineering Specifications The fire alarm speaker shall be Gentex WSSPK,WSSPK24-15/75 or equivalent.The speaker shall be capable of producing alarm tones or voice on all 25 or 70.7 VRMs audio systems.The speaker shall provide incremental tap settings of 1/8.1/4, 1/2,1,2,or 4 watts.Minimum dBA ratings at 1/4 watt shall be 76.7 dBA and at 4 watts 87.9dBA.Tap settings shall be adjustable with field selectable jumper pins.The speaker shall also have an optional visual signal capability. The visual signal shall have a 1 Hz flash rate regardless of input voltage.All field wiring connections shall be made via separate in-out terminal connections. The appliance has extended temperature range of-31°to 150°F(-35°to 66°C).The appliance shall satisfy all outdoor and severe environment applications. The GBLP back box includes a gasket that must be inserted between the box and device.There are drain holes in the back box to allow for draingage,the seal on the GBLP is not water tight.The speaker or speaker/strobe shall be ANSI/UL,CSFM listed and comply with all local,state and federal fire alarm codes/standards. Potter Electric Signal Company.LLC • St. Louis. MO • Tech Support: 866-956-1211 /Customer Service: 866-572-3005 • www.pottersignal.com 8830062-REV B • 08/15 PAGE 2 OF 3 4 P P WSSPK POTTER 1_lt Outdoor Wall Mount Speaker and The Symbol of Protection Speaker Strobe Series Power Tap Selection Mounting Diagram Fig 1 Fig 2 LINE %/I�r VOLTS .` ate ®c- 25 70 _000�1110�����/ o • �� J — 114 '/iC o I 1/2 ��o �116 1 o Fla �i o """ moo 1/4 2 o 600 1/2 4 o 1 —jmmmiii l@ a 4 — CAik11 1 i Sly. , NOTE:Adjust Power taps using needle nosepliers. Wiring Diagram Fig TO NEXT APPLIANCE FROM LAST APPLIANCE SPEAKER + 0 NOTE:DO NOT USE 25 OR 70V EOLR SOURCE 0 / LOOPED WIRE UNDER TERMINALS. BREAK WIRE TO NEXT APPLIANCE FROM LAST AWL LANCE OBE RUN TO PROVIDE 24V POWER O- "' ��EOLR SUPERVISION OF SOURCE I' "' I CONNECTION. DI] �i[74 WIRE CONDUCTIVITY STROBE SPEAR 18 AWG 60 (OPTIONAL) 16AWG 95 14AWG 153 12AWG 244 • MAX WIRE DISTANCE- PANEL VOLTAGE-DEVICE MINIMUM VOLTAGE X WIRE CONDUCTIVITY TOTAL CURRENT DRAW • CAUTION:APPLIES ONLY TO REGULATED SUPPLIES. • NOTICE: POWER IS SUPPLIED TO DEVICES WHEN CONTROL PANEL IS LATCHED. Potter Electric Signal Company,LLC • St. Louis, MO • Tech Support: 866-956-1211 /Customer Service: 866-572-3005 • www.pottersignal.com IDO DOal:zoas DE SIGNING,MANUFACTURING, CERTIFIED I&DISTRIBUTING QUALITY SYSTEMS 8830062-REV B • 08/15 PAGE 3 OF 3