FIRE SPRINKLER
PRODUCT SUBMITTAL
1 1 H 411
FOR:
Tigard Triangle
nd
8vkt._72 __aff1sjiv_Eta)/Ior St.
Tigard, OR 97223
ir:+ c
DATE: 06-01-2020
fim HI ,
SUBMITTED BY:
ro n t ire yste s Inc
7402 SE JOHNSON CREEK BLVD.
PORTLAND, OREGON 97206
PHONE NO. (503)777-5030
FAX NO. (503)777-0659
4077 Airpark Dr.Standish, MI 48658•989-846-4583•www.globesprinkler.com
434 Technical Support•989-414-2600•techservice@globesprinkler.com
SERIES GL-RES
RESIDENTIAL PENDENT AND RECESSED PENDENT
K-FACTOR: 3.0, 4. 1, 4.9, 5.6
GENERAL DESCRIPTION
The series GL-RES pendent sprinklers are decorative fast K k
response glass bulb sprinklers specifically tested and List-
ed for use in residential applications such as homes, apart- it .
ments, hotels, and dormitories to provide control of these `
residential type fires and to improve the chance for occu-
pants to escape. They utilize a 3mm frangible glass bulb as
its heat sensing operating element. The recessed version
of each of these Residential Sprinklers is intended for use
in areas with finished ceilings. It employs a two-piece Re- SERIES GL-RES
cessed Escutcheon. The Recessed Escutcheon provides a GL3010, GL4110, GL4910, GL5610
total adjustment of 1/2 inch (12.7mm)from the flush ceiling
position or±1/4 inch (6.4mm) of recessed adjustment. The TECHNICAL DATA
adjustment provided by the Recessed Escutcheon reduces
the accuracy to which the pipe drops to the sprinklers must Approvals
be cut.
• See TABLE A
This sprinkler may be installed within dwelling occupancies Maximum Working Pressure
as allowed by NFPA 13, 13D, 13R and any other related • 175 psi (12 bar)
documents as appropriate. Temperature Rating
The GL3010 is typically utilized when maximum coverag- ' See TABLE A
K-Factor
es are not needed, thereby reducing flow demands. The • /Z '/z
GL5610 is typically the sprinkler of choice when utilizing • GL3010 K3.0 gpm/psi1/2 (43.2 Ipm/barn)
Residential Sprinklers within an NFPA 13 Occupancy. The GL4110 K4.1 gpmlpsi� (59.0 Ipm/bard)
larger K-factor can be advantageous when needed to con- • GL4910 K4.9 gpm/psi , (70.6 Ipm/barz)
•
form to the NFPA 13 hydraulic Special Design Approach for GL5610 K5.6 gpm/psi (80.6 Ipm/bar )
Residential Sprinklers. Thread Size
• 1/2" NPT(15 mm)
Length
• 2-1/2" (6.3 cm)
Materials of Construction
OPERAT/ON • Frame- bronze • Deflector-brass•Screw-brass
Upon exposure to heat such as from a fire, the fluid in the • Lodgement Wire (GL5610 only)-stainless steel • Bulb
bulb expands, compressing the air bubble within the bulb. seat-copper
When the air bubble can no longer compress, the fluid ex- ' Spring- nickel alloy• Seal -teflon
pansion causes breakage of the glass bulb, resulting in re- • Bulb glass with alcohol based solution, 3mm
lease of the water seat assembly, and discharge of water ' Escutcheon Assembly-carbon steel
from the sprinkler. FINISHES AND ACCESSORIES
Finishes
• Factory Bronze •Chrome•White Polyester
NOTE: • Black Polyester-special order
Users should refer to Globe's web site (www.globesprinkler.com) Escutcheons
to assure that the most recent technical literature is being utilized. Brass• Chrome•White Polyester•Black Polyester
Wrenches
• Standard• Recess•1/2"NPT
APRIL 2019 REV.A GFS-302 PAGE 1 of 4
DESIGN CRITERIA
The Globe Residential Pendent Sprinkler Series GL-RES is Hydraulic Design (NFPA 13)
cULus Listed for installation in accordance with this data The minimum required discharge from each design area
sheet as well as the applicable installation Standard being sprinkler shall be the greater of the following:
utilized. (1) In accordance with minimum flow rates indicated in
Globe Residential Sprinkler Installation Guide TABLE A.
(2) In rooms or compartments greater than 800 ft2
When conditions exist that are outside the scope of the pro- (74.3 m2), calculated based on delivering a minimum
vided criteria, refer to the Globe Residential Sprinkler Instal- of 0.1 gpm/ft2 (4.1 mm/min)over the coverage area of
lation Guide (Document GFS-380) for recommendations each sprinkler, calculated in accordance with the
that may be acceptable to the authority having jurisdiction. S x L Rules for density area sprinklers.
Hydraulic Design (NFPA 13D and 13R) (3) In roams or compartments 800 ft2(74.3 m2)or less
(Defined as"Small Rooms")calculated based on de-
For systems designed to NFPA 13D or NFPA 13R, the min- livering a minimum of 0.1 gpm/ft2(4.1 mm/min)over
imum required sprinkler flow rate is given in Table A for the the room or compartment using the area of the room
coverage areas shown. The sprinkler flow rate is the min- divided by the number of sprinklers in the room. (7psi
imum required discharge from each of the total number of minimum)
"design sprinklers"as specified in NFPA 13D or NFPA 13R.
TABLE A: NFPA 13, 13R, AND 13D
HYDRAULIC AND INSTALLATION DESIGN CRITERIA
DEFLECTOR TO MINIMUM
K TEMPERATURE MAX.AREA OF MINIMUM MINIMUM CEILING/ DISTANCE
SIN FACTOR COVERAGE PRESSURE FLOW MOUNTING BETWEEN
ca ,Ps.; FEET(mi PS1(bar) GPM(vmim) SURFACE SPRINKLERS
(?mr�o)r'') DISTANCE
155"F 175T 200'F INCFEET(rn/
(68"C) (79°C) (93°C) hEs(rnm)
cULus cULus cULus 12(3.6)x 12(3.6) 7.1 (.49) 8.0(30.3)
3.0 Elio)
GL3010
(43.2) cULus
EUI'I cULus cULus 14(4.3)x 14(4.3) 11.1 (.765) 10.0(37.8)
cULus cULus
Elio) EUI'I NA 12(3.6)x 12(3.6) 7.2(.5) 11.0(42)
Smooth Ceilings
4.1 cULus Recessed
GL4110 (59) EUUS NA NA 14(4.3)x 14(4.3) 8.6(.59) 12.0(45) 1-1/8(29)
to 1-5/8(41)
cULus
Elio) cULus NA 16(4.9)x 16(4.9) 11.7(.81) 14.0(53)
Smooth Ceilings
cULus cULus Exposed
EUI'I EUI'I NA 12(3.6)x 12(3.6) 7.0(.48) 13.0(49) Max.4(101.6)
cULus EU('S EUm'S NA 14(4.3)x 14(4.3) 8.2(.57) 14.0(53) Beamed Ceilings
Adjacent 8(2.4)
4.9 cULus cULus per NFPA 13, 13D,
GL4910 (70.6) aimEUI'I NA 16(4.9)x 16(4.9) 8.2(.57) 14.0(53) or 13R
as appropriate
cULus cULus
EUI'I EU`'I NA 18(5.5)x 18(5.5) 12.0(.83) 17.0(64) Beamed Ceilings
cULus cULus In Beam
aim Elio) NA 20(6.1)x 20(6.1) 16.7(1.15) 20.0(76) 14"Max.Beam Depth
1-1/8(29)
cULus NA NA 12(3.6)x 12(3.6) 7.2(.5) 15.0(57) to 1-5/8(41)
5.6 cULus NA NA 16(4.9)x 16(4.9) 11.5(.79) 19.0(72)
GL5610
(80.6) cULus NA NA 18(5.5)x 18(5.5) 14.1 (.97) 21.0(79)
cULus NA NA 20(6.1)x 20(6.1) 18.4(1.27) 24.0(91)
NOTE: Deflector-to-Ceiling Distance Criteria reflects 2019 Edition of NFPA 13D and 13R.
O'LISTED BY UNDERWRITERS LABORATORIES,INC.FOR USE IN THE U.S.,CANADA, AND EUROPEAN UNION.
APRIL 2019 REV.A GFS-302 PAGE 2 of 4
•
INSTALLATION
NOTICE
Do not install any bulb-type sprinkler if the bulb is cracked or
there is loss of liquid from the bulb. Sprinklers should be tightened t•
,'
enough to obtain a leak-tight joint when water pressure is applied
and/or hydrostatic test is performed. Sprinklers should not be ny -
overtightened as this can result in distortion and subsequent leak-
age.
It is recommended not to exceed 14 ft.-lb. (19.0 Nm) torque FIGURE 1: STANDARD WRENCH
for 1/2 inch NPT sprinkler threads.
P/N 325390
Step1. Sprinklers must be properly oriented.
Step2. With pipe thread sealant applied to the pipe
threads, hand tighten the sprinkler into the sprin-
kler fitting. Note:Do not grasp the sprinkler by s =
the deflector. " '
Step3. Wrench-tighten the sprinkler using only the ,
appropriate wrench.Wrenches are only to be
applied to theisprinkler wrench flats or wrench
hex as applicable. Note: Do not apply wrench to FIGURE 2: RECESSED WRENCH
frame arms. P/N 325391
CARE AND MAINTENANCE
Prior to installation, it is important to read and follow the
"Sprinkler Caution" sheet (GFS-840) included within each
box of sprinklers. This sheet is available on Globe's web
site (www.globesprinkler.com).
Always obtain permission from the proper authorities to 215116°oA
shut down the affected fire protection system and notify all
personnel who may be affected by this action before closing HOLE MIN CEILING
a fire protection system main control valve for maintenance - 29132•DIA.
work on the system that it controls.
Sprinklers should only be cleaned by means of gently dust-
ing with a feather duster; otherwise, non-operation in the
event of a fire or inadvertent operation may result. 1.x,a"REDUCER
`
Store sprinklers in a cool, dry place. Exposure to extremeIY ACE OFFTG.
heat will damage the thermal sensing element, possibly re- ,� = 1 d� ` RMIN.
suiting in premature activation.Avoid direct sunlight -411 � . ,1�j �° ,n
Replace any sprinkler that shows any corrosion, damage, CNR I I L8. CEILING
or loss of liquid from the glass bulb. IV MIN(REF
RETAINER ,5/8'MAX.(REF.)
Do not attempt to paint or alter the sprinkler's coating in any
manner after leaving the manufacturing plant. -----
• (INNER RETAINER FLUSH WITH CEILING)
Do not attach wiring, ropes, decorations or fixtures to a
sprinkler. FIGURE 3: 1/2"ADJUSTMENT RECESSED PENDENT
Absence of an escutcheon, used to cover a ceiling hole,
may delay sprinkler operation in a fire situation.
It is the owner's responsibility for inspection, testing and
maintenance of the fire sprinkler system with all components
and devices in accordance with the National Fire Protection
Association Pamphlet 25 as well as any other requirements
as set forth by the local Authority Having Jurisdiction (AHJ).
4077 Airpark Dr.Standish, MI 48658•989-846-4583•www.globesprinkler.com
Technical Support•989-414-2600•techservice@globesprinkler.com
APRIL 2019 REV.A GFS-302 PAGE 3 of 4
ORDERING INFORMATION
TABLE B: PART NUMBER SELECTION
PART NUMBER
SIN + TEMPERATURE + FINISH
XXXX XXX XX
SIN TEMPERATURE FINISH
GL3010 i 3010 i 155 155°F(68°C) 01 BRONZE
GL4110 4110 175 175°F(79°C) 02 CHROME
GL4910 4910 200 200°F(93°C) 03 WHITE POLYESTER
GL5610 5610 04 BLACK POLYESTER
Note:All combinations may not be available.
Refer to TABLE A for available listed combinations
TABLE C: ESCUTCHEONS
1/2"(13mm)ADJUSTABLE RECESSED ESCUTCHEON
FINISH FRICTION FIT 1/2"NPT THREADED 1/2"NPT
Chrome 332071 329301
White Polyester 332073-W 329303-W
•
Brass 332072 NA
Black Polyester 332073-0 NA
SPECIFY:
• SPRINKLER
•Quantity•SIN•Temperature Rating•Finish
•Part Number(See TABLE B)
• ESCUTCHEON
•Quantity•Finish• Part Number (See TABLE C) GLOBE® PRODUCT WARRANTY
• WRENCH
•Quantity•Part Number Globe agrees to repair or replace any of its manufactured
1/2"NPT Standard 325390 products found to be defective in material or workmanship
1/2"NPT Recess 325391 for a period of one year from date of shipment.
• PROTECTIVE CAPS
•Quantity•Part Number For specific details of our warranty please refer to Price List
Cap 327109-Cap Terms and Conditions of Sale (Our Price List).
APRIL 2019 REV.A GFS-302 PAGE 4 of 4
AUTOMATIC SPRINKLERS
GL SERIES
UPRIGHT 0 PENDENT
VERTICAL SIDEWALL
HORIZONTAL SIDEWALL
CONVENTIONAL (OLD STYLE)
DESCRIPTION AND OPERATION
The Globe Quick Response GL Series Sprinklers are a low
profile yet durable design which utilizes a 3mm frangible glass
ampule as the thermosensitive element. This provides sprinkler
operation approximately six times faster than ordinary sprinklers.
While the Quick Response Sprinkler provides an aesthetically " '
pleasing appearance, it can be installed wherever standard spray
sprinklers are specified when allowed by the applicable standards.
It offers the additional feature of greatly increased safety to life and 11
s
is available in various styles, orifices, temperature ratings and
finishes to meet many varying design requirements. Quick QUICK RESPONSE
Response Sprinklers should be used advisedly and under the UPRIGHT CONVENTIONAL
direction of approving authorities having jurisdiction.
The heart of Globe's GL Series sprinkler proven actuating
assembly is a hermetically sealed frangible glass ampule that a
contains a precisely measured amount of fluid. When heat is
absorbed, the liquid within the bulb expands increasing the internal '
pressure. At the prescribed temperature the internal pressure
within the ampule exceeds the strength of the glass causing the
glass to shatter. This results in water discharge which is distributed 2
in an approved pattern depending upon the deflector style used. QUICK RESPONSE
TECHNICAL DATA PENDENT VERTICAL
•See reverse side for Approvals and Specifications. SIDEWALL
*Temperature Ratings - 135°F (57°C), 155°F (68°C),
175°F (79°C), 200°F (93°C), 286°F (141°C)
*Water Working Pressure Rating - 175 psi (12 Bars) ,
•Factory tested hydrostatically to 500 psi (34 Bars)
•Maximum low temperature glass bulb rating is -67°F (-55°C) QUICK RESPONSE
•Frame - bronze • Deflector- brass • Screw- brass HORIZONTAL LPC/CE
•Lodgement Wire - stainless steel • SIDEWALL HORIZONTAL
•Bulb seat - copper • Spring - nickel alloy • Seal - teflon SIDEWALL
•Bulb - glass with alcohol based solution, 3mm size
®SPRINKLER TEMPERATURE RATING/CLASSIFICATION and COLOR CODING
CLASSIFICATION AVAILABLE SPRINKLER BULB COLOR N.F.P.A. MAXIMUM
TEMPERATURES CEILING TEMPERATURE
ORDINARY 15E A: m ORANGE/RED S4e
INIt moil EGIHft , p ?,,,i; wlvv.,?. . rcLLuvV1urcccIVViito.4,7:n: m. ..
T IIOI I A. `DOT ,',1 a BLUE l-K L.3T ® ; '"';
4077 AIRPARK DRIVE,STANDISH,MICHIGAN 48658 989-846-4583 o FAX 989-846-9231
JULY 2012 A-20 BULLETIN GL5615, REV.#9
iLIICK1ESPONSE
AUTOMATIC SPRINKLERS
GL SERIES
UPRIGHT PENDENT S VERTICAL SIDEWALL
HORIZONTAL SIDEWALL a CONVENTIONAL (OLD STYLE)
SPECIFICATIONS
NOMINAL "K" FACTOR THREAD SIZE LENGTH' FINISHES
2.0 (30 . ,�LIL,) ./2" ur T 2 1,4" (5.7,....)
4.2 (33 „,..LL.) 1/2" rim- Y I/!" (5.7.,,,,) Factory Bronze
Chrome
5.6 (80 metric) 1/2" NPT 2 1/4" (5.7cm)
White Polyester 3
TM Olt ,,,..L:�) 1/2" Nr T 2 1/1" (L.7.....) Black Polyester 2.3
I.1 (11C ®e:e) 3n" NrT Q 7110" (0.2..,,,)
METRIC CONVERSIONS ARE APPROXIMATE.
'HORIZONTAL SIDEWALL IS 2 9/16".
I FINISHES AVAILABLE ON SPECIAL ORDER.
'AVAILABLE AS cULus LISTED CORROSION RESISTANT WHEN SPECIFIED ON ORDER.
APPROVALS
STYLE SIN K HAZARD' 135°F 155°F 175°F 200°F 286°F cULus FM LPC CE NYC-DOB
MODEL FACTOR 57°C 68°C 79°C 93°C 141°C MEA 101-92-E
GL2815 2.8 LH X X X X X X — — — X
GL4215 4.2 LH X X X X X X — — — X
UPRIGHT GL5615 5.6 LH/OH X X X X X X X X X X
GL8115 7.8" LH/OH X X X X X X — — — X
GL8118 8,1 LH/OH X X X X X X X X X X
GL2801 2.8 LH X X X X X X — — — X
GL4201 4.2 LH X X X X X X — — — X
PENDENT GL5601 5.6 LH/OH X X X X X X X X X X
GL8101 7.8* LH/OH X X X X X X X — — X
GL8106 8.1 LH/OH X X X X X X X X X X
VERTICAL GL5632 5.6 LH X X X X X X X — — —
SIDEWALLt GL8133 8.1 LH X X X X X X — — — -
-
GL2826§ 2.8 LH X X X X X X — — — X
HORIZONTAL GL4226§ 4.2 LH X X X X X X — — — X
SIDEWALL GL5626§ 5.6 LH/OH X X X X X X X — — X
GL5627o 5.6 LH/OH X X X X X — — X X —
GL8127§ 8.1 LH/OH X X X X X X , — — — —
CONVENTIONAL GL5624 5.6 LH/OH X X X X X — — X X —
(OLD STYLE) GL8125 8.1 LH/OH X X X X X — — X X —
1SPRINKLERS SHALL BE LIMITED AS PER THE REQUIREMENTS OF NFPA13 AND ANY OTHER RELATED DOCUMENTS.
§HORIZONTAL SIDEWALL cULus LISTED FOR DEFLECTOR 4"TO 12"BELOW THE CEILING,FM APPROVED 4"TO 6"BELOW THE CEILING.
rlINSTALL IN ACCORDANCE TO BS5306 AND ANY OTHER RELATED DOCUMENTS.
1PENDENT VERTICAL SIDEWALL cULus LISTED FOR 6'MIN.SPACING.
tUPRIGHT VERTICAL SIDEWALL cULus LISTED FOR 9'MIN.SPACING.
OH: ORDINARY HAZARD
LH: LIGHT HAZARD
"1/2"NPT
ORDERING INFORMATION GLOBE®PRODUCT WARRANTY
SPECIFY
•Quantity • Model Number • Style Globe agrees to repair or replace any of its own manufactured
"Orifice • Thread Sizes • Temperature products found to be defective in material or workmanship for a
•Finishes desired period of one year from date of shipment.
•Quantity-Wrenches - P/N 325390 (1/2"); For specific details of our warranty please refer to Price List
PIN 312366 (L.O.) Terms and Conditions of Sale (Our Price List).
- -� 4077 AIRPARK DRIVE, STANDISH, MICHIGAN 48658
989-846-4583 FAX 989-846-9231
FIRE ## 1 LE C RPO AT6t9 1-800-248-0278 www.globesprinkler.com
JUNE2012 PRINTED U.S.A. BULLETIN GL5615,REV.#9
CkiF
� ��t� r 4077 Airpark Dr.Standish, MI 48658 •989-846-4583•www.globesprinkler.com
ARE SPRINKLER CORPORATION Technical Support•989-414-2600•techservice@globesprinklercom
SPECIFIC APPLICATION MODEL "IC" INTERSTITIAL
COMBUSTIBLE CONCEALED SPACE UPRIGHT
SPRINKLER GL5608
GENERAL DESCRIPTION
The Globe Model "IC" GL5608 Interstitial Combustible
Space Sprinkler is a quick response, upright, specific appli-
cation sprinkler designed to provide protection of light haz-
ard combustible and non-combustible concealed spaces.
Each GL5608 sprinkler can be designed for up to 16ft x
16ft (4.9m x 4.9m) spacing, providing as much as 256 ft2
(23.8m2)of protection per sprinkler.
The GL5608 sprinkler meets the requirements of Under-
writers Laboratories UL 199H to comply with criteria for the
protection of combustible concealed spaces as described in
NFPA 13.
•
When heat is absorbed, liquid within the glass bulb ex-
pands, increasing the internal pressure. At the prescribed
temperature the internal pressure within the ampule ex-
ceeds the strength of the glass causing the glass to shatter.
This results in water discharge which is distributed in an ap- MODEL "IC" UPRIGHT GL5608
proved pattern.
APPLICATION
The Model "IC" GL5608 can be designed for installation GLOBE MODEL "IC" UPRIGHT
in CPVC wet pipe sprinkler systems and steel wet pipe or SPRINKLER:
dry pipe sprinkler systems. The Model "IC" GL5608 can be
used in concepled spaces having roof pitch of 2 in 12 or The Globe Model "IC" GL5608 Interstitial Combustible Up-
less constructed of wood truss, non-combustible bar joist, right Sprinkler has been Listed to be used beyond the 36"
solid wood joists, or composite wood joists. The specific de- (914.4mm) height to a height of 60" (1.5m)to provide more
sign requirements for each type of piping system, and con- functionality in installation specifically in areas where the
struction materials can be found in the following sections of height of the concealed space is both above and below the
this document. height of 36" (914.4mm).
NFPA 13 REQUIREMENTS TECHNICAL DATA
Sprinklers shall be Listed for use in combustible concealed • cULus Listed for coverage areas up to 256 ft2(23.8 m2)
spaces (with a slope not exceeding 2 in 12) with combus- • 16 ft(4.9 m)maximum and 6 ft(1.8 m) minimum
tible wood truss, wood joist construction, or bar joist con- Sprinkler Spacing
struction having a combustible upper surface and where the Maximum Open Space Height 60 in (1.5 m)
depth of the space is less than 36" (914.4mm) from deck • Temperature Ratings- 175°F '79°C' 200°F (93°C)
to deck or with double wood joist and composite wood joist
construction with a maximum of 36"(914.4mm) between the • Finish - Factory Bronze
top of the bottom joist and the bottom of the upper joist. • Water Working Pressure Rating - 175 psi (12 Bars)
HYDRAULIC DESIGN AREA • (Maximum low temperature glass bulb rating-67°F
55 C)
For all pipe and construction types the design area shall be • Materials of Construction, Frame- bronze, Deflector-
1000 ft2(92.9m2)except for Steel Pipe Systems with insula- brass, Screw- brass, Bulb seat-copper, Spring-nickel
tion filled joists, the design area shall be in accordance with alloy, Seal -teflon, Bulb-glass with alcohol based
the Light Hazard Systems requirements of NFPA 13. solution, 3mm size
SPRINKLER COVERAGE
AREA
The coverage area of any single Model IC Sprinkler shall
utilize the SxL rule for all sprinkler spacings (i.e. 16 x 10 =
160 sq.ft. X 0.10= 16 gpm).
APRIL 2016 Page 1 of 6 GFS-600 (Formerly A-40)
TABLE A GENERAL INSTALLATION ALLOWANCES
STEEL PIPING CPVC PIPING
OPEN SPACE HEIGHT TOTAL OPEN SPACE HEIGHT TOTAL COVERAGE DISTANCE
CONSTRUCTION TYPE ALLOWED ALLOWED AREA BETWEEN
SPACE SPACE Fee' SPRINKLERS
MINIMUM MAXIMUM '.HEIGHT' MINIMUM MAXIMUM HEIGHT' (Meters') Feet(Meters)
Inches(mm) Inches(mm) Inches(mm) Inches(min)
Inches(mm) Inches(mm)
Unobstructed Wood Truss
6(152) 60(1524) 60(1524) 6(152) 60(1524) 60(1524)
Non-Combustible Bar Joist MINIMUM6( .8)
Obstructed Wood Truss 256(78.0)
6(152) 60(1524) 84(2134) N/A N/A N/A MAXIMUM 16(4.9)
Solid Wood Joist MAXIMUM
Insulation Filled Joist 6(152) 60(1524) 72(1829)' 6(152) 60(1524) 72(1829)"
NOTE:METRIC CONVERSIONS ARE APPROXIMATE.
WHEN TRUSS OR JOIST SPACE IS NONINSULATION FILLED, THE MAXIMUM ALLOWED TOP MEMBER DEPTH IS 12`(305 mm).
2 UP TO 12"(305mm)LOWER MEMBER SPACE.
TABLE B SPRINKLER SPECIFICATION AND APPROVALS
TEMPERATURE
RATING
NOMINAL MAX.LOW
STYLE SIN "K" HAZARD' THREAD` SPRINKLER FINISH PRESSURE TEMP BULB cULus
MODEL FACTOR SIZE LENGTH 175°F 200°F RATING RATING
(79°C) (93°C)
UPRIGHT GL5608 5.6 LH 1/2"NPT 2 1/4" Factory X x 175 psi -67°F x
(80 metric) (15mm) (5.7cm) Bronze (12 Bars) (-55°C)
NOTE.
METRIC CONVERSIONS ARE APPROXIMATE.
2 SPRINKLERS SHALL BE LIMITED AS PER THE REQUIREMENTS OF NFPA13 AND ANY OTHER RELATED DOCUMENTS.
OBSTRUCTION CRITERIA
For systems where the Globe "IC" Upright Sprinklers are the Globe "IC" Upright Sprinkler must use the obstruction
positioned with 15' (4.6m) or less between sprinklers the requirements for extended coverage upright sprinklers.
Globe "IC" Upright Sprinkler must use the obstruction re-
quirements for standard spray upright sprinklers. NOTE:
For systems where the Globe "IC" Upright Sprinklers are ' WEB MEMBERS AND GUSSETS SHALL NOT BE CONSIDERED OB-
STRUCTIONS PROVIDED THE MINIMUM 4-1/2 INCH LATERAL DISTANCE
positioned with greater than 15' (4.6m) between sprinklers REQUIRED BY THE SPECIFIC APPLICATION LISTING IS MAINTAINED.
CPVC DESIGN REQUIREMENTS
SYSTEM TYPE PARTITION REQUIREMENTS
The concealed space being protected must be broken up
Wet pipe system. into areas no greater than 1000 square feet either by full
height walls or by draft curtains.
ALLOWABLE CONSTRUCTION DRAFT CURTAINS
TYPES When draft curtains are used they must be 8" (203.2mm)
• Unobstructed wood truss construction in height or one third of the depth of the concealed
• Unobstructed bar joist construction' space, whichever is greater. Draft curtains must be
o Non-combustible insulation filled solid wood joist constructed of a material that will not allow for heat to
construction' escape through or above them.
• Non-combustible insulation filled composite wood joist
construction2
NOTE:
UpperjoisUhuss cannot be more than 4"(101.6mm)in height.
The joist space in non-combustible insulation filled joist construction must be
completely filled with noncombustible insulation and secured in place by metal
wire netting to hold the insulation in place in the event of a fire.
APRIL 2016 Page 2 of 6 GFS-600 (Formerly A-40)
DEFLECTOR POSITION CPVC PIPE INSTALLATION
• 1 '/to 4 inches below the upper deck for wood truss and Horizontal runs of CPVC piping must be located with the I
bar joist constructions. bottom of the piping not more than 6" (152.4mm) above the
• 1 1/2 to 4 inches below the joists for non-combustible ceiling below or above ceiling insulation (if present), or one
insulation filled solid and composite wood joist third depth of the combustible concealed space as mea-
constructions. sured between the top surface of the ceiling below to the
• 4 '/inches away from trusses. bottom of the floor above or the bottom of the noncombus-
tible insulation above. Whichever is smaller.
CONCEALED SPACE SIZE When the lower joists are greater than 6"(152.4mm) in
All spaces must have a minimum open space (from top of height, CPVC piping is permitted to be attached directly to
lower joist, cord, or truss to bottom of upper joist, cord, or the topof theIjoist. ThetCPVC piping can be used to supply
truss)of 6" (152.4mm). (see Figures 1 and 2) the Globe he Upright Sprinklers as well as the sprinklers
protecting the space below.
Unobstructed wood truss and bar joist construction must not When using 1" (DN25) or larger pipe, a hanger must be
have a total bottom of floor to top of ceiling space height of located at the truss nearest a sprig for purposes of re-
more than 60" (1.5m). (see Figure 2) straint. If using 3/," (DN19) piping, all sprigs over 12"
Joist construction with noncombustible insulation in the (304.8mm) must be laterally braced using methods
upper deck must not have an open space (from top of lower described in the NFPA standards. Where CPVC piping must
joist to bottom of upper joist) of greater than 60 inches in be offset to go over an obstruction that will violate the hori-
size. They must not have a total concealed space height of zontal positioning requirements the CPVC piping must be
greater than 72" (1.8m). This allows for a maximum lower spaced not greater than 6 inches from that obstruction and
joist space of 12" (304.8mm). an additional Globe IC Upright Sprinkler must be provided
Solid wood joist and obstructed truss construction must to protect the section of CPVC piping (see Figure 1 and 2).
not have an open space (from top of lower joist or truss to CPVC piping must be kept a minimum of 18"(457.2mm)lat-
bottom of upper joist or truss) of greater than 60"(1.5m) in erally away from heat sources such as heat pumps,fan mo-
size. They must not have a total concealed space height of tors, and heat lamps.
greater than 84"(2.1m). The upper joist space must not be
greater than 12"(304.8mm) in depth (see Figure 2)
I@"(114mm)MIN.
1 1n'(30mm)MIN. TO FACE OF WOOD TRUSS 6'(152mm)MAX.
P(1)38m)MIN.7 OR TOP CHORD OF BAR JOIST FOR CPVC PIPE UPPER DECK
%/////II///////////I///WAWA////////////////'I.%///////
TOP CHORD ,
4'(100mm)MAX.
FRAME ARMS MUST BE \ ill
b
.. INSTALLED IN-LINE ..
" WITH PIPE RUN • .'(125mm)MAX.
a (MODEL IC SPRINKLER) -rMMI=ate FOR CPVC PIPE
12'(305m30 MIN. P ! ! 1.1. . I,' 6'1152mm)MIN.
00'(1524mm)MAX. I"I"t"I'•'I"I' '�f OBSTRUCTION
I-IIII�-Illi._-Ill. ;1 I.
1 1 �-
CEILING\-BOTTOMP OF OF PIPE/
D
WHEN OFFSETTING CPVC PIPE OVER AN
'(152mm)MAX.ABOVE CEILING TO BOTTOM OF PIPE OBSTRUCTION A GL5608 MODEL'IC-SPRINKLER
OR NON COMBUSTIBLE CEILING INSULATION.OR 1/3 OVER BE INSTALLED DIRECTLY ON THE CPVC
OBSTRUCTION.
C
THE DEPTH OF CONCEALED SPACE(AS MEASURED OVER THE OBSTRUCTION.
FROM TOP SURFACE OF CEILING TO BOTTOM SURFACE
OF DECK),OR WHICH EVER IS SMALLER.
FIGURE 1 : CPVC PIPE UNOBSTRUCTED WOOD TRUSS AND BAR
JOIST CONSTRUCTION
APRIL 2016 Page 3 of 6 GFS-600 (Formerly A-40)
INSULATION MUST BE HELD NONCOMBUSTIBLE
SOLID WOOD JOIST IN PLACE WITH METAL. INSULATION • POSITE WOOD JOIST
12'(305mm)MAX.DEPTH WIRE NETTING 12'(305mm)MAX.DEPTH
r�rt4irl\ r at!Tri\\U\�\a\� rr \'\\I" UPPER DECK
ulY�'uu /�uuuluu/Ou 13uuuulC,Lu.
,,1W111I11QIN1tItItIVAWNI1,ttt111T11tItYNltltlltltl l�ltltltlt�ltltltrtltl,��,•Itlt
1'(I(38mm)MIN. 1t1��1/1tltltl/It//1t/t1/11� /////t/t1/lt/t/t///t�i111t/t{//tIt//11/t1///Y/t/tltlt/t/t/t1/7t/t/tltll�l/it/11
4'0°2mm)MAX.1.H� ✓//It/1tHIryr,P Itrmm ,••IIIII,,,, •1,1
1 .
L5fi0: •"(152mm)MAX.
T (MODEL IC SPRINKLER) FOR CPVC
FRAME ARMS MUST '(152mm)MAX.
BE INSTALLED _1k FOR CPVC
IN-LINE WITH PIPE RUN
U
6'(152mm)MIN. ••�•••t••�•••I•'f ' OBSTRUCTION 72'
60'(1524mm)MAX. (1829mm)
..1..1..1..1..1.. ' MAX.
.1..1..1..1..1.. FILING
BOTTOM OF PIPE-• 5 TOP F CHORD w��wvvvvvvvvvvvvvvwvvvvvvvvvvvvvvvvvvvv�smvvvvvvcavvvvvvvvvvvvvvvvc�
WHEN OFFSETTING CPVC PIPE OVER AN
OBSTRUCTION A GL560B MODEL'IC'SPRINKLER
MUST BE INSTALLED DIRECTLY ON THE PIPE
OVER THE OBSTRUCTION.
6'(152mm)MAX.ABOVE CEILING OR NON-COMBUSTIBLE CEILING INSULATION.OR 10 THE DEPTH OF CONCEALS
AREA(AS MEASURED FROM TOP SURFACE OF CEILING TO TOP SURFACE OF JOIST INSULATION ABOVE),OR WHICH
EVER IS SMALLER.WHEN THE LOWER JOIST IS GREATER THAN 6'(152mm)IN HEIGHT CPVC PIPING IS PERMITTED
TO BE ATTACHED DIRECTLY TO THE TOP OF THE JOIST.
FIGURE 2: CPVC PIPE NON-COMBUSTIBLE INSULATION FILLED
UPPER DECK SOLID WOOD OR COMPOSITE WOOD JOIST
CONSTRUCTION
STEEL PIPING DESIGN REQUIREMENTS
SYSTEM TYPE DRAFT CURTAINS
Wet pipe system and dry type systems. Unobstructed wood truss construction and noncombustible
bar joist construction must be 8" (203.2mm) in height or
ALLOWABLE CONSTRUCTION one third of the depth of the concealed space, whichever
is greater. Draft curtains must be constructed of a material
TYPES that will not allow for heat to escape through or above them.
• Unobstructed wood truss construction' Obstructed wood truss and solid wood joist construction
• Unobstructed bar joist construction' must be 6" (152.4mm) in height or one third of the depth of
• Solid wood joist construction2 the concealed space, whichever is greater. Draft curtains
• Obstructed wood truss construction2 must be constructed of a material that will not allow for heat
to escape through or above them.
• Non-combustible insulation filled solid wood joist
constructions DEFLECTOR POSITION
• Non-combustible insulation filled composite wood joist • 1 'A to 4 inches below the upper deck for unobstructed
construction wood truss and bar joist constructions
NOTE: • 1 1/2 to 4 inches below the joists for noncombustible
Upper joist/truss cannot be more than 4"(101.6mm)in height. insulation filled solid and composite wood joist
2 Upper joist/truss cannot be more than 12"(304.8mm)in height.
3 The joist space in non-combustible insulation tilled joist construction must be construction.
completely filled with noncombustible insulation and secured in place by metal • 1 %to 2 inches below the joist or truss for solid wood
wire netting to hold the insulation in place in the event of a fire, joist or obstructed truss construction.
PARTITION REQUIREMENTS • 4 'A2 inches away from trusses
For unobstructed wood truss construction, unobstructed BLOCKING
bar joist construction, solid wood joist construction, and For solid wood joist and obstructed wood truss construction
obstructed wood truss construction the concealed space blocking must be provided in each of the channels between
being protected must be broken up into areas no greater the upper joists or trusses. The blocking must be located
than 1000 square feet either by full height walls or by draft where the draft curtains intersect the channels. The block-
curtains. ing must be installed to the full depth of the joists and be
Noncombustible filled joist construction is not required to be installed as to not allow heat to escape through or above the
broken up into partitioned areas. blocking. The blocking must be installed using either the
same material as the joists or a noncombustible material.
APRIL 2016 Page 4 of 6 GFS-600 (Formerly A-40)
CONCEALED SPACE SIZE
All spaces must have a minimum open space (from top of size. They must not have a total concealed space height of
lower joist, cord, or truss to bottom of upper joist, cord, or greater than 72"(1.8m). This allows for a maximum lower
truss)of 6"(152.4mm)(see Figures 3, 4, and 5). • joist space of 12"(304.8mm) (see Figure 4).
Unobstructed wood truss and bar joist construction must not Solid wood joist and obstructed truss construction must
have a total concealed space height of more than 60"(1.5m). not have an open space (from top of lower joist or truss to
(see Figure 3). bottom of upper joist or truss) of greater than 60"(1.5m) in
Joist construction with noncombustible insulation in the size. They must not have a total concealed space height of
upper deck must not have an open space (from top of lower greater than 84"(2.1 m). The upper joist space must not be
joist to bottom of upper joist) of greater than 60"(1.5m) in greater than 12"(304.8mm)in depth(see Figure 4).
4 1/2"(114mm)MIN.T• UPPER DECK
FACE OF WOOD TRUSS OR
TOP CHORD OF BAR JOIST 1 1/2"(38mm)MIN.
PI, Naito.
TOP CHORD
4"(100mm)MAX.
P GL5608 U
m" (MODEL IC SPRINKLER) 'R; I 60"
FRAME ARMS MALLEDUST M ��r� (1524mm)
BE INST
IN-LINE WITH PIPE RUN
(152mm)
MAX.
6"
MIN.
�u�lr
/�/-% FILINGimmemonnommomi
$
FIGURE 3: STEEL PIPE UNOBSTRUCTED WOOD
TRUSS OR NON-COMBUSTIBLE BAR JOIST
CONSTRUCTION
2OLIDOR UPPER DECK
SOLID WOOD JOISTS/OBSTRUCTEDCENTER
TRUSS
16"(406mm)ON CEN
II�6�ggql 1
12"�3A5 mm) 6 i1 1"( 1mm MAX.
2"(51 mm)MAX.
GL5608
FRAME ARMS MUST (MODEL IC SPRINKLER) 84"
BE INSTALLED " ' (2134mm)
IN-LINE WITH PIPE RUN = Y- MAX.
I I
CEILING
60"(1524mm)MAX.
I
�• J FRAMING
CEILING
FIGURE 4: STEEL PIPE OBSTRUCTED WOOD TRUSS
OR SOLID WOOD JOIST CONSTRUCTION
APRIL 2016 Page 5 of 6 GFS-600 (Formerly A-40)
•
UPPER DECK NON-COMBUSTIBLE
2x FLOOR SOLID INSULATION COMPOSITE WOOD JOIST
WOOD JOIST
10000.�000cA00000000aoo�w.aw000���.:aa0000����
YI%/Yit4YIVIViteillPdiYJiLStVI %VI '�L4'O�lilP:'�'�4�i'�4ti'di'ic'i IVI
t/tlti%IIII/tit/YiVIt/tlt/t/t1/11tIt/�it/�ltit/tltitl/*W/tit11/t/t{titlt/t/AYN/t/tll/tViYOYi 1 1i2"(38mm)MIN.
PM lltilltIt/t1�It/tlt/tlt.-t/t11/�1�1/t/tlt/t/ttootltitltltIyt/t/t/otlt/t/yt/t{ttlt/t/tllilt/tit, A"(102mm)MAX.
�tftt.Etryttt 4ttttteetttttl P1tttttm. 2/Att ,trot/y,, r
INSULATION MUST BE HELD L5608 I 1
IN PLACE WITH METAL R (MODEL IC SPRINKLER)
WIRE NETTING ow UP I 6'(152mm)MIN.
- -ed- 60"(1524mm)MAX.
FRAME ARMS MUST
BE INSTALLED ' ' 72"
IN-LINE WITH PIPE RUN (1826mm)
.
FILING FRAMING
MAX
CEILING
FIGURE 5: STEEL PIPE NON-COMBUSTIBLE
INSULATION FILLED UPPER DECK SOLID WOOD OR
COMPOSITE WOOD JOIST CONSTRUCTION
ORDERING INFORMATION GLOBE® PRODUCT
Quantity* Model Number • Style • Orifice *Thread Size WARRANTY
Temperature • Finishes • Desired Quantity Globe agrees to repair or replace any of its own manu-
factured products found to be defective in material or work-
Wrenchmanship for a period of one year from date of shipment.
For specific details of our warranty please refer to Price
List Terms and Conditions of Sale (Our Price List).
4077 Airpark Dr. Technical Support
Standish, MI 48658 1-800-248-0278 www.globesprinkler.com r,�!
Ph. 989-846-4583 techservice@globesprinkler.com
,1„
APRIL 2016 Page 6 of 6 GFS-600 (Formerly A-40)
•
@WICK ESPONSE= EXTENDED COVERAGE
kikr LIGHT HAZARD
AUTOMATIC SPRINKLERS
FIRE SPRINKLER CORPORATION MODEL GL5614
PENDENT• RECESSED PENDENT
DESCRIPTION AND OPERATION
The Globe Quick Response Model GL5614 Extended
Coverage Pendent Sprinkler for Light Hazard occupancies is a `
low profile yet durable design which utilizes a 3mm frangible glass
ampule as the thermosensitive element. This provides sprinkler
operation approximately six times faster than ordinary sprinklers.
,45
While this Quick Response Sprinkler provides an aesthetically M
pleasing appearance, it can be installed wherever standard light
hazard extended coverage pendent sprinklers are specified; but
offers the additional feature of greatly increased safety to life.
Quick Response Sprinklers should be used advisedly and under
the direction of approving authorities having jurisdiction, in accor QUICK RESPONSE
dance with their listings and in accordance with NFPA 13. EXTENDED COVERAGE
The heart of Globe's GL Series sprinkler proven actuating PENDENT
assembly is a hermetically sealed frangible glass ampule that
contains a precisely measured amount of fluid. When heat is
absorbed, the liquid within the bulb expands increasing the inter-
nal pressure. At the prescribed temperature the internal pressure
within the ampule exceeds the strength of the glass causing the
glass to shatter. This results in water discharge which is distrib-
uted in an approved pattern.
-4111111011111111011
TECHNICAL DATA
.See reverse side for Approvals and Specifications.
•Temperature Ratings -
135°F (57°C), 155°F (68°C), 175°F (79°C), 200° (93°C)
•Water Working Pressure Rating - 175 psi (12 Bars) ,.
•Factory tested hydrostatically to 500 psi (34 Bars)
.Maximum low temperature glass bulb rating is -67°F (-55°C)
•Frame - bronze •Deflector- brass •Screw- brass QUICK RESPONSE
•Bulb seat- copper •Spring - nickel alloy •Seal - teflon EXTENDED COVERAGE
•Bulb - glass with alcohol based solution, 3mm size RECESSED PENDENT
•Escutcheon Assembly-steel
•SPRINKLER TEMPERATURE RATING/CLASSIFICATION and COLOR CODING
CLASSIFICATION AVAILABLE SPRINKLER BULB COLOR N.F.P.A.MAXIMUM CEILING
TEMPERATURES TEMPERATURE
ORDINARY ORANGE/RED
INTERMEDIATE YELLOW/GREEN
JANUARY 2014 A-42 BULLETIN GL5614,REV.
EXTENDED COVERAGE LIGHT HAZARD
AUTOMATIC SPRINKLERS
MODEL GL5614
PENDENT • RECESSED PENDENT
SPECIFICATIONS
NOMINAL THREAD SIZE LENGTH FINISHES
"K"FACTOR
FACTORY BRONZE
5.6 (80 metric) 1/2"NPT (15mm) 2 1/2" (6.4cm) CHROME s
WHITE POLYESTER
BLACK POLYESTER"
NOTE: METRIC CONVERSIONS ARE APPROXIMATE.
'FINISHES AVAILABLE ON SPECIAL ORDER.
'AVAILABLE AS cULus LISTED AS CORROSION RESISTANT WHEN SPECIFIED ON ORDER.
APPROVALS
SIN
STYLE MODEL FACTOR HAZARD' 135°F(57°C) 155°F(68°C) 175°F(79°C) 200°F(93°C) cULus
PENDENT GL5614 5.6 LH X X X X X
RECESSED PENDENT
1SPRINKLERS SHALL BE LIMITED AS PER THE REQUIREMENTS OF NFPA13 AND ANY OTHER RELATED DOCUMENTS.
cULus LISTING DESIGN - USE REQUIREMENTS FOR LIGHT HAZARDS ONLY
SIN MODEL STYLE TEMP. AREA OF MIN.PRESSURE FLOW IN
COVERAGE P.S.I. G.P.M.
135°F/57°C 16'x 16' 21.5 26
155°F/68°C
GL5614 PENDENT 175°F/79°C 18'x 18' 34.7 33
RECESSED PENDENT 200°F/93°C
135°F/57°C 20'x 20' 51 40
CROSS SECTION
2 15/16"DIA.
2"MIN.DIA.
HOLE IN CEILING
129/32"
1
L _I 1"x 1/2"
j f REDUCER
Ji1�7
118"MMS..
Ir j1075.
CEILING cup -� 1/8"
RETAINER I"MIN.
I 3/4"MAx.
ORDERING INFORMATION GLOBE® PRODUCT WARRANTY
SPECIFY Globe agrees to repair or replace any of its own manufactured
•Quantity•Model Number•Style •Orifice products found to be defective in material or workmanship for a
+Thread Size •Temperature•Finishes desired period of one year from date of shipment.
*Quantity-Wrenches- P/N 325390 For specific details of our warranty please refer to Price List
•Quantity- Recessed Wrenches- P/N 325391 Terms and Conditions of Sale(Our Price List).
•Quantity- Protective Caps- P/N 327109-CAP(Friction Fit Recessed)
4077 AIRPARK DRIVE,STANDISH,MICHIGAN 48658
-Air 11-
959-846-4583 FAX 989-846-9231
1-800-248-0278 www.g)obesprinkler.com
FIRE SPRINKLER CORPORATION
JANUARY 2014 PRINTED U.S.A. BULLETIN GL5614,REV.#
• LUCK "ESPONSE
AUTOMATIC SPRINKLERS
TRM GL SERIES
.�{ �_ k if 110Si i £
UPRIGHT® PENDENT
KLE . CI(` Ps
VERTICAL SIDEWALL
HORIZONTAL SIDEWALL
CONVENTIONAL (OLD STYLE)
DESCRIPTION AND OPERATION
The Globe Quick Response GL Series Sprinklers are a low
profile yet durable design which utilizes a 3mm frangible glass
ampule as the thermosensitive element. This provides sprinkler
operation approximately six times faster than ordinary sprinklers.
While the Quick Response Sprinkler provides an aesthetically
pleasing appearance, it can be installed wherever standard spray , 4,
sprinklers are specified when allowed by the applicable standards.
It offers the additional feature of greatly increased safety to life and
is available in various styles, orifices, temperature ratings and
finishes to meet many varying design requirements. Quick QUICK RESPONSE
Response Sprinklers should be used advisedly and under the UPRIGHT a NVENTIONAL
direction of approving authorities having jurisdiction.
The heart of Globe's GL Series sprinkler proven actuating
assembly is a hermetically sealed frangible glass ampule that 4,4
contains a precisely measured amount of fluid. When heat is
absorbed, the liquid within the bulb expands increasing the internal =-'
pressure. At the prescribed temperature the internal pressure
within the ampule exceeds the strength of the glass causing the
glass to shatter. This results in water discharge which is distributed
in an approved pattern depending upon the deflector style used. QUICK RESPI SE
TECHNICAL DATA PENDENT JERTICAL
*See reverse side for Approvals and Specifications. SIDEWALL
*Temperature Ratings - 135°F (57°C), 155°F (68°C), .�
175°F (79°C), 200°F (93°C), 286°F (141°C)
*Water Working Pressure Rating - 175 psi (12 Bars)
•Factory tested hydrostatically to 500 psi (34 Bars)
*Maximum low temperature glass bulb rating is -67°F (-55°C) QUICK RESPONSE
HORIZONTAL LPC C ;,
_ - !
*Frame bronze * Deflector- brass * Screwbrass
•Lodgement Wire - stainless steel a
SIDEWALL HORIZONT
•Bulb seat - copper • Spring - nickel alloy a Seal - teflon SIDEWALL
•Bulb - glass with alcohol based solution, 3mm size
*SPRINKLER TEMPERATURE RATING/CLASSIFICATION and COLOR CODING
CLASSIFICATION AVAILABLE SPRINKLER BULB COLOR N.F.P.A. MAXIMUM
TEMPERATURES CEILING TEMPERATURE
ORDINARY 135°F 551`- C/68°C ,'' ORANGE/RED - °F 00
s _=i
IN ICKr7I UIH a IC r7 tzvu r; 74`C..1 3 C r ELwvvivREmiv
HIGH °F 141°C = BLUE 225°F' ,,I
4077 AIRPARK DRIVE,STANDISH,MICHIGAN 48658 989-846-4583 * FAX 989-846-9231
JULY 2012 A-20 BULLETIN GL5615, REV. #9
UICK ESPONSE
AUTOMATIC SPRINKLERS
GL SERIES
UPRIGHT 0 PENDENT 8 VERTICAL SIDEWALL
HORIZONTAL SIDEWALL 0 CONVENTIONAL (OLD STYLE)
SPECIFICATIONS
NOMINAL "K" FACTOR THREAD SIZE LENGTH, FINISHES
2.0 (33 ,..mot, L.) 1/2" t rT 2 1/4" (.5.7...,.)
1.2 (.i3 „...LI.,) 1/2" 14rT 2 1/1" (:..7.,,„) Factory Bronze
Chrome
5.6 (80 metric) 1/2" NPT 2 1/4" (5.7cm)
White Polyester 3
7.0 (111 t,.0l,l..) 1/2" NrT 2 1/4" (5.7..,..)
Black Polyester 2.3
8.1 (11C me,io) 3/1" NrT 2 7/10" ((I£ „.)
METRIC CONVERSIONS ARE APPROXIMATE.
'HORIZONTAL SIDEWALL IS 2 9/16".
'FINISHES AVAILABLE ON SPECIAL ORDER.
3 AVAILABLE AS cULus LISTED CORROSION RESISTANT WHEN SPECIFIED ON ORDER.
APPROVALS
STYLE SIN K HAZARD' 135°F 155°F 175°F 200°F 286°F cULus FM LPC CE NYC-DOB
MODEL FACTOR 57°C 68°C 79°C 93°C 141°C MEA 101-92-E
GL2815 2.8 LH X X X X X X — X
G14215 4 7 1 H X X X X X X — — — X
UPRIGHT IGL5615 5.6 LH/OH X X X X X X X X X X I
GL8115 7.8* LH/OH X X X X X X — — — X
GL8118 8.1 LH/OH X X X X X X X X X X
GL2801 2.8 LH X X X X X X — — — X
GL4201 4.2 LH X X X X X X — X
PENDENT GL5601 5.6 LH/OH X X X X X X X X X X
GL8101 7,8° LH/OH X X X X X X X — — X
GL8106 8.1 LH/OH X X X X X X X X X X
VERTICAL GL5632 5.6 LH X X X X X X X — — —
SIDEWALLt GL8133 8.1 LH X X X X X X — — — —
GL2826§ 2.8 LH X X X X X X — — — X
'
HORIZONTAL 14226 8, 4 2 I H , X X X X X X X
SIDEWALL L5626§ 5.6 LH/OH X X X X_ X X X — -- X
GL56276 5.6 LH/OH X X X X X — — X X -- j
GL8127§ 8.1 LH/OH X X X X X X — — — —
CONVENTIONAL GL5624. 5.6 LH/OH X X X X X — — 1 X X —
(OLD STYLE) GL8125 8.1 LH/OH X X X X X — — I X X --
1SPRINKLERS SHALL BE LIMITED AS PER THE REQUIREMENTS OF NFPA13 AND ANY OTHER RELATED DOCUMENTS.
§HORIZONTAL SIDEWALL cULus LISTED FOR DEFLECTOR 4"TO 12"BELOW THE CEILING,FM APPROVED 4"TO 6"BELOW THE CEILING.
INSTALL IN ACCORDANCE TO BS5306 AND ANY OTHER RELATED DOCUMENTS.
PENDENT VERTICAL SIDEWALL cULus LISTED FOR 6'MIN.SPACING.
"I-UPRIGHT VERTICAL SIDEWALL cULus LISTED FOR 9'MIN.SPACING.
OH: ORDINARY HAZARD
LH: LIGHT HAZARD
"1/2"NPT
ORDERING INFORMATION GLOBE®PRODUCT WARRANTY
SPECIFY
•Quantity • Model Number • Style Globe agrees to repair or replace any of its own manufactured
•Orifice • Thread Sizes • Temperature products found to be defective in material or workmanship for a
•Finishes desired period of one year from date of shipment.
•Quantity-Wrenches- P/N 325390 (1/2"); For specific details of our warranty please refer to Price List
P/N 312366 (L.O.) Terms and Conditions of Sale (Our Price List).
� n Anti �� 4077 AIRPARK DRIVE, STANDISH, MICHIGAN 48658
,3 ; so 989-846-4583 FAX 989-846-9231
)F SA t LE RPORA IC# 1-800-248-0278 www.globesprinkler.com
JUNE2012 PRINTED U.S.A. BULLETIN GL5615,REV.#9
• 161 AUTOMATIC SPRINKLERS
vor GL SERIES DRY TYPE
SPRINKCORPOLER HORIZONTAL SIDEWALL
FIREDESCRIPTION AND OPERATION
The Globe Quick Response GL Series Dry Type Horizontal Sidewall
Sprinkler is designed for use in special applications such as freezing
environments and conditions where sediment or foreign materials might
accumulate in ordinary horizontal pipe nipples.
The Globe Quick Response GL Series Dry Type Horizontal Sidewall
Sprinkler utilizes a 3mm frangible glass ampule as the thermosensitive SURFACE MOUNT
element. This provides sprinkler operation approximately six times
faster than ordinary sprinklers. At the ampule's rated temperature,
the sprinkler opens releasing the bulb seat, causing the inner tube
assembly to move, allowing the spring assembly to pivot alongside
the inner tube. At this time, water flows through the sprinkler and is
distributed by the deflector, in an approved discharge pattern. It can be
installed wherever standard spray sprinklers are specified but offers the fh
additional feature of greatly increased safety to life. Quick Response
Sprinklers should be used advisedly and under the direction of approv-
ing authorities having jurisdiction.
The heart of Globe's GL Series sprinkler proven actuating assembly SLEEVE & SKIRT
is a hermetically sealed frangible glass ampule that contains a precisely
measured amount of fluid. When heat is absorbed, the liquid within
the bulb expands increasing the internal pressure. At the prescribed
temperature the internal pressure within the ampule exceeds the
strength of the glass causing the glass to shatter. This results in water
discharge which is distributed in an approved pattern.
j
TECHNICAL DATA
• See reverie side for Approvals and Specifications. RECESSED
• Temperature Ratings -
135°F (57°C), 155°F (68°C), 175°F (79°C)
200°F (93°C), 286°F (141°C)
• Water Working Pressure Rating - 175 psi (12 Bars)
• Factory tested hydrostatically to 500 psi (34 Bars) , �� _
• Maximum low temperature glass bulb rating is -67°F (-55°C) $�
• Frame - bronze • Deflector- brass • Screw- brass
• Bulb Seat - brass • Spring - nickel alloy • Seal -teflon
• Retainer- brass • Pin - stainless steel
• Torsion Spring - stainless steel • Orifice Insert- brass EXTENDED
• Bulb- glass with alcohol based solution, 3mm size
• 3/4"NPT or 1"NPT• Outer Tube-galvanized steel pipe
• Inner Tube - stainless steel
•SPRINKLER TEMPERATURE RATING/CLASSIFICATION and COLOR CODING
CLASSIFICATION AVAILABLE SPRINKLER BULB COLOR N.F.P.A.MAXIMUM CEILING
TEMPERATURES TEMPERATURE
ORDINARY �� „. �� �r€ � �+ arse ORANGE/RED
INTERMEDIATE a 'S YELLOW/GREEN a > K
HIGH BLUE
APR 2017 GFS-520a(Formerly A-58)
LUCK ESPONSE
AUTOMATIC SPRINKLERS
GL SERIES DRY TYPE HORIZONTAL SIDEWALL
SPECIFICATIONS
SIN MODEL NOMINAL THREAD LENGTH FINISHES
"K"FACTOR SIZE
GL5641 1 5.6(80 metric) 1"NPT Factory Bronze
GL5642 5.6(80 metric) 3/4"NPT cULus Variable to 48" Chrome
FM Variable to 36" White Polyester2
GL8141 8.0(115 metric) 1"NPT Black Polyester'•'
NOTE: METRIC CONVERSIONS ARE APPROXIMATE.
'FINISHES AVAILABLE ON SPECIAL ORDER.
'cULus LISTED CORROSION RESISTANT WHEN SPECIFIED ON ORDER.
APPROVALS
DEFLECTOR MIN.
SIN 135°F 155°F 175°F 200°F 286°FDISTANCE
STYLE MODEL HAZARD' (57°C) (68°C) . (79°C) (93°C) (141°C) *FM cULus TODI TANCE BETWEEN
Inches(mm) SPRINKLERS 11
Feet(Meters)
Horizontal GL5641 LH X X X X X X X
Sidewall 4(102)
Recessed GL5642 LH X X X X X -- X to 6(1.8)
Horizontal 12(305)
Sidewall GL8141 LH/OH X X X X X -- X
SPRINKLERS SHALL BE LIMITED AS PER THE REQUIREMENTS OF NFPA13 AND ANY OTHER RELATED DOCUMENTS.
'HORIZONTAL SIDEWALL STYLE-FM APPROVED 155°F(68°C),200°F(93°C) AND 286°F(141°C)
'RECESSED HORIZONTAL SIDEWALL STYLE-FM APPROVED 155°F(68°C)AND 200°F(93°C)
LH:LIGHT HAZARD; OH:ORDINARY HAZARD
TEE FIITMG CROSS SECTIONS IMPORTANT INSTALLATION DATA
MEI B1fiJ°'S 15500. Globe GL Series Dry Pendent Sprinklers should be
�AN9 IBA wssyss TEEIPTING "
GP.M". ANSI MA
/ ,r , installed in accordance with the requirements set
la•r ALL �MS'T16A CLAM Iss
�'""G ( forth in NFPA 13. These sprinklers are to be installed
1 4•ro lr i CDUNG° Z
- — nslvG^om NE---
s , Ts
using a pipe wrench applied to the outer tube. When
31rri 2"°IA MIN.
GA I� E°" , 1 "GEINWA1 this is not possible, the proper sprinkler head wrench
s__ may be used with extreme care for lengths up to •
r WOFIEGE a' approximately 18". Excessive force may distort the
FACE OF F I:H MIN.
FACE OF
FACE
OF
,_,ACE OF frame thus destroying the unit.
FITTING MOUNTING "i FITTING A"
•A. �/ SURFACE "'i 3/4'NPi -�MWNT[NG
1•MIN.WRIT- l+ 33/4"MIN. I 23/4•MIN.1°"PT $UPrACE When installed in a wet system extending into a
3/4"MIN.1"NVI 4 JO'MAX.-,
EXTENDED RECESSED freezing area see chart on Dry Caution Sheet for
ffNG EF ➢NG minimum exposed barrel length to prevent ice
EIONG T ,8630." 3oa plugs. Please refer to our Dry Caution Sheet for further
PNA G163 LIAR 155 00. I AN5]
U 3)/3•GIA UU T r -- T CLASS i
PNSI1fiA CUSS III lu
J E
NG 7 important installation data.
r ro lr
4 - ESCIRCHECN
�4 'HG']UN WALL 13• u11R"OIA MIN •�
rl it
'' ° '" "" ORDERING INFORMATION
•
M FGN / /' SPECIFY
MOUNTING •Quantity•Model Number•Style•Orifice
FAQ FACE OF F0T°F M RFACE
TEE— l SURFACMOUE Fi NGNG - SURFACE
FIRING •>• •Temperature• Finishes desired
-31/T MIN.3•NVf-'.I
3I/2"'N•••'"•"°`'-31/'•"'" ""'M1M I'"°' •Quantity-Wrenches-P/N 333010
l l/1•MIN.I"NPT AI MAX.
SLEEVE&SKIRT SURFACE MOUNT •Quantity Recessed Wrenches-PIN 337014
GLOBE®PRODUCT WARRANTY •Quantity-Protective Caps-P/N 327109-cap(Friction Fit Recessed)
•
Globe agrees to repair or replace any of its own manufactured Escutcheons Desired
products found to be defective in material or workmanship for a "A"Dimension-Distance from face of fitting to the finished
period of one year from date of shipment. ceiling line regardless of escutcheon used.
For specific details of our warranty please refer to Price List
Terms and Conditions of Sale(Our Price List).
,_ 4077 AIRPARK DRIVE,STANDISH,MICHIGAN 48658
989-846-4583 FAX 989-846-9231
FIRE 5PRIM( EF1CO8PORATION 1-800-248-0278 www.globesprinkler.com
APR 2017 PRINTED U.S.A. GFS-520a(Formerly A-58)
tLJCD Fire & Building
Products
Technical Services:Tel:(800)381-9312/Fax:(800)791-5500
Series EC-5 — 5.6 K-factor
Extended Coverage (Light Hazard)
Pendent and Recessed Pendent Sprinklers
/± not representative of all possible cor-
General rosive atmospheres. Consequently, it
is recommended that the end user be
Description consulted with respect to the suitability
of these corrosion resistant coatings
The Series EC-5 Extended Coverage for any given corrosive environment.
Pendent Sprinklers are decorative The effects of ambient temperature,
glass bulb sprinklers designed for use concentration of chemicals, and ( °
in light hazard occupancies.They are gas/chemical velocity, should be con-
intended for use in automatic sprinkler sidered, as a minimum, along with the
systems designed in accordance with corrosive nature of the chemical to
standard installation rules (e.g., NFPA which the sprinklers will be exposed.
13) for a maximum coverage area of
400 ft2 (37,2 m2), as compared to the WARNINGS
maximum coverage area of 225 ft2 The Series EC-5 Extended Coverage
(20,6 m2)for standard coverage sprin- Sprinklers described herein must be
klers used in light hazard occupancies. installed and maintained in compli-
The recessed version of the EC-5, in- ance with this document, as well as
tended for use in areas with a finished with the applicable standards of the
ceiling, uses the two-piece Style 50 National Fire Protection Association,
Recessed Escutcheon. The Style 50 in addition to the standards of any AlitV
Recessed Escutcheon provides up to other authorities having jurisdiction.
3/8 inch (9,5 mm) of total adjustment Failure to do so may impair the per-
from the flush pendent position. The formance of these devices.
adjustment provided by the Recessed The owner is responsible for maintain-
Escutcheon reduces the accuracy to ing their fire protection system and de-
which the fixed pipe drops to the sprin- vices in proper operating condition. k ; -,
klers must be cut. The installing contractor or sprinkler
Corrosion resistant coatings, where
manufacturer should be contacted
applicable, are utilized to extend the with any questions.
life of copper alloy sprinklers beyond
that which would otherwise be ob- Model/Sprinkler
tained when exposed to corrosive at-
mospheres. Although corrosion resis- Identification Technical
tant coated sprinklers have passed the
standard corrosion tests of the appli- Number Data
cable approval agencies, the testing is
TY3232- Pendent,5.6K Approvals
UL and C-UL Listed. FM and NYC Ap-
TY3232 is a redesignation for C3232. proved. (Refer to Table A for complete
IMPORTANT approval information including corro-
Always refer to Technical Data sion resistant status. The approvals
Sheet TFP700 for the "INSTALLER apply to the service conditions indi-
WARNING" that provides cautions cated in the Design Criteria section.)
with respect to handling and instal-
lation of sprinkler systems and corn- Maximum Working Pressure
ponents. Improper handling and in-
stallation can permanently damage Pipe Thread Connection
a sprinkler system or its compo- 1/2 inch NPT
nents and cause the sprinkler to fail Discharge Coefficients
to operate in a fire situation or cause 1/2
it to operate prematurely. K=5.6 GPM/ps2
(80,6 LPM/bar )
Pagel of 6 JANUARY, 2005 TFP228
. .... .__ -_
Page 2 of 6 TFP228
Components: 1/2"** ESCUTCHEON PLATE
1 • Frame 1 NPT SEATING SURFACE
3- Button - I
3- Seaaling Assembly — 1f/
4- Bulbp 2 % NV = 2-1/16"
5- Compression ifili
Screw 3 ���; >_ (_) I (52,4 mm)
6 Deflector* J \ 7/1m 111
NO mm) 1-5/16"
* Temperature rating is 4 I ' NOMINALMAKE-IN (33,3 mm)
indicated on Deflector. t�5 ;=s`* Pipe thread �
connections per ISO
7/1 can be provided 6*
on special request.
FIGURE 1
SERIES EC-5(TY3232)EXTENDED COVERAGE PENDENT SPRINKLERS
SPRINKLER FINISH(See Note 4)
HAZARD TYPE TEMP. BULB NATURAL CHROME WHITE*
LIQUID BRASS PLATED POLYESTER
LIGHT PENDENT 135F/57°C Orange 1,2,5
Refer to Table B for UL and C-UL 155°F/68°C Red 1,2,3,5
Sensitivity Rating
and REC.PENDENT 135°F/57°C Orange 1,2,5
Refer to Table C for FM w/Style 50 Esc.
Sensitivity Rating
155°F/68°C Red 1,2,3,5
NOTES:
1 Listed by Underwriters Laboratories, Inc.(UL).
2 Listed by Underwriters Laboratories, Inc.for use in Canada(C-UL).
3.Approved by Factory Mutual Research Corporatipn(FM).
4.Where Polyester Coated Sprinklers are noted to be UL and C-UL Listed,the sprinklers are UL and C-UL Listed as Corrosion Resistant
Sprinklers.
5.Approved by the City of New York under MEA 113-04-E.
*Frame and Deflector only.Listings and approvals apply to color(Special Order).
TABLE A
LABORATORY LISTINGS AND APPROVALS
(Refer to the Design Criteria Section)
Temperature Ratings installation, as applicable (Ref. Table
135°F/57°C and 155°F/68°C Operation A, B, and C).,
Finish The glass bulb contains a fluid that UL and C-UL Listing
Sprinkler: Refer to Table A expands when exposed to heat.When Requirements
Recessed Escutcheon:White Coated, the rated temperature is reached, the .
Chrome Plated, and Brass Plated fluid expands sufficiently to shatter the 1. The Series EC-5 Sprinklers may be
glass bulb, allowing the sprinkler to used for the coverage areas shown
Physical Characteristics activate and flow water. in Table ID,based on maintaining the
Frame Bronze minimum specified flow rate as a
Button Bronze function of coverage area and haz-
Sealing Assembly Design and group for all of the sprinklers in
Beryllium Nickel IN/Teflon-1- - the design area.
Bulb Glass (3 mm dia.) Criteria
Compression Screw 2. With respect to heat sensitivity, the
Bronze The Series EC-5 Extended Coverage Series EC-5 Sprinklers are permit-
Deflector Brass Pendent Sprinklers must only be in- ted to be used with unobstructed
stalled in accordance with the applica- construction consisting of flat,
(Registered trademark of DuPont ble UL and C-UL Listing or FM Ap- smooth ceilings with a pitch of one in
proval requirements as indicated six as defined and permitted by
below.Only the Style 50 Recessed Es- NFPA 13.
cutcheon is to be used for recessed
3. The minimum allowable spacing be-
TFP228 Page 3 of 6
Installation
135°F 155°F The Series EC-5 Sprinklers must be
installed in accordance with the follow-
AREA STYLE ing instructions:
NOTES
16 x 16 Pendent OR OR Do not install any bulb type sprinkler if
16 x 16 Style 50 Recessed QR CR the bulb is cracked or there is a loss of
liquid from the bulb. With the sprinkler
18 x 18 Pendent QR QR held horizontally, a small air bubble
18 x 18 Style 50 Recessed OR QR should be present. The diameter of the
air bubble is approximately 1/16 inch
20 x 20 Pendent OR N/A (1,6 mm).
20 x 20 Style 50 Recessed QR N/A A leak tight 1/2 inch NPT sprinkler joint
should be obtained with a torque of 7
QR:Quick Response to 14 ft.lbs. (9,5 to 19,0 Nm). A maxi-
N/A:Not Applicable mum of 21 ft.lbs. (28,5 Nm) of torque
is to be used to install sprinklers.
TABLE B Higher levels of torque may distort the
SENSITIVITY RATING FOR UL AND C-UL LISTING sprinkler inlet with consequent leak-
OF SERIES EC-5 SPRINKLERS age or impairment of the sprinkler.
Do not attempt to compensate for in-
sufficient adjustment in an Escutcheon
Plate by under-or over-tightening the
Sprinkler. Readjust the position of the
135°F 155°F sprinkler fitting to suit.
Step 1.The sprinkler must be installed
AREA STYLE with the deflector parallel to the mount-
ing surface. Pendent sprinklers must
16 x 16 Pendent OR OR be installed in the pendent position.
16 x 16 Style 50 Recessed QR QR Step 2. After installing the Style 50
mounting plate (or other escutcheon,
18 x 18 Pendent QR QR as applicable) over the sprinkler pipe
18 x 18 Style 50 Recessed OR OR threads and with pipe thread sealant
applied to the pipe threads, hand
20 x 20 Pendent QR QR tighten the sprinkler into the sprinkler
20 x 20 Style 50 Recessed QR QR fitting.
Step 3.Wrench tighten pendent sprin-
QR:Quick Response klers using only the W-Type 6 (End A)
Sprinkler Wrench.Wrench tighten the
recessed pendent sprinklers using
only the W-Type 7 Sprinkler Wrench.
The wrench recess of the applicable
sprinkler wrench (Ref.Figure 3 and 4)
is to be applied to the sprinkler wrench
flats (Ref.Figure 1).
TABLE C
SENSITIVITY RATING FOR FM APPROVAL
OF SERIES EC-5 SPRINKLERS
tween the Series EC-5 Sprinklers, FM Approval
to prevent cold soldering, is 8 feet Requirements
(2,4 m). The Series EC-5 Extended Coverage
Sprinklers are to be installed in ac-
4. The Series EC-5 Sprinklers are to be cordance with the applicable Factory
installed in accordance with all other Mutual Loss Prevention Data Sheet.
requirements of NFPA 13 for ex- Information provided in the FM Loss
tended coverage pendent sprin- Prevention Data Sheets relate to, but
klers. are not limited to, hydraulic design,
ceiling slope and obstructions, mini-
mum and maximum allowable spacing,
and deflector-to-ceiling distance.
Page 4 of 6 TFP228
DESCRIPTION AREA GPM PSI
I TY3232(K=5.6)PENDENT 16 x 16 26 21.6
18 x 18 33 34.7 / WRENCH RECESS
20 x 20 40 51.0 (END"A"USED
1 ft.=0.3048 m FOR TY3232)
1 ft2=0.093 m2
1 gpm=3.785 Ipm
1 psi=0.06895 bar
1 gpm/ft2=40.74 mm/min
FIGURE 4
TABLED W-TYPE 6 SPRINKLER
FLOW CRITERIA FOR UL AND C-UL LISTING WRENCH
OF SERIES EC-5 SPRINKLERS
WRENCH
RECESS
2-7/8"DIA.
9/16±1/8" (73,0 mm) 7/16"(11,1 mm)
(14,2a3,2 mm) 2-1/4"DIA. 3/16"(4,8 mm) '�n FACE OF (57,2 mm) 11 /
SPRINKLER 3/32"
FITTING (2,4 mm) (� /
\Jr
PUSH WRENCH
IN TO ENSURE
ENGAGEMENT
MOUNTING MOUNTING WITH SPRINKLER
SURFACE PLATE WRENCHING AREA
CLOSURE FIGURE 5
1-1/8"(28,6 mm) W-TYPE 7 RECESSED
7/8"(22,2 mm) SPRINKLER WRENCH
FIGURE 2
SERIES EC-5 RECESSED PENDENT SPRINKLER ASSEMBLY annual inspections per NFPA 25
WITH TWO-PIECE 3/8 INCH TOTAL ADJUSTMENT should suffice; however, instead of in-
STYLE 50 RECESSED ESCUTCHEON specting from the floor level, a random
sampling of close-up visual inspec-
tions should be made, so as to better
altered after leaving the factory. Modi- determine the exact sprinkler condi-
Care and fled sprinklers must be replaced. tion and the long term integrity of the
Sprinklers that have been exposed to corrosion resistant coating as it may
Maintenance corrosive products of combustion, but be affected by the corrosive conditions
have not operated,should be replaced present.
The Series EC-5 Sprinklers must be if they cannot be completely cleaned
maintained and serviced in accord- by wiping the sprinkler with a cloth or The owner is responsible for the fin-
ance with the following instructions: by brushing it with a soft bristle brush. spection, testing, and maintenance of
Care must be exercised to avoid dam- their fire protection system and de-
NOTE vices in compliance with this docu-
Before closing a fire protection system age to the sprinklers - before, during, ment, as well as with the applicable
and after installation. Sprinklers dam-
main control valve for maintenance standards of the National Fire Protec-
work on the fire protection system that aged by dropping, striking, wrench tion Association (e.g., NFPA 25), in
it controls,permission to shut down the twist/slippage, or the like, must be re- addition to the standards of any other
affected fire protection systems must placed.Also,replace any sprinkler that authorities having jurisdiction.The in-
be obtained from the proper authori- has a cracked bulb or that has lost stalling contractor or sprinkler manu-
ties and all personnel who may be liquid from its bulb. (Ref. Installation facturer should be contacted relative
affected by this action must be notified. Section). to any questions.
Sprinklers that are found to be leaking Frequent visual inspections are rec- It is recommended that automatic
or exhibiting visible signs of corrosion ommended to be initially performed for sprinkler systems be inspected,
must be replaced. corrosion resistant coated sprinklers, tested, and maintained by a qualified
after the installation has been corn- Inspection Service in accordance with
Automatic sprinklers must never be pleted,to verify the integrity of the cor- local requirements and/or national
painted, plated, coated, or otherwise rosion resistant coating. Thereafter,
codes.
TFP228 Page 5 of 6
Limited Ordering
Warranty Procedure
Products manufactured by Tyco Fire When placing an order,indicate the full
Products are warranted solely to the product name. Please specify the
original Buyer for ten (10) years Sprinkler Identification Number(SIN),
against defects in material and work- quantity,and temperature rating.Refer
manship when paid for and properly to the Price List for complete listing of
installed and maintained under normal Part Numbers.
use and service.This warranty will ex- Contact your local distributor for avail-
pire ten (10) years from date of ship- ability.
ment by Tyco Fire Products. No war-
ranty is given for products or Sprinkler Assemblies with NPT
components manufactured by compa- Thread Connections:
vies not affiliated by ownership with Specify:TY3232,(specify temperature
Tyco Fire Products or for products and rating), Extended Coverage Pendent
components which have been subject Sprinkler with (specify finish), P/N
to misuse,improper installation,corro- (specify).
sion,or which have not been installed,
maintained,modified or repaired in ac- 135'F/57c
cordance with applicable Standards of Natural Brass PSN 51-051-1-135
chrome Plated PSN 51-051-9-135
the National Fire Protection Associa-
White Coaled PSN 51-051-4-135
tion,and/or the standards of any other White(RAL9010)* PSN 51-051-3-135
Authorities Having Jurisdiction. Mate- 155°F/6a°C
rials found by Tyco Fire Products to be Natural Brass PSN 51-051-1-155
defective shall be either repaired or Chrome Plated PSN 51-051-9-155
replaced, at Tyco Fire Products' sole White Coated PSN 51-051-4-155
option.Tyco Fire Products neither as- White(RAL9010)* PSN 51-051-3-155
sumes, nor authorizes any person to *Eastern Hemisphere sales only.
assume for it, any other obligation in
connection with the sale of products or Recessed Escutcheon:
parts of products. Tyco Fire Products Specify: Style 50 Recessed Escutch-
shall not be responsible for sprinkler eon with(specify finish), P/N(specify).
system design errors or inaccurate or
incomplete information supplied by Style 50 Recessed Escutcheon Chrome Plated PSN 56-711-9-010
Buyer or Buyer's representatives. White Color Coated PSN 56-711-4-010
IN NO EVENT SHALL TYCO FIRE White(RAL9010)* PSN 56-7113.010
PRODUCTS BE LIABLE, IN CON- Brass Plated PSN 56-711-2-010
TRACT,TORT,STRICT LIABILITY OR *Eastern Hemisphere sales only.
UNDER ANY OTHER LEGAL THE-
ORY, FOR INCIDENTAL, INDIRECT, Sprinkler Wrench:
SPECIAL OR CONSEQUENTIAL Specify: W-Type 6 Sprinkler Wrench,
DAMAGES, INCLUDING BUT NOT P/N 56-000-6-387
LIMITED TO LABOR CHARGES, RE-
GARDLESS OF WHETHER TYCO Specify:W-Type 7 Recessed Sprinkler
FIRE PRODUCTS WAS INFORMED Wrench, P/N 56-850-4-001
ABOUT THE POSSIBILITY OF SUCH
DAMAGES, AND IN NO EVENT
SHALL TYCO FIRE PRODUCTS' LI-
ABILITY EXCEED AN AMOUNT
EQUAL TO THE SALES PRICE.
THE FOREGOING WARRANTY IS
MADE IN LIEU OF ANY AND ALL
OTHER WARRANTIES EXPRESS OR
IMPLIED.INCLUDING WARRANTIES
OF MERCHANTABILITY AND FIT-
NESS FOR A PARTICULAR PUR-
POSE.
Page 6 of 6 TFP226