Report (11) rPS20 ocjo 7 SimplexGrinnell /2 3541 5;j .A.40tL' L 2 S mplexGrinnell BE SAFE, A Division of Grinnell Corporation 6305 SW Rosewood Street,Suite"A" A Tyco International Company Lake Oswego, OR 97035 Date: 01,`16/15 Tele:503-683-9000 Fax:503-675-6521 lityj y YA13 JAN2 CON „Ni N BUILDING l. ELITE CARE KNOLL TIGARD, OREGON MATERIAL SUBMITTAL Fire Protection, Automatic Sprinkler 1. Pipe & Fittings a. Tyco CPVC Pipe and Fittings 2. Hangers a. Tolco Fig. 200 Ring b. Tolco Fig. 4A Longitudinal Sway Brace Attachment a c. Tolco Fig. 980 Earthquake Brace Clamp d. Tolco Fig. 1000 Sway Brace Attachment e. Sammy Sidewinder • f. CPVC Pipe Hangers 3. Valves a. Tyco Riser Manifold b. Milwaukee BB-SC SO2 Slow Close Butterfly Valve 4. Sprinklers a. Tyco Model TY-FRB, Quick Response SSP/SSU b. Tyco Model TY-FRB, Quick Response Sidewall c. Tyco Model LFII, Quick Response Residential SSP 5. Alarms a. Potter Electric Bell b. Potter VSR-F Flow Switch 6. Miscellaneous Sprinkler Equipment a. Tyco 6 Head Sprinkler Cabinet b. Tyco Style 10, Ceiling Escutcheon c. Drain Valves d. Pressure Gauge Y tgccs Ire & Building Products rapid response HOME FIRE SPRINKLER SYSTEM Technical Services:Tel:(800)381-9312/Fax:(800)791-5500 BlazeMaster CPVC Fire Sprinkler Pipe & Fittings Submittal Sheet General Description Technical . ® Data Tyco CPVC Pipe and Fittings pro-duced by Tyco Fire & Building Prod- ucts (TFBP) are designed exclusively Sizes for use in wet pipe automatic fire sprin- 314"to 3" 1 4 kler systems. The Tyco CPVC Pipe Maximum Working Pressure and Fittings are produced from Blaze- 175 psi Master® CPVC compound that is a $ „ specially developed thermoplastic Approvals compound composed of post chlorin- UL, FM, C-UL, NSF, LPCB, MEA, and � , P ` � �� ' � ated polyvinyl chloride (CPVC) resin the City of Los Angeles. (Refer to (n- and state of the art additives. Tyco stallation Handbook IH-1900 dated p FittingsJune 2008 for exact listing/approval CPVC Pi e and are easier to �' j ° install than traditional steel pipe sys- information.) tems, and at the same time, provide Manufacture Source - superior heat resistance and strength U.S.A. as compared to traditional CPVC and PVC piping materials used in the Material plumbing trade. Various adapters are • Pipe: ASTM F442,SDR 13.5 available to connect CPVC pipe to me- tallic p piping. All female pipe thread • Fittings: ASTM F438 (Sch. 40) and adapters have brass inserts for dura- ASTM F439(Sch.80),ASTM F1970 bility. Grooved adapters connect di- Color rectly to grooved end valves and me- Orange tallic pipe, with flexible grooved end couplings. NOTICE Tyco® CPVC Pipe and Fittings pro- duced with BlazeMaster®CPVC com- pound described herein must be in- stalled and maintained in compliance with this document and with the appli- cable standards of the National Fire Protection Association, in addition to the standards of any authorities having jurisdiction. Failure to do so may im- pair the performance of these devices. The owner is responsible for maintain- ing their fire protection system and de- vices in proper operating condition. The installing contractor or sprinkler manufacturer should be contacted with any questions. BlazeMaster®is a registered trademark of The Lubrizol Corporation Page 1 of 2 JUNE, 2008 TFP1915 Page 2 of 2 TFP1915 Installation Limited Wa rranty Tyco CPVC Pipe and Fittings pro- duced by Tyco Fire & Building Prod- ucts (TFBP) are to be installed in Products manufactured by Tyco Fire& accordance with Installation Hand- Building Products (TFBP) are war- book IH-1900 dated June 2008. ranted solely to the original Buyer for ten(10)years against defects in mate- Care and rial and workmanship when paid for and properly installed and maintained Maintenance under normal use and service. This warranty will expire ten (10) years for the in- from date of shipment by TFBP. No The owner is responsible warranty is given for products or corn- spection, testing, and maintenance of ponents manufactured by companies their fire protection system and de- not affiliated by ownership with TFBP vices in compliance with this docu- or for products and components which ment, as well as with the applicable have been subject to misuse,improper standards of the National Fire Protec- installation, corrosion, or which have tion Association (e.g., NFPA 25), in not been installed, maintained, modi- addition to the standards of any fied or repaired in accordance with ap- authority having jurisdiction. The in- plicable Standards of the National Fire stalling contractor or product manufac- Protection Association, and/or the turer should be contacted relative to standards of any other Authorities any questions. Having Jurisdiction. Materials found Automatic sprinkler systems should be by TFBP to be defective shall be either inspected,tested,and maintained by a repaired or replaced, at TFBP's sole qualified Inspection Service in accord- option. TFBP neither assumes, nor ance with local requirements and/or authorizes any person to assume for it, national codes. any other obligation in connection with the sale of products or parts of prod- ucts.NOTICE TFBP shall not be responsible for sprinkler system design errors or sup- Beforeinac- closing a fire protection system curate or incomplete information_ control valve for inspection or mainte- plied Buyer or Buyer's repre- nance work on the fire protection sys- tem sentatives. that it controls,permission to shut In no event shall TFBP be liable, in down the affected fire protection sys- contract, tort, strict liability or under tern must first be obtained from the any other legal theory, for incidental, proper authorities and all personnel indirect,special or consequential dam- who may be affected by this action ages, including but not limited to labor must be notified. charges, regardless of whether TFBP was informed about the possibility of After placing a fire protection system such damages, and in no event shall in service,notify the proper authorities TFBP's liability exceed an amount and advise those responsible formoni- equal to the sales price. toying proprietary and/or central sta- The foregoing warranty is made in lieu lion alarms. of any and all other warranties. ex- press or imolied. including warranties of merchantability and fitness for a par- ticular ournose This limited warranty sets forth the ex- clusive remedy for claims based on failure of or defect in products,materi- als or components, whether the claim is made in contract, tort, strict liability or any other legal theory. This warranty will apply to the full ex- tent permitted by law.The invalidity, in whole or part, of any portion of this warranty will not affect the remainder. ©2008 TYCO FIRE&BUILDING PRODUCTS,451 North Cannon Avenue,Lansdale,Pennsylvania 19446 TOLCO - www.toko.com NIBCD Revision 12/18/2008 Fig. 200 - "Trimline" Adjustable Band Hanger Dusre Fig. 200R (Import) - "Trimline" Adjustable Band Hanger , L w/Retainer Ring Size Range — 1/2" thru 8" pipe Material — Carbon Steel, Mil. Galvanized to G90 ,- specifications .�r Function — For fire sprinkler and other general piping $Z / purposes. Knurled swivel nut design permits hanger ;' adjustment after installation. / / \ �- Features — - — � � , • (1/2" thru 2") Flared edges ease installation for s 11 j s J' I j all pipe types and protect CPVC plastic pipe = 1/ �/i )% from abrasion. Captured design keeps adjusting j // I/ ' 1 ; nut from separating with hanger. Hanger is eas- " `i' �' ' i ily installed around pipe. ���\`'-%'5 A • (21" thru 8") Spring tension on nut holds it 'Il securely in hanger before installation. Adjusting nut is easily removed. Fig.2001"-2" Fig.200 21h"-8" Approvals — Underwriters' Laboratories listed lok (1/2" thru 8") in the USA(UL)and Canada(cUL) `"e, for steel and CPVC plastic pipe and Factory Mutual Engineering Approved (3/4" thru 8"). Conforms to , U - Federal Specifications WW-H-171 E,Type 10 and ® / ��= ` Manufacturers Standardization Society SP-69,Type ' ,• gl; B _ 10. 1i j Maximum Temperature — 650°F 1 ;i , , B i ; Finish — Mil. Galvanized. Stainless Steel materials will , ;1 ! i// 1 1I be supplied with (2) hex nuts in place of a knurl nub. 'I - ! // ( i Order By — Figure number and pipe size i I A . Note — Figure 200R (import)with retainer ring and A ------- Fig. :, �z`,--,% non-captured knurl nut. 200R 21/2"-8" Fig.200R 1/2"-2" Dimensions •Weights Pipe Rod Size Max.Rec. Approx. Size Inch Metric A B Load Lbs. WtJ100 1/2 3/8 8mm or 10mm 31/e 25/81 400 11 3/4 3/8 8mm or 10mm 31/e 21/2 400 11 1 3/8 8mm or 10mm 31 25/3 400 12 11/4 3/8 8mm or 10mm 33 27/s 400 13 vh 3/8 8mm or 10mm 37/8 21/2 400 14 2 3/8 8mm or 10mm 41/2 3 400 15 21.6 3/8 10mm 55/s 41/2 600 27 3 3/8 10mm 57/8 4 600 29 31/2 3/8 10mm 73,43 51/4 600 34 4 3/8 10mm 73/s 5 1000 35 5 1/2 12mm 91/8 61/4 1250 66 6 1/2 12mm 101/e 63 1250 73 8 1/2 12mm 131/e 83/4 1250 136 OFFICE/MANUFACTURING FACILITY•1375 SAMPSON AVE.•CORONA,CA 92879•PH: 951.737.5505•FAX: 951.737.0330 CUSTOMER SERVICE•500.786.5266 91 www.tolcc.com 0 TOLCO wwwaolco.com NIBCO Revision 10/15/2008 Component of State of Fig. 4A - Pipe Clamp for Sway Bracing California OSHPD Approved a 0Iususwl • Seismic Restraints System Size Range — 4" thru 8" pipe. For sizes smaller than 4" use TOLCO® Fig. 4. 8 Material — Carbon Steel Function — For bracing pipe against sway and seismic disturbance. Approvals — Underwriters' Laboratories Listed in the USA(UL)and Canada J . } (cUL)4" thru 8". Included in our Seismic Restraints Catalog approved by the State of California Office of Statewide Health Planning and Development / 1 (OSHPD). / -,,,,,i , ,•----) Installation Instructions — The Fig. 4A is the "braced pipe" attachment a / / ; A component of a longitudinal, lateral or riser brace assembly. It is intended to I / // # be combined with the "bracing pipe" and TOLCO transitional and structural \ l / �7 /7 ii - attachment component(s) to form a complete bracing assembly. NFPA 13 •-•., D 1 - and/or OSHPD guidelines should be followed. To Install — Place the Fig. 4A over the pipe to be braced. Attach TOLCO "y`,/° transitional fitting, either Fig. 980, 910 or 909, to the clamp ears. Tighten 7 bolts and nuts; torque requirement is a minimum of 50 ft. lbs. Transitional fit- ting attachment can pivot for adjustment to proper brace angle. C I '/� Finish — Plain Note — Available in Electro-Galvanized and HDG finish or Stainless Steel materials. Order By — Figure number, pipe size and finish r / /`5 o W � n I Fig. 4A - Longitudinal Brace Fig. 4A - Lateral Brace TOLCO®brand bracing components are desgined to be compatible ONLY with other TOLCO®brand bracing components,resulting in a Listed seismic bracing assembly. DISCLAIMER— NIBCO does NOT warrant against the failure of TOLCO®brand bracing components,in the instance that such TOLCO®brand bracing components are used in combination with products,parts or systems which are not manufactured or sold under the TOLCO®brand. NIBCO shall NOT be liable under any circumstance for any direct or indirect,incidental or consequential damages of any kind, including but not limited to loss of business or profit,where non-TOLCO brand bracing components have been,or are used. Dimensions•Weights Pipe Max.Horizontal Approx. Sizes A B C D Bolt Size Design Load WtJ100 4 81/2 9/16 33/e 311/46 1/2 2015 221 5 93/4 9/16 37/8 43/8 1/2 2015 253 - 6 111h 5/8 5 51/8 1/2 2015 513 8 131/4 3/4 611/is 61/8 1/2 2015 601 OFFICE/MANUFACTURING FACILITY•1375 SAMPSON AVE.•CORONA,CA 92879•PH: 951.737.5599•FAX: 951.737.0330 7.:-'. CUSTOMER SERVICE•800.780.5266 www.tofco.cem ToLco NIBCO Revision 11/7/2008 Fig. 980 - Universal Swivel Sway Brace Attachment E uL LtSTFR Size Range — One size fits bracing pipe 1" thru 2",TOLCO 12 gauge channel, and all structural steel up to 1/4" thick. Material — Carbon Steel Component of State of '/ California OSHPD Approved Function — Multi-functional attachment to structure or Seismic Restraints System braced pipe fitting. Features — This product's design incorporates a concen- tric attachment opening which is critical to the performance of structural seismic connections. NFPA 13 (2002) Figure 9.3.5.9.1 indicates clearlythat fastener table load values are based only on concentric loading. Mounts to any surface angle. Break off bolt head assures verification of proper installation. 411/4. Installation — The Fig.980 is the structural or transitional A attachment component of a longitudinal or lateral sway brace assembly. It is intended to be combined with the B "bracing pipe" and TOLCO "braced pipe" attachment, Fig. 1000, 1001, 2002, 4L, 4A or 4B to form a complete bracing assembly. NFPA 13 and/or OSHPD guidelines should be followed. To Install — Place the Fig. 980 onto the "bracing pipe". Tighten the set bolt until set bolt head breaks off. Attachment can pivot for adjustment to proper brace angle. Approvals — Underwriters Laboratories Listed in the USA(UL) and Canada(cUL). Approved by Factory Mutual Engineering (FM). Included in our Seismic Restraints Catalog approved by the State of California Office of Statewide Health Planning and Development(OSHPD). For additional load, spacing and placement information relating to OSHPD projects, please refer to the TOLCO Seismic Restraint Systems Guidelines. - Note — The Fig. 980 Swivel Attachment and the Fig. 1001, Fig. 1000 , Fig. 2001 or Fig. 4A Pipe Clamp make up a sway brace system of UL Listed attachments and bracing materials which satisfies the requirements of Underwriters' Laboratories and the National Fire Protection Association (NFPA) Finish — Plain r -/ Note — Available in Electro-Galvanized finish. Order By — Figure number and finish. // r PATENT#6,273,372, PATENT#6,517,030, PATENT#6,953,174, (e7,, PATENT#6,708,930, PATENT#7,191,987, PATENT#7,441,730 \ ,\ �6n x f4 Lateral Brace Dimensions •Weights Max.Design **Max.Design Approx. A B H* Load Lbs. Load Lbs. Wt./100 (cULus) (FM) 51/4 17A 17/32 2765 2800 132 * Available with hole sizes to accommodate up to 3/4"fastener. Consult factory. **Load shown is allowable with brace installed,between 30°-90°.No reduction of load based on brace angle is required. TOLCO0 brand bracing components are desgined to be compatible ONLY with other TOLCO®brand bracing components,resulting in a Listed seismic bracing assembly. DISCLAIMER — NIBCO does NOT warrant against the failure of TOLCO®brand bracing components,in the instance that such TOLCO5'brand bracing components are used in combination with products,parts or systems which are not manufactured or sold under the TOLCO®brand. NIBCO shall NOT be liable under any circumstance for any direct or indirect,incidental or consequential damages of any kind,including but not limited to loss of business or profit,where non-TOLCO brand bracing components have been,or are used. OFFICE/MANUFACTURING FACILITY•1375 SAMPSON AVE.•CORONA,CA 92879•PH: 951.737.5599•FAX: 951.737.0330 CUSTOMER SERVICE•800 786 5266 149 www.talco.com Ili TOLCO www.tolco.com NIBCO Revision 5/27/2008 Fig. 1000 - "Fast Clamp" Sway Brace Attachment California O OS tHPD Appot Sproved Seismic Restraints System Size Range — Pipe size to be braced: 1" thru 6" Schedule /--- 10 thru 40 IPS.* Pipe size used for bracing: 1" and 11 Schedule 40 G®U5 LISTED IPS. \ v Additionally(UL) approved for use to brace Schedule 7 41> .w � sprinkler pipe up to 4" (maximum horizontal design load ' / "`,, 1 655 lbs.) Torque requirement 6 — 8 ft. lbs. , .. V `t Material — Carbon Steel Function — For bracing pipe against sway and seismic I disturbance. The pipe attachment component of a sway brace sys- tem: Fig. 1000 is used in conjunction with a TOLCO Fig. 900 Series Fitting and joined together with bracing pipe per ) / NFPA 13*or TOLCO OSHPD Approved Seismic Manual, , , /' �- forming a complete sway brace assembly. , F/ A y; Features — Field adjustable, making critical pre-engineering of ' ' '/ bracing pipe unnecessary. Unique design requires no threading of y yl ,- ;/ bracing pipe. Can be used as a component of a 4-way riser brace. l' T ;t ` f' j Can be used as longitudinal brace with Fig. 907. Comes assembled y:, C , " and individually packaged with illustrated installation instructionskz. '. — sizes are clearly marked. Steel leaf spring insert provided to /' -r` assure installer and inspector necessary minimum torque has been achieved. Installation — The Fig. 1000 is the "braced pipe" attachment component of a lateral sway brace assembly. It is intended to be Maximum Design Load combined with the 'bracing pipe" and TOLCO structural attach- 1" thru 4" pipe size — 2015 lbs. ment component, Fig. 980, 910 or 909 to form a complete bracing 6" size — 1265 lbs. assembly. Follow NFPA 13 and/or OSHPD guidelines. To Install — Place the Fig. 1000 over the pipe to be braced, insert bracing pipe through opening leaving a minimum of 1" extension. FM Approved Design Loads* Brace pipe can be installed on top or bottom of pipe to be braced. 1" - 21/2" - 600 lbs. Tighten hex nuts until leaf spring is flat. It is recommended that the 3" -4" - 700 lbs. • brace angle be adjusted before hex nuts are fully tightened. Approvals — Underwriters Laboratories Listed in the USA(UL) and Canada(cUL). Approved by Factory Mutual Engineering (FM). Included in our Seismic Restraints Catalog approved by the State of California Office of Statewide Health Planning and Development (OSHPD). For additional load, spacing and placement informa- %A tion relating to OSHPD projects, please refer to the TOLCO Seismic y , Restraint Systems Guidelines. / J ~ ) Application Note — Position Fast Clamp and tighten two hex nuts / F / until leaf spring flattens. A minimum of 1" pipe extension beyond /` d; the Fig. 1000 is recommended. / ,,, / Finish — Plain it ) 'u Note —Available in Electro-Galvanized and HDG finish or Stainless 3 y ; 7' \ / Steel materials. ;'� . Order By — Order first by pipe size to be braced, followed by pipe size used for bracing,figure number and finish. Lateral Brace TOLCO®brand bracing components are desgined to be compatible ONLY with other TOLCO®brand bracing components,resulting in a Listed seismic bracing assembly. DISCLAIMER — NIBCO does NOT warrant against the failure of TOLCO®brand bracing components,in the instance that such TOLCO®brand bracing components are used in combination with products,parts or systems which are not manufactured or sold under - the TOLCO®brand. NIBCO shall NOT be liable under any circumstance for any direct or indirect,incidental or consequential damages of any kind,including but not limited to loss of business or profit,where non-TOLCO brand bracing components have been,or are used. OFFICE/MANUFACTURING FACILITY•1375 SAMPSON AVE.•CORONA,CA 92879•PH: 951.737.5599•FAX 951.737.0330 11111 CUSTOMER SERVICE•860 786 5266 www.tolco.com MIMMINNINIIIIIIIII OANNTO SIDEWINDER® FOR WOOD -Horizontal Application Application Product Features Not less than 2'nomina width .„, •No pre-drilling required. (1.1/2`)up to 3-112'pipe:not less than ;..•�,:..._.(m._ 3°(2-1)2°)nominal width 4"&5"pipe •Quick to install using the Sammy s 11--10' Floor Joist Nut Driver with an 18V cordless a e drill/driver. Minimum 2-1)2'from bottom for 2r- branch Imes-Minimum 3"from bet- ' -36335 5 39131 tom for main hoes.Exception:This •Saves time from traditional !4 ' requirement shall not apply to2'or - methods. W thicker nailing strips resting on top of W steel beams- .a4 ,,. •Reduces installation costs. {{' 1 1 y Sl' ; " _ •Made in the U.S.A. ' Ca rtpnsite l l r'uss „ + r ' conCrfl use mazmtmbeorffor . < 1 !a ;. ,ri i recortgtYerktledmstallatiai..•01.6tr �'Prwdrrdat9 mexhersqulraifarMoudt' 0).. .s ,, sWo28.aeo Toole"!olatdeum page 11t, l g 655 �r`� Wa ,ovsoroemr'.,:rir a •d Y.,'°•' www.ihvbuildex.com Ise Rod Part Screw Ultimate UL Test Box Case ': ,w Approvals Size Number Model Descriptions Pullout(Ibs) Load(Ibs) Qty - Qty l -I i3RIZQNTMA0UNT-': _ .:., .• - - 8019957 SWG 200 114 x 2' 1725 (Fir) 25 125 Q- 3,B" 8D2)3967 SWG 10 14 x 1' 622(Fir) 300 25 __-_125- ) tti. 3E 802'957 SWG 20 114 z 2" 1725 (Fir) 1050 25 125 , - 9- 3.`8" 6072925 SWG 20-SS 1 i4 x 2" 1725=;Fitt 650 25 125 I .;�"' Q- 3/8'• 8222925 SW'S2 330 +t 2 2-1 i'2" 2249 (Firl 1530 25 125 414 SW Red _ 318" 8023925 SWG 30 114 a 3" 1.684 (Fir) 23 125 '�11 Drive, Part b 81'4910 •May requite pre-drilling;consult joist manufacturer. 0 SAMMYS SWIVEL HEAD° FOR WOOD - Swivel Application - Z - Application • Product Features iDa •Eliminates distortion of threaded rod. ;. swtancsrne > .+, •Accommodates up to 3 lh x 12 pitch roof ; --- : 6. •Allows 17°deflection from vertical. a •y AW R, ., -, UPI •Saves time from traditional methods. • • a 1. i •Reduces installation costs. gfr t km—,• t •Made in the U.S.A. IC) koor• )/ MAX ANGLE ZS" . , Rod Part Screw Ultimate UL Test Load FM Test - Min Box Case aerl Approvals Model , ,+ Size Number DescriptionsPullout Qbs) (Ills) Load(Ibs) Thickness Qty Qty V T SYdiVELMOIINT - , #14 Black QO 318" 8139957 SH GST 20 5 114 x 2" 1257(Fir) 1 D50 1475 25 125 it. . Q Part#8113910 'm - 318" 8141957. SH-GS730' 114x3°. 1720(Fix) - -•1500 - . 1475 25- -125 -- -.- 1903 Dim,Lumber --- t.a^+, , 1500 318- 8269957 SH-GS?iCST 20 511E x 1-314' 1406 @ 45"eff vertical 550 @ 45' 25 125 ,w Dim.Lumber _) 903 Dim.Lumber J 1l26 8303957 SHGST(CST2.0-„Silt x 1,314" 1406§451'off vertical - 25 125 - 4 + *- .: Chin.'Lumbet _ .art J 'May require pre-elrllllog:consult joist manufacturer 0. b av1d"e a ��a s r ` , aW a s a a' s p , %,: '.s a a s ati x` sT s ^� r �z a. 'otrld adfshkbldt rreneeryot s„: a ry @ ,s„„ 4 s s 'w s . .D sf§ < a, a• 5 a q a�,'�,. x,•s �a u RIr'`=:,;:�..,�«. -"'�..>`,..:�.'^. c TOLCO wwwaolco.com NIBCO Revision 12/3/2008 Fig. 22 - Hanger for CPVC Plastic Pipe Single Fastener Strap Type COUS LISTED Size Range — 3/4" thru 2" CPVC pipe - ' Material — Pre-Galvanized Steel c--i'V Function — Intended to perform as a hanger to support CPVC piping used in automatic fire sprinkler systems. The product acts as a hanger when tab -' is upward and the fastener screw is in the horizontal position. Figure 22 can 1 °?-� - be installed on the top of a beam, but in this situation acts as a guide to 1 the piping which is supported by the beam itself. It is not intended to sup- °\ ,.,, port CPVC pipe from under a flat horizontal surface, such as a ceiling. For yr` '�, \, ``°, this type of installation, use the TOLCO® Fig. 23, Double Fastener Strap for i k.l ,, -r CPVC Piping. Fig. 22, when inverted, with the hanger tab downward, can A % .,'i \s, - function as a restrainer to prevent the upward movement of the sprinkler \. ;; )/ head during activation. �3v a Approvals — Underwriters' Laboratories Listed in the USA(UL) and Canada -,�--' ---' -,. (cUL)to support fire sprinkler piping. May be installed in wood using ,,r ` ''-„,, fasteners supplied with product, or into minimum 20 gauge steel using (1) 1/4" x 1" tek type screw. Meets and exceeds the requirements of NFPA 13, 13R and 13D. Features — Fig. 22 incorporates features which protect the pipe and ease installation. The flared edge design pro- tects CPVC pipe from any rough surface. It is easily attached to the building structure using the special UL Listed hex head self threading screw*furnished with the product. It is recommended that rechargeable electric drills fit- ted with a hex socket attachment to be used as installation tools. No impact tools (such as a hammer) are allowed. Damage has been known to result from installations using impact type tools. No pre-drilling of a pilot hole in wood is required. Finish — Pre-Galvanized Order By — Figure number and CPVC pipe size. Hardened hex head self threading screw is furnished with the product and is the minimum fastener size acceptable. Dimensions •Weights CPVC Max.Hanger Fastener Hex Approx. Pipe Size A B C Spacing(Ft.) Head Size Wt./100 3/4 27/16 15/16 13/16 51/2 5/16 9 1 211/16 17/6 13/46 6 5/16 9 11/4 31/i8 15/8 13/46 61h 5/16 11 11/2 33/46 13/4 13/46 7 5/16 12 2 33/4 21/6 13/46 8 5/16 15 OFFICE/MANUFACTURING FACILITY•1375 SAMPSON AVE.•CORONA,CA 92879•PH: 951 737 5599•FAX: 951.737.0330 CUSTOMER SERVICE•800.786.5268 111 www.tolca.com ® ToLimo www.toko.com NIBCO Revision 12/11/2009 Fig. 23 - Hanger for CPVC Plastic Pipe Double Fastener Strap Type ` °` 05 LISTED ' Size Range — 3/4" thru 3" CPVC pipe ', Material — Pre-Galvanized Steel r Function — Intended to perform as a hanger/restrainer to support /` //' - CPVC piping used in automatic fire sprinkler systems. Fig. 23 can i /� be installed on the top, bottom or side of a beam.The Fig. 23 also i /" 7 functions as a restrainer to prevent the upward movement of the \, 1( , sprinkler head during activation. . i� y ' Approvals — Underwriters' Laboratories Listed in the USA(UL) % and Canada(cUL) sizes 3/4" thru 2" to support fire sprinkler piping. May be installed in wood using fasteners supplied with product, f or into minimum 20 gauge steel using (2) 1/4" x 1" tek type screw. Meets and exceeds the requirements of NFPA 13, 13R and 13D. B Features — Fig. 23 incorporates features which protect the pipe / r and ease installation. The flared edge design protects the CPVC J pipe from any rough surface. It also incorporates snap restrain- C B A ers allowing easier and faster installation. Easily attaches to the building structure using the two UL Listed hex head self thread- ing screws*furnished with the product. It is recommended that rechargeable electric drills fitted with a hex socket attachment be used as installation tools. No impact tools (such as a hammer) are allowed. Damage has been known to result from installations using impact type tools. No pre-drilling of a pilot hole in wood is required. Finish — Pre-Galvanized Order By — Figure number and pipe size * Hardened hex head self threading screw is furnished with the product and Is the minimum fastener size acceptable. Dimensions •Weights CPVC Max.Hanger Fastener Hex Approx. Pipe Size A B C Spacing(Ft.) Head Size Wt./100 3/4 31/s 19/16 Wie 51/2 5/16 9 1 3% 1t1/16 13/16 6 5/16 9 11/4 43/18 23/32 13/16 61/2 5/16 11 11/2 47/16 21/22 We 7 5/16 12 2 47/3 27/is We 8 5/16 15 21/2 109/32 211/16 13/16 Consult Factory 5/16 22 3 117/8 3 13/18 Consult Factory 5/16 25 OFFICE/MANUFACTURING FACILITY•1375 SAMPSON AVE.•CORONA,CA 92879•PH'. 951.737.5599•FAX: 951.737.0330 MI CUSTOMER SERVICE•B00.786.5266 www.Mlco.com TOLCO www.tolco.com NIBCO Revision 10/24/2007 Fig. 24 - Hanger for CPVC Plastic Pipe Double Fastener Strap Type - Side Mount CC OS MED Size Range — 3/4" thru 2" CPVC pipe c Material — Pre Galvanized Steel Function — Intended to perform as a hanger/restrainer to support / >,_ I CPVC piping on in automatic fire sprinkler Fig. 24 systems. Can be installedion (----N---N\,— ason the top or on the bottom of a beam. The Fig. 24 can also function ?a restrainer to prevent the upward movement of the sprinkler head F during activation. '., ''• f r )* ! Approvals — Underwriters' Laboratories Listed in the USA(UL) and 1 i Canada(cUL)to support fire sprinkler piping. May be installed in wood using jt-,x' -• fasteners supplied with product, or into minimum 20 gauge steel using (2) '.. .y: 1/4" x 1" tek type screws. Meets and exceeds the requirements of NFPA 13, i 13R and 13D. • Features = Fig. 24 incorporates features which protect the pipe and • ease installation. The flared edge design protects the CPVC pipe from any rough surface. Easily attaches to the building structure using the two UL Listed hex head self threading screws*furnished with the product. It 1 i 8 is recommended that rechargeable electric drills fitted with a hex socket -' y'r attachment be used as installation tools. No impact tools (such as a ham- i --- )- mer)are allowed. Damage has been known to result from installations using I B` A impact type tools. No pre-drilling of a pilot hole in wood is required. ' / Finish — Pre-Galvanized Order By — Figure number and pipe size Hardened hex head self threading screw is furnished with the product and is the minimum fastener size acceptable. Dimensions •Weights CPVC Max.Hanger Fastener Hex Approx. Pipe Size A B C Spacing (Ft.) Head Size Wt./100 3/4 23/46 1%2 13/46 51/2 5/16 9 1 2% 13/46 1V16 6 5/16 9 11/4 3 11/2 13/48 61/2 5/16 11 11/2 31/a 1% 11/16 7 5/16 12 2 3t1/16 12%2 1V16 8 5/16 15 OFFICE/MANUFACTURING FACILITY•1375 SAMPSON AVE.•CORONA,CA 92879•PH: 951.737.5599•FAX: 951.737.0330 CUSTOMER SERVICE•800.786.5266 39 www.Iofco.coin (pit TOLCO www.toIco.com NIBCO Revision 1/11/2011 Fig. 28M - Offset Hanger and Restrainer for _ c UL US LISTED CPVC Plastic Pipe and IPS Pipe - Size Range — 3/4" thru 1-1/4" Material — Carbon Steel, Pre-Galvanized Function — Designed to be used as a hanger and restrainer for CPVC piping or A steel piping where the "stand-off" design will ease installation by eliminating the i),\ need for wood blocking. Features — A tiogi • Flared edge design protects CPVC pipe from any rough or abrasive surfaces • Unique snap-on design holds pipe firmly in place and allows retrofit type of installation• The "Stand-Off" design eliminates the need for wood block extension ' • Can be installed on horizontal or vertical piping regardless of mounting l surface orientation C • Attaches easily to wood structure with two hex head self-threading ���,--- screws furnished with product L 0B • Installs easily using rechargeable electrical driver with 5/16" extension socket eliminating impact tool damage to pipe • Attaches easily to steel, minimum 18 gauge with (2) 1/4" x 1" tek type self drilling tapping screws • cULus Listed as a hanger and a restrainer for fire sprinkler piping Installation Note — When installed in wood structural member and threads from the#10 x 1" screws are exposed, use FIG. 27B speed nut to secure Approvals — Underwriters' Laboratory Listed in the USA(UL)and Canada (cUL) to support automatic fire sprinkler systems. May be installed into wood using fas- - teners screws. Meets and exceeds the requirements of NFPA 13, 13R and 13D. Fig.28M satisfies the UL vertical restraint requirements where needed. Order By — Figure number and pipe size •Patent#7,744,042 �_ A „ „ I 4 \' TOLCO FIG. 27B n n "� (2) REQUIRED /AI I - a I'�`\ 11 I it II 4 4 4 . 3�' I ILA L--- - . -_---_J IVY I / c 1 t RESTRAINT HANGER AND RESTRAINT �` APPLICATION � rt, +. �_ 1171 RESTRAINT +;r II I,i II i Dimensions •Weights 1 Max. 2,1 Spacing ' • vqa� Pipe required per Approx TOLCO FIG. 27B `V, - Size A B C NFPA 13 for Wt./100 (1) REQUIRED " ICPVC plastic pipe HIGH SIDE 1Ly 3/4 2 3/16 3-5/16 5'-6" 9 OF HANGER - 1 2-1/8 3/16 3-1/2 6'-0" 12 DETAIL A 1-1/4 2-5/16 3/16 3-1/2 6'-6" 13 HANGER APPLICATION ® OFFICE/MANUFACTURING FACILITY•1375 SAMPSON AVE.•CORONA,CA 92879•PH: 951.737.5599•FAX 95'.737.033J CUSTOMER SERVICE•309.786.5366 www.roJco.com tICC1 I Fire & Buildingft Products vapid response" HOME FIRE SPRINKLER SYSTEM Technical Services:Tel:(800)381-9312/Fax:(800)791-5500 Figure 513D (13D) and 513D/R (13D/R) Riser Manifolds 1, 1-1/2, and 2 Inch (DN25, DN4O, and DN5O) For NFPA 13D/13R Residential Sprinkler Systems General Technical Description Data °' rt The Riser Manifolds described in this Approvals .- _ technical data sheet provide the nec- The Figure 513D (13D) and 513D/R essary waterflow alarm, pressure (13D/R) Riser Manifolds with a cover gauge,and drain equipment in a single tamper switch for the waterflow alarm assembly for use in NFPA 13D or 13R switch are UL Listed, ULC Listed, and residential sprinkler systems as fol- FM Approved. lows: The Figure 513D (13D) and 513D/R NFPA 13D (13D/R) Riser Manifolds without a 513D(13D) cover tamper switch for the waterflow • Figure 1 Inch 513D alarm switch are UL Listed and FM W (DN2Female Thread x Female Thread Approved. NFPA 13Dl13R Maximum Working Pressure 175 psi(12,1 bar) line prior to performing the alarm test. ' • Figure 513D/R(13D/R) Assemblf The second option is to install an In- 1-1/2 Inch (DN40) The maniold body of the Figure 513 is spector's Test Connection down- Male Thread x Female Thread ductile iron, whereas the manifold stream of the WaterflowAlarm Switch. Male Thread x Male Thread body of the Figure 13 is cast iron.The (3) Never remove any piping compo- • Figure 513D/R(13D/R) two assemblies are completely inter- nent nor correct or modify any piping 2 Inch (DN50) changeable in function, application, deficiencies without first depressuriz- Groove x Groove and end-to-end laying length. ing and draining the system. Male Thread x Groove Finish Step 1. Install the manifold body with The variety of sizes and end connec- Red painted. the flow arrow pointing in the down- tions allow cost effective and easy stream position using threaded con- transition to check valves, control Installation nections and/or listed mechanical valves, and system piping. The Riser grooved connections, as applicable. Manifolds may be installed in either the The Riser Manifolds may be installed Step 2. Connect the drain line, and horizontal (flow switch on top)or verti- in either the horizontal(flow switch on then close the drain valve. cal (flow going up). top) or vertical (flow going up). The inlet of the Riser Manifold may be di- Step 3. Refer to Figure 4 for wiring WARNING rectly connected to a shut-off control guidance. All wiring must be per- The Riser Manifolds described herein salve. formed in accordance with the Author- must be installed and maintained in ity Having Jurisdiction and/or the Na- compliance with this document, as NOTES tional Electrical Code. well as with the applicable standards (1) Where applicable pipe thread Step4. Place the system in service by of the National Fire Protection Asso- pp y ciation, in addition to the standards of sealant is r e applied sparingly. Use filling the system with water.When fill- any other authorities having jurisdic- of a non-hardening pipe thread sealant ing the system, partially open the con- tion. Failure to do so may impair the is recommended. trot valve to slowly fill the system. Fill- d performance of these devices. (2) Provisions for an alarm test Flow ing the system slowly will alhearm itch. must be made. The alarm test flow is damaging the waterflow alarm switch. The owner is responsible for maintain- to be through an orifice having a flow After the system is fully pressurized, ing their fire protection system and de- capacity equal to or smaller than the completely open the control valve. vices in proper operating condition. p tY q, p y p The installing contractor or sprinkler smallest orifice sprinkler cohe nsidered. Step 5. Secure all supply valves One of two options can be considered. manufacturer should be contacted The first option is to temporarily install open. with any questions. a test orifice in the outlet of the drain Page 1 of 6 APRIL, 2006 TFP960 Page 2 of 6 TFP96O NO. DESCRIPTION QTY. P/N I 7 El I 1"Manifold Body, 3-1/2" Female x Female NPT... 1 N/A (88,9 mm) 2 Waterflow Alarm Switch: (I LiVSR-SF modified with Paddle,UUFM 1 971-096-01 VSR-SF modified with Paddle and Cover Tamper Switch,ULC/FM 1 976-519-01 3 200 psU1400 kPa Water Pressure Gauge .. 1 2343 3 NM 2 NOTES: 1. Approximate weight,7.5 lbs.(3,4 kg). 2. ULC Listed Manifolds are equipped with WaterBow '=' Cover Tamper Switches installed internal 9-3/4" in to the Waterflow m Switches. (247,7 mm) I 1"1.11111111111111111111. 3. CH:Common Hardware t 3-5/8" 2-7/8" (92,1 mm) M,� 1 (73,0 mm) 1■ 3/4"NPT Drain Valve _. 4-1/2" (Normally Closed) (114,3 mm) 10" (254,0 mm) FIGURE 1 1 INCH(DN25)RISER MANIFOLD ASSEMBLY AND DIMENSIONS NO. DESCRIPTION QTY. P/N rr \_ 1 1-1/2"Manifold Body, 3-1/2" 11 Male x Female NPT 1 N/A (88,9 mm) I - Male x Male NPT 1 N/A 2 Waterfiow Alarm Switch: VSR-SF modified with Paddle,UUFM 1 971-096-00 - VSR-SF modified with Paddle and Cover Tamper , Switch,ULC/FM 1 976-519-02 3 300 psi/2000 kPa 3012 Water Pressure Gauge .. 1 2341 NOTES: Waterflow Mil 1 1. Approximate weight,8.7 lbs.(3,9 kg). 2. ULC Listed Manifolds are equipped with Cover Tamper SwitchesAlarm installed internal1819/8" 11111"...rellAh �� to the Waterflow Alarm Switches. (288,9 mm) 3. CH:Common Hardware 4-1/2" 5-3/8" (114,3 mm) (136,5 mm) AI I / ii, o i" NPT Drain Valve 2-1/8" (Normally Closed) (54,0 mm) 10"(254,0 mm) Male x Female NPT - Manifold 11-1/8"(282,6 mm) Male x Male NPT -- Manifold FIGURE 2 1-1/2 INCH(DN40)RISER MANIFOLD ASSEMBLY AND DIMENSIONS TFP96O Page 3 of 6 NO. DESCRIPTION OTY. PM I - 1 2"Manifold Body, 3-1/2" Groove x Groove 1 N/A (88,9 mm) Male NPT x Groove 1 N/A +I 1-1 1 2 Water(low Alarm Switch: '"- VSC with Paddle, UL/FM 1 976-357-01 VSC with Paddle and Cover Tamper Switch, ULC/FM 1 976-520-01 3 300 psi/2000 kPa 3 2 Water Pressure Gauge .. 1 2341 Optionally Waterfow NOTES: 1GSupply End Male NPTr1. Approximate weight,11.0 Ilu.(5,0 kg). Connection 2. ULC Listed Manifolds are equipped withIl_I' Cover Tamper Switches installed internal 12to the Waterow Alarm Switches. (304,8 mm) 3. CH:Common Hardware i i4-112" 5-7/16" NM (114,3 mm) (138,1 mm) .r � III 11 11 NPT Drain Valve FIGURE 3, (Normally Closed) (57,2 ' mm) 2 INCH(DN50)RISER MANIFOLD ASSEMBLY AND DIMENSIONS 13"(330,2 mm) Groove x Groove, - Male NPT x Groove result in operation of the associated recorded for the system when it was Care and alarms. Consequently, notification first installed. must be given to the owner and the fire Maintenance department, central station, or other Alarm Test Procedure With A Test signal station to which the alarms are Orifice(See Installation Note 2) The following inspection procedure connected, and notification must be must be performed as indicated,in ad- given to the building occupants. Step 1. Temporarily install a test ori- dition to any specific requirements of Before closing a fire protection system fice in the drain line outlet. the NFPA, and any impairment must control valve for inspection or mainte- Step 2. Fully open the drain valve. be immediately corrected. nance work on the fire protection sys- Make certain that drainage water will The owner is responsible for the in- tem that it controls,permission to shut not cause any damage or injury. spection, testing, and maintenance of down the effected fire protection sys- Step 3.Verify operation of the associ- their fire protection system and de- tern must first be obtained from the ated alarms. vices in compliance with this docu- proper authorities and all personnel ment, as well as with the applicable who may be affected by this action Step 3. Close the drain valve. standards of the National Fire.Protec- must be notified. tion Association (e.g., NFPA 25), in Step 4. Remove the test orifice from addition to the standards of any After placing a fire protection system the drain line outlet. authority having jurisdiction. The in- in service, notify the proper authorities stalling contractor or product manufac- and advise those responsible for moni- Alarm Test Procedure With An turer should be contacted relative to toring proprietary and/or central sta- Inspector's Test Connection (See any questions. Lion alarms. Installation Note 2) It is recommended that automatic Flow Test Procedure Step 1.Fully open the Inspector's Test sprinkler systems be inspected, Connection Valve. Make certain that tested, and maintained by a qualified Step 1. Fully open the drain valve. drainage water will not cause any dam- Inspection Service in accordance with Make certain that drainage water will age or injury. local requirements and/or national not cause any damage or injury. Step 2.Verify operation of the associ- codes. Step 2. Verify that the residual (flow- ated alarms. NOTES ing) pressure indicated by the pres- Step 3. Close the Inspector's Test No attempt is to be made to repair any sure gauge is no less that originally Connection Valve. Riser Manifold component in the field. recorded for the system when it was Only the pressure gauge or waterfiow first installed. alarm switch can be replaced. If any Step 3. Close the drain valve. - other problems are encountered the entire riser manifold must be replaced. Step 4.Verify that the static(not flow- ing) pressure indicated by the pres- The flow and alarm test procedure will sure gauge is no less that originally Page 4 of 6 TFP960 SWITCH TERMINAL CONNECTIONS UNINSULATED CLAMPING SEVERED LOOPED SECTION CAUTION: PLATE STRIPPED SINGLE An uninsulated section of a TERMINAL ENDS CONDUCTOR single conductor is not `�` SEPARATE the to bese looped around `� CONDUCTORS CLAMPING the terminal and serve h two PLATE separate connections.The TERMINAL wire must be severed to serve ' INCOMING as two separate connections, thereby providing supervision of the connection in the event `✓ that the wire becomes dislodged from the terminal. OUTGOING IMPROPER CONNECTION METHOD PROPER CONNECTION METHOD WATERFLOW SWITCH TYPICAL ELECTRICA CONNECTIONS CONTACTS SPDT(Form C) END OF LINE LOCAL RESISTOR CONTACT RATING .... 5A @ 125 VAC SIGNAL 2.5A@ 30 VDC DEVICE r,.L NC L NO NC NO NO• n NC f// COM COM COM CONTROL POWER PANEL NO FLOW NON-SUPERVISED STYLE B/CLASS B CONDITION CIRCUIT SUPERVISED CIRCUIT (SEE NOTE) NOTE: For supervised circuits,see"Switch Terminal Connections"above.The Waterflow Alarm Switch has two switches,one can be used to operate a central station,proprietary or remove signaling unit,while the other contact is used to operate a local audible or visual annunciator. COVER TAMPER SWITCH(ULC ASSEMBLIES ONLY) CONTACTS SPDT(Form C) CONTACT RATING .... 3A @ 250 VAC 5A @ 125 VAC 1mA @ 5 VDC min. NO\ • NC COM CONTACTS SHOWN WITH COVER IN PLACE FIGURE 4 WIRING GUIDANCE TFP96O Page 5 of 6 Limited Ordering Warranty Information Products manufactured by Tyco Fire& Riser Manifold: Building Products (TFBP) are war- Specify;Size(specify),Figure(specify ranted solely to the original Buyer for 513D or 513D/R, (specify connection ten(10)years against defects in mate- type inlet x outlet) Riser Manifold rial and workmanship when paid for (specify-without or with)a cover tam- and properly installed and maintained per switch for the waterflow alarm under normal use and service. This switch, P/N (specify). warranty will expire ten (10) years from date of shipment by TFBP. No NOTES warranty is given for products or corn- Orders for Figure 513D or 513D/R may ponents manufactured by companies be filled with a Figure 13D or 13D/R, not affiliated by ownership with TFBP respectively. The two assemblies are or for products and components which completely interchangeable in func- have been subject to misuse,improper tion, application, and end-to-end lay- installation, corrosion, or which have ing length. not been installed, maintained, modi- If a ULC Listing is required, the Riser fied or repaired in accordance with ap- Manifold must be ordered with a cover plicable Standards of the National Fire tamper switch for the waterflow alarm Protection Association, and/or the switch. standards of any other Authorities Having Jurisdiction. Materials found by TFBP to be defective shall be either UUULC/FM Assemblies repaired or replaced, at TFBP's sole With Cover Tamper Switch option. TFBP neither assumes, nor 1 Inch(DN25) authorizes any person to assume for it, FT x FT P/N 4085 anyother obligation in connection with 1-1/2 Inch(DN40) 9 MT x FT P/N 4088 the sale of products or parts of prod- 1-1/2 Inch(DN40) ucts.TFBP shall not be responsible for MT x MT P/N 4089 sprinkler system design errors or inac- 2 Inch(DN50)G x G P/N 4093 curate or incomplete information sup- 2 Inch(DN50) plied by Buyer or Buyer's repre- MTxG P/N4094 sentatives. In no event shall TFBP be liable, in UL/FM Assemblies contract, tort, strict liability or under Without Cover Tamper Switch - any other legal theory, for incidental, 1 Inch(DN25) FT x FT P/N 4047 indirect,special or consequential dam- 1-1/2 Inch(DN4o) ages, including but not limited to labor MT x FT P/N 4057 charges, regardless of whether TFBP 1-1/2 Inch(DN40) was informed about the possibility of MT x MT P/N 4058 damages, and no even such int shall 21nch(DN50) G x G P/N 4059 TFBP's liability exceed an amount 2 Inch(DN50) equal to the sales price. MT x G P/N 4064 The foregoing warranty is made in lieu of any and all other warranties. ex- Replacement Parts: press or implied. including warranties Specify: (description)for use with Fig- f merchantability and fitness for a nar- ure 513D, 513D/R, 13D, or 13D/R ticular oucpose. Riser Manifold, P/N (Ref. Figure 1, 2 This limited warranty sets forth the ex- or 2, as applicable). clusive remedy for claims based on failure of or defect in products, materi- als or components, whether the claim is made in contract, tort, strict liability or any other legal theory. This warranty will apply to the full ex- tent permitted by law.The invalidity,in whole or part, of any portion of this warranty will not affect the remainder. Page 6 of 6 TFP96O TYCO FIRE&BUILDING PRODUCTS,451 North Cannon Avenue,Lansdale, Pennsylvania 19446 BB-SC © 1 '= 2h/2 ' SLOW CLOSE Approved by:NYC Board l.# 9 -81-Stds &Apppeeals, Ca1.1G986-81-SM(175psi 720-83-SA(350&500 psi) BRONZE BUTTERFLY VALVE ONE-PIECE,FULL-PORT 175 PSI ,Q THREADED ENDS '" ,InrnoVIM DIMENSIONS .. 4-112 Valve Size ...I „,,g,. DIM 1" 1-1/4" 1-112" 2" 2-112 ( "K" � ■ +w:,��A 2.13 2,63 2.8H 325 4.13 a 1 °- tigilirl!=m464114 °"" 4 B' 316 3.31 3.41 3.63 3.82 B ENTRY) �`W. --^ C 1.56 1.94 2.19 2.75 3.19 I ,,,,, D 172 211 238 3.07 3.50 j' 4.16 4,16 4.51 4.76 4.66 li K .66 .73 73 .79 1.18 - C L L .83 90 10 1.41 1,29 M-40' 1,10 1.38 1.61 2.07 2.47 _ • �. . M-60'. .96 1.28 1.50 1.94 2.32 ,�y/,rlyna YI/ l.4r,✓.r N-40' 2,25 2.00 2.50 2.25 10,00 w° 1.19 1.25 1.41 1.69 1,75 ALL DIMENSIONS-INCHES D ; A 'Pertains to BB-SC100 only. 'Pertains to BB-SCS02 only. 'M-4 P ARE DIMENSIONS USING SCHEDULE 40 E Bp-S�+1®0 'M-8 PAPS DIMENSIONS USING SCHEDULE 80 Sizes 1", 1-1/4", t11-1/2", 2", 2-1/2" 'N-40 IS FLOW RESISTANCE EXPRESSEDIN EQUIVALENT LENGTH OF SCHEDULE 40 PIPE 'W IS THE WRENCH MAKE-UP LENGTH FEATURES 4-12°` •Slow opening and closing 0 Q - •Quarter turn operation illtAVIti- W 0 1& •Water Hammer elimination V.4 © /•Oponaliernaltmper switch " IrrY4*\(Indoor/Outdoor use). i '�d t - Signals disc movement II ■ Oa <" Ij' ,,, -Factory or Field installation Q IMMIIM J ✓* -10 Amp/115 VAC-60 Hz 'I ,� , -0.5Amp/28VDC rt • Grooved Ends Available inlit i d Sizes 2"and 2-1/2" litt 1- tj �W4 MATERIALS LIST ITEM PART MATERIALS ASTM SPEC. D1 Indicator Iron F0098P A 2 Housing Bronze ASTM 584 UNS BB-SCSO2 3 Body' C8440 (Includes Switch) 4 Handle Brass ASTM B176 UNS C85800 5 Disk ASTM A276, Stainless Steel Type 304 6 Disk Seal EPDM 7 Switch Housing Aluminum (BB-SCS02) The information presented on this sheet is correct at the time of publication. Milwaukee Valve reserves the right to change - design,and/or material specifications without notice. For the most current information access www.milwaukeevalve.com i MILWAUKEE VALVE WIRING DIAGRAM (SWITCH POSITION VALVE FULL OPEN) SWITCH 1: DUAL LEADS BLACK LISTED FIRE ALARM ,_I t. L TO NEXT INDICATOR CONTROL PANEL "`° OR SUPERVISORY CIRCUIT T WHITE ', — END OF LINE RESISTOR cam RED SWITCH 2:SINGLE LEADS ORANGE AUXILIARY ,c 6, EQUIPMENT VOLTAGE SLUE SOURCE oOM '°o YELLOW Green Lead provided is ground for switch housing Switch Rating: 10AMP/115 VAC .5 AMP/28 VDC Cap unused leads with wire nuts and tuck Inside junction box(not provided) NOTE:Valves incorporating supervisory tamper switches are for Indoor use only. SUPERVISORY TAMPER 1J2"ELECTRICAL SWITCH CONDUIT t 0 9( f rt7 RN mm 73 ICSto `. > t UL USTEO JJUUCTION SOX 4 Milwaukee Valve Company 2375 South Burrell Street Milwaukee,Wisconsin 53207-1592 Telephone 414/744-5240 ILWAUKEE VALVE FAX 414/744-5840 UL89_SC040300,air 4 t CO Worldwide www.tyco-fire.com Fire Protection Contacts Products _ Series TY-FRB — 2.8, 4.2, 5.6, and 8.0 K-Factor Upright, Pendent, and Recessed Pendent Sprinklers Quick Response, Standard Coverage General spheres.Although corrosion-resistant coated sprinklers have passed the N Description standard corrosion tests of the appli- cable approval agencies,the testing ispg The TYCO Series TY-FRB, 2.8, 4.2, not representative of all possible cor- . i� i 5.6, and 8.0 K-factor, Upright, Pen- rosive atmospheres. Consequently, dent, and Recessed Pendent Sprin- it is recommended that the end user 'II -11 klers described in this data sheet are be consulted with respect to the suit- f quick response, standard coverage, ability of these coatings for any given i decorative 3 mm glass bulb-type spray corrosive environment.The effects of ; sprinklers designed for use in light or ambient temperature,concentration of «. ordinary hazard,commercial occupan- chemicals, and gas/chemical velocity, cies such as banks, hotels,and shop- should be considered,as a minimum, ping malls. along with the corrosive nature of the chemical to which the sprinklers will be The recessed version of the Series TY- exposed. ' N. FRB Pendent Sprinkler,where applica- t ble,is intended for use in areas with a An intermediate level of the Series TY- finished ceiling.This recessed pendent FRB Pendent Sprinklers is detailed , sprinkler uses one of the following: in Technical Data Sheet TFP356, and / Sprinkler Guards are detailed in Tech- • A two-piece Style 10(1/2 inch NPT) nical Data Sheet TFP780. or Style 40(3/4 inch NPT)Recessed '; '. ' Escutcheon with 1/2 inch(12,7 mm)of . - recessed adjustment or up to 3/4 inch NOTICE (19,1 mm)of total adjustment from the The Series TY-FRB, 2.8, 4.2, 5.6, pF flush pendent position,or a and 8.0 K-factor, Upright, Pendent, • A two-piece Style 20(1/2 inch NPT) and Recessed Pendent Sprinklers Y described herein must be installed or Style 30(3/4 inch NPT)Recessed and maintained in compliance with Sprinkler Escutcheon with 1/4 inch(6,4 mm)of this document and with the applica- p recessed adjustment or up to 1/2 inch ble standards of the National Fire Pro- Identification (12,7 mm)of total adjustment from the tection Association, in addition to the flush pendent position. standards of any authorities having Number (SIN) The adjustment provided by the jurisdiction.Failure to do so may impair Recessed Escutcheon reduces the the performance of these devices. TY1131: Upright 2.8K, 1/2"NPT accuracy to which the fixed pipe drops The owner is responsible for maintain- TY1231: Pendent 2.8K,1/2"NPT to the sprinklers must be cut. ing their fire protection system and TY2131: Upright 4.2K,1/2"NPT Corrosion-resistant coatings, where devices in proper operating condition. TY2231: Pendent 4.2K,1/2"NPT applicable, are utilized to extend the The installing contractor or sprinkler TY3131: Upright 5.6K,1/2"NPT life of copper alloy sprinklers beyond manufacturer should be contacted with TY3231: Pendent 5.6K,1/2"NPT that which would otherwise be obtained any questions. TY4131: Upright 8.0K,3/4"NPT when exposed to corrosive atmo- TY4231: Pendent 8.0K,3/4"NPT TY4831: Upright 8.0K,1/2"NPT TY4931: Pendent 8.0K,1/2"NPT IMPORTANT Always refer to Technical Data Sheet TFP700 for the"INSTALLER WARNING"that provides cautions with respect to handling and instal- _ lation of sprinkler systems and com- ponents. Improper handling and installation can permanently dam- age a sprinkler system or its compo- - nents and cause the sprinkler to fail to operate in a fire situation or cause it to operate prematurely. Page 1 of 10 OCTOBER 2013 TFP171 TFP171 Page 2 of 10 *Temperature rating ** Pipe thread connections per 1 - Frame 3 - Sealing 5 - Compression is indicated on ISO 7-1 can be provided on ESCUTCHEON 2 - Button Assembly Screw Deflector. special request. PLATE SEATING 4 - Bulb 6 - Deflector* SURFACE 7 - Bushing — / Y :Yia7/161�rMEW— 1 � (11,1 NAL NOMINAL 2-1/4" '����MAKE-IN (57,2 mm)r�� 2-3/16"(55,6mm) 1 1-9/16" 411, (39,7 mm) II * 1/2"NPT** t WRENCH STYLE 10 or 20 2-7/8"(73,0 mm)DIA. —*- FLATS RECESSED UPRIGHT PENDENT ESCUTCHEON RECESSED PENDENT CROSS SECTION FIGURE 1 QUICK RESPONSE SERIES TY-FRB UPRIGHT(TY1131)AND PENDENT(TY1231)SPRINKLERS 2.8 K-FACTOR, 1/2 INCH NPT *Temperature rating ** Pipe thread connections per 1 - Frame 3 - Sealing 5 - Compression is indicated on ISO 7-1 can be provided on ESCUTCHEON 2 - Button Assembly Screw Deflector. special request. PLATE SEATING 4 - Bulb 6 - Deflector* SURFACE orr>r11 ��, 1 ill) ______ 7/16" � I�f„N: d (11,1 mm) 111 III ������ / i 2 NOMINAL 2-3/16" , MAKE-IN (55,6 mm) a II I I 2-3/16" 1-1/2" 1 4 (55,6 mm) i (38,1 mm) �j� r, 5 1/2" NPT** f WRENCH 01•1 STYLE 10 or 20 (73,0mm)D i II S�Yr.... 6 FLATS RECESSED UPRIGHT PENDENT ESCUTCHEON RECESSED PENDENT CROSS SECTION FIGURE 2 QUICK RESPONSE SERIES TY-FRB UPRIGHT(TY2131)AND PENDENT(TY2231)SPRINKLERS 4.2 K-FACTOR, 1/2 INCH NPT TFP171 Page 3 of 10 *Temperature rating ** Pipe thread connections per 1 - Frame 3 - Sealing 5 - Compression is indicated on ISO 7-1 can be provided on 2 - Button Assembly Screw Deflector. special request. ESCUTCHEON 4 - Bulb 6 - Deflector* PLATE SEATING SURFACE rG//71R\C / 1 7/16" �r2 P* 3 (11,1 mm) � �NOMINAL � 1 MI 2-3/16" ���-� A �� 2 MAKE-IN (55,6 mm}t4/11014 Alli�r 2-3/16" lii1-1/2" (55,6 mm) I (38,1 mm) a I�l 5 IIII 6* 1/2"NPT** WRENCH STYLE 10 or 20 - 2-7/8"(73,0 mm)DIA. - FLATS RECESSED UPRIGHT PENDENT ESCUTCHEON RECESSED PENDENT CROSS SECTION FIGURE 3 QUICK RESPONSE SERIES TY-FRB UPRIGHT(TY3131)AND PENDENT(TY3231)SPRINKLERS 5.6 K-FACTOR, 1/2 INCH NPT *Temperature rating ** Pipe thread connections per 1 - Frame 3 - Sealing 5 - Compression is indicated on ISO 7-1 can be provided on ESCUTCHEON 2 - Button Assembly Screw Deflector. special request. PLATE SEATING 4 - Bulb 6 - Deflector* SURFACE 1/2" _� . (12,7 mm) II 3 NOMINAL /_I } 2-5/16' -II �_� 2 MAKE-IN li I (58,7 mm) 41 0 2-1/4" 1-9/16" 4 (57,2 1 mm) ■ (39,7 mm) . 1 5 3/4"NPT** i WRENCH--_-_-_-_--. STYLE 30 or 40 ..--_-----_--. 6* FLATS RECESSED r 2-7/8"(73,0 mm)DIA. - UPRIGHT PENDENT ESCUTCHEON RECESSED PENDENT CROSS SECTION FIGURE 4 QUICK RESPONSE SERIES TY-FRB UPRIGHT(TY4131)AND PENDENT(TY4231)SPRINKLERS 8.0 K-FACTOR, 3/4 INCH NPT TFP171 Page 4 of 10 CEILING PLATE 1 - Frame 5 - Compression SEATING SURFACE 2 - Button Screw 1 3 - Sealing 6 - Deflector* r _—:- � $ r Assembly Y / �yt 3 4 Bulb 7/16"m) ��� 2-1/4" �� A Y {tt,t NAL 1 1 + (57,2 mm) .'4/1 •' 6 2 MAKIE-AI * Temperature rating is 1�/ 2-3/16" � 1-9/16" 4 indicated on Deflector. (55,6 mm) (39,7 mm) \ --. - s'�� 5 ** Pipe thread connections ,,,., per ISO 7-1 can be �` 6 * provided on special 1/2" NPT** t WRENCH request. FLATS UPRIGHT PENDENT CROSS SECTION FIGURE 5 QUICK RESPONSE SERIES TY-FRB UPRIGHT(TY4831)AND PENDENT(TY4931)SPRINKLERS 8.0 K-FACTOR, 1/2 INCH NPT Technical Design torque can distort the sprinkler Inlet with consequent leakage or impairment Data Criteria of the sprinkler. The TYCO Series TY-FRB, 2.8, 4.2, Do not attempt to compensate for Approvals insufficient adjustment in the Escutch- UL and C-UL Listed 5.6, and 8.0 K-factor, Upright, Pen- eon Plate by under-or over-tightening FM, LPCB,and NYC Approved dent,and Recessed Pendent Sprinklers the sprinkler. Re-adjust the position of Refer to Table A and B for complete are intended for fire protection sys- the sprinkler fitting to suit. approval information including terns designed in accordance with the corrosion-resistant status. standard installation rules recognized Series TY-FRB Upright and Pendent by the applicable Listing or Approval Sprinklers _ Maximum Working Pressure agency (such as, UL Listing is based The Series TY-FRB Pendent and Refer to Table C. on the requirements of NFPA 13, and Upright Sprinklers must be installed FM Approval is based on the require- in accordance with the following Discharge Coefficient ments of FM's Loss Prevention Data instructions. K=2.8 GPM/psiv2 (40,3 LPM/bar112) Sheets). Only the Style 10, 20, 30, or Step1.Install Pendent sprinklers in the K=4.2 GPM/psi1f2 (60,5 LPM/bar1'2) 40 Recessed Escutcheon, as applica- p K=5.6 GPM/psiv2 (80,6 LPM/bar112) ble,is to be used for recessed pendent Pendent position. Install upright sprin v2 v installations. klers in the upright position. K=8.0 GPM/psi (115,2 LPM/bar 2) Step 2. With pipe-thread sealant Temperature Rating Installation applied to the pipe threads, hand- Refer to Table A and B. tighten the sprinkler into the sprinkler The TYCO Series TY-FRB, 2.8, 4.2, fitting. Finishes 5.6,and 8.0 K-factor,Upright,Pendent, Sprinkler: Refer to Table D. Recessed and Recessed Pendent Sprinklersmust Step 3.Tighten the sprinkler into the Escutcheon: White Coated, Chrome be installed in accordance with this sprinkler fitting using only the W-Type 6 Plated, or Brass Plated. section. Sprinkler Wrench(Figure 14).With refer- ence to Figures 1 through 5, apply the Physical Characteristics General Instructions W-Type 6 Sprinkler Wrench to the sprin- Frame Bronze Do not install any bulb-type sprinkler if kler wrench flats. Button Brass/Copper the bulb is cracked or there is a loss Sealing Assembly Beryllium of liquid from the bulb.With the sprin- Series TY-FRB Recessed Pendent Nickel w/TEFLON kler held horizontally, a small air bub- Sprinklers Bulb Glass ble should be present. The diameter The Series TY-FRB Recessed Pendent Compression Screw Bronze of the air bubble is approximately 1/16 Sprinklers must be installed in accor- Deflector Copper/Bronze inch(1,6 mm)for the 135°F(57°C)and dance with the following instructions. Bushing(K=2.8) Bronze 3/32 inch(2,4 mm)for the 286°F(141°C) Step A.After installing the Style 10,20, Operation temperature ratings. 30, or 40 Mounting Plate, as applica- p A leak-tight 1/2 inch NPT sprinkler joint ble,over the sprinkler threads and with - The glass bulb contains a fluid that shold be obtained by applying a min- pipe-thread sealant applied to the pipe expands when exposed to heat.When imum to maximum torque of 7 to 14 threads, hand-tighten the sprinkler into the rated temperature is reached, the ft.-lbs. (9,5 to 19,0 Nm). A leak tight the sprinkler fitting. fluid expands sufficiently to shatter the 3/4 inch NPT sprinkler joint should be Step B.Tighten the sprinkler into the - glass bulb, allowing the sprinkler to obtained with a torque of 10 to 20 ft.- sprinkler fitting using only the W-Type activate and water to flow. lbs. (13,4 to 26,8 Nm). Higher levels of 7 Recessed Sprinkler Wrench (Figure TFP171 Page 5 of 10 SPRINKLER FINISH(See Note 5) K BULB LIQUID NATURAL CHROME SIGNAL*** FACTOR TYPE TEMPERATURE COLOR BRASS PLATED WHITE 135°F(57°C) Orange PENDENT 155°F(68°C) Red (TY1231) and 175°F(79°C) Yellow 1,2,3,4 UPRIGHT(TY1131) 200°F(93°C) Green 286°F(141°C) Blue 135°F(57°C) Orange 2.8 RECESSED 1 1/2"NPT PENDENT 55°F(68°C) Red (TY1231)* 175°F(79°C) Yellow Figure 6 • 200°F(93°C) Green 1,2,4 135°F(57°C) Orange RECESSED (PENDENT 155°F 68°C) Red (TY1231)** 175°F(79°C) Yellow Figure 7 200°F(93°C) Green 135°F(57°C) Orange PENDENT 155°F(68°C) Red (TY2231) and 175°F(79°C) Yellow UPRIGHT (TY2131) 200°F(93°C) Green 286`F(141°C) Blue 135°F(57°C) Orange 4.2 RECESSED °°155F 68C 1/2"NPT PENDENT ( ) Red 1,2 (TY2231)* 175°F(79°C) Yellow Figure 8 200°F(93°C) Green 135°F(57°C) Orange RECESSED )PENDENT (155°F 68°C Red (TY2231)** 175°F(79°C) Yellow Figure 9 200°F(93°C) Green NOTES: 1. Listed by Underwriters Laboratories,Inc.,(UL)as Quick Response Sprinklers. 2. Listed by Underwriters Laboratories,Inc.,for use in Canada(C-UL)as Quick Response Sprinklers. 3. Approved by Factory Mutual Research Corporation(FM)as Quick Response Sprinklers. 4. Approved by the City of New York under MEA 354-01-E. 5. Where Polyester Coated Sprinklers are noted to be UL and C-UL Listed,the sprinklers are UL and C-UL Listed as Corrosion-Resistant Sprinklers. *Installed with Style 10(1/2"NPT)or Style 40(3/4"NPT)3/4"Total Adjustment Recessed Escutcheon,as applicable. Installed with Style 20(1/2"NPT)or Style 30(3,'4"NPT) 1/2"Total Adjustment Recessed Escutcheon,as applicable. "*Frame and Deflector only.Listings and approvals apply to color(Special Order). N/A;Not Available TABLE A LABORATORY LISTINGS AND APPROVALS FOR 2.8 AND 4.2 K-FACTOR SPRINKLERS 15). With reference to Figures 1 to 4, apply the W-Type 7 Recessed Sprinkler Wrench to the sprinkler wrench flats. Step C. After ceiling installation and finishing, slide on the Style 10, 20,30, or 40 Closure over the Series TY-FRB Sprinkler and push the Closure over the Mounting Plate until its flange comes in contact with the ceiling. TFP171 Page 6 of 10 SPRINKLER FINISH(See Note 8) K TYPE TEMPERATURE BULB LIQUID NATURAL CHROME SIGNAL*** LEAD FACTOR COLOR BRASS PLATED WHITE COATED 135°F(57°C) Orange PENDENT 155°F(68°C) Red (TY3231) and 175°F(79°C) Yellow 1,2,3,4,5,6,7 1,2,3,5 UPRIGHT 200°F(93°C) Green (TY3131) 286°F(141'C) Blue 135°F(57°C) Orange RECESSED 155°F(68°C) Red 5.6 PENDENT 175°F(79°C) Yellow 1,2,4,5 N/A 1/2"NPT (TY3231)* Figure 10 200°F(93°C) Green 286°F(141°C) Blue 135°F(57°C) Orange RECESSED 155'F(68°C) Red PENDENT 175°F(79°C) Yellow 1,2,3,4,5 N/A (TY3231) Figura 11 200°F(93°C) Green 286°F(141°C) Blue 135°F(57°C) Orange PENDENT(TY4231) 155'F(68°C) Red and 175'F(79°C) Yellow 1,2,3,4,5,6,7 1,2,5 UPRIGHT 200°F(93°C) Green (TY4131) 286°F(141°C) Blue 135°F(57°C) Orange RECESSED 155°F(68°C) Red 8.0 PENDENT 175°F(79°C) Yellow 1,2,5 N/A 3/4"NPT (TY4231)* Figure 12 200°F(93`C) Green 286°F(141°C) Blue 135°F(57°C) Orange RECESSED 155°F(68°C) Red PENDENT 175°F(79°C) Yellow 1,2,3,5 N/A (TY4231)** Figure 13 200°F(93°C) Green 286°F(141°C) Blue 135°F(57°C) Orange PENDENT 155°F(68'C) Red 8.0 (TY4931) 1/2"NPT and 175°F(79°C) Yellow 1,2,4,5,6 1,2,5 UPRIGHT 200°F(93'C) Green (TY4831) 286°F(141°C) Blue NOTES: 1. Listed by Underwriters Laboratories,Inc,(UL)as Quick Response Sprinklers. 2. Listed by Underwriters Laboratories,Inc.,for use in Canada(C-UL)as Quick Response Sprinklers. 3. Approved by Factory Mutual Research Corporation(FM)as Quick Response Sprinklers. 4. Approved by the Loss Prevention Certification Board(LPCB Ref.No.007k/04)as Quick Response Sprinklers.However,LPCB does not rate the thermal sensitivity of recessed sprinklers. 5. Approved by the City of New York under MEA 354-01-E. 6. VdS Approved(For details,contact Tyco Fire Suppression&Building Products,Enschede,Netherlands,Tel.31-53-428-4444/Fax 31-53-428-3377.) 7. Approved by the Loss Prevention Certification Board(LPCB Ref.No.094a/06)as Quick Response Sprinklers. 8. Where Polyester Coated and Lead-Coated Sprinklers are noted to be UL and C-UL Listed,the sprinklers are UL and C-UL Listed as Corrosion-Resistant Sprinklers.Where Lead-Coated Sprinklers are noted to be FM Approved,the sprinklers are FM Approved as a Corrosion-Resistant Sprinklers. 'Installed with Style 10(1/2"NPT)or Style 40(3/4"NPT)3/4"Total Adjustment Recessed Escutcheon,as applicable. *`Installed with Style 20(1/2"NPT)or Style 30(3/4"NPT)1/2"Total Adjustment Recessed Escutcheon,as applicable. **Frame and Deflector only. Listings and approvals apply to color(Special Order). N/A:Not Available TABLE B LABORATORY LISTINGS AND APPROVALS FOR 5.6 AND 8.0 K-FACTOR SPRINKLERS TFP171 Page 7 of 10 SPRINKLER FINISH K TYPE NATURAL CHROME SIGNAL LEAD FACTOR BRASS PLATED WHITE COATED PENDENT(TY1231) and 2.8 UPRIGHT(TY1131) 1/2"NPT 175 PSI(12,1 BAR) N/A RECESSED PENDENT(TY1231) PENDENT(TY2231) and 4.2 UPRIGHT(TY2131) 1/2"NPT 175 PSI(12,1 BAR) N/A RECESSED PENDENT(TY2231) PENDENT(TY3231) 175 PSI and UPRIGHT(TY3131) 250 PSI(17,2 BAR) (12,1 BAR) 5.6 OR 175 PSI(12,1 BAR) 1/2"NPT RECESSED (SEE NOTE 1) PENDENT(TY3231) N/A PENDENT(TY4231) 175 PSI and (12,1 BAR) UPRIGHT(TY4131) 8.0 175 PSI(12,1 BAR) 3/4"NPT RECESSED N/A PENDENT(TY4231) PENDENT(TY4931) .0 175 PSI 1/28 NPT and 175 PSI(12,1 BAR) (12,1 BAR) UPRIGHT(TY4831) NOTES: 1. The maximum working pressure of 250 psi(17,2 bar)only applies to the Listing by Underwriters Laboratories Inc.(UL);the Listing by Underwriters Laboratories,Inc.for use in Canada(C-UL);and,the Approval by the City of New York. TABLE C - MAXIMUM WORKING PRESSURE Care and corrosive products of combustion, but tion Service in accordance with local have not operated,should be replaced requirements and/or national codes. Maintenance if they cannot be completely cleaned by wiping the sprinkler with a cloth or Care must be exercised to avoid dam- The TYCO Series TY-FRB must be by brushing it with a soft bristle brush. age to the sprinklers -before, during, and after installation.Sprinklers dam- maintained and serviced in accordance Care must be exercised to avoid dam- aged by dropping, striking, wrench with this section. age to the sprinklers- before, during, twist/slippage, or the like, must be Before closing a fire protection system and after installation.Sprinklers dam- replaced. Also, replace any sprinkler main control valve for maintenance aged by dropping, striking, wrench that has a cracked bulb or that has lost work on the fire protection system twist/slippage, or the like, must be liquid from its bulb. (Ref. Installation that it controls, obtain permission to replaced. Also, replace any sprinkler Section). shut down the affected fire protection that has a cracked bulb or that has lost systems from the proper authorities liquid from its bulb. (Ref. Installation Initial and frequent visual inspections of and notify all personnel who may be Section.) random samples are recommended for for the corrosion-resistant sprinklers to verify affected by this action. The owner is responsible the integrity of the corrosion-resistant Absence of the outer piece of an inspection,testing,and maintenance of material of construction. Thereafter, escutcheon, which is used to cover their fire protection system and devices annual inspections per NFPA 25 should a clearance hole, can delay sprinkler in compliance with this document, as suffice. operation in a fire situation. well as with the applicable standards of the National Fire Protection Associa- Inspections of corrosion-resistant Sprinklers which are found to be leak- tion (e.g., NFPA 25), in addition to the sprinklers are recommended at close _ ing or exhibiting visible signs of corro- standards of any other authorities hav- range, instead of from the floor level sion must be replaced. ing jurisdiction. Contact the installing per NFPA. Inspection at close range Automatic sprinklers must never be contractor or sprinkler manufacturer can better determine the exact sprin- painted, plated, coated, or other- regarding any questions. kler condition and the long-term integ- rity of the corrosion-resistant material, wise altered after leaving the factory. Automatic sprinkler systems are rec- which can be affected by the corrosive Modified sprinklers must be replaced. ommended to be inspected, tested, conditions present. Sprinklers that have been exposed to and maintained by a qualified Inspec- TFP171 Page 8 of 10 2-7/8" DIA. _ 2-7/8"DIA. 5/8±1/4" (73,0 mm) 3/4"(19,1 mm) 1/2±1/8 (73,0 mm) - 1/2"(12,7 mm (15,9±6,4 mm) 2-1/4"DIA. 1/4"(6,4 mm) (12,7±3,2 mm) 2-1/4"DIA. 1/4"(6,4 mm) / FACE OF (57,2 mm) / FACE OF r (57,2 mm) MOUNTING MOUNTING - SPRINKLER PLATE SPRINKLER PLATE FITTING FITTING / 1/8" / 1/8" (3,2 mm) (3,2 mm) 14 ` `��- MOUNTING i MOUNTING SURFACE � SURFACE iir ill CLOSURE SERIES 1-5/16"(33,3 mm) CLOSURE SERIES 1-5/16"(33,3 mm) TY-FRB 13/16"(20,6 mm) TY-FRB 1-1/16"(27,0 mm) FIGURE 6 FIGURE 7 SERIES TY-FRB RECESSED PENDENT SERIES TY-FRB RECESSED PENDENT WITH TWO-PIECE 3/4 INCH TOTAL ADJUSTMENT WITH TWO-PIECE 1/2 INCH TOTAL ADJUSTMENT STYLE 10 RECESSED ESCUTCHEON STYLE 20 RECESSED ESCUTCHEON 2.8 K-FACTOR, 112 INCH NPT 2.8 K-FACTOR, 1/2 INCH NPT 2-7/8" DIA 2-7/8"DIA. 5/8±1/4" (73,0 mm) 3/4"(19,1 mm) 1/2±1/8" (73,0 mm) 1/2"(12,7 mm) (15,9±6,4 mm) 2-1/4" DIA. 1/4" (6,4 mm) (12,7±3,2 mm) 2-1/4"DIA. 1/4"(6,4 mm) / FACE OF (57,2 mm) MOUNTING / FACE OF (57,2 mm) MOUNTING SPRINKLER PLATE SPRINKLER1/8" n--- PLATE FITTING FITTING 1/8" 2m (3,2 mm) (3,2 mm) al_ 7------------:-----13_ I mai ��� I MOUNTING gjir MOUNTING i. t SURFACE . SURFACE CLOSURE SERIES 1-1/4"(31,8 mm) CLOSURE SERIES 1-1/4"(31,8 mm) TY-FRB 3/4"(19,1 mm) TY-FRB 1"(25,4 mm) FIGURE 8 FIGURE 9 SERIES TY-FRB RECESSED PENDENT SERIES TY-FRB RECESSED PENDENT WITH TWO-PIECE 3/4 INCH TOTAL ADJUSTMENT WITH TWO-PIECE 1/2 INCH TOTAL ADJUSTMENT STYLE 10 RECESSED ESCUTCHEON STYLE 20 RECESSED ESCUTCHEON 4.2 K-FACTOR, 1/2 INCH NPT 4.2 K-FACTOR, 1/2 INCH NPT TFP171 Page 9 of 10 2-7/8"DIA. 2-7/8"DIA. _ (73,0 mm) 3/4"(19,1 mm) (73,0 mm) 5/8±1/4" 1/2±1/8" 1/2"(12,7 mm) (15,9±6,4 mm) 2-1/4"DIA. 1/4"(6,4 mm) (12,7±3,2 mm) 2-1/4"DIA. 1/4"(6,4 mm) / FACE OF (57,2 mm) MOUNTING / FACE OF (57,2 mm) 1 MOUNTING - SPRINKLER PLATE SPRINKLER PLATE FITTING FITTING / 1/8" / 1/8" (3,2 mm) (3,2 mm) j %i } ` ,,� i MOUNTING 1�, MOUNTING I SURFACE SURFACE =rwl_ II SERIES 1-1/4"(31,8 mm) SERIES 1-1/4"(31,8 mm) CLOSURE TY-FRB 3/4"(19,1 mm) CLOSURE TY-FRB 1"(25,4 mm) FIGURE 10 FIGURE 11 SERIES TY-FRB RECESSED PENDENT SERIES TY—FRB RECESSED PENDENT WITH TWO—PIECE 3/4 INCH TOTAL ADJUSTMENT WITH TWO—PIECE 1/2 INCH TOTAL ADJUSTMENT STYLE 10 RECESSED ESCUTCHEON STYLE 20 RECESSED ESCUTCHEON 5.6 K—FACTOR, 1/2!NCH NPT 5.6 K-FACTOR, 1/2 INCH NPT 2-7/8"DIA. 2-7/8"DIA. 5/8±1/4" (73,0 mm) 3/4"(19,1 mm) 1/2±1/8" (73,0 mm) 1/2"(12,7 mm) (15,9±6,4 mm) 2-1/4"DIA. 1/4"(6,4 mm) (12,7±3,2 mm) 2-1/4"DIA. 1/4"(6,4 mm) / ~ (57,2 mm) 1 / (57,2 mm) -� FACE OF MOUNTING / FACE OF MOUNTING SPRINKLER PLATE SPRINKLER PLATE FITTING FITTING 1/8" 1/8" / (3,2 mm) / (3,2 mm) I ; d I 1 ` F77%. 1 t + \ -47) ` MOUNTING MOUNTING SURFACE SURFACE I CLOSURE SERIES 1-5/16"(33,3 mm) CLOSURE SERIES 1-5/16"(33,3 mm) TY-FRB 13/16"(20,6 mm) TY-FRB 1-1/16"(27,0 mm) FIGURE 12 FIGURE 13 SERIES TY-FRB RECESSED PENDENT SERIES TY—FRB RECESSED PENDENT WITH TWO—PIECE 3/4 INCH TOTAL ADJUSTMENT WITH TWO—PIECE 1/2 INCH TOTAL ADJUSTMENT STYLE 40 RECESSED ESCUTCHEON STYLE 30 RECESSED ESCUTCHEON 8.0 K-FACTOR,3/4 INCH NPT 8.0 K—FACTOR,3/4 INCH NPT C� WRENCH RECESS WRENCH RECESS (END"A" USED FOR ror �„� 1/2"NPT MODELS) t WRENCH RECESS (END"B"USED FOR Na.... 3/4"NPT MODELS) PUSH WRENCH IN TO ENSURE ENGAGEMENT WITH SPRINKLER _ WRENCHING AREA FIGURE 14 FIGURE 15 W-TYPE 6 SPRINKLER W—TYPE 7 RECESSED WRENCH SPRINKLER WRENCH TFP171 Page 10 of 10 P/N 57 - XXX - X - XXX - I � SIN SPRINKLER TEMPERATURE FINISH RATINGS 330 2.8K UPRIGHT(1/2"NPT) TY1131 1 NATURAL BRASS 135 135°F(57°C) 331 2.8K PENDENT(1/2"NPT) TY1231 3 PURE WHITE 155 155°F(68°C) (RAL9010)` 340 4.2K UPRIGHT(1/2"NPT) TY2131 4 SIGNAL WHITE 175 175°F 79°C (RAL9003) ( ) 341 4.2K PENDENT(1/2"NPT) TY2231 5 JET BLACK 200 200°F(93°C) (RAL9005)" 370 5.6K UPRIGHT(1/2"NPT) TY3131 7 LEAD COATED 286 286°F(141°C) 371 5.6K PENDENT(1/2"NPT) TY3231 9 CHROME PLATED 390 8.0K UPRIGHT(3/4"NPT) TY4131 *Eastern Hemisphere sales only. "Available in only 2.8K,4.2K,and 391 8.0K PENDENT(3/4"NPT) TY4231 8.0K,155°F(68°C)and 200°F(93°C); requires lead time to manufacture. 360 8.0K UPRIGHT(1/2"NPT) TY4831° 361 8.0K PENDENT(1/2"NPT) TY4931° TABLE D SERIES TY-FRB PENDENT AND UPRIGHT SPRINKLERS PART NUMBER SELECTION - Ordering Procedure Contact your local distributor for availability. When placing an order, indicate the full product name and Part Number(P/N). Sprinkler Assemblies with NPT Thread Connections Specify: Series TY-FRB(Specify SIN), (specify K-factor), (specify Pendent or Upright) Sprinkler (specify) tempera- ture rating, (specify) finish or coating, P/N (specify from Table D) Recessed Escutcheon: Specify: Style (10, 20, 30, or 40) Recessed Escutcheon with (specify`) finish, P/N (specify') Sprinkler Wrench Specify: W-Type 6 Sprinkler Wrench, P/N 56-000-6-387 Specify: W-Type 7 Sprinkler Wrench, P/N 56-850-4-001 Refer to Technical Data Sheet TFP770 GLOBAL HEADQUARTERS)1400 Pennbrook Parkway,Lansdale,PA 19446 I Telephone+1-215-362-0700 Copyright©2013 Tyco Fire Products,LP. All rights reserved. Vico TEFLON is trademark of The DuPont Corporation. Fire Protection Products Worldwide www.tyco-fire.com Fire Protection Contacts Products Series TY-FRB — 5.6 K-factor Horizontal and Vertical Sidewall Sprinklers Quick Response, Standard Coverage General tained when exposed to corrosive at- mospheres. Although corrosion Descriptionresis- tant coated sprinklers have passed the standard corrosion tests of the appli- " The Series TY-FRB, 5.6 K-factor, Hor- cable approval agencies,the testing is -IF " izontal and Vertical Sidewall Sprin- not representative of all possible cor- klers described in this data sheet rosive atmospheres. Consequently, it �. - are quick response -standard cover- is recommended that the end user be l { 4 age, decorative 3 mm glass bulb type consulted with respect to the suitabil- - spray sprinklers designed for use in ity of these coatings for any given cor- rosive environment.The effects of am- . f light and ordinary hazard,banks, ho- bient temperature, concentration of t, telloccupancies such as banks, ho chemicals, and gas/chemical velocity, tels,shopping malls,etc.They are de- " signed for installation along a wall or should be considered, as a minimum, the side of a beam and just beneath a along with the corrosive nature of the smooth ceiling. Sidewall sprinklers are chemical to which the sprinklers will p commonly used instead of pendent or be exposed. upright sprinklers due to aesthetics or NOTICE building construction considerations, ..< where piping across the ceiling is not The Series TY-FRB Sprinklers de desirable. scribed herein must be installed and The recessed version of the Series maintained in compliance with this TY-FRB Horizontal Sidewall Sprin- document, as well as with the appli- kler is intended for use in areas with cable standards of the National Fire a finished wall. It uses a two-piece Protection Association, in addition to Style 10 Recessed Escutcheon with the standards of any other authorities - 1/2 inch(12,7 mm)of recessed adjust- having jurisdiction. Failure to do so ment or up to 3/4 inch(19,1 mm)of to- may impair the performance of these tal adjustment from the flush sidewall devices. position, or a two-piece Style 20 Re- The owner is responsible for main- cessed Escutcheon with 1/4 inch (6,4 taining their fire protection system mm) of recessed adjustment or up to and devices in proper operating con- 1/2 inch (12,7 mm)of total adjustment dition. Contact the installing contrac- from the flush sidewall position. The tor or sprinkler manufacturer with any adjustment provided by the Recessed questions. Technical Escutcheon reduces the accuracy to which the fixed pipe nipples to the Sprinkler Data sprinklers must be cut. Corrosion resistant coatings, where Identification Approvals applicable, are utilized to extend the UL and C-UL Listed. life of copper alloy sprinklers beyond Numbers FM, LPCB,and NYC Approved. that which would otherwise be ob- (Refer to Table A for complete approv- TY3331 Horizontal al information including corrosion re- IMPORTANT TY3431 Vertical sistant status.) Always refer to Technical Data Maximum Working Pressure Sheet TFP700 for the "INSTALLER Refer to Table B. WARNING" that provides cau- Discharge Coefficient tions with respect to handling K=5.6 GPM/psi1'2(80,6 LPM/bar1i2) and installation of sprinkler sys- - tems and components. lmprop- Temperature Ratings er handling and installation can Refer to Table A. permanently damage a Sprin- Finishes - Icier system or its components Sprinkler: Refer to Table C. and cause the sprinkler to fail Recessed Escutcheon:Signal or Pure to operate in a fire situation or cause White,Jet Black,Chrome Plated,or it to operate prematurely. Brass Plated. Page 1 of 6 FEBRUARY 2014 TFP176 TFP176 Page 2 of 6 1 Frame DEFLECTOR Installation - 2 - Button HAT �^ 5 The Series TY-FRB, 5.6 K-factor, Hori- 3 - Sealing zontal and Vertical Sidewall Sprinklers Assembly must be installed in accordance with 4 - Bulb this section. 5 Compression General Instructions Screw 6 - Deflector* 6*/ 4 2 3 1 Do not install any bulb type sprin- kler if the bulb is cracked or there is a loss of liquid from the bulb. With the 9/16" WRENCH 1/2"** sprinkler held horizontally, a small air (14,3 mm) FLATS NPT bubble should be present. The diam- eter of the air bubble is approximately 1r/ / 1/16 inch(1,6 mm)for the 135°F(57°C) to 3/32 inch (2,4 mm) for the 286°F '��iO�- ��' (141°C)temperature ratings. .12 �' A leak tight 1/2 inch NPT sprinkler joint • should be obtained with a torque of 7 1-13/16" 7/16. to 14 ft.-lbs. (9,5 to 19,0 Nm). Higher '—(46,0 mm) (11,1 mm) levels of torque may distort the sprin- NOMINAL kler and cause leakage or impairment CENTERLINE MAKE-IN of the sprinkler. OF SPRINKLER WATERWAY Do not attempt to make-up for insuf- 1-1/2" ficient adjustment in the escutcheon (38,1 mm)--- plate by under-or over-tightening the *Temperature rating 2 3/16" sprinkler. Readjust the position of the is indicated on (55,6 mm) sprinkler fitting to suit. Deflector. Series TY-FRB Horizontal and STYLE ESCUTCHEON Vertical Sidewall Sprinkler ** Pipe thread 10 or 20 — PLATE SEATING Installation connections per RECESSEDI SURFACE ISO 7-1 can be ESCUTCHEON The Series TY-FRB Horizontal and provided on Vertical Sidewall Sprinklers must be special request. lifdlifilitilIii�� installed in accordance with the fol- • -7/873,0 m IA lowing instructions. 2-7/8"DIA. Step 1. Horizontal sidewall sprinklers � are to be installed in the horizontal po- sition with their centerline of waterway perpendicular to the back wall and parallel to the ceiling.The word "TOP" on the Deflector is to face towards the ceiling. Vertical sidewall sprinklers are to be FIGURE 1 installed in the pendent or upright po- 5.6 K-FACTOR QUICK RESPONSE sition with the arrow on the Deflector SERIES TY-FRB HORIZONTAL SIDEWALL(TY3331)SPRINKLERS pointing away from the wall. Step 2. With pipe thread sealant ap- Physical Characteristics hye Bronze Design plied to the pipe threads, hand tighten Fr Button Brass/Copper the sprinkler into the sprinkler fitting. Sealing Assembly Beryllium Nickel w/ Criteria Step 3. Tighten the sprinkler into the TEFLON sprinkler fitting using only the W-Type Bulb Glass The Series TY-FRB,5.6 K-factor, Hori- 6 Sprinkler Wrench (Ref. Figure 5), Compression Screw Bronze zontal and Vertical Sidewall Sprinklers With reference to Figure 1 or 2,the W- HSW Deflector Bronze are intended for fire protection sys- Type 6 Sprinkler Wrench is to be ap- VSW Deflector Copper tems designed in accordance with the standard installation rules recognized plied to the wrench flats. Operation by the applicable Listing or Approval agency (e.g., UL Listing is based on The glass bulb contains a fluid which the requirements of NFPA 13, and FM expands when exposed to heat.When Approval is based on the requirements - the rated temperature is reached, the of FM's Loss Prevention Data Sheets). fluid expands sufficiently to shatter Only the Style 10 or 20 Recessed Es- the glass bulb, allowing the sprinkler cutcheon, as applicable, is to be used to activate and water to flow. for recessed horizontal installations. TFP776 Page 3 of 6 Series TY-FRB Recessed *Temperature ** Pipe thread 1 - Frame 4 - Bulb 7 - Ejection Horizontal Sidewall Sprinkler rating is connections 2 - Button 5 - Compression Spring _ Installation indicated on per ISO 7-1 can 3 - Sealing Screw The Series TY-FRB Recessed Hori- Deflector. be provided on Assembly 6 - Deflector* zontal Sidewall Sprinklers must be special request. installed in accordance with this section. ARROW MUST Step A. Recessed horizontal sidewall POINT ANDAW BEY i'� sprinklers are to be installed in the7l1m FROMPE horizontalposition with their center- LA ESCUTCHEON TIN NOMINAL (11,1 PERPENDICULAR O PLATE SEATING TO THE BACK line of waterway perpendicular to the SURFACE NPT** MAKE-IN WALL SURFACE back wall and parallel to the ceiling. The word "TOP" on the Deflector is to I j 6* face towards the ceiling. + '— �"— - } Step B.After installing the Style 10 orI \ ��- F pW p 5 20 Mounting Plate over the sprinkler threads,hand tighten the sprinkler into 2-3/16" 1 2-3/16" 4 the sprinkler fitting. (55,6 mm) I (55,6 mm) Step C. Tighten the sprinkler into the 1-1/2" II /-I 2 sprinkler fitting using only the W-Type (38,1 mm) WRENCH 7 Recessed Sprinkler Wrench (Ref. FLATS 7 3 Figure 6). With reference to Figure 1, the W-Type 7 Recessed Sprinkler 1 Wrench is to be applied to the sprin- SHOWN SHOWN CROSS kler wrench flats. PENDENT UPRIGHT SECTION Step D. After the ceiling has been in- FIGURE 2 stalled or the finish coat has been ap- 5.6 K-FACTOR QUICK RESPONSE plied, slide on the Style 10 or 20 Clo- SERIES TY-FRB VERTICAL SIDEWALL(TY3431)SPRINKLERS sure over the Series TY-FRB Sprinkler and push the Closure over the Mount- ing Plate until its flange comes in con- if they cannot be completely cleaned The owner is responsible for the in- tact with the ceiling. by wiping the sprinkler with a cloth or spection, testing, and maintenance by brushing it with a soft bristle brush. of their fire protection system and de- ,. Care and Care must be exercised to avoid dam- vices in compliance with this docu- age to the sprinklers before, during, ment, as well as with the applicable Maintenance and after installation. Sprinklers dam- standards of the National Fire Pro- tectaged by dropping, striking, wrench ion Association (e.g., NFPA 25), in - The Series TY-FRB, 5.6 K-factor, Hori- twist/slippage, or the like, must be addition to the standards of any oth- zontal and Vertical Sidewall Sprinklers replaced. Also, replace any sprinkler er authorities having jurisdiction. The must be maintained and serviced in that has a cracked bulb or that has installing contractor or sprinkler man- accordance with this section. lost liquid from its bulb. (Ref. Installa- ufacturer should be contacted relative Before closing a fire protection sys- tion Section). to any questions. tern main control valve for mainte- The owner must assure that the sprin- It is recommended that automatic nance work on the fire protection sys- klers are not used for hanging any ob- sprinkler systems be inspected, test- tern that it controls,permission to shut jects and that the sprinklers are only ed, and maintained by a qualified In- down the affected fire protection sys- cleaned by means of gently dusting local spection Service in accordance with tern must be obtained from the prop- with a feather duster; otherwise, non- local requirements and/or national er authorities and all personnel who operation in the event of a fire or inad- codes. may be affected by this action must vertent operation may result. be notified. Frequent visual inspections are rec- Absence of an escutcheon, which is ommended to be initially performed used to cover a clearance hole, may for corrosion resistant coated sprin- delay the time to sprinkler operation in klers, after the installation has been a fire situation. completed,to verify the integrity of the Sprinklers that are found to be leaking corrosion resistant coating. Thereaf- or exhibiting visible signs of corrosion ter, annual inspections per NFPA 25 must be replaced. should suffice; however, instead of in- specting from the floor level,a random Automatic sprinklers must never be sampling of close-up visual inspec- painted, plated, coated or other- tions should be made, so as to better wise altered after leaving the factory. determine the exact sprinkler condi- Modified sprinklers must be replaced. tion and the long term integrity of the Sprinklers that have been exposed to corrosion resistant coating, as it may corrosive products of combustion, but be affected by the corrosive condi- have not operated,should be replaced tions present. TFP176 Page 4 of 6 5/8±1/4" Gv (15,9±6,4 mm) MOUNTING FACE OF WRENCH RECESS SURFACE _ SPRINKLER (END"A"USED FOR FITTING 1/2"NPT MODELS) FIGURE 5 CLOSURE , W-TYPE 6 SPRINKLER WRENCH 2-7/8"DIA. (73,0 mm) SERIES TY-FRB 2-1/4"DIA. WRENCH (57,2 mm) RECESS MOUNTING PLATE W41 41, y 1/8" 14114 (3,2 mm) 1-1/4"(31,8 mm) 3/4"(19,1 mm) PUSH WRENCH 3/4"(19,1 mm) 1/4"(6,4 mm) IN EE ENGAGEMENT FIGURE 3 WITH SPRINKLER SERIES TY-FRB RECESSED HORIZONTAL SIDEWALL SPRINKLER WRENCHING AREA WITH TWO-PIECE 3/4 INCH TOTAL ADJUSTMENT FIGURE 6 STYLE 10 RECESSED ESCUTCHEON W-TYPE 7 RECESSED SPRINKLER WRENCH 1/2±1/8" (12,7±3,2 mm) MOUNTING FACE OF SURFACE ---- SPRINKLER FITTING CLOSURE 2-7/8"DIA. SERIES (73,0 mm) TY-FRB 2-1/4"DIA. (57,2 mm) MOUNTING PLATE is 1/8" (3,2 mm) 1-1/4"(31,8 mm) 1/2"(12,7 mm) 1"(25,4 mm) 1/4"(6,4 mm) FIGURE 4 SERIES TY-FRB RECESSED HORIZONTAL SIDEWALL SPRINKLER WITH TWO-PIECE 1/2 INCH TOTAL ADJUSTMENT STYLE 20 RECESSED ESCUTCHEON TFP176 Page 5 of 6 SPRINKLER FINISH(See Note 11) K TYPE TEMP. LIQUID D NATURALLB BRASS PLATED POLYESTER*** LEAD COATED 135'F(57°C) Orange HORIZ. 155°F(68°C) Red SIDEWALL 175°F(79°C) Yellow 1,2,3,4,9,10 I,2,3,9 1,2,3,9 (TY3331) 200°F(93°C) Green 286°F(141°C) Blue 5.6 RECESSED 135°F(57°C) Orange 1/2" HORIZ. 155°F(68°C) Red NPT SIDEWALL 175°F(79°C) Yellow 1,2,4,9, 10 1,2,9 N/A (TY3331)* Figure 3 200°F(93°C) Green RECESSED 135°F(57°C) Orange HORIZ. 155°F(68°C) Red SIDEWALL 1. 2,3,4,9 N/A (TY3331)** 175°F(79°C) Yellow Figure 4 200°F(93°C) Green VERTICAL 135°F(57°C) Orange SIDEWALL 155°F(68°C) Red 5.6 (TY3431) 1/2" Installed 175°F(79°C) Yellow 5,6,7,8,9 5,6, 7,9 NPT Pendent ( ) or 200C 93°200°F° Green Upright 286°F(141°C) Blue NOTES: 1. Listed by Underwriters Laboratories,Inc.(UL)as Quick Response Sprinklers for use in Light and Ordinary Hazard Occupancies at a 4 to 12 inch(100 to 300 mm)top of deflector to ceiling distance. 2. Listed by Underwriters Laboratories Inc.for use in Canada(C-UL)as Quick Response Sprinklers for use in Light and Ordinary Hazard Occupancies at a 4 to 12 inch(100 to 300 mm)top of deflector to ceiling distance. 3. Approved by Factory Mutual Research Corporation(FM)as Quick Response Sprinklers for use in Light Hazard Occupancies at a 4 to 12 inch(100 to 300 mm)top of deflector to ceiling distance. 4. Approved by the Loss Prevention Certification Board(LPCB Ref.No.007a/04)at a 4 to 6 inch(100 to 150 mm)top of deflector to ceiling distance.The LPC does not rate the thermal sensitivity of horizontal sidewall sprinklers. 5. Listed by Underwriters Laboratories,Inc.as Quick Response Sprinklers for use in Light and Ordinary Hazard Occupancies. 6. Listed by Underwriters Laboratories for use in Canada(C-UL)as Quick Response Sprinklers for use in Light and Ordinary Hazard Occupancies. 7. Approved by Factory Mutual Research Corporation(FM)as Quick Response Sprinklers for use in Light Hazard Occupancies. 8. Approved by the Loss Prevention Certification Board(LPCB Ref.No.094a/06&007a/04)as Quick Response Sprinklers. 9. Approved by the City of New York under MEA 354-01-E. 10. Approved by the Loss Prevention Certification Board(LPCB Ref.No.094a/06)at a 4 to 6 inch(100 to 150 mm)top of deflector to ceiling distance.The LPC does not rate the thermal sensitivity of horizontal sidewall sprinklers. 11. Where Polyester Coated and Lead Coated Sprinklers are noted to be UL and C-UL Listed,the sprinklers are UL and C-UL Listed as Corrosion Resis- tant Sprinklers.Where Lead Coated Sprinklers are noted to be FM Approved,the sprinklers are FM Approved as Corrosion Resistant Sprinklers. *Installed with Style 10(1/2"NPT)3/4"Total Adjustment Recessed Escutcheon. **Installed with Style 20(1/2"NPT)1/2"Total Adjustment Recessed Escutcheon. ***Frame and deflector only. TABLE A LABORATORY LISTINGS AND APPROVALS TFP176 Page 6 of 6 SPRINKLER FINISH K TYPE NATURAL BRASS CHROME PLATED POLYESTER LEAD COATED HORIZONTAL SIDEWALL 250 PSI(17,2 BAR) (TY3331) Or 175PSI(12.1 BAR) 5.6 RECESSED HORIZ. 1/2 SIDEWALL(TY3331) (SEE NOTE 1) NPT VERTICAL SIDEWALL 175 PSI(12,1 BAR) (TY3431) NOTES: 1. The maximum working pressure of 250 psi(17,2 bar)only applies to the Listing by Underwriters Laboratories, Inc.(UL);the Listing by Underwriters Laboratories,Inc.for use in Canada(C-UL);and,the Approval by the City of New York. TABLE B MAXIMUM WORKING PRESSURE P/N 57 - XXX - X - XXX � I SIN SPRINKLER TEMPERATURE FINISH RATINGS 378 HORIZONTALSIDEWALL TY3331 1 NATURALBRASS 135 135°F(57°C) 375 VERTICAL SIDEWALL TY3431 3 PURE WHITE(RAL9010)* 155 155°F(68°C) POLYESTER 4 SIGNAL WHITE(RAL9003) 175 • 175°F(79°C) POLYESTER • • 5 JET BLACK(RAL9005)" 200 200°F(93°C) POLYESTER 7 LEAD COATED 286 286°F(141°C) 9 CHROME PLATED Eastern Hemisphere sales only. Available in 155°F(68°C)or 200°F (93°C)temperature rating only. TABLE C PART NUMBER SELECTION SERIES TY-FRB HORIZONTAL AND VERTICAL SIDEWALL SPRINKLERS Ordering Sprinkler Assemblies with NPT Recessed Escutcheon Thread Connections: Specify:Style(10 or 20) Recessed Es- Procedure Specify: Series TY-FRB (specify SIN), cutcheon with (specify') finish, P/N (specify K-factor), (specify) Horizontal (specify*). Contact your local distributor for avail- Sidewall or Vertical Sidewall Sprinkler, Refer to Technical Data Sheet TFP770 ability. When placing an order, indi- Standard Response, Standard Coy- cate the full product name and Part erage, (specify) temperature rating, Sprinkler Wrench Number(P/N). (specify) finish or coating, P/N (spec- Specify: W-Type 6 Sprinkler Wrench, ify from Table C) P/N 56-000-6-387 Specify: W-Type 7 Sprinkler Wrench, P/N 56-850-4-001 GLOBAL HEADQUARTERS 1 1400 Pennbrook Parkway,Lansdale,PA 19446 I Telephone+1-215-362-0700 Copyright©2013 Tyco Fire Products,LP. All rights reserved. TEFLON is trademark of The DuPont Corporation. Fire Protection Products Worldwide www.tyco-fire.com Fire Protection Contacts Products - RAPID RESPONSE Series LFII Residential Sprinklers 4.9 K-factor Pendent Wet Pipe and Dry Pipe Systems General Escutcheon reduces the accuracy to which the pipe drops to the sprinklers Description must be cut. The Series LFII Residential Sprinklers The TYCO RAPID RESPONSE have been designed with heat sensi- "ij Series LFII Residential Pendent tivity and water distribution charac- and Recessed Pendent Sprinklers teristics proven to help in the control (TY2234) are decorative, fast of residential fires and to improve the response, frangible bulb sprinklers chance for occupants to escape or be designed for use in residential occu- evacuated. pancies such as homes, apart- ments, dormitories,and hotels.When Dry Pipe System Application aesthetics and optimized flow charac- The Series LFII Residential Pendent teristics are the major consideration, and Recessed Pendent Sprinklers the Series LFII Residential Sprinklers offers a laboratory approved option (TY2234)should be the first choice. for designing dry pipe residential Sprinkler rinklers sprinkler systems, whereas, most The Series LFII Residential Sprinklers residential sprinklers are laboratory Identification are intended for use in the following approved for wet systems only.scenarios: Number (SIN) Through extensive testing, it has been • wet and dry pipe residential sprin- determined that the number of design TY2234 kler systems for one-and two-family sprinklers(hydraulic design area)for dwellings and mobile homes per the Series LFII Residential Pendent Technical - NFPA 13D and Recessed Pendent Sprinklers • wet and dry pipe residential sprin- (TY2234) need not be increased kler systems for residential occu- over the number of design sprinklers Data - pancies up to and including four (hydraulic design area) as specified stories in height per NFPA 13R for wet pipe sprinkler systems, as is Approvals accustomed for density/area sprinkler UL Listed for use with wet pipe and • wet and dry pipe sprinkler systems systems designed per NFPA 13. dry pipe systems for the residential portions of any Consequently, the Series LFII C-UL Listed for use only with wet pipe occupancy per NFPA 13 Residential Sprinklers offer the systems The recessed version of the Series features of non-water filled pipe in NSF Certified to NSF/ANSI 61 LFII Residential Sprinklers is intended addition to not having to increase the for use in areas with finished ceilings. number of design sprinklers(hydraulic For details on these approvals, refer It employs a two-piece Style 20 design area)for systems designed to to the Design Criteria section. Recessed Escutcheon.The Recessed NFPA 13, 13D,or 13R. Escutcheon provides 1/4 inch(6,4 mm) Maximum Working Pressure of recessed adjustment or up to 1/2 NOTICE 175 psi(12,1 bar) inch (12,7 mm) of total adjustment The Series LFII Residential Pendent and Discharge Coefficient from the flush ceilingposition. The K=4.9 GPM/psi1/2(70,6 LPM/bar1/2) adjustment provided by the Recessed Recessed Pendent Sprinklers(TY2234) described herein must be installed and Temperature Rating maintained in compliance with this 155°F(68°C)or 175°F(79°C) document and the applicable stan- IMPORTANT dards of the National Fire Protection Finishes Always refer to Technical Data Association, in addition to the stan- Natural Brass Sheet TFP700 for the "INSTALLER dards of any authorities having jurisdic- Pure or Signal White WARNING" that provides cautions tion. Failure to do so may impair the Chrome Plated with respect to handling and instal- performance of these devices. Physical Characteristics lotion of sprinkler systems and The owner is responsible for main- Frame Brass components. Improper handling and taming their fire protection system and Button l Sealing Assembly Berylper lium installation can permanently damage devices in proper operating condi- Nickel w/TEFLON a sprinkler system or its components tion. Contact the installing contractor Bulb(3 mm) Glass - and cause the sprinkler to fail to or sprinkler manufacturer with Compression Screw Bronze operate in a fire situation or cause it any questions. Deflector Bronze to operate prematurely. Election Spring Stainless Steel Page 1 of 6 FEBRUARY 2014 TFP400 TFP400 Page 2 of 6 7/16"(11,1 mm) ESCUTCHEON 1/2" Components: NOMINAL NPT PLATE SEATING 2-7/8"DIA. 1 - Frame MAKE-IN SURFACE (73,0 mm) 2 - Button i 3 Sealing Assembly 1 y (1/ - 4 Bulb iMIE_ 5 Compression 2 A ! 21/4" •���- Sefew r I MEW i (57,2 mm 6 Deflector' 3 + • t _ I ) rar j_iI 4 I 1-5/8" STYLE 20 kii (41,3 mm) WRENCH �� RECESSED 5- —_ :®I FLATS Temperature ME . I . ESCUTCHEON rating is 6* -At--_ 11 indicated on Deflector. CROSS SECTION PENDENT RECESSED PENDENT FIGURE 1 RAPID RESPONSE SERIES LFII RESIDENTIAL PENDENT AND RECESSED PENDENT SPRINKLERS(TY2234) 2-7/8"DIA. fao, (73,0 mm)7/16±1/8" 1/2"(12,7 mm) (11,1±3,2 mm) 2-1/4"DIA. 1/4"(6,4 mm) RECESS FACE OF (57,2 mm) END"A"USED SPRINKLER MOUNTING /TRENCHFOR TY2234) FITTING PLATE FIGURE 3 •� W-TYPE 6 SPRINKLER WRENCH . 11, WRENCH MOUNTING RECESS SURFACE 1/8" . (3,2 mm) CLOSURE TY2234 11054-1P- 1-3/8"(34,9 mm) 1-18"(28,6 mm) FIGURE 2 STYLE 20 RECESSED ESCUTCHEON FOR USE WITH THE Of RAPID RESPONSE SERIES LFII RESIDENTIAL PENDENT SPRINKLER ter' ' (TY2234) PUSH WRENCH IN TO ENSURE Operation Residential Sprinkler Design Guide ENGAGEMENT A When conditions exist that are WITH SPRINKLER The glass bulb contains a fluid that outside the scope of the provided WRENCHING AREA expands when exposed to heat.When criteria, refer to the Residential FIGURE 4 the rated temperature is reached,the Sprinkler Design Guide TFP490 for W-TYPE 7 RECESSED fluid expands sufficiently to shatter the the manufacturer's recommendations SPRINKLER WRENCH glass bulb, allowing the sprinkler to that may be acceptable to the local activate and flow water. authority having jurisdiction. Ceiling Types Smooth flat horizontal, or beamed, or System Types sloped, in accordance with the 2013 Design Per the UL Listing, wet pipe and dry Edition of NFPA 13D, 13R, or 13 as pipe systems may be utilized. Per the applicable. Criteria C-UL Listing, only wet pipe systems may be utilized. Hydraulic Design The TYCO RAPID RESPONSE Refer to Technical Data Sheet TFP485 (NFPA 13D and 13R) - Series LFII Residential Pendent for the use of residential sprinklers in For systems designed to NFPA and Recessed Pendent Sprinklers residential dry pipe systems. 13D or NFPA 13R, the minimum (TY2234)are UL and C-UL Listed for required sprinkler flow rates are _ installation in accordance with this section. TFP400 Page 3 of 6 given in Tables A and B as a func- Step C. Tighten the sprinkler into the tion of temperature rating and the Installation sprinkler fitting using only the W-Type 7 maximum allowable coverage areas. The TYCO RAPID RESPONSE Recessed Sprinkler Wrench (Figure 4). The sprinkler flow rate is the minimum Series LFII Residential Pendent With reference to Figure 1, apply the required discharge from each of the and Recessed Pendent Sprinklers W-Type 7 Recessed Sprinkler Wrench total number of"design sprinklers"as (TY2234) must be installed in accor- to the sprinkler wrench flats. specified in NFPA 13D or NFPA 13R. The number of "design sprinklers" dance with this section: Step D. After the ceiling has been specified in NFPA 13D and 13R for wet installed or the finish coat has been pipe systems is to be applied when General Instructions applied, slide on the Style 20 Closure designing dry pipe systems. Do not install any bulb type sprin- over the Series LFII Residential kler if the bulb is cracked or there is a Sprinkler and push the Closure over the Hydraulic Design loss of liquid from the bulb. With the Mounting Plate until its flange comes in (NFPA 13) sprinkler held horizontally, a small air contact with the ceiling. For systems designed to NFPA 13, bubble should be present.The diam- the number of design sprinklers is eter of the air bubble is approximately to be the four most hydraulically 1/16 inch(1,6 mm). demanding sprinklers.The minimum A leak-tight 1/2 inch NPT sprinkler required discharge from each of the joint should be obtained by applying four sprinklers is to be the greater of a minimum-to-maximum torque of 7 the following: to 14 ft.-lbs. (9,5 to 19,0 Nm). Higher • The flow rates given in Tables A levels of torque can distort the sprin- or B as a function of temperature kler Inlet with consequent leakage or rating and the maximum allowable impairment of the sprinkler. coverage area. Do not attempt to compensate • A minimum discharge of 0.1 gpm/ft2 for insufficient adjustment in an over the "design area" comprised Escutcheon Plate by under- or over- of the four most hydraulically tightening the sprinkler. Re-adjust the demanding sprinklers for actual position of the sprinkler fitting to suit. coverage areas protected by the four sprinklers. Series LFII Residential Pendent Sprinklers The number of "design sprinklers" The Series LFII Residential Pendent specified in NFPA 13 for wet pipe Sprinklers must be installed in accor- systems is to be applied when dance with the following instructions. designing dry pipe systems. Step 1. Install pendent sprinklers in Dry Pipe System Water Delivery the pendent position with the deflector When using the Series LFII Residential parallel to the ceiling. Sprinklers(TY2234) in dry pipe sprin- Step 2. With pipe thread sealant kler systems, the time for water applied to the pipe threads, hand- delivery must not exceed 15 seconds tighten the sprinkler into the sprinkler for the most remote operating fitting. sprinkler. Step 3. Tighten the sprinkler into Obstruction to Water Distribution the sprinkler fitting using only the Sprinklers are to be located in accor- W-Type 6 Sprinkler Wrench (Figure dance with the obstruction rules 3). With reference to Figure 1, apply of NFPA 13D, 13R, and 13 as appli- the W-Type 6 Sprinkler Wrench to the cable for residential sprinklers as wrench flats. well as with the obstruction criteria Series LFII Residential Recessed described within the Technical Data Pendent Sprinklers Sheet TFP490. The Series LFII Residential Recessed Operational Sensitivity Pendent Sprinklers must be installed Sprinklers are to be installed with a in accordance with the following deflector-to-ceiling distance of 1-1/4 to instructions. 4 inches. Step A. Install recessed pendent sprinklers in the pendent position with Sprinkler Spacing the deflector parallel to the ceiling. The minimum spacing between sprin- Step B. After installing the Style 20 klers is 8 feet(2,4 m). The maximum Mounting Plate over the sprinkler spacing between sprinklers cannot threads and with pipe thread sealant exceed the length of the coverage area(Table A or B)being hydraulically applied to the pipe threads, hand calculated(e.g.,maximum 12 feet for a tighten the sprinkler into the sprinkler 12 ft.x 12 ft.coverage area, or 20 feet fitting. for a 20 ft. x 20 ft.coverage area). TFP400 Page 4 of 6 WET PIPE SYSTEM Minimum Flow and Residual Pressurelb,c) MaxOrdinary Temp.Rating Intermediate Temp.Rating Coverage 155°F(68°C) 175°F(79°C) Minimum Area(a) - Deflector to Installation Spacing Ft.x Ft. Flow Pressure Flow Pressure Ceiling Type Ft. (m x m) GPM PSI GPM PSI (m) (L/min) (bar) (L/min) (bar) 12 x 12 13 7.0 13 7.0 Smooth (3,7 x 3,7) (49,2) (0,48) (49,2) (0,48) Ceilings 14x14 13 7.0 13 70 linches 4 inches (4,3 x 4,3) (49,2) (0,48) (49,2) (0,48) Recessed Beamed using Style 20 16 x 16 13 7.0 13 7.0 Escutcheon or 8 (4,9 x 4,9) (49,2) (0,48) (49,2) (0,48) Ceilings per non-recessed (2,4) NFPA 13D per NFPA 13D, 18 x 18 17 12.0 17 12.0 or 13R 13R,or 13 (5,5 x 5,5) (64,3) (0,83) (64,3) (0,83) 1-1/4 to 1-3/4 inches below 20 x 20 20 16.7 20 16.7 bottom of (6,1 x 6,1) (75,7) (1,15) (75,7) (1,15) beam. (a) For coverage area dimensions less than or between those indicated,use the minimum required flow for the next highest coverage area for which hydraulic design criteria are stated. (b) Requirement is based on minimum flow in GPM(LPM)from each sprinkler.The associated residual pressures are calculated using the nominal K-factor.Refer to Hydraulic Design under the Design Criteria section. (c) For NFPA 13 residential applications,the greater of 0.1 gpm/ft2 over the design area of the flow in accordance with the criteria in this table must be used. TABLE A WET PIPE SYSTEM SERIES LFII RESIDENTIAL PENDENT AND RECESSED PENDENT SPRINKLERS(TY2234) NFPA 13D, 13R,AND 13 HYDRAULIC DESIGN CRITERIA DRY PIPE SYSTEM Maximum Minimum Flow and Residual Pressuretb,c) Coverage Ordinary Temp.Rating Intermediate Temp.Rating Area(a) 155°F(68°C) 175°F(79°C) Minimum Ft.x Ft. Deflector to Installation Spacing (m z m) Flow Pressure Flow Pressure Ceiling Type Ft. GPM PSI GPM PSI (m) (L/min) (bar) (L/min) (bar) 12 x 12 13 7.0 13 7.0 Smooth (3,7 x 3,7) (49,2) (0,48) (49,2) (0,48) Ceilings 14 x 14 14 8.2 14 8.2 1-1/4 to 4 inches (4,3 x 4,3) (53,0) (0.57) (53,0) (0,57) Recessed Beamed using Style 20 16 x 16 15 9.4 15 9.4 Ceilings per Escutcheon or 8 (4,9 x 4,9) (56,8) (0,65) (56,8) (0,65) NFPA 13D non-recessed (2,4) 18 x 18 18 13.5 18 13.5 or 13R per NFPA 13D, (5,5 x 5,5) (68,1) (0,93) (68,1) (0,93) 1-1/4 to 1-3/4 13R,or 13 inches below 20 x 20 21 18.4 21 18.4 bottom of (6,1 x 6,1) (79,5) (1,27) (79,5) (1,27) beam. (a) For coverage area dimensions less than or between those indicated,use the minimum required flow for the next highest coverage area for which hydraulic design criteria are stated. (b) Requirement is based on minimum flew in GPM(LPM)from each sprinkler.The associated residual pressures are calculated using the nominal K-factor.Refer to Hydraulic Design under the Design Criteria section. (c) For NFPA 13 residential applications,the greater of 0.1 gpm/ft2 over the design area of the flow in accordance with the criteria in this table must be used. TABLE B DRY PIPE SYSTEM SERIES LFII RESIDENTIAL PENDENT AND RECESSED PENDENT SPRINKLERS(TY2234) NFPA 13D, 13R,AND 13 HYDRAULIC DESIGN CRITERIA TFP400 Page 5 of 6 Care and Automatic sprinkler systems are recommended to be inspected, Maintenance tested, and maintained by a qualified Inspection Service in accordance with The TYCO RAPID RESPONSE Series local requirements and/or national LFII Residential Pendent and Recessed codes. Pendent Sprinklers(TY2234) must be maintained and serviced in accordance Limited with this section: Before closing a fire protection system Warranty main control valve for maintenance work on the fire protection system that For warranty terms and conditions, it controls, permission to shut down visit www.tyco-fire.com. the affected fire protection system must be obtained from the proper Ordering authorities and notify all personnel who may be affected by this action. Procedure Absence of the outer piece of an escutcheon, which is used to cover Contact your local distributor for a clearance hole, can delay sprinkler availability. When placing an order, operation in a fire situation. indicate the full product name and Part The owner must assure that the Number(P/N). sprinklers are not used for hanging Sprinkler Assembly any objects and that the sprinklers Specify: Series LFII(TY2234), K=4.9, are only cleaned by means of gently Residential Pendent Sprinkler, dusting with a feather duster; other- (specify)temperature rating, (specify) wise, non-operation in the event of finish, P/N (specify): a fire or inadvertent operation may 155°F(68°C) result. Natural Brass P/N 51-201-1-155 Sprinklers which are found to be Pure White(RAL 9010)* P/N 51-201-3-155 leaking or exhibiting visible signs of Signal White(RAL 9003) P/N 51-201-4.155 Chrome Plated P/N 51-201-9-155 corrosion must be replaced. 175°F(79°C) Automatic sprinklers must never be Natural Brass P/N 51-201-1-175 painted, plated, coated, or other- Pure White(RAL 9010)* P/N 51-201-3-175 wise altered after leaving the factory. Signal White(RAL 9003) P/N 51-201-4-175 Modified sprinklers must be replaced. Chrome Plated P/N 51-201-9-175 Sprinklers that have been exposed to 'Eastern Hemisphere sales only corrosive products of combustion, but Recessed Escutcheon have not operated,should be replaced Specify: Style 20 Recessed if they cannot be completely cleaned Escutcheon with (specify*)finish, P/N by wiping the sprinkler with a cloth or (specify') by brushing it with a soft bristle brush. Care must be exercised to avoid Refer to Technical Data Sheet TFP770 damage to the sprinklers - before, Sprinkler Wrench during, and after installation. Specify: W-Type 6 Sprinkler Wrench, Sprinklers damaged by dropping, P/N 56-000-6-387 striking,wrench twist/slippage,or the Specify: W-Type 7 Sprinkler Wrench, • like, must be replaced. Also, replace P/N 56-850 4 001 any sprinkler that has a cracked bulb or that has lost liquid from its bulb. (Ref. Installation Section.) The owner is responsible for the inspection, testing, and mainte- nance of their fire protection system and devices in compliance with this document, as well as with the appli- cable standards of the National Fire Protection Association (e.g., NFPA 25),in addition to the standards of any authorities having jurisdiction. Contact the installing contractor or sprinkler manufacturer regarding any questions. TFP400 Page 6 of 6 GLOBAL HEADQUARTERS 11400 Pennbrook Parkway,Lansdale,PA 19446 I Telephone+1-215-362-0700 Copyright©2014 Tyco Fire Products,LP. All rights reserved. tricr3 TEFLON is trademark of The DuPont Corporation. Fire Protection Products J • A, The Symbol of Protection PBA-AC & MBA-DC ( UL,ULC,and FM Approved Sizes Available: 6"(150mm),8"(200mm)and 10"(250mm) Voltages Available: 24VAC 120VAC '� 12VDC(10.2 to 15.6)Polarized a •t r y " 24VDC(20.4 to 31.2)Polarized 1 il� Service Use: Fire Alarm {I General Signaling Burglar Alarm � P ,� Environment: Indoor or outdoor use(See Note 1) � . -40°to 150°F(-40°to 66°C) (Outdoor use requires weatherproof backbox.) Termination: AC Bells-4 No. 18 AWG stranded wires U C M DC Bells-Terminal strip * E Finish: Red powder coating Optional: Model BBK-1 weatherproof backbox Model BBX-1 deep weatherproof backbox These vibrating type bells are designed for use as fire,burglar or general Notes: signaling devices. They have low power consumption and high decibel 1. Minimum dB ratings are calculated from integrated sound pressure ratings.The unit mounts on a standard 4"(101mm)square electrical box measurements made at Underwriters Laboratories as specified in UL for indoor use or on a model BBK-1 weatherproof backbox or BBX-1 Standard 464. UL temperature range is-30°to 150°F(-34°to 66°C). deep weatherproof backbox for outdoor applications. Weatherproof 2. Typical dB ratings are calculated from measurements made with a backbox model BBK-1,Stock No.1500001. conventional sound level meter and are indicative of output levels in an actual installation. 3. ULC only applies to MBA DC bells. Size inches Voltage Model Stock Current Typical dB at Minimum dB at (mm) Number Number (Max.) 10 ft.(3m)(2) 10 ft.(3m)(1) 6(150) 12VDC MBA126 1750070 .12A 85 76 8(200) 12VDC MBA128 1750080 .12A 90 77 10(250) 12VDC MBAI210 1750060 .12A 92 78 6(150) 24VDC MBA246 1750100 .06A 87 77 8(200) 24VDC MBA248 1750110 .06A 91 79 10(250) 24VDC MBA2410 1750090 .06A 94 80 6(150) 24VAC PBA246 1806024* .17A 91 78 8(200) 24VAC PBA248 1808024* .17A 94 77 10(250) 24VAC PBA2410 1810024* .17A 94 78 6(150) 120VAC PBA1206 1806120* .05A 92 83 8(200) 120VAC PBA1208 1808120* .05A 99 84 10(250) 120VAC PBA12010 1810120* .05A 99 86 All DC bells are polarized and have built-in transient protection. *Does not have ULC listing. ! \WAR l[ I�G na In outdoor or wet installations,bell must be mounted with weatherproof backbox,BBK-1 or BBX-1.Standard electrical boxes will not provide a weatherproof enclosure.If the bell andlor assembly is exposed to moisture,it may fail or create an electrical hazard. Potter Electric Signal Company,LLC•2081 Craig Road,St.Louis.MO,63146-4161•Phone:800-325-3936/Canada 888-882-1833•www.pottersignal.com PRINTED IN USA MPG #5400776-REV Y PAGE 1 OF 2 5/08 R POTT R The Symbol of Protection PBA-AC & MBA-DC w Bells Dimensions Inches(mm) Wiring(rear view) Fig. 1 Fig.3 A.C.BELLS [ ].) werrE(m) DLACKQ WHITE(OW) (250) s„ FROM CONTROL IPIpili (200) 6' PA_VEL OR (i50) PRHCFIDING BELL Tf) �I� BLACK(OUT) CAUTION' WHEN ELECTRICAL SUPERVISION IS REQUIRED USE IN AND OUT LEADS AS SHOWN. 2 11/16" (68) DWCI'7e-1 NOTES: 1.WHEN USING AC BELLS,TERMINATE EACH EXTRA WIRE SEPARATELY AFTER LAST BELL. 2 END.OR.ILNE RESISTOR IS NOT REQUIRED ON AC BELLS. DW&naa Weatherproof Backbox Dimensions Inches(mm) Fig.2 FA(P Box has one threaded 112"conduit entrance Ili H �IN 1 D s 3:4- s1 ) 11271 J,_-.- To Next Device or End-of-Line 4 •� Resistor 3 3/8" 15/S" _ (R6) (41) ......_ 4 I/4" y aoe) Installation DW4a]/62 I. The bell shall be installed in accordance with NFPA 13,72,or local AHJ.The top of the device shall be no less than 90"AFF and not less than 6"below the ceiling. 2. Remove the gong. / 3. Connect wiring(see Fig.3). 1:1:11)11111'e 4. Mount bell mechanism to backbox(bell mechanism must be D mounted with the striker pointing down). 5. Reinstall the gong(be sure that the gong positioning pin,in the mechanism housing,is in the hole in the gong). 6. Test all bells for proper operation and observe that they can b-. BBX-1 be heard where required(bells must be heard in all areas as designated by the authority having jurisdiction). 1' d "' -'oF ' .1. , Failure to install striker down will prevent bell from operating. PR,N 1ED IN USA MED. 5400776-REV'S P%GE 2 OF 2 POTTER VSR VANE TYPE WATERFLOW The Symbol of Protection ALARM SWITCH WITH RETARD r e UL,CUL and CSFM Listed,FM Approved,LPCBApproved,For "mot x� hr1 a CE Marked(EN12259-5)/VdS Approved model use VSR-EU ltt Service Pressure: 450 PSI(31 BAR)-UL • Flow Sensitivity Range for Signal: 4-10GPM(15-38LPM)-UL Maximum Surge: 18 FPS(5.5 m/s) tiContact Ratings: Two sets of SPDT(Form C) •NI1 10.0 Amps at 125/250VAC 2.0 Amps at 30VDC Resistive 10 mAmps min.at 24VDC Conduit Entrances: Two knockouts provided for 1/2"conduit. ' Individual switch compartments suitable for dissimilar voltages. Environmental Specifications: • NEMA 4/1P54 Rated Enclosure suitable for indoor or outdoor use with factory installed gasket and die-cast housing when used with appropriate conduit fitting. WARN. • Temperature Range: 40°F-120°F,(4.5°C-49°C)-UL A ;affit s Non-corrosive sleeve factory installed in saddle. • Installation must be performed by qualified personnel and in Service Use: accordance with all national and local codes and ordinances. Automatic Sprinkler NFPA-l3 • Shock hazard.Disconnect power source before servicing.Serious One or two family dwelling NFPA-I3D injury or death could result Residential occupancy up to four stories NFPA-13R • Risk of explosion.Not for use in hazardous locations.Serious National Fire Alarm Code NFPA-72 injury or death could result Optional: Cover Tamper Switch Kit,stock no.0090148 Replaceable Components:Retard/Switch Assembly,stock no. 1029030 General Information The Model VSR is a vane type waterflow switch for use on wet Note:Do not leave cover off for an extended period of time. sprinkler systems. It is UL Listed and FM Approved for use on steel Drain the system and drill a hole in the pipe using a hole saw in a slow pipe;schedules 10 through 40,sizes 2"thru 8"(50 mm thru 200 nun). speed drill.(see Fig. 1) LPC approved sizes are 2"thru 8"(50 mm thru 200 mm). See Ordering Clean the inside pipe of all growth or other material for a distance equal Information chart. to the pipe diameter on either side of the hole. The VSR may also be used as a sectional waterflow detector on Roll the vane so that it may be inserted into the hole; do not bend or large systems. crease it. Insert the vane so that the arrow on the saddle points in the The VSR contains two single pole,double throw,snap action switches direction of the waterflow.Install the saddle strap and tighten nuts and an adjustable,instantly recycling pneumatic retard. The switches alternately to required torque.(see Fig. 1).The vane must not rub the are actuated when a flow of 10 GPM (38 LPM) or more occurs inside of the pipe or bind in any way. downstream of the device. The flow condition must exist for a period of time necessary to overcome the selected retard period. Specifications subject to change without notice. Enclosure Ordering Information The VSR switches and retard device are enclosed in a general purpose, die-cast housing. The cover is held in place with two tamper resistant Nominal Pipe Size Model Part Number screws which require a special key for removal. A field installable 2" DN50 VSR-2 1144402 cover tamper switch is available as an option which may be used 2 1/2" DN65 VSR-2 1/2 1144425 to indicate unauthorized removal of the cover. See bulletin number 3" DN80 VSR-3 1144403 5401103 for installation instructions of this switch. Installation (See Fig. 1) 3 1/2" VSR-3 1/2 1144435 These devices may be mounted on horizontal or vertical pipe. On 4" DNI00 VSR-4 1144404 horizontal pipe they should be installed on the top side of the pipe 5" - VSR-5 1144405 where they will be accessible. The device should not be installed 6" DN150 VSR-6 1144406 within 6" (15 cm) of a fitting which changes the direction of the waterflow or within 24" (60 cm)of a valve or drain. 8" DN200 VSR-8 1144408 Potter Electric Signal Company,LLC•2081 Craig Road,St.Louis,MO,63146-4161•Phone:800-325-3936/Canada 888-882-1833•www.pottersignal.com PRINTED 1N USA MFG.#5401146-REV K PAGE 1 OF 3 12/08 VANE TYPE WATERFLOW The Symbol of Protection ALARM SWITCH WITH RETARD Fig.1 Fig.2 Switch Terminal Connections °A011tiTIENI Clamping Plate Terminal ur,°x„ , uR ron ��3 in lr ry � vw i�-une°Lrnrs pl Irlj .0 N°r LEAVE m.Ckl-ro m rEQr'�°meuvt,. !3'�'1 ,: tweoeEwo°oEr°re x ALSEALUMS. /\I fir.• =0.umiurvNAX `�\i/�` �ii nNon�F• It° USFQ)SItl111 E]AOAPiEftC AS SHOWN ABIRE .f.� ° 91LL �� ARROWIII MOW ON PIM% ON SADDLE b*Wli 5" An uninsulated section of a single conductor O. �Y should not be looped around the terminal and 11111111111111 °°"'"°"'"" serve as two separate connections. The wire must ormsrrE uwEcr,ow be severed,thereby providing supervision of the ,„,"°. \ connection in the event that the wire become WATTMOW \ j dislodged from under the terminal. Failure to sever the wire may render the device inoperable risking severe property damage and loss of life. J (Flowing water activates device in one direction only.) Installation Requirements A CAUTION Model Nominal Pipe Size Nominal Pipe O.D. Hole Size U-Bolt Nuts Torque Waterliow switches that are monitoring wet pipe inch mm inch mm inch mm ft-lb n-m sprinkler systems shall not be used as the sole VSR-2 2 DN50 2.375 60.3 initiating device to discharge AFFF, deluge, or chemical suppression systems. Waterllow switches VSR-212 21/2 2.875 73.0 1.25+.125/462 33.0±2.0 used for this application may result in unintended VSR-2 1/2 212 DN65 3.000 76.1 discharges caused by surges,trapped air,or short retard times. VSR-3 3 DN80 3.500 88.9 - VSR-312 312 4.000 1016 20 27 VSR-4 4 DN100 4.500 114.3 2.00±.125 50.8±2.0 VSR-5 5 5.563 141.3 VSR-6 6 DN150 6.625 168.3 VSR-8 8 DN200 8.625 219.1 Fig.3 Typical Electrical Connections Fig.4 fig.5 NEca IVE Breakout thin section of cover when wiring both To remove knockouts:Place screwdriver at Ea I II BELL w,L switches from one conduit entrance. inside edge of knockouts,not in the center. AC '' I ' r In" I . . . POSITIVE DC OR HOT AC 11 NNW 1 +D I ti :: ,' �' WAJERFLOW ZONE �- -w— ., III ON FlliE PANEL I ` J UUUU \�V :_ l` ,11147,11 Notes: ��--.. � : 1. The Model VSR has two switches,one can be used 1`7". .' �, Nio to operate a central station,proprietary or remote 'J 111 0'il ,i'-'"- signaling unit,while the other contact is used toz. � ,,,,,,y11 l='� j operate a local audible or visual annunciator. VNII �d�„ Pe /) II 2. A condition of LPC Approval of this product 'r i "- is that the electrical entry must be sealed to �exclude moisture. �O 3. For supervised circuits see "Switch Terminal - Connections"drawing and caution note(Fig.2). PRINTED IN USA MFG.45401146-REV K PAGE 2 OF 3 12/08 SR VANE TYPE POTTER E WATERFLOW `. The Symbol of Protection ALARM SWITCH WITH RETARD Compatible Pipe Note:For copper or plastic pipe use Model VSR-CF. Model Nominal Pipe Nominal Pipe Pipe Wall Thickness Size O.D. Schedule 10(UL) Schedule 40(UL) BS-1387(LPC) DN(VDS) inch mm inch mm inch mm inch mm inch nun inch mm VSR-2 2 DN50 2.375 60.3 0.109 2.77 0.154 3.91 0.142 3.6 0.091 2.3 VSR-2 1/2 212 2.875 73.0 0.120 3.05 0.203 5.16 VSR-2 1/2 DN65 3.000 76.1 0.142 3.6 0.102 2.6 VSR-3 3 DN80 3.500 88.9 0.120 3.05 0,216 5.49 0.157 4.0 0.114 2.9 VSR-3 1/2 312 4.000 101.6 0.120 3.05 0.226 5.74 VSR-4 4 DN100 4.500 114.3 0.120 3.05 0.237 6.02 0.177 4.5 0.126 3.2 VSR-5 5 5.563 141.3 0.134 3.40 0.258 6.55 VSR-6 6 DN150 6.625 168.3 0.134 3.40 0.280 7.11 0.197 5.0 0.157 4.0 VSR-8 8 DN200 8.625 219.1 0.148 3.76 0.322 8.18 0.248 6,3 0.177 4.5 Testing The frequency of inspection and testing for the Model VSR and its associated protective monitoring system should be in accordance with applicable NFPA Codes and Standards and/or the authority having jurisdiction(manufacturer recommends quarterly or more frequently). If provided,the inspector's test valve,that is usually located at the end of the most remote branch line,should always be used for test purposes.If there are no provisions for testing the operation of the flow detection device on the system,application of the VSR is not recommended or advisable. A minimum flow of 10 GPM(38 LPM)is required to activate this device. Maintenance Inspect detectors monthly for leaks. If leaks are found,replace the detector. The VSR waterfiow switch should provide years of trouble-free service. The retard and switch assembly are easily field replaceable.In the unlikely event that either component does not perform properly,please order replacement retard switch assembly stock#1029030.There is no maintenance required,only periodic testing and inspection. Removal - • To prevent accidental water damage,all control valves should be shut tight and the system completely drained before waterflow detectors are removed or replaced. • Turn off electrical power to the detector,then disconnect wiring. - • Loosen nuts and remove U-bolts. • Gently lift the saddle far enough to get your fingers under it. With your fingers,roll the vane so it will fit through the hole while continuing to lift the waterflow detector saddle. • Lift detector clear of pipe. Important Notice Please advise the person responsible for testing of the fire protection system that this system must be tested in accordance with the testing instructions. Mounting Dimensions 89,0 mm GROUND SCREWS (3.50') 141,2 mm n (5.56") I "1/11 II � 59Q93 m Sg6mm 2.00') ri I �1� U-DOLTNUT _ E _-__k Cl ■��. F O U-aOLT WASHER i..A .. PIPEMA y •-I_O '.�1(.p (-5-1/4") , ' T1 ; PIPE SADDLE NI r PIPE 1111 PLASTID PADDLE 11 U-60LT NOMINAL PIPE DIA.*44,5 mm)'1-3/4)FOR DN50-DN65(2-2-1/2') - NOMINAL PIPE CNA.+54,0nun(+2-1B")FOR DN60-DN200(3-6") 5W0t 1:=6-6 PRINTED IN USA MFG.45401146-REV K PAGE 3 OF 3 12/08 tqC0 I Fire & Building Products Technical Services:Tel: (800)381-9312/ Fax: (800)791-5500 Sprinkler Cabinets 3, 6, & 12 Sprinklers, 1/2 or 3/4 Inch NPT 6 ESFR Sprinklers, 3/4 or 1 Inch NPT General Description Tyco® Sprinkler Cabinets are con- rr,� structed of metal enclosures with hinged covers designed to provide on- site storage of an emergency supply Wf'. of sprinklers and a sprinkler wrench. NFPA 13 requires a representative number of each type of sprinkler used ' � hn, in a sprinkler system to be stored in a ;t cabinet on-site to allow for immediate removal and replacement of sprinklers �e' � that may have operated or become damaged. Sprinkler Cabinets are manufactured of heavy gauge steel with knock-outs to accommodate NPT threaded sprin- klers and are painted an attractive red enamel. WARNINGS Technical The Sprinkler Cabinets described here- Data in must be installed and maintained in compliance with this document, as Material well as with the applicable standards Carbon Steel of the National Fire Protection Asso- Weights ciation, in addition to the standards of any other authorities having jurisdic- 3 Sprinkler Cabinet tion. Failure to do so may impair the 1.5 Lbs.(0,68 kg) performance of these devices. 6 Sprinkler Cabinet The owner is responsible for maintain- 2 3 Lbs.(1,04 kg) .:I ing their fire protection system and de- 12 Sprinkler Cabinet tc- Q vices in proper operating condition. 4 0 Lbs.(1,81 kg) \'�Q,; The installing contractor or sprinkler 6 ESFR Sprinkler Cabinet '_ / manufacturer should be contacted 3 3 Lbs. (1,36 kg) {� with any questions. Page 1 of 4 AUGUST, 2007 TFP785 Page 2 of 4 TFP785 REMOVE KNOCKOUTS HOLES ACCOMMODATE TO ACCOMMODATE 1/2"NPT SPRINKLERS 3/4"NPT SPRINKLERS HINGES _FROM s 1-5/16' 5-1/4"R (33,3 mm) (133,4 mm) 7-1/4" 1-1/4" DOOR SWING r(184,2 mm) (31,8 mm) 5" 1-1/8" (127,0 mm) (28,6 mm) / 01 3-1/4" — I 2" 2-5/8" 1-3/16' ' 2-9/16" (98,4 mm) (50,8 mm) (66,7 mm) (30,2 mm) '/ (65,1 mm) I 6"(150 mm) y(J MINIMUM HOLES FOR CLEARANCE 3/16"(5 mm) — • I 0 5 SCREWS 1-3/4" maim (25,4 mm) (127,0 mm) (44,5 mm) _ SPRINKLER SLOTS FOR WRENCH DOOR 1"(25,4 mm) AND HINGES SHELF STRAP HANGER SHELF NOT SHOWN FIGURE 1 3 SPRINKLER CABINET REMOVE KNOCKOUTS HOLES ACCOMMODATE TO ACCOMMODATE 1/2"NPT SPRINKLERS - 3/4"NPT SPRINKLERS HINGES 01 I T-) i' d O C ) Lj4 1-5/16" 5-1/4"R (33,3 mm) (133,4 mm) _ 14-1/16" _ 1-1/4" DOOR SWING (357,2 mm) (31,8 mm) 10-13/16' 1-5/8" 1'1 (274,6 mm) �(41,3 mm) / / 6"(150 mm) / 2" 6' 1-3/16" 2-9/16" 3-1/4" (50,8 mm) (152,4 mm) (30,2 mm) MINIMUM '/ (65,1 mm) (98,4 mm) 1 I CLEARANCE f - f 0 I "" 1 1" (127,0 mm) ��_� 1 4' ,��� (25'4 mm) I _ \ (44,5 mm) HOLES FOR SLOTS FOR DOOR - 3/16"(5 mm) SPRINKLER 1"(25,4 mm) WRENCH AND HINGES SCREWS SHELF STRAP HANGER SHELF NOT SHOWN FIGURE 2 6 SPRINKLER CABINET TFP785 Page 3 of 4 REMOVE KNOCKOUTS HOLES ACCOMMODATE TO ACCOMMODATE 1/2"NPT SPRINKLERS 3/4"NPT SPRINKLERS i L 1-1/2' HINGES - rr� '��) ',�4) �( Q Q (38,1 mm) I ,' 1-1/2" 5-1/4"R (38,1 mm) (133,4 mm) 14-1/16" L 1-1/8" DOOR SWING (357,2 mm) (28,6 mm) _____ 10-13/16" 1-5/8" 17 (274,6 mm) 1 �(41,3 mm) 2" 6 I 1-3/16" 6"(150 mm) //" (14-1/8" ) 3-1/4" (50,8 mm) (152,4 mm) y (30,2 mm) MINIMUM 04,8 mm (98,4 mm) CLEARANCE // / 0 I f„ -.4/ 1" (127,0 mm) v*� 041:5/mm) ■� (25,4 mm) J \ HOLES FOR SPRINKLER SLOTS FOR WRENCH DOOR 3/16"(5 mm) 1"(25,4 mm) AND HINGES SCREWS SHELF STRAP HANGER SHELF NOT SHOWN FIGURE 3 12 SPRINKLER CABINET REMOVE KNOCKOUTS HOLES ACCOMMODATE TO ACCOMMODATE 3/4"NPT SPRINKLERS - 1"NPT SPRINKLERS 1 is:. „ „:. /- ') ' ) Oo/HINGES J) `=' L 1-9/16" 6-7/16"R (163,5 mm) (39,7 mm) DOOR SWING 14-1/16" _ 1-9/16" -- / (357,2 mm) (39,7 mm) lr 10-13/16" 1-5/8" (274,6mm) 1 }(41,3mm) I 1 7"(180 mm) 2" 6" 1-3/16" / 3-1/8' (50,8 mm) (152,4 mm) (30,2Imm) MINIMUM y (79,4 mm) 1 1 CLEARANCE � J1J 3-13/13 D I i (96,8 mm) IL 1" 6-3/16" (25,4 mm) (757,2jmm) ---42-3/8" (60,3 mm) !mom— 1 \ HOLES FOR SPRINKLER SLOTS FOR WRENCH SLOTS 3/16"(5 mm) 1"(25,4 mm) AND HINGES - SCREWS SHELF STRAP HANGER SHELF NOT SHOWN FIGURE 4 6 ESFR SPRINKLER CABINET Page 4 of 4 TFP785 Installation Limited Ordering Sprinkler Cabinets are designed with Warranty Procedure two 3/16 Inch(4,7 mm)diameter holes - for wall mounting or direct attachment Products manufactured by Tyco Fire When placing an order,indicate the full - to the system riser with a strap-type & Building Products (TFBP) are war- product name. Contact your local dis- hanger. The Sprinkler Cabinet should ranted solely to the original Buyer for tributor for availability. be installed at or near the system con- ten(10)years against defects in mate- Sprinkler Cabinet: trol valve and must be stocked with an rial and workmanship when paid for Specify:(Description), P/N(specify). adequate supply of spare sprinklers and properly installed and maintained and a sprinkler wrench. under normal use and service. This 3 Sprinkler Cabinet P/N 1177 warranty will expire ten(10)years from 6 Sprinkler Cabinet P/N 1119 The stock of spare sprinklers should 12 Sprinkler Cabinet P/N 1124 include sprinklers of each type and date of shipment by TFBP. No warran- 6 ESFR Sprinkler Cabinet P/N 1111 temperature rating as are installed in ty is given for products or components the sprinkler system, in the following manufactured by companies not af- quantities: filiated by ownership with TFBP or for products and components which have In Sparere Sprinklers been subject to misuse, improper in- SprinklersSpstem Required stallation,corrosion,or which have not been installed,maintained,modified or Under 300 6 repaired in accordance with applicable Standards of the National Fire Protec- 300-1000 12 tion Association,and/or the standards Over 1000 24 of any other Authorities Having Juris- diction. Materials found by TFBP to be defective shall be either repaired or re- The 3, 6, and 12 Sprinkler Cabinets placed, at TFBP's sole option. TFBP are designed to accept both 1/2&3/4 neither assumes, nor authorizes any Inch NPT threaded sprinklers, where- person to assume for it, any other ob- as the 6 ESFR Sprinkler Cabinets are ligation in connection with the sale of designed to accept both 3/4 & 1 Inch products or parts of products. TFBP NPT threaded sprinklers. As neces- shall not be responsible for sprinkler sary, insert a screwdriver blade from system design errors or inaccurate or the front top of the shelf and under the incomplete information supplied by near bottom part of the knockout an- Buyer or Buyer's representatives. nular ring. Press the screwdriver han- In no event shall TFBP be liable, in die down to remove the knockout ring. contract, tort, strict liability or under any other legal theory, for incidental, Care and indirect,special or consequential dam- ages, including but not limited to labor Maintenance charges, regardless of whether TFBP was informed about the possibility of The Sprinkler Cabinet, wrench, and such damages, and in no event shall stock of spare sprinklers should be in- TFBP's liability exceed an amount spected at least quarterly. The follow- equal to the sales price. ing items should be checked: The foregoing warranty is made in lieu •The Sprinkler Cabinet should be of any and all other warranties. ex- readily accessible, and not exposed press or implied. including warranties to a corrosive atmosphere or tern- of merchantability and fitness for a peratures in excess of 100°F(38°C). particular purpose. •The stock of spare sprinklers should This limited warranty sets forth the ex- include an adequate number of each clusive remedy for claims based on type and temperature rating. failure of or defect in products, materi- als or components, whether the claim •The stock of sprinklers must be in is made in contract, tort, strict liability good condition. or any other legal theory. •A sprinkler wrench of the appropriate This warranty will apply to the full ex- type must be included in the Sprin- tent permitted by law. The invalidity, kler Cabinet. in whole or part, of any portion of this warranty will not affect the remainder. TYCO FIRE&BUILDING PRODUCTS,451 North Cannon Avenue,Lansdale Pennsylvania 19446 tqca Fire & Building Products Technical Services: Tel:(800)381-9312/Fax:(800)791-5500 Style 10, 20, 30, 40, and 50 Recessed Escutcheons & Protective Paint Caps For Automatic Sprinkler Recessed Installation WARNING General The Recessed Escutcheons described herein must be installed and main- Description tained in compliance with this docu- ment, as well as with the applicable The Tyco®Style 10,20,30,40,and 50 standards of the National Fire Protec- Recessed Escutcheons are designed 9 tion Association, in addition to the � s , for recessed installation with certain standards of any other authorities hav- pendent and horizontal sidewall sprin- ing jurisdiction. Failure to do so may klers. They are intended for use in impair the performance of these de- areas with finished ceilings or walls, vices. and the adjustment provided by these escutcheons reduces the accuracy to The owner is responsible for maintain- which fixed piping to the sprinklers ing their fire protection system and de- must be cut,while providing a decora- vices in proper operating condition. tive recessed sprinkler installation. The installing contractor or sprinkler manufacturer should be contacted The two-piece Style 10(1/2 inch NPT) with any questions. or Style 40 (3/4 inch NPT) Recessed Escutcheon provides 1/2 inch (12,7 mm) of recessed adjustment or 3/4 inch (19,1 mm) of total adjustment Technical from the flush position. The two-piece Style 20(1/2 inch NPT)or Style 30(3/4 Data inch NPT) Recessed Escutcheon pro- vides 1/4 inch (6,4 mm) of recessed Approvals adjustment or 1/2 inch (12,7 mm) of le, total adjustment from the flush posi- foApproval information,e0, 20, as40, and tion. The two-piece Style 50 (1/2 inch Recessedr the Style 1 tes 30, and 5n Escutcheons is detailed in NPT) Recessed Escutcheon provides individual pendent and horizontal side- 1/4 inch (6,4 mm)of recessed adjust- wall sprinkler data sheets that include ment or 3/8 inch (9,5 mm)of total ad- details of recessed installation. justment from the flush position. The Style 10, 20, 30, 40, and 50 Re- Materials and Finishes Carbon steel chrome plated, white cessed Escutcheons are redesigna- tions for Central,Gem and Star brands coated, orbrass plated. Series 300 as follows: stainless s steel whitete coated or plain unpolished. (Other colors are avail- Style Central Gem Star able on special request.) 10 3211 F700(1/2") 2085 20 3221 F705(1/2") 2084 30 4221 F705(3/4") 2086 40 4211 F700(3/4") 2088 50 307X -As an option, Protective Paint Caps (Ref.Figures 6 and 7)may be obtained to help protect the sprinkler while ceil- ings or walls are being finished. The Model Z-392 is suitable for use with the Style 10, 20, 30, or 40 Recessed Es- cutcheons,whereas the Model Z-84 is suitable for use with the Style 50 Re- cessed Escutcheon. Page 1 of 4 DECEMBER, 2007 TFP770 Page 2 of 4 TFP770 1/2"NPT 1-15/16"DIA. CLOSURE " MOUNTING PLATE (49,2 mm) Installation I Installation information, as applicable, for the Style 10, 20, 30, 40, and 50 1-1/8" Recessed Escutcheons is detailed in (28,6 mm) individual pendent and horizontal side- wall sprinkler data sheets that include ► } details of recessed installation. FLU SH TO L J 2-7/8"DIA. 18" NOTE 3/4"(19,1 mm) (73,0 mm) (3,2 mm) The Style 10, 20, 30, 40, and 50 Re- FIGURE 1 cessed Escutcheons must only be STYLE 10 ESCUTCHEON, 1/2 INCH NPT—3/4 INCH ADJUSTMENT used with sprinklers for which they have been specifically laboratory ap- proved(i.e., UL, C-UL, ULC, or FM). 1/2"NPT 1-15/16"DIA. CLOSURE As an option, Protective Paint Caps MOUNTING PLATE (49,2 mm) (Ref. Figures 6 and 7)may be utilized to help protect the sprinkler while the ceiling or wall, as applicable, is being 13/16• finished (painting or plastering for ex- 1 (20,6mm) ample). The Protective Paint Cap is simply pushed overthe Mounting Plate } of the Recessed Escutcheon in lieu of the Closure. After the ceiling or wall FLUSH TO 2-7/8"DIA. 1/8" finish is completed, the Protective 1/2"(12,7 mm) (73,0 mm) (3,2 mm) Paint Cap is removed and the Closure is installed. FIGURE 2 The Protective Paint Cap may be dis- STYLE 20 ESCUTCHEON, 1/2 INCH NPT— 1/2 INCH ADJUSTMENT carded as a plastic commodity (Low Density Polyethylene Recycling Cate- 3/4"NPT 1-15/16"DIA. CLOSURE gory 4)in conformance with local regu- MOUNTING PLATE (49,2 mm) lations, or the Protective Paint Cap may be be reused. - I NOTE I13/16' The sprinkler cannot operate properly (20,6 mm) with the Protective Paint Cap in place. 1 1 ' FLUSH TO _ 2-7/B"DIA. 1/8" 1 l2"(12,7 mm) (73,0 mm) (3,2 mm) FIGURE 3 STYLE 30 ESCUTCHEON, 3/4 INCH NPT— 1/2 INCH ADJUSTMENT 3/4"NPT 1-15/16"DIA. CLOSURE MOUNTING PLATE y (49,2 mm) I 1-1/8" I (28,6 mm) I FLUSH TO 2-7/8"DIA. 1/8" 3/4"(19,1 mm) (73,0 mm) (3,2 mm) FIGURE 4 STYLE 40 ESCUTCHEON, 3/4 INCH NPT—3/4 INCH ADJUSTMENT TFP77O Page 3 of 4 1/2"NPT y 1-13/16"DIA. CLOSURE MOUNTING PLATE (46,0 mm) Care and Maintenance 13/16" Specific requirements of the NFPA ' + (20,6 mm) must be performed, and any impair- I 1 t ment must be immediately corrected. NOTE FLUSH TO 2-7/B'DIA. 3/32" Absence of an escutcheon, used to 3/8"(9,5 mm) (73,0 mm) (2,4 mm) cover a clearance hole, may delay the FIGURE 5 time to sprinkler operation in a fire STYLE 50 ESCUTCHEON, 1/2 INCH NPT—3/8 INCH ADJUSTMENT situation. The owner is responsible for the in- - spection, testing, and maintenance of their fire protection system and de- 3-1/4"/ vices in compliance with this docu- ment,(82 mm) _ as well as with the applicable \ / • ,., standards of the National Fire Protec- \\, ,,�,/// l tion Association (e.g., NFPA 25), in 16� ' ���4 fly addition to the standards of any '. � authority having jurisdiction. The in- 1-7/8"DIA. ` stalling contractor or product manufac- (48 mm) • FRICTION FIT turer should be contacted relative to PAINT CAP OVER any questions. ESCUTCHEON MOUNTING PLATE Automatic sprinkler systems should be inspected,tested,and maintained by a qualified Inspection Service in accord- ance with local requirements and/or FIGURE 6 national codes. MODEL Z-392 PROTECTIVE PAINT CAP (For use with Style 10,20, 30, or 40 Recessed Escutcheons) 2-1/2"...-r- (64 mm) �� g It" , ;:k 1-13/16"DIA. (46 mm) FRICTION FIT 11 PAINT CAP OVER ESCUTCHEON MOUNTING PLATE FIGURE 7 MODEL Z-84 PROTECTIVE PAINT CAP (For use with Style 50 Recessed Escutcheons) Page 4 of 4 TFP77O Limited Ordering STAINLESS STEEL Warranty Information Style 10, ite 1/2"NPT(15mm) White P/N 56-701-5-010 Products manufactured by Tyco Fire& When placing an order,indicate the full Plain Unpolished P/N 56-701-1-010 Building Products (TFBP) are war- product name. Refer to Price List for style 20 ranted solely to the original Buyer for complete listing of Part Numbers. 1/2"NPT(15mm) ten(10)years against defects in mate- White P/N 56-705-S-010 rial and workmanship when paid for Contact your local distributor for avail- and properly installed and maintained ability. Style P P Y 3/4"NPT(20mm) under normal use and service. This Recessed Escutcheon: White P/N 56-705-S-011 warranty will expire ten (10) years Specify: Style (specify) Recessed Es- Style4o from date of shipment by TFBP. No cutcheon with (specify material and 3/4"NPT(20mm)White P/N 56-700-S-010 warranty is given for products or corn- finish), P/N (specify). Plain Unpolished P/N 56-700-1-010 ponents manufactured by companies not affiliated by ownership with TFBP Style 50 or for products and components which CARBON STEEL 1/2"NPT(15mm) have been subject to misuse,improper White P/N 56.711•S-010 installation, corrosion, or which have Style 10, not been installed, maintained, modi- 1/2"NPT(15mm) Protective Paint Cap: Pied or repaired in accordance with Chrome Plated P/N 56-701-9-010 Specify: Model (specify) Protective P ap- White P/N 56-701-4-010 Paint Cap, P/N (specify). plicable Standards of the National Fire Brass Plated P/N 56-701-2-010 Protection Association, and/or the White(RAL9010)" P/N 56-701-3-010 Model Z-392 P/N 56-711-1-392 standards of any other Authorities Model Z-84 P/N 56-711-1-084 Having Jurisdiction. Materials found Style 20 byTFBP to be defective shall be either ChromePT (15mm)Plated Chrome P/N 56-705-9-010 repaired or replaced, at TFBP's sole White P/N 56-705-4-010 option. TFBP neither assumes, nor Brass Plated P/N 56-705-2-010 authorizes any person to assume for it, White(RAL9010)' P/N 56-705-3-010 any other obligation in connection with Style 30 the sale of products or parts of prod- 3/4"NPT(20mm) ucts.TFBP shall not be responsible for Chrome Plated P/N 56-705-9-011 sprinkler system design errors or inac- White P/N 56-705-4-011 curate or incomplete information sup- Brass Plated ) P/N 56-705-2-011 plied by Buyer or Buyer's repre- White RAL9010' P/N56-7053-011 sentatives. Style 40 20mm) In no event shall TFBP be liable, in ChromePT Plated Chrome P/N 56-700-9-010 contract, tort, strict liability or under White P/N 56-700-4-010 any other legal theory, for incidental, Brass Plated P/N 56-700-2-010 indirect,special or consequential dam- White(RAL9010)' P/N 56-700-3-010 ages,including but not limited to labor Style 50 charges, regardless of whether TFBP 1/2"NPT(15mm) was informed about the possibility of Chrome Plated P/N 56-711-9-010 such damages, and in no event shall White P/N 56-711-4-010 TFBP's liability exceed an amount Brass Plated P/N 56-711-2-010 equal to the sales price. White(RAL9010) P/N 56-711-3-010 * The foregoing warranty is made in lieu Eastern Hemisphere sales only. of any and all other warranties ex- press or implied. including warranties of merchantahility and fitness fora par- ticular ouroose This limited warranty sets forth the ex- clusive remedy for claims based on failure of or defect in products,materi- als or components, whether the claim is made in contract, tort, strict liability or any other legal theory. This warranty will apply to the full ex- tent permitted by law.The invalidity,in whole or part, of any portion of this warranty will not affect the remainder. ©2007 TYCO FIRE&BUILDING PRODUCTS,451 North Cannon Avenue,Lansdale, Pennsylvania 19446 POTTER ROEMER ME MYER r~ , Cerritos,California C Union,New Jersey i i 0 Fire Protection Products I'FIRE PactrEcnotv F44ttasm7ivT/ ,;„.-.. - * ' BALL TYPE SHUT-OFF VALVES * FM • o cr o .iii. EI it r B v, U IMP IN i IF 71 01110 m ii 0III 2 2 M 0 2 2 4 3 A I • 6 - F 0 - • 0 3 FOR USE WITH:•Sprinkler Systems •Dry Sprinkler Systems g, •Standpipe Systems •Manual Deluge Control Valve 0 2 4 i REGULARLY FURNISHED: Forged brass body.Cadmium plated vinyl insulated handle.Chrome-plated s brass ball with nylon seat. w 0 0 s PRESSURE FIG.NO. SIZE A B C 0 RATING P.S.I. 4 4405 1/2 * 2 3/16 13B .472 31/16 600 m 0 4407 3/4 • 21/2 13/4 .672 313/16 600 4410 1 * 3 17/8 .891 313/16 500 0 w 4412 11/4' 37/16 21/16 1.109 313/16 500 s 4 i 4415 11/2' 3 3/4 2 3/8 1.378 413/16 500 0 4420 2 * 4 3/8 211/16 1.772 413/16 500 w a 4425 21/2 5 3/4 31/4 2.250 6 400 4430 3 61/4 31/2 2.625 6 400 - ALL DIMENSIONS IN INCHES DATE FIGURE NUMBER 3-1-8 6 I 1 6�,.1��—`j �11441 BRECCO Gauges. • Gauges For use with wet or dry systems. Gauges have a bronze burbon tube movement , ' in a stainless steel case." `ad ..� Sq )� � •: @P c4� pal . ' t,4s • 3-1/2" Diameter y w • UL and FM approved. tr Y • 47 t • Custom gauges can be made. s y 4.p, V • 1 ,s `'Iisj �,` Lc,' 'Unless otherwise noted, S k 9 -ivb-.- " ;11*21 3-Way Valve Included in Accessory Pack! y +' - Gauges can be custom branded with your name and logo. Please call for more information. Part No. Description Box Box Crate Case Qty. Weight Qty. Weight GAAWSS350 AIR/WATER 0.300 PSI WI STAINLESS STEELLCASE sr ` 60 42 Lbs 480 5351.bs GAASS250 AIR W/RETARD 250 PSI 3-1/2" DIAMETER, 60 40 Lbs. 480 530 Lbs. W/STAINLESS STEEL CASE 2"RESIDENTIAL GAUGE 300PSIu, t k�"' Mtv:'*'.? x;150 45 Lbs. 120Ct ,580"Lbs GAWP200 - W/BLACK STEEL CASE(NOT 19L,ORF111AP.PROViE.Dy* i...:;.. GAUGE KITS -AIR OR AIR/WATER AIR/WATER GAUGE'0-300 PSI W1 STAINLESS•STE'EI r* t=' GAKITAWSS350 CASE, 1/4'x4" PLU G;' ' t1A 14 Lbs' NAA NA 1/2"x 1/4" HEXHEAD REDUCING RUSHING r'4 ',. . ` =�t" r...", � , i ' ' .;'- AIR GAUGE 0-250 PSI W/STAINLESS STEEL CASE, GAKITAOSS250 1/4"x 4" NIPPLE, 1/4"3 WAY VALVE, 1/4" PLUG, 10 14 Lbs. NA NA 1/2"x 1/4" HEXHEAD REDUCING BUSHING Call Toll Free: 1-800-543-4194 Fax: 1-877-474-9248 26