Loading...
Report ELC20<7-4962 7z / moteC T Ae Portland General Electric Company 09/28/19 PGE CONTACT: Liam O'Brien PHONE: 503-734-5838 CUSTOMER NAME: Ironwood Pacific Inc ADDRESS: 7291 SW Tech Center Dr SDPM/ENGR: Luis Mendivil WR: M2787930 PHONE: 503-672-5454 3-PHASE SECONDARY LINE-LINE FAULT CURRENT (RMS) TRANSFORMER DATA PAD MOUNT? YES XFMR Impedance(%): 2.98 % 3-PH SUBMERS YES TRANSFORMER SIZE: 300 KVA XFMR? NO Secondary VOLTAGE (L to L): 480 v WYE OH BANK? NO VAULT--> VAULT ( or Pole --> Pole) SECONDARY Secondary Wire LENGTH: 0 Feet WIRE SIZE Number of SECONDARY RUNS: 1 Run(s)of: Secondary WIRE Resistance R: 0.0180 Ohms/1000' Secondary WIRE Reactance X: 0.0258 Ohms/1000' VAULT ( or Pole) --> PANEL SECONDARY (or Svc Drop) Service Wire LENGTH: 160 Feet WIRE SIZE Number of Service RUNS: 1 Run(s)of: 350 QX UG M Service WIRE Resistance R: 0.0600 Ohms/1000' Service WIRE Reactance X: 0.0330 Ohms/1000' MAXIMUM FAULT CURRENT*: 8,189 Amps *Maximum fault current based upon transformers/conductors sized for 100% of electrical panel rating. Based on a panel size of: 600 Amps To Print This Page: "Ctrl M"and choose"Print 3-Phase Data"