Report (2) 4. Supply air economizers shall be provided on each cooling system and are capable of providing 100-percent outdoor air,even if
additional mechanical cooling is required to meet the cooling load of the building.Systems provide a means to relieve excess outdoor
air during economizer operation to prevent overpressurizing the building.
Exception(s):
rj Cooling equipment less than 54,,000 Btu/hr total cooling capacity.
Plans reference page/section:
Generic Requirements:Must be met by all systems to which the requirement is applicable:
Ar 1. Calculation of heating and cooling loads.Design loads are determined in accordance with the procedures described in the
ASHRAEJACCA Standard 183.Alternatively,design loads have been determined by an approved equivalent computation procedure.
❑ 2. Packaged Electric Equipment.Specified packaged electrical equipment has a heat pump as the primary heating source.
Exception(s):
❑ Unstaffed equipment shelters or cabinets used solely for personal wireless service facilities.
❑ Requirement is not applicable. l�
Plans reference page/section: `U
6 3. Equipment and system sizing.Heating and cooling equipment and systems capacity do not exceed the loads calculated in accordance
with Section 503.2.1.
Exception(s):
O Required standby equipment and systems provided with controls and devices that allow such systems or equipment to operate
automatically only when the primary equipment is not operating.
O Multiple units of the same equipment type with combined capacities exceeding the design load and provided with controls that
have the capability to sequence the operation of each unit based on load.
Plans reference page/section:
`p 4. HVAC Equipment Performance Requirements.Reported efficiencies have been tested and rated in accordance with the applicable test
procedure.The efficiency has been verified through certification under an approved certification program or,if no certification program
exists,the equipment efficiency ratings are supported by data furnished by the manufacturer.
4 5. Thermostatic Controls.The supply of heating and cooling energy to each zone is controlled by individual thermostatic controls that
respond to temperature within the zone.
Plans reference page/section:
❑ 6. Heat pump supplementary heat.Heat pumps having supplementary electric resistance heat have controls that,except during defrost,
prevent supplementary heat operation when the heat pump can meet the heating load.
Plans reference page/section: N I A"
rlt 7. Set point overlap restriction.Where used to control both heating and cooling,zone thermostatic controls provide a temperature range
or deadband of at least 5°F(2.8°C)within which the supply of heating and cooling energy to the zone is capable of being shut off or
reduced to a minimum.
Exception(s):
O Thermostats requiring manual change over between heating and cooling modes.
Plans reference page/section. t�'
Ni 8. Optimum Start Controls_Each HVAC system has controls that vary the start-up time of the system to just meet the temperature set
point at time of occupancy.
Plans reference page/section: I
(A 9. Off-hour controls.Each zone Is provided with thermostatic setback controls that are controlled by either an automatic time clock or
programmable control system.
Exception(s):
❑ zones that will be operates continuously.
O Zones with a full HVAC load demand not exceeding 6,800 Btu/h(2 kW)and having a readily accessible manual shutoff switch.
Plans reference page/section: 1v`,
10.Shutoff damper controls.Both outdoor air supply and exhaust are equipped with not less than Class I motorized dampers.
Exception(s):
J Gravity dampers shall be permitted for outside air intake or exhaust airflows of 300 cfm or less.
Plans reference page/section:
Project Title:Tigard Animal Hospital Report date:04/03/20
Data filename: Untitled.cck Page 2 of 5
11.Freeze Protection and Snow melt system controls.Freeze protection systems,such as heat tracing of outdoor piping and heat
exchangers,including self-regulating heat tracing,include automatic controls capable of shutting off the systems when outdoor air
temperatures meet code criteria. h` y5
Plans reference page/section: \1 fi
12.Separate air distribution systems.Zones with special process temperature requirements and/or humidity requirements are served by
separate air distribution systems from those serving zones requiring only comfort conditions;or shall include supplementary control
provisions so that the primary systems may be specifically controlled for comfort purposes only.
Exception(s):
0 [503.2.4.8+]Zones requiring only comfort heating or comfort cooling that are served by a system primarily used for process
temperature and humidity control.
Plans reference page/section: Pr
O 13.Humidity control.If a system is equipped with a means to add or remove moisture to maintain specific humidity levels in a zone or
zones,a humidity control device is provided.
Plans reference page/section: ry I k
O 14.Humidity control.Where a humidity control device exists it is set to prevent the use of fossil fuel or electricity to produce relative
humidity In excess of 30 percent.Where a humidity control device is used for dehumidification,it is set to prevent the use of fossil fuel
or electricity to reduce relative humidity below 60 percent.
Exception(s):
O Hospitals,process needs,archives,museums,critical equipment,and other non-comfort situations with specific humidity
requirements outside this range.
Plans reference page/section: !
• 15.Humidity control.Where a humidity control device exists it is set to maintain a deadband of at least 10%relative humidity where no
active humidification or dehumidification takes place.
Exception(s):
Q Heating for dehumidification is provided with heat recovery or heat pumping and the mechanical cooling system efficiency is 10
percent higher than required in section 503.2.3,HVAC equipment performance requirements.
N
Plans reference page/section. I P-16.Ventilation.Ventilation,either natural or mechanical,is provided in accordance with Chapter 4 of the International Mechanical Code.
Where mechanical ventilation is provided,the system has the capability to reduce the outdoor air supply to the minimum required by
Chapter 4 of the International Mechanical Code.
Plans reference page/section:
O 17.Demand controlled ventilation(DCV).DCV is required for spaces larger than 500 ft2 for simple systems and spaces larger than 150 ft2
for multiple zone systems.
Exception(s): -
O Systems with energy recovery complying with Section 503.2.6
O Spaces less than 750 ft2(69.7 m2)where an occupancy sensor turns the fan off,closes the ventilation damper,or closes the
zone damper when the space is unoccupied.
Plans reference page/section: t+ I
18.Kitchen hoods.Kitchen makeup is provided as required by the Oregon Mechanical Specialty Code.
Exception(s):
O Where hoods are used to exhaust ventilation air that would otherwise be exhausted by other fan systems.
O Kitchen exhaust systems that include exhaustyai
air energy recovery complying with section 503.2.6.
Plans reference page/section: ,V I t '
0 19.Enclosed parking garage ventilation controls.In Group S-2,enclosed parking garages used for storing or handling automobiles employs
automatic carbon monoxide sensing devices.
` y�
Plans reference page/section: ----
1Vi 20.Duct and plenum insulation and sealing.All supply and return air ducts and plenums are insulated with the specified insulation.When
located within a budding envelope assembly,the duct or plenum is separated from the building exterior or unconditioned or exempt
spaces by a minimum of R-8 insulation.All ducts,air handlers and filter boxes are sealed.Joints and seams comply with Section 603.9
of the International Mechanical Code.
Exception(s):
When located within equipment.
di When the design temperature difference between the interior and exterior of the duct or plenum does not exceed 15°F(8°C).
Project Title:Tigard Animal Hospital Report date:04/03/20
Data filename: Unfitled.cck Page 3 of 5
21.Low-pressure duct systems.All longitudinal and transverse joints,seams and connections of low-pressure supply and return ducts are
securely fastened and sealed with welds,gaskets,mastics(adhesives),mastic-plus-embedded-fabric systems or tapes installed in
accordance with the manufacturer's installation instructions.
Exception(s):
❑ Continuously welded and locking-type longitudinal joints and seams on ducts operating at static pressures less than 2 inches w.g.
pressure classification.
Plans reference page/section:
0 22.Medium-pressure duct systems.All ducts and plenums designed to operate medium-pressure are insulated and sealed in accordance
with Section 503.2.7.Pressure classifications specific to the duct system are clearly indicated on the construction documents.
tV�
Plans reference page/section: ' 114-
❑ 23.High-pressure duct systems.Ducts designed to operate at high-pressure are insulated and sealed in accordance with Section 503.2.7.
In addition,ducts and plenums are leak-tested in accordance with the SMACNA HVAC Air Duct Leakage Test Manual.
Plans reference page/section: t I
24.Air system balancing.Each supply air outlet and zone terminal device is equipped with means for air balancing in accordance with the
requirements of IMC 663.17.Discharge dampers intended to modulate airflow w are prohibited on constant volume fans and variable
volume fans with motors 10 horsepower.
Plans reference page/section:
25.Manuals.The construction documents require that an operating and maintenance manual be provided to the buikfing owner by the
mechanical contractor.See long description for specifications.
Plans reference page/section: lkA4
❑ 26.Air System Design and Control.Each HVAC system having a total fan system motor nameplate hp exceeding 5 hp meets the provisions
of Sections 503.2.10.1 through 503.2.10.2.1
Plans reference page/section: N !L'
r)y 27.Allowable fan floor horsepower.Each HVAC system at tan system design conditions does not exceed the allowable fan system motor
nameplate hp(Option 1)or fan system bhp(Option 2)as shown and calulated in requirement details.
Exception(s):
❑ Hospital and laboratory systems that utilize flow control devices on exhaust and/or return to maintain space pressure relationships
necessary for occupant health and safety or environmental control shall be permitted to use variable volume fan power limitation.
❑ Individual exhaust fans with motor nameplate horsepower of 1 hp or less.
Plans reference page/section: µ)
'M 28.Motor nameplate horsepower.For each fan,the selected fan motor is no larger than the first available motor size greater than the brake
T.' horsepower(bhp).
Exception(s):
❑ For fans less than 6 bhp,where the first available motor larger than the brake horsepower has a nameplate rating within 50
percent of the bhp,selection of the next larger nameplate motor size is allowed.
❑ For fans 6 bhp and larger,where the first available motor larger than the bhp has a nameplate rating within 30 percent of the bhp,
selection of the next larger nameplate motor size is allowed.
Plans reference page/section: k�A
❑ 29.Large Volume Fan Systems.Fan systems over 8,000(7 m3/s)cfm without direct expansion cooling coils that serve single zones reduce
airflow based on space thermostat heating and cooling demand.A two-speed motor or variable frequency drive reduces airflow to a
maximum 60 percent of peak airflow or minimum ventilation air requirement as required by Chapter 4 of the International Mechanical
Code,whichever is greater.
Exception(s):
❑ Systems where the function of the supply air is for purposes other than temperature control,such as maintaining specific humidity
levels or supplying an exhaust system. t�
Plans reference page/section: r+
❑ 30.All air-conditioning equipment and air-handing units with direct expansion cooling and a cooling capacity at ARt conditions greater than
or equal to 110,000 Btu/h that serve single zones have their supply fan operation controlled according to code specific requirements.
Exception(s):
() Systems where the function of the supply air is for purposes other than temperature control,such as maintaining specific humidity
levels or supplying an exhaust system.
Plans reference page/section: iv I r T
Project Title:Tigard Animal Hospital Report date:04/03/20
Data filename: Untitled.cck Page 4 of 5
r
O 31.Serles fan-powered terminal unit fan motors.Fan motors for series fan-powered terminal units are electronically-commutated motors
and have a minimum motor efficiency of 70 percent when rated in accordance with NEMA Standard MG 1-2006 at full load rating
conditions.
Plans reference page/section: 1\1f 4
•
u 32.Hot Gas Bypass Limitation.For cooling systems<=240 kBtulh,maximum hot gas bypass capacity is no more than 50%total cooling
capacity. p`
Plans reference page/section: B' 1 k
Section 5: Compliance Statement
Compliance Statement: The proposed mechanical design represented in this document is consistent with the building plans,specifications
and other calculations submitted with this permit application.The proposed mechanical systems have been designed to meet the 2014
Oregon Energy Efficiency Specialty Code requirements in COMcheck Version 4.1.1.0 and to comply with the mandatory requirements in the
Requirements Checklist. p,�
uiYet- LAiiVt — Mum)9-e/v `� viName-Title Sig a D
Section 6: Post Construction Compliance Statement
HVAC record drawings of the actual installation,system capacities,calibration information,and performance data for each equipment
provided to the owner.
HVAC O&M documents for all mechanical equipment and system provided to the owner by the mechanical contractor.
Written HVAC balancing and operations report provided to the owner.
The above post construction requirements have been co ed L
C ►a- Lab bur✓ ///// ( >l31 Za�v
Principal Mechanical Designer-Name Signature Date
Project Title:Tigard Animal Hospital Report date:04/03/20
Data filename: Untitied.cck Page 5 of 5