Report ELC20<7-4962
7z / moteC T Ae
Portland General Electric Company
09/28/19 PGE
CONTACT: Liam O'Brien
PHONE: 503-734-5838
CUSTOMER NAME: Ironwood Pacific Inc
ADDRESS: 7291 SW Tech Center Dr
SDPM/ENGR: Luis Mendivil WR: M2787930
PHONE: 503-672-5454
3-PHASE SECONDARY LINE-LINE FAULT CURRENT (RMS)
TRANSFORMER DATA PAD MOUNT? YES
XFMR Impedance(%): 2.98 % 3-PH SUBMERS YES
TRANSFORMER SIZE: 300 KVA XFMR? NO
Secondary VOLTAGE (L to L): 480 v WYE OH BANK? NO
VAULT--> VAULT ( or Pole --> Pole) SECONDARY
Secondary Wire LENGTH: 0 Feet WIRE SIZE
Number of SECONDARY RUNS: 1 Run(s)of:
Secondary WIRE Resistance R: 0.0180 Ohms/1000'
Secondary WIRE Reactance X: 0.0258 Ohms/1000'
VAULT ( or Pole) --> PANEL SECONDARY (or Svc Drop)
Service Wire LENGTH: 160 Feet WIRE SIZE
Number of Service RUNS: 1 Run(s)of: 350 QX UG M
Service WIRE Resistance R: 0.0600 Ohms/1000'
Service WIRE Reactance X: 0.0330 Ohms/1000'
MAXIMUM FAULT CURRENT*: 8,189 Amps
*Maximum fault current based upon transformers/conductors sized for 100% of electrical panel rating.
Based on a panel size of: 600 Amps
To Print This Page: "Ctrl M"and choose"Print 3-Phase Data"