Specifications (33) •
• 13up aoi9 . 00035
Triplett Submittal Stamp Page
Seismic Design and Calcs
Wellman REC VED
CONTRACTORS OFFICE COPY'
REVISION MAR 2020
CITY OF TIGARD
General Contractor Stamp:
BUILDING DIVISION
Project Name Triplett
Twality Middle School Wellman
0 REVIEWED ❑REJECTED
❑ MAKE CORRECTIONS ❑NOT REVIEWED
BY Chris Olenyik DATE 3/9/20
SUBMITTAL# 095100-PD-2 SPEC 09 51 00
This review is only for general conformance of the project and general
compliance. Corrections or comments made on these drawings during this
review do not relieve Contractor/Subcontractor from compliance with the
requirements of the plans and specifications. Contractor is responsible for all
dimensions and fabrication to be confirmed and correlated at the job site
Architect Stamp:
Consultant Stamp:
&*r. 4 ,leew.44 •
PO Box 189 Tualatin, Or. 97062
Phone: 612-0100
Fax: 612-0101
Project: Twality Middle School
INCLUSIONS: Div 09 51 00 Acoustical Ceilings
MANUFACTURER PRODUCT INFO TYPE QUANTITY
Includes: Product Data: 1 PDf Copy
Certainteed Suspension System
15/16" Classic Stab System
Terminus Straight Perimeter Trim
LBRC L-Bracket
ACT-1
Cashmere CM 497 NRCP
2'x4' Trim Edge
Maintenance & Cleaning Info
ACT-2
Fine Fissured
FFCL-224 2'x4' Reveal Edge
Maintenance & Cleaning Info Previously
Submitted
ACT-3
Symphony M RX
1220 RXS-1 2'x 4' Trim Edge
ICC-ES Report ESR-3336
NWCB Suspended Ceiling 401 Document
Docs Marketing W300 Eye Lag screw for Wood
ICC Evaluation Report ESR-4272 J
Lewis & Van Vleet Inc. Seismic Design & Calculations 1 PDF Copy
Prepared By: Cascade Acoustics
3-3-20
LEWIS &
1111
VAN VLEET
principals
gary j. lewis, p,e.
Scott debo, m.b.a.
STRUCTURAL CALCULATIONS
FOR
Twality Middle School
Ceilings
Tigard, Oregon
FOR
Cascade Acoustics
s`�RL' t
�S pI ��2
15,
lvv) • 23,
�� Klti
JAMES ti
EXPIRES 12-31-2020
Lewis & Van Vleet Inc. Project No. 19128
Sheets S-1 through S-63 and D-I through D-6
consulting engineers
18660 s.w. boones ferry road
tualatin, oregon 97062
(503) 885-8605 phone
SUSPENDED CEILING CALCULATIONS
LEWIS &
consulting engineers
7.11 18660 s.w.boones ferry road
tualatin,Oregon 97062
503.885.8605 phone 503.885.1206 fax
VAN VLEET
incorporated
PROJECT: Twality Middle School -Condition 1, Sector A, Level 1, Type 1
TYPE OF GRID: ACOUSTICAL CEILING
CERTAINTEED 15/16" TEE SYSTEM
CS12-12-20 HEAVY DUTY MAINS
CS4-12-12 4'CROSS TEE
CS2-12-12 2' CROSS TEE
WA15-15 WALL ANGLE
CTSPC-2 PERIMETER CLIP
DISTANCE FROM CEILING ACOUSTICAL GRID - MAX. DROP = 5 FEET
TO STRUCTURE:
COMPRESSION STRUTS: SEE PAGE S-8 FOR SUMMARY
DIAGONAL WIRE SPLAYS: 12 GA. 55 KSI 4 WAYS AT EACH COMPRESSION STRUT
VERTICAL HANGER WIRES: 12 GA. 55 KSI AT4'-0" O.C. ALONG MAIN RUNNERS
STRUCTURE ABOVE CEILING: OPEN WEB JOIST
FASTENERS FOR SPLAY WIRES: 1/4" DIA. X 3" LAG SCREW W/ EYE TO JOIST CHORD OR TIE
TO JOIST CHORD
PERIMETER WIRES IN EACH ORTHOGONAL DIRECTION, ONE END OF THE
AND ATTACHMENTS: CEILING GRID MAY BE ATTACHED TO THE CLOSURE ANGLE.
THE OTHER ENDS IN EACH HORIZONTAL DIRECTION SHALL
HAVE 3/4 INCH CLEARANCE FROM THE WALL AND BE
SUPPORTED BY AN CERTAINTEED WA15-15 SEISMIC
PERIMETER CLIP AT ALL MAIN AND CROSS RUNNERS. NO
PERIMETER WIRES ARE REQUIRED IN THIS INSTANCE. THIS
FRAMING OPTION MUST BE APPROVED BY THE LOCAL
AUTHORITY HAVING JURISDICTION.
STRUT AND SPLAY SPACING: 12'-0"X 12'-0" OR MAXIMUM 144 SQUARE FEET
sz
SUSPENDED CEILING CALCULATIONS
LEWIS &
consulting engineers
18660 s.w.boones ferry road
tualatin,oregon 97062
503.885.8605 phone 503.885.1206 fax
VAN VLEET
incorporated
CEILING MOUNTED LIGHT LIGHTING FIXTURES, EGRESS LIGHTING, SPEAKER, AIR
FIXTURES, EGRESS LIGHTS, TERMINALS, OR MECHANICAL SERVICES WEIGHING UP
SPEAKER,AIR TERMINALS, TO 56 POUNDS AND DIRECTLY SUPPORTED BY THE
MECHANICAL SERVICES, CEILING GRID SYSTEM SHALL BE POSITIVELY
AND OTHER CEILING ATTACHED TO THE CEILING SYSTEM. ATTACHMENT
SUPPORTED EQUIPMENT: SHALL BE MADE WITH A MINIMUM OF 4 APPROVED
FASTENERS LOCATED WITHIN 3 INCHES OF THE GRID
INTERSECTIONS TO SUSPENSION MAIN RUNNERS, OR
TO CROSS RUNNERS WITH THE SAME CARRYING
CAPACITY OF THE MAIN RUNNERS. IN ADDITION TO
THE ABOVE GRID CONNECTION, FIXTURES WEIGHING
AT LEAST 20 POUNDS BUT NOT MORE THAN 56
POUNDS SHALL HAVE TWO 0.080 INCH (12 GAUGE
A.W.G.) HANGER WIRES CONNECTED FROM THE
FIXTURE TO THE CEILING SYSTEM HANGERS OR TO
THE STRUCTURE ABOVE. THESE WIRES MAY BE
SLACK. FIXTURES WEIGHING LESS THAN 20 POUNDS
DO NOT REQUIRE SLACK WIRES. FIXTURES WEIGHING
MORE THAN 56 POUNDS SHALL BE SUPPORTED
INDEPENDENTLY FROM THE STRUCTURE ABOVE
INDEPENDENTLY OF THE GRID SYSTEM WITH
APPROVED HANGERS. CABLE TRAYS, ELECTRICAL
CONDUIT, COMMUNICATION CABLE, AND OTHER
SIMILAR INSTALLATIONS SHALL BE SUPPORTED
INDEPENDENTLY FROM THE CEILING.
DESIGN SCOPE: STRUTS AND SPLAYS ARE NOT REQUIRED FOR CEILINGS IN
ROOMS LESS THAN 1000 SQUARE FEET IN AREA(IN AREAS
WITH THE SURROUNDING WALLS BRACED TO STRUCTURE).
ENGINEERING: LEWIS&VAN VLEET INC. HAS BEEN RETAINED TO DESIGN
THE CEILING GRID SUPPORT AND BRACING, AND
ATTACHMENTS FROM THE GRID SYSTEM TO THE
SUPPORTING STRUCTURE. IT IS THE RESPONSIBILITY OF
THE BUIDING OWNER, CONTRACTOR, OR ENGINEER OF
RECORD TO VERIFY THAT THE STRUCTURE HAS ADEQUATE
STRENGTH AND LATERAL STABILITY TO RESIST THE LOADS
IMPOSED ON IT BY THE SUSPENDED CEILING.
CODES: LEWIS&VAN VLEET, INC. HAS FOLLOWED THE STANDARD
PROVISIONS OF THE 2012 IBC, THE 2014 OSSC, AND ASCE 7-
1CD IN THE DESIGN OF THIS SYSTEM.
SUSPENDED CEILING CALCULATIONS
LEWIS &
11 consulting engineers
18660 s.w.boones ferry road
tualatln,oregon 97062
503.885.8605 phone 503.885.1206 fax
VAN VLEET
incorporated
LATERAL LOADING: CONDITION NO. 1,SECTOR A, LEVEL 1,TYPE 1
SPECTRAL ACCELERATION Sos= 0.716
SITE CLASS = D
IMPORTANCE FACTOR Ip= 1.25
COMPONENT AMPLIFICATION FACTOR ap= 1
COMPONENT AMPLIFICATION FACTOR Rp= 2.5
CEILING WEIGHT w= 4 PSF 1
ATTACHMENT HEIGHT OF CEILING z= 15.167 FEET 1+ 2 *z/h = 1.687
AVERAGE ROOF HEIGHT h= 44.167 FEET
DESIGN FOR TOTAL LATERAL FORCE FOR A 12'X 12' GRID:
TOTAL WEIGHT: Wp = w* 12' * 12'= 576 LBS.
LATERAL LOAD: Fp = 0.4 * ap*Sos*Wp *0.7 2 *z
1 +
Rp/Ip h
Fp = 97 LBS. ASCE 7-14 ++ (EQ. 13.3-1)
MANDATORY LOWER BOUND: Fp = 108 LBS. ASCE 7-14.++ (EQ. 13.3-3)
OPTIONAL UPPER BOUND: Fp= 577 LBS. ASCE 7-14 ++ (EQ. 13.3-2)
++ NOTE: 0.7 FACTOR IS APPLIED TO THE FORCES FOR ALLOWABLE STRESS DESIGN
SUSPENDED CEILING CALCULATIONS
LEWIS &
consulting engineers
18660 s.w.boones ferry road
tualatin,oregon 97062
503.885.8605 phone 503.985.1205 fax
SPLAY WIRE AND CONNECTION TO STRUCTURE: CONDITION NO. 1, SECTOR A, LEVEL 1, TYPE 1
Strut Wire CEILING GRID 12 FT. X 12 FT.
45 deg.
Ceiling
CHECK DIAGONAL WIRE SPLAYS: 12 GA. Fy = 55,000 PSI A= 0.0088 SQ. IN.
CAPACITY OF WIRE: Tmax= 0.6 * Fy 8 *A
= 290 LB.
CONTROLLING SEISMIC FORCE: Fp DESIGN = 108 LB.
TENSION IN WIRE: T = Fp DESIGN/COS 45 DEG. = 153 LB. OK
114" DIA. X 3" LAG SCREW W/EYE TO JOIST CHORD OR TIE TO JOIST CHORD
CHECK COMPRESSION STRUT:
1'-0" to 6'-0" use 1 5/8"-20 GA. STUD WITH 1 114" FLANGES
SSMA SECTION 162S125-33
5-
SUSPENDED CEILING CALCULATIONS
• LEWIS &
COnSUItinCI engineers
18660 s.w.boones Ferry road
tualatin,Oregon 97082
503.885.8605 phone 503.885.1206 fax
VAN VLEET
incorporated
PERIMETER CLOSURE ANGLE SUPPORT AT WALL:
CHECK WALL ANGLE SUPPORT AT WALL--MINIMUM 7/8"X 7/8"X 0.0188"ANGLE
1.1
CHECK THIS SPAN MINIMUM#8 SCREW
2 ft.
I i I
ft. SUSPENSION WIRE
CONNECTION POINT
4ft. 4ft.
FRAMING PLAN
P DL= 4 PSF
P =4PSFx4FTx1/2x8FTx1/2x1/2
w = 16 LB
11111111111111111111
w =4 PSF x 2 FT x 1/2
4 PLF
R R
RMAx = 16 LB +4 PLF x 4 FT x 1/2 (CONTINUOUS ANGLE)
= 24 LB
M = 16 LB x 2 FT x 1/8 + 4 PLF x (2 FT)2 x 1/12 (CONTINUOUS ANGLE)
.- 5.33 FT-LB
OK- SEE ANGLE CAPACITY CALCULATION ON NEXT PAGE
� w
SUSPENDED CEILING CALCULATIONS
• LEWIS &
conSuItinq engineers
18660 s.w.boones ferry road
tualatin,oregon 97062
503.885.8605 phone 503.885.1206 fax
VAN VLEET
incorporated
ANGLE CAPACITY CALCULATION
0.875" IVIIN.
/
__ / 0.0188"
0.875" I411I.
DISREGARD
STIFFENING LIPS
/ ��
(0.875 IN) (0.0188 IN)`
0.0188 IN + (0.875 IN -0.0188 IN) -
2 _ 2
y _
0,0188 IN x (2 x 0.875 IN -0.0188 IN)
y= 0.2258 IN
- (0.875 IN)' 0.875 IN 2
IYVLEG =0.0188 IN x + 0.0188 IN x 0.875 IN x -0.226 IN
12 2
= 0.0018 IN4-
(0.0188 IN)3 1 0.0188 IN- 2
IYHLEG =(0.875 IN-0.0188 IN) +(0.875 IN-0.0188 IN)x0.0188 IN x 0.226 IN -
12 2
= 0.00076 IN4
ly= IYvi_EG+ IYHLEG= 0. 0.00254 IN4
ly
Sy= = 0.0039 IN3
0.875 IN -0.226 IN
MCAP= Sy x 0,6 x 33 KSI =6.46 FT-LB> 5.33 FT-LB ACTUAL-OK
ANGLE SPANS 24" BETWEEN STUDS
SUSPENDED CEILING CALCULATIONS
LEWIS &
consulting engineers
18660 s.w.boones ferry road
tualatin,oregon 97062
503,885.8605 phone 503.885.1206 fax
VAN VLEET /4
In an rporaled �/
ANGLE FASTENING TO STUDS
24 LB MAXIMUM
:.l
no miip.al
L
I
.i
V
R
24"
. - . Fp
R #8 SCREWSSTU
TO STUDS
Rr= Rv= 24 LB MAXIMUM
TcAPAaTY= 117 LB
VCAPACiry= 90 LB
24 24
INTERACTION: - + = 0.4718 <1 OK
117 90
#8 SCREW TO EACH STUD OK
--t3
Project Name: Condition 1 Page 1 of 1
Model: Condition 1 Date:02/18/2020
Code: 2012 NASPEC(AISI S100-2012] Simpson Strong-Tie®CFS De.signorTM 3.2.0.5
Section : 1625125-33(33 ksi)Single C Stud
Maxo = 114.0 Ft-Lb Va= 600.7 lb I= 0.07 in^4
jl Loads have not been modified for strength checks
TN® Loads have been multiplied by 0.70 for deflection calculations
Bridging Connectors-Design Method=AISI S100
Simpson Strong-Tie
Span/CantiLever Bridging Connector Stress Ratio
Span N/A -
Shear and Web Crippling Checks
Bending and Shear(Unstiffened): N/A
5.00 Bending and Shear(Stiffened): NA
Web Stiffeners Required?: No
f, b
1
Simpson Strong-Tie®Connectors
Connector Anchor
Support Rx(Ib) Ry(lb) Simpson Strong-Tie®Connector Interaction Interaction
R2 0 0 SCB45.5(2)&Anchorage Designed by Engineer 0.00% NA
R1 0 108 FCB43.5 Min(4#12-14)&Anchorage Designed by 14.30% NA
Engineer
*Reference catalog for connector and anchor requirement notes as well as screw placements requirement
Flexural and Deflection Check Deflection
Mmax Mmaxl Mpos Bracing Ma(Brc) Mpos/
Span Ft-Lb Maxo Ft-Lb (in) Ft-Lb Ma(Brc) (in) Ratio
Span 0.0 0.000 0.0 None 90.1 0.000 0.000 L/0
Distortional Buckling Check
Span K-phi Lm Brac Ma-d Mmaxl
lb-in/in in Ft-Lb Ma-d
Span 0.00 60.0 123.4 0.000
Combined Bending and Axial Load Details
Axial Ld Bracing(in) Max K-phi Lm Bracing Allow Intr.
Span (lb) KyLy KtLt KL/r (lb-in/in) (in) load(lb) P/Pa Value
Span 108.0(c) None None 136 0.0 60.0 403.7(c) 0.27 0.27
SIMPSON STRONG-TIE COMPANY INC. www.strongtie.cam
5 -`t
SUSPENDED CEILING CALCULATIONS
• LEWIS &
consulting engineers
18660 s.w. boones ferry road
tualatin,oregon 97062
503.885.8605 phone 503.885.1206 fax
VAN VLEET
incorporated
PROJECT: Twality Middle School -Condition 2, Sector B, Level 1, Type 1
TYPE OF GRID: ACOUSTICAL CEILING
CERTAINTEED 15/16"TEE SYSTEM
CS12-12-20 HEAVY DUTY MAINS
CS4-12-12 4' CROSS TEE
CS2-12-12 2' CROSS TEE
WA15-15 WALL ANGLE
CTSPC-2 PERIMETER CUP
DISTANCE FROM CEILING ACOUSTICAL GRID - MAX. DROP = 7 FEET
TO STRUCTURE: 1
COMPRESSION STRUTS: SEE PAGE S-16 FOR SUMMARY
DIAGONAL WIRE SPLAYS: 12 GA. 55 KSI 4 WAYS AT EACH COMPRESSION STRUT
VERTICAL HANGER WIRES: 12 GA. 55 KSI AT 4'-0" O.C. ALONG MAIN RUNNERS
STRUCTURE ABOVE CEILING: OPEN WEB JOIST
FASTENERS FOR SPLAY WIRES: 1/4" DIA. X 3" LAG SCREW W/EYE TO JOIST CHORD OR TIE
TO JOIST CHORD
PERIMETER WIRES IN EACH ORTHOGONAL DIRECTION, ONE END OF THE
AND ATTACHMENTS: CEILING GRID MAY BE ATTACHED TO THE CLOSURE ANGLE.
THE OTHER ENDS IN EACH HORIZONTAL DIRECTION SHALL
HAVE 3/4 INCH CLEARANCE FROM THE WALL AND BE
SUPPORTED BY AN CERTAINTEED WA15-15 SEISMIC
PERIMETER CLIP AT ALL MAIN AND CROSS RUNNERS. NO
PERIMETER WIRES ARE REQUIRED IN THIS INSTANCE. THIS
FRAMING OPTION MUST BE APPROVED BY THE LOCAL
AUTHORITY HAVING JURISDICTION.
STRUT AND SPLAY SPACING: 12'-0"X 12'-0" OR MAXIMUM 144 SQUARE FEET
S -l0
• SUSPENDED CEILING CALCULATIONS
LEWIS &
consulting engineers
18660 s.w.boones Ferry road
tualatin,oregon 97062
503.885.8605 phone 503.885.1206 Fax
VAN VLEET
incorporated
CEILING MOUNTED LIGHT LIGHTING FIXTURES, EGRESS LIGHTING, SPEAKER, AIR
FIXTURES, EGRESS LIGHTS, TERMINALS, OR MECHANICAL SERVICES WEIGHING UP
SPEAKER,AIR TERMINALS, TO 56 POUNDS AND DIRECTLY SUPPORTED BY THE
MECHANICAL SERVICES, CEILING GRID SYSTEM SHALL BE POSITIVELY
AND OTHER CEILING ATTACHED TO THE CEILING SYSTEM.ATTACHMENT
SUPPORTED EQUIPMENT: SHALL BE MADE WITH A MINIMUM OF 4 APPROVED
FASTENERS LOCATED WITHIN 3 INCHES OF THE GRID
INTERSECTIONS TO SUSPENSION MAIN RUNNERS, OR
TO CROSS RUNNERS WITH THE SAME CARRYING
CAPACITY OF THE MAIN RUNNERS. IN ADDITION TO
THE ABOVE GRID CONNECTION, FIXTURES WEIGHING
AT LEAST 20 POUNDS BUT NOT MORE THAN 56
POUNDS SHALL HAVE TWO 0.080 INCH (12 GAUGE
A.W,G.) HANGER WIRES CONNECTED FROM THE
FIXTURE TO THE CEILING SYSTEM HANGERS OR TO
THE STRUCTURE ABOVE. THESE WIRES MAY BE
SLACK. FIXTURES WEIGHING LESS THAN 20 POUNDS
DO NOT REQUIRE SLACK WIRES. FIXTURES WEIGHING
MORE THAN 56 POUNDS SHALL BE SUPPORTED
INDEPENDENTLY FROM THE STRUCTURE ABOVE
INDEPENDENTLY OF THE GRID SYSTEM WITH
APPROVED HANGERS. CABLE TRAYS, ELECTRICAL
CONDUIT, COMMUNICATION CABLE,AND OTHER
SIMILAR INSTALLATIONS SHALL BE SUPPORTED
INDEPENDENTLY FROM THE CEILING.
DESIGN SCOPE: STRUTS AND SPLAYS ARE NOT REQUIRED FOR CEILINGS IN
ROOMS LESS THAN 1000 SQUARE FEET IN AREA(IN AREAS
WITH THE SURROUNDING WALLS BRACED TO STRUCTURE).
ENGINEERING: LEWIS &VAN VLEET INC. HAS BEEN RETAINED TO DESIGN
THE CEILING GRID SUPPORT AND BRACING, AND
ATTACHMENTS FROM THE GRID SYSTEM TO THE
SUPPORTING STRUCTURE. IT IS THE RESPONSIBILITY OF
THE BUIDING OWNER, CONTRACTOR, OR ENGINEER OF
RECORD TO VERIFY THAT THE STRUCTURE HAS ADEQUATE
STRENGTH AND LATERAL STABILITY TO RESIST THE LOADS
IMPOSED ON IT BY THE SUSPENDED CEILING.
CODES: LEWIS &VAN VLEET, INC. HAS FOLLOWED THE STANDARD
PROVISIONS OF THE 2012 IBC, THE 2014 OSSC,AND ASCE 7-
16 IN THE DESIGN OF THIS SYSTEM.
S -11
SUSPENDED CEILING CALCULATIONS
• LEWIS &
consulting engineers
18660 s.w.boones ferry road
tuala , ego
503.885.8605tin Or n phone97062 503.885.1206 fax
VAN VLEET
incorporated
LATERAL LOADING: CONDITION NO.2, SECTOR B, LEVEL 1, TYPE 1
SPECTRAL ACCELERATION SDS 0.716
SITE CLASS = D
IMPORTANCE FACTOR Ip= 1.25
COMPONENT AMPLIFICATION FACTOR ap= 1
COMPONENT AMPLIFICATION FACTOR Rp= 2.5
CEILING WEIGHT w= 4 PSF
ATTACHMENT HEIGHT OF CEILING z = 15.167 FEET 1+ 2*z/h = 1.687
AVERAGE ROOF HEIGHT h = 44.167 FEET
DESIGN FOR TOTAL LATERAL FORCE FOR A 12' X 12' GRID:
TOTAL WEIGHT: Wp= w* 12' * 12' = 576 LBS.
LATERAL LOAD: Fp= 0.4 *ap*Sos*Wp*0.7 2 *z
1 +
Rp/ Ip
Fp= 97 LBS. ASCE 7-16 ++ (EQ. 13.3-1)
MANDATORY LOWER BOUND: Fp = 108 LBS.. ASCE 7-1(o ++ (EQ. 13.3-3)
OPTIONAL UPPER BOUND: Fp = 577 LBS. ASCE 7-14 ++ (EQ. 13.3-2)
++ NOTE: 0.7 FACTOR IS APPLIED TO THE FORCES FOR ALLOWABLE STRESS DESIGN
S-v2
SUSPENDED CEILING CALCULATIONS
' LEWIS &
consulting engineers
18660 s.w.Peones ferry road
tualatin, oregon 97062
503.885.8605 phone 503.885.1206fax
SPLAY WIRE AND CONNECTION TO STRUCTURE: CONDITION NO. 2, SECTOR B, LEVEL 1,TYPE 1
Strut Wire CEILING GRID 12 FT. X 12 FT.
45 deg.
Ceiling
CHECK DIAGONAL WIRE SPLAYS: 12 GA. Fr 55,000 PSI A= 0.0088 SO. IN.
CAPACITY OF WIRE: Tmax= 0.6 * Fy 8 *A
= 290 LB.
CONTROLLING SEISMIC FORCE: Fp DESIGN = 108 LB.
TENSION iN WIRE: T = Fp DESIGN /COS 45 DEG. = 153 LB. OK
114" DIA. X 3" LAG SCREW W/ EYE TO JOIST CHORD OR TIE TO JOIST CHORD
CHECK COMPRESSION STRUT:
1'-0" to 7'-0" use 1 5/8" -20 GA. STUD WITH 1 1/4" FLANGES
SSMA SECTION 1625125-33
5-13
SUSPENDED CEILING CALCULATIONS
• LEWIS &
consulting engineers
18660 s.w.boones ferry road
tua[atin,oregon 97062
503.885.8605 phone 503.885.1206 fax
VAN VLEET
Incorporated
PERIMETER CLOSURE ANGLE SUPPORT AT WALL:
CHECK WALL ANGLE SUPPORT AT WALL--MINIMUM 7/8"X 7/8"X 0.0188"ANGLE
IL. ——V-- .-——I————11\
CHECK THIS SPAN —MINIMUM#8 SCREW
2 ft
t i I
2fl.. SUSPENSION WIRE
CONNECTION POINT
/R - - - —
4ft. 4ft.
FRAMING PLAN
P DL= 4 PSF
P =4PSFx4FTx1/2x8FTx1/2x1/2
`u = 16 LB
III- IlIlIllIllUlIIll
w = 4PSFx2FTx1/2
= 4 PLF
R R
RMAx = 16 LB +4 PLF x 4 FT x 1/2 (CONTINUOUS ANGLE)
= 24 LB
M = 16 LB x 2 FT x 1/8+4 PLF x(2 FT)a x 1/12 (CONTINUOUS ANGLE)
= 5.33 FT-LB
OK- SEE ANGLE CAPACITY CALCULATION ON NEXT PAGE
SUSPENDED CEILING CALCULATIONS > 1`i
• LEWIS &
71 Consulting engineers
18660 s.w.boones ferry road
tualatin,oregon 97062
503.885.8605 phone 503.885.1206 fax
VAN VLEET
i ncorporaied
ANGLE CAPACITY CALCULATION
0.875"MIN.
/ '1
.11/
0.0188"
0.875"MIN.
DISREGARD
STIFFENING LIPS
(0.875 IN)` (0.0188 I N)`
0.0188 IN + (0.875 IN -0.0188 IN)
2 2
y_
0.0188 1N x (2 x 0.875 IN -0.0188 IN)
y r 0.2258 IN
- (0.875 IN)' 0.875 IN 2
IYvLEG =0.0188 IN x +0.0188 IN x 0.875 IN x -0.226 IN
_ 12 2
= 0.0018 IN4
C (0.0188 IN)3 1 0.0188 IN 2
IYHLEG =(0.875 IN-0.0188 IN) +(0.875 IN -0.0188 IN)x0.0188 IN x 0.226 IN-
12 2
= 0.00076 IN4
ly= IYvLEG+ IYHLEG= 0. 0.00254 IN4
ly
Sy= = 0.0039 IN3
0.875 IN -0.226 IN
MGAP = Sy x 0.6 x 33 KSI =6.46 FT-LB> 5.33 FT-LB ACTUAL-OK
ANGLE SPANS 24" BETWEEN STUDS
a--1
•
SUSPENDED CEILING CALCULATIONS
LEWIS &
consulting engineers
18660 s.w.boones ferry road
tualatln,oreg0n 97062
503.885.8605 phone 503.885.1206 fax
VAN VLEET I
Incorporated
ANGLE FASTENING TO STUDS
11 24 LB MAXIMUM
/ I
R
24e Z
,,lc.—.4111.• Fp
R M8 SCREWS
TO STUDS
Rr= Rv= 24 LB MAXIMUM
'CAPACITY= 117 LB
VCAPACITY— 90 LB
24 24
INTERACTION: + = 0.4718 <1 OK
117 90
#8 SCREW TO EACH STUD OK
S_tH
Project Name: Condition 1 Page 1 of 1
Model: Condition 2
Date: 02/18/2020
Code: 2012 NASPEC [AISI S100-2012] Simpson Strong-Tie®CFS DesignerTM 3.2.0.5
Section : 1625125-33(33 ksi) Single C Stud
I Maxo= 114.0 Ft-Lb Va = 600.7 lb I = 0.07 in"4
Loads have not been modified for strength checks
NO
Loads have been multiplied by 0.70 for deflection calculations
Bridging Connectors-Design Method=AISI S100
Simpson Strong-Tie
SpanlCantiLever Bridging Connector Stress Ratio
Span N/A -
Shear and Web Crippling Checks
Bending and Shear(Unstiffened): N/A
7.00 Bending and Shear(Stiffened): NA
Web Stiffeners Required?: No
?'®
1
Simpson Strong-Tie®Connectors
Connector Anchor
Support Rx(Ib) Ry(lb) Simpson Strong-Tie®Connector Interaction Interaction
R2 0 0 SCB45.5(2)&Anchorage Designed by Engineer 0.00% NA
R1 0 108 FCB43.5 Min(4#12-14) &Anchorage Designed by 14.30% NA
Engineer
Reference catalog for connector and anchor requirement notes as well as screw placements requirement
Flexural and Deflection Check Deflection
Mmax Mmaxl Mpos Bracing Ma(Brc) Mpos/
Span Ft-Lb Maxo Ft-Lb (in) Ft-Lb Ma(Brc) (in) Ratio
Span 0.0 0.000 0.0 None 58.8 0.000 0.000 L/0
Distortional Buckling Check
Span K-phi Lm Brae Ma-d Mmax/
lb-in/in in Ft-Lb Ma-d
Span 0,00 84.0 123.4 0.000
Combined Bending and Axial Load Details
Axial Ld Bracing(in) Max K-phi Lm Bracing Allow Intr.
Span (lb) KyLy KtLt KL/r (lb-inlin) (in) load(lb) P/Pa Value
Span 108.0(c) None None 191 0.0 84.0 262.0(c) 0.41 0.41
SIMPSON STRONG-TIE COMPANY INC. www.strongtie.com
S-l"1
• SUSPENDED CEILING CALCULATIONS
• LEWIS &
consulting engineers
18660 s.w.boones ferry road
Tualatin, oregon 97062
503.885.8605 phone 503.885.1206 fax
VAN VLEET
incorporated
PROJECT: Twality Middle School-Condition 3, Sector C, Level 1, Type 1
TYPE OF GRID: ACOUSTICAL CEILING
CERTAINTEED 15/16"TEE SYSTEM
CS12-12-20 HEAVY DUTY MAINS
CS4-12-12 4' CROSS TEE
CS2-12-12 2' CROSS TEE
WA15-15 WALL ANGLE
CTSPC-2 PERIMETER CLIP
DISTANCE FROM CEILING ACOUSTICAL GRID- MAX. DROP = 2.6667 FEET
TO STRUCTURE:
COMPRESSION STRUTS: SEE PAGE S-24 FOR SUMMARY
DIAGONAL WIRE SPLAYS: 12 GA 55 KSI 4 WAYS AT EACH COMPRESSION STRUT
VERTICAL HANGER WIRES: 12 GA. 55 KSI AT 4'-0" O.C. ALONG MAIN RUNNERS
STRUCTURE ABOVE CEILING: GLULAM BEAMS
FASTENERS FOR SPLAY WIRES: 1/4" DIA. X 3" LAG SCREW W/ EYE TO BEAM
PERIMETER WIRES IN EACH ORTHOGONAL DIRECTION, ONE END OF THE
AND ATTACHMENTS: CEILING GRID MAY BE ATTACHED TO THE CLOSURE ANGLE.
THE OTHER ENDS IN EACH HORIZONTAL DIRECTION SHALL
HAVE 3/4 INCH CLEARANCE FROM THE WALL AND BE
SUPPORTED BY AN CERTAINTEED WA15-15 SEISMIC
PERIMETER CLIP AT ALL MAIN AND CROSS RUNNERS. NO
PERIMETER WIRES ARE REQUIRED IN THIS INSTANCE. THIS
FRAMING OPTION MUST BE APPROVED BY THE LOCAL
AUTHORITY HAVING JURISDICTION.
STRUT AND SPLAY SPACING: 12'-0" X 12'-0" OR MAXIMUM 144 SQUARE FEET
`✓ `\t$
4
SUSPENDED CEILING CALCULATIONS
LEWIS &
711 consulting engineers
18660 s.w.boones ferry road
tualatin,oregon 97062
503.885.8605 phone 503.885.1206 fax
VAN VLEET
incorporated
CEILING MOUNTED LIGHT LIGHTING FIXTURES, EGRESS LIGHTING, SPEAKER, AIR
FIXTURES, EGRESS LIGHTS, TERMINALS, OR MECHANICAL SERVICES WEIGHING UP
SPEAKER, AIR TERMINALS, TO 56 POUNDS AND DIRECTLY SUPPORTED BY THE
MECHANICAL SERVICES, CEILING GRID SYSTEM SHALL BE POSITIVELY
AND OTHER CEILING ATTACHED TO THE CEILING SYSTEM. ATTACHMENT
SUPPORTED EQUIPMENT: SHALL BE MADE WITH A MINIMUM OF 4 APPROVED
FASTENERS LOCATED WITHIN 3 INCHES OF THE GRID
INTERSECTIONS TO SUSPENSION MAIN RUNNERS, OR
TO CROSS RUNNERS WITH THE SAME CARRYING
CAPACITY OF THE MAIN RUNNERS. IN ADDITION TO
THE ABOVE GRID CONNECTION, FIXTURES WEIGHING
AT LEAST 20 POUNDS BUT NOT MORE THAN 56
POUNDS SHALL HAVE TWO 0,080 INCH (12 GAUGE
A.W.G.) HANGER WIRES CONNECTED FROM THE I
FIXTURE TO THE CEILING SYSTEM HANGERS OR TO
THE STRUCTURE ABOVE. THESE WIRES MAY BE
SLACK. FIXTURES WEIGHING LESS THAN 20 POUNDS
DO NOT REQUIRE SLACK WIRES. FIXTURES WEIGHING
MORE THAN 56 POUNDS SHALL BE SUPPORTED
INDEPENDENTLY FROM THE STRUCTURE ABOVE
INDEPENDENTLY OF THE GRID SYSTEM WITH
APPROVED HANGERS. CABLE TRAYS, ELECTRICAL
CONDUIT, COMMUNICATION CABLE, AND OTHER
SIMILAR INSTALLATIONS SHALL BE SUPPORTED
INDEPENDENTLY FROM THE CEILING.
DESIGN SCOPE: STRUTS AND SPLAYS ARE NOT REQUIRED FOR CEILINGS IN
ROOMS LESS THAN 1000 SQUARE FEET IN AREA(IN AREAS
WITH THE SURROUNDING WALLS BRACED TO STRUCTURE).
ENGINEERING: LEWIS &VAN VLEET INC. HAS BEEN RETAINED TO DESIGN
THE CEILING GRID SUPPORT AND BRACING, AND
ATTACHMENTS FROM THE GRID SYSTEM TO THE
SUPPORTING STRUCTURE. IT IS THE RESPONSIBILITY OF
THE BUIDING OWNER, CONTRACTOR, OR ENGINEER OF
RECORD TO VERIFY THAT THE STRUCTURE HAS ADEQUATE
STRENGTH AND LATERAL STABILITY TO RESIST THE LOADS
IMPOSED ON IT BY THE SUSPENDED CEILING,
CODES: LEWIS &VAN VLEET, INC. HAS FOLLOWED THE STANDARD
PROVISIONS OF THE 2012 IBC,THE 2014 OSSC,AND ASCE 7-
110 IN THE DESIGN OF THIS SYSTEM.
• SUSPENDED CEILING CALCULATIONS
• LEWIS &
711 consulting engineers
18660 s.w.boones ferry road
tualatin,Oregon 97062
503.885.8605 phone 503.885.1206 fax
VAN VLEET
incorporated
LATERAL LOADING: CONDITION NO. 3,SECTOR C, LEVEL 1, TYPE 1
SPECTRAL ACCELERATION Sps= 0.716
SITE CLASS = D
IMPORTANCE FACTOR Ip= 1.25
COMPONENT AMPLIFICATION FACTOR ap = 1
COMPONENT AMPLIFICATION FACTOR Rp= 2,5
CEILING WEIGHT w= 4 PSF
ATTACHMENT HEIGHT OF CEILING z= 15 FEET 1+2 *z/h = 1.679
AVERAGE ROOF HEIGHT h = 44.167 FEET
DESIGN FOR TOTAL LATERAL FORCE FOR A 12' X 12' GRID:
TOTAL WEIGHT: Wp= w* 12' * 12' = 576 LBS.
LATERAL LOAD: Fp= 0.4 *ap*Sos* Wp* 0.7 2 *z
1 +
Rp/ IP h _
Fp= 97 LBS. ASCE 7-1(v++ (EQ. 13.3-1)
MANDATORY LOWER BOUND: Fp = 108 LBS. ASCE 7-16++ (EQ. 13.3-3)
OPTIONAL UPPER BOUND: Fp= 577 LBS. ASCE 7-1.++ (EQ. 13.3-2)
++ NOTE: 0.7 FACTOR IS APPLIED TO THE FORCES FOR ALLOWABLE STRESS DESIGN
SUSPENDED CEILING CALCULATIONS
' LEWIS &
71 consulting engineers
18660 s.w. boones ferry road
tualatin,oregon 97062
503.885.8605 phone 503.885.1206 fax
SPLAY WIRE AND CONNECTION TO STRUCTURE: CONDITION NO. 3, SECTOR C, LEVEL 1, TYPE 1
Strut Wire CEILING GRID 12 FT. X 12 FT.
45 deg.
Ceiling
CHECK DIAGONAL WIRE SPLAYS: 12 GA Fy = 55,000 PSI A= 0,0088 SQ. IN.
CAPACITY OF WIRE: Tmax= 0.6 * Fy 8 *A
= 290 LB.
CONTROLLING SEISMIC FORCE: Fp DESIGN = 108 LB,
TENSION IN WIRE: T = Fp DESIGN /COS 45 DEG. = 153 LB. OK
1/4" DIA. X 3" LAG SCREW W/ EYE TO BEAM
CHECK COMPRESSION STRUT:
1'-0" to 5'-0"use 1 5/8" - 20 GA. STUD WITH 1 1/4" FLANGES
SSMA SECTION 1625125-33
S-21
SUSPENDED CEILING CALCULATIONS
• LEWIS &
consulting enqineers
18660 s w. boones ferry road
tualatin, oregon 97062
503.885.8605 phone 503.885.1206 fax
VAN VLEET
incorporated
PERIMETER CLOSURE ANGLE SUPPORT AT WALL:
CHECK WALL ANGLE SUPPORT AT WALL-- MINIMUM 7/8"X 7/8"X 0.0188"ANGLE
MOM
\CHECK THIS SPAN "MINIMUM#8 SCREW
2 ft..
I I
SUSPENSION WIRE
2 ft. CONNECTION POINT
4ft. Oft.
FRAMING PLAN
DL = 4 PSF
P =4PSFx4FTx1/2x8FTx1/2x1/2
= 16 LB
11111111111111111111
w =4PSFx2FTx1/2
= 4 PLF
R R
RMAX = 16 LB + 4 PLF x 4 FT x 1/2 (CONTINUOUS ANGLE)
24 LB
M = 16 LB x 2 FT x 1/8 +4 PLF x(2 FT)2 x 1/12 (CONTINUOUS ANGLE)
= 5.33 FT-LB
OK SEE ANGLE CAPACITY CALCULATION ON NEXT PAGE
S 22
SUSPENDED CEILING CALCULATIONS
LEWIS &
Iconsulting engineers
18660 s.w.boones ferry road
tualatin,oregon 97062
503.885.8605 phone 503.885,1206 fax
VAN VLEET
incorporated
ANGLE CAPACITY CALCULATION
0.875" MIN.
/ /
11,
0.6188"
0.875"MIN.
DISREGARD
STIFFENING LIPS
f
(0.875 IN)` (0.0188 IN)`
0.0188 IN 1+ (0.875 IN -0.0188 IN)
2 _ 2
Y=
0.0188 IN x(2 x 0.875 IN -0.0188 IN)
y= 0.2258 IN
- (0.875 IN)' 0.875 IN 2
IYVLEG = 0.0188 IN x + 0.0188 IN x 0.875 IN x -0,226 IN
12 2 _
= 0.0018 IN4
C (0.0188 IN)3 _ 0.01881N— 2
IYHLEG =(0.875 IN-0.0188 IN) 4-(0.875 1N -0.0188 IN)x0.0188 IN x 0.226 IN -
12 2
= 0.00076 IN4
IY= IYvLEG+ IYHLEG= 0• 0.00254 IN4
iy
Sy= = 0.0039 IN3
0.875 IN - 0.226 IN
McAP= Sy x 0.6 x 33 KSI = 6.46 FT-LB > 5.33 FT-LB ACTUAL-OK
ANGLE SPANS 24" BETWEEN STUDS
V LJ
SUSPENDED CEILING CALCULATIONS
LEWIS &
consultinq enqineers
18660 s.w boones ferry road
tualatin,oregon 97062
503.886.8605 phone 603.885.1206 fax
VAN VLEET I
incorporaIPd
ANGLE FASTENING TO STUDS •
24 LB MAXIMUM
V
. 4
/ •5'
R II
24"
/i`-^-�► Fp
R t8 SCREWS
TO STUDS
RT= RV= 24 LB MAXIMUM
TCAPACITY= 117 LB
UCAPACITY= 90 LB
24 24
INTERACTION: + = 0.4718 <1 OK
117 90
#8 SCREW TO EACH STUD OK
S Z`(
Project Name: Condition 1 Page 1 of 1
Model: Condition 3 Date:02/18/2020
Code: 2012 NASPEC]AISI S100-2012] Simpson Strong-Tie®CFS Designer.," 3.2.0.5
Section : 162S125-33(33 ksi)Single C Stud
1 Maxo= 114.0 FL-Lb Va = 600.7 lb I = 0.07 inA4
Loads have not been modified for strength checks
N Loads have been multiplied by 0.70 for deflection calculations
Bridging Connectors-Design Method=AISI S100
Simpson Strong-Tie
SpanlCantiLever Bridging Connector Stress Ratio
Span N/A -
Shear and Web Crippling Checks
Bending and Shear(Unstiffened): N/A
2.67 Bending and Shear(Stiffened): NA
Web Stiffeners Required?: No
?.'®
I
Simpson Strong-Tie®Connectors
Connector Anchor
Support Rx(Ib) Ry(lb) Simpson Strong-Tie®Connector Interaction Interaction
R2 0 0 SCB45.5(2) &Anchorage Designed by Engineer 0.00% NA
R1 0 108 FCB43.5 Min(4#12-14)&Anchorage Designed by 14.30% NA
Engineer
*Reference catalog for connector and anchor requirement notes as well as screw placements requirement
Flexural and Deflection Check Deflection
Mmax Mmax/ Mpos Bracing Ma(Brc) Mpos/
Span Ft-Lb Maxo Ft-Lb (in) Ft-Lb Ma(Brc) (in) Ratio
Span 0.0 0,000 0.0 None 112.4 0.000 0.000 L/O
Distortional Buckling Check
Span K-phi Lm Brac Ma-d Mmax/
lb-in/in in Ft-Lb Ma-d
Span 0.00 32.0 123.4 0,000
Combined Bending and Axial Load Details
Axial Ld Bracing(in) Max K-phi Lm Bracing Allow Intr.
Span (lb) KyLy KtLt KL/r (lb-in/in) (in) load{lb) P/Pa Value
Span 108.0(c) None None 73 0.0 32.0 1024.0(c) 0.11 0.11
SIMPSON STRONG-TIE COMPANY INC. 1ww.strongtle.com
SUSPENDED CEILING CALCULATIONS
LEWIS &
consulting engineers
18660 s.w.boones ferry road
Tualatin,Oregon 97062
503.885.8605 phone 503.885.1206 fax
VAN VLEET
incorporated
PROJECT: Twality Middle School - Condition 4, Sector A, Level 2, Type 1
TYPE OF GRID: ACOUSTICAL CEILING
CERTAINTEED 15/16" TEE SYSTEM
CS12-12-20 HEAVY DUTY MAINS
CS4-12-12 4' CROSS TEE
CS2-12-12 2' CROSS TEE
WA15-15 WALL ANGLE
CTSPC-2 PERIMETER CLIP
DISTANCE FROM CEILING ACOUSTICAL GRID- MAX. DROP = 6.333 FEET
TO STRUCTURE:
COMPRESSION STRUTS: SEE PAGE S-32 FOR SUMMARY
DIAGONAL WIRE SPLAYS: 12 GA. 55 KSI 4 WAYS AT EACH COMPRESSION STRUT
VERTICAL HANGER WIRES: 12 GA. 55 KSI AT 4'-0" O.C. ALONG MAIN RUNNERS
STRUCTURE ABOVE CEILING: WOOD I-JOISTS
FASTENERS FOR SPLAY WIRES: 1/4" DIA. X 3" LAG SCREW W/EYE TO JOIST CHORD
PERIMETER WIRES IN EACH ORTHOGONAL DIRECTION, ONE END OF THE
AND ATTACHMENTS: CEILING GRID MAY BE ATTACHED TO THE CLOSURE ANGLE.
THE OTHER ENDS IN EACH HORIZONTAL DIRECTION SHALL
HAVE 3/4 INCH CLEARANCE FROM THE WALL AND BE
SUPPORTED BY AN CERTAINTEED WA15-15 SEISMIC
PERIMETER CLIP AT ALL MAIN AND CROSS RUNNERS. NO
PERIMETER WIRES ARE REQUIRED IN THIS INSTANCE. THIS
FRAMING OPTION MUST BE APPROVED BY THE LOCAL
AUTHORITY HAVING JURISDICTION.
STRUT AND SPLAY SPACING: 12'-0"X 12'-0" OR MAXIMUM 144 SQUARE FEET
S _2(0
SUSPENDED CEILING CALCULATIONS
LEWIS &
consulting engineers
18660 s.w.boones ferry road
tualatin,oregon 97062
503.885.8605 phone 503.885.1206 fax
VAN VLEET
incorporated
CEILING MOUNTED LIGHT LIGHTING FIXTURES, EGRESS LIGHTING, SPEAKER, AIR
FIXTURES,EGRESS LIGHTS, TERMINALS, OR MECHANICAL SERVICES WEIGHING UP
SPEAKER,AIR TERMINALS, TO 56 POUNDS AND DIRECTLY SUPPORTED BY THE
MECHANICAL SERVICES, CEILING GRID SYSTEM SHALL BE POSITIVELY
AND OTHER CEILING ATTACHED TO THE CEILING SYSTEM. ATTACHMENT
SUPPORTED EQUIPMENT: SHALL BE MADE WITH A MINIMUM OF 4 APPROVED
FASTENERS LOCATED WITHIN 3 INCHES OF THE GRID
INTERSECTIONS TO SUSPENSION MAIN RUNNERS, OR
TO CROSS RUNNERS WITH THE SAME CARRYING
CAPACITY OF THE MAIN RUNNERS. 1N ADDITION TO
THE ABOVE GRID CONNECTION, FIXTURES WEIGHING
AT LEAST 20 POUNDS BUT NOT MORE THAN 56
POUNDS SHALL HAVE TWO 0.080 INCH (12 GAUGE
A.W.G.) HANGER WIRES CONNECTED FROM THE
FIXTURE TO THE CEILING SYSTEM HANGERS OR TO
THE STRUCTURE ABOVE. THESE WIRES MAY BE
SLACK. FIXTURES WEIGHING LESS THAN 20 POUNDS
DO NOT REQUIRE SLACK WIRES. FIXTURES WEIGHING
MORE THAN 56 POUNDS SHALL BE SUPPORTED
INDEPENDENTLY FROM THE STRUCTURE ABOVE
INDEPENDENTLY OF THE GRID SYSTEM WITH
APPROVED HANGERS. CABLE TRAYS, ELECTRICAL
CONDUIT, COMMUNICATION CABLE, AND OTHER
SIMILAR INSTALLATIONS SHALL BE SUPPORTED
INDEPENDENTLY FROM THE CEILING.
DESIGN SCOPE: STRUTS AND SPLAYS ARE NOT REQUIRED FOR CEILINGS IN
ROOMS LESS THAN 1000 SQUARE FEET IN AREA(IN AREAS
WITH THE SURROUNDING WALLS BRACED TO STRUCTURE).
ENGINEERING: LEWIS &VAN VLEET INC. HAS BEEN RETAINED TO DESIGN
THE CEILING GRID SUPPORT AND BRACING, AND
ATTACHMENTS FROM THE GRID SYSTEM TO THE
SUPPORTING STRUCTURE. IT IS THE RESPONSIBILITY OF
THE BUIDING OWNER, CONTRACTOR, OR ENGINEER OF
RECORD TO VERIFY THAT THE STRUCTURE HAS ADEQUATE
STRENGTH AND LATERAL STABILITY TO RESIST THE LOADS
IMPOSED ON IT BY THE SUSPENDED CEILING.
CODES: LEWIS&VAN VLEET, INC. HAS FOLLOWED THE STANDARD
PROVISIONS OF THE 2012 IBC, THE 2014 OSSC, AND ASCE 7-
16 IN THE DESIGN OF THIS SYSTEM,
SUSPENDED CEILING CALCULATIONS
• LEWIS &
71 consulting engineers
18660 s.w.boones ferry road
tualatin,oregon 97062
503.885.8605 phone 503.885.1205 fax
VAN VLEET
Incorporated
LATERAL LOADING: CONDITION NO.4,SECTOR A, LEVEL 2,TYPE 1
SPECTRAL ACCELERATION SDS= 0.716
SITE CLASS= D
IMPORTANCE FACTOR Ip= 1,25
COMPONENT AMPLIFICATION FACTOR ap= 1
COMPONENT AMPLIFICATION FACTOR Rp= 2.5
CEILING WEIGHT w= 4 PSF
ATTACHMENT HEIGHT OF CEILING z = 31.5 FEET 1+ 2 *zlh = 2.426
AVERAGE ROOF HEIGHT h= 44.167 FEET
DESIGN FOR TOTAL LATERAL FORCE FOR A 12' X 12' GRID:
TOTAL WEIGHT: WF = w* 121 * 12' = 576 LBS.
LATERAL LOAD: F = 0.4*ap *Sps*Wp * 0.7 2 *z^
1 +
RP/1p h
Fp = 140 LBS. ASCE 7-11a++ (EQ. 13.3-1)
MANDATORY LOWER BOUND: Fp = 108 LBS. ASCE 7-11e++ (EQ. 13.3-3)
OPTIONAL UPPER BOUND: Fp= 577 LBS. ASCE 7-11s++ (EQ. 13.3-2)
++ NOTE: 0.7 FACTOR IS APPLIED TO THE FORCES FOR ALLOWABLE STRESS DESIGN
SUSPENDED CEILING CALCULATIONS S 28
• LEWIS &
71 consulting engineers
18660 s.w.boones ferry road
tualatin,oregon 97062
503.885.8605 phone 503.885.1206 fax
SPLAY WIRE AND CONNECTION TO STRUCTURE: CONDITION NO.4, SECTOR A, LEVEL 2, TYPE 1
Strut Wire CEILING GRID 12 FT. X 12 FT.
45 deg.
Ceiling
CHECK DIAGONAL WIRE SPLAYS: 12 GA. Fy = 55,000 PSI A= 0.0088 SQ. IN.
i
CAPACITY OF WIRE: Tmax = *0.6 Fy 8 A
= 290 LB.
CONTROLLING SEISMIC FORCE: Fp DESIGN = 140 LB.
TENSION IN WIRE: T= Fp DESIGN /COS 45 DEG. = 198 LB. OK
1/4" DIA. X 3" LAG SCREW W/ EYE TO JOIST CHORD
CHECK COMPRESSION STRUT:
1'-0"to 5'-0"use 1 5/8" -20 GA. STUD WITH 1 1/4" FLANGES
SSMA SECTION 162S125-33
,d4 'J
SUSPENDED CEILING CALCULATIONS
LEWIS &
consulting engineers
18660 s.w.boones ferry road
tualatin,Oregon 97062
503.885.8605 phone 503.885.1206 fax
VAN VLEET
Incorporated
PERIMETER CLOSURE ANGLE SUPPORT AT WALL:
CHECK WALL ANGLE SUPPORT AT WALL -- MINIMUM 7/8"X 7/8"X 0.0188"ANGLE
\CHECK THIS SPAN `MINIMUM#8 SCREW
2ft.
I I f
2 ft. SUSPENSION WIRE
CONNECTION POINT
4ft. 4ft.
FRAMING PLAN
DL = 4 PSF
P =4 PSF x 4 FT x 1/2 x 8 FT x 1/2 x 1/2
= 16 LB
111111.11111111111
w =4PSFx2FTx1/2
= 4 PLF
R R
RMAX = 16 LB +4 PLF x 4 FT x 1/2 (CONTINUOUS ANGLE)
= 24 LB
M = 16 LB x 2 FT x 1/8+ 4 PLF x (2 FT)2 x 1/12 (CONTINUOUS ANGLE)
= 5.33 FT-LB
OK- SEE ANGLE CAPACITY CALCULATION ON NEXT PAGE
SUSPENDED CEILING CALCULATIONS
LEWIS &
consulting engineers
18660 s.w.boones ferry road
tualatin,oregon 97062
,,w,- 503.885.8605 phone 503.885.1206 fax
VAN VLEET
incorporated
ANGLE CAPACITY CALCULATION
0.875"MIN.
/ /
/
0.0188"
0.875" MIN.
DISREGARD
STIFFENING PS
/
(0.875 IN)r (0.0188 IN)`
0.0188 IN + (0.875 IN-0.0188 IN)
2 2
Y=
0.0188 IN x(2 x 0.875 IN -0.0188 IN)
y= 0.2258 IN
- (0.875 IN)' 0.875 IN 2
lyvi-Ec =0.0188 IN x f 0.0188 IN x 0.875 IN x — -0.226 IN
= 0.0018 IN4_
12 2
(0.0188!N}3 r
0.0188 I 2
IYHLEG =(0.875 IN -0.0188 IN)
12 J+(0.875 IN-0.0188 IN)x0.0188 IN x 0.226 IN-
- 2
= 0.00076 IN4
ly= lYv>_EG+ IYHLEG= 0. 0.00254 IN4
ly
Sy= = 0.0039 IN3
0.875 IN -0.226 IN
Mpp,P= Sy x 0.6 x 33 KSI =6.46 FT-LB > 5.33 FT-LB ACTUAL -OK
ANGLE SPANS 24" BETWEEN STUDS
SUSPENDED CEILING CALCULATIONS
LEWIS &
consulting engineers
18660 s.w.boones ferry road
tualatin,oregon 97062
503.885.8605 phone 503.885.1206 fax
VAN VLEET
incorporated
ANGLE FASTENING TO STUDS
24 LB MAXIMUM
•
..1
1
AV/ 1
R ..A,
24"
r!v ......,Or` Fp
R #8 SCREWS
TO STUDS
RT=Rv= 24 LB MAXIMUM
TCAPACI?Y= 117 LB
UCAPACITV= 9O LB
24 24
INTERACTION: + = 0.4718 <1 OK
117 90
#8 SCREW TO EACH STUD OK
•
V _)u
Project Name: Condition 1 Page 1 of 1
Model: Condition 4 Date:02/18/2020
Code: 2012 NASPEC[AISI S100-2012] Simpson Strong-Tie®CFS DesignerTM 3.2.0.5
Section : 162S125-33(33 ksi) Single C Stud
I Maxo= 114.0 Ft-Lb Va= 600.7 lb I = 0.07 in"4
Loads have not been modified for strength checks
0 Loads have been multiplied by 0.70 for deflection calculations
Bridging Connectors -Design Method =AISI S100
Simpson Strong-Tie
Span/CantiLever Bridging Connector Stress Ratio
Span N/A -
Shear and Web Crippling Checks
Bending and Shear(Unstiffened): N/A
6.33 Bending and Shear(Stiffened): NA
Web Stiffeners Required?: No
z '
r O
t
Simpson Strong-Tie®Connectors
Connector Anchor
Support Rx(Ib) Ry(Ib) Simpson Strong-Tie®Connector Interaction Interaction
R2 0 0 SCB45.5(2)&Anchorage Designed by Engineer 0.00% NA
R1 0 140 FCB43.5 Min(4412-14)&Anchorage Designed by 18.54 % NA
Engineer
*Reference catalog for connector and anchor requirement notes as well as screw placements requirement
Flexural and Deflection Check Deflection
Mmax Mmax/ Mpos Bracing Ma(Brc) Mpos/
Span Ft-Lb Maxo Ft-Lb (in) Ft-Lb Ma(Brc) (in) Ratio
Span 0.0 0.000 0.0 None 68.1 0.000 0.000 L/O
Distortional Buckling Check
Span K-phi Lm Brae Ma-d Mmaxl
lb-in/in in Ft-Lb Ma-d
Span 0.00 76.0 123.4 0.000
Combined Bending and Axial Load Details
Axial Ld Bracing(in) Max K-phi Lm Bracing Allow Intr.
Span (lb) KyLy KtLt KL/r (lb-in/in) (in) load(lb) PIPa Value
Span 140.0(c) None None 173 0.0 76.0 295.4(c) 0.47 0.47
SIMPSON STRONG-TIE COMPANY INC. www.strongtie.com
• SUSPENDED CEILING CALCULATIONS
LEWIS &
71 consulting engineers
18660 s.w.boones ferry road
tualatin,oregon 97062
503.885.8605 phone 503.885.1206 fax
VAN VLEET
incorporated
PROJECT: Twality Middle School -Condition 5, Sector B, Level 2, Type 1
TYPE OF GRID: ACOUSTICAL CEILING
CERTAINTEED 15/16"TEE SYSTEM
CS12-12-20 HEAVY DUTY MAINS
CS4-12-12 4' CROSS TEE
CS2-12-12 2' CROSS TEE
WA15-15 WALL ANGLE
CTSPC-2 PERIMETER CLIP
DISTANCE FROM CEILING ACOUSTICAL GRID - MAX. DROP = 8.5 FEET
TO STRUCTURE:
COMPRESSION STRUTS: SEE PAGE S-40 FOR SUMMARY
DIAGONAL WIRE SPLAYS: 12 GA. 55 KSI 4 WAYS AT EACH COMPRESSION STRUT
VERTICAL HANGER WIRES: 12 GA. 55 KSI AT 4'-0"O,C. ALONG MAIN RUNNERS
STRUCTURE ABOVE CEILING: WOOD I-JOISTS
FASTENERS FOR SPLAY WIRES: 1/4" DIA. X 3" LAG SCREW W/ EYE TO JOIST CHORD
PERIMETER WIRES IN EACH ORTHOGONAL DIRECTION, ONE END OF THE
AND ATTACHMENTS: CEILING GRID MAY BE ATTACHED TO THE CLOSURE ANGLE.
THE OTHER ENDS IN EACH HORIZONTAL DIRECTION SHALL
HAVE 3/4 INCH CLEARANCE FROM THE WALL AND BE
SUPPORTED BY AN CERTAINTEED WA15-15 SEISMIC
PERIMETER CLIP AT ALL MAIN AND CROSS RUNNERS. NO
PERIMETER WIRES ARE REQUIRED IN THIS INSTANCE. THIS
FRAMING OPTION MUST BE APPROVED BY THE LOCAL
AUTHORITY HAVING JURISDICTION.
STRUT AND SPLAY SPACING: 12'-0"X 12'-0" OR MAXIMUM 144 SQUARE FEET
s-3 9
• SUSPENDED CEILING CALCULATIONS
• LEWIS &
11 consulting engineers
18660 s.w.boones ferry road
tualatin,oregon 97062
503.885.8605 phone 503.685.1206 fax
VAN VLEET
incorporated
CEILING MOUNTED LIGHT LIGHTING FIXTURES, EGRESS LIGHTING, SPEAKER,AIR
FIXTURES, EGRESS LIGHTS, TERMINALS, OR MECHANICAL SERVICES WEIGHING UP
SPEAKER,AIR TERMINALS, TO 56 POUNDS AND DIRECTLY SUPPORTED BY THE
MECHANICAL SERVICES, CEILING GRID SYSTEM SHALL BE POSITIVELY
AND OTHER CEILING ATTACHED TO THE CEILING SYSTEM. ATTACHMENT
SUPPORTED EQUIPMENT: SHALL BE MADE WITH A MINIMUM OF 4 APPROVED
FASTENERS LOCATED WITHIN 3 INCHES OF THE GRID
INTERSECTIONS TO SUSPENSION MAIN RUNNERS, OR
TO CROSS RUNNERS WITH THE SAME CARRYING
CAPACITY OF THE MAIN RUNNERS. IN ADDITION TO
THE ABOVE GRID CONNECTION, FIXTURES WEIGHING
AT LEAST 20 POUNDS BUT NOT MORE THAN 56
POUNDS SHALL HAVE TWO 0.080 INCH (12 GAUGE
A.W.G.) HANGER WIRES CONNECTED FROM THE
FIXTURE TO THE CEILING SYSTEM HANGERS OR TO
THE STRUCTURE ABOVE. THESE WIRES MAY BE
SLACK. FIXTURES WEIGHING LESS THAN 20 POUNDS
DO NOT REQUIRE SLACK WIRES. FIXTURES WEIGHING
MORE THAN 56 POUNDS SHALL BE SUPPORTED
INDEPENDENTLY FROM THE STRUCTURE ABOVE
INDEPENDENTLY OF THE GRID SYSTEM WITH
APPROVED HANGERS. CABLE TRAYS, ELECTRICAL
CONDUIT, COMMUNICATION CABLE,AND OTHER
SIMILAR INSTALLATIONS SHALL BE SUPPORTED
INDEPENDENTLY FROM THE CEILING.
DESIGN SCOPE: STRUTS AND SPLAYS ARE NOT REQUIRED FOR CEILINGS IN
ROOMS LESS THAN 1000 SQUARE FEET IN AREA(IN AREAS
WITH THE SURROUNDING WALLS BRACED TO STRUCTURE).
ENGINEERING: LEWIS &VAN VLEET INC. HAS BEEN RETAINED TO DESIGN
THE CEILING GRID SUPPORT AND BRACING,AND
ATTACHMENTS FROM THE GRID SYSTEM TO THE
SUPPORTING STRUCTURE. IT IS THE RESPONSIBILITY OF
THE BUIDING OWNER, CONTRACTOR, OR ENGINEER OF
RECORD TO VERIFY THAT THE STRUCTURE HAS ADEQUATE
STRENGTH AND LATERAL STABILITY TO RESIST THE LOADS
IMPOSED ON IT BY THE SUSPENDED CEILING.
CODES: LEWIS &VAN VLEET, INC. HAS FOLLOWED THE STANDARD
PROVISIONS OF THE 2012 IBC, THE 2014 OSSC, AND ASCE 7-
1bIN THE DESIGN OF THIS SYSTEM.
SUSPENDED CEILING CALCULATIONS
LEWIS &
consulting engineers
18660 s.w.boones ferry road
.. ,' tu1alalin,oregon 97062
503,885.8605 phone 503.885.1206 fax
;.
VAN VLEET
incorporated
LATERAL LOADING: CONDITION NO. 5, SECTOR B, LEVEL 2, TYPE 1
SPECTRAL ACCELERATION SIDS= 0.716
SITE CLASS = D
IMPORTANCE FACTOR Ip= 1.25
COMPONENT AMPLIFICATION FACTOR ap= 1
COMPONENT AMPLIFICATION FACTOR Rp= 2.5
CEILING WEIGHT w= 4 PSF
ATTACHMENT HEIGHT OF CEILING z= 1 31.5 FEET 1+2 *z/h = 2.426
AVERAGE ROOF HEIGHT h = 44.167 FEET
DESIGN FOR TOTAL LATERAL FORCE FOR A 12' X 12' GRID:
TOTAL WEIGHT: Wp= w* 12' * 12'= 576 LBS.
l
LATERAL LOAD: FP= 0.4 *ap *SIDS*Wp* 0.7 2 *z
1 +
Rp/Ip h
Fp = 140 LBS. ASCE 7-142++ (EQ. 13.3-1)
MANDATORY LOWER BOUND: Fp= 108 LBS. ASCE 7.1ff ++ (EQ. 13,3-3)
OPTIONAL UPPER BOUND: Fp= 577 LBS. ASCE 7-1t0++ (EQ. 13.3-2)
++ NOTE: 0.7 FACTOR IS APPLIED TO THE FORCES FOR ALLOWABLE STRESS DESIGN
J J
•
SUSPENDED CEILING CALCULATIONS
• LEWIS &
consulting engineers
18660 s.w. boones ferry road
tualatin,oregon 97062
503.885.8605 phone 503.885.1206 fax
SPLAY WIRE AND CONNECTION TO STRUCTURE: CONDITION NO. 5, SECTOR B, LEVEL 2,TYPE 1
Strut Wire CEILING GRID 12 FT. X 12 FT.
45 deg.
Ceiling
CHECK DIAGONAL WIRE SPLAYS: 12 GA. Fy= 55,000 PSI A= 0.0088 SQ. IN.
CAPACITY OF WIRE: Tmax = 0.6 " Fy 8 *A
290 LB.
CONTROLLING SEISMIC FORCE: Fp DESIGN = 140 LB.
TENSION IN WIRE: T= Fp DESIGN /COS 45 DEG. = 198 LB OK
1/4" DIA. X 3" LAG SCREW W/ EYE TO JOIST CHORD
CHECK COMPRESSION STRUT:
1'-0"to 9'-0" use 1 5/8" -20 GA. STUD WITH 1 1/4" FLANGES
SSMA SECTION 1628125-33
SUSPENDED CEILING CALCULATIONS
• LEWIS &
consulting engineers
18660 s.w.boones ferry road
tualatin,oregon 97062
503.885.8605 phone 503.885,1206 fax
VAN VLEET
incorporated
PERIMETER CLOSURE ANGLE SUPPORT AT WALL:
CHECK WALL ANGLE SUPPORT AT WALL -- MINIMUM 7/8"X 718"X 0.0188"ANGLE
I
CHECK THIS SPAN MIMUM/18 SCREW N
2 ft.
I I
SUSPENSION WIRE 2ft
CONNECTION POINT
Oft.
4 ft.
FRAMING PLAN
DL= 4 PSF
P = 4PSFx4FTx1/2x8FTx1/2x1/2
= 16 LB
uluuuuul■uiuuuluuuu11
w =4PSFx2FTx1/2
= 4 PLF
R R
RMAx = 16 LB +4 PLF x 4 FT x 1/2 (CONTINUOUS ANGLE)
= 24 LB
M = 16 LB x 2 FT x 1/8 +4 PLF x(2 FT)2x 1/12 (CONTINUOUS ANGLE)
= 5.33 FT-LB
OK- SEE ANGLE CAPACITY CALCULATION ON NEXT PAGE
SUSPENDED CEILING CALCULATIONS
LEWIS &
consulting engineers
18860 s.w.boones ferry road
tualatin,oregon 97062
503.885.8605 phone 503.885.1206 fax
VAN VLEET
incorporated
ANGLE CAPACITY CALCULATION
0275"MIN.
r/
0.0188"
0.875"MIN.
DISREGARD
STIFFENING LIPS
I
/
(0.875 IN)`' (0.0188 IN)`
0.0188 IN + (0.875 IN -0.0188 IN)
2 _ 2
y_ —
0.0188 IN x(2 x 0.875 IN-0.0188 IN)
y = 0.2258 IN
r (0.875 IN)' - 0.875 IN —2
IYVLEG =0.0188 IN x +0.0188 IN x 0,875 IN x -0.226 IN
_ 12 2 _
= 0.0018 IN4
(0.01881N)3 0.0188IN 2
[
IYHLEG =(0.875 IN-0.0188 IN) + 0.875 IN-0.0188 IN)x0.0188 IN x IIr 0.226 IN -
12 EELL 2
= 0.00076 IN4
IY= IYVLEG+ IYHLEG =0. 0.00254 IN4
ly
Sy= = 0.0039 IN3
0.875 IN -0.226 IN
MCAP= Sy x 0.6 x 33 KSI =6.46 FT-LB> 5.33 FT-LB ACTUAL -OK
ANGLE SPANS 24" BETWEEN STUDS
J V l
•
SUSPENDED CEILING CALCULATIONS
LEWIS &
71 consulting engineers
18660 sm.boones ferry road
tualatin,Oregon 97062
503.885.8605 phone 503.885.1206 fax
VAN VLEET /l .
incorporated �/
ANGLE FASTENING TO STUDS -
•
24 LB MAXIMUM
ono nee mil
4
•
t..
AV
R
24" Zr
1111111111111111111.111- ,�_ Ffl
R #8 SCREWS
do 1171".
TO STUDS
RT= RV= 24 LB MAXIMUM
TcAPACITY= 117 LB
VCAPACITY= 90 LB
24 24
INTERACTION: + = 0.4718 <1 OK
117 90
#8 SCREW TO EACH STUD OK
-. L.V
Project Name: Condition 1 Page 1 of 1
Model: Condition 5 Date:02/18/2020
Code: 2012 NASPEC [AISI S100-20121 Simpson Strong-Tie®CFS DesignerTM 3.2.0.5
Section : 162S125-33 (33 ksi) Single C Stud
I Maxo= 114.0 Ft-Lb Va= 600.7 lb I = 0.07 in'4
Loads have not been modified for strength checks
N Loads have been multiplied by 0.70 for deflection calculations
Bridging Connectors-Design Method =AISI S100
Simpson Strong-Tie
Span/CantiLever Bridging Connector Stress Ratio
Span N/A -
Shear and Web Crippling Checks
Bending and Shear(Unstiffened): N/A
8.50 Bending and Shear(Stiffened): NA
Web Stiffeners Required?: No
I
Simpson Strong-Tie®Connectors
Connector Anchor
Support Rx(Ib) Ry(lb) Simpson Strong-Tie®Connector Interaction Interaction
R2 0 0 SCB45.5(2) &Anchorage Designed by Engineer 0.00% NA
R1 0 140 FCB43.5 Min(4#12-14)&Anchorage Designed by 18.54% NA
Engineer
Reference catalog for connector and anchor requirement notes as well as screw placements requirement
Flexural and Deflection Check Deflection
Mmax Mmax/ Mpos Bracing Ma(Brc) Mpos/
Span Ft-Lb Maxo Ft-Lb (in) Ft-Lb Ma(Brc) (in) Ratio
Span 0.0 0.000 0.0 None 45.4 0.000 0.000 L/0
Distortional Buckling Check
Span K-phi Lm Brae Ma-d Mmaxl
lb-in/in in Ft-Lb Ma-d
Span 0.00 102.0 123.4 0.000
Combined Bending and Axial Load Details
Axial Ld Bracing(in) Max K-phi Lm Bracing Allow Intr.
Span (lb) KyLy KtLt KL/r (lb-inlin) (in) load(lb) P/Pa Value
Span 140.0(c) None None 232 0.0 102,0 211.3(c) 0.66 0.66
SIMPSON STRONG-TIE COMPANY INC. www.strongtie.com
SUSPENDED CEILING CALCULATIONS
. LEWIS &
71 consulting engineers
18660 s.w. boones ferry road
tualatin,Oregon 97062
503.885.8605 phone 503.885.1206 fax
VAN VLEET
into rp n r algid
PROJECT: Twality Middle School- Condition 6, Sector C, Level 2, Type 1
TYPE OF GRID: ACOUSTICAL CEILING
CERTAINTEED 15/16"TEE SYSTEM
CS12-12-20 HEAVY DUTY MAINS
CS4-12-12 4' CROSS TEE
CS2-12-12 2' CROSS TEE
WA15-15 WALL ANGLE
CTSPC-2 PERIMETER CLIP
DISTANCE FROM CEILING ACOUSTICAL GRID - MAX. DROP= 7 FEET
TO STRUCTURE:
COMPRESSION STRUTS: SEE PAGE S-48 FOR SUMMARY
DIAGONAL WIRE SPLAYS: 12 GA. 55 KSI 4 WAYS AT EACH COMPRESSION STRUT
VERTICAL HANGER WIRES: 12 GA. 55 KSI AT 4'-0" 0.C. ALONG MAIN RUNNERS
STRUCTURE ABOVE CEILING: WOOD I-JOISTS
FASTENERS FOR SPLAY WIRES: 1/4" DIA. X 3" LAG SCREW W/ EYE TO JOIST CHORD
PERIMETER WIRES IN EACH ORTHOGONAL DIRECTION, ONE END OF THE
AND ATTACHMENTS: CEILING GRID MAY BE ATTACHED TO THE CLOSURE ANGLE.
THE OTHER ENDS IN EACH HORIZONTAL DIRECTION SHALL
HAVE 3/4 INCH CLEARANCE FROM THE WALL AND BE
SUPPORTED BY AN CERTAINTEED WA15-15 SEISMIC
PERIMETER CLIP AT ALL MAIN AND CROSS RUNNERS. NO
PERIMETER WIRES ARE REQUIRED IN THIS INSTANCE. THIS
FRAMING OPTION MUST BE APPROVED BY THE LOCAL
AUTHORITY HAVING JURISDICTION.
STRUT AND SPLAY SPACING: 12'-0"X 12'-0" OR MAXIMUM 144 SQUARE FEET
c7 "T Li
SUSPENDED CEILING CALCULATIONS
LEWIS &
consulting engineers
18660 s.w.boones ferry road
tualatin,oregon 97062
•
503.885.8605 phone 503.885.1206 fax
VAN VLEET
Incorporated
CEILING MOUNTED LIGHT LIGHTING FIXTURES, EGRESS LIGHTING, SPEAKER, AIR
FIXTURES, EGRESS LIGHTS, TERMINALS, OR MECHANICAL SERVICES WEIGHING UP
SPEAKER, AIR TERMINALS, TO 56 POUNDS AND DIRECTLY SUPPORTED BY THE
MECHANICAL SERVICES, CEILING GRID SYSTEM SHALL BE POSITIVELY
AND OTHER CEILING ATTACHED TO THE CEILING SYSTEM. ATTACHMENT
SUPPORTED EQUIPMENT: SHALL BE MADE WITH A MINIMUM OF 4 APPROVED
FASTENERS LOCATED WITHIN 3 INCHES OF THE GRID
INTERSECTIONS TO SUSPENSION MAIN RUNNERS, OR
TO CROSS RUNNERS WITH THE SAME CARRYING
CAPACITY OF THE MAIN RUNNERS. IN ADDITION TO
THE ABOVE GRID CONNECTION, FIXTURES WEIGHING
AT LEAST 20 POUNDS BUT NOT MORE THAN 56
POUNDS SHALL HAVE TWO 0.080 INCH (12 GAUGE
A.W.G.) HANGER WIRES CONNECTED FROM THE
FIXTURE TO THE CEILING SYSTEM HANGERS OR TO
THE STRUCTURE ABOVE.THESE WIRES MAY BE
SLACK. FIXTURES WEIGHING LESS THAN 20 POUNDS
DO NOT REQUIRE SLACK WIRES. FIXTURES WEIGHING
MORE THAN 56 POUNDS SHALL BE SUPPORTED
INDEPENDENTLY FROM THE STRUCTURE ABOVE
INDEPENDENTLY OF THE GRID SYSTEM WITH
APPROVED HANGERS. CABLE TRAYS, ELECTRICAL
CONDUIT, COMMUNICATION CABLE, AND OTHER
SIMILAR INSTALLATIONS SHALL BE SUPPORTED
INDEPENDENTLY FROM THE CEILING.
DESIGN SCOPE: STRUTS AND SPLAYS ARE NOT REQUIRED FOR CEILINGS IN
ROOMS LESS THAN 1000 SQUARE FEET IN AREA (IN AREAS
WITH THE SURROUNDING WALLS BRACED TO STRUCTURE).
ENGINEERING: LEWIS&VAN VLEET INC. HAS BEEN RETAINED TO DESIGN
THE CEILING GRID SUPPORT AND BRACING, AND
ATTACHMENTS FROM THE GRID SYSTEM TO THE
SUPPORTING STRUCTURE. IT IS THE RESPONSIBILITY OF
THE BUIDING OWNER, CONTRACTOR, OR ENGINEER OF
RECORD TO VERIFY THAT THE STRUCTURE HAS ADEQUATE
STRENGTH AND LATERAL STABILITY TO RESIST THE LOADS
IMPOSED ON IT BY THE SUSPENDED CEILING.
CODES: LEWIS&VAN VLEET, INC. HAS FOLLOWED THE STANDARD
PROVISIONS OF THE 2012 IBC, THE 2014 OSSC, AND ASCE 7-
110 IN THE DESIGN OF THIS SYSTEM.
S- `I-3
SUSPENDED CEILING CALCULATIONS
• LEWIS &
711 consulting engineers
18660 s.w.boones ferry road
fualatin,Oregon 97062
503.885.8605 phone 503.885.1206 fax
VAN VLEET
into(pot a l ad
LATERAL LOADING: CONDITION NO. 6, SECTOR C, LEVEL 2, TYPE 1
SPECTRAL ACCELERATION Sos= 0.716
SITE CLASS = D
IMPORTANCE FACTOR I,= 1.25
COMPONENT AMPLIFICATION FACTOR ap= 1
COMPONENT AMPLIFICATION FACTOR Rp= 2.5
CEILING WEIGHT w= 4 PSF
ATTACHMENT HEIGHT OF CEILING z= 31.5 FEET 1+ 2 *z/h = 2.426
AVERAGE ROOF HEIGHT h = 44.167 FEET
DESIGN FOR TOTAL LATERAL FORCE FOR A 12' X 12' GRID:
TOTAL WEIGHT: Wp= w* 12' * 12' = 576 LBS. I
LATERAL LOAD: Fp= 0.4 *ap* Sos*WP*0.7 2 *z
1 +
Rp/ 1p h
Fp= 140 LBS. ASCE 7-1b ++ (EQ. 13,3-1)
MANDATORY LOWER BOUND: Fp = 108 LBS. ASCE 7-1ta++ (EQ. 13.3-3)
OPTIONAL UPPER BOUND: Fp = 577 LBS. ASCE 7-11e++ (EQ. 13.3-2)
++ NOTE; 0.7 FACTOR IS APPLIED TO THE FORCES FOR ALLOWABLE STRESS DESIGN
r
SUSPENDED CEILING CALCULATIONS
LEWIS &
71 consulting engineers
18660 s.w.boones ferry road
tualatin, oregon 97062
503.885.8605 phone 503.885.1206 fax
SPLAY WIRE AND CONNECTION TO STRUCTURE: CONDITION NO. 6, SECTOR C, LEVEL 2, TYPE 1
Strut Wire CEILING GRID 12 FT. X 12 FT.
45 deg.
Ceiling
CHECK DIAGONAL WIRE SPLAYS: 12 GA, Fy= 55,000 PSI A= 0.0088 SQ. IN.
CAPACITY OF WIRE: Tmax= 0.6 " Fy 8 *A
= 290 LB.
CONTROLLING SEISMIC FORCE: Fp DESIGN = 140 LB.
TENSION IN WIRE: T= Fp DESIGN/COS 45 DEG. = 198 LB. OK
114" DIA. X 3" LAG SCREW W/ EYE TO JOIST CHORD
CHECK COMPRESSION STRUT:
1'-0" to 7'-0" use 1 5/8" -20 GA. STUD WITH 1 1/4" FLANGES
SSMA SECTION 162S125-33
SUSPENDED CEILING CALCULATIONS
- LEWIS &
consuitina engineers
18660 s.w.boones ferry road
tualatin,oregon 97062
503.885.8605 phone 503.885.1206 fax
VAN VLEET
ncorpor a led
PERIMETER CLOSURE ANGLE SUPPORT AT WALL:
CHECK WALL ANGLE SUPPORT AT WALL -- MINIMUM 7/8"X 7/8"X 0.0188"ANGLE
-
CHECK THIS SPAN 'MINIMUM#8 SCREW
2 ft
I I I
2ft SUSPENSION WIRE
CONNECTION POINT
4fl,. 4ft.
FRAMING PLAN
P DL = 4 PSF
P =4PSFx4 FTx1/2x8FTx1/2x1/2
= 16 LB
1111111111MH
w =4PSFx2FTx1/2
= 4 PLF
R R
RMAx = 16 LB +4 PLF x 4 FT x 1/2 (CONTINUOUS ANGLE)
= 24 LB
M = 16 LB x 2 FT x 1/8 + 4 PLF x (2 FT)2 x 1/12 (CONTINUOUS ANGLE)
= 5.33 FT-LB
OK- SEE ANGLE CAPACITY CALCULATION ON NEXT PAGE
s.,Iy
SUSPENDED CEILING CALCULATIONS
• LEWIS &
consulting engineers
18660 s.w.boones ferry road
tualatin, Oregon 97062
503.885.8606 phone 503.885.1206 fax
VAN VLEET
incorporated
ANGLE CAPACITY CALCULATION
0.875" MIN.
11
0,0188"
0275"MIN.
DISREGARD
STIFFENING LIPS
(0.875 IN)` (0.0188 I N)`
0.0188 IN + (0.875 IN -0.0188 IN)
2 _ _ 2
Y=
0.0188 IN x (2 x 0.875 IN -0.0188 IN)
y= 0.2258 IN
(0.8751N)' 0.875 IN ^2
IYVLEG =0.0188 IN x + 0.0188 IN x 0.875 IN x -0.226 IN
12 2
= 0.0018 IN4
[ (0.0188 IN)3 1 _ 0.01881N- 2
IYHLEG = (0.875 IN-0.0188 IN) IL +(0.875 IN-0.0188 IN)x0.0188 IN x 0.226 IN-
12 2
= 0.00076 IN4
IY= 1YVLEG+ IYHLEG= 0. 0.00254 IN4
ly
Sy= = 0.0039 IN3
0.875 IN-0.226 IN
MCAP= Sy x 0.6 x 33 KSI =6.46 FT-LB > 5.33 FT-LB ACTUAL-OK
ANGLE SPANS 24" BETWEEN STUDS
J t I
. SUSPENDED CEILING CALCULATIONS
LEWIS &
consulting engineers
18660 s.w.boones ferry road
tualatin,oregon 97062
503.885.8605 phone 503.885.1206 fax
VAN VLEET
incorporaiee
ANGLE FASTENING TO STUDS -
24 LB MAXINSUIvI
. 1
,
1
R
24" A,
R 1✓ #8 SCREWS
TO STUDS
RT=RV= 24 LB MAXIMUM
TCAPACITY= 117 LB
✓CAPACITY= 90 LB
24 24
INTERACTION: + = 0.4718 <1 OK
117 90
#8 SCREW TO EACH STUD OK
S-` 5
Project Name: Condition 1 Page 1 of 1 I
Model: Condition 6 Date: 02/18/2020
Code: 2012 NASPEC [AISI S100-2012] Simpson Strong-Tie@ CFS DesignerT*' 3.2.0.5
Section : 162S125-33(33 ksi) Single C Stud
I Maxo= 114.0 Ft-Lb Va= 600.7 lb I= 0.07 in"4
•
Loads have not been modified for strength checks
N 0 Loads have been multiplied by 0.70 for deflection calculations
Bridging Connectors -Design Method =AISI S100
Simpson Strong-Tie
Span/CantiLever Bridging Connector Stress Ratio
Span N/A -
Shear and Web Crippling Checks
Bending and Shear(Unstiffened): N/A
7,00 Bending and Shear(Stiffened): NA
Web Stiffeners Required?: No
�®
I
Simpson Strong-Tie®Connectors
Connector Anchor
Support Rx(lb) Ry(lb) Simpson Strong-Tie®Connector Interaction Interaction
R2 0 0 SCB45,5(2) &Anchorage Designed by Engineer 0.00% NA
R1 0 140 FCB43.5 Min(4#12-14) &Anchorage Designed by 18.54% NA
Engineer
*Reference catalog for connector and anchor requirement notes as well as screw placements requirement
Flexural and Deflection Check Deflection
Mmax Mmaxl Mpos Bracing Ma(Brc) Mposl
Span Ft-Lb Maxo Ft-Lb (in) Ft-Lb Ma(Brc) (in) Ratio
Span 0.0 0.000 0.0 None 58.8 0.000 0.000 L/0
Distortional Buckling Check
Span K-phi Lm Brac Ma-d Mmax/
lb-in/in in Ft-Lb Ma-d
Span 0.00 84,0 123.4 0.000
Combined Bending and Axial Load Details
Axial Ld Bracing(in) Max K-phi Lm Bracing Allow Intr.
Span (lb) KyLy KtLt KL/r (lb-inlin) (in) load(lb) P/Pa Value
Span 140.0(c) None None 191 0.0 84.0 262.0(c) 0.53 0.53
SIMPSON STRONG-TIE COMPANY INC. www.strongtie.com
• SUSPENDED CEILING CALCULATIONS S-961
• LEWIS &
consulting engineers
18660 s.w. boones ferry road
tualatin,oregon 97062
503.885.8605 phone 503.885,1206 fax
VAN VLEET
incorporated
PROJECT: Twality Middle School -Condition 7, Sector D, Level 2, Type 1
TYPE OF GRID: ACOUSTICAL CEILING
CERTAINTEED 15/16"TEE SYSTEM
CS12-12-20 HEAVY DUTY MAINS
CS4-12-12 4' CROSS TEE
CS2-12-12 2' CROSS TEE
WA15-15 WALL ANGLE
CTSPC-2 PERIMETER CLIP
DISTANCE FROM CEILING ACOUSTICAL GRID - MAX. DROP = 8 FEET
TO STRUCTURE:
COMPRESSION STRUTS: SEE PAGE S-54 FOR SUMMARY
DIAGONAL WIRE SPLAYS: 12 GA. 55 KS] 4 WAYS AT EACH COMPRESSION STRUT
VERTICAL HANGER WIRES: 12 GA. 55 KSI AT 4'-0" Q.C. ALONG MAIN RUNNERS
STRUCTURE ABOVE CEILING: WOOD I-JOISTS
FASTENERS FOR SPLAY WIRES: 1/4" DIA, X 3" LAG SCREW W/ EYE TO JOIST CHORD
PERIMETER WIRES IN EACH ORTHOGONAL DIRECTION, ONE END OF THE
AND ATTACHMENTS: CEILING GRID MAY BE ATTACHED TO THE CLOSURE ANGLE,
THE OTHER ENDS IN EACH HORIZONTAL DIRECTION SHALL
HAVE 3/4 INCH CLEARANCE FROM THE WALL AND BE
SUPPORTED BY AN CERTAINTEED WA15-15 SEISMIC
PERIMETER CLIP AT ALL MAIN AND CROSS RUNNERS. NO
PERIMETER WIRES ARE REQUIRED IN THIS INSTANCE. THIS
FRAMING OPTION MUST BE APPROVED BY THE LOCAL
AUTHORITY HAVING JURISDICTION.
STRUT AND SPLAY SPACING: 12'-0"X 12'-0"OR MAXIMUM 144 SQUARE FEET
• SUSPENDED CEILING CALCULATIONS •Sb
. LEWIS &
7711 consulting engineers
18660 s.w.boones ferry road
tualatin,oregon 97062
503.885.8505 phone 503.885.1206 fax
VAN VLEET
Incorporated
CEILING MOUNTED LIGHT LIGHTING FIXTURES, EGRESS LIGHTING, SPEAKER, AIR
FIXTURES, EGRESS LIGHTS, TERMINALS, OR MECHANICAL SERVICES WEIGHING UP
SPEAKER, AIR TERMINALS, TO 56 POUNDS AND DIRECTLY SUPPORTED BY THE
MECHANICAL SERVICES, CEILING GRID SYSTEM SHALL BE POSITIVELY
AND OTHER CEILING ATTACHED TO THE CEILING SYSTEM, ATTACHMENT
SUPPORTED EQUIPMENT: SHALL BE MADE WITH A MINIMUM OF 4 APPROVED
FASTENERS LOCATED WITHIN 3 INCHES OF THE GRID
INTERSECTIONS TO SUSPENSION MAIN RUNNERS, OR
TO CROSS RUNNERS WITH THE SAME CARRYING
CAPACITY OF THE MAIN RUNNERS. IN ADDITION TO
THE ABOVE GRID CONNECTION, FIXTURES WEIGHING
AT LEAST 20 POUNDS BUT NOT MORE THAN 56
POUNDS SHALL HAVE TWO 0.080 INCH (12 GAUGE
A.W.G.) HANGER WIRES CONNECTED FROM THE
FIXTURE TO THE CEILING SYSTEM HANGERS OR TO
THE STRUCTURE ABOVE. THESE WIRES MAY BE
SLACK. FIXTURES WEIGHING LESS THAN 20 POUNDS
DO NOT REQUIRE SLACK WIRES. FIXTURES WEIGHING
MORE THAN 56 POUNDS SHALL BE SUPPORTED
INDEPENDENTLY FROM THE STRUCTURE ABOVE
INDEPENDENTLY OF THE GRID SYSTEM WITH
APPROVED HANGERS. CABLE TRAYS, ELECTRICAL
CONDUIT, COMMUNICATION CABLE, AND OTHER
SIMILAR INSTALLATIONS SHALL BE SUPPORTED
INDEPENDENTLY FROM THE CEILING.
DESIGN SCOPE: STRUTS AND SPLAYS ARE NOT REQUIRED FOR CEILINGS IN
ROOMS LESS THAN 1000 SQUARE FEET IN AREA(IN AREAS
WITH THE SURROUNDING WALLS BRACED TO STRUCTURE).
ENGINEERING: LEWIS &VAN VLEET INC. HAS BEEN RETAINED TO DESIGN
THE CEILING GRID SUPPORT AND BRACING, AND
ATTACHMENTS FROM THE GRID SYSTEM TO THE
SUPPORTING STRUCTURE. IT IS THE RESPONSIBILITY OF
THE BUIDING OWNER, CONTRACTOR, OR ENGINEER OF
RECORD TO VERIFY THAT THE STRUCTURE HAS ADEQUATE
STRENGTH AND LATERAL STABILITY TO RESIST THE LOADS
IMPOSED ON IT BY THE SUSPENDED CEILING.
CODES: LEWIS&VAN VLEET, INC. HAS FOLLOWED THE STANDARD
PROVISIONS OF THE 2012 IBC, THE 2014 OSSC, AND ASCE 7-
16 IN THE DESIGN OF THIS SYSTEM.
SUSPENDED CEILING CALCULATIONS a Si
LEWIS &
consulting engineers
18660 s.w.boones ferry road
tualatin,oregon 97062
503.885.8605 phone 503.885.1206 fax
VAN VLEET
incorporated
LATERAL LOADING: CONDITION NO. 7, SECTOR D, LEVEL 2,TYPE 1
SPECTRAL ACCELERATION Sos= 0.716
SITE CLASS = D
IMPORTANCE FACTOR IP= 1.25
COMPONENT AMPLIFICATION FACTOR ap= 1
COMPONENT AMPLIFICATION FACTOR Rp= 2.5
CEILING WEIGHT w= 4 PSF
ATTACHMENT HEIGHT OF CEILING z= 28 FEET 1+ 2 *z/h = 2.268
AVERAGE ROOF HEIGHT h= 44.167 FEET
DESIGN FOR TOTAL LATERAL FORCE FORA 12' X 12' GRID:
TOTAL WEIGHT: Wp = w* 12' * 12' = 576 LBS.
LATERAL LOAD: Fp = 0.4 *ap* Sps*W,*0.7 2 *z
1 +
Rp/Ip h _,
Fp= 131 LBS. ASCE 7-1b ++ (EQ. 13.3-1)
MANDATORY LOWER BOUND: Fp = 108 LBS. ASCE 7-14,++ (EQ. 13.3-3)
OPTIONAL UPPER BOUND: Fp= 577 LBS. ASCE 7-Ito++ (EQ. 13.3-2)
++ NOTE: 0.7 FACTOR IS APPLIED TO THE FORCES FOR ALLOWABLE STRESS DESIGN
•
»`
SUSPENDED CEILING CALCULATIONS
• LEWIS &
11 consulting engineers
18660 s.w.boonesferry road
tualatin,oregon 97062
503.885.8605 phone 503.885.1206fax
SPLAY WIRE AND CONNECTION TO STRUCTURE: CONDITION NO. 7, SECTOR D, LEVEL 2,TYPE 1
Strut Wire CEILING GRID 12 FT. X 12 FT.
45 deg.
Ceiling
CHECK DIAGONAL WIRE SPLAYS: 12 GA. Fy= 55,000 PSI A= 0.0088 SQ. IN.
CAPACITY OF WIRE: Tmax= 0.6 ` Fy 8 *A
= 290 LB.
CONTROLLING SEISMIC FORCE: Fp DESIGN = 131 LB.
TENSION IN WIRE:
T= FpDESIGN I COS 45 DEG. = 185 LB. OK
1/4" DIA. X 3" LAG SCREW W/EYE TO JOIST CHORD
CHECK COMPRESSION STRUT:
1'-0" to 8'-0" use 1 5/8" -20 GA. STUD WITH 1 1/4" FLANGES
SSMA SECTION 162S125-33
S-5:S
. SUSPENDED CEILING CALCULATIONS
• LEWIS &
Iconsulting engineers
18660 s.w.boones ferry road
tuaiatin,oregon 97062
\ , 503.885.8605 phone 503.885.1206 fax
VAN VLEET
incorporated
PERIMETER CLOSURE ANGLE SUPPORT AT WALL:
CHECK WALL ANGLE SUPPORT AT WALL -- MINIMUM 7/8"X 718"X 0.0188"ANGLE
MOW 1
\CHECK THIS SPAN MINIMUM#8 SCREW
2 It.
i I I
ft SUSPENSION WIRE
CONNECTION POINT
4 P.. r 4 ft. 1
FRAMING PLAN
P DL= 4 PSF
P =4 PSF x 4 FT x 1/2 x 8 FT x 1/2 x 1/2
VI
= 16 LB
11111111111111111111
w =4PSFx2FTx1/2
= 4 PLF
R R
RMAx = 16 LB +4 PLF x 4 FT x 1/2 (CONTINUOUS ANGLE)
= 24 LB
M = 16 LB x 2 FT x 1/8 +4 PLF x(2 FT)2 x 1/12 (CONTINUOUS ANGLE)
= 5.33 FT-LB
OK-SEE ANGLE CAPACITY CALCULATION ON NEXT PAGE
s -5�
• SUSPENDED CEILING CALCULATIONS
• LEWIS &
consulting engineers
18660 s.w.boones ferry road
tualatin, Oregon 97062
503.885.8605 phone 503.885.1206fax
VAN VLEET
incorporated
ANGLE CAPACITY CALCULATION
0,87S" MIN.
f f
0.0188"
0.875"MIN.
DISREGARD
STIFFENING LIPS
(0.875 IN)` (0.0188 IN)`
0.0188 IN + (0.875 IN -0.0188 IN)
2 2
Y=
0.0188 IN x(2 x 0.875 IN -0.0188 IN)
y = 0.2258 1N
- (0.875 IN)' 0.875 IN 2
IYvLEG =0.0188 IN x + 0.0188 IN x 0.875 IN x -0.226 IN
_ 12 2
0.0018 IN4
C (0.0188 IN)3 - - 0.0188 IN- 2
IyHLEG =(0.875 IN-0.0188 IN) +(0.875 IN-0.0188 IN)x0.0188 IN x 0.226 IN-
12 2
= 0.00076 IN4
ly= IyvLEG + IYHLEG= 0. 0.00254 IN4
ly
Sy= = 0.0039 IN3
0.875 IN -0.226 IN
McAQ = Sy x 0.6 x 33 KSI =6.46 FT-LB > 5.33 FT-LB ACTUAL- OK
ANGLE SPANS 24" BETWEEN STUDS
SUSPENDED CEILING CALCULATIONS
LEWIS &
consulting engineers
18660 s.w.boons ferry road
Tualatin,Oregon 97062
603.885.8605 phone 503.885.1206 fax
VAN VLEET
incorporated
ANGLE FASTENING TO STUDS
24 LB MAXIMUM
AVI
24"
R f#8 SCREWS
TO STUDS
RT=Rv= 24 LB MAXIMUM
TTAPAcir'= 117 LB
VcAPACITY- 90 LB
24 24
INTERACTION: + = 0.4718 <1 OK
117 90
#8 SCREW TO EACH STUD OK
U -plc)
Project Name: Condition 1 Page 1 of 1
Model: Condition 7
Date:02/18/2020
Code: 2012 NASPEC [AISI S100-2012] Simpson Strong-Tie®CFS Designer1M 3.2.0.5
Section : 162S125-33(33 ksi) Single C Stud
Maxo= 114.0 Ft-Lb Va= 600,7 lb 1= 0.07 in"4
ILoads have not been modified for strength checks
N Loads have been multiplied by 0.70 for deflection calculations
Bridging Connectors -Design Method=AISI S100
Simpson Strong-Tie
SpanfCantiLever Bridging Connector Stress Ratio
Span N/A -
Shear and Web Crippling Checks
Bending and Shear(Unstiffened): N/A
8.00 Bending and Shear(Stiffened): NA
Web Stiffeners Required?: No
I
Simpson Strong-Tie®Connectors
Connector Anchor
Support Rx(Ib) Ry(lb) Simpson Strong-Tie®Connector Interaction Interaction
R2 0 0 SCB45.5(2) &Anchorage Designed by Engineer 0.00% NA
R1 0 131 FCA43,5 Min(4/112-14)&Anchorage Designed by 17.35 % NA
Engineer
Reference catalog for connector and anchor requirement notes as well as screw placements requirement
Flexural and Deflection Check Deflection
Mmax Mmaxl Mpos Bracing Ma(Brc) Mpos/
Span Ft-Lb Maxo Ft-Lb (in) Ft-Lb Ma(Brc) (in) Ratio
Span 0.0 0.000 0,0 None 49.1 0.000 0.000 L/0
Distortional Buckling Check
Span K-phi Lm Brac Ma-d Mmaxl
lb-in/in in Ft-Lb Ma-d
Span 0.00 96.0 123.4 0.000
Combined Bending and Axial Load Details
Axial Ld Bracing(in) Max K-phi Lm Bracing Allow Intr.
Span (lb) KyLy KtLt KLIr (lb-in/in) (in) load(lb) PIPa Value
Span 131.0(c) None None 218 0.0 96.0 225.4(c) 0.58 0.58
SIMPSON STRONG-TIE COMPANY INC. www.strongtle.com
LEW,15 &
x; conLsulting engineers
Client
18660 s.w. boanes ferry rd. Job No. By
tualatIn.Oregon 97062
(503)BB5.96D5 phone [503]68 Job
5.1206 fax Date Sheet No. 5`S-
VAIN VLEET
Incorporated
f' 4Y ,, ..t_ S3 a tt z ,, .7,„ i 'r.�xzYc '[fiN tics rs t .+•>. 111 v.1 L.:t .3+-
1 ' 1 1 - t I -
1 c l V I7zs] �1 _ I Y.�/-7 .. : 4 1� .Y, ,I - I 1 _ _ -+ 1 1 ._I-
I
`, 1
;: 1 , 1 1 , 1 l � fiu -� "-(i r,+.)11` .M 1-- n7 I ( ' -
I
I 1 1 --- --,. 1 - - --
' I , I. 1
1 � I 1 � 1 ..-- - _ 1 11 I
I :• i t I '.. 1 : 1 1 , 1 : 1 i ti I -
I 1 I I I I
d r
p I t L._. ,
I � , b I ' IJ I '_ Y I -_ C Y V 11 - I I I--� F 1 1 :-- I
I I I I . I 1 , 1 I I 1._
- - � . .. 1 1 _ I � l 1
•
"' I I-- , ._-1-_ , 1_ rlls}u. 1 -_ TI t 1.--; 1--
, ,-, 1�'.-I ' 1 - 1— —, 1 1
1 !
I 1 I
- po I1
t I ! I e - ' 1 L. , I .L , 1-._ I. -r— -__, 1_ Ili — , -,—I I, I'.
I
r.
�� 3 a
.. 1 1 ; 1 1 I btiwp Cr i� —'
p � 1 >ti c
�r Fs y
1 ', 1 I ---t 1 I I 11 . l , I I 4f Ii1 1 -1- , 1 1 I ' t ' ' ; 1
i _
�
Q I I I I I•
, ... I
'RGe ,� _
1 I i I, 1 I 1 I ' I _ i -r _ 1 I1 -- , : ;11 I 1
•
•
I. .._ .I I __' I _ I_. : -_ ' j ...1.....1 , 1 4- - ! , I I_
-I ^ I...._i .I I - I •
PI
_ _ I I I 7- -'--°;7 1 1.� 1 '7- l.l_ c_I .. - _I I r 1 I 1 1 ; :
t I ' I _.... T 1-
1 1 ` III I I I
1 �py+�- Ir-� YY yy3 �}1. 1 � y�
k _ i.^ r I ..-. 1.R .�1 1 X * A A+ n. 1 ..�.!a..1 i __.1 • rf
! I. I U x 1 1 1 J 1 L. e
II
t � - I i i I I I _ _ I • . (7� ' • til 'L-, 1). FS l �' I ' It , , V4 . , . i ! i Hi :
d
1�l T
1 t
1IIl - . i
I_..i
-t t 1
I I
—
- -
_I •Ir l - t r . I
1I i I• , ra �1i ` 1 �� • -' S -i 1 L, I I I I I I I 1 AyT `t£51 -t�. 4= . . :- I .i-.i ! Fi- I ---t 1 1 1 I - — -'I I t !r . 4 1 _ . rJVS 7 } ' � { 1l 1-1I 1 0S � �$ �,� . • , I•`---• _ - { -f I 1 I t + II 1"-: i ' '- 25 - �� I 1 _• '1 I I ( i'- 4x � 2C. �- a - — 1 , _ :`i • , , 1 1 .—: : _,1 : . I 1 , I I
1f I ! I ;_ ' ! 1 t ,- V: - , �.-113.: c
. ' . } ;..,. \V - :`� ' 'C v� , v1 L_2a t O.w.c e..kq,'I I ' T, c ' (�nc . ca .- 41ot 4
11
I I I , 1 1 1 I I 1 E I I , i , k { 1la ,I I 1 -1 - I • i'I I. 1 -_ 1 I - 1 1 , 1 j' l 1 1r ` i. I � 1 1 1 I !f (I 1 _ t 1 : I i J11 : H III
. 11
{ a i I t ! ' 1 + .
. t I , 1 .,"—i 1 s I I'
1 N. .., f 1 i I t i -i
I
ti
1i I I I ,+ I I I I!I I 1 i I I , 7 - .i.- 7_ 1 I IFii 1 l I
1 - + .. . j.,:I 4-1 aaF.1I 1 1 • t< ux N .o'y� w 3s ES'nR` F bTT:'X..4-.F"4.-Y-.M` r R...:&G"uc...sbrrn4'a.kra was/ifi Y--- ,=7Fsn,.
Technical Information t imminim.
_ ,,,,
S-SS
Screw and Weld Capacities , : _'
Screw fable Nv 3'5
1. Capacities based on AISI 5100 Section E4 specification. 5. Screws are assumed to have a center-of-screw to edge-of-steel dimension of at
2.When connecting materials of different steel thicknesses or tensile strengths, least 1.5 times the nominal diameter(d)of the screw.
use the lowest values.Tabulated values assume two sheets of equal thickness 6. Values are for pure shear or tension loads.See AISI S100 Section E4.5 for
are connected, combined shear and pull-aver.
3. Capacities are based on Allowable Strength Design(ASD)and include safety 7. Tension capacity Is based on the lesser of pull-out capacity in sheet closest to
factor of 3.0. screw tip,or pull-over capacity for sheet closest to screw head(based on head
4. Where multiple fasteners are used,screws are assumed to have a center-to- diameter shown).
center spacing of at least 3 times the nominal diameter(d). 8. Higher values,especially for screw strength,may be obtained by specifying
screws from a specific manufacturer.
Allowable Screw Connection Capacity (Pounds Per Screw)
86 Screw 118 Screw d18 Screw 1112 Screw V."Screw
Designation Design Fy Yield Fe Tensie Thickness Thickness {ksi) (ksi) 0.138°Dia;0.25'Head 0.164'Dla;0.313'Head 0.190"Dia;0340'Head 0.216"Dia;0,340"Head 0.250'Dig 0.409"Head
Shear Tension Shear Tension Shear Tension Shear Tension Shear Tension
D25 0.0155 50 65 111' 39 111' 47 111' 54 - - - -
D20 0.0188 57 65 142' 48 150' 57 164' 66 109 75 - -
30EQD 0.0235 57 65 174' 60 184' 71 236' 82 152 93 - -
33EQD 0.0235 57 65 174' 60 184' 71 236' 82 152 93 - -
33EQS 0.0295 57 65 171 75 187 89 201 103 214 117 231 135
43EQS 0.0400 57 65 270 102 295 121 317 140 338 159 364 184
Values are based on testing using AISI SI00 procedures.
Weld'fable Notes
1. Weld capacities are based on the AISI 5100 Specification Sections E2.4 for fillet 5. Weld capacities are based an either 0,0938`or 0.125"diameter E60 or E70
welds and E2.5 for groove welds, electrodes.The use of 0.030"to 0.035"diameter wire electrodes may provide
2. When connecting materials of different steel thicknesses or tensile strengths best results.
(Fu),the lowest values should be used. 6.Transverse capacity is loading in perpendicular direction of the length of the weld.
3. Capacities are based on Allowable Strength Design(ASD)and Include appropriate 7. For flare groove welds,the effective throat of weld is conservatively assumed to
safety factors, be less than 2t.
4. Longitudinal capacity is loading In parallel direction of the length of the weld.
Weld Capacity (Pounds Per 1" Weld)
Weld Type
Designation Design Fy Yield Fu Tensile Nominal
Thickness Thickness (ksl) (ksi) Weld Size Filet Flam Groove
Longitudinal Ti g
an Longitudinal Transverse
43EQS 0.0400 57 65 '/s 639 1 1106 696 1 849
'For welds less than I"In length,AISI5100 equations E2.5-I and E2.5-2 must be checked.
a Values based on AISI S100 equation E2.6-2
R vaunnf.SCAFCO.cnrn Fri r l,,a nnnia 7 end CI nerce.rec an nre,,:n„c rnf r.»aflne
4U _Cci
it '2 4AC'et(A/X-e-411 .
PO BOX CCB#39 Tualatin,OR REGliC2 Phone:(503)612-01001 Request for Seismic Calculations
DR CCB#38335.WA RE(i#CASCAA'203QK Fax(503}612-0101
TO: Lewis &Van Vleet
18660 SW Boones Ferry Rd Tualatin DATE: 2/18/2020 12:09 PM
FAX: FROM: Dwight Smith
PROJECT: Twality Middle School PLEASE PROVIDE BY: Please work in when you can.
LOCATION: 14650 SW 97(h Ave Tigard Or 97224 This Is not time sensitive now.
GRID COMPONENTS TO BE USED
TYPE 1 TYPE 2
Manufacturer Certainteed 2'x4' pattern
Mains CS12-12-20
4'Cross Tees CS4-12-12
2'Cross Tees CS2-12-12
Wall Angle WA I5-15
ROOF CONDITION 1:Sector A Level 1
-- - Wood Framed Floor structure TJI @ 18"&24"oc with 1-118"sheathing&1.112"Topping
Structure above(Floor): 290'-0"
Grade to Roof highest pt 319'-2"
ACOUSTICAL CEILING Grade to Slab on Grade 275'-0"
Grade to Acoustical Varies from 285'-0"to 286'-4"
NtHFLR' Ceiling
' - Y -
Special Note: See detail 16/A9.30 at Ext. Learning A 107
I-
a
r
a rr CONDITION 2:Sector B Level 1
oo oo Wood Framed Floor Structure TJI @ 18"&24"oc with 1.118"sheathing&1-1I2"Topping
\ ACOUSTICAL CEILING a Structure above(Floor): 290'-0"
o
1- z o Grade to Roof highest pt 3 19'-2"
o - 2h °FAR a Grade to Slab on Grade 275'-0"
a o -- Grade to Acoustical Varies from 283'-0"to 287'-0"
e
0< o
_ Ceiling
0 W Special Note: See detail I6/A9.30 at Ext. Learning B107
ACOUSTICAL CELINC 0 u 0
a CONDITION 3:Sector C Level 1
Wood Framed Floor Structure 518"plywood over 3x T&G Decking w 3"topping slab
F.F. Structure above(Floor): 290'-0"
`---^ — - - Grade to Roof highest pt 319'-2"
Grade to Slab on Grade 278'-0"
FOR THE NTH FLOOR ORAONESTORY BUILDING,GR1DET0 Grade to Acoustical 287'-2"
TOP OF FLOOR DOESN'T EXIST. Ceiling
Special Note:
ADDITIONAL COMMENTS: CONDITION 4:Sector A Level 2
Pop Rivets on Attached Side✓ Wood Framed Roof Structure 18"Red I-Joist 24"oc with 5/8"Roof Sheathing
Seismic Perimeter Clips on unattached side ✓ Structure above(Roof): Varies from 305' to 306'-6"
Perimeter wires may be omitted at Pop Rivet side - Grade to Roof highest pt 319'-2"
Perimeter wires may be omitted at perimeter clips Grade to top of Floor 290'-O"
Please provide Bracing detail for 16/A9.30 _ Grade to Acoustical Varies from 300'-2"to 301'-4"
Ceiling
Special Note: See detail 16/A9.30 at Ext. Learning A207
•
CONDITION 5:Sector B Level 2
• R Wood Framed Roof structure 18"Red IJoist 24"oc with 5/8"Roof Sheathing
Structure above(Roof): Varies from 305' to 306'-6"
Grade to Roof highest pt 319'-2"
ACOUSTICAL CEILING Grade to top of floor 290'-0"
Grade to Acoustical Varies from 298' to 302'
NTHFLR' \ Ceiling
Special Note: See detail I6/A9.30 at Ext. Learning B207
C
CONDITION .Sector C Level 2
p p Wood Framed Roof Structure 14"&18"Red I-Joist 24"oc with 518"Roof Sheathing
rc \ ACOUSTICAL CEILING Structure above(Roof): 307'
o o Grade to Roof highest pt 319'-2"
0 2� FLR _a Grade to top of Floor 290'
o F Grade to Acoustical 300'
o
_a¢ Ceiling
° Special Note:
OO a
1\ACOUSTICAL CEILING o o
CONDITIONS!Sector D Level 1
Wood Framed Roof Structure 18"Red IJoist 16"&24"oc with 518"Roof Sheathing
F.F. Structure above(Roof): 303'
----- -- --- Grade to Roof highest pt 319'-2"
Grade to Slab on Grade 286'
FOR THE NTH FLOOR OR A ONE STORY BUILDING,GRADE TO Grade to Acoustical Varies from 295' to 296'-6"
TOP OF FLOOR DOESNT EXIST. Ceiling
Special Note:
ADDITIONAL COMMENTS:
Pop Rivets on Attached Side
Seismic Perimeter Clips on unattached side
Perimeter wires may be omitted at Pop Rivet side
Perimeter wires may be omitted at perimeter clips
Please provide Bracing detail for 16/A9.30
9/9/2019 U.S.Seismic Design Maps �e(
• SEAS OSHPD
Twality Middle School
14650 SW 97th Ave, Tigard, OR 97224, USA
Latitude, Longitude: 45.4141637, -122.77413309999997
SW Inez St SW Inez St
Twality Middle School Tuality Field
SW Pembrook St
SW Pinebrook St SW Pinebrook St
SW Murdock St James Templeton Mallard Lakes
Go gle Elementary School Map data®zo19
19
Date 9/9/2019,2:02:33 PM
Design Code Reference Document ASCE7-10
Risk Category II
Site Class D-Stiff Soil
tion
Value Description
P
SS 0.983 MCER ground motion.(for 0.2 second period)
St 0.42 MCER ground motion.(for 1.0s period)
SMS 1.074 Site-modified spectral acceleration value
SMt 0.664 Site-modified spectral acceleration value
Sos 0.716 Numeric seismic design value at 0.2 second SA
SD1 0.443 Numeric seismic design value at 1.0 second SA
Type Value Description
SDC D Seismic design category
Fe 1,115 Site amplification factor at 0.2 second
Fv 1.58 Site amplification factor at 1.0 second
PGA 0.422 MCEG peak ground acceleration
FpGA 1.078 Site amplification factor at PGA
PGAM 0.455 Site modified peak ground acceleration
T� 16 Long-period transition period In seconds
SsRT 0.963 Probabilistic risk-targeted ground motion.(0.2 second)
SsUH 1.074 Factored uniform-hazard(2%probability of exceedance in 50 years)spectral acceleration
SsD 1.062 Factored deterministic acceleration value.(0.2 second)
S1RT 0,42 Probabilistic risk-targeted ground motion.(1.0 second)
SI UH 0.483 Factored uniform-hazard(2%probability of exceedance in 50 years)spectral acceleration.
Sb D 0.651 Factored deterministic acceleration value.(1.0 second)
PGAd 0.717 Factored deterministic acceleration value.(Peak Ground Acceleration)
CRS 0.896 Mapped value of the risk coefficient at short periods
https://seismicmaps.org 1/3
9/9/2019 U.S.Seismic Design Maps `c
•
Type Value Description
•
CR1 0.87i Mapped value of the risk coefficient at a period of 1 s
https://seismicrnaps.org
2/3
U.S.Seismic Design Maps
91yl2.01..o �
MCER Response Spectrum
1.5
1.0
m € 1
0.5 . . . •
0.0
5 10 15
Period, T(sec)
-- Sa(g)
Design Response Spectrum
0.8
0.6
0.4 I j
0,2 ! i
0.0
0 5 10 15
Period, T(see)
Sa(g)
DISCLAIMER
While the information presented on this website is believed to be correct,SEAQC ip ,fjp°and its sponsors and contributors assume no responsibility or
liability for its accuracy.The material presented in this web application should not be used or relied upon for any specific application without competent examination
and verification of its accuracy,suitability and applicability by engineers or other licensed professionals.SEAOC/OSHPD do not intend that the use of this
information replace the sound judgment of such competent professionals,having experience and knowledge in the field of practice,nor to substitute for the
standard of care required of such professionals in interpreting and applying the results of the seismic data provided by this website.Users of the information from
this website assume all liability arising from such use.Use of the output of this website does not imply approval by the governing building code bodies responsible
for building code approval and interpretation for the building site described by latitude/longitude location in the search results of this webstie.
https:llseismicmaps.org 3/3
41110 NOTE: ��a
PERIMETER WIRES ARE NOT \ tip .. O.
REQUIRED FOR CEILINGS OF a I9• l
144 SQ. FT. OR LESS
1313=8 a r ,
wwQ2 n m
�=m m 25 GA. X STUD WIDTH X 3° r �' oo �"
c,O0n ccj( C [p LONG METAL TRACK EA. SIDE 4) ' ',23. 1' 4
N a°o° _, WITH (1) #8 SCREW EACH LEG OPEN WEl3 JO
Ste'' �AMEs
• z -HOLD TIGHT TO STRUCTURE
o-. < EXPIRES 12-31-2020
a z< TYPICAL HANGER WIRE
In r WITH 1/4" DIA. X 2" LAC
A m SCREW WITH EYE
to in
...1
/ /
Zcirdi ‘..., + •
1625I25--33 LIGHT GA_ I I I 1 .)
r -1--i , , . , @
l\ STEEL STUD '� -m'
z D o ��1\ l \ t2 GA_ DIAGONAL WIRES
o AT 45 DEG. MAX_ TO PLANE
0 _o
-C ' �/ OF CEILING AND PARAI I Fl
D o K j. I TO COMPONENTS (4 TOTAL
cn of m p WRAP WIRE AROUND I AT �ID DEG. TO EACH OTHER
II
> O u PERT. ELEMENT OF I I IN PLAN)
0 z m JOIST. HAND WRAP II �_ II
WIRE WITH (3) 360°
0 n II REVOLUTIONS MIN.
II II
O = TYP. ALL DIAGONAL II
C 8 WIRES OR USE (1)Y4"4' 45° MAX_ II I I
-1 1— X 3" LAG SCREW W/ h -- - II
n EYE INTO BOTTOM \\4 U 11
cn CHORDJ • •
is R
CROSS TEE \MAIN RUNNER
m (2) 48 SCREWS
-, E W SEISMIC BRACE DETAIL - CONDITIONS 1 $ 2
1I 2
€ w r,z SEISMIC BRACE SPACING: 12'-0" X 12-0" MAX.
0
N
0
IC'
If
S, -GINi
4
mtsif .f. 15, l
40
F ph
� JJAME.5 V4"
' EXPIRES 12-31-2020
....................
. . ............
......................
..................
S NOTE:
PERIMETER WIRES ARE NOT
REQUIRED FOR CEILINGS OF
144 SQ. FT. OR LESS
1
GLU-LAM BEAM
I Q C BY OTHERS
II II
STRUCTURE v
25 GA. X STUD WIDTH X 3" LONG i I 1`�I 1/4" DIA. X 3" LAG SCREW
METAL TRACI< WITH (I) #8 WITH EYE
SCREW EACH LEG -HOLD
TIGHT TO STRUCTURE
TYPICAL HANGER WIRE
1625125-33 LIGHT GA.
STEEL STUD
12 GA. DIAGONAL WIRES
--Ni--- / AT 45 DEG. MAX. TO PLANE OF
'` CEILING AND PARALLEL TO
O.\ ii 10 DEG. TO EACH OTHER
COMPONENTS (4 TOTAL AT
II II IN PLAN). FASTENER TO ATTACH
i TO TOP CHORD
II li
11 II
II II
45° MAX. II it f/f
II ` 11 � /1/
fl u - - \1I
2 #8 SCREWS
( ) MAIN RUNNER
CROSS TEE
SEISMIC BRACE DETAIL- - CONDITION 3
SEISMIC BRACE SPACING: 12'-0" X 12'-0" MAX.
PROJECT: FEB 20, 2020
LEWIS ExVAN VLEET INC.
CONSULTING ENGINEERS TWALITY MIDDLE SCHOOL "18163
18660 sw boones terry road TIGARD, OREGON
tualattn, oregon 97062
(503)50 885.) 8605 208 prone CLIENT: CASCADE ACCOUSTICS D-2
tcEinnta
clo.D PROTei
NOP TERIMETER WIRES ARE NOT A 151.• 9
REQUIRED FOR CEILINGS OF ,�
144 SQ. FT. OR LESS fee w [ y
o°
4 • 23, ti ti*
DAMES v,
(E) PLYWD. SHEATHING EXPIRES 12-31-2020 I
1/4" DIA. X 2" LAG SCREW f ROOF FRAMING
WITH EYE
I I I
1r
1 1\1 STRUCTURE
1
25 GA. X STUD WIDTH X 3" LONG ' I 1\ 1/4" DIA. X 2" LAG SCREW
METAL TRACK WITH (I) #g WITH EYE
SCREW EACH LEG -HOLD
TIGHT TO STRUCTURE
TYPICAL HANGER WIRE
162S125-33 LIGHT GA.
STEEL STUD
12 GA. DIAGONAL WIRES
/ AT 45 DEG. MAX. TO PLANE OF
��''� CEILING AND PARALLEL TO
COMPONENTS (4 TOTAL AT
10 DEG. TO EACH OTHER
II ' ii ►y FLAN). FASTENER TO ATTACH
TO TOP CHORD
f1 II
11 Ii
11
45.AIL II �� 11f�i i1 �i it _J/
\(2) 4:08 SCREWS MAIN RUNNER
CROSS TEE
SEISMIC JRACE DETAIL - CONDITIONS 4, 5, 6, a 1
SEISMIC BRACE SPACING: 12'-O X 12'-0" MAX.
PROJECT: FEB 20, 2020
LEWIS & VAN VLEET [NC. DATE
ENGINEERS TWALITY MIDDLE SCHOOLJ�2$
18660 aw boonea ferry road TIGARD, OREGON
tualatln, oregon 97062
(503) 885.8605 phone D—3
(503)771
885.1206 fax CLIENT: CASCADE ACCOUSTICS ,.,,o
i •
��Q, k) PROre,
�QIN 00#
• 4, 151 -
lite A
.1:, r •• 3, Z �-*
N.
DAMES V
I EXPIRES 12-31-2020
/ / \\ 7 / \ \
/ 7 \\ / /
/ i \• / i
7 / \\ 7 /
/ 7 \\ / /
/ / 7 /
/ / -. 7 /
7 / 7 /
// / OPEN WEB OR
/i (2)- OTHERS BY
\ / i EA.. 5OIST I57
7 /
250SFT125-30EQ0 W/UD#8 , (2)- #10 SCREWS
S.M.S. EA. PAGE, EA. ST , ,
TOP AND BOTTOM
2505P5-30EQD 1
AT 4'-0" O.G. 1
250SPS-30EQD AT 4'-0" O.G. 64
}
7n
(2)- #10 S.M.S. SUSPENDED CEILING
-SEE D-I AND D-2
IllIW
SUSPENDED CEILING
-SEE D-1 AND D-2
7v-
1
ACT TRANSITION SUPPORT AT
EXTENDED LEARNING AREAS
TWAL-174 1/4" = I'-0"
PROJECT: FEB 20, 2020
LEWIS & VAN VLEET INC. °"
CONSULTING ENGINEERS TWALITY MIDDLE SCHOOL
18660 ew hooves ferry road TIGARD, OREGON
tualatin, Oreggon 9706
503 BB5.8605 phone711
D-4
L503) 865.1206 fax CLIENT: CASCADE ACCOUSTICS
•
� W�G IPN A. 47
\� 0 c:r/ 15,09' l
j '',--„„,,,,s,U i frViiiif& .!:/® l \ AMES
EXPIRES 12-31-2020
8" MAX. PERIMETER 8' MAX. PERIMETER
- -HANGER 10 HANGER
I RE WIRE
%' ¢f 2
CTSPC-2 "� "-
SEISMIC CLSP y� i o -`/
WAI5-15 WALL it �� WAI5-15 WALLS TEE
MOLDING ��� ` �. TEE MOL•PING V1 ji �'';„,
i Q V7.
f i
ATTACHED WALL UNATTACHED WALL
Perimeter Wire .yy
±10° from vertical 4li� ` ,, Perimeter Wire Perimeter Wire ��.
'' ±10°from vertical ±10° from vertical"
8" Max,— ��. %.t_..
8" Max. 8" Max.
CTSPC-2 \ •� , 3/4"from grid to
inside of angle
II _ -- - 1iLI=MI ' 1/0
.511.111'..j1
CTSPC-2 -✓
-- 15/16" Angle Screw optional I—15/16" Angle
15/16 Angle II Pop Rivet
CTSPC-2 CTSPC-2 POP RIVET
TIGHT WALL CLEARANCE WALL TIGHT WALL
INSTALLATION INSTALLATION INSTALLATION
(ATTACHED WALL) (UNATTACHED WALL) (ATTACHED WALL)
NOTE:
AT CONTRACTOR'S DISCRETION PERIMETER WIRES MAY BE OMITTED AT ATTACHED AND
UNATTACHED WALL CONNECTIONS WHERE POP RIVETS OR PERIMETER CTSPC-2 ARE USED.
LEWIS & VAN VLEET INC, PROJECT: FEB 20, 2020
CONSULTING ENGINEERS TWALITY MIDDLE SCHOOL
18660 ew boonea ferryrood TIGARD, OREGON
tualotin, oregon 97062
(503) 885.8605z2 phone%71
CLIENT: CASCADE ACCOUSTICS D-5
fax 43
�QE�'''p PRO.
5 �0 t N ''',
1 ii
ir ,:,,. .,, v ,,,.. 0
ev
DAMES,r .As is,y• / -?_---
EXPIRES 12-31-2020
STRUCTURAL NOTES:
1. ACCOUST1CAL AND GYPSUM CEILINGS
a. Main runners to be rated heavy—duty and have a minimum simple span rated uniform
load capacity of 16,35 pounds per lineal foot.
b. Space main runners at 4'-0" on center maximum.
c. Support grid system vertically and laterally from adequate building structure using #12
SWG galvanized wire per attached drawing details (4'-0" on center maximum along
main runners adjacent to cross tee intersections). Provide minimum of three turns of
hanger wire at end loop connections, Install lateral bracing as indicated In drawings
d. Use CTSPC-2 clips by CertainTeed to secure main runners and cross runners to walls
and perimeter trim per drawing details.
e. If cross runners supporting light fixtures are not the same carrying capacity as main
runners, provide supplementary hanger wires within 3 inches of each corner of each
fixture supported by cross tees. Light fixtures weighing not more than 10 pounds shall
have one #12 gauge hanger wire connected from the fixture housing to the structure
above. This wire may be slack and supplementary hanger wires are not required.
Lighting fixtures weighing more than 10 pounds but less than 56 pounds shall have in
addition to the requirements above, two #12 gauge hanger wires connected from the
fixture housing to the structure above. These wires may be slack. Lighting fixtures
weighing 56 pounds or more shall be supported directly from the structure above by
approved hangers. Supplementary hangers are not required. Pendant—hung light fixtures
shall be supported directly from the structure above using #9 gouge wire or an approved
alternate support without using the ceiling suspension system for direct support.
2. Per ASTM E580 Section 1.6, ceilings with areas less than 1000 square feet are exempt
from lateral force bracing requirements, and do not require splay wires or compression struts
when the surrounding walls are braced to the structure.
3. Suspended ceilings with areas less than or equal to 144 sq. ft, that are surrounded by
walls or soffits that are laterally braced to the structure above do not require perimeter wires.
SEISBRACE
PROJECT: FEB 20, 2020
LEWIS & VAN VLEET INC. TWALITY MIDDLE SCHOOL ��
CONSULTING ENGINEERS 19128
18660 sw boonea ferry road TIGARD, OREGON
tualatln, ore on 97062
�50 3 885.8605 2 pone1771
CLIENT: CASCADE ACCOUSTICS D-6
foxSICKT NO