Report me G2015-- 33
13707 sup pie 11wy
5T
Project: -Untitled194 10/16/2018
Prepared By: 02:28PM
cO RECEIVED
5T JAN 14 2019
CITY OF TIGARD
BUILDING DIVISION
Tag Cover Sheet
Unit Report
Certified Drawing
Performance Report
Unit Feature Sheet
Packaged Rooftop Builder 1.49j Page 1 of 9
Unit Report For 5T
Project: —Untitled194 10/16/2018
Prepared By: 02:28PM
Unit Parameters Dimensions(ft. in.)&Weight(lb.)***
Unit Model' 48KCDA06A2A5-0A0A0 Unit Length' 6' 2.375"
Unit Size' 06(5 Tons) Unit Width: ....3' 10.75"
Volts-Phase-Hertz. 208-3-60 Unit Height_.............................__.._.___......._3' 5.375"
Heating Type' Gas *** Total Operating Weight. 607 lb
Duct Cfg• Vertical Supply/Vertical Return
Low Heat *** Weights and Dimensions are approximate. Weight does
Single Stage Compressor Models not include unit packaging. Approximate dimensions are
provided primarily for shipping purposes.For exact
dimensions and weights,refer to appropriate product
data catalog.
Lines and Filters
Return Air Filter Type' Throwaway
Return Air Filter Quantity' 4
Return Air Filter Size' 16 x 16 x 2
Unit Configuration
Medium Static Option Belt Drive
Al/Cu -Al/Cu
Base Electromechanical Controls
Standard Packaging
Warranty Information
1-Year parts(std.)
5-Year compressor parts(std.)
10-Year heat exchanger-Aluminized(std.)
No optional warranties were selected.
NOTE: Please see Warranty Catalog 500-089 for explanation of policies and ordering methods.
Ordering Information
Part Number Description Quantity
48KCDA06A2A5-OAOA0 Rooftop Unit 1
Base Unit
Medium Static Option Belt Drive
None
Packaged Rooftop Builder 1.49j Page 2 of 9
Certified Drawing for 5T
Project: ^'Untitled194 10/16/2018
Prepared By: 02:28PM
NOTES: UNITED PAR BOX PM Txli XKO EWT n TIE FROMM Of CARRIER COREIM ION
0 iECHNOLOOIES inAMI.XI API IS ECIIYnER PCI ISE EXPRESS CCIPITICO ilAI TXf gIgS10i Cglil,000,
ltllE IAATnI[tlRf01WIlKE'q
1. DIMENSIONS ARE IX MINCHESILLIMETERS.
DIMENSIONS UNIT J K 11 PHASE/ K 13 PHASE) CARRIER 11Ex+ CORPORATION,TIOl i wiiIOPEI56mt a USED Minn unlit ARMORS OF ARNnACT.
IN I I ARE IN MILLIMETERS.
33
2.G CENTER OF GRAVITY 48nC 0/ 18 7/8 1 1E311118 14 1311718
33 3/8 14//8 18 5/0 CONNECTION SIZES
3. DIRECTION Of AIR FLOW 48nC OS 18471 f3171 14721 - A 1 3/8' f351 DIA FIELD POWER SUPPLY HOLE
480C IN 411051I I3T71 3/8 14 i/8 18 5/8
[412] B 2' [501 DEA POWER SUPPLY KNOCKOUT
1
C 1 314' (51I DIA GAUGE ACCESS PLUG
D 7/8' 1221 DIA FIELD CONTROL WIRING NOTE
33-3/8
f8481 E 3/4'-1/NPT CONDENSATE DRAIN
f 1/2' IN NPT GAS CONNECTION
• A 6 2 1/2 ' 1641 DIA POKER SUPPLY KNOCK-OUT
32-1/4 + ECONOMIZER HOOD 16
1818] [OPTIONAL/ONALI [1067
FILTER ACCESS PANEL 4 I THAU-THE-BASE CHART
❑OOL-LE557 COMP. F
THESE HOLES REQUIRED FOR USE
ACCESS CONDENSER y ' ,� 1 CROTNPWROOIA01, 003A01
PANEL
THREADED WIRE REO-D HOLE
IN500R COIL '� I CdIDUiT SIZE USE SIZES IYA%.1
I ACCESS PANEL \
6/fa-AA
� 1 [6527B W 1/2' ACC. 7/8' [22.2]
10-118 ♦ % 1/2' 212 718' [22.2]
"" y [217] Y « 3/4' 1001,003/ POWER 1 I/B' 128.41
10 DNB. I. RETURN AIR RETURN
I.IeI]BBBI�I—BBBBBBBBBB�9���WIIH£I 44 110 \ r�'T R �. .. I AIR Z.. 10031 1/2' FPT GAS 1 3/18' [30.01
111111
:��,,
ANDLE 2-5/8 t�p Q FOR 'TNRU-THE-BASEPAN' FACTORY OPTION,
HACK 1671 FITTINGS FOR ONLY R,Y, b 2 ARE PROVIDED
TIP • _ E AL1.J -• I SELECT EITHER 3/4.OR I/O"
CURB W CONDENSATE • 1T-314 EA FOR POWER, DEPENDING ON WIRE SIZE
•% DA AIN OPENING
WIDTH ,Y [1511 10011 PROVIDES 3/P FPi iN RU CURB
1 ' IN BASER!' SUPPLY . 26-f/2 29-318 FLANGE b FITTING.
IB-I/8 Z AIR [673] [717] SUPPLY -
[4591 AIR
16-I/8 14-I14 12-1// -
[/111 13631 13121 it SEE THOU THE- - •-. 6 7— 5
11 I V 4 ., BASE.CHART I1571 . 5
• I f 3-SI8
12-I/B 1651
25 — LUC [30T]
16361 4 HOOD 18-1/2-+
it
11001 TOP En
d-5/8 10-1/2 7-0l4
11181 [2651 132]
LECTRICAL
1
_—_ � DISCONNECT
D
-F 5-I1/N—
COXOEXSER
COIL =— pI• OAON —= CONTROL BOY
ACCESS PANEL
— ® [XDODI BLOWER
ACCESS E STD
CONDENSATE
IL TAEI
R
MO. OPTIONAL I I 2ETUR8 I —_
OUTSIDE
INSALDED , IW 19.712 OPTIONAL XAMDLF 11-318 RAIN
I SU1P631 AIR 1CONVENIEN — I �I 6-5/8N9] AY = F - 12891 I •
I IAR �21-1/4OUTL DISCONNECT -X� — ]
391
6-f/8 —
— �,BBC i—Bll 681 �OO • IU ��
3-3/4 HANDLE 8-3/8 6-518 7
195] 16-3/4 — 30-1/8 E2131 f1691 11771 6
[11811 1764] (1521
71.3/8 26-1/8
73/ 16821 31-1/4 BAROMETRIC
17931 FLOW[F
LEFT SUPPLY 1 FLFLOWFRONT AIR lk RETURN
RIGHT AIR
SAn RAIL SPENCERS
48KC 04-06 SINGLE ZONE ELECTRICAL wN
48K0000281
I OF2 09-16-14 - COOLING WITH GAS HEAT —
Packaged Rooftop Builder 1.49j Page 3 of 9
Certified Drawing for 5T
Project: —Untitled194 10/16/2018
Prepared By: 02:28PM
iftUNITED P 0.IM(IN Ills w SEI1 IS wl IIwa11 a[w11(1 wIT AII2 "MU a'KU“4""a aC11Nln
TECXNOLO6IE$blltw[.II III IS Iftirtlll II NN OSIA[SI w1I11Iw I111 11l w!9 pl a1911IYTF nST IHHOIY110E w
SID. UNIT CORNER CORNER CORNER CORNER C G. HEIGHT CARRIER tun CSITwu nu Nor a DISCLOSED w MI nllm unrzl I[tnWKt a cwn¢r
UNIT WEIGHT WEIGHT RAI WEIGHT TOT WEIGHT ICI WEIGHT IDI wlwnw l wnm coma.
LBS. KG. LBS. KG. LBS, KG. LBS. KG. LBS. HG. R T I
481C 01 /90 222 120 5/ 111 50 125 58 135 11 35 1/4 19081 24 3/4(1281 18 7/9 H111
181C 05 IAA 246 130 58 126 57 112 61 146 66 36 311(9331 21 3/1 11281 18 248(1191
/88C 08 591 270 141 6/ 158 7D 158 71 142 6/ 34 1I8 19931 23 1/2(5971 20 1/8(5111
A STANDARD UNIT WEIGHT [S WITH LON GAS HEAT AND WITHOUT PACKAGING.
FOR OTHER OPTIONS AND ACCESSORIES. REFER TO THE PRODUCT DATA CATALOG.
CORNER A CORNER B
0
.
1n'i Ii' `1�` )NTT .
•
CORNER D CORNER C
TOP
•
•
O O
1100 �I� I �I� l'. 00�
FRONT
3XF11 wrz SIH[KMMS 48KC 04-06 SINGLE ZONE ELECTRICAL
20E2 09-16-14 - COOLING WITH GAS HEAT 48NC000281
Packaged Rooftop Builder 1.49j Page 4 of 9
1
Certified Drawing for 5T
Project: —Untitled194 10/16/2018
Prepared By: 02:28PM
Service Clearance
•
4110
COa337
LOCATION DIMENSION CONDITION
48-In(1219 mm) •unit disconnect is mounted on panel
A Y8-in(d57 mm( •No disconnect,convenhence outlet option
•Recommended serviceclearance
12-In(305 mm) •Minimum clearance
42-in(1067 mm( *Surface behind servicer Is grounded(e.g.,metal,masonry wall)
8 36-in(914mm) •surface behind senicer is electrically non-conductive(e.g..wood,fiberglass)
Special •Check for sources of flue products within 10-ft.of unit fresh air Intake hood
36-In(914 mm) •Side condensate train is used
18-in(457 mm) •Minimum clearance
48-In(1219 mm) •No flue discharge accessorylnstaNed,surfacels combustible material
42-in(1067 min( •Surface behind servicer Is grounded(e.g.,metal,masonry wag,another unit)
D 36-in(914 min) •Surface behind servicer is electricaly non-conductive(e.g.,wood,fiberglass(
Special •Check for adjacent units or building fresh air Intakes within 10-ft.of this unit's
flue outlet
NOTE:Unit not designed to have overhead obstruction.Contact Application Engineering for guidance on any
application planning overhead obstruction or vertical clearances.
Packaged Rooftop Builder 1.49j Page 5 of 9
Performance Summary For 5T
Project: -Untitled194 10/16/2018
Prepared By: 02:28PM
Part Number:48KCDA06A2A5-0A0AO
ARI SEER' 14.10
Base Unit Dimensions
Unit Length. 74.4 in
Unit width:........ 46.8 in
Unit Height' 41.4 in
Operating Weight
Base Unit Weight 597 lb
Medium Static Option Belt Drive. 10 lb
Total Operating Weight' 607 lb
Unit
Unit Voltage-Phase-Hertz. 208-3-60
Air Discharge. Vertical
Fan Drive Type. Belt
Actual Airflow. 2000 CFM
Site Altitude. 0 ft
Cooling Performance
Condenser Entering Air DB• 95.0 F
Evaporator Entering Air DB. 80.0 F
Evaporator Entering Air WB: . . ..... . . ... ................................................................... 67.0 F
Entering Air Enthalpy• 31.44 BTU/Ib
Evaporator Leaving Air DB:.... . .......................... .......................................................58.6 F
Evaporator Leaving Air WB. 57.3 F
Evaporator Leaving Air Enthalpy 24.57 BTU/Ib
Gross Cooling Capacity 61.84 MBH
Gross Sensible Capacity:.................... 46.23 MBH
Compressor Power Input 5.19 kW
Coil Bypass Factor..... ...................................... 0.058
Heating Performance
Heating Airflow. 2000 CFM
Entering Air Temp. 70.0 F
Leaving Air Temp• 97.3 F
GasHeating Input Capacity:---- ............................................. ............_................................................ 72.0 MBH
Gas Heating Output Capacity' 0.0/59.0 MBH
Temperature Rise. 27.3 F
Thermal Efficiency(%)• 82.0
Supply Fan
External Static Pressure' 0.75 in wg
Fan RPM• 1303
Fan Power 1.34 BHP
NOTE. Selected IFM RPM Range: 1035-1466
Electrical Data
VoltageRange: -..........................................................................................................._...187 -253
Compressor#1 RLA• 15.9
Compressor#1 LRA. 110
Outdoor Fan Motor Qty: .............-.............---.................. .... ..................................... 1
Outdoor Fan FLA(ea)• 1.4
Indoor Fan Motor Type- MED
Indoor Fan Motor FLA. 8.4
Combustion Fan Motor FLA(ea)• 0.48
Power Supply MCA. 30
Power Supply MOCP(Fuse or HACR)• 45
Packaged Rooftop Builder 1.49j Page 6 of 9
Performance Summary For 5T
Project: -Untitled194 10/16/2018
Prepared By: 02:28PM
Disconnect Size FLA: 30
Disconnect Size LRA 185
Electrical Convenience Outlet. None
Control Panel SCCR: 5kA RMS at Rated Symmetrical Voltage
Acoustics
Sound Power Levels, db re 10E-12 Watts
Discharge Inlet Outdoor
63 Hz 88.1 87.6 87.5
125 Hz 83.2 80.2 82.5
250 Hz 76.3 67.4 76.1
500 Hz 71.9 64.5 73.6
1000 Hz 68.5 63.8 71.3
2000 Hz 62.9 57.9 67.1
4000 Hz 64.7 53.8 64.1
8000 Hz 60.4 46.6 60.0
A-Weighted 75.3 69.8 77.0
Advanced Acoustics
fri
0 r
91 Iry
911
911 416
Advanced Accoustics Parameters
1. Unit height above ground- 30.0 ft
2. Horizontal distance from unit to receiver 50.0 ft
3. Receiver height above ground 5.7 ft
4. Height of obstruction- 0.0 ft
5. Horizontal distance from obstruction to receiver 0.0 ft
6. Horizontal distance from unit to obstruction- 0.0 ft
Detailed Acoustics Information
Octave Band Center Freq. Hz 63 125 250 500 1k 2k _ 4k 8k Overall
A 87.5 82.5 76.1 73.6 71.3 67.1 64.1 60.0 89.2 Lw
B 61.3 66.4 67.5 70.4 71.3 68.3 65.1 58.9 76.7 LwA
C 55.1 50.1 43.7 41.2 38.9 34.7 31.7 27.6 56.8 Lp
D 28.9 34.0 35.1 38.0 38.9 35.9 32.7 26.5 44.3 LpA
Legend
A Sound Power Levels at Units Acoustic Center, Lw
B A-Weighted Sound Power Levels at Unit's Acoustic Center, LwA
C Sound Pressure Levels at Specific Distance from Unit, Lp
D A-Weighted Sound Pressure Levels at Specific Distance from Unit, LpA
Packaged Rooftop Builder 1.49j Page 7 of 9
Performance Summary For 5T
Project: —Untitled194 10/16/2018
Prepared By: 02:28PM
Calculation methods used in this program are patterned after the ASHRAE Guide; other ASHRAE Publications and the AHRI
Acoustical Standards. While a very significant effort has been made to insure the technical accuracy of this program, it is assumed
that the user is knowledgeable in the art of system sound estimation and is aware of the tolerances involved in real world acoustical
estimation. This program makes certain assumptions as to the dominant sound sources and sound paths which may not always be
appropriate to the real system being estimated. Because of this, no assurances can be offered that this software will always generate
an accurate sound prediction from user supplied input data. If in doubt about the estimation of expected sound levels in a space, an
Acoustical Engineer or a person with sound prediction expertise should be consulted.
FanCurve
20 3]p�q 15CORFIv1 \ 1 ��
Zi„
18
r A
1 1A ; '
16 11CORPM , I `
ch14
N `= �n61-IP=
A
L.:::-12
a1
soar�f�t
0 1D A
N
o_
as
= 1
\ LI1
04 ,900 A , 1.50BHP
— 0.75BHP �1.00&-P ,
02 0.5001 P I \ \ \
COOD
03 C6 fB 12 15 18 21 24 27 31 33
Airflow(CFM-thousands)
RPM=1303 BHP=134 MaximumBHM=2100 MaximumBHP=2.90
Note:Pleasecontastapplicationengineeringforselectionsoutsidetheshadedregion.
SC-SystemCurveRP-RatedPoint
Packaged Rooftop Builder 1.49j Page 8 of 9
Unit Feature Sheet for 5T
Project: -Untitled194 10/16/2018
Prepared By: 02:28PM
rriet
WeatherMaker — 48KC
PACKAGED ROOFTOP GAS HEATING/ELECTRIC COOLING UNITS-14 SEER
3.4.5 TONS
STANDARD FEATURES INCLUDE:
�°"°"`- "•""-• •Puron('R-410A)HFC refrigerant
•Meets and exceeds AS HR•E 90.1 energy efficiency levels
•Some compressor s',rith internal Fine break and overload protection
•Single-stage cooling capacity control
•SEERs up to 14.0,EER's up to 12.0
i 'a • Acutmi*•refrgere•••nt metering system
• Excel sae non-corrosive congooaite condensate panin accordance with
7ti✓ I+ u" •. ASHRAE Standard 52.,sloping design,side oroenterdren
• Standard cooing operation up to 115'F(45'C)and dower to 40'F(4'C)
- down to 25'F(-4'C)with winter start kit
• Pre anted extedorpanels and primer-coated interwar panels tested to
500 hours salt spray protection
•Fuey insulated cabinet
•Excausrve IGC solid-state oontrolfor on-beard diagnostics with LED
error code designaton burne rcontml logic and energy saving indoor
ASII RA E fan motor delay
PT'S •Low Max models that meet California Air Quality Management
uron a Induced draft gas neat combustion design
COMPLIANT •Redonda nt gas valves with up to two stages of heating
• Low pressure and high pressure switch protected,
MAINTENANCE FEATURES:
•Accesspanetswith easy grip handles
•Innovative eery starting,no-stop screws on unit access panels
•Two-inch disposable return airfilters and Tool-less filter aeceasdoor
WEATHERMAKER SERIES • DirectDrWe—ECMndoormotorisstandardwithoptionedbettdrive
systems
WeatherMaker 48KC (14-SEER) units are one-piece gas aTerminal idboard trolb xarrasimple safety circuit troubleshooting and
heating, electric cooling units that are pre-wired and charged simplified control cox arrangement
with Puron(R-410)refrigerant They are factory tested in both • Fntsme lGCsotdstate control for onboard diagnostics with LED
heating and cooling modes,and rated in accordance with AH RI error code designation,bumercontrol logic and energy saving indoor
Standards 210/240. WeatherMaker units are designed in fan motor delay.
accordance with UL Standard 1995, and listed by the INSTALLATION FEATURES:
Underwriters'Laboratories.
•Thru-the-bottom power entry cepatarty
•Single posit gas and electric connections
Approved and certified • Fue perimeter base rea with bust-n rigging adapters and fork slots
by: • Field convertible from vertical to horoontalarfow
craTiF.Eri STANDARD WARRANTY:
• 10-year heat exchanger—15-yearstainless steel option
/1� [� ui•u»win c«aloe • 5yearconrpressar
L/ US euwn+rwa.a.,... . i-yearpe
iii°"•'•" • Many optional upgrades also avaaebie
r w•Fr
mow,ror,srfalZakr, nit•.,
cote..4t.t> OPTIONS INCLUDE BUT ARE NOT LIMITED TO:
...m*wmso-yov. • Prerrnedsk and RTU Open Mutt Protocol DOC Controls
• Supply and Return Air Smoke Detectors.high stab:motors
• Louvered condenser cod guards
• Oisconnectswitch and convenience outlet options
• Starless Steel heat exchangeroption
• Corrosion resistant coil coating.
Certified to ISO 9001 • Rkgh statiemator options
• Patented Hunadi4aZe?adaptive dehurrndification system.This option
also ncodes Motormaster I controls
• Ringed access panels
• Integrated economizer system Standard and Ultra Low Leek versions
For a complete Sat of options and accessories referto the Product Data
Catalog forttns unit.
Packaged Rooftop Builder 1.49j Page 9 of 9